k-flex name product november k-flex k-flex k-fire · 2017. 2. 3. · k-klex fire ex mortar pg. 34...
TRANSCRIPT
K-FLEX NAME PRODUCT
K-FLEX K-FIRE K-FLEX
K-FLEX POLSKA Sp. z o.o. Pucka 112 - 81-154 Gdynia, Polandtel.: +48 632880200 - fax: +48 632880236 e-mail: [email protected] www.K-FLEX.pl
N o v e m b e r 2 0 1 6
K-FLEX K-FIREf i r e s t o p p i n g s o l u t i o n s
K-FLEX K-FIRE
INDEX
K-FLEX K-FIRE Pg. 2K-KLEX K-FIRE COLLAR-P Pg. 5K-KLEX K-FIRE COLLAR-S Pg. 6K-KLEX K-FIRE COLLAR-Z Pg. 7K-KLEX FIRE WRAP Pg. 10K-KLEX FIRE ACRYLIC Pg. 14K-KLEX K-FIRE SEALANT A PLUS Pg. 16K-KLEX K-FIRE SEALANT S PLUS Pg. 18K-KLEX K-FIRE HP SEALANT Pg. 203M™ FIRE BARRIER WATER TIGHT SEALANT 3000 WT Pg. 22K-KLEX K-FIRE MORTAR Pg. 32K-KLEX FIRE EX MORTAR Pg. 343M™FIRE BARRIER DUCT WRAP 615+ Pg. 38
K-FLEX K-FIRE
2
K-FLEX K-FIRE
K-FLEX is proud to announce K-FLEX K-FIRE, the new range of product for passive fire protection.
In an ever evolving world, there is growing awareness and attention to the protection of people in dangerous situations, such as those resulting from a fire.
New larger, more futuristic and innovative buildings are in the design and/or construction phase and therefor require more efficient solutions for passive protection against fire .
K-FLEX wants to provide designers and installers a complete range of solutions for fire protection, capable of ensuring the compliance to the most stringent regulatory requirements.
K-FLEX K-FIRE solutions are economical, versatile, easy to install and, above all, reliable.
Each solution of K-FLEX K-FIRE is tested by independent and recognized laboratories and evaluated according to the current standard of fire resistance tests.
K-FLEX continues to develope new products and solutions able to meet the requirements of fire stopping and fire protection applications.
K-FLEX K-FIRE
K-F
LEX
K-F
IRE
3
A range of devices designed to be fitted around plastic pipes where they penetrate fire separating structures.Under fire conditions the intumescent material within the collar expands to crush the softening pipe and fill the resultant opening, thereby maintaining the fire integrity and insulation performance of the floor or wall.
K-FLEX K-FIRE COLLARs provide up to 240 minutes fire resistance to:- Plastic pipes penetrating fire partitioning walls.- Plastic pipes penetrating fire partitioning floors.
K-FLEX K-FIRE COLLAR APPLICATIONS
- The substrate around pipe should be flat and free from obstructions;- Release the retaining system and position the collar around pipe;- Secure the retaining system of the collar;- Secure the collar by 50mm x 8mm steel, masonry screws or 50mm minimum expanding metallic bolts;- Do not use fixings that rely on plastic components for grip.
INSTALLATION APPROVALS
K-FLEX K-FIRECOLLAR
K-FIRE COLLAR-S
K-FIRE COLLAR-P
K-FIRE COLLAR-Z
K-FLEX K-FIRE COLLAR
CE Marked 0843–CPR–0279ETA 15-0756ETAG 026-2 (2011) according EN 1366-3 Penetration Seals
4
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE COLLAR
Property Value Test method
Fire Rating Up to EI 240 EN 1366-3
Tested penetration seal inFlexible walls: min. thickness 100 mm;Rigid walls: min. thickness of 100 mm;Rigid floors: min. thickness of 150 mm;
Tested service penetration
- PVC-U pipe up to Ø200mm;- PE pipe up to Ø160mm;
- ABS pipe up to Ø160mm;- SAN+PVC pipe up to Ø160mm;
- PVC-U pipe up to Ø55mm + FEF insulation- Copper pipe up to Ø54mm + FEF insulation
- Cables in bundles up to Ø100mm
*FEF = Flexible Elastomeric Foam
Durability and serviceabilityType Y2: intended for use at temperature below 0°C,
but with no exposure to rain nor UV. Includes lower use categories.
EOTA TR 024:2009
TECHNICAL DATA
K-FIRE COLLAR-P
K-FIRE COLLAR-P is K-FLEX‘s premium solution for protecting combustible pipe penetrations up to DN200* (larger diameter will be soon available) and consists of red painted steel shells secured by a hinge and latch system.
K-FLEX K-FIRE COLLAR-P
Type Item/Box Code Bar Code
K-FLEX K-FIRE COLLAR-P - 55 mm 24 85CFPC00055 8027409727200
K-FLEX K-FIRE COLLAR-P - 82 mm 24 85CFPC00082 8027409727217
K-FLEX K-FIRE COLLAR-P - 110 mm 24 85CFPC00110 8027409727224
K-FLEX K-FIRE COLLAR-P - 125 mm 22 85CFPC00125 8027409727231
K-FLEX K-FIRE COLLAR-P - 140 mm 20 85CFPC00140 8027409727248
K-FLEX K-FIRE COLLAR-P - 160 mm 12 85CFPC00160 8027409727255
K-FLEX K-FIRE COLLAR-P - 200 mm 1 85CFPC00200 8027409727262
K-FLEX K-FIRE COLLAR-P
DOCUMENTATION PDF
> ETA <
K-FLEX K-FIRE COLLAR
K-F
LEX
K-F
IRE C
OLLA
R
> TDS < > MSDS <
5
K-FLEX K-FIRE COLLAR
K-FIRE COLLAR-S represents an ideal solution for protecting penetration of small diameter pipes and comprises stainless steel shells that are secured by interlocking fastening system.
K-FLEX K-FIRE COLLAR-S
Type Item/Box Code Bar Code
K-FLEX K-FIRE COLLAR-S - 32 mm 60 85CFSS00032 8027409727149
K-FLEX K-FIRE COLLAR-S - 38 mm 60 85CFSS00038 8027409727156
K-FLEX K-FIRE COLLAR-S - 42 mm 60 85CFSS00042 8027409727163
K-FLEX K-FIRE COLLAR-S - 46 mm 60 85CFSS00046 8027409727170
K-FLEX K-FIRE COLLAR-S - 48 mm 60 85CFSS00048 8027409727187
K-FLEX K-FIRE COLLAR-S - 50 mm 60 85CFSS00050 8027409727194
K-FLEX K-FIRE COLLAR-S
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
6
K-FIRE COLLAR-S represents an ideal solution for protecting penetration of small diameter pipes and comprises stainless steel shells that are secured by interlocking fastening system.
K-FLEX K-FIRE COLLAR-S
Type Item/Box Code Bar Code
K-FLEX K-FIRE COLLAR-S - 32 mm 60 85CFSS00032 8027409727149
K-FLEX K-FIRE COLLAR-S - 38 mm 60 85CFSS00038 8027409727156
K-FLEX K-FIRE COLLAR-S - 42 mm 60 85CFSS00042 8027409727163
K-FLEX K-FIRE COLLAR-S - 46 mm 60 85CFSS00046 8027409727170
K-FLEX K-FIRE COLLAR-S - 48 mm 60 85CFSS00048 8027409727187
K-FLEX K-FIRE COLLAR-S - 50 mm 60 85CFSS00050 8027409727194
K-FLEX K-FIRE COLLAR
K-F
LEX
K-F
IRE C
OLLA
R
K-FIRE COLLAR-Z represents the economical solution for protecting combustible pipe penetration, made of galvanized steel metal shells and interlocking fastening system.
K-FLEX K-FIRE COLLAR-Z
Type Item/Box Code Bar Code
K-FLEX K-FIRE COLLAR-Z - 55 mm 30 85CFGS00055 8027409727057
K-FLEX K-FIRE COLLAR-Z - 65 mm 30 85CFGS00065 8027409727064
K-FLEX K-FIRE COLLAR-Z - 70 mm 30 85CFGS00070 8027409727071
K-FLEX K-FIRE COLLAR-Z - 82 mm 30 85CFGS00082 8027409727088
K-FLEX K-FIRE COLLAR-Z - 90 mm 30 85CFGS00090 8027409727095
K-FLEX K-FIRE COLLAR-Z - 110 mm 30 85CFGS00110 8027409727101
K-FLEX K-FIRE COLLAR-Z - 125 mm 30 85CFGS00125 8027409727118
K-FLEX K-FIRE COLLAR-Z - 140 mm 30 85CFGS00140 8027409727125
K-FLEX K-FIRE COLLAR-Z - 160 mm 30 85CFGS00160 8027409727132
K-FLEX K-FIRE COLLAR-Z
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
7
K-FLEX K-FIRE COLLAR - APPLICATIONS
Combustible pipes fitted with K-Flex K-Fire Collar to the recessed/cast in, within the soffit of the floor.
