KAWASAKIBoiler and Absorption Chillerfor Co-generation system
14 November, 2018
Kawasaki Thermal Engineering Co., Ltd.
Overseas Project Department
2© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Organization of Kawasaki
Ship & Offshore Structure
Rolling Stock
Aerospace System
Energy System & Plant Engineering
Motorcycle & Engine
Precision Machinery & Robot
Kawasaki Thermal Engineering
KAWASAKIBoiler
4© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Gas Turbine Cogeneration System
Chilled
Water
Supply
Electricity
Steam
NG
Heat Recovery Rate:23%
Efficiency:31%
Exhaust Gas
HRSG
Gas Turbine Generator
Boiler SteamAbsorption Chiller
Steam
5© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Boiler planning (For example)
GT Model GPB17D GPB80D
Boiler Model RGB-60GE RGB-200GE
GT outlet exhaust gas amount
m3N/h 22,637 76,132
GT outlet exhaust gas temp.
Deg C 525 525
Drum pressure MPaG 0.83 1.68
Feed water temp. Deg C 60 60
Boiler inlet exhaustgas amount
m3N/h 22,637 76,132
Boiler inlet exhaust gas temp.
Deg C 525 525
Economizer outlet exhaust gas temp.
Deg C 114 123
Steam output kg/h 5,150 16,900
Heat Recovery Steam Generator (Water Tube Type)
6© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Gas Engine Cogeneration System
Chilled
Water
Supply
Electricity
Hot Water
Supply
Steam
Hot Water Absorption Chiller
NG
CommercialPower
電力
Chilled WaterHot Water
Steam
Sub Station
HeatExchanger
Centrifugal Chiller
Heat Exchanger
Steam Absorption Chiller
Header
Steam
Exhaust Gas
HRSG
Gas Boiler
Exhaust Gas
7© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
• GE modelKAWASAKI KG-18-V
• Boiler modelRF-40GKE
• Boiler inlet exhaust gas35,800m3
N/h at 320℃
• Pressure0.80MPa
• Steam output3,190kg/h at 60℃
Boiler planning (For example)
Heat Recovery Steam Generator (Once Through)
8© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Gas Turbine Cogeneration System
Chilled
Water
Supply
Electricity
Steam
NG
Heat Recovery Rate:23%
Efficiency:31%
Exhaust Gas
HRSG
Gas Turbine Generator
Boiler SteamAbsorption Chiller
Steam
9© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Once Through Boiler “IF Series”
A Comparison of KTE’s Line-up Boiler
Water Tube Fire TubeOnce-through
(KF)Once-through
(IF)
Actual Evaporation
t/h 5 5 1.68×3 5
Weight ton 12 11.5 2.4×3=7.2 7.8
Retained Water Volume
L/t 3,000 6,000275×3=825 990
Cold startAdvantage
Min 40 40~60 10 15
Control
Combustion ContinuousIntermittent(3 positions)
Continuous
Water Feeding ContinuousIntermittent(2 positions)
Continuous
Heating Surface Area 1,174 693 106×3=318 317
Max. Boiler Efficiency (%) 94 92 98 98
Dimension (m2) 25 12.6 2.5×3=7.5 7.3
Note) The boiler efficiency is indicated on the steam pressure of 0.49Mpa, the feed water temperatureof 15 deg C and the room temperature of 35 deg C. The boiler efficiency shall have +/-3% allowance in concideration of the mesurement tolerance.
10© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Summaries (1)
Why is Once-through Boiler popular in Japan?
HighEfficiency
CompactQuick
Start-up
11© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Once Through Boiler “IF Series”
☆Harmonized Multi-Control for more than 2 Boilers
4.Efficiency 98% for Gas Fired,95% for Oil Fired (with Economizer)
1.Capacity 2.5 ~ 5 t/h
3.License
0.98 / 1.56 / 1.96/ 3.2 MPa
8.Option
7.Steam Dryness
PI Control(with de-aeration device)5.Control
Pressure Fluctuation: ±0.01 MPaRange of combustion:30~100%(Oil)
17~100%(Gas)
De-aeration device, PI combustion6.Life Cycle More than 15 years
Big Once-through Boiler
2.MaximumWorking Pressure
Not required in Japan
☆100% Drain Recovery at high pressure
More than 99.5%Equivalent Performance
& High dryness
12© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Water Tube2.1%
Fire Tube3.0%
HRSG3.8%
Once Though (less than 2 ton)
35.5%
Once Though(over 2 ton)
55.7%
10,089ton(2016)
Boiler Market Trend in Japan
#Japan Boiler Association Market database
0
1,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
Water Tube Smoke TubeHRSG Onece Though (below than 2 ton)Onece Though (over 2t)
Absorption Chiller
14© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Gas Turbine Cogeneration System
Chilled
Water
Supply
Electricity
Steam
NG
Heat Recovery Rate:23%
Efficiency:31%
Exhaust Gas
HRSG
Gas Turbine Generator
Boiler SteamAbsorption Chiller
Steam
15© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Absorption Chiller “Efficio”
Kawasaki had developed the highest efficient absorption chillerin the world in 2013
Note) COP is based on LHV
16© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Steam Absorption Chiller “Efficio”
The Efficio delivers high annual operational efficiency by adopting a parallel-flow, solution invertercontrol and larger absorbent solution storage tank. These features ensure excellent efficiencyacross the full range of load conditions, contributing to greater energy savings.
