itc maurya,new delhi - uvka · 2017-04-28 · itc maurya, new delhi acknowledged as the preferred...
TRANSCRIPT
ITC Maurya, New Delhi
Acknowledged as the preferred residence of visiting heads of state and global business
leaders for over 25 years – ITC Maurya epitomizes the luxury hotel experience. The
Hotel has started its operation in the year 1977.
The Maurya is a luxury business hotel with modern and contemporary facilities, located
in the heart of the exclusive Diplomatic Enclave, approximately 14 k.m. (25 min) from
the International Airport; offering a superb view of Delhi’s green belt – the forested
ridge.
Named after the Mauryan Dynasty of the 3rd century, B.C. it is an imposing structure of
superb luxury with 440 Rooms, inclusive of 29 uniquely designed Suites. The striking
pyramidal architecture of the hotel inspired by the Buddhist stupas and ambiance are a
tribute to the age of the great Mauryan Dynasty, which gave Indian history its golden era.
The hotel offers a bouquet of room categories; the Executive Club, pioneers a tradition
in corporate hospitality, the Towers, presents eight luxurious floors of elegance and
tranquility, the Luxury Room, Combines the best of luxury, space and service standards
& the ITC One, our premium room category offers magnificent decor, impeccable
service & the latest in modern conveniences / amenities. Behind the lavishness is a crisp
efficiency and a deep understanding of the needs of “The discerning Global Traveller
“.The hotel has 07 food and beverage outlets in the building.
The total area of the hotel is 6 acres; air-conditioned area being 41283 sq meters and total
built up area 55044 sq meters. Temperature maintained through out the air-conditioned
space is 22 degree. The connected load of the hotel is approximately 4657 KW.
AWARDS & ACCOLADES
Energy Conservation Award 2006-07 awarded by BEE Government of India.
National Tourism Award 2006-07 – Best Eco-Friendly Hotel Awarded by National
tourism Department Government of India
ITC Hotels awarded the PATA green Gold award 2005 in Corp. Environment category.
“Greentech Safety Platinum Award” for the year 2003-04 amongst ‘Services Sector’ for
outstanding achievement in EHS Management, from the Greentech Foundation.
“Greentech Safety Gold Award” for the year 2002-03 amongst ‘Services Sector’ for
excellence in EHS Management, from the Greentech Foundation.
“Environment Champion Hotel of the Year 2002” (among Large Hotels) across the
country by the Federation of Hotel & Restaurant Association of India (FHRAI).
IH & RA Environment Award 2002 (Corp. Category) - Runners Up,
for: "Energy and Indoor Air Quality in Hotels & Restaurants".
Golden Peacock Environment Award 2001 (Category : Large Service Industry) from
World Environment Foundation, U.K.
Best Green Hotel for the year 2000 from Pacific Asia Travel Writers Association, World
Travel Market, London, U.K.
Environment Good Practices in Hotels-1997 Case study: Maurya Sheraton Published by
International Hotels and Restaurant Association (IH&RA).
Green Hotelier and Most Eco Friendly Hotel for the year 1997 from International Hotels
& Restaurant Association (IH&RA).
Corporate Award for the Most Eco-friendly Hotel : across the globe, for the year 1997
and 2000 from IH&RA.
Energy consumption trends for ITC Maurya
Electricity Consumption
132.31
123.83
117.99
132.28
115.00
117.00
119.00
121.00
123.00
125.00
127.00
129.00
131.00
133.00
135.00
2004-05 2005-06 2006-07 2007-08
Lakh
s K
WH
co
nsu
med
PNG Consumption
7.577.52
6.86
6.63
6.40
6.60
6.80
7.00
7.20
7.40
7.60
7.80
2004-05 2005-06 2006-07 2007-08
Lakh
s S
CM
co
nsu
med
Energy Consumption (Kcal/Sqmt/day)
964.43
951.68
898.52
864.05
850.00
870.00
890.00
910.00
930.00
950.00
970.00
990.00
2004-05 2005-06 2006-07 2007-08
Kcal/S
qm
t/d
ay c
on
su
med
Electricity Cost (in Lakhs)
937.10
816.70
758.07
572.23
500.00
550.00
600.00
650.00
700.00
750.00
800.00
850.00
900.00
950.00
1000.00
2004-05 2005-06 2006-07 2007-08
RS
. In
Lakh
s
Major Energy Conservation measures implemented at ITC Maurya during 2007-08
1. Replacement of two more fixed speed centrifugal chillers with Variable Speed
Screw Chillers( Commissioned Sept 07 and is yielding good results)
2. Existing EFF-2 motors has been replaced with energy efficient NEMA premium super
E Baldor Motors in all the AHU’s and TFA’s.