Combustible pipes fitted with K-Flex K-Fire Collar to the soffit of the floor
K-FLEX K-FIRE COLLAR
Application Classification
PVC-U pipe - diameter 110 mm, wall thickness 3.2 mm EI 90 U/U, EI 90 C/U, EI 90 U/C, EI 90 C/C
PVC-U pipe - diameter 200 mm, wall thickness 3.9 mm EI 240 U/U, EI 240 C/U, EI 240 U/C, EI 240 C/C
Application Classification
PVC-U pipe - diameter 32 mm, wall thickness 3 mm
EI 240 U/U, EI 240 C/U, EI 240 U/C, EI 240 C/CPVC-U pipe - diameter 38 mm, wall thickness 3 mm
PVC-U pipe - diameter 40 mm, wall thickness 3 mm
PVC-U pipe - diameter 42.2 mm, wall thickness 2 mm
EI 180 U/U, EI 180 C/U, EI 180 U/C, EI 180 C/C
PVC-U pipe - diameter 46 mm, wall thickness 2 mm
PVC-U pipe - diameter 48.3 mm, wall thickness 2 mm
PVC-U pipe - diameter 50 mm, wall thickness 2 mm
PVC-U pipe - diameter 55 mm, wall thickness 2 mm
PVC-U pipe - diameter 82 mm, wall thickness 3.2 mm
PE, ABS, SAN+PVC pipe - diameter 32 mm, wall thickness 3.7 mm
EI 180 U/U, EI 180 C/U, EI 180 U/C, EI 180 C/CPE, ABS, SAN+PVC pipe - diameter 38 mm, wall thickness 3.7 mm
PE, ABS, SAN+PVC pipe - diameter 40 mm, wall thickness 3.7 mm
PE, ABS, SAN+PVC pipe - diameter 75 mm, wall thickness8.2 mmEI 240 U/U, EI 240 C/U, EI 240 U/C, EI 240 C/C
PE, ABS, SAN+PVC pipe - diameter 110 mm, wall thickness 8.2 mm
PE, ABS, SAN+PVC pipe - diameter 160 - 200 mm, wall thickness 6.2 mm EI 180 U/U, EI 180 C/U, EI 180 U/C, EI 180 C/C
8
K-FLEX K-FIRE COLLAR
Application Classification
PVC-U pipe - diameter 32 - 40 mm, wall thickness 3 mmEI 120 U/U, EI 120 C/U, EI 120 U/C, EI 120 C/C
PVC-U pipe - diameter 42.2 - 82 mm, wall thickness 3.2 mm
PE, ABS, SAN+PVC pipe - diameter 32 - 40 mm, wall thickness 3.7 mmEI 120 U/U, EI 120 C/U, EI 120 U/C, EI 120 C/C
PE, ABS, SAN+PVC pipe - diameter 42.2 - 50 mm, wall thickness 4.6 mm
PE, ABS, SAN+PVC pipe - diameter 75 mm, wall thickness 6.8 mm EI 60 U/U, EI 60 C/U, EI 60 U/C, EI 60 C/C
PE, ABS, SAN+PVC pipe - diameter 75 - 90 mm, wall thickness 5.1 mm EI 120 U/U, EI 120 C/U, EI 120 U/C, EI 120 C/C
PE, ABS, SAN+PVC pipe - diameter 110 mm, wall thickness 6.2 mm EI 120 U/U, EI 120 C/U, EI 120 U/C, EI 120 C/C
PE, ABS, SAN+PVC pipe - diameter 110 mm, wall thickness 10 mm EI 60 U/U, EI 60 C/U, EI 60 U/C, EI 60 C/C
PE, ABS, SAN+PVC pipe - diameter 160 - 200 mm, wall thickness 7 mm EI 120 U/U, EI 120 C/U, EI 120 U/C, EI 120 C/C
PVC-U pipe, FEF insulation 19 mm - diameter 55 mm, wall thickness 2 mmE 120 U/U, E 120 C/U, E 120 U/C, E 120 C/C
EI 90 U/U, EI 90 C/U, EI 90 U/C, EI 90 C/C
Copper pipe, FEF insulation19 mm - diameter 54 mm, wall thickness 0.8 mmE 120 U/U, E 120 C/U, E 120 U/C, E 120 C/C
EI 60 U/U, EI 60 C/U, EI 60 U/C, EI 60 C/C
Telecomunication cable - diameter up to 21 mm or bundle diameter up to 100 mm EI 90
Telecomunication cable diameter up to 21 mm or bundle diameter up to 100 mm, Insuwrap insulation 300 mm
EI 120
K-FLEX K-FIRE COLLAR - APPLICATIONS
Insulated metal and combustible pipes and telecoms cables fitted with K-Flex K-Fire Collar to both sides of the wall.
9
K-FLEX FIRE WRAP is a pipe closure device used to form penetration seals where combustible pipes and insulated metal pipes penetrate walls and floors.K-FLEX FIRE WRAP is supplied in bags sized according to pipe diameter. The wrap is wrapped around the pipe and pushed into the aperture in the separating element or cast in with K-FLEX FIRE EX MORTAR.
- Sealing combustible pipe penetrations;- Sealing non-combustible pipe penetration with thermal insulation;- Sealing cable penetrations.
K-FLEX FIRE WRAP APPLICATIONS
- The substrate around the pipe should be of solid construction;- Fix the Wrap around the pipe using the adhesive tab and slide along pipe into wall/floor opening to the correct position;- Seal any gap with the correctr sealant.
CE Marked 0843–CPR–0269ETA 15-0566ETAG 026-2 (2011) according EN 1366-3 Penetration Seals
INSTALLATION APPROVALS
K-FLEX FIREWRAP
K-FLEX FIRE WRAP
10
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX FIRE WRAP
Property Value Test method
Fire Rating Up to EI 240 EN 1366-3
Tested penetration seal inFlexible walls: min. thickness 100 mm;Rigid walls: min. thickness of 150 mm;Rigid floors: min. thickness of 150 mm;
Tested service penetration
- PVC-U pipe up to Ø315mm;- PP pipe up to Ø75mm;- PE pipe up to Ø250mm;
- ABS pipe up to Ø250mm;- SAN+PVC pipe up to Ø250mm;
- Bundle of 2 pipes made of PVC-U, PP, PE, ABS and SAN+PVC;- Geberit Mepla pipe up to Ø75mm;
- PVC-U pipe up to Ø110mm + FEF insulation;- Copper pipe up to Ø54mm + FEF insulation;- Steel pipe up to Ø165mm + FEF insulation;
*FEF = Flexible Elastomeric Foam
Durability and serviceability Type X: intended for use at conditions exposed to weathering. EOTA TR 024:2009
TECHNICAL DATA
K-FLEX FIRE WRAP
K-F
LEX
FIR
E W
RA
P
K-FLEX FIRE WRAP
Type Item/Box Code Bar Code
K-FLEX FIRE WRAP - 55 mm precut strip 100 850VRFW0055 8027409727842
K-FLEX FIRE WRAP - 82 mm precut strip 100 850VRFW0082 8027409727774
K-FLEX FIRE WRAP - 110 mm precut strip 100 850VRFW0110 8027409727781
K-FLEX FIRE WRAP - 125 mm Pprecut strip 48 850VRFW0125 8027409727798
K-FLEX FIRE WRAP - 160 mm precut strip 24 850VRFW0160 8027409727804
K-FLEX FIRE WRAP - 200 mm precut strip 24 850VRFW0200 8027409727811
K-FLEX FIRE WRAP - 250 mm precut strip 24 850VRFW0250 8027409727828
K-FLEX FIRE WRAP - 25 m x 50 mm roll 24 85NSFW25050 8027409727866
K-FLEX FIRE WRAP - 25 m x 75 mm roll 24 85NSFW25075 8027409727873
RANGE
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
11
K-FLEX FIRE WRAP - APPLICATIONSInsulated cooper pipe - EI180
Insulated copper pipe - EI60 Insulated Pex/Al/Pex pipe - EI180
Insulated Pex/Al/Pex pipe - EI90 Insulated steel pipe - EI240
Insulated steel pipe - EI120
Plastic pipe - EI60 - EI240 Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE WRAP2 layers 50 mm width
K-FLEX FIRE WRAP2 layers 50 mm width
K-FLEX FIRE WRAP2 layers 50 mm width
K-FLEX FIRE WRAP2 layers 50 mm width
Steel pipe Ø ≤ 40 mmFEF insulation 13 mm thickness
K-FLEX FIRE WRAP1 layer 50 mm width
K-FLEX FIRE WRAPon botom
Copper pipe Ø ≤ 12 mmFEF insulation 9 mm thickness
Copper pipe Ø ≤ 54 mmFEF insulationthickness 13 - 25 mm
Pex/Al/Pex pipe Ø ≤ 16 mmFEF insulation thickness 9 mm
Pex/Al/Pex pipe Ø ≤ 75 mmFEF insulationthickness 13 - 25 mm
K-FLEX FIRE WRAP2 layers 50 mm width
Steel pipe Ø ≤ 165 mmFEF insulation thickness 13 - 19 mm
Plastic pipe
Pipe type Wrap typeMaximum opening
Fire classification
Ø ≤ 75 mm PP 50 x 3,6 mm (2 layers)300 x 300 mm EI240 C/C
1200 x 2400 mm El180 C/C
Ø ≤ 110 mm PE, ABS; SAN+PVC 50 x 1,8 mm (1 layer) 1200 x 2400 mm El60 C/C
Ø ≤ 110 mm PVC-U; PVC-C
75 x 1,8 mm (1 layer) 1200 x 2400 mm El180 C/C
50 x 3,6 mm (2 layers)200 x 200 mm EI240 C/C
1200 x 2400 mm El180 C/C
Ø ≤ 125 mm PE, ABS; SAN+PVC 75 x 3,6 mm (2 layers) 1200 x 2400 mm El180 C/C
