Page 1: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

The Most Informative Home Inspection Experience.

Jason Chow

123 90s Home

Calgary, AB

SAMPLE REPORT FOR CLIENT

Monday, December 1, 2014

JChow Home Inspection

177 Cramond Close SE

Calgary, AB T3M1C2

403-606-4546

[email protected]

Page 2: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

February 10, 2017

Dear Sample Report For Client,

RE: Report No. 1003, v.4123 90s HomeCalgary, AB

Thanks very much for choosing us to perform your home inspection. The inspection itself and the attached report complywith the requirements of the Standards of Practice of our national Association. This document defines the scope of ahome inspection.

Clients sometimes assume that a home inspection will include many things that are beyond the scope. We encourageyou to read the Standards of Practice so that you clearly understand what things are included in the home inspection andreport.

The report has been prepared for the exclusive use of our client. No use by third parties is intended. We will not beresponsible to any parties for the contents of the report, other than the party named herein .

The report is effectively a snapshot of the house, recording the conditions on a given date and time. Home inspectorscannot predict future behavior, and as such, we cannot be responsible for things that occur after the inspection. Ifconditions change, we are available to revisit the property and update our report.

The report itself is copyrighted, and may not be used in whole or in part without our express written permission.

Again, thanks very much for choosing us to perform your home inspection.

Sincerely,

Jason Chowon behalf ofJChow Home Inspection

JChow Home Inspection177 Cramond Close SE

Calgary, AB T3M1C2403-606-4546

[email protected]

Page 3: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

SUMMARY

This Summary outlines potentially significant issues from a cost or safety standpoint. This section is provided as acourtesy and cannot be considered a substitute for reading the entire report. Please read the complete document.

Priority Maintenance Items

Plumbing

WASTE PLUMBING \ Drain piping - performanceCondition: LeakLeak from main floor bathtub drain connection. Ceiling tile was removed to view drain connection, as thermal imagingcamera indicated a wet/moist spot.Implication(s): Sewage entering the buildingLocation: First Floor BathroomTask: RepairTime: Immediate

1. Leak

FIXTURES AND FAUCETS \ Basin, sink and laundry tubCondition: LeakLeak from Ensuite Sink Drain connection. Recommend repairing to prevent water damage to cabinetry and interiorfinish.Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the buildingLocation: First Floor BathroomTask: Repair or replaceTime: Immediate

2. Leak

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 1 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 4: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

SUMMARY

FIXTURES AND FAUCETS \ BathtubCondition: LeakLeak from Second Floor Bathtub. Moisture is concentrated above ceiling fan in kitchen, no visible moisture staining onthe ceiling, but was very visible with thermal imaging camera.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Second Floor BathroomTask: CorrectTime: Immediate

3. Leak

This concludes the Summary section.

The remainder of the report describes each of the home's systems and also details any recommendations we have forimprovements. Limitations that restricted our inspection are included as well.

The suggested time frames for completing recommendations are based on the limited information available during apre-purchase home inspection. These may have to be adjusted based on the findings of specialists.

Home Improvement - ballpark costs

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 2 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 5: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

ROOFING

Description

Sloped roofing material:Asphalt shingles

4. Asphalt shingles

Sloped roof flashing material: Metal

Limitations

Inspection performed: By walking on roof

Recommendations

SLOPED ROOFING \ Asphalt shingles1. Condition: Exposed fastenersVarious shingles were nailed on the surface of the shingle, where it does not overlap. This can be a cause of water entryand leakage. Recommend correcting, and sealing with roof tar.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Front ExteriorTask: CorrectTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 3 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 6: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

ROOFING

5. Exposed fasteners 6. Exposed fasteners

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 4 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 7: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

EXTERIOR

Description

Gutter & downspout material: Aluminum

Gutter & downspout type: Eave mounted

Wall surfaces and trim: Vinyl siding

Driveway: Concrete

Deck: Raised Pressure-treated wood

Exterior steps: Concrete

Fence:Metal

Metal Chain Link Fence

Limitations

Upper floors inspected from: Ground level

Exterior inspected from: Ground level

Recommendations

ROOF DRAINAGE \ Downspouts2. Condition: Downspouts end too close to buildingFront downspout extension is missing. Extension tube should discharge 6-10 feet away from home to ensure water isdirected away.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Front ExteriorTask: ImproveTime: Regular maintenance