3. Installion of State of the art energy efficient PNG fired Gen Set with exhaust heat
recovery through exhaust gas boiler to generate steam to operate existing double effect
vacuum absorption chiller. ( PNG fired generator has been commissioned in Jan’o8 &
Exhaust Gas Boiler is under commissioning stage)
Energy Efficient VFD Screw Chillers (02 Nos)
Energy efficient PNG fired Engine Exhaust Gas Boiler
4. Energy efficient steam boilers in place of old VINTAGE boilers with total steam
engineering RE DONE along with state of the art skid mounted plate heat
exchangers in place of old shell and tube heat exchangers with proper automation
(Commissioned in February-2008 and is yielding good results).
5. Centralized voltage regulation for lighting circuits in order to save energy.
6. Occupancy Sensors for all guest room bathrooms and public areas.
7. Energy efficient motors for Airconditiong plant.
8. VFD installation( 14 Nos) for Exhausts, AHU Motors, Air washers Etc
S
E
G
B SStteeaamm
V
A
M
1380 KVA
CAT ENGINE
Power
Hot water generation
Energy efficient Steam Boilers (02 Nos) Skid Mounted Plate Heat Exchanger
Chilled water Out
Chilled water In
9. Bifurcation of water line as lower head and higher head requirement to save the
pumping energy and for water conservation. ( approximate savings of 50 KL water per
day)
Average water Consumption (KL/day)
709.57
681.63
571.21
500.00
550.00
600.00
650.00
700.00
750.00
2005-06 2006-07 2007-08
KL
/day
10. As part of Tower block (111 rooms) renovation bed side CFL’s have been replaced
with energy efficient LED’s and also LED’s based lights in lift landings corridors etc.
11. Ozone Injection System to Use in the Laundry for Reduction the Chemical and energy.
12. Ozone injection thus reducing fresh air in intake in to AHU’s –reduction in air-
conditioning load.
13. Old washer extractor have been replaced with energy efficient washers, operated with
Variable Frequency Drives.
Ozone Injection System
14. Condensate / Flash steam recovery from Laundry ensures no wastage of energy
Energy conservation measures under implementation during 2008-09
1. All Cold Storages in Main Kitchen Will Be of CFC Free and energy efficient – Stand
Alone Cooling Unit.
2. Enhancement of ETP to STP Plant with energy efficient pumps blowers etc
3. Energy efficient PNG fired Calendar machine in place of existing steam heated
calendar machine (commissioned in July’ 2008 and yielding good results).
4. Direct PNG Fired energy efficient Tumbler Dryer for laundry. (Commissioned in July’
2008).
5. Conversion of the entire Electrical Oven to PNG Oven in kitchen.
6. Heat Pipes : for TFA’s for RH management and reduction of airconditiong load.
7. Conversion of the entire Electrical Oven to PNG Oven in kitchen.
8. Zonal segregation of chilled water lines to save airconditioning load.
9. Air Separator and expansion tanks in the chilled water loop for effective utilization
Energy efficient PNG fired Tumbler (04 Nos) Energy efficient PNG fired Calendar
Condensate/ Flash recovery System New Washer Extractor
10. Dublin airconditioning enhancement.
11. Cooling tower replacement from forced draft to induced draft so as to increase
efficiency of air-conditioning system.