Ø = 125 mm PVC-U; PVC-C 50 x 7,2 mm (4 layers)300 x 300 mm EI240 C/C
1200 x 2400 mm El180 C/C
Ø = 160 mm PE, ABS; SAN+PVC 75 x 7,2 mm (4 layers) 1200 x 2400 mm El180 C/C
Ø = 160 mm PVC-U; PVC-C
50 x 10,8 mm (6 layers)300 x 300 mm EI240 C/C
1200 x 2400 mm El180 C/C
75 x 7,2 mm (4 layers) 300 x 300 mm EI240 C/C
75 x 5,4 mm (3 layers) 1200 x 2400 mm El180 C/C
Ø = 200 - 250 mm PE, ABS; SAN+PVC 75 x 12,6 mm (7 layers) 1200 x 2400 mm El180 C/C
12
K-FLEX FIRE WRAP - APPLICATIONS
Pipe type Wrap typeFire
classification
Ø ≤ 40 mm PVC-U; PVC-C
50 x 1,8 mm (1 layer)
E120 U/C, C/C ; El60 U/C, C/C
Ø ≤ 40 mm PE, ABS; SAN+PVCEl120 U/C, C/C
Ø ≤ 40 mm PP
Ø ≤ 110 mm PVC-U; PVC-C
50 x 3,6 mm (2 layers)
E120 U/C, C/C ; El90 U/C, C/C
Ø = 41 - 110 mm PE, ABS; SAN+PVC El 60U/C, C/C
Ø = 41 - 110 mm PP E120 U/C, C/C ; El90 U/C, C/C
Ø ≤ 125 mm PVC-U; PVC-C
50 x 5,4 mm (3 layers)El120 U/C, C/C
Ø ≤ 125 mm PE, ABS; SAN+PVC
Ø = 125 mm PP E120 U/C, C/C ; El90 U/C, C/C
Ø = 160 mm PVC-U; PVC-C
50 x 7,2 mm (4 layers)
El60 U/C, C/C
Ø = 160 mm PE, ABS; SAN+PVCE120 U/C, C/C ; El90 U/C, C/C
Ø = 160 mm PP
Insulated steel pipe - EI60
Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
Steel pipe Ø ≤ 165 mmFEF insulationthickness 13 - 25 mm
K-FLEX FIRE WRAP2 layers 50 mm width
Plastic pipe - EI120
Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
PVC-U pipeØ = 315 mm
K-FLEX FIRE WRAP10 layers 75 mm width
Insulated steel pipe - EI120
Insulated copper pipe - EI120 Insulated Pex/Al/Pex pipe - EI120
Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 25 mmboth sides
K-FLEX FIRE EX MORTARthickness ≥ 25 mm
K-FLEX FIRE EX MORTARthickness ≥ 25 mm
Steel pipe Ø ≤ 40 mmFEF insulationthickness 13 mm
Copper pipe Ø ≤ 54 mmFEF insulationthickness 9 - 25 mm
Pex/Al/Pex pipe Ø ≤ 75 mmFEF insulationthickness 9 - 25 mm
K-FLEX FIRE WRAP2 layers 50 mm width
K-FLEX FIRE WRAP2 layers 50 mm width
K-FLEX FIRE WRAP2 layers 50 mm width
Mineral woolthickness 50 mmdensity 150 kg/m3
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Insulated steel pipe - EI60
Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 50 mmboth sides
Steel pipe Ø ≤ 165 mmFEF insulationthickness 13 - 32 mm
K-FLEX FIRE WRAP2 layers 50 mm width
Insulated steel pipe- EI240
Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTAR
Plastic pipeK-FLEX FIRE WRAP
13
K-FLEX FIRE ACRYLIC is an one part acrylic sealant designed to prevent the spread of fire and smoke through joints and openings in fire rated walls and floors including openings formed around building service penetrations. K-FLEX FIRE ACRYLIC will also maintain the acoustic design performance in walls and floors. K-FLEX FIRE ACRYLIC cures when it is subjected to atmospheric conditions and retain a certain elasticity for joint movement. Under fire exposure, K-FLEX FIRE ACRYLIC creates a robust fire seal creating a durable intumescent char. Thermal activation takes place at about 180°C when the material will expand (intumesce) and prevent the passage of fire and smoke for periods up to and beyond 4 hours.
- Construction joints in fire separating walls and floors;- Acoustic seals around perimeters of fire resistant partitions;- Gaps behind fire resistant door casings;- Seating of fire resistant grills, intumescent pipe closer around pipes.
K-FLEX FIRE ACRYLIC APPLICATIONS
- Ensure all contact surfaces are free from dust, oil and grease;- Ensure opening is filled using a backing material (if required);- Filling depth: 10 to 25mm.
INSTALLATION
K-FLEX FIREACRYLIC
K-FLEX FIRE ACRYLIC
CE Marked 0843-CPR-0257ETA 15-0322 ETAG 026-2 (2011) according EN 1366-3 Penetration SealsAgBB and EC1Plus for Low VOC
APPROVALS
14
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX FIRE ACRYLIC
Property Value Test method
Fire Rating Up to EI 240 EN 1366-3
Tested Penetration Seal InFlexible walls: min. thickness 100 mmRigid walls: min. thickness of 150 mmRigid floors: min. thickness of 150 mm
Tested Service Penetration
- PVC-U pipes up to Ø32mm- PVC-U pipes up to Ø40mm + MW Insulation
- PE, PE-HD pipes up to Ø40mm + MW Insulation- ABS pipes up to Ø40mm + MW Insulation
- SAN+PVC pipes up to Ø40mm + MW Insulation- PP pipes up to Ø32mm
- PP pipes up to Ø75mm + AESW Insulation- Geberit Mepla up to Ø75mm + FEF / MW / AESW Insulation
- Copper pipes up to Ø54mm- Copper pipes up to Ø54mm + FEF / MW / AESW Insulation
- Steel pipes up to Ø16mm- Steel pipes up to Ø165mm + FEF / AESW Insulation
- Steel pipes up to Ø219mm + MW Insulation- Alupex pipes up to Ø75mm + MW / AESW Insulation
- Electrical Cables in bundles up to Ø100mm- Telecom Cables in bundles up to Ø100mm
- Blank Seal + AESW Insulation
*FEF: Flexible Elastomeric Foam*MW: Mineral Wool
*AESW: Alkaline earth silicate wool
Durability And ServiceabilityType Z2: Intended for uses in internal conditions,
excluding temperature below 0°C, without exposure to rain or UV.EOTA TR 024:2009
Reaction To Fire D-s1,d1 EN 13501-1Storing Temp. +5 to +30°CService Temp. -20°C to +70°CDensity 1.58 g/mlFlexibility 7.5%Cure Rate 3 to 5 days depending on thickness and temperatureTack Free 75 minutesWater Resistance Good when fully curedU.V. Resistance GoodJoint Movement Remains flexibleShelf Life 12 monthsWater Solubility Miscible
Acoustic Performances up to 62 dB (single side)over 62 dB (double side) EN 10140-2
Ecological Data EMICODE emission class EC 1PLUS Low Emission
TECHNICAL DATA
K-FLEX FIRE ACRYLIC
K-F
LEX F
IRE
AC
RYLIC
K-FLEX FIRE ACRYLIC
Type Item/Box Code Bar Code
K-FLEX FIRE ACRYLIC - 310 ml cartridge, white 12 850CL020213 8027409727736
K-FLEX FIRE ACRYLIC - 310 ml cartridge, grey 12 850CL020214 8027409727743
K-FLEX FIRE ACRYLIC - 600 ml sausage, white 12 850CL020215 8027409727750
RANGE
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
15
K-FIRE SEALANT A PLUS is a fire resistant water based acoustic acrylic sealant, designed for internal use with fire and smoke resisting gaps and service penetrating capability.
K-FIRE SEALANT A PLUS can be used where a low movement fire resistant and/or acoustic joint is required.
K-FIRE SEALANT A PLUS provides good adhesion to most common building materials like brick, concrete, plasterboard, wood etc.
- Construction joints in fire partitioning walls and floors;- Acoustic seals around perimeters of fire resistant partitions;- Gaps behind fire resistant door casings;- Seating of fire resistant grills, intumescent pipe closers, etc.;- Around metallic pipes;- Around cable penetrations.
K-FLEX K-FIRE SEALANT A PLUS APPLICATIONS
- Ensure all contact surfaces are free from dust, oil and grease;- Ensure opening is filled using a backing material (if required);- Fill opening to the required depth;- Filling depth: 10 to 30mm;- Tool surface with moist spatula within 30 minutes.
