it. nema contactors, starters, overload relays, and...
TRANSCRIPT
IT. NEMA Contactors, Starters,
Overload Relays, and AccessoriesProduct Focus
Control and ExpandedFunctionality for IntelligentTechnologies (IT.)
See How IT. All Works Together
A Complete Family of NEMA Components and Assemblies
� Size 00-5� Full Voltage Non-Reversing (FVNR) Contactors
� Size 00-5� Full Voltage Non-Reversing (FVNR) Starters � Full Voltage Reversing (FVR) Starters� Full Voltage Reversing (FVR) Contactors
SNAP (Starter Network Adapter Product) for Applications Requiring Communications� QSNAP for QCPort� DSNAP for DeviceNet™
� Auxiliary Contacts� Reversing Wiring Kits
Solid-StateOverload Relays� Non-Reversing/
Reversing� 3-Phase� Microprocessor-
Based Design� Selectable Trip Class,
Protective Functions,and Reset Mode
� Adjustable FLA, 3.2:1� Contactor Mounted
or Standalone
� 3-Pole with Integral Solid-State Hold-in Circuit� 24V DC Control
Electromechanical Motor
Control Products: Part of IT.With a direct focus on speed,control system design, andcustomer profitability; Eaton isproud to offer Cutler-HammerIntelligent Technologies (IT.) –a complete line of forward-thinking motor control devicesincluding contactors, starters, overload relays, and accessories. These newproducts are available as openstyle components and inenclosed control and motorcontrol centers. Eaton’snewest Cutler-HammerElectromechanical MotorControl products are the mostinnovative in the world. Theseadvanced components are
There’s more to IT.!!
small in size but deliver bigfeatures; including 24V DCcontrol, communicationcapabilities, and expandedfunctionality.
See how many ways thesedevices can revolutionize theselection and use of whatwas once thought to bestandard control.
Lower Installed Costs
We’ve designed IT. to keepinstallation costs to aminimum. Small size, lessweight, modularity, removableterminal blocks, integrallywired solid-state controlcircuit components, completestarter assemblies, andcommunications capabilitiesto minimize point-to-pointwiring are just a few featuresthat keep overall costs down.
Low coil and overload relaypower consumption reducesenergy usage; and less heatgeneration eliminates orreduces control panel coolingand ventilation requirements.
24V DC Control
The Smartest and Safest
Choice in Power Today
Control with 24V DC isreliable, cost-efficient, globallyaccepted, and offers hugesafety advantages overtraditional AC control. Manyproducts ranging fromsensors to PLCs to valvemanifolds have alreadychanged to 24V DC power.
By incorporating 24V DCcontrol, we’ve reduced therisk inherent to working with higher control voltages.Other safety features includeguarded terminals, an environ-mentally friendly design – nohazardous materials,Type 2Coordination, and “hold-open”continuity of service. ThroughIT., we’ve ensured a safe working environment for personnel.
Improved Process and
Application Management
Say goodbye to the days ofreactive management! We’ve made IT. smart withcommunication capabilities,status indication, diagnostics,
remote reset abilities, and selectable andprogrammable protectivefunctions that simplifytroubleshooting and maximizeproduction time. Monitoringapplication parameters, suchas thermal memory, phaseloss, current unbalance, and"time-to-reset," over acommunication networkenables proactivemanagement of processesand applications.
S801 Soft Starters were
the first components of
the IT. family.
PUSH latch DOWN TO REMOVE terminal block
Insert terminal block completely and PUSH latch UP TO LOCK in place
Sealed Coil Power - IT. Versus Typical NEMA AC Operated Contactors
Se
ale
d W
att
s
8
7
6
5
4
3
2
1
0
IT. NEMA Size 1 Typical NEMA Size 1 w/ AC Coil
4.2
7.8
IT. sealed coil power is
46% less than typcial
NEMA Size 1 AC
operated contactors.
IT. Contactors
High performance andmultiple features make thesecontactors the industry’sfinest. Low power coils,voltage loss ride through,integrated control circuitwiring, and long life (10 millionoperations) – all in the mostcompact, modular, and easy-to-install package available.
� Small size: Size 0, 5HP @460V in a 45mm wideframe Size and Size 1, 10HP@ 460V in a 54mm wideframe size.
� 24V DC control – safe,reliable, a global standard.Pulse width modulated coilutilizes minimum power –only 3.7W on Size 0 devicesto 5.6W on Size 4 devices.
� Control circuit is auto-matically configured duringfactory and field assembly.� Integral solid-state
auxiliary hold-in circuit.� Removable control wiring
terminal block with locking feature.
� Accessories can be easilyinstalled and removed. � 1- and 2-pole, front
mounted auxiliary contacts.
� 1- and 2-pole, side mounted auxiliary contacts (Size 5).
� Mechanical interlocks for reversing assemblies.
� DIN rail installation andremoval without the use oftools for devices up to Size2. Unobstructed fixing holesfor panel installation.
� NEMA, UL, CSA, and CE approvals.
� Meets or exceeds globalstandards for EMC (Electro-Magnetic Compatibility)immunity and emissions.
� NEMA Size 1 and 2contactors and startersfeature an innovative “hold-open” contact design thatuses fault currents and theirassociated forces to latchthe moveable contactassemblies open duringshort circuit fault conditions.This feature allows themolten contact material tocool and solidify before re-closure resulting in weldresistant operation.
� IP20 guarded terminals toprevent accidental contactwith live parts.
Control terminal block with locking feature is
easily removed and wired without interfering with
power wire connections.
Sealed coil power is as littleas 21% of typical devices,enabling the use of smallerpower supplies. Reduceenergy consumption andminimize heat generation inthe electrical enclosure.Eliminate or reduce the needfor ventilation and cooling.
Long Life
IT. NEMA contactors havebeen rated for excellentelectrical life. Superiormechanical life is anotherbenefit of their small size. Ingeneral, mechanical life isinversely proportional tocontactor size due to thegreater mechanical poundingassociated with the increasedmass and armature closingspeeds of larger devices.
Brownout Protection
Reduce downtime and scrapmaterial costs due to sags inline voltage. When used withIT. Power Supplies, IT.
Contactors will remain closedfor at least 300 ms on voltageloss while fully loaded.
Easy to Wire
Even though they’re small,wiring is still easy. Terminalsare clearly marked. Powerterminal wiring is easy withbox lug pressure typeterminals for 2.5mm to 8mm(5/16in.) hex tools.
Maximum Flexibility
Modular design and fieldinstallable accessoriesmaximize inventory flexibilityand permit customization.
Size 1, 10HP @ 460V
IT. FVNR Contactor
saves an average of 40%
panel area and 68%
weight of equivalently
rated devices.
� Environmentally friendly -cadmium free contacts and non-hazardous molding materials.
� Power contacts can beinspected for trouble-shooting and ease ofmaintenance.
Optimized for 24V DC
Simple and efficient DCmagnet system proceduresmaximum performance andminimum size. This design hasno laminations, rivets orshading coils to fail. Noise dueto contamination on themagnet and armature surfacesis eliminated.
Small Size
IT. Contactors are the smalleston the market today. The small size is a result of theoptimized DC magnet systemand not due to reductions incontact size, current carryingparts, or electrical clearances.IT. Contactors require as littleas 31% of the panel area, andweigh as little as 17% ofequally rated devices. Buildsmaller, lighter machines andequipment by building smaller,lighter control panels toreduce material, shipping andhandling costs.
Safety and Low Power with
24V DC Control
OSHA allows employees towork on live systems under50 volts. 24V DC control leadsto safer systems andsimplified compliance withemerging safety standards.
IT. FVNR Contactor Size 2
45 A, 25HP @ 460V
cat. no. N111DS2X3N
IT. Starters
Easy-to-Install
Compact Devices
Electric motors are the primemovers in industry today. IT.
components satisfy all of thefeature, performance, andfunctional requirements fornon-reversing and reversingelectric motors. Productivitycan be maximized andoperating costs reduced byproperly protecting motorsand their controllers. Hold-open protection for continuityof service, and Type 2Coordination ensure thestarters won’t be damaged byshort circuit fault currents.We’ve developed selectableand programmable motorprotective functions that arenot available in a "traditionaloverload relay,” and we’vemade them cost-effective foreach and every motor.
� 24V DC pulse widthmodulated coil utilizesminimum power, only 3.7Won Size 0 devices to 5.6Won Size 4 devices.
� Microprocessor-basedoverload relay withadvanced functionality.
� Selectable Trip Class – 10, 20 (factory default), or 30 without software.
� Selectable phase loss and current unbalance protection.
� Wide range full load amperes (FLA) adjustment, 3.2:1.