12. IBMS for better management of utilities through sensors thus achieving energy
savings
13. HEAT WHEELS: It is proposed recover wasted thermal energy through Heat wheels
from the bath rooms exhaust and re- cool the fresh air entering the building (proposed
for two tower buildings)
14. Project Surya Mukhi: Solar Concentrator installation to generate steam for
steam utilities. It is proposed to install 02 nos of Arun 160 Sqmtr. Solar dishes to
generate 400 Kgs of steam per hour during sunny days/time and 12nos of Dishes from
Thermax on various loacations on the terraces to generate steam of 75 Kgs/ hour on
sunny days/time as shown in the pictures given below:
Solar concentrators
1. Thermax dishes-12 nos @ 76 kgs/ Hr each
2. Arun Solar dishes-2 nos @ 200 kgs/ Hr each
Project cost Rs 112 lacs, Commencement- November 08, Completion- January 09,Pay
back period-4.8 years
Main steam header 8 – 10 kg/cm2
Arun 1 Arun 2
Thermax -12
Laundry sub header
Low pressure line option
3.5 kgs/cm2
Kitchen SPA
Hot water Generation
Pool
Heating
Schematic for Concentrator Dishes
Schematic for ARUN Dishes
Proposed location ARUN Dishes
Major Energy Conservation measures implemented at ITC Maurya during 2006-07
1. Installation of two nos of VFD operated energy efficient and eco-friendly 19 XR
centrifugal compressors chillers. These new chillers were installed replacing two of the
existing fixed speed centrifugals which were in good working condition.
2. Installation of primary and secondary chilled water system with highly efficient motors
(EFF 1) for airconditioning plant in place of conventional direct pumping..
Old Fixed Speed Centrifugal Chillers New VFD Centrifugal Chillers (02 Nos)
Proposed THERMAX Dishes
3. Screw air compressors in place of old reciprocating compressors for laundry air
requirement.
4. All transfer pumps and fountain pumps were replaced with energy efficient pumps .
5. Replacement of three way valves to two way valves for all guest room FCUs to work
in tandem with the secondary system of pumping.
This has resulted in saving energy thru slowing down of the secondary pumps during
low load conditions.
6. Rationalization of two transformers as part of electrical system revamp. The reduced
number of transformers resulted in energy saving by eliminating the fixed losses
7. Replacement of tri port valves into bi port valves in guest rooms with state of the art
thermostats in guest rooms and offices for better energy efficiency.
8. As part of main building room renovation state of the art energy efficient lighting,
electronic bed side control panel for the control of lighting and Air conditioning in the
guest rooms.
9. Upgradtion of automisedCapacitor Banks to Maintain Unity Power Factor.
10. Two way Automatic Balancing chilled water valve for Basement /Ground Floor
AHU’s. operated with thermostats.
11. Usage of Flow Regulating Devices to Extend To All Taps to Reduce Water
Consumption thus saving pumping energy
12. New energy efficient cooling towers in place of old cooling towers with VFD operated
motors..
13. VFD installation( 15 Nos) for DG Exhaust, AHU Motors Etc
14. Installation of kitchen energy star rating equipments during Fist phase of renovation.
15. Saving in PNG achieved by adopting following measure- repairing of pipe line with
proper insulation, changed all the steam traps for better utilization of steam and energy.
Old Reciprocating Compressor (02 Nos) New Screw Compressor (02 Nos)
Energy Conservation at ITC Maurya during 2004-05 & 2005-06
The following energy efficient measures have been implemented in the following areas
1. Building Management System ( PC based):- The Building Management System
is key centre for retrieving the datas of all AHUs, TFAs & exhaust used for kitchen. It uses DP
sensor for sending the details of for eg. For AHU / TFA the load conditions of the
corresponding area in terms of return air and supply air temperature, accordingly adjust the
frequency for the drive. For the exhaust, being the most essential part for the kitchen operation
DP sensor gives the running condition of the exhaust.