CE Marked 0843-CPR-0284ETA 15-0818 ETAG 026-2 (2011) according EN 1366-3 Penetration SealsETA 15-0795ETAG 026-3 (2011) according EN 1366-4 Linear Joint and Gap Seals
INSTALLATION APPROVALS
K-FLEX K-FIRESEALANT A PLUS
K-FLEX K-FIRE SEALANT A PLUS
16
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE SEALANT A PLUS
Property Value Test method
Fire Rating Up to EI 240EN 1366-3EN 1366-4
Tested penetration seal InFlexible walls: min. thickness 100 mmRigid walls: min. thickness of 100 mmRigid floors: min. thickness of 150 mm
Tested service penetration
- Copper pipes up to Ø35mm- Copper pipes up to Ø54mm + MW insulation
- Steel pipes up to Ø89mm- Steel pipes up to Ø219mm + MW insulation
- Electrical Cables in bundles- Telecom Cables in bundles
- Linear Joint up to W50 + backing material
*MW: Mineral Wool
Durability and serviceabilityType Z1: Intended for use at internal conditions,
excluding temperature below 0°C.EOTA TR 024:2009
Application Temp. +5°C to +40°C
Storing Temp. +5°C to +30°C
Density 1.64 g/ml
Water solubility Miscible
Ecological dataHalogen Free
Non-toxicDust Free
TECHNICAL DATA
K-FLEX K-FIRE SEALANT A PLUS
Type Item/Box Code Bar Code
K-FLEX K-FIRE SEALANT A PLUS - 310 ml cartridge, white 25 850CL020201 8027409727279
K-FLEX K-FIRE SEALANT A PLUS - 310 ml cartridge, grey 25 850CL020202 8027409727286
K-FLEX K-FIRE SEALANT A PLUS - 600 ml sausage, white 12 850CL020203 8027409727293
K-FLEX K-FIRE SEALANT A PLUS - 600 ml sausage, grey 12 850CL020204 8027409727309
RANGE
DOCUMENTATION PDF
> ETA - J < > TDS < > MSDS <> ETA - P <
ETA - J : JointsETA - P : Penetrations
K-FLEX K-FIRE SEALANT A PLUS
K-F
LEX
K-F
IRE
SE
ALA
NT A
PLU
S
17
A one part, fire resistant, neutral curing, silicone sealant to be used in situations where a flexible fire resistant joint is required. Excellent adhesion to most building substrates, including porous materials, without the use of primers.Good durability.
- Construction joints in fire partitioning walls and floors;- Glazing applications, including curtain walls;- Seating of fire resistant grills, intumescent pipe closers, etc.;- Around metallic pipes;- Around cable penetrations.
K-FLEX K-FIRE SEALANT S PLUS APPLICATIONS
- Ensure all contact surfaces are free from dust, oil and grease;- Ensure opening is filled using a backing material (if required);- Fill opening to the required depth;- Filling depth: 10 to 25mm.
CE Marked 0843–CPR–0285ETA 15-0819ETAG 026-2 (2011) according EN 1366-3 Penetration SealsETA 15-0817ETAG 026-3 (2011) according EN 1366-4 Linear Joint and Gap Seals
INSTALLATION APPROVALS
K-FLEX K-FIRESEALANT S PLUS
K-FLEX K-FIRE SEALANT S PLUS
18
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE SEALANT S PLUS
Property Value Test method
Fire Rating Up to EI 240EN 1366-3EN 1366-4
Tested Penetration Seal InRigid walls: min. thickness of 150 mmRigid floors: min. thickness of 150 mm
Tested Service Penetration
- Copper pipes up to Ø38mm- Copper pipes up to Ø38mm + FEF Insulation
- Steel pipes up to Ø40mm- Steel pipes up to Ø40mm + FEF Insulation
- Cables in bundle up to Ø80mm
- Linear Joint up to W40 + backing material
*FEF: Flexible Elastomeric Foam
Durability And ServiceabilityType X: Intended for use at conditions exposed to weathering and in the temperature range -20°C to 70°C. Also suitable for internal conditions.
EOTA TR 024:2009
Movement Capability +/- 25%
Storing Temp. +5°C to +30°C
Application Temp. -5°C to +40°C
Density 1.40 g/ml
Water Solubility Immiscible
Ecological Data
Halogen FreeNon-toxic
Low smokeDust Free
TECHNICAL DATA
K-FLEX K-FIRE SEALANT S PLUS
K-F
LEX
K-F
IRE
SE
ALA
NT S
PLU
S
K-FLEX K-FIRE SEALANT S PLUS
Type Item/Box Code Bar Code
K-FLEX K-FIRE SEALANT S PLUS - 310 ml cartridge, white 25 850CL020208 8027409727347
K-FLEX K-FIRE SEALANT S PLUS - 310 ml cartridge, grey 25 850CL020209 8027409727354
RANGE
DOCUMENTATION PDF
> TDS < > MSDS <
ETA - J : JointsETA - P : Penetrations
> ETA - J < > ETA - P <
19
K-FLEX K-FIRE HP SEALANT is a is an intumescent pressure sealant which, when exposed to fire, expands protecting penetrations including cables, cable bunches, cable trays, plastic and metallic pipes.K-FLEX K-FIRE HP SEALANT maintains the integrity and insulation performance of the seal through masonry and plasterboard. The sealant is intended for use in service penetrations through walls and floors where fire integrity and insulation needs to be preserved. Under fire conditions the product swells and exerts pressure to the surrounding substrates leading to closure of the penetration.
K-FLEX K-FIRE HP SEALANT
APPLICATIONS
CE Marked 1121-CPR-JA5097ETA 15-0778ETAG 026-2 (2011) according EN 1366-3 Penetration Seals
- Ensure all contact surfaces are free from dust, oil and grease;- Ensure opening is filled using proper backing material (if required);- Fill opening around service on both exposed sides: < Ø75mm pipe = 10mm annular gap > Ø75mm pipe = 1/8 of pipe Ø annular gap- Filling depth: 25mm;- Tool surface with moist spatula, using water.
INSTALLATION
APPROVALS
K-FLEX K-FIREHP SEALANT
- Combustible pipe penetration;- Insulated pipes penetrations;- Electric and telecom cables penetrations;- Combination of cables and pipe penetrations.
K-FLEX K-FIRE HP SEALANT
20
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE HP SEALANT
Property Value Test method
Fire Rating Up to EI 240 EN 1366-3
Tested Penetration Seal InFlexible walls: min. thickness of 100 mm
Rigid walls: min. thickness of 100 mmRigid floors: min. thickness of 150 mm
Tested Service Penetration
- PVC pipes up to Ø125mm- HDPE pipes up to Ø63mm- ABS pipes up to Ø63mm- PP pies up to Ø110mm- PE pipes up tp Ø125mm
- Copper pipes up to Ø60mm + FEF / MW Insulation- Single cables up to Ø80mm
- Cables in bundle up to Ø100mm
- Linear Joint up to W40 + backing material
*FEF: Flexible Elastomeric Foam*MW: Mineral Wool
Durability And ServiceabilityType Z2: Intended for uses in internal conditions, excluding temperature
below 0°C, without exposure to rain or UV.EOTA TR 024:2009
Movement Capability +/- 25%
Storing Temp. +5°C to +25°C
Application Temp. -5°C to +35°C
Density 1.28 g/ml
Cure Time 1.7 mm per 24 hours
Expansion Up to 20x
Expansion Temp. 180°C
Shore Hardness 68 ISO 7619-1:2010
Air permeability 600Pa EN 1026
Ecological Data
Low Ozone Depletion Potential (ODP)Low Global Warming Potential (GWP)
Low VOC (0.05g/l)Dust Free
TECHNICAL DATA
K-FLEX K-FIRE HP SEALANT
Type Item/Box Code Bar Code
K-FLEX K-FIRE HP SEALANTS - 310 ml cartridge, gray 12 850CL020212 8027409727385
RANGE
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
K-FLEX K-FIRE HP SEALANT
K-F
LEX
K-F
IRE
HP
SE
ALA
NT
21
3M™ Fire Barrier Water Tight Sealant 3000 WT is a high-performance, ready-to-use, single component, neutral cure, non-slumping intumescent silicone sealant. Product cures upon exposure to atmospheric humidity to form a flexible firestop seal that also acts as a barrier to water leakage and airborne sound transmission. 3M™ Fire Barrier Water Tight Sealant 3000 WT helps control the spread of fire, smoke and noxious gasses before, during and after exposure to a fire when installed in accordance with a listed through penetration or fire-resistive joint assembly.
3M™ 3000 WT
APPLICATIONS
DOP NO 3M FB 3000WT 1121-CPR-JA5006
- Ensure all contact surfaces are free from dust, oil and grease;- Do not use alcohol to clean surfaces in penetration or joint opening- Sealant can be installed with a standard caulking gun- Install the applicable depth of backing material- Clean all tools immediately after use with a commercial solvent
INSTALLATION
APPROVALS
3000 WT SEALANT
- Steel pipe penetration;- Insulated pipes penetrations;- Electric and telecom cables penetrations;- Combination of cables and pipe penetrations.
