ke2 flash drive · 2019. 11. 19. · ke2 flash drive (pn 21146) thermsolutions for data logging the...

4
Your Key to Energy Efficient Refrigeration Solutions Q.5.48 October 2016 thermsolutions KE2 Flash Drive for Data Logging the KE2 LDA

Upload: others

Post on 10-Sep-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: KE2 Flash Drive · 2019. 11. 19. · KE2 Flash Drive (pn 21146) thermsolutions for Data Logging the KE2 LDA Q.5.48 October 2016 Page 2 The KE2 Flash Drive now provides Data Logging

Your Key to Energy Efficient Refrigeration Solutions

Q.5.48 October 2016

thermsolutionsKE2 Flash Drivefor Data Logging the KE2 LDA

Page 2: KE2 Flash Drive · 2019. 11. 19. · KE2 Flash Drive (pn 21146) thermsolutions for Data Logging the KE2 LDA Q.5.48 October 2016 Page 2 The KE2 Flash Drive now provides Data Logging

Plug the KE2 Flash Drive into the KE2 LDA

LDA

USB Reset

KE2 LDA -Left Side

© Copyright 2016 KE2 Therm Solutions, Inc. . Washington, Missouri 63090

KE2 Flash Drive (pn 21146)for Data Logging the KE2 LDAthermsolutions

Q.5.48 October 2016Page 2

The KE2 Flash Drive now provides Data Logging for your KE2 LDA communication device.

These fields are included in the log for each device,

where applicable:

The KE2 Flash Drive provides the ability to: Keep 366 days of data, for up to 10 devices Set the interval from 5 minutes to 24 hours between data points, allowing the user to customize their data for their spe-cific requirements.

Run reports for any individual controller, or for all controllers Data logging for KE2 Therm’s Ethernet and MODBUS controllers

Important!The user interface for logging will only show up if a KE2 Flash Drive is plugged into the KE2 LDA communication device.

The KE2 LDA must be upgraded to version 1.1.0, or newer, for data logging.

From the moment the KE2 Flash Drive is connected to the KE2 LDA, the first 10 auto-populated devices, will begin logging.

KE2 LDA - Front

Timestamp

Location

Room Temp Setpoint

Room Temp

Alarms

IP Addresss

MAC Address

System Messages

System Mode

KE2 Flash Drive Kit (pn 21146)

Changing which controllers are logged is made from the KE2 LDA Management Console.

The devices must be visible on the KE2 LDA dashboard in or-der to be recorded. The logging interval is also set in the KE2 LDA Management Console and can range from 5 minutes to 24 hours.

It should be noted that the KE2 Flash Drive’s logging capability is not designed for diagnostics, but rather for audit purposes. As such, a limited range of pre-set values are logged including Room Temp Setpoint, Room Temp, and the Time Stamp. The log-ging interval must be a minimum of five minutes.

All logs are periodically output to CSV files on the USB drive, and the CSV files are stored indefinitely.

KE2 Flash Drive

* The USB Hub connects into the USB port on the KE2 LDA, this allows the KE2 Flash Drive and serial devices to be con-nected to the KE2 LDA.

USB Hub*

Page 3: KE2 Flash Drive · 2019. 11. 19. · KE2 Flash Drive (pn 21146) thermsolutions for Data Logging the KE2 LDA Q.5.48 October 2016 Page 2 The KE2 Flash Drive now provides Data Logging

© Copyright 2016 KE2 Therm Solutions, Inc. . Washington, Missouri 63090

thermsolutions

Q.5.48 October 2016Page 3

KE2 Flash Drive (pn 21146)for Data Logging the KE2 LDA

To enable logging from the LDA Management Console, click the Manage button.

Then use the check box on the right side. By default, a new record will be logged for each selected controller every 10 minutes, but the interval can be edited by the user.

The button to “Download All Logs” will download all avail-able logs in the database.

Upon connecting to the KE2 LDA Dashboard, the buttons for downloading logs are on the right side :

User Interface

1

2

1

2

3

4

2a

3

4

The “Logs” button will bring up a dialog to download logs for a specific controller, in a given date range.

The previous 30 days is the de-fault date interval, but the user can change this as desired.

2a

Page 4: KE2 Flash Drive · 2019. 11. 19. · KE2 Flash Drive (pn 21146) thermsolutions for Data Logging the KE2 LDA Q.5.48 October 2016 Page 2 The KE2 Flash Drive now provides Data Logging

© Copyright 2016 KE2 Therm Solutions, Inc. . Washington, Missouri 63090

KE2 Flash Drive (pn 21146)for Data Logging the KE2 LDAthermsolutions

Q.5.48 October 2016Page 4

KE2 Therm Solutions, Inc. 12 Chamber Drive . Washington, MO 63090

1-888-337-3358 . www.ke2therm.com

Sample Data from a Download of an Individual Controller NOTE: The time stamp is pulled from the PC running the report. Coordinated Universal Time (UTC) is also shown for reference.

Sample Data from Download All Logs

Connect customer Network to WAN

WAN

PowerLAN

.

KE2 EvaporatorEfficiency

TM

thermsolutions

ENTER

BACK

.

MODIFY STATUSABC Contracting(888)555-3358

All ClearCompressorOn

System ModeCool

Evaporator FanOff

Room Temp-8.5 F

Coil Temp15.4 F

Sat Temp46.0 F

Superheat0.0 F

Valve PositionManual

Suct Pressure96.2 F

Suct Temp87.7 F

Dig Input 3Dis

DefrostOff

Aux TempDis

Dig Input 1Closed

Dig Input 2Dis

KE2 EvaporatorEfficiency

TM

thermsolutions

ENTER

BACK

.

Ethernet Controllers:KE2 Evaporator E�ciency, KE2 Evap for Rack E�ciency,KE2 Controlled Environment

Serial-Modbus Controllers:KE2 Temp, KE2 Low TempKE2 Adaptive Control

.

Hold for manual defrost

thermsolutions

KE2 Temp

Hold for manual defrost

thermsolutions

KE2 Temp

.

USB Hub

KE2 Flash DriveFor datal logging up to 10 Ethernet or Serial-Modbus controllers