2. Energy management strategy for Airconditioning:-
a. Chilled water flow for the all AHUs and TFAs is adjusted by the use of two way valves in
the pipeline which according to the load adjust the flow of water through the coils.
b. Cooling Towers fans speed is adjusted according to the return water temperature from the
Tower and hence, save lots of energy.
c. VFD’s for Condenser & Chilled Water Pumps
3. Lighting Upgrade/ Modification: - Extensive use of CFLs and PL bulbs in place of
incandescent bulbs. Use of T5 28 watts tube lights in place of ordinary 40 w tubes.
4. Modernization of Elevators:- Hotel has total 14 elevators out of which it has replaced 12
numbers with VVF ( variable voltage and frequency) Mitsubishi elevators which according to
the load and call adjust its operations.
5. Up gradation of generators: - Installation of 2 numbers 1500 KVA diesel generator which
are in accordance with EURO NORMS for environment and energy saving.
6. Installation of Capacitor banks for improving power factor.
7. Installation of Water & Energy Meters for tracking water and electrical consumption.
8. Installation of burners for boilers to use PNG as fuel for energy conservation with almost
negligible smoke.
9. Solar Photovoltaic panels for lighting of Hotel sinage generates electricity of 15000 watts
per day ( a pilot project)
Solar Photovoltaic cell Solar Photovoltaic cell
Energy Conservation Measure implemented in 2007-2008
ID to be filled by BEE Sector – Air-conditioning
Year to be filled by BEE
Title of the measure
Screw Chillers with VFD
Technology- Screw VFD
Description of the energy conservation measure:
Replacement of two numbers fixed speed centrifugal chillers with Variable Speed Screw Chillers( Commissioned Sept 07 and is yielding good results)
Picture/ sketch/ drawing before modification (if available)
Picture/ sketch/ drawing after modification
10
Agency that executed the project (with complete address and email): Carrier Air-conditioning & Refrigeration Limited, E-mail- [email protected]
Total investment, Rs.: 160 Lacs Year of implementation: 2007
First year energy cost savings, Rs.: 1886650
First year other savings, Rs.: NA
On annual basis kWh 000’
Coal (Tons)
Gas Nm
3Oil (kL)
Other
Energy consumption before
Energy consumption after
Energy tariff, Rs/ kWh/ Ton/ Nm3/ kL … 4.85
Company complete address: I T C Maurya, Diplomatic Enclave New Delhi 110021 , Tel - 011 26112233 Contact person who could be contacted for more information: N.Ramamoorthy, Chief Engineer , I T C Maurya, Diplomatic Enclave New Delhi 110021 , Tel - 011 26112233 extn 1888/1887, Fax -011 26119999, E-mail - [email protected]
We authorise Bureau to use this information for dissemination Signature Date
Energy Conservation Measure implemented in 2007-2008
ID to be filled by BEE Sector – Steam Generation
Year to be filled by BEE
Title of the measure
Steam Boilers
Technology- IBR
Description of the energy conservation measure:
Energy efficient steam boilers in place of existing VINTAGE boilers with total steam engineering RE DONE along with state of the art skid mounted plate heat exchangers in place of old shell and tube heat exchanger with proper automation (commissioned in February-2008))
Picture/ sketch/ drawing before modification (if available)
Picture/ sketch/ drawing after modification
10
Agency that executed the project (with complete address and email): Thermax Limited. Total investment, Rs.: 50 lacs Year of implementation: 2007-08
First year energy cost savings, Rs.: 548400
First year other savings, Rs.: NA
On annual basis kWh 000’
Coal (Tons)
Gas Nm
3Oil (kL)
Other
Energy consumption before
Energy consumption after
Energy tariff, Rs/ kWh/ Ton/ Nm3/ kL … 22.85
Company complete address: I T C Maurya, Diplomatic Enclave New Delhi 110021 , Tel - 011 26112233 Contact person who could be contacted for more information: N.Ramamoorthy, Chief Engineer , I T C Maurya, Diplomatic Enclave New Delhi 110021 , Tel - 011 26112233 extn 1888/1887, Fax -011 26119999, E-mail - [email protected]
We authorise Bureau to use this information for dissemination Signature Date