PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
SCHEMATIC DIAGRAM DEVICE DESIGNATIONSONE-LINE AND CONTROL DIAGRAMS
PLANS
SINGLE SPEED NON-REVERSING
MAGNETIC MOTOR STARTER
SINGLE SPEED NON-REVERSING
MANUAL MOTOR STARTER
REDUCED VOLTAGE
SOLID-STATE STARTER
VARIABLE FREQUENCY DRIVE
POWER CIRCUIT AND EQUIPMENT
INSTALLED BY THIS CONTRACT
FUTURE POWER CIRCUIT
AND EQUIPMENT
EQUIPMENT ENCLOSURE
CONTROL OR INTERLOCK CIRCUIT
TERMINAL
CONNECTION
CIRCUIT BREAKER
FUSE
FUSED DISCONNECT SWITCH
PLUG-IN OR DRAWOUT CONNECTION
DISCONNECT SWITCH
POWER TRANSFORMER (XFMR)
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER, SINGLE
RATIO (SHOWN WITH QUANTITY)
POTENTIAL TRANSFORMER
(SHOWN WITH QUANTITY)
CAPACITOR
THERMAL OVERLOADS
GROUND CONNECTION
LIGHTNING ARRESTOR
"X" INDICATES NUMBER OF
DEVICES WHEN MORE THAN ONE
(X)
200:5
(2)
DELTA WINDING CONNECTION
GROUNDING Y WINDING
CONNECTION
CIRCLED NUMBER IS THE SAME
NUMBER THAT APPEARS AFTER THE
NOTE: NO DIAGRAM NUMBER
INDICATED SAME AS SCHEMATIC
DEVICE IDENTIFICATION
DEVICE DESIGNATION
CR1
B = BLACK; R = RED; ETC.
DEVICE IDENTIFICATION
DEVICE DESIGNATION
DIAGRAM NUMBER
20-CR1
CONTACT CALLOUT
DEVICE CALLOUT
WIRE COLOR DESIGNATION:
HYPHEN IN THE "CIRCUIT NUMBER"B
CIRCUIT CALLOUT
(2)
RVSS
AMMETER
VOLTMETER
VFD
A
V
GENERATOR
HP
ELECTRIC MOTOR - APPROX.
HORSEPOWER AS INDICATED
EQUIPMENT AS NOTED
ON DIAGRAM
SCHEMATIC DIAGRAMS
TERMINAL
POSITIVE TERMINAL
NEGATIVE TERMINAL
(A) CONDUCTOR CONNECTION
(B) NO CONNECTION
SWITCH (AS DESIGNATED
ON DIAGRAM)
(A) CONTACT - NORMALLY OPEN
(B) CONTACT - NORMALLY CLOSED
A B
A B
SELECTOR SWITCH (AS
DESIGNATED ON DIAGRAM)
A
O
H
HAND-OFF-AUTO
SELECTOR SWITCH
(A) PUSH-BUTTON - NORMALLY
OPEN MOMENTARY
(B) PUSH-BUTTON - NORMALLY
CLOSED MOMENTARY
(A) MAINTAINED PUSH-BUTTON -
NORMALLY OPEN
(B) MAINTAINED PUSH-BUTTON -
NORMALLY CLOSED
(A) PRESSURE OR VACUUM SWITCH-
CLOSES WITH INCREASING PRESSURE
OR DECREASING VACUUM
(B) PRESSURE OR VACUUM SWITCH-
OPENS WITH INCREASING PRESSURE
OR DECREASING VACUUM
(A) FLOAT OR OTHER LIQUID LEVEL
SWITCH - CLOSES WITH RISING LEVEL
(B) FLOAT OR OTHER LIQUID LEVEL
SWITCH - OPENS WITH RISING LEVEL
A B
A B
A B
A B
(A) TEMPERATURE SWITCH - CLOSES
WITH RISING TEMPERATURE
(B) TEMPERATURE SWITCH - OPENS
WITH RISING TEMPERATURE
A B
EXISTING CIRCUIT AND EQUIPMENT
POWER CIRCUIT AND EQUIPMENT
INSTALLED BY THIS CONTRACT
FUTURE POWER CIRCUIT
AND EQUIPMENT
EQUIPMENT ENCLOSURE
CONTROL OR INTERLOCK CIRCUIT
EXISTING CIRCUIT AND EQUIPMENT
REMOTE WIRING
CIRCUIT BREAKER
FUSE
POWER TRANSFORMER (XFMR)
GROUND CONNECTION
LIGHTNING ARRESTOR
THERMAL OVERLOAD RELAY
(SHOWN WITH QUANTITY)
SOLENOID VALVE COIL
O.L. (3)
INDICATING LIGHT -
PILOT PUSH-TO-TEST
TYPE WITH COLOR INDICATED:
R-RED, A-AMBER, G-GREEN, W-WHITE,
BL-BLUE, I-IVORY AND Y-YELLOW.
R
NEW CONSTRUCTION
CONDUIT EXPOSED
CONDUIT CONCEALED IN WALL,
CEILING OR HIDDEN FROM VIEW
CONDUIT CONCEALED IN
FLOOR OR UNDERGROUND
EXISTING CONSTRUCTION
FLEXIBLE CONDUIT
HOME RUN TO PANELS,
ARROWHEADS INDICATE NUMBER
OF CIRCUITS
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT TERMINATED AND CAPPED
CONDUIT PASSING THRU ELEVATION
GROUND CABLE
BOLTED GROUND CONNECTION
WELDED GROUND CONNECTION
CONDUIT WITH BUSHING
GROUND ROD
PANELBOARD
DISCONNECT SWITCH
FUSED DISCONECT SWITCH
COMBINATION DISCONNECT/
MAGNETIC MOTOR STARTER
SINGLE POLE SWITCH
WEATHERPROOF SWITCH
3X
WP
SURFACE MOUNTED DUPLEX
RECEPTACLE OUTLET
SURFACE MOUNTED DUPLEX
RECEPTACLE OUTLET. GROUND
FAULT CIRCUIT INTERRUPTER TYPE.
"WP" DENOTES WEATHERPROOF
WHILE IN USE.
T
THERMOSTAT
INTEGRAL PHOTOELECTRIC CELL
AND RELAY (PHOTOCONTROL)
P
M
PULL BOX
MOTOR
JUNCTION BOX
TELEPHONE OUTLET
DATA OUTLET
TELEPHONE/DATA OUTLET
DIAGRAM NUMBER
(A) LIMIT SWITCH - NORMALLY CLOSED
(B) LIMIT SWITCH - NORMALLY CLOSED-
HELD OPEN
(A) LIMIT SWITCH - NORMALLY OPEN
(B) LIMIT SWITCH - NORMALLY OPEN-
HELD CLOSED
A B
A B
RVAT
REDUCED VOLTAGE AUTO-
TRANSFORMER
DUAL THROW TRANSFER SWITCH
GENERAL NOTES:NOT ALL DEVICES AND DEVICE DESIGNATIONS SHOWN ON THIS LEGEND ARE USED ON
THIS PROJECT.
COORDINATE ALL CONDUIT TURN UP LOCATIONS AND PENETRATIONS WITH EQUIPMENT
PROVIDED.
CONDUIT ROUTING DESIGNATED AS "AG/BG" DENOTES ABOVE-GRADE ROUTING
TRANSITIONING TO BELOW-GRADE ROUTING AND VICE-VERSA.
REFER TO P&ID LEGEND DRAWING D001 AND D002 FOR ADDITIONAL INSTRUMENT AND
EQUIPMENT ABBREVIATIONS.
ALL INSTALLATIONS SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE AND ALL
APPLICABLE LOCAL CODES AND STANDARDS.
REFER TO SPECIFICATION SECTION 26 05 19 FOR CABLE SCHEDULE.
1.
2.
3.
4.
5.
6.
EMERGENCY BATTERY POWERED
LIGHTING UNIT.
ABBREVIATIONSAMPERES
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPS INTERRUPTING CURRENT
ARC REDUCTION MAINTENANCE SWITCH
AUTOMATIC TRANSFER SWITCH
AMERICAN WIRE GUAGE
BARE COPPER WIRE
BATTERY CHARGER
BELOW FLOOR
BELOW GRADE
BREAKER
BYPASS SWITCH
CONDUIT
CAMERA
CIRCUIT BREAKER
CONTROL PANEL
COPPER PATCH PANEL
CONTROL POWER TRANSFORMER
CONTROL STATION
DRIVE / DRIVE MOTOR
DISCONNECT SWITCH
ELEVATION
ELECTRICALLY OPERATED
EMERGENCY PULL SWITCH
EXPOSED
EXPLOSION-PROOF
(CLASS 1, DIV 1, GROUP D)
EXTERIOR
FIRE ALARM CONTROL PANEL
FIBER OPTIC PATCH PANEL
FIELD PANEL (PRE-PACKAGED)
GENERATOR
GROUND
HANDHOLE
JUNCTION BOX
POWER CONTACTOR
A
AFF
AFG
AIC
ARMS
ATS
AWG
BC
BCH
BF
BG
BKR
BSW
C
CAM
CB
CP
CPP
CPT
CST
DRV
DS
EL
EO
EPS
EX
EXP
EXT
FACP
FOP
FP
GEN
GND
HH
JB
JS
LC
LCP
LS
LVT
M
MCC
MCP
MDM
N.C.
N.O.
NER
NSW
OIT
OWS
P
PCS
PDP
PHC
PLC
PNL
PP
PRN
PSU
RCPT
RGS
SP
SPD
SVR
SW
TOC
TYP
UE
UPS
VFD
WP
XFMR/XF
LIGHTING CONTACTOR
LOCAL CONTROL PANEL
LIMIT SWITCH
LOW VOLTAGE TRANSFORMER
MOTOR
MOTOR CONTROL CENTER
MAIN CONTROL PANEL
MODEM (EXTERNAL PCS ALARM)
NORMALLY CLOSED
NORMALLY OPEN
NETWORK EQUIPMENT RACK
NETWORK SWITCH
OPERATOR INTERFACE
TERMINAL
OPERATOR WORKSTATION
POLE
PLANT CONTROL SYSTEM
POWER DISTRIBUTION PANEL
PHOTOCELL
PROGRAMMABLE LOGIC CONTROLLER
PANELBOARD
POWER PANEL
PRINTER
POWER SUPPLY UNIT
RECEPTACLE
RIGID GALVANIZED STEEL
SPARE
SURGE PROTECTIVE DEVICE
SERVER
SWITCH
TOP OF CONCRETE
TYPICAL
UNDERGROUND ELECTRICAL
UNINTERRUPTIBLE POWER SUPPLY
VARIABLE FREQUENCY DRIVE
WEATHERPROOF
TRANSFORMER
CONDUIT, CABLE AND EQUIPMENT NUMBERING
CONDUIT ROUTING: AG - ABOVE GRADE
BG - BELOW GRADE
CONDUIT TYPE: FLEX - FLEXIBLE ALUMINUM
RGS - RIGID GALVANIZED STEEL
RAL - RIGID ALUMINUM
CRGS - PVC COATED RGS
40PVC - PVC SCHEDULE 40
80PVC - PVC SCHEDULE 80
CABLE TYPE: REFER TO CABLE SPECIFICATION SECTION.