3M™ FIRE BARRIER WATERTIGHT SILICONE 3000 WT SEALANT
22
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE HP SEALANT
Property Value Test method
Fire Rating Up to EI 120 EN 1366-3
Reaction to Fire Class E DIN EN 13501-1
Durability And Serviceability Type Z1
Colour Grey
Odor Week
Max. Application Temp. +50°C
Density 1.25 g/ml
Expansion Up to 6x
Expansion Temp. 350°C
Full strength 14 - 21 days
TECHNICAL DATA
K-FLEX K-FIRE HP SEALANT
Type Item/Box Code
3M™ FIRE BARRIER WATERTIGHT SILICONE 3000 WT SEALANT - 298 ml 12 850CL020106
3M™ FIRE BARRIER WATERTIGHT SILICONE 3000 WT SEALANT - 592 ml 10 850CL020107
RANGE
DOCUMENTATION PDF
> DOP <
3M™ FIRE BARRIER WATERTIGHT SILICONE 3000 WT SEALANT
3M™
FIR
E B
AR
RIE
R W
ATE
RTI
GH
T S
ILIC
ON
E 3
00
0 W
T S
EA
LA
NT
23
K-FLEX FIRE ACRYLIC - APPLICATIONSSealing line - EI60 - El180
Insulated steel pipe- EI180 Insulated steel pipe- EI60
Insulated copper pipe - EI120 Insulated copper pipe - EI120
Sealing line - EI60 - El240
Maximum opening 300 x 300 mm Maximum opening 300 x 300 mm
Maximum opening 300 x 300 mm Maximum opening 300 x 300 mm
K-FLEX FIRE ACRYLIC K-FLEX FIRE ACRYLIC
Steel pipe Ø ≤ 40 mm FEF insulationthickness 13 - 19 mm
K-FLEX FIRE ACRYLICthickness ≥ 25 mm
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm
Electrical cableØ ≤ 21 mm single or bundle
Steel pipe Ø ≤ 219 mm mineral wool insulationth. ≥ 30 mm dens.≥ 80 kg/m3
lenght 100 cm both sides
Steel pipe Ø ≤ 165 mm FEF insulationthickness 13 - 19 mm
Copper pipe Ø ≤ 54 mm FEF insulationthickness 9 - 13 mm
K-FLEX FIRE ACRYLICthickness ≥ 25 mm both sides
K-FLEX FIRE ACRYLICthickness ≥ 15 mm both sides
K-FLEX FIRE ACRYLICthickness ≥ 15 mm both sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mm both sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mm both sides
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 26 mm
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 50 mm
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm
Copper pipe Ø ≤ 54 mm mineral wool insulation th. ≥ 20 mm dens..≥ 80 kg/m3 lenght 100 cm both sides
Mineral wooldensity ≥ 35 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 25 mm
Maximum opening 300 x 300 mm Maximum opening 300 x 300 mm
Electrical cable - EI120 Insulated steel pipe- EI120
Maximum width The minimum depth of the seal
Position Fire resistance
100 mm 25 mm All El60 / E120
100 mm 25 mm The top face El180 / E180
100 mm 15 mm The top and ceiling El120 / E120
100 mm 15 mm The top and ceiling El180 / E180
Maximum width
Construction Deep Fire resistance
30 mm Light wall 12.5 mm (primer with mineral wool deep 20 mm) El120 / E120
30 mm Light wall 25 mm (without primer) El120 / E120
30 mm Concrate wall 25 mm (primer with mineral wool deep 20 mm) El60 / E240
30 mm Concrate wall 15 mm (primer with mineral wool deep 20 mm) El240 / E240
24
K-FLEX FIRE ACRYLIC - APPLICATIONSPlastic pipe - EI180
Maximum opening 300 x 300 mm
Plastic pipe - EI240
Maximum opening Ø = 100 mm
Plastic pipe - EI240
Electrical cable - EI120 Insulated steel pipe - EI120Maximum opening Ø = 65 mm
Maximum opening 300 x 300 mm Maximum opening 300 x 300 mm
K-FLEX FIRE ACRYLICthickness ≥ 25 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mmboth sides
Steel pipeØ ≤ 22 mm
Electrical cableØ ≤ 21 mmsingle or bundleØ ≤ 100 mm
Mineral wooldensity ≥ 35 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm
Telecommunication cable - EI240
Maximum opening 300 x 300 mm
Steel pipe Ø ≤ 219 mmMineral wool insulationdens. ≥ 80 kg/m3
th. ≥ 30 mmlenght 100 cm
Telecommunication cableØ ≤ 21 mm,single or bundleØ ≤ 100 mm
ElectricalcableØ ≤ 21 mmsingle or bundle
K-FLEX FIRE ACRYLICthickness ≥ 15 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 15 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 15 mmboth sides
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 48 mm
Mineral wooldensity ≥ 35 kg/m3
thickness ≥ 25 mm
Electrical cable - EI120 Steel pipe - EI120
Maximum opening 300 x 300 mm Maximum opening 300 x 300 mm
PP pipe Ø ≤ 75 mm
PE, PE-HD, ABS, SAN+PVCpipe Ø ≤ 40 mm
PVC-U, PVC-C pipe Ø ≤ 75 mm
K-FLEX FIRE ACRYLICthickness ≥ 25 mm both sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mm both sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mm both sides
Mineral wooldensity ≥ 140 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 140 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 35 kg/m3
thickness ≥ 25 mm
25
K-FLEX FIRE ACRYLIC- APPLICATIONSInsulated steel pipe- EI120
Maximum opening 300 x 300 mm
Insulated steel pipe- EI90
Maximum opening 300 x 300 mm
Insulated steel pipe- EI120
Insulated copper pipe - EI120 Insulated copper pipe - EI60Maximum opening 300 x 300 mm
Maximum opening 300 x 300 mm Maximum opening 300 x 300 mm
Insulated steel pipe- EI60
Maximum opening 300 x 300 mm
Pex/Al/Pex insulated pipe- EI60 Plastic pipe - EI90
Maximum opening 300 x 300 mm Maximum opening Ø = 90 mm
K-FLEX FIRE ACRYLICthickness ≥ 12.5 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 25 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 12,5 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 12,5 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 12,5 mmboth sides
K-FLEX FIRE ACRYLICthickness ≥ 12,5 mmboth sides
Steel pipe Ø ≤ 219 mmMineral wool insulationdens. ≥ 80 kg/m3th. ≥ 30 mmlenght 50 cm
Steel pipe Ø ≤ 165 mmFEF insulationth. 13 - 19 mm
Copper pipe Ø ≤ 54 mmFEF insulationth. 9 - 25 mm
PP, PVC-U, PVC-C pipeØ ≤ 32 mm
Steel pipe Ø ≤ 40 mmMineral wool insulationdens. ≥ 80 kg/m3
th. ≥ 20 mmlenght 50 cm
Steel pipe Ø ≤ 40 mmFEF insulationth. 13 - 19 mm
Copper pipe Ø ≤ 54 mmMineral wool insulationdens. ≥ 80 kg/m3
th. ≥ 20 mm lenght 50 cm
Pex/Al/Pex pipe Ø ≤ 75 mmFEF insulationth. 9 - 25 mm
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 25 mm
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm both sides
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm both sides
Mineral wooldensity ≥ 40 kg/m3
thickness ≥ 20 mm both sides
Mineral wooldensity ≥ 128 kg/m3
thickness ≥ 25 mm both sides
26
3M™ FIRE BARRIER 3000 WT SEALANT - APPLICATIONSTelecommunication cable - EI90
Maximum opening 410 x 170 mm or d = 298 mm
Steel pipe - EI90 C/U
Maximum opening d = 72 mm
Mineral wooldensity ≥ 64 kg/m3
thickness ≥ 75 mm
3000 WT SEALANTthickness 15 mm
Telecomunication cableØ ≤ 21 mm orbundle Ø ≤ 100 mm