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 5 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 8: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

EXTERIOR123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 6 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 9: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

EXTERIOR

7. Downspouts end too close to building

WALLS \ Soffits and fascia3. Condition: Loose or missing piecesFascia Cladding has been torn/blown off. Section of soffit has been dislodged, and can allow rodents/pests to enter atticarea.Implication(s): Cosmetic defects | Chance of water damage to contents, finishes and/or structure | Chance of pestsentering buildingLocation: Various Exterior WallTask: Repair or replaceTime: Regular maintenance

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 7 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 10: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

EXTERIOR

8. Loose or missing pieces 9. Loose or missing pieces

10. Loose or missing pieces

WALLS \ Trim4. Condition: Caulking missing or deterioratedExterior wall penetrations should be caulked to prevent water entry.Implication(s): Chance of water damage to contents, finishes and/or structure | Material deteriorationLocation: Rear Exterior WallTask: CorrectTime: Regular maintenance

11. Caulking missing or deteriorated 12. Caulking missing or deteriorated

WALLS \ Vinyl siding5. Condition: Mechanical damage

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 8 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 11: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

EXTERIOR

Vinyl siding appears to be damaged from hail storm(s). Recommend patching or replacing siding to prevent water entryinto wall.Implication(s): Cosmetic defects | Chance of water damage to contents, finishes and/or structureLocation: Various Exterior WallTask: Repair or replace

13. Mechanical damage 14. Mechanical damage

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 9 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 12: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

STRUCTURE

Description

Configuration: Basement

Foundation material: Poured concrete

Floor construction: Wood I-joists Steel columns Built-up wood beams Subfloor - OSB (Oriented Strand Board)

Exterior wall construction: Wood frame

Roof and ceiling framing:Trusses

15. Trusses

Plywood sheathing

Limitations

Inspection limited/prevented by: New finishes/paint Insulation

Percent of foundation not visible: 80 %

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 10 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 13: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

ELECTRICAL

Description

Service entrance cable and location:Overhead

16. Overhead

Service size: 100 Amps (240 Volts)

Main disconnect/service box rating: 125 Amps

Main disconnect/service box type and location: Breakers - basement

System grounding material and type: Copper - water pipe and ground rod

Distribution panel type and location:Breakers - basement

17. Breakers - basement 18. Breakers - basement

Distribution wire material and type: Copper - non-metallic sheathed Copper - metallic sheathed

Type and number of outlets (receptacles): Grounded - typical

Circuit interrupters: Ground Fault (GFCI) & Arc Fault (AFCI): GFCI - bathroom GFCI - outside

Smoke detectors:Present

Recommend replacing old smoke detectors if 10 years or older, recommend replacement with combination Smoke/CODetector(s)

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 11 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 14: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

ELECTRICAL

19. Present 20. Present

Recommendations

SERVICE BOX, GROUNDING AND PANEL \ Panel wires6. Condition: OverheatingLoose connection at breaker, Breaker #14. Wire is overheating and the connection may be loose at the breaker.Implication(s): Fire hazardLocation: Basement Furnace RoomTask: CorrectTime: Immediate

21. Overheating

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 12 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 15: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

HEATING

Description

Fuel/energy source: Gas

System type: Furnace Boiler

Furnace manufacturer:Lennox

22. Lennox 23. Lennox

24. Lennox

Heat distribution: Ducts and registers

Approximate capacity: 75,000 BTU/hr

Efficiency: Mid-efficiency

Exhaust venting method: Direct vent

Approximate age: 18 years

Main fuel shut off at: Basement

Supply temperature: Basement slab is heated with boiler, coverage of basement living room, bedrooms and bathroomwere confirmed to be very functional.

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 13 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 16: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

HEATING

25. 