� Selectable manual, auto-matic, and remote reset.
� Integral remote reset function can be actuated by an external input device.
� 24-bit floating point math calculations to provide RMS calibrated current measurement.
� Alarm output or “Alarm without trip” for critical applications that cannot be shut down.
� LED status indication provides power initialized,fault test, thermal memory, current unbalance, trip reset, and device setting information.
� Control circuit is auto-matically configured duringfactory or field assembly.
� Integral solid-state hold-in circuit and overload relay trip circuit.
� Reversing contactor and starter coil control/ overload circuit energizes both forward and reverse contactors – only one control point for wiring.
� Test function verifies per-formance and functionalityof the overload relay.
� Protective cover can belocked closed, preventingunauthorized adjustment ofoverload relay settings.
� NEMA Size 1 and 2contactors and startersfeature an innovative “hold-open” contact design thatuses fault currents and theirassociated forces to latchthe moveable contactassemblies open duringshort circuit fault conditions.This feature allows themolten contact material tocool and solidify before re-closure resulting in weldresistant operation.
� Type 2 Coordination up to100kA with standard fusesor circuit breakers. Type 2Coordination requires the
Overload Relay Heat Dissipation
Wa
tts
6
5
4
3
2
1
0
IT. Typical Eutectic Alloy
6
6
5
4
3
2
1
0
0.65A single typical eutectic
alloy overload relay
generates as much heat
as 10 IT. overload relays.
starter to be fullyoperational after a shortcircuit fault.
� NEMA, UL, CSA, and CE approvals.
� SNAP (Starter NetworkAdapter Product) modulesthat enable communicationsin standard IT. Starters.SNAP modules providepositive contact statusindication, network controland monitoring capabilitiesas well as diagnostics and enhanced protectivefunctions.
LED Status Indication
and Diagnostics
� Flashing LED providesapplication parameters,diagnostics, and devicesettings to simplifytroubleshooting,maintenance, and improve application andprocess management.
� Fault indication (overload, phase loss,“ready-to-reset”)
� Settings (Trip Class, phaseloss, and current unbalanceenabled or disabled)
� Application parameters(thermal memory)
Class 10:
Class 20:
Class 30:
Trip Class Indication on Power-up – Phase Loss/ Current Unbalance Enabled
Phase Loss and Current Unbalance Trip Indication
Thermal Memory Status LED
80% – 90% 2 flashes
Thermal Memory Indication
Overload Relay LED Status Indication
604
8
12
16
52
242832
36
40
44
4810
562
6
14
18
22
2630
34
38
42
46
50
54
58
10
1040
Trip Time Due to Phase Loss
Typical eutectic alloy
overload relay takes 40
seconds or more to trip
on phase loss
IT. trips in 10 seconds
on phase loss!
20
604
8
12
16
52
242832
36
44
48
562
6
14
18
22
2630
34
38
42
46
50
54
58
20
10
40
Number of Unique Devices
Am
pe
res
Eutectic AlloyClass 10
IT.Class 10, 20, 30
640
27
13.5
0Eutectic Alloy
Class 20Eutectic Alloy
Class 30
40 40
Only six IT. Overload Relays are required
to cover all NEMA Size 1 requirements
compared to over 40 eutectic alloy heater
elements for a given trip class.The IT.
Overload Relay features selectable trip
class compared to many solid-state and
eutectic alloy heater elements that are a
single class.
Phase Loss Protection
� Single-phase conditions are the leading cause ofmotor damage. IT. OverloadRelays trip within 10seconds on phase loss,compared to 40 seconds ormore for typical eutecticalloy overload relays.
Low Power Consumption
and Low Heat Generation
� IT. Overload Relays actuallymeasure current, unliketraditional eutectic alloyoverload relays whichindirectly model motortemperature.
� IT. Overload Relays generateonly 650mW of heatcompared to 6W for typicaleutectic overload relays.
� Reduce energy consump-tion and minimize heatgeneration in the controlpanel. Eliminate the needfor ventilation and cooling.
Wide FLA Adjustment Range
� Each IT. Overload Relay canbe adjusted over a range of 3.2:1. Inventory is mini-mized, and FLAs can alsobe set for motors with varying service factors.
IT. Accessories
When standard contactor and starter features andfunctionality need to beexpanded for the mostdemanding applications,customize them with fieldinstallable accessories.
Starter Network Adapter
Product (SNAP)
� Can be installed or removedon standard IT. starterswithout tools.
� Requires no additional panel space.
� Wiring harness provided asstandard for easy connec-tion to the overload relay.
� DeviceNet™ or QuickConnect Port versions.
� Communicate applicationparameters (power andcontact status, FLA setting, trip codes, startersize, operating current,thermal memory, overloadrange, ground fault).
� Starter control functions(forward/reverse, trip reseton left).
� Protective functions (alarmon current threshold,extended thermal overloadand current unbalance,nuisance trip avoidance).
System Wellness Relay
� Enhanced system wellnessthat goes well beyond thethermal motor protectionoffered by typical thermaland solid-state overloadrelays. Exclusive mechanicalwellness capabilities suchas pump cavitaion,rotational unbalance andshaft misalignmentdetection to diagnosesystem problems beforecostly failures occur. TheSystem Wellness Relay alsoprovides parameters forPower Metering.
General Items
� Common accessories can be used on all devices – contactors, starters, and reversing assemblies.
� IP20 guarded terminals andfanning strip covers (forreversing assemblies)prevent accidental contactwith live parts.
� Visible indicator on Auxiliary Contacts showing operation.
Mechanical Interlock
� 6mm wide, prevents thesimultaneous operation of the forward and reverse contactors.Electrical interlock is part ofmicroprocessor.
Reversing Kits
� Includes fanning strips,mechanical interlock,mounting plate, and hardware.
Auxiliary Contacts
� 1- and 2-pole front mountedfor Size 00-5 devices.
� Standard and logic level 1-and 2-pole side mounted forSize 5 devices.
� 2-pole front mounted logiclevel (0.1A @ 125-250V AC)for Size 00-5 devices.
NetworkCommunications
The complete family of IT..components (contactors andstarters, soft starters,communication gateways,cover controls, I/O, and powersupplies) can be easilyintegrated into a completemanufacturing system ordistributed control solution.Motor control centers andenclosed starters assembledfrom individual componentsare available as part of thesolution too. devices areplug-and-play andcommunication ready forintegration in DeviceNet™networks. Configuration iseasy with Cutler-HammerStudio Software.
Benefit from Network
Communications
� Improve process andapplication management.� Monitor device and
application parameters� Troubleshoot with device
diagnostics and status indication
� Expand control and protective functions
� Share information across the enterprise
� Reduce installed costs� Minimize point-to-point
hardwiring� Simplify control system
design and future upgrades and expansions
� Enhanced safety.� 24V DC control –
safe, reliable, and a global standard
Where Can You Use IT.?
Everywhere!
Designed and tested for the most demanding global applications.
IT. Contactors, Starters,
Overload Relays, and
Accessories comply with, or
exceed, applicable global
standards:
� NEMA ICS 1, ICS 2, and ICS 5
� UL 508� CSA C22.2 No. 14� CSA Certified for
Elevator Duty
More importantly, they
meet the demanding
requirements of the
industrial plant floor:
� Operating temperature: -40ºC to 65º C (-40º F to 149º F).
� Humidity: 95% non-condensing.
� Shock: 15g, half-wavesinusoidal, 11msec.
� Vibration: 5-150Hz (100 to6.7 msec).
� Meets or exceeds globalstandards for EMC (Electro-Magnetic Compatibility)immunity and emissions.
� Conformal coated printedcircuit boards for resistanceto harsh environments.
IT. provides solutions and
offers benefits in a wide
variety of industries:
Material Handling, PackagingMachinery, Plastics andRubber Machinery, Furnacesand Ovens, Machine Tool, Pulpand Paper, Chemical andPetro-Chemical, Mining andMetals, Water andWastewater Treatment, Foodand Beverage Processing,Automotive, Transportation,and Pumps and Compressors.
Here are two specific
applications…
1- Pulp and Paper
Processing Plant
IT. Starters are used to controlmaterial handling systems.The installation also includesSNAP modules to monitoraverage current – which isused as a measure of thematerial viscosity and toprovide indication of a clogged filter.The result: Increasedproductivity because overloadconditions are minimized andrequired filter maintenance isperformed during scheduleddowntime.
2- Welding Control
IT. Contactors are used tocontrol welding equipment inan automotive assembly plant.The result: Smaller controlpanels were required due tothe small size of IT. devices.Enhanced safety was providedto shop floor and maintenanceemployees with 24V DCcontrol, guarded terminals,and Type 2 Coordination.
Come and Get IT.
Contactors, Starters,
Overload Relays, and
Accessories – a Total
System Solution
Providing:
� Lower Installed Costs.� Enhanced Safety.� Improved Process and
Application Management.
Power Supplies
Motor Control Centers Enclosed Control Contactors and Starters
Soft Starters SNAP Modules Cover Controls I/O and Adapter Modules
NEMA SizeContinuous Ampere Rating (A)HP @ 460VHP @ 575V
Non-Reversing Contactors
Catalog No. Prefix: N111Height (mm/in)Width (mm/in)Depth (mm/in)Weight (kg/lbs)Coil Sealed Power (W)Reversing Contactors
Catalog No. Prefix: N511
Overload Relays for Non-Reversing Starters
Catalog No. Prefix: N05N
FLA Adjustment Range
Overload Relays for Reversing Starters
Catalog No. Prefix: N06N
Non-reversing Starters
Catalog No. Prefix: N101
Height (mm/in)Width (mm/in)Depth (mm/in)Weight (kg/lbs)Coil Sealed Power (W)Reversing Starters
Catalog No. Prefix: N501Accessories
Auxiliary Contacts Front Mounted 1- & 2-Pole (Cat. No. Prefix: EMA) Side Mounted 1- & 2-Pole (Cat. No. Prefix: C320KGS)SNAP Modules - for use with starters DSNAP for DeviceNet QSNAP for Quick Connect PortReversing Kits Includes fanning strips, mechanical interlock, mounting plate and hardware
00 0 1 9 18 27 2 5 10 2 5 10
BSA BS0 CS1 111/4.4 113/4.4 45/1.8 54/2.1 60/2.4 60/2.4 0.31/0.70 0.42/0.90 3.7 4.2 BSA BS0 CS1
BXR CXR
0.25-0.8, 0.59-1.9, 1.4-4.4,2.8-9.0, 6.3-20, 10-32
0.25-0.8, 0.59-1.1.4-4.4, 2.8-9.0
5-16, 8.4-27,16-50
BXR CXR
BSA BS0 CS1
127/5.0 138/5.4 45/1.8 54/2.1 63/2.5 63/2.5 0.4/0.9 0.53/1.2 3.2 3.6
BSA BS0 CS1
EMRKTB EMRKTC
Technical Specifications
2 3 4 5 45 90 135 270 25 50 100 200 25 50 100 200
DS2 ES3 ES4 FS5 150/5.9 203/8.0 354/13.9 76/3.0 105/4.1 140/5.5 79/3.1 90/3.5 178/7.0 1.27/2.8 3.05/6.7 9.1/20 5.0 5.6 DS2 ES3 ES4 FS5
9,,
DXR EXR FXR
5-16, 8.4-27,14-45, 31-100
14-45, 28-90,42-135, 63-200 (ES4)
42-135, 84-270, 125-400
DXR EXR FXR
DS2 ES3 ES4 FS5
150/5.9 203/8.0 492/19.4 76/3.0 105/4.1 145/5.7 79/3.1 90/3.5 178/7.0 1.32/2.90 3.2/7.1 12.3/27.0 5.0 5.6 13.0
DS2 ES3 ES4 FS5
EMRKTD EMRKTE EMRCKTFEMRSKTF
© 2004 Eaton CorporationAll Rights ReservedPrinted in USAForm No. BR03305001E / CSS 2912March 2004
Eaton Electrical Inc.1000 Cherrington ParkwayMoon Township, PA 15108United Statestel: 1-800-525-2000www.EatonElectrical.com
Eaton Electrical Inc. is a global leader in electrical control, power distribution,and industrial automation products and services. Through advanced productdevelopment, world-class manufacturing methods, and global engineeringservices and support, Eaton Electrical® provides customer-driven solutions underbrand names such as Cutler-Hammer®, Durant®, Heinemann®, Holec® and MEM®,which globally serve the changing needs of the industrial, utility, lightcommercial, residential, and OEM markets. For more information, visitwww.EatonElectrical.com.
Eaton Corporation is a global diversified industrial manufacturer with 2003 salesof $8.1 billion that is a leader in fluid power systems; electrical power quality,distribution and control; automotive engine air management and powertraincontrols for fuel economy; and intelligent drivetrain systems for fuel economyand safety in trucks. Eaton has 51,000 employees and sells products tocustomers in more than 100 countries. For more information, visitwww.eaton.com.