Cable tray - EI90
Insulated steel pipe - EI120 C/U Telecomunication cable - EI120Maximum opening 410 x 170 mm or d = 298 mm
Maximum opening 410 x 170 mm or d = 298 mm Maximum opening 410 x 170 mm or d = 298 mm
Insulated steel pipe - EI90 C/U
Maximum opening 410 x 170 mm or d = 298 mm
Cable tray - EI90 Insulated steel pipe - EI90 C/U
Maximum opening 410 x 170 mm or d = 298 mm Maximum opening 410 x 170 mm or d = 298 mm
Mineral wooldensity ≥ 64 kg/m3
3000 WT SEALANTthickness 7 mm
Steel pipe Ø = 40 mm
Mineral wooldensity ≥ 64 kg/m3
3000 WT SEALANTthickness 15 mm
Cable tray45 x 230 x 1,5 mm
Mineral wooldensity ≥ 64 t kg/m3
hickness ≥ 75 mm
3000 WT SEALANTthickness 15 mm
Steel pipe Ø = 40 - 152 mmGlass wool insulationthickness 25 mm
Mineral wooldensity ≥ 64 kg/m3
thickness ≥ 75 mm
3000 WT SEALANTthickness 15 mm
Steel pipe Ø = 40 - 152 mmFEF insulationthickness 19 mm 3000 WT SEALANT
12,5 mm thickness both sides
Telecomunication cable Ø ≤ 21 bundle Ø ≤ 100 mm
Mineral wooldensity ≥ 64 kg/m3
thickness ≥ 75 mm
3000 WT SEALANT12,5 mm thickness both sides
Steel pipe Ø = 40 - 152 mmMineral wool insulationthickness 25 mm
Mineral wooldensity ≥ 64 kg/m3
thickness ≥ 75 mm3000 WT SEALANT12,5 mm thickness both sides
Cable tray 45 x 230 x 1,5 mm
Mineral wooldensity ≥ 64 kg/m3
thickness ≥ 75 mm
27
K-FLEX K-FIRE SEALANT A PLUS - APPLICATIONSPenetration seal with metal pipe including combustible insulation
Penetration seal with metal pipe including combustible insulation
Penetration seal with metal pipe with stone wool insulation
Rock mineral fibrelayers 50 mm thick
Rock mineral fibrebacking
Mineral fibre backingdensity 110 kg/m3
K-FLEX K-FIRE SEALANT A PLUS 10 mm thick
K-FLEX K-FIRE SEALANT A PLUS 10 mm thick
K-FLEX K-FIRE SEALANT A PLUS
FEF INSULATION thickness 19 mm
FEF INSULATION thickness 19 or 25 mm
STONE WOOL INSULATION thickness 40 mmdensity 140 kg/m3
K-FIRE Sealant A Plus Penetration Seals in Rigid Walls 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
300 x 300
10 mm deep K-FIRE Sealant A Plus flush to both faces of the
wall backed with 130 mm deep Stone
wool (90 kg/m3)
Single mild steel pipe 89 mm diameter and 3 – 14.2 mm wall
Central
EI 120 C/U
Single copper or mild steel pipe 35 mm diameter and 1 – 14.2 mm wall
EI 90 C/U
K-FIRE Sealant A Plus Penetration Seals in Rigid Walls 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
150 diameter
10 mm deep K-FIRE Sealant A Plus flush to both faces of the
wall backed with 130 mm deep Stone
wool (90 kg/m3)
Single mild steel pipe 89 mm diameter and 3 – 14.2
mm wall. Insulation thickness - 25 mmCentral
E 240 C/U EI 120 C/U
150 diameter
10 mm deep K-FIRE Sealant A Plus flush to both faces of the
wall backed with 130 mm deep Stone
wool (90 kg/m3)
Single copper or mild steel pipe 35 mm diameter and 1.2 – 14.2 mm wall with
local (500 mm long) or continuous/interrupted 19 mm thick FEF
insulation
CentralE 240 C/U EI 180 C/U
K-FIRE Sealant A Plus Penetration Seals in Rigid Floors 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
300 diameter
20 mm deep K-FIRE Sealant A Plus flush to both faces of the wall backed with 25
mm deep Stone wool (110 kg/m3)
Steel pipe, diameter 219 mm, wall thickness 8-14.2 mm
CentralE 180 C/C EI 120–C/C
120 diameter
15 mm deep K-FIRE Sealant A Plus flush to both faces of the wall backed with 25
mm deep Stone wool (110 kg/m3)
Copper or steel pipe, diameter 54 mm,
wall thickness 1.2-14.2 mmCentral
E 240 C/C EI 180–C/C
28
K-FLEX K-FIRE HP SEALANT - APPLICATIONSPenetration seal with K-FLEX – K-Fire HP Sealant – Insulated Metallic Pipes
Penetration seal with K-FLEX – K-Fire HP Sealant – Plastic Pipes
Penetration seal with metal pipe with stone wool insulation
Mineral fibre backingdensity 110 kg/m3
K-FLEX K-FIRE HP SEALANT
K-FLEX K-FIRE HP SEALANT
K-FLEX K-FIRE SEALANT A PLUS
STONE WOOL INSULATION thickness 40 mmdensity 140 kg/m3
K-FIRE Sealant A Plus Penetration Seals in Rigid Walls 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
300 x 300
10 mm deep K-FIRE Sealant A Plus flush to both faces of the
wall backed with 130 mm deep Stone
wool (90 kg/m3)
Single mild steel pipe 89 mm diameter and 3 – 14.2 mm wall
Central
EI 120 C/U
Single copper or mild steel pipe 35 mm diameter and 1 – 14.2 mm wall
EI 90 C/U
Penetration Specification
K-FLEX – K-Fire HP Sealant (installed both faces)
Backing Material
Classification
Copper/Steel Pipe ø 60 mm wall thickness 0.8mm -14.2 mm
insulated with 32 mm FEF (CS) Continued Sustained
20 mm annulus x 25 mm deep N/AE120 U/C EI90 U/C
Copper/Steel Pipe ø 15 mm wall thickness 0.8 mm -7 mm
insulated with 13mm ‘FEF (CS) Continued Sustained
15 mm annulus x 25 mm deep N/A EI120 U/C
K-FIRE Sealant A Plus Penetration Seals in Rigid Walls 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
150 diameter
10 mm deep K-FIRE Sealant A Plus flush to both faces of the
wall backed with 130 mm deep Stone
wool (90 kg/m3)
Single mild steel pipe 89 mm diameter and 3 – 14.2
mm wall. Insulation thickness - 25 mmCentral
E 240 C/U EI 120 C/U
150 diameter
10 mm deep K-FIRE Sealant A Plus flush to both faces of the
wall backed with 130 mm deep Stone
wool (90 kg/m3)
Single copper or mild steel pipe 35 mm diameter and 1.2 – 14.2 mm wall with
local (500 mm long) or continuous/interrupted 19 mm thick FEF
insulation
CentralE 240 C/U EI 180 C/U
Penetration SpecificationK-FLEX – K-Fire HP Sealant
(installed both faces)Backing Material
Classification
PVC Pipe 40 mm ø 1.9 mm wall thickness
20 mm annulus x 25 mm deep N/A EI120 C/U
PVC Pipe 25 mm ø 9.2 mm wall thickness
20 mm annulus x 25 mm deep N/A EI60 C/U
PVC Pipe 40 mm ø 1.9 mm wall thickness
20 mm annulus x 25 mm deep N/A EI120 C/U
PVC Pipe 40 mm ø 2 mm wall thickness
20 mm annulus x 25 mm deep N/A EI120 C/U
K-FIRE Sealant A Plus Penetration Seals in Rigid Floors 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
300 diameter
20 mm deep K-FIRE Sealant A Plus flush to both faces of the wall backed with 25
mm deep Stone wool (110 kg/m3)
Steel pipe, diameter 219 mm, wall thickness 8-14.2 mm
CentralE 180 C/C EI 120–C/C
120 diameter
15 mm deep K-FIRE Sealant A Plus flush to both faces of the wall backed with 25
mm deep Stone wool (110 kg/m3)
Copper or steel pipe, diameter 54 mm,
wall thickness 1.2-14.2 mmCentral
E 240 C/C EI 180–C/C
K-FIRE Sealant A Plus Penetration Seals in Rigid Floors 150 mm thick (min.)