Chimney liner: Metal

Limitations

Safety devices: Not tested as part of a building inspection

Heat exchanger: Only a small portion visible

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 14 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 17: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

INSULATION AND VENTILATION

Description

Attic/roof insulation material:Glass fiber

26. Glass fiber

Attic/roof insulation amount/value: R-28

Attic/roof ventilation: Roof and soffit vents

Attic/roof air/vapor barrier: Plastic

Wall insulation material: Glass fiber

Wall insulation amount/value: R-20

Wall air/vapor barrier: Plastic

Foundation wall insulation material: Glass fiber

Foundation wall insulation amount/value: R-12

Foundation wall air/vapor barrier: Plastic

Limitations

Attic inspection performed: From access hatch

Air/vapor barrier system: Continuity not verified

Recommendations

ATTIC/ROOF \ Insulation7. Condition: Gaps or voidsGarage attic area is sparingly insulated, as visible from thermal imaging. If a furnace will be installed in the garage, Irecommend insulating the entire attic area to improve energy efficiency and to prevent condensation/frost.Implication(s): Increased heating and cooling costs | Reduced comfortLocation: GarageTask: ImproveTime: If necessary

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 15 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 18: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

INSULATION AND VENTILATION

27. Gaps or voids

ATTIC/ROOF \ Hatch8. Condition: Not weatherstrippedAttic Hatch is not weather-stripped, and can allow a significant amount of warm moist air to escape into the attic.Implication(s): Chance of condensation damage to finishes and/or structure | Increased heating and cooling costsLocation: First FloorTask: ImproveTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 16 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 19: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

INSULATION AND VENTILATION

28. Not weatherstripped

WALLS \ Insulation9. Condition: Sagging or voidsInsulation missing under basement bedroom window.Implication(s): Increased heating and cooling costs | Reduced comfortLocation: Basement Living RoomTask: ImproveTime: When remodelling

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 17 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 20: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

INSULATION AND VENTILATION

29. Sagging or voids

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 18 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 21: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

Description

Water supply source: Public

Service piping into building: Plastic

Supply piping in building:Polybutylene (PB)

Polybutylene supply plumbing present. This is now a discontinued product, due to prior failures in the past. All fixtureswere tested, tubs and sinks filled/drained multiple times, and no issues were present.

30. Polybutylene (PB)

Main water shut off valve at the: Meter

Water flow and pressure: Functional

Water heater fuel/energy source: Gas

Water heater type: Conventional

Water heater exhaust venting method: Natural draft

Water heater manufacturer:Rheem

31. Rheem 32. Rheem

Tank capacity: 40 gallons

Water heater approximate age: 18 years

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 19 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 22: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

Typical life expectancy: 8 to 12 years

Water heater failure probability: High

Waste and vent piping in building: ABS plastic

Pumps:Sump pump

Sump and Pump present, tested and is functional.

33. Sump pump

Floor drain location: Near heating system

Main fuel shut off valve at the: Gas meter

Exterior hose bibb: Present Frost proof

Limitations

Items excluded from a building inspection: Isolating/relief valves & main shut-off valve Water heater relief valvesare not tested

Recommendations

WATER HEATER \ Life expectancy10. Condition: High failure probabilityWater heater is close to 18 years old, and has began leaking from the drain valve during the home inspection.Implication(s): No hot waterLocation: Basement Furnace RoomTask: ReplaceTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 20 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 23: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

34. High failure probability

WATER HEATER \ Tank11. Condition: Hot/Cold Supply lines are plastic from the hot water tank. In/Out supply lines should be 16-20" copper, due to the higher temperature from the top of the tank.Location: Basement Furnace RoomTask: Repair or replaceTime: Immediate

35. 

WASTE PLUMBING \ Drain piping - performance12. Condition: LeakLeak from main floor bathtub drain connection. Ceiling tile was removed to view drain connection, as thermal imagingcamera indicated a wet/moist spot.Implication(s): Sewage entering the buildingLocation: First Floor BathroomTask: RepairTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 21 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 24: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

36. Leak

WASTE PLUMBING \ Drain piping - installation13. Condition: Defective ABS pipingABS with Flexible hose drain connection has cracked. This may allow waste water to leak into basement.Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the buildingLocation: Basement Furnace RoomTask: Repair or replaceTime: Immediate

37. Defective ABS piping

FIXTURES AND FAUCETS \ Basin, sink and laundry tub14. Condition: LeakLeak from Ensuite Sink Drain connection. Recommend repairing to prevent water damage to cabinetry and interiorfinish.Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the buildingLocation: First Floor BathroomTask: Repair or replaceTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 22 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 25: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