The Efficio employs below items for highly efficient operation at partial load.
Parallel Flow
Solution Pump Inverter Control
Larger Absorbent Solution Storage Tank
Parallel flow can be operated with highefficiency at partial load.
Solution pump inverter control so that it canbe operated with high efficiency at partialload.
The larger absorbent solution storage tankprevents the heat transfer tubes in thesolution at low load. It can keep heat transferarea.
Partial Load Characteristics
Cooling water inlet temperature conditions are as specified by the JIS standards (32℃ at 100% load, 27℃ at 0% load, with the temperature varying proportionally at loads between 0% and 100%).
17© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Gas Engine Cogeneration System
Chilled
Water
Supply
Electricity
Hot Water
Supply
Steam
Hot Water Absorption Chiller
NG
CommercialPower
電力
Chilled WaterHot Water
Steam
Sub Station
HeatExchanger
Centrifugal Chiller
Heat Exchanger
Steam Absorption Chiller
Header
Steam
Exhaust Gas
HRSG
Gas Boiler
Exhaust Gas
18© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Hot Water Chiller “TSH Series”
The highest efficiency
COP (based on JIS) = 0.80
2-stage generation/condensationwhich structure has double generator and condenser(higher and lower pressure), it can be used to low temperature hot water (Min. 75’C).
Efficiency
Structure
Lower PressureGenerator
Higher PressureGenerator
19© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Exhaust HeatFossil Fuel
Various energy sources can be utilized
Direct firing
Oil
Gas
Waste Hot Water
Gas Engine
Gas Turbine
Solar, Geo-thermal
Renewable Energy
HotWater
Steam
AbsorptionChiller
Chilled Water
SteamExhaust
Gas
SteamExhaust
Gas
HRSG
HRSG
20© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Supply Record for Solar Cooling
21© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Applying JCM Project in Indonesia
Cilegon
Cikampek
1High Efficiency Once-through boiler in Film Factory (2016)IF-4000 / 1 unit
2High Efficiency Once-through boiler in Golf Ball Factory (2016)IF-3000 / 1 unit
2) Boiler
Karawang
1) Chiller
1Absorption chiller in Chemical Factory (2018)NES-630A / 1 unit
22© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Introduction of KTE Boilers Lineup
Water TubeBoiler
Multi TubeOnce-Trough
Steam Output Kg/h
10,0
00
7,0
00
6,0005,0004,0003,0002,0001,5001,000500
20,0
00
30,0
00
40,0
00
Smoke(Fire)Tube Boiler
HRSGSmoke Tube
Type
HRSGWater Tube
Type
HRSG Multi TubeOnce-Through
Type
400
2,500
5,000
606
2,516
1,000
4,000 30,000
10,000
10,000
5,000
35,000
KD Series
KS Series
IF Series
KF Series
KS-HR Series
RGA Series (KDF Series)
RF Series
1,677
5,031
23© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved
Line up of KTE Chillers
Cooling Capacity kW(USRT)
3,517(1,000)
3,165(900)
2,814(800)
2,462(700)
2,110(600)
1,759(500)
1,407(400)
1,055(300)
703(200)
352(100)
DirectFired
StreamFired
Gene-LinkGas&
Hot Water
Hot Water
Triple Effect Direct Fired Absorption Chiller
NZ Series
NH, NU, NE Series
SIGMA MIDY Series
NES Series
Triple Effect Direct Fired Absorption Chiller
NZJ Series
NHJ Series
TZU Series
TSH Series
563(160)
281(80)
280(80)
141(40)
281(80)
510(145)
281(80)
281(80)
281(80)
281(80)
1,196(340)
3,517(1,000)
3,517(1,000)
246(70)
3,517(1,000)
1,090(310)
3,517(1,000)
3,517(1,000)
1,055(300)
1,759(500)
24© 2015 Kawasaki Heavy Industries, Ltd. All Rights Reserved