Aperture size (mm)
Seal composition
Service(s) Position of service(s)
Classification
300 diameter
20 mm deep K-FIRE Sealant A Plus flush to both faces of the wall backed with 25
mm deep Stone wool (110 kg/m3)
Steel pipe, diameter 219 mm, wall thickness 8-14.2 mm
CentralE 180 C/C EI 120–C/C
120 diameter
15 mm deep K-FIRE Sealant A Plus flush to both faces of the wall backed with 25
mm deep Stone wool (110 kg/m3)
Copper or steel pipe, diameter 54 mm,
wall thickness 1.2-14.2 mmCentral
E 240 C/C EI 180–C/C
29
K-FLEX K-FIRE SEALANT A PLUS - APPLICATIONSLinear joint or gap seal, vertically oriented with sealant to both faces
Linear joint or gap seal, vertically oriented with sealant to the exposed face
Linear joint or gap seal, horizontal linear joint seals, between the head of flexible walls minimum 100 mm thick and rigid floors
K-FLEX K-FIRE SEALANT A PLUS
K-FLEX K-FIRE SEALANT A PLUS
20 mm wide x 10 deep
PE backing Rod 20 mm wide x 15 deep
Mineral rock fibre backing or backing rod
Backing rod
20 mm wide x 25 deep
K-FIRE Sealant A Plus Linear Joint Seals in Rigid Walls 150 mm thick (min.) Sealant flush to both faces of the wall
Substrate Depth Backing Classification
Masonry / concrete
15 mm Polyethylene rod E 240 – V – X – F – W 30 EI 180 – V – X – F – W 30
10 mm Polyethylene rodE 240 – V – X – F – W 20 EI 180 – V – X – F – W 20
Masonry / concrete to
steel
10 mm Polyethylene rodE 240 – V – X – F – W 30 EI 90 – V – X – F – W 30
25 mm50 mm Rockwool RW4
Stone woolEI 240 – V – X – F – W 50
Masonry / concrete to
timber
20 mm Polyethylene rod EI 120 – V – X – F – W 30
15 mmRockwool RW4 Stone
wool, 120 mm deep min. EI 180 – V – X – F – W 30
Timber/ Concrete
25 mm50 mm Rockwool RW4
Stone wool EI 120 – V – X – F – W 50
K-FIRE Sealant A Plus Linear Joint Seals in Rigid Walls 100 mm thick (min.) – Sealant flush to both faces of the wall
Substrate Depth Backing Classification
Masonry / concrete
15 mm Polyethylene rod E 240 – V – X – F – W 00 to 30 EI 120 – V – X – F – W 00 to 30
Substrate Depth Backing Classification
plasterboard / concrete
25 mm 50 mm steel head trackEI 120 – T – X – F – W 20
10 mm15 mm PE backer plus 50 mm steel head track
30
K-FLEX K-FIRE SEALANT S PLUS - APPLICATIONSLinear joint or gap seal, vertically oriented with sealant to the one face (either)
Linear joint or gap seal, between floor slabs or between floor slab and wall with sealant to the top face of the floor only
Linear joint or gap seal, vertically oriented with sealant to both faces
Linear joint or gap seal, between floor slabs or between floor slab and wall with sealant to both faces
Backing rod
Mineral rock fibre backing
Mineral rock fibre backing or backing rod
Backing rod
K-FLEX K-FIRE SEALANT S PLUS
K-FLEX K-FIRE SEALANT S PLUS
K-FLEX K-FIRE SEALANT S PLUS
K-FLEX K-FIRE SEALANT S PLUS
K-FIRE Sealant A Plus Linear Joint Seals in Rigid Walls 150 mm thick (min.) Sealant flush to both faces of the wall
Substrate Depth Backing Classification
Masonry / concrete
15 mm Polyethylene rod E 240 – V – X – F – W 30 EI 180 – V – X – F – W 30
10 mm Polyethylene rodE 240 – V – X – F – W 20 EI 180 – V – X – F – W 20
Masonry / concrete to
steel
10 mm Polyethylene rodE 240 – V – X – F – W 30 EI 90 – V – X – F – W 30
25 mm50 mm Rockwool RW4
Stone woolEI 240 – V – X – F – W 50
Masonry / concrete to
timber
20 mm Polyethylene rod EI 120 – V – X – F – W 30
15 mmRockwool RW4 Stone
wool, 120 mm deep min. EI 180 – V – X – F – W 30
Timber/ Concrete
25 mm50 mm Rockwool RW4
Stone wool EI 120 – V – X – F – W 50
K-FIRE Sealant S Plus Linear Joint Seals in Rigid Walls 150 mm thick (min.) – Sealant on One Side of the Seal Only (Either)
Substrate Depth Backing Classification
Masonry / concrete
15 mm Polyethylene rodE 240 – V – X – F – W 00 to 25 EI 120 – V – X – F – W 00 to 25
10 mm Polyethylene rodE 240 – V – X – F – W 00 to 15 EI 180 – V – X – F – W 00 to 15
K-FIRE Sealant S Plus Linear Joint Seals in Rigid Floors 150 mm thick (min.) – Sealant to the top of the floor only
Substrate Depth Backing Classification
Masonry / concrete
2:1 Ratio Width to Depth 25 mm Stone wool
90 kg/m3
E 240 – H – X – F – W 20 to 40 EI 120 – H – X – F – W 20 to 40
10 mmE 240 – H – X – F – W 00 to 20 EI 180 – H – X – F – W 00 to 20
K-FIRE Sealant A Plus Linear Joint Seals in Rigid Walls 100 mm thick (min.) – Sealant flush to both faces of the wall
Substrate Depth Backing Classification
Masonry / concrete
15 mm Polyethylene rod E 240 – V – X – F – W 00 to 30 EI 120 – V – X – F – W 00 to 30
K-FIRE Sealant S Plus Linear Joint Seals in Rigid Walls 150 mm thick (min.) – Sealant flush to both faces of the wall
Substrate Depth Backing Classification
Masonry / concrete
2:1 Ratio Width to Depth
Polyethylene rod EI 240 – V – X – F – W 20 to 40
25 mm 25 mm Stone wool 90 kg/m3 EI 240 – V – X – F – W 0 to 40
10 mm 15 mm Stone wool 90 kg/m3 EI 240 – V – X – F – W 0 to 15
K-FIRE Sealant S Plus Linear Joint Seals in Rigid Floors 150 mm thick (min.) – Sealant to the top of the floor only
Substrate Depth Backing Classification
Masonry / concrete
2:1 Ratio Width to Depth
Polyethylene rodEI 180 – H – X – F – W 20 to 40
20 mm EI 240 – H – X – F – W 00 to 40
Substrate Depth Backing Classification
plasterboard / concrete
25 mm 50 mm steel head trackEI 120 – T – X – F – W 20
10 mm15 mm PE backer plus 50 mm steel head track
31
A single pack material that, when mixed with water, provides a fire resistant and smoke seal able to reinstate fire resistance of separating walls and floors when penetrated by building services.
- Safe: free of fibres, silica and halogens;- Up to 4 hours fire resistance (integrity and insulation);- Can be used in wall and floor penetrations to accommodate a variety of penetrating services;- Easy to use: can be applied by trowel or poured into position;- Does not require specialist equipment. Simple mixing and application tools can be used and cleaned with water;- Does not shrink on setting and provides a rigid, gas-tight barrier to smoke, combustion gasses and halon gas.
K-FLEX K-FIRE MORTAR APPLICATIONS
Ensure contact surfaces within the opening and services are clean, and free of grease and loose material.Gradually add K-FLEX MORTAR to clean water in a container while stirring manually or mechanically. Continue mixing until a smooth, lump-free consistency is obtained.Recommended mix ratios are as follows:Pouring into floor openings: 2 1/2 :1 (Water by volume)Stiff, but trowellable, into wall openings: 3 : 1 (Water by volume)The pot life and setting time depends on the size of mix; the amount of water used and ambient/water temperatures. Typical set times are between 45 and 90 minutes.
CE Marked 0843–CPR–0277ETA 15-0757ETAG 026-2 (2011) according EN 1366-3 Penetration Seals
INSTALLATION
APPROVALS
K-FLEX K-FIREMORTAR
K-FLEX K-FIRE MORTAR
32
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE MORTAR
Property Value Test method
Fire Rating Up to EI 240 EN 1366-3
Tested penetration seal inFlexible walls: min. thickness 100 mm;Rigid walls: min. thickness of 100 mm;Rigid floors: min. thickness of 150 mm;
Tested service penetration
- PVC-U pipes up to Ø 200mm;- PE pipes up to Ø 55mm;
- ABS pipes up to Ø 55mm;- SAN+PVC pipes up to Ø 55mm;
- Copper pipes up to Ø93mm;- Copper pipes up to Ø93mm + FEF / MW insulation;
- Steel pipes up to Ø194mm;- Steel pipes up to Ø194mm + FEF insulation;
- Single cables up to Ø80mm;- Cable bundles up to Ø 100mm;- Cable trays up to 300x25mm;
- Perforated steel trays up to 500x60mm
*FEF: Flexible Elastomeric Foam*MW: Mineral Wool
Durability and serviceabilityType Y2: intended for use at temperature below 0°C, with no exposure
to rain nor UV. Includes lower use categories.EOTA TR 024:2009
Density Approximately 860 kg/m3 one month after application
Thermal Conductivity < 0.3 W /m K
Shelf life 6 months
Ecological data Free of fibers, silica and halogens
TECHNICAL DATA
K-FLEX K-FIRE MORTAR
Type Item/Box Code Bar Code
K-FLEX K-FIRE MORTAR - 20 kg bag 1 850VR020653 8027409727392
K-FLEX K-FIRE MORTAR - 10 kg bag 1 850VR020654 8027409727408
RANGE
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
K-FLEX K-FIRE MORTAR
K-F
LEX
K-F
IRE
MO
RTA
R
33
K-FLEX FIRE EX MORTAR is a gypsum based mortar material, used to reinstate the fire resistance performance of wall and floor constructions where they have been provided with apertures for the penetrations of multiple services. When mixed with water, the compounds form a highly thermally insulating fire sealing compound to prevent the spread of fire and smoke through openings in fire rated walls and floors, including openings formed around building service penetrations. K-FLEX FIRE EX MORTAR will also maintain the acoustic design performance in walls and floors. K-FLEX FIRE EX MORTAR expands approx. 1% by hydraulic action during curing ensuring a very tight seal around the service penetrations and the surrounding opening apertures.
K-FLEX FIRE EX MORTAR may be used to offer a penetration seal with cables, cable trays, plastic pipes, composite pipes and metallic pipes with and without insulation- Up to 4 hours fire resistance (integrity and insulation);- Can be used in wall and floor penetrations to accommodate a variety of penetrating services;- Easy to use: can be applied by trowel or poured into place;- Does not need specialist equipment: simple mixing and application tools can be used and cleaned with water;- Does not shrink on setting and provides a rigid, gas-tight barrier to smoke, combustion and halogen gasses.
K-FLEX FIRE EX MORTAR APPLICATIONS
The mortar must be mixed to a thick but fluid mass at a rate of approx. 2 parts of powder to 1 part water. Maximum loadbearing performance will be achieved 28 days after casting.
CE Marked 0843–CPR–0251ETA 15-0261ETAG 026-2 (2011) according EN 1366-3 Penetration Seals
INSTALLATION APPROVALS
K-FLEX FIREEX MORTAR
K-FLEX FIRE EX MORTAR
34
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX FIRE EX MORTAR
Property Value Test method
Fire Rating Up to EI 240 EN 1366-3
Tested penetration seal inFlexible walls: min. thickness 100 mm;Rigid walls: min. thickness of 150 mm;Rigid floors: min. thickness of 150 mm.
Tested service penetration
- PVC-U pipes up to Ø315mm;- PVC pipe bundles up to Ø32mm;
- PE pipes up to Ø160mm;- PE pipe bundles up to Ø32mm;
- ABS pipe bundles up to Ø32mm;- SAN+PVC pipe bundles up to Ø32mm;
- PP pipes up to Ø75mm;- PP pipe bundles up to Ø32mm;
- Geberit Mepla pipes up to Ø75mm + FEF / MW insulation;- Alupex pipes up to Ø75mm;
- Alupex pipes up to Ø75mm + FEF / AESW insulation;- Copper pipes up to Ø54mm + FEF / MW insulation;
- Steel pipes up to Ø165 mm + FEF insulation;- Steel pipes up to Ø219 mm + MW insulation;
- Single cables up to Ø80mm;- Cable bundles up to Ø 100mm;- Steel cable trays and ladders;
- Metal or plastic conduits up to Ø16mm;- Blank seals up to 2400x1200mm.
*FEF: Flexible Elastomeric Foam*MW: Mineral Wool
*AESW: Alkaline earth silicate wool
Durability and serviceabilityType Z2: Intended for uses in internal conditions, excluding temperature
below 0°C, without exposure to rain or UV. EOTA TR 024:2009
Reaction to fire A1 EN 13501-1Storing temperature 5 to 30 °CDensity About 900 kg/m3 after full cureThermal conductivity 0.051 W/mKCure rate Up to 30 days depending on thickness and temp.Tack free time Less than 1 hour depending on the local climateShelf life 6 monthsAcoustic performances 64 dBEcological data EMICODE emission class EC 1PLUS
TECHNICAL DATA
K-FLEX FIRE EX MORTAR
K-F
LEX
FIR
E E
X M
OR
TA
R
K-FLEX FIRE EX MORTAR
Type Item/Box Code Bar Code
K-FLEX FIRE EX MORTAR - 20 kg bag 1 850VR020658 8027409727767
RANGE
DOCUMENTATION PDF
> ETA < > TDS < > MSDS <
35
K-FLEX MORTAR / EX MORTAR- APPLICATIONSElectrical cable - EI180
Pex/Al/Pex insulated pipe - EI180 Plastic pipe - EI120
Electrical cable - EI60 Cable tray - EI60
Electrical cable - EI90
Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 50 mm
Pex/Al/Pex pipeØ ≤ 75 mmMineral wool insulationth.≥ 20 mm dens.≥ 80 kg/m3 lenght≥ 50 cm both sides
PE, ABS,SAN+PVC & PP,PVC-U & PVC-C pipeØ ≤ 40 mm
CableØ ≤ 21 mm,bundle Ø ≤ 100 mmconduit Ø ≤ 16 mm
K-FLEX FIRE EX MORTARthickness ≥ 150 mm
Telecomunication cableØ ≤ 21 mm, bundle Ø ≤ 100 mmor conduit Ø ≤ 16 mm
K-FLEX FIRE EX MORTARthickness ≥ 50 mm
K-FLEX FIRE EX MORTARthickness ≥ 50 mm
Cable Ø ≤ 80 mm,bundle Ø ≤ 24 mmconduit Ø ≤ 16 mm cable tray
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Mineral wooldensity 150 ≥ kg/m3
thickness 50 mm
Mineral wooldensity 150 ≥ kg/m3
thickness 50 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm K-FLEX FIRE EX MORTAR
thickness ≥ 100 mm
Electrical cableØ ≤ 50 mm, bundleØ ≤ 16 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
Cable tray - EI120 Insulated steel pipe - EI120
Cable Ø ≤ 21 mm,bundles Ø ≤ 100 mm,cable tray
Steel pipe Ø ≤ 219 mmMineral wool insulationgr. ≥ 30 mm dens. ≥ 80 kg/m3
lenght ≥ 100 cm both sides
K-FLEX K-FIRE MORTAR / K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
36
K-FLEX MORTAR / EX MORTAR - APPLICATIONSInsulated steel pipe- EI120
Maximum opening 1200 x 2400 mm
Plastic pipe - EI120
Maximum opening 1200 x 2400 mm
PVC-U, PVC-C,PE, ABS, SAN+PVC & PP pipe Ø ≤ 32 mm
Steel pipeØ ≤ 219 mmMineral wool insulationth ≥ 30 mm dens ≥ 80 kg/m3 lenght ≥ 100 cm both sides
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
K-FLEX FIRE EX MORTARthickness ≥ 100 mm
Pex/Al/Pex pipe - EI60
Electrical Cable - EI90 Insulated steel pipe - EI120Maximum opening 1200 x 2400 mm
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
K-FLEX FIRE EX MORTARthickness ≥ 25 mmboth sides
K-FLEX FIRE EX MORTARthickness ≥ 25 mmboth sides
K-FLEX FIRE EX MORTARthickness ≥ 25 mmboth sides
K-FLEX FIRE EX MORTARthickness ≥ 25 mmboth sides
Pex/Al/Pex pipeØ ≤ 75 mmFEF Insulationthickness 32 mm lenght≥ 60 cm both sides
Cable Ø ≤ 21 mmconduit Ø ≤ 16 mm
Steel pipe Ø ≤ 40 mmMineral wool insulationth. ≥ 20 mm dens. ≥ 80 kg/m3 lenght≥ 50 cm both sides
PVC-U, PVC-C, PE, ABS,SAN+PVC & PP pipeØ ≤ 32 mm
Pex/Al/Pex pipe Ø ≤ 75 mmminerall wool insulationth. ≥ 20 mm dens. ≥ 80 kg/m3 lenght ≥ 50 cm both sides
K-FLEX FIRE EX MORTARthickness ≥ 50 mm
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Cable tray - EI120
Maximum opening 1200 x 2400 mm
K-FLEX K-FIRE MORTARthickness ≥ 25 mmboth sides
Cable Ø ≤ 21 mm,bundles Ø ≤ 100 mm,cable tray
Mineral wooldensity ≥ 150 kg/m3
thickness ≥ 50 mm
Pex/Al/Pex insulated pipe - EI120 Pex/Al/Pex insulated pipe - EI120
Maximum opening 1200 x 2400 mm Maximum opening 1200 x 2400 mm
37
3M Flexible Wrap Systems address a variety of application needs including air ducts, grease ducts, chemical exhaust ducts and plenum. They are also excellent for oil and gas refineries and other industrial applications. The insulative properties help keep heat, fire and smoke contained. Manufactured with a man-made vitreous spun fibre,a calcium-magnesium silicate (CMS) wool technology which is bio-soluable, allowing for low thermal transfer properties in a lightweight, low profile, easy to apply product.
3M™ DUCT WRAP 615+
APPLICATIONS
DOP NO 3M FB DW 615+ 1121-CPR-NA5000
- Zero clearance to combustible throughout the entire enclosure system.- High flexibility for installation ease.- Foil encapsulated for blanket protection, less dust, and high wrap strength.- Wide range of penetration seal systems.- Blanket adhered to foil scrim helps prevent wrap from slumping.
PRODUCT FEATURES
APPROVALS
DUCT WRAP 615+ WT
- Vertically oriented insulated ventilation duct;- Horizontally oriented insulated ventilation duct;
3M™ FIRE BARRIER DUCT WRAP 615+
38
K-FLEX reserves the right to change data and technical requirements without notice.
K-FLEX K-FIRE HP SEALANT
Property Value Test method
Fire Rating Up to EI 240 S EN 1366-1
Roll Width 609 mm
Roll Length 7 602 mm
Density 96 kg/m3
Roll Weight 4.38 kg/m2
Thickness 38 mm
TECHNICAL DATA
K-FLEX K-FIRE HP SEALANT
Type Roll size Code
3M™ FIRE BARRIER DUCT WRAP 615+ 0.61 x 7.62 m 850VR020634
RANGE
DOCUMENTATION PDF
> DOP <
3M™ FIRE BARRIER DUCT WRAP 615+
3M™
FIR
E B
AR
RIE
R D
UC
T W
RA
P 6
15
+
INSTALLATION TECHNIQUES
Telescoping Overlap Wrap
1. 3M™ FIRE BARRIER DUCT WRAP 615+.
2. Metal band - width min 12.7 mm.
3. 100 mm overlap.
Checkerboard Overlap Wrap
1. 3M™ FIRE BARRIER DUCT WRAP 615+.
2. Metal band - width min 12.7 mm.
3. 100 mm overlap.
Butt Joint with Collar
1. 3M™ FIRE BARRIER DUCT WRAP 615+.
2. Metal band - width min 12.7 mm.
3. 200 mm overlap.
4. Tightly butted joint
> ETA <
39
K-FLEX NAME PRODUCT
CONTACT DETAIL
Scan QRCODE to find Your local K-FLEX Representative K-FLEX K-FIRE Distributor
INT_
BR
O_K
-FIR
E_V1
_111
6
K-FLEX K-FIRE
K-FLEX POLSKA Sp. z o.o. Pucka 112 - 81-154 Gdynia, Polandtel.: +48 632880200 - fax: +48 632880236 e-mail: [email protected] www.K-FLEX.pl
K-FLEX K-FIREf i r e s t o p p i n g s o l u t i o n s