38. Leak

FIXTURES AND FAUCETS \ Faucet15. Condition: Drip, leakLeak/Drip from kitchen sprayer hose faucet. Recommend replacing to prevent water damage to interior finishes andcabinetry.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: First Floor KitchenTask: Repair or replaceTime: Regular maintenance

39. Drip, leak

FIXTURES AND FAUCETS \ Toilet16. Condition: LeakLeak from Toilet Tank, and is spilling onto floor/wall when toilet is flushed.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Basement BathroomTask: Repair or replaceTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 23 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 26: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

40. Leak

17. Condition: LooseBasement Toilet is Loose/Wobbles. This can compress the wax seal, and cause the toilet to leak around the base.Implication(s): Chance of water damage to contents, finishes and/or structure | Sewage entering the buildingLocation: Basement BathroomTask: CorrectTime: Immediate

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 24 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 27: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

PLUMBING

41. Loose

FIXTURES AND FAUCETS \ Bathtub18. Condition: LeakLeak from Second Floor Bathtub. Moisture is concentrated above ceiling fan in kitchen, no visible moisture staining onthe ceiling, but was very visible with thermal imaging camera.Implication(s): Chance of water damage to contents, finishes and/or structureLocation: Second Floor BathroomTask: CorrectTime: Immediate

42. Leak

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 25 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 28: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

INTERIOR

Description

Major floor finishes: Carpet Laminate

Major wall finishes: Plaster/drywall

Major ceiling finishes: Plaster/drywall Stucco/texture/stipple

Glazing: Double

Exterior doors - type/material: Plastic/fiberglass

Appliances: Refrigerator Range hood Dishwasher

Limitations

Inspection limited/prevented by: Carpet Storage/furnishings

Appliances: Self-cleaning features on ovens not tested Effectiveness of dishwasher drying cycle not tested

Garage door opener: Steel-Craft Opener, Manufactured by Chamberlain.

43.  44. 

Recommendations

GARAGE \ Vehicle doors19. Condition: Rusted or dentedGarage Vehicle door is dented, and appears to have been pushed by a vehicle. Garage door was tested, and stilloperates.Implication(s): Material deteriorationLocation: Front ExteriorTask: Repair or replaceTime: When remodelling

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 26 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 29: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

INTERIOR

45. Rusted or dented

APPLIANCES \ Dryer20. Condition: Dryer vent obstructedClean dryer vent to prevent blockage. Damper is stuck open due to lint, and can allow cold air, insects/rodents to enter.Implication(s): Equipment ineffective | Fire hazardLocation: Rear Exterior WallTask: CleanTime: Regular maintenance

46. Dryer vent obstructed

END OF REPORT

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 27 of 28

SUMMARY ROOFING EXTERIOR STRUCTURE ELECTRICAL HEATING INSULATION PLUMBING INTERIOR REFERENCE

Page 30: JChow Home Inspections Sample Report · The Most Informative Home Inspection Experience. Jason Chow 123 90s Home Calgary, AB SAMPLE REPORT FOR CLIENT Monday, December 1, 2014 JChow

REFERENCE LIBRARY

The links below connect you to a series of documents that will help you understand your home and how it works. Theseare in addition to links attached to specific items in the report.

Click on any link to read about that system.

01. ROOFING, FLASHINGS AND CHIMNEYS

02. EXTERIOR

03. STRUCTURE

04. ELECTRICAL

05. HEATING

06. COOLING/HEAT PUMPS

07. INSULATION

08. PLUMBING

09. INTERIOR

10. APPLIANCES

11. LIFE CYCLES AND COSTS

12. SUPPLEMENTARY

Asbestos

Radon

Urea Formaldehyde Foam Insulation (UFFI)

Lead

Carbon Monoxide

Mold

Household Pests

Termites and Carpenter Ants

13. HOME SET-UP AND MAINTENANCE

14. MORE ABOUT HOME INSPECTIONS

123 90s Home, Calgary, AB December 1, 2014 www.jchi.ca

Providing great home inspections for every client every time

Report No. 1003, v.4

Page 28 of 28