CABLE NUMBER: M-AAA-BBBXXXYZ-NNN
P:
C:
I:
F:
T:
R:
POWER
CONTROL
INSTRUMENTATION
FIBER
COMMUNICATIONS (COPPER)
COAX
BUILDING/STRUCTURE DESIGNATOR (OPTIONAL)
SEQUENTIAL NUMBER (OPTIONAL)
ASSOCIATED EQUIPMENT
EQUIPMENT NUMBER: AAA-BBB-XXYZ
BUILDING OR STRUCTURE ABBREVIATION (OPTIONAL)
LOOP NUMBER
EQUIPMENT/INSTRUMENT INDENTIFIER
UNIT NUMBER AND MODIFIER (OPTIONAL)
A
AUTO
ACK
CL
FWD
H
NC
NO
O
OP
REV
RMT
AUTOMATIC
ACKNOWLEDGE
CLOSE
FORWARD
HAND
NORMALLY CLOSED
NORMALLY OPEN
OFF
OPEN
REVERSE
REMOTE
I/I
IL
IPB
ISP
ISS
LLS
LS
M
MV/I
MX
OL
PB
PS
SOL
SPB
SS
SV
TDR
TMR
TS
VS
XFMR
CURRENT TO CURRENT TRANSDUCER
INDICATING LIGHT
ILLUMINATED PUSHBUTTON
ILLUMINATED SELECTOR PUSHBUTTON
ILLUMINATED SELECTOR SWITCH
LIQUID LEVEL SWITCH
LIMIT SWITCH
MOTOR STARTER COIL OR CONTACT
MILLIVOLT TO CURRENT TRANSDUCER
MOTOR STARTER AUXILIARY RELAY
OVERLOAD RELAY
PUSHBUTTON
PRESSURE SWITCH
SOLENOID (OTHER THAN VALVE)
SELECTOR PUSHBUTTON
SELECTOR SWITCH
SOLENOID VALVE
TIME DELAY RELAY
TIMER
TORQUE SWITCH
VACUUM SWITCH
TRANSFORMER
DESIGNATIONS DESCRIBINGDEVICE OPERATION OR FUNCTION
(IF APPLICABLE)
FOC
COMMUNICATION CABLE (COPPER)
COMMUNICATION CABLE
(FIBER OPTIC CABLE)
SOFTWARE OR COMMUNICATION
LINK
O O
E
ELECTRICAL DUCT BANK
J
CONDUIT CONTINUATION
X
SURFACE OR PENDANT FIXTURE
(TYP FOR ALL LUMINIARE TYPES)
THREE-WAY SWITCH "X"
CORRESPONDS TO THE ASSOCIATED
BANK OF LIGHTS (IF USED)
KWHUTILITY METER
SURGE PROTECTION DEVICE
SPD
CXXXX
(PREFERRED)
CXXXX
(ALTERNATE)
3
X
3 X
CKT NO. TYP
3
X
3
X
CIRCUIT AND DEVICEIDENTIFICATION
X
X
X
DEVICE ORIENTATION
TYPE LX
CKT NO.
MTNG ELV
HOMERUNIDENTIFICATION
LUMINAIREIDENTIFICATION
K1KEY INTERLOCK
AC CIRCUIT BREAKER52-X
X
ANSI DEVICE
86 = LOCKOUT RELAY
71 = OIL LEVEL SWITCH
49 = TRANSFORMER THERMAL SWITCH
ELECTRONIC TRIP UNIT
L = LONG TIME
S = SHORT TIME
I = INSTANTANEOUS
G = GROUND
TU
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
001.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
ELECTRICAL LEGEND
ELECTRICAL
95307
E001 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
TIME DELAY RELAY CLOSES ON TIME
DELAY AFTER ENERGIZATION
FLOW SWITCH CLOSES ON LOSS
OF FLOW
DEMOLITION HATCHING
DEMOLITION HATCHING
ARMS
ARC REDUCTION MAINTENANCE
SWITCH
XX
XX
X X X X X X X X X X X X X X
XX
XX
XX
XX
XX
XX
XX
X
XXX
WW
WW
W
W W W W W W
W
X X X X X X X X X X X
W W W
W
W
XX
X
ST ST ST ST ST ST ST
STST
STST
PLPL
SS SS SS SS SS SS SS SS
SSSS
SSSS
SSSS
SSSS
SSSS
SSSS
SSSS
SS
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
SSFM
W W
WW
W
W W W W W W
W W W W W W W W W W W W
WW
E
E
E
E
E
E
SS
SS
SS
E
E
E
E
E E E E E E
EE
E
E
E
E
E
E
E
E
E
J
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
0 20'10'
SCALE IN FEET
NORTH
ELECTRICAL SITE PLAN
GENERAL NOTES:
KEYED NOTES:
1 DUCT BANK STUB-UPS SHALL BE COORDINATED WITH GENERATOR
MANUFACTURER. DUCT BANK ROUTING SHALL BE ADJUSTED
ACCORDINGLY TO INSTALL CONDUIT TURN-UPS IN GENERATOR ENTRY IN
SKID.
CONDUITS FROM DUCT BANK SHALL BE STUBBED UP NEXT TO EXTERIOR
BUILDING WALL. CONDUITS SHALL BE EXTENDED UP EXTERIOR WALL TO
CABLE TRAY, #4/0 BC2 GROUND CABLE SHALL BE INSTALLED IN A 1"
SCHEDULE 40 PVC CONDUIT UP TO THE CABLE TRAY AND BONDED TO
THE CABLE TRAY GROUND CABLE USING A IRREVERSIBLE COMPRESSION
STYLE CONNECTOR.
DUCT BANK GROUND CABLE SHALL BE EXTENDED TO EXISTING GROUND
GRID. CONTRACTOR SHALL FIELD VERIFY THE EXISTING GROUND TRIAD
AND EXCAVATE TO EXPOSE THE EXISTING GROUND CONDUCTOR. THE
EXISTING GROUND CABLE SHALL BE CLEANED. THE NEW #4/0 BC2 SHALL
BE EXOTHERMICALLY WELDED TO THE EXISTING GROUND CABLE. IF THE
EXISTING GROUND CABLE IS DAMAGED DURING EXCAVATION IT SHALL BE
REPAIRED AT NO COST TO OWNER (THE REPAIR METHOD SHALL BE
APPROVED BY THE ENGINEER OF RECORD).
#2 BC2 GROUND CABLE SHALL BE INSTALLED BETWEEN CANOPY
STRUCTURAL STEEL TO CABLE TRAY AND BONDED TO THE #2 GREEN
INSULATED GROUND CABLE INSTALLED IN THE CABLE TRAY (A UL LISTED
HIGH COMPRESSION GROUND CLAMP SHALL BE USED). GROUND CABLE
SHALL BE CONNECTED TO STRUCTURAL STEEL WITH A UL RATED
COMPRESSION TYPE CONNECTOR. REFER TO DRAWING E103 FOR CABLE
TRAY LOCATION.
BOND GROUND CABLE TO GENERATOR FRAME (TYP 2 PLACES).
ELECTRICAL DUCT BANK SHALL BE INSTALLED BELOW NEW WATER LINE.
BOND GROUND CABLE TO SWITCHGEAR GROUND BUS.
GROUND CABLE SHALL BE BONDED TO METAL SWITCHGEAR ENCLOSURE
(TYP OPPOSITE CORNERS).
#4/0 BC2 SHALL BE BONDED TO STAIR.
BOND #4/0 BC2 GROUND CABLE TO ODOR CONTROL FAN SKID.
GROUND CABLE SHALL BE BONDED TO FENCE POST, REFER TO DETAIL
ON DRAWING E502 FOR FENCE GROUNDING DETAIL.
BRACE OR GUY THE EXISTING POLE AS REQUIRED. COORDINATE WORK
AND COMPLY WITH EPB REQUIREMENTS.
INSTALL GENERATOR EMERGENCY SHUT DOWN SWITCH (PS-ES-090) ON
PS-SWG-010 ENCLOSURE. INSTALL ENCLOSURE 48-INCHES ABOVE
FINSISHED GRADE. INSTALL PHENOLIC NAMEPLATE ON ENCLOSURE
STATING "GENERATOR EMERGENCY SHUTDOWN SWITCH PS-ES-090."
REFER TO CABLE TRAY GROUNDING DETAIL ON DRAWING E502.
DUCT BANK SHALL BE STUBBED OUT 5-FEET FROM EDGE OF CONCRETE
PAD. CONDUITS SHALL EXTEND 12-INCHES PAST CONCRETE
ENCASEMENT AND CAPPED FOR FUTURE USE (REFER TO DETAIL ON
DRAWING E501).
DUCT BANK GROUND CONDUCTOR SHALL BE STUBBED UP AND
CONNECTED TO RELOCATED CABLE SUPPORT AND CONDUIT STRUT
SUPPORT RACKS.
DUCT BANK GROUND CONDUCTOR SHALL BE STUBBED UP AND
CONNECTED TO CONDUIT STRUT SUPPORT RACKS.
1. REFER TO DRAWING E501 FOR DUCT BANK CONSTRUCTION DETAILS.
2. ALL BELOW GRADE UTILITIES SHALL BE LOCATED PRIOR TO
EXCAVATION FOR THE ELECTRICAL DUCT BANKS.
3. ALL GROUNDING CABLE SHALL BE #4/0 BC2 UNLESS NOTED
OTHERWISE.
4. FOR FENCE GROUNDING DETAIL REFER TO DRAWING E502.
5. ALL GROUND RODS SHALL BE 3/4" X 10'-0".
6. GENERATOR SHALL BE ORIENTED SUCH THAT THE AIR INTAKE IS ON
THE NORTH SIDE OF THE GENERATOR. THE GENERATOR FUEL PORT
SHALL BE INSTALLED ON THE SOUTHWEST SIDE OF THE ENCLOSURE.
7. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR CABLE SCHEDULE.
8. THE EXISTING PUMP STATION SCREEN ROOM, EXISTING PUMP
STATION WET WELL, EBPS WET WELL AND INFLUENT CHANNEL ARE A
CLASS I, DIV 2 AREA. SEAL CONDUIT AT THE BOUNDARY OF ALL
CLASSIFIED AREAS PER THE NATIONAL ELECTRIC CODE. EQUIPMENT
ENLCOSURES LOCATED ON THE NORTH SIDE OF THE EBPS SHALL BE
SEALED PER THE TYPICAL EBPS EQUIPMENT INSTALLATION DETAIL
ON DRAWING E502.
PS-GEN-090
2
3
4
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
101.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
ELECTRICAL SITE PLAN
ELECTRICAL
95307
E101 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
5
5
66
EMERGENCY BACKUP
PUMP STATION (EBPS)
EXISTING PUMP STATION
(REFER TO DRAWING E103
FOR ENLARGED PLAN
EXISTING WATER LINE
EXISTING SANITARY
EXISTING
OVERHEAD
ELECTRIC
PS-SWG-010
(OUTDOOR
ENCLOSURE)
8'X8'X8'PRECAST CONCRETE
ELECTRICAL MAN HOLE
EXISTING UTILITY
POLE
1
7
8
7
8
E301
E
F
E301
E301
D
E301
B
E301
A
E301
C
2
3
4
6
9
9
9
10
10
16
11
11
11
11
12
12
E301
G
FUTURE UTILITY
TRANSFORMER
6
FUEL PORT
AIR INTAKE
RELOCATED
WATER LINE
C-PS-GEN090-03
13
PS-EDB-001
PS-EDB-004
PS-EDB-005
PS-EDB-001
PS-EDB-00615
E501
1
PS-EDB-003
PS-EDB-002
14
OCS-EF-001
PS-PAC-001
14
15
16
17
17
#4/0 BC2 BOND TO STRUCTURAL
STEEL SUPPORT COLUMN
13
5
X X X X X X X X X X X X
X
X X X X X X X X X X X X X X X X X X X X X X X X X X
X
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
NORTH
ENLARGED POWER PLAN
PS-SWBD-020
EBPS-PLC-060
PS-XF-040
SCALE IN FEET
0 2' 4' 8'
EBPS-GR-101
EBPS-P-101
EBPS-P-102
EBPS-LIT-111
GENERAL NOTES:
KEYED NOTES:
1
FOR DUCT BANK CONTINUATION REFER TO
DRAWING E101.
MANUFACTURER PROVIDED CABLE.
CONTRACTOR SHALL VERIFY EXACT LOCATION
OF ODOR CONTROL DUCT WORK WITHIN WET
WELL. INSTALL CONDUITS SUCH THAT TO
AVOID CONFLICTS WITH DUCT.
CONDUIT RISERS SHALL HAVE A 90-DEGREE
BEND FROM VERTICAL TO HORIZONTAL AT
CABLE TRAY. RISER CONDUITS SHALL BE
FILLED WITH DUCT SEAL COMPOUND. SPARE
CONDUITS SHALL BE INSTALLED ON THE EAST
(SIDE OF THE DUCT BANK RISER) AND CAPPED
12-INCHES ABOVE TOP OF DUCT BANK AND
CAPPED FOR FUTURE USE. REFER TO DETAIL 1
ON DRAWING E501 FOR DUCT BANK STUB UP
DETAIL.
1. REFER TO DRAWING E501 FOR DUCT BANK
CONSTRUCTION DETAILS.
2. ALL BELOW GRADE UTILITIES SHALL BE
LOCATED PRIOR TO EXCAVATION FOR THE
ELECTRICAL DUCT BANKS.
3. REFER TO SPECIFICATIONS SECTION 26 05 19
FOR CABLE SCHEDULE.
4. THE EXISTING PUMP STATION SCREEN ROOM,
EXISTING PUMP STATION WET WELL, EBPS WET
WELL AND INFLUENT CHANNEL ARE A CLASS I,
DIV 2 AREA. SEAL CONDUIT AT THE BOUNDARY
OF ALL CLASSIFIED AREAS PER THE NATIONAL
ELECTRIC CODE. EQUIPMENT ENCLOSURES
LOCATED ON THE NORTH SIDE OF THE EBPS
SHALL BE SEALED PER THE TYPICAL EBPS
EQUIPMENT INSTALLATION DETAIL ON DRAWING
E502.
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
102.D
WG
5/16/2017 9:21 A
M LP
IR
TLE
04/14/17
CABCMK CSH
EMERGENCY BACKUP
PUMP STATION POWER
PLAN
ELECTRICAL
95307
E102 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
EQUIPMENT ROOM
EBPS-VFD-101
PS-PNL-040
EBPS-VFD-102
OCS-EF-001
P-EBPS-GRCP-101-01A,02A,03A
PS-CT-003
PS-CT-002
P-PS-SWBD020-13
EBPS-SG-004
P-EBPS-GRCP-103-
01A,02A,03A
P-EBPS-GRCP-102
-01A,02A,03A
EBPS-GR-102
EBPS-GR-103
EBPS-SG-003
EBPS-SG-002
EBPS-SG-001
P-PS-SWBD020-12
P-PS-SWBD020-10
P-PS-SWBD020-11
EBPS-STR-001
P-PS-SWBD020-15
P-EBPS-VFD102-01A
P-EBPS-VFD101-01A
P-PS-SWBD020-14
EBPS-PJB-100
EBPS-SPCP-101
P-EBPS-VFD101-01,
P-EBPS-VFD102-01
P-PS-SWBD020-18
EBPS-SP-101
P-EBPS-GRCP103-01,02,03
P-EBPS-GRCP102-01,02,03
P-EBPS-GRCP101-01,02,03
EBPS-GRJB-101
P-EBPS-GRCP101-01,02,03
P-EBPS-GRCP102-01,02,03
P-EBPS-GRCP103-01,02,03
EBPS-GRCP-102
EBPS-GRCP-103
EBPS-GRCP-101
P-PS-SWBD020-07
P-PS-SWBD020-08
P-PS-SWBD020-09
PS-RXT-001
PS-CT-001
SAMPLE PUMP
CONTROL PANEL
PS-PAC-001
EBPS-STR-002 (INSTALL
ON STRUT RACK)
EBPS-SF-002
EBPS-SF-001
E303
E
E302
C
E302
B
E302
A
2
P-PS-SWBD020-16
P-PS-SWBD020-19
3
3
OCS-STR-001 (INSTALL ON
STRUT RACK)
P-PS-SWBD020-03
P-OCS-STR001-01
P-EBPS-STR001-01
P-EBPS-STR002-01
P-EBPS-SPCP101-01
P-EBPS-DS102-01
EBPS-DS-102
(INSTALL ON STRUT
RACK)
4
1
ALUMINUM CABLE TRAY SCHEDULE
DESIGNATION TRAY WIDTH LOADING DEPTH METALLIC DIVIDER
PS-CT-001 12-INCH 4-INCH YES (6"P - 6"I/C)
PS-CT-002 18-INCH 4-INCH YES (12"P - 6"I/C)
PS-CT-003 36-INCH 4-INCH YES (34"P - 2"I/C)
PS-CT-004 18-INCH 4-INCH YES (12"P - 6"I/C)
SIDE RAIL HEIGHT
5-INCH
5-INCH
5-INCH
5-INCH
PS-CT-004
LEGEND:
P - POWER CABLES.
I/C - INSTRUMENT AND CONTROL CABLES.
BOND #2 BC2
GROUND CABLE BETWEEN
CABLE TRAY GROUND CABLE
AND STRUCTURAL SUPPORT
E503
A
E503
B
EBPS-IJB-100
P-EBPS-VFD101-02,
P-EBPS-VFD102-02
EBPS-DS-101
2
2
2
2
4
2
CC
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
NORTH
POWER PLAN
SCALE IN FEET
0 2' 4' 8'
GENERAL NOTES:
KEYED NOTES:
1 FOR DUCT BANK CONTINUATION REFER TO DRAWING E101.
REPLACE EXISTING PULL BOX FOR CSO TREATMENT
FACILITY WITH NEW FUSED DISCONNECT. REUSE AND
RE-TERMINATE EXISTING CSO TREATMENT FACILITY FEED
TO LOAD SIDE OF NEW DISCONNECT.
RELOCATE EXISTING SAMPLE PUMP CONTROL PANEL.
RECONNECT CONTROL PANEL TO MATCH EXISTING
INSTALLATION. REFER TO DRAWING E109 FOR EXISTING
LOCATION.
REMOVE EXISTING CABLE SUPPORTS AND EXISTING
ANCHOR BOLTS (2 POSTS WITH BASE PLATE AND CROSS
BRACE AT TOP), FILL IN ANY HOLES LEFT BY ANCHOR BOLTS
WITH EPOXY.
RELOCATE EXISTING SUPPORT (2 POSTS WITH BASE PLATE
AND CROSS BRACE AT TOP), AS SHOWN. USE NEW
STAINLESS STEEL EPOXY ANCHORS WITH 4” MIN EMBED
INTO EXISTING CONCRETE TOPPING SLAB, MATCH EXISTING
BOLT DIAMETER. EXISTING CABLE SADDLES SHALL BE
REUSED. INSTALL NEW #4/0 BC2 GROUND CABLE FROM
RELOCATED SUPPORT TO EXISTING TRANSFORMER
GROUNDING CONDUCTOR, INSTALL HIGH-COMPRESSION
GROUNDING CONNECTION TO BOND CABLES.
REFER TO DRAWING S002 FOR EQUIPMENT ROOM SUPPORT
NOTES.
CABLES SHALL PASS THRU EXISTING TRAY OPENING ON
SOUTH EXTERIOR WALL ABOVE EXISTING ELECTRICAL
EQUIPMENT.
1. REFER TO DRAWING E501 FOR DUCT BANK CONSTRUCTION
DETAILS.
2. ALL BELOW GRADE UTILITIES SHALL BE LOCATED PRIOR TO
EXCAVATION FOR THE ELECTRICAL DUCT BANKS.
3. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR CABLE
SCHEDULE.
4. THE EXISTING PUMP STATION SCREEN ROOM, EXISTING
PUMP STATION WET WELL, EBPS WET WELL AND INFLUENT
CHANNEL ARE A CLASS I, DIV 2 AREA. SEAL CONDUIT AT THE
BOUNDARY OF ALL CLASSIFIED AREAS PER THE NATIONAL
ELECTRIC CODE. EQUIPMENT ENCLOSURES LOCATED ON
THE NORTH SIDE OF THE EBPS SHALL BE SEALED PER THE
TYPICAL EBPS EQUIPMENT INSTALLATION DETAIL ON
DRAWING E502.
CSO-DSW-001
CSO-DSW-002
(EXISTING)
XF-1
(EXISTING)
2
2
EQUIPMENT ROOM
ELECTRICAL ROOM
SWITCHBOARD
(EXISTING)
MCC (EXISTING)
EXISTING VFD1
PS-SWBD-020
PS-XF-040
EBPS-VFD-101
PS-PNL-040
EBPS-PLC-060
P-PS-SWG010-02
EBPS-VFD-102
P-PS-SWBD020-06
P-PS-STR002-01
PS-SF-002
PS-STR-002
PS-ATS-040
3
PS-CT-001
SAMPLE PUMP
CONTROL
PANEL
3
E302
D
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
103.D
WG
5/15/2017 11:42 A
M JR
EC
KA
RT
04/14/17
CABCMK CSH
PUMP STATION POWER
PLAN
ELECTRICAL
95307
E103 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
PS-CU-001
PS-AHU-001
4
4
5
6
P-PS-SWG010-03
AIR TERMINALS
P-PS-SWBD020-17
P-PS-MCC-01
P-PS-XF1-01
P-PS-MCC-02
P-PS-DS102-01
PS-DS-102
6
6
5
P-PS-XF040-01
1
1
P-PS-MCC-03
PS-DS-001
P-PS-DS101-01
P-PS-SWG010-01
7
7
P-SWBD-01
P-PS-SWBD020-01
P-PS-SWBD020-02
EXISTING PUMP
STATION CONTROL
PANEL
PS-RXT-001
E505
AP-PS-SWBD020-04
P-PS-SWBD020-05
EXTEND CONDUCTOR TO
EXISTING PUMP STATION
SWITCHBOARD
P-PS-SWG010-04
P-PS-ATS040-01
PS-HVAC-CP-001
WP
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
NORTH
LIGHTING & SMALL POWER PLAN
PS-SWBD-020
PS-XF-040
SCALE IN FEET
0 2' 4' 8'
GENERAL NOTES:1. REFER TO DRAWING E501 FOR LUMINAIRE
SCHEDULE.
2. LUMINAIRE HEIGHTS SHOWN ARE ABOVE TOP OF
CONCRETE TO BOTTOM OF LUMINAIRE.
LUMINAIRE HEIGHTS ARE BASED ON A HOOK
HEIGHT OF 14'-0" ABOVE TOC. IF A CRANE IS
PROVIDED THAT CONFLICTS WITH INDICATED
MOUNTING HEIGHT, THE REVISED MOUNTING
HEIGHT SHALL BE APPROVED BY ENGINEER AND
PROVIDED AT NO COST TO OWNER.
3. REFER TO CANOPY LUMINAIRE MOUNTING
DETAIL ON DRAWING E503.
4. REFER TO SPECIFICATIONS SECTION 26 05 19
FOR CABLE SCHEDULE.
5. THE EXISTING PUMP STATION SCREEN ROOM,
EXISTING PUMP STATION WET WELL, EBPS WET
WELL AND INFLUENT CHANNEL ARE A CLASS I,
DIV 2 AREA. SEAL CONDUIT AT THE BOUNDARY
OF ALL CLASSIFIED AREAS PER THE NATIONAL
ELECTRIC CODE. EQUIPMENT ENCLOSURES
LOCATED ON THE NORTH SIDE OF THE EBPS
SHALL BE SEALED PER THE TYPICAL EBPS
EQUIPMENT INSTALLATION DETAIL ON DRAWING
E502.
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
104.D
WG
5/15/2017 11:42 A
M JR
EC
KA
RT
04/14/17
CABCMK CSH
EMERGENCY BACKUP
PUMP STATION
LIGHTING & SMALL
POWER PLAN
ELECTRICAL
95307
E104 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
EQUIPMENT ROOM
EBPS-VFD-101
PS-PNL-040
EBPS-PLC-060
TYPE L-1
MOUNT AT
18'-6" TOC (TYP)
EBPS-VFD-102
WP
GFCI
WP
GFCI
P-PS-PNL040-07
P-PS-PNL040-05
KEYED NOTES:
1 INSTALL RECEPTACLE 36-INCHES ABOVE
FINISHED GRADE TO EXISTING EXTERIOR WALL.
CANOPY LIGHT SWITCH SHALL BE INSTALLED
48-INCHES ABOVE STAIR PLATFORM FROM
EQUIPMENT ROOM.
1
1
2
2
3
3
CC
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
NORTH
LIGHTING & SMALL POWER PLAN
SCALE IN FEET
0 2' 4' 8'
GENERAL NOTES:
KEYED NOTES:
1 EXISTING LUMINAIRE SHALL BE RELOCATED TO
NEW STRUCTURAL STEEL CABLE TRAY SUPPORT.
INSTALL LUMINAIRE 12-INCHES BELOW HORIZONTAL
CABLE TRAY SUPPORT. INSTALL NEW NEMA 4
STAINLESS STEEL JUNCTION BOX AT EXISTING
LUMINAIRE LOCATION, EXTEND EXISTING LIGHTING
CIRCUIT WITH SAME SIZED CONDUCTOR IN 3/4-INCH
RGS CONDUIT TO NEW LUMINAIRE LOCATION.
EMERGENCY BALLAST UNITS SHALL BE WIRED
AHEAD OF SWITCH FOR PROPER OPERATION.
1. REFER TO DRAWING E501 FOR LUMINAIRE
SCHEDULE.
2. LUMINAIRE HEIGHTS SHOWN ARE ABOVE THE
FINISHED FLOOR TO BOTTOM OF LUMINAIRE.
3. REFER TO DRAWING E501 FOR INTERIOR STRIP
LUMINAIRE INSTALLATION DETAIL.
4. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR
CABLE SCHEDULE.
5. THE EXISTING PUMP STATION SCREEN ROOM,
EXISTING PUMP STATION WET WELL, EBPS WET
WELL AND INFLUENT CHANNEL ARE A CLASS I, DIV 2
AREA. SEAL CONDUIT AT THE BOUNDARY OF ALL
CLASSIFIED AREAS PER THE NATIONAL ELECTRIC
CODE. EQUIPMENT ENCLOSURES LOCATED ON THE
NORTH SIDE OF THE EBPS SHALL BE SEALED PER
THE TYPICAL EBPS EQUIPMENT INSTALLATION
DETAIL ON DRAWING E502.
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
105.D
WG
5/15/2017 11:42 A
M JR
EC
KA
RT
04/14/17
CABCMK CSH
PUMP STATION
LIGHTING & SMALL
POWER PLAN
ELECTRICAL
95307
E105 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
CSO-DSW-002
(EXISTING)
XF-1
(EXISTING)
EQUIPMENT ROOM
ELECTRICAL ROOM
SWITCHBOARD
(EXISTING)
MCC (EXISTING)
VFD'S
(EXISTING)
PS-SWBD-020
PS-XF-040
EBPS-VFD-101
PS-PNL-040
EBPS-PLC-060
EBPS-VFD-102
PS-ATS-040
TYPE L-3
MOUNT AT 7'-6"AFF
P-PS-PNL040-04
P-PS-PNL040-01
TYPE L-4
MOUNT AT 7'-6"AFF
TYPE L-2
MOUNT AT 9'-0"
AFF (TYP)
TYPE L-3.
MOUNT AT 7'-6"AFF
P-PS-PNL040-03
P-PS-XF040-01
1
2
2
PS-HVAC-CP-001
P-PS-PNL040-06
PS-BACP-001
P-PS-PNL040-02
A
AELEVATION
PS-AIC-001
PS-AIC-002
PS-AIC-003
PS-BACP-001
NOT TO SCALE
2#12, #12 GND, 3/4"C
4#12, 2#12GND, 3/4"C
2#12, #12GND, 3/4"C
2#12, #12GND, 3/4"C
J
S S S
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
NORTH
ENLARGED INST & CONTROL PLAN
PS-SWBD-020
PS-XF-040
SCALE IN FEET
0 2' 4' 8'
GENERAL NOTES:
KEYED NOTES:
1 FOR DUCT BANK CONTINUATION REFER TO
DRAWING E101.
COIL 10-FEET OF SPARE CABLE ON HOOK (NOT
SHOWN FOR CLARITY).
INSTALL ON STAINLESS STEEL STRUT RACK.
1. REFER TO DRAWING E501 FOR DUCT BANK
CONSTRUCTION DETAILS.
2. ALL BELOW GRADE UTILITIES SHALL BE
LOCATED PRIOR TO EXCAVATION FOR THE
ELECTRICAL DUCT BANKS.
3. REFER TO SPECIFICATIONS SECTION 26 05 19
FOR CABLE SCHEDULE.
4. THE EXISTING PUMP STATION SCREEN ROOM,
EXISTING PUMP STATION WET WELL, EBPS WET
WELL AND INFLUENT CHANNEL ARE A CLASS I,
DIV 2 AREA. SEAL CONDUIT AT THE BOUNDARY
OF ALL CLASSIFIED AREAS PER THE NATIONAL
ELECTRIC CODE. EQUIPMENT ENCLOSURES
LOCATED ON THE NORTH SIDE OF THE EBPS
SHALL BE SEALED PER THE TYPICAL EBPS
EQUIPMENT INSTALLATION DETAIL ON DRAWING
E502.
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
106.D
WG
5/15/2017 11:42 A
M JR
EC
KA
RT
04/14/17
CABCMK CSH
EMERGENCY BACKUP
PUMP STATION
INSTURMENTATION &
CONTROL PLAN
ELECTRICAL
95307
E106 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
EQUIPMENT ROOM
EBPS-VFD-101
PS-PNL-040
EBPS-PLC-060
EBPS-GR-101
EBPS-LSL-112 EBPS-LSH-111
EBPS-LIT-111
EBPS-VFD-102
OCS-EF-001
EBPS-SG-004
EBPS-SG-003
EBPS-SG-002
EBPS-SG-001
EBPS-LSH-101
EBPS-STR-001
PS-CT-004
EBPS-SPCP-101
EBPS-GRJB-101
EBPS-GRCP-102
EBPS-GRCP-103
EBPS-GRCP-101
C-EBPS-GRCP-103-02
C-EBPS-GRCP-103-02
C-EBPS-GRCP103-01
C-EBPS-GRCP-101-02
C-EBPS-GRCP-102-02
C-EBPS-GRCP-102-02
C-EBPS-GRCP-102-01
C-EBPS-LS110-01
C-EBPS-SPCP101-01
C-EBPS-LSH111-01
C-EBPS-LSL112-01
I-EBPS-LIT-111-01
C-EBPS-GRCP-101-02
C-EBPS-GRCP-101-01
C-EBPS-SG001-01
C-EBPS-SG002-01
C-EBPS-SG003-01
C-EBPS-SG004-01
C-EBPS-LSH101-01
I-EBPS-LIT101-01
EBPS-LIT-101
PS-CT-003
PS-CT-001
PS-CT-002
PS-RXT-001
EBPS-PJB-100
C-OCS-STR001-01
C-OCS-STR001-02
C-OCS-STR001-03
C-OCS-STR001-04
C-OCS-STR001-05
C-OCS-STR001-06
EBPS-JB-001
EBPS-IJB-100
EBPS-AE-1
A
TO PS-AIC-001
LOCATED IN OFFICE AREA
PVC COATED
RGS COATED
ASECTION
I-PS-AIC003-02
STAINLESS STEEL
CABLE STRAIN
RELIEF
18
"
EXPLOSION PROOF
SEAL FITTING
COMBUSTIBLE
GAS DETECTOR
EBPS-AE-1
18
"
HATCH
EXISTING PUMP STATION
EXTERIOR WALL
4'-0
"
2
2
NOT TO SCALE
INTERIOR
OF WET
WELL
3
OCS-STR-001
EBPS-STR-002
C-EBPS-STR002-01
PS-HVACCP-01
OCS-EF-001
SMOKE DETECTOR
OCS-EF-001
SMOKE DUCT
DETECTOR
SD-EBPS-SF-001
SMD-EBPS-SF-001
EBPS-SF-001
EBPS-SF-002
SMD-PS-PAC-001
SD-PS-PAC-001
C-EBPS-STR001-01,
C-EBPS-STR001-02,
C-EBPS-STR001-03
C-EBPS-IJB100-01
C-EBPS-IJB100-02
E503
AE503
B
REFER TO SECTION B
ON DRAWING E503 FOR
TYPICAL CONDUIT EMBED
IN CONCRETE WALL
SS-OCS-EF-001
C-OCS-STR001-07
C-EBPS-JB001-01
PS-PAC-001
C-EBPS-VFD101-02,
C-EBPS-VFD102-02
S S
S
S
S S
CC
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
NORTH
INST & CONTROL PLAN
SCALE IN FEET
0 2' 4' 8'
GENERAL NOTES:
KEYED NOTES:
1 RELOCATE EXISTING SAMPLE PUMP CONTROL
PANEL. RECONNECT CONTROL PANEL TO MATCH
EXISTING INSTALLATION. REFER TO DRAWING E109
FOR EXISTING LOCATION.
COORDINATE WITH MANUFACTURER FOR
MOUNTING ELEVATION IN SCREEN ROOM LOWER
LEVEL FOR GAS DETECTORS.
GAS DETECTOR MONITORS SHALL BE INSTALLED
ADJACENT TO THE BUILDING ALARM CONTROL
PANEL (STACKED IN A VERTICAL ORIENTATION).
CIRCUITS ROUTED IN (1) 1-INCH CONDUIT BACK TO
PS-BACP-001. REFER TO MOUNTING DETAIL ON
DRAWING E608.
1. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR
CABLE SCHEDULE.
2. WARNING STROBES INSTALLED ON THE EXTERIOR
SIDE OF THE EXISTING PUMP STATION SHALL BE
MOUNTED 7'-6" ABOVE FINISHED INTERIOR FLOOR
ELEVATION.
3. WARNING HORN SHALL BE INSTALLED 8'-0" ABOVE
FINISHED FLOOR.
4. ALL GAS DETECTOR MOUNTING ELEVATIONS SHALL
BE INSTALLED PER MANUFACTURER
RECOMMENDATIONS.
5. THE EXISTING PUMP STATION SCREEN ROOM,
EXISTING PUMP STATION WET WELL, EBPS WET
WELL AND INFLUENT CHANNEL ARE A CLASS I, DIV
2 AREA. SEAL CONDUIT AT THE BOUNDARY OF ALL
CLASSIFIED AREAS PER THE NATIONAL ELECTRIC
CODE. EQUIPMENT ENCLOSURES LOCATED ON
THE NORTH SIDE OF THE EBPS SHALL BE SEALED
PER THE TYPICAL EBPS EQUIPMENT INSTALLATION
DETAIL ON DRAWING E502.
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
107.D
WG
5/15/2017 11:41 A
M JR
EC
KA
RT
04/14/17
CABCMK CSH
PUMP STATION
INSTURMENTATION &
CONTROL PLAN
ELECTRICAL
95307
E107 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
CSO-DSW-002
(EXISTING)
XF-1
(EXISTING)
EQUIPMENT ROOM
ELECTRICAL ROOMSWITCHBOARD
(EXISTING)
MCC (EXISTING)
VFD'S
(EXISTING)
PS-SWBD-020
EBPS-VFD-101
EBPS-VFD-102
PS-SF-002
PS-STR-002
PS-ATS-040
PS-XF-040
PS-PNL-040
EBPS-PLC-060
T-EBPS-PLC060-01
PS-AE-2
I-PS-AIC302-01
PS-AE-3
(MOUNTED BELOW
AT ELEVATION 623'-0" WITHIN
DRY WELL)
PS-IL-4, PS-IL-5, PS-IL-6
SAMPLE PUMP
CONTROL
PANEL
1
PS-AE-4
PS-AE-1
PS-CT-001
PS-AE-5
I-PS-AIT302-03
P-PS-IL4-01, P-PS-IL5-01,
P-PS-IL6-01
I-PS-AIC301-02
PS-AE-6
I-PS-AIC303-01
2
2
2
STAIRWELL(DOWN TO DRY
WELL)
PS-BACP-001
C-PS-BACP001-01,
C-PS-BACP001-02
OFFICE
SCREEN ROOM
I-PS-AIC302-02
PS-T-001
PS-T-002
P-PS-HVACCP1-01, P-PS-HVACCP1-02,
C-PS-HVACCP1-01, C-PS-HVACCP1-02,
C-PS-HVACCP1-03, C-PS-HVACCP1-04,
C-PS-HVACCP1-05, C-PS-HVACCP-06,
C-PS-HVACCP-07
PS-HVAC-CP-01
C-PS-STR002-01,
C-PS-STR002-02,
C-PS-STR002-03
SD-PS-SF-002
SMD-PS-SF-002
I-PS-AIC301-01
PS-AIC-001
PS-AIC-002
PS-AIC-003
3
3
4
4
P-PS-IL1-01,
P-PS-IL2-01,
P-PS-IL3-01
4
PS-IL-1, PS-IL-2, PS-IL-3
C-EBPS-JB001-01
C-PS-GEN090-02
P-PS-HVACCP-01
P-PS-HVACCP-02
P-EBPS-VFD102-02
C-EBPS-VFD102-01
I-EBPS-VFD102-01
I-EBPS-VFD102-02
P-EBPS-VFD101-02
C-EBPS-VFD101-01
I-EBPS-VFD101-01
I-EBPS-VFD101-02
EXISTING
PUMP STATION
CONTROL PANEL
EXISTING RTU
CABINET
VFD'S
(EXISTING)
EXISTING PUMP 1 VFD
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
GENERAL NOTES:1. REMOVE INDICATED EQUIPMENT. ALL CONDUIT AND
CABLE SHALL BE REMOVED BACK TO THE MCC,
SWITCHBOARD OR PANELBOARD BREAKER. FILL IN
ANY PENETRATIONS WHERE CONDUIT WAS
REMOVED.
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
108.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
PUMP STATION
LIGHTING & SMALL
POWER DEMO PLAN
ELECTRICAL
95307
E108 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
REVISION .
AS INDICATED ON BURNS & McDONNELL DRAWING
ONLY ASSUMES RESPONSIBILITY FOR THE CHANGES
SEAL, DATED ,
THE NEWLY APPLIED
THE REGISTRANT OF
4/14/17
E108 C
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
GENERAL NOTES:
KEYED NOTES:
1 REMOVE AND RELOCATE SAMPLE PUMP CONTROL PANEL.
REINSTALL CONTROL PANEL AS INDICATED ON DRAWING
E103. INSTALL CONDUIT AND CABLING TO MATCH EXISTING
INSTALLATION.
1. REMOVE INDICATED EQUIPMENT. ALL CONDUIT AND CABLE
SHALL BE REMOVED BACK TO MCC, SWITCHBOARD OR
PANELBOARD BREAKER. FILL IN ANY PENETRATIONS WHERE
CONDUIT WAS REMOVED.
2. REPLACE ALL BREAKER NAMEPLATES OF REMOVED MCC &
SWITCHBOARD EQUIPMENT WITH NEW NAMEPLATES
LABELED AS "SPARE" REVISE PANELBOARD SCHEDULE,
RELABEL BREAKERS WITH REMOVED EQUIPMENT AS
"SPARE".
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
109.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
PUMP STATION POWER
DEMO PLAN
ELECTRICAL
95307
E109 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
GENERATOR
QUICK-CONNECT
SWITCHGEAR
AHU-1
CONDENSING
UNIT DISCONNECT
SEE PHOTO 1
1
GENERATOR
SWITCH
PHOTO 1
PUMP STATION POWER DEMO PLANNOT TO SCALE
UH-1
DISCONNECT
REVISION .
AS INDICATED ON BURNS & McDONNELL DRAWING
ONLY ASSUMES RESPONSIBILITY FOR THE CHANGES
SEAL, DATED ,
THE NEWLY APPLIED
THE REGISTRANT OF
4/14/17
E109 C
EXISTING INFLUENT
H2S GAS MONITOR
EXISTING GAS MONITOR
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
E101
BSECTIONNOT TO SCALE
P-PS-SWG010-02
DUCT SCHEDULE "PS-EDB-002"
CIRCUIT DESCRIPTION
A1
P-PS-SWG010-02A2
P-PS-GEN090-01A3
P-PS-GEN090-01A4
P-PS-GEN090-01B4
DUCT
(ROW x COLUMN)
P-PS-SWG010-02B1
P-PS-SWG010-02B2
P-PS-GEN090-01B3
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
301.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
DUCT BANK SECTIONS
ELECTRICAL
95307
E301 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
ELECTRICAL DUCT BANKPS-EDB-002
1 2 3 4
A
B
#4/0 BC2
C
D
GENERATORNEW SWBD
SPARE
P-PS-GEN090-01C4
P-PS-SWG010-02C1
P-PS-SWG010-02C2
P-PS-GEN090-01C3
P-PS-GEN090-01D4
P-PS-SWG010-02D1
SPARED2
C-PS-GEN090-03D3
E101
CSECTIONNOT TO SCALE
P-PS-SWG010-02
DUCT SCHEDULE "PS-EDB-003"
CIRCUIT DESCRIPTION
A1
P-PS-SWG010-02A2
P-PS-SWG010-02A3
P-PS-PNL030-32A4
C-PS-GEN090-01,02B4
DUCT
(ROW x COLUMN)
P-PS-SWG010-02B1
P-PS-SWG010-02B2
SPAREB3
ELECTRICAL DUCT BANKPS-EDB-003
1 2 3 4
A
B
#4/0 BC2
C
480V
AUX PWR
GENERATOR
NEW SWBD
SPARE
SPAREC4
P-PS-SWG010-02C1
P-PS-SWG010-02C2
SPAREC3
GENERATOR
CONTROL
E101
A, DSECTIONNOT TO SCALE
P-PS-SWG010-01
DUCT SCHEDULE "PS-EDB-001"
CIRCUIT DESCRIPTION
A1
P-PS-SWG010-01A2
P-PS-SWG010-04A3
P-PS-SWG010-03A4
P-PS-SWG010-03B4
DUCT
(ROW x COLUMN)
P-PS-SWG010-01B1
P-PS-SWG010-01B2
P-PS-SWG010-04B3
ELECTRICAL DUCT BANKPS-EDB-001
1 2 3 4
A
B
#4/0 BC2
C
D
UTILITY
TRANSFORMER
EXISTING SWBD
SPARE
P-PS-SWG010-03C4
P-PS-SWG010-01C1
P-PS-SWG010-01C2
SPAREC3
SPARED4
P-PS-SWG010-01D1
SPARED2
SPARED3
CSO EFF PUMPSCSOTF MCC
5 6
P-PS-XF1-01A5
P-PS-XF1-01A6
P-PS-XF1-01B5
P-PS-XF1-01B6
P-PS-XF1-01C6
P-PS-XF1-01C5
P-PS-XF1-01D6
P-PS-XF1-01D5
E101
ESECTIONNOT TO SCALE
ELECTRICAL DUCT BANKPS-EDB-004
P-PS-SWG010-03
DUCT SCHEDULE "PS-EDB-004"
CIRCUIT DESCRIPTION
A1
P-PS-XF1-01A2
P-PS-XF1-01A3
DUCT
(ROW x COLUMN)
1 2 3
A
#4/0 BC2
B
C
D
CSO EFF PUMPS UTILITY
TRANSFORMER
SPARE
P-PS-SWG010-03B1
P-PS-XF1-01B2
P-PS-XF1-01B3
P-PS-SWG010-03C1
P-PS-XF1-01C2
P-PS-XF1-01C3
SPARED1
P-PS-XF1-01D2
P-PS-XF1-01D3
E101
FSECTIONNOT TO SCALE
ELECTRICAL DUCT BANKPS-EDB-005
P-PS-SWG010-01
DUCT SCHEDULE "PS-EDB-005"
CIRCUIT DESCRIPTION
A1
P-PS-SWG010-01A2
P-PS-SWG010-04A3
DUCT
(ROW x COLUMN)
1 2 3
A
#4/0 BC2
B
C
D
EXISTING SWBD CSOTF MCC
SPARE
P-PS-SWG010-01B1
P-PS-SWG010-01B2
P-PS-SWG010-04B3
P-PS-SWG010-01C1
P-PS-SWG010-01C2
SPAREC3
P-PS-SWG010-01D1
SPARED2
SPARED3
E101
GSECTIONNOT TO SCALE
ELECTRICAL DUCT BANKPS-EDB-006
FUTURE UTILITY
DUCT SCHEDULE "PS-EDB-006"
CIRCUIT DESCRIPTION
A1
FUTURE UTILITYA2
FUTURE UTILITYA3
DUCT
(ROW x COLUMN)
1 2 3
SPARE
A
B
4 5
FUTURE UTILITYA4
SPAREA5
FUTURE UTILITYB1
FUTURE UTILITYB2
FUTURE UTILITYB3
FUTURE UTILITYB4
SPAREB5
FUTURE UTILITY
TRANSFORMER
GENERATOR CONTROL
GENERAL NOTES:1. ALL CONDUIT SHALL BE 4-INCH UNLESS NOTED
OTHERWISE.
SPARE
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
302.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
CABLE TRAY SECTIONS
ELECTRICAL
95307
E302 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
E102
ASECTION
E102
BSECTION
E102
CSECTION
E103
DSECTION
PS-CT-003
BRIDGE CRANE
EL 673'-0"
EL 674'-0"
EL 660'-0"
PS-CT-002
PS-CT-001
PS-CT-003
PS-CT-002
EL 673'-0"
EL 674'-0"
EL 660'-0"
PS-CT-002
PS-CT-003
PS-CT-001
PS-CT-004
EL 670'-0"
EL 673'-0"
EL 674'-0"
EL 674'-4"
EL 670'-10"
EXISTING
DOOR
DUCT BANK
EL 683'-4"
EL 660'-0"
EXISTING XF-1
(TRANSFORMER SHOWN
IS NOT TO SCALE)
EL 683'-4"
EL 679'-8"
EL 662'-4"
EXISTING CONDUITS
SHALL BE CUT FLUSH
WITH WALL ON THE
INTERIOR AND
EXTERIOR (INSTALL
NON-SHRINK GROUT
IN CONDUITS TO FILL VOID)
CSO-DSW-0011
'-0
"
1 COORDINATE EXACT HEIGHT OF RELOCATED
SUPPORT TO PREVENT SAG OF UTILITY SECONDARY
CONDUCTOR. REFER TO DRAWING E103 FOR
SUPPORT LOCATIONS AND ADDITIONAL DETAILS.
PVC COATED RGS CONDUIT SHALL BE STUBBED OUT
OF DUCT BANK 12-INCHES THEN TRANSITION TO
RGS.
CONTRACTOR TO CONSTRUCT STAINLESS STEEL
STRUT RACK FOR SUPPORT OF VERTICAL CONDUITS
FROM DUCT BANK. CONDUITS SHALL BE
SUPPORTED AT A MINIMUM OF 2 PLACES ON
VERTICAL RISER.
DUCT BANK SHALL EXTEND A MINIMUM OF 6-INCHES
ABOVE TOP SLAB OF EXISTING CONCRETE.
INSTALL CONDUCTORS TO EXISTING SWITCHBOARD
THRU EXISTING CABLE TRAY.
DISCONNECT SHALL BE INSTALLED ON A STAINLESS
STEEL STRUT RACK.
KEYED NOTES
1
PVC COATED
RGS
2
3
2
3
4
4
TYPE L-1
(REFER TO DRAWING E104
FOR ADDITIONAL INFORMATION)
EXISTING CABLE TRAY
5
5
6
6
ROXTEC UNIT
(INSTALLED IN REMOVED WINDOW)
REFER TO DWGS E504-E507
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
303.D
WG
4/20/2017 2:05 P
M LP
IR
TLE
04/14/17
CABCMK CSH
CABLE TRAY SECTIONS
& EQUIPMENT
ELEVATIONS
ELECTRICAL
95307
E303 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
E102
ESECTION
PS-CT-003
EL 670'-0"
EL 673'-0"
PS-CT-004
EL 660'-0"
EBPS-
GRCP-
101
EBPS-
GRCP-
102
EBPS-
GRCP-
103
EBPS-GRJB-101
EBPS-SPCP-101
EBPS-PJB-100
EBPS-IJB-100
PS-CT-002
EL 679'-8"
UTILITY
MAIN
FEEDERS
TIE
FEEDER
FEEDERS
SWITCHGEAR (PS-SWG-010) ELEVATION
FEEDER
BREAKERS
MAIN
BREAKER
SWITCHBOARD (PS-SWBD-010) ELEVATIONNOT TO SCALE
GENERATOR
MAIN
WEATHERPROOF
ENCLOSURE FLOOR
EQUIPMENT PAD
NOT TO SCALE
*LOOKING NORTH WITHIN EQUIPMENT ROOM.
FUTURE
UTILITY
MAIN
*LOOKING NORTH WITHIN SWITCHGEAR ENCLOSURE.
FEEDERS
EBPS-SF-001
EBPS-SF-002
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
REV
TYPICAL DUCT BANK INSTALLATION DETAIL
WARNING TAPE
12" (M
IN
)
30"
KEYED NOTES:
30-INCHES MINIMUM UNLESS INDICATED OTHERWISE TO AVOID BELOW
GRADE PIPING OR BELOW GRADE OBSTRUCTIONS.
DUCT BANK SHALL BE SLOPED TOWARDS HAND HOLE TO PROVIDE
PROPER DRAINAGE.
1
2
1 2
FINISHED GRADE
REFER TO PLANS FOR
ACTUAL NUMBER AND
SIZE OF CONDUITS
NOT TO SCALE
TYPICAL BURIED CONDUIT DETAILNOT TO SCALE
12" (M
IN
)
30"
FINISHED GRADE
WARNING TAPE
CONDUIT (TYP)
PVC COATED
RGS NIPPLE
INTERIOR
WALL
FINISHED
FLOOR
TYPICAL EXTERIOR STUB-UP DETAILNOT TO SCALE
TYPICAL EXTERIOR EXPOSED CONDUITTHROUGH CONCRETE/CMU WALL DETAIL
NOT TO SCALE
PVC COATED
RGS NIPPLE
RGSRGS
12" M
IN
PVC COATED RGS ELBOW
EXTERIOR INTERIOR
RGS WITH PVC COATED
RGS NIPPLE FOR
LENGTH AS REQUIRED
FINISH
GRADE
SCHEDULE
40 PVC
PVC COATED
RGS
DETAIL 1NOT TO SCALE
EBPS LIFT STATION AND VALVE VAULT CLASSIFIED ENVELOPENOT TO SCALE
PARTIAL LEGEND
CLASS 1, DIVISION 2
NOT TO SCALE
3' RADIUS FROM VENT
GRADE
TYPICAL VALVE VAULT UNVENTILATED, VENTILATED WET WELL,& VENTILATED DIVERSION CHAMBER CLASSIFIED ENVELOPE
GENERAL NOTE:1. PROVIDE ALL NECESSARY FITTINGS AND OTHER ASSOCIATED
EQUIPMENT AS REQUIRED BY NEC TO MEET ELECTRICAL
INSTALLATION IN CLASSIFIED SPACES.
RGS COUPLING (TYP)
RGS CONDUIT
ELBOW (TYP)
ENCASE WITH A
MINIMUM OF 3" CONCRETE,
AS SHOWN, FOR STABILITY.
RGS COUPLING OR
ADAPTER, AS APPLICABLE (TYP)
SCHED. 40 PVC CONDUIT,
AS REQUIRED.
24"R MIN.
TOP OF CONCRETE
PVC COATED
RGS CONDUIT (TYP)
12"
04/14/17
CABCMK CSH
ELECTRICAL DETAILS
SHEET 1
ELECTRICAL
95307
E501 0
770-587-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
EXISTING
BUILDING WALL
E101
CONCRETE
TYPICAL DUCT BANK CONSTRUCTION SECTION
GENERAL NOTES:
QUANTITY OF CONDUITS SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY.
REFER TO PLANS AND DUCT BANK SECTIONS FOR ACTUAL CONDUIT
QUANTITIES REQUIRED.
WHEN TERMINATING AT HANDHOLES CONTRACTOR SHALL EMBED
LONGITUDINAL DUCT BANK REINFORCEMENT 3" MINIMUM INTO PRECAST
HANDHOLE WALLS WITH HILTY150 INJECTION ADHESIVE OR APPROVED
EQUAL. TYPICAL THREE (3) BARS MINIMUM TOP AND BOTTOM.
INSTALL CONDUIT SPACERS EVERY 6-FEET TO MAINTAIN DUCT SPACING.
DUCT SPACERS NOT SHOWN FOR CLARITY. REFER TO SPECIFICATIONS
FOR ADDITIONAL REQUIREMENTS.
DUCT BANK CONCRETE REQUIREMENTS SHALL BE 3000PSI MINIMUM AS
SPECIFIED IN DIVISION 03.
1.
2.
3.
4.
7 1/2"
NOT TO SCALE
3 1/2" MIN.
3 1/2" MIN.
7 1/2"
#4/0 BC2
#5 BARS @ 8"
MAX SPACING
4" CONDUIT (TYP)
(UNLESS NOTED OTHERWISE)
#3 U BARS @ 12"
CENTERS, TOP &
BOTTOM, WITH 18" LAP
TYPICAL HAND HOLE DETAIL
7.5"
7.5"
6" (MIN)
SUMP PULLING IRON
TYPICAL HAND HOLE CABLE RACK DETAIL
CONCRETE WALL
STAINLESS STEEL
ANCHOR (MIN OF 5)
STAINLESS STEEL
HEX HEAD CAP
SCREW
CABLE SADDLE
(NUMBER OF SADDLES
SHOWN IS FOR
ILLUSTRATION
PURPOSES ONLY)
COORDINATE DUCT BANK
ENTRY ELEVATION TO
PROVIDE REQUIRED
DUCT BANK SLOPE AND
AVOID OTHER INFRASTRUCTURE
FINISHED GRADE
CABLE RACK
(REFER TO DETAIL
THIS DRAWING)
NUMBER OF
DUCTS AS
REQUIRED
6" MIN.
COMPACTED
GRANULAR FILL
MANHOLE COVER
NOT TO SCALE
NOT TO SCALE
LUMINAIRE SCHEDULELOCATION LUMINAIRE
TYPEACCEPTABLE
MANUFACTURERCATALOG NUMBER CONSTRUCTION MOUNTING TYPE OF FIXTURE OPTICS LAMP ACCESSORIES/NOTES
EMERGENCY
BACKUP PUMP
STATION
L-1 GE LIGHTING ABR1-1-2-H-47-1-N-N-23-
A-N-R
NEMA 4X
CORROSION
RESISTANT
HOUSING
PENDANT
MOUNT 18'-0"
AFF
INDUSTRIAL HIGH
BAY
WIDE 120°
GLASS, 70CRI,
4000K
2 LED
MODULES
1. TOTAL WATTAGE PER FIXTURE: 178 WATTS
2. LUMINAIRE SHALL INCLUDE ALL NECESSARY
ACCESSORIES FOR PENDANT MOUNT TO A 3/4"
RGS CONDUIT.
EQUIPMENT
ROOM
L-2 GE LIGHTING ALRI-1-1-V-47-1-4-S-N-N-
ST-K-N-W
FIBERGLASS
HOUSING
INDUSTRIAL LOW
BAY
70 CRI, 4000K LED 1. TOTAL WATTAGE PER FIXTURE: 55 WATTS
EQUIPMENT
ROOM
L-3 LITHONIA
LIGHTING
EU2 LED M12 THERMOPLASTIC
HOUSING
EMERGENCY WALL
PACK
TWO
ADJUSTABLE
LED LAMPS
1. TOTAL WATTAGE PER FIXTURE: 3.6 WATTS
2. 90 MINUTES OF EMERGENCY POWER
EQUIPMENT
ROOM
L-4 LITHONIA
LIGHTING
ECR LED M6 THERMOPLASTIC
HOUSING WITH
RED EXIT SIGN
PENDANT
MOUNT 18'-0"
AFF
EMERGENCY WALL
PACK AND EXIT SIGN
COMBO
TWO
ADJUSTABLE
LED LAMPS
1. TOTAL WATTAGE PER FIXTURE: 18 WATTS
2. 90 MINUTES OF EMERGENCY POWER
12" (MIN)
CAP FOR
FUTURE USE
DUCTBANK STUBOUT DETAIL FOR FUTURE UTILITY SERVICENOT TO SCALE
CONDUIT SHALL BE INSTALLED
UP TO CABLE TRAY
PVC COATED RGS SHALL BE
EXTENDED 12 INCHES OUT OF DUCT
BANK THEN TRANSITION TO RGS
#4/0 BC2, 1" SCHED 40 PVC
UP TO CABLE TRAY
INTERIOR STRIP LUMINAIRE INSTALLATION DETAIL
LUMINAIRE
EXISTING
WOOD ROOF
TRUSSES
INSTALLATION NOTE:1. EXISTING WOODEN ROOF TRUSSES ARE ON 2-FOOT CENTERS.
2. STRUT SUPPORT SHALL SPAN A MINIMUM OF 3 TRUSSES. INSTALL
ANCHOR INTO EXISTING WOODEN TRUSS (MINIMUM 3).
NOT TO SCALE
2'-0" 2'-0"
1/2" PLYWOOD
RGS CONDUIT
GALV. STRUT
SUPPORT
CONDUIT
CLAMP
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
REV
04/14/17
CABCMK CSH
DETAILS SHEET 2
ELECTRICAL
95307
E502 0
770-587-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
30"
18"
TYPICAL GROUNDING INSTALLATION DETAIL
COPPER GROUND CABLE
FINISHED GRADE EXOTHERMIC WELD
(TYP OF ALL GROUND RODS)
REFER TO DETAIL THIS DRAWING
STRANDED BARE SOFT DRAWN COPPER
COUNTERPOISE SIZE AS INDICATED
EXOTHERMIC WELDED
CONNECTION (CADWELD
OR EQUIVALENT)
3/4" X 10'-0"
COPPERCLAD STEEL
GROUND ROD
TYPICAL GROUND ROD CONNECTION
TYPICAL EXOTHERMIC WELDS
3/4" DIA X 10'-0" COPPER CLAD
STEEL SECTIONAL GROUND ROD
EXOTHERMIC WELD
GROUND CONNECTION
COPPER
GROUND
CABLE
EXOTHERMIC WELD
GROUND CONNECTION
EXOTHERMIC WELD
COPPER
GROUND
CABLE
COPPER GROUND CABLE
EXOTHERMIC WELD
GROUND CONNECTION
GROUND ROD
EXOTHERMIC WELD
GROUND CONNECTON
COPPER GROUND CABLE
GROUND ROD
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
TYPICAL CABLE TRAY GROUNDING
MOUNT BOLT HEAD
TO INSIDE WALL
OF CABLE TRAY
ONE OR MORE
CABLE TRAYS (AS
INDICATED ON PLANS)
CABLE TRAY
GROUND
CABLE #2 AWG
BURNDY CABLE TRAY
GROUND CLAMP
OR EQUAL
#4/0 BC2 BETWEEN TRAYS AWG
GROUND CABLE TO GROUND
SYSTEM AS SHOWN ON PLANS
xx
xx
x x
xxxx
xxxx
xxxx
x
x xx
xx
xx xx
xx
xx
x
x
x
1'-6" MAX (TYP)
(T
YP
)
3'-0" M
AX
30" MIN
TYPICAL FENCE GROUNDING
GROUND ROD (TYP)
GATE FENCE
FLEXIBLE COPPER
BRAID STRAPS
BURNDY TYPE GAR GROUNDING
CONNECTOR FOR ROUND POST
OR APPROVED EQUAL
EXOTHERMIC WELDED
GROUNDING CONNECTORS
(TYP)
SPLIT BOLT OR
COMPRESSION-TYPE
CONNECTORS (TYP)
GROUND CORNER
POSTS, END POSTS &
EVERY FIFTH LINE POST
NO. 2 AWG BARE COPPER
RISERS (WEAVE THRU
FENCE FABRIC)
NO. 4/0 AWG BARE
COPPER STRANDED
GROUND CABLE
NOT TO SCALE
NOT TO SCALE
6'-0" M
AX
IM
UM
TYPICAL EQUIPMENT INSTALLED ON STEEL COLUMN DETAILNOT TO SCALE
STAINLESS STEEL
STRUT SUPPORT
WITH STAINLESS STEEL
SUPPORT HARDWARE
ELECTRICAL ENCLOSURE
(ENCLOSURE SIZE VARIES)
6'-0" M
AX
IM
UM
ENCLOSURE
STAINLESS STEEL
THREADED ROD (TYP)
A
TOP OF
CONCRETE
TOP OF
CONCRETE
AELEVATIONNOT TO SCALE
STEEL SUPPORT COLUMN
GROUND TAB
(PROVIDED BY
STEEL FABRICATOR)
#4/0 BC2
1"C (SCHED 40)
GROUT
FINISHED
FLOOR
PIPE/CABLE TRAY
SUPPORT
TYPICAL STRUCTURAL COLUMN/CABLE TRAYSUPPORT GROUNDING DETAIL
NOT TO SCALE
TO GROUND
GRID
12"
BRASS SERVIT
POST (UL LISTED)
(INSTALL THRU
PREDRILLED GROUND
TAB)
EXPLOSION PROOF
SEAL FITTING WITH DRAIN
PVC COATED
RGS TO WET WELL
MANUFACTURER
SUPPLIED CABLE
STAINLESS STEEL
CABLE GLAND
24"
STAINLESS STEEL
CABLE GLAND
NEMA 4X STAINLESS
STEEL ENCLOSURE
(INSTALLED ON STAINLESS
STEEL STRUT RACK)
UP TO CABLE TRAY
18"
TYPICAL EBPS EQUIPMENT INSTALLATION DETAILNOT TO SCALE
TOP OF
CONCRETE
MYERS HUB
CABLE TRAY
INSULATED BUSHING
CABLE TRAY CLAMP, STEEL AND/OR MALLEABLE IRON.
FOR PERPENDICULAR (90°) CONNECTION, USE TYPE
SIMILAR TO THAT SHOWN. FOR CONNECTION AT ANGLES
OTHER THAN 90°, USE SWIVEL-TYPE CLAMPS.
TYPICAL CABLE TRAY/CONDUIT INSTALLATION DETAILNOT TO SCALE
RIGID METALLIC
CONDUIT (TYP)
CONTRACTOR TO INSTALL
METALLIC DIVIDER PLATE IF
REQUIRED TO SEPARATE
CONTROL/INSTRUMENTATION
CABLES FROM POWER CABLES
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
503.D
WG
4/20/2017 2:04 P
M LP
IR
TLE
04/14/17
CABCMK CSH
DETAILS SHEET 3
ELECTRICAL
95307
E503 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
TYPICAL SUBMERSIBLE LEVEL TRANSDUCER MOUNTING DETAILNOT TO SCALE
24"
CONDUIT, CONTINUED
TO JUNCTION BOX
PIPE SUPPORT AND CLAMP
GUIDED WAVE RADAR LEVEL
TRANSDUCER (REFER TO
SPECIFICATIONS FOR LENGHT OF PROBE)
ALUMINUM CORD GRIP
WITH BASKET SUPPORT GRIP
LIQUID-TIGHT
FLEXIBLE CONDUIT
4-INCH SCHEDULE 80 PVC
PERFORATED PIPE
KEYED NOTES:
PIPE CLAMPS SHALL BE INSTALLED TO SECURE THE STILLING WELL TO WALL. ALL
HARDWARE SHALL BE STAINLESS STEEL INCLUDING WALL ANCHORS.
NONSHRINK GROUT SHALL BE INSTALLED.
STILLING WELL SHALL HAVE 3/4-INCH HOLES DRILLED ON OPPOSITE SIDES OF THE PIPE
SPACED 6-INCHES APART FOR THE FULL LENGTH OF PIPE.
1
2
GENERAL NOTE:1. THIS DETAIL IS SHOWN FOR WET WELL OR CHANNEL INSTALLATIONS. PIPING AND SUPPORTS
SHALL BE PROVIDED BY CONTRACTOR. REFER TO PLANS FOR MOUNTING LOCATIONS AND
CONDUIT ROUTING.
1
2
4" ANSI CLASS
150 STAINLESS
STEEL FLANGE
4-INCH 316 STAINLESS
STEEL, SCHEDULE 40 PIPE
WALL COLLAR, LOCATE
IN CENTER OF TOP SLAB
MANUFACTURER
PROVIDED CABLE
STAINLESS STEEL
STRUT SUPPORT
PVC COATED
RGS CONDUIT
INSTALLED WITHIN
WET WELL
TYPICAL CABLE SUPPORT DETAIL WITHIN WET WELLNOT TO SCALE
TO EQUIPMENT
ENCLOSURE
18"
STAINLESS STEEL SUPPORT CHANNEL
(STAINLESS STEEL HARDWARE)
TOP OF WET WELL
MOUNT SUPPORT HOOK FOR PUMP CABLE ON OPPOSITE SIDE OF
HATCH HINGES.
STAINLESS STEEL STRAIN RELIEF GRIP. 10-FEET OF COILED
(SPARE) CABLE NOT SHOWN FOR CLARITY.
STAINLESS STEEL CONDUIT SUPPORT (SUPPORT AS REQUIRED
PER NEC).
MANUFACTURER SUPPLIED CABLE.
CONDUIT SHALL NOT SPAN MORE THAN 24-INCHES (MAX)
WITHOUT SUPPORT. A MINIMUM OF 1 SUPPORT SHALL BE
INSTALLED IF THE CONDUIT SPANS LESS THAN 12-INCHES WITHIN
THE INTERIOR OF THE WET WELL.
1
KEYED NOTES:
1
4
3
2
2
3
4
PVC COATED RGS
CONDUIT BUSHING
HATCH
STAINLESS STEEL
BRACKET (SIZE
AS REQUIRED)
STAINLESS
STEEL HOOK
STAINLESS STEEL
THREADED ROD (TYP)
STRAIN RELIEF FITTING
24" (MAX)
5
5
CONCRETE BEAM
AROUND HATCH OPENING
1'-0"
3" (TYPICAL SPACING
BETWEEN CONDUITS)
3" (TYPICAL SPACING
BETWEEN CONDUITS)
3/4" PVC COATED
RGS CONDUIT (TYP)
2'-0"
4 1/2"
1'-0"
1'-0"
3/4" PVC COATED
RGS CONDUIT (TYP)
E102
ASECTION6'
SCALE IN FEET
0 2' 4'
HATCH HATCH
2"
12"
3'-0"
6'-0"
18"
TOC EL. 660'-0"
E102
BSECTION
SCALE IN FEET
0 1' 2' 4'
3/4" PVC COATED
RGS CONDUIT (TYP)
1'-0"
1'-0"
C
NOT TO SCALE
SECTION
C
C
TYPICAL CANOPY LUMINAIREMOUNTING DETAIL
NOT TO SCALE
ROOF STEEL
STRUTS
CLAMPED TO
STRUCTURAL
STEEL
LUMINAIRE AS SPECIFIED
MOUNTING HEIGHT
AS NOTED ON PLAN
PURLIN
RGS STRUT SUPPORT
(TYP OF 2)
CONDUIT CLAMP
(TYP OF 2)3/4" RGS
CONDUIT (TYP)
TEE FITTING
3
OPEN BOTTOM
3
All rights reserved. U
nauthorized reproduction, use
or disclosure to third parties is strictly forbidden.
烙克赛克保留所有权利。未经授权严禁复制,
使用以及向第三方泄漏。
RTD Version No: 4.1.1.2665
Cutout Detail
Frame: GH 6+6x3 FL100 AISI316 Solution: 1
Citico Pump Station
Casey Behrends 2017-02-22 [93.96]
Weight
Rev
TotWeight
Roxtec Art No
Project
Format
Created Date
Roxtec Packing Material
Responsible
Client
QtyItem
Drawing number
2017-03-10
Modify Date
Sheet No
NTS
PS-RXT-001
Location/ Sublocation
Transit name
42.6
mm [ "] Kg [lb]
1/5
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
504.D
WG
4/20/2017 2:04 P
M LP
IR
TLE
04/14/17
CABCMK CSH
ELECTRICAL DETAILS
SHEET 4
***FILL IN DISCIPLINE***
95307
E504 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
All rights reserved. U
nauthorized reproduction, use
or disclosure to third parties is strictly forbidden.
烙克赛克保留所有权利。未经授权严禁复制,
使用以及向第三方泄漏。
RTD Version No: 4.1.1.2665
MODULE WITH CABLE SPARE MODULE SOLID MODULEMODULE WITH PIPE
CUTOUT TO FIT SOLUTION BOLTING 408.5x475 [16.083"x18.701"]
Detail Drawing
Solution: 1
21.4 [47.18]105511GH 6+6x3 FL100 AISI31611
0.1 [0.31]RM00100401000RM 40 21.5-34.5 [0.846"-1.358"]392
0.1 [0.18]RM00100301000RM 30 10-25 [0.394"-0.984"]363
0.1 [0.15]RM00120401000RM 20W40 3.5-16.5 [0.138"-0.650"]424
0.1 [0.26]RM00310121000RM 10/0x1215
0.8 [1.76]ARW0001201021Wedge 120 AISI 31666
0.1 [0.22]ASP0001200021Stayplate 120 AISI 316377
Citico Pump Station
Casey Behrends 2017-02-22 [93.96]
Weight
Rev
TotWeight
Roxtec Art No
Project
Format
Created Date
Roxtec Packing Material
Responsible
Client
QtyItem
Drawing number
2017-03-10
Modify Date
Sheet No
NTS
PS-RXT-001
Location/ Sublocation
Transit name
42.6
mm [ "] Kg [lb]
2/5
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
505.D
WG
4/20/2017 2:04 P
M LP
IR
TLE
04/14/17
CABCMK CSH
ELECTRICAL DETAILS
SHEET 5
***FILL IN DISCIPLINE***
95307
E505 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
E103
AELEVATIONNOT TO SCALE
E506
1
E507
E506
2
All rig
hts re
se
rve
d. U
na
uth
orize
d re
pro
du
ctio
n, u
se
or d
isclo
su
re
to
th
ird
p
artie
s is strictly fo
rb
id
de
n.
烙克
赛克
保留
所有
权利
。未
经授
权严
禁复
制,
使用
以及
向第
三方
泄漏
。
MODULE WITH CABLE SPARE MODULE SOLID MODULEMODULE WITH PIPE
RTD Version No:
Pos Cable IDModule Type
Cable Type Cable Category OD
( mm/ [ "] )
Name
4.1.1.2665
A3:13 RM 20W40 3.5-16.5 [0.138"-0.650"]
A3:12 5500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:11 4500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:10 3500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:9 29500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:8 28500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:7 27500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:6 26500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:5 25500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:4 24500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:3 23500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:2 22500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A3:1 21500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A2:6 RM 20W40 3.5-16.5 [0.138"-0.650"]
A2:5 RM 40 21.5-34.5 [0.846"-1.358"]
A2:4 9500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A2:3 8500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A2:2 7500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A2:1 6500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
A1:31 RM 10/0x12
A1:30 RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:29 RM 30 10-25 [0.394"-0.984"]
A1:28 RM 40 21.5-34.5 [0.846"-1.358"]
A1:27 753/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:26 743/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:25 733/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:24 723/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:23 713/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:22 703/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:21 693/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:20 683/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:19 673/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:18 663/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:17 653/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:16 643/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:15 1153/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:14 1143/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:13 1133/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:12 1123/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:11 1113/C #10 PWR 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:10 1103/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:9 1093/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:8 1083/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:7 1073/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:6 1063/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:5 1053/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:4 1043/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:3 1033/C #12 PWR 10.7 [0.420"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
A1:2 763/C #6 PWR 18.3 [0.720"]
RM 30 10-25 [0.394"-0.984"]
A1:1 633/C #1 PWR 27.9 [1.100"]
RM 40 21.5-34.5 [0.846"-1.358"]
3/5
Rev
TotWeightProject
Format
Created DateResponsible
Client
Drawing number
Modify Date
Sheet No
NTS
Location/ Sublocation
Transit name
Citico Pump Station
Casey Behrends 2017-02-22 2017-03-10
PS-RXT-001
[93.96]
42.6
A3A2A1
A3A2A1
B3B2B1
OPENING TABLE CONTINUE ON THE NEXT PAGE
All rig
hts re
se
rve
d. U
na
uth
orize
d re
pro
du
ctio
n, u
se
or d
isclo
su
re
to
th
ird
p
artie
s is strictly fo
rb
id
de
n.
烙克赛克保留所有权利。未经授权严禁复制,
使用以及向第三方泄漏。
MODULE WITH CABLE SPARE MODULE SOLID MODULEMODULE WITH PIPE
RTD Version No:
Pos Cable IDModule Type
Cable Type Cable Category OD
( mm/ [ "] )
Name
4.1.1.2665
B2:24 9112/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
B2:23 9012/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
B2:22 8912/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
B2:21 889/C CNTRL 17.5 [0.690"]
RM 30 10-25 [0.394"-0.984"]
B2:20 879/C CNTRL 17.5 [0.690"]
RM 30 10-25 [0.394"-0.984"]
B2:19 865/C CNTRL 14.5 [0.570"]
RM 30 10-25 [0.394"-0.984"]
B2:18 855/C CNTRL 14.5 [0.570"]
RM 30 10-25 [0.394"-0.984"]
B2:17 845/C CNTRL 14.5 [0.570"]
RM 30 10-25 [0.394"-0.984"]
B2:16 835/C CNTRL 14.5 [0.570"]
RM 30 10-25 [0.394"-0.984"]
B2:15 797/C CNTRL 15.5 [0.610"]
RM 30 10-25 [0.394"-0.984"]
B2:14 787/C CNTRL 15.5 [0.610"]
RM 30 10-25 [0.394"-0.984"]
B2:13 777/C CNTRL 15.5 [0.610"]
RM 30 10-25 [0.394"-0.984"]
B2:12 1539/C CNTRL 17.5 [0.690"]
RM 30 10-25 [0.394"-0.984"]
B2:11 1529/C CNTRL 17.5 [0.690"]
RM 30 10-25 [0.394"-0.984"]
B2:10 1519/C CNTRL 17.5 [0.690"]
RM 30 10-25 [0.394"-0.984"]
B2:9 15012/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
B2:8 14912/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
B2:7 12812/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
B2:6 1269/C CNTRL 17.5 [0.690"]
RM 30 10-25 [0.394"-0.984"]
B2:5 1235/C CNTRL 14.5 [0.570"]
RM 30 10-25 [0.394"-0.984"]
B2:4 1225/C CNTRL 14.5 [0.570"]
RM 30 10-25 [0.394"-0.984"]
B2:3 1187/C CNTRL 15.5 [0.610"]
RM 30 10-25 [0.394"-0.984"]
B2:2 1177/C CNTRL 15.5 [0.610"]
RM 30 10-25 [0.394"-0.984"]
B2:1 1167/C CNTRL 15.5 [0.610"]
RM 30 10-25 [0.394"-0.984"]
B1:34 RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:33 RM 30 10-25 [0.394"-0.984"]
B1:32 100TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:31 99TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:30 98TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:29 97TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:28 96TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:27 95TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:26 94TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:25 93TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:24 823/C CNTRL 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:23 813/C CNTRL 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:22 803/C CNTRL 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:21 148TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:20 147TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:19 146TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:18 145TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:17 144TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:16 143TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:15 142TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:14 141TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:13 140TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:12 139TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:11 137TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:10 136TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:9 135TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:8 134TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:7 133TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:6 132TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:5 1213/C CNTRL 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:4 1203/C CNTRL 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:3 1193/C CNTRL 11.9 [0.470"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:2 101TSP 7.6 [0.300"]
RM 20W40 3.5-16.5 [0.138"-0.650"]
B1:1 9212/C CNTRL 19.3 [0.760"]
RM 30 10-25 [0.394"-0.984"]
4/5
Rev
TotWeightProject
Format
Created DateResponsible
Client
Drawing number
Modify Date
Sheet No
NTS
Location/ Sublocation
Transit name
Citico Pump Station
Casey Behrends 2017-02-22 2017-03-10
PS-RXT-001
[93.96]
42.6
A3A2A1
B3B2B1
B3B2B1
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
506.D
WG
4/20/2017 2:04 P
M LP
IR
TLE
04/14/17
CABCMK CSH
ELECTRICAL DETAILS
SHEET 6
***FILL IN DISCIPLINE***
95307
E506 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
E505
1DETAILNOT TO SCALE
E505
2DETAILNOT TO SCALE
All rights reserved. U
nauthorized reproduction, use
or disclosure to third parties is strictly forbidden.
烙克
赛克
保留
所有
权利
。未
经授
权严
禁复
制,
使用
以及
向第
三方
泄漏
。
MODULE WITH CABLE SPARE MODULE SOLID MODULEMODULE WITH PIPE
RTD Version No:
Pos Cable IDModule Type
Cable Type Cable Category OD
( mm/ [ "] )
Name
4.1.1.2665
B3:13 RM 20W40 3.5-16.5 [0.138"-0.650"]
B3:12 20500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:11 19500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:10 18500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:9 17500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:8 16500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:7 15500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:6 14500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:5 13500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:4 12500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:3 11500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:2 10500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
B3:1 1500kcmil 1/C PWR 23.5 [0.925"]
RM 40 21.5-34.5 [0.846"-1.358"]
5/5
Rev
TotWeightProject
Format
Created DateResponsible
Client
Drawing number
Modify Date
Sheet No
NTS
Location/ Sublocation
Transit name
Citico Pump Station
Casey Behrends 2017-02-22 2017-03-10
PS-RXT-001
[93.96]
42.6
A3A2A1
B3B2B1
B3B2B1
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
507.D
WG
4/20/2017 2:04 P
M LP
IR
TLE
04/14/17
CABCMK CSH
ELECTRICAL DETAILS
SHEET 7
***FILL IN DISCIPLINE***
95307
E507 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
E505
2DETAILNOT TO SCALE
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
WHCT
TO EPB
3000A
3P
EXISTING PUMP STATION SWITCHBOARD
900A
3P
900A
3P
900A
3P
900A
3P
600A
3PP
UM
P
ST
AT
IO
N
P-1
450
VFD
PU
MP
ST
AT
IO
N
P-2
450
VFD
PU
MP
ST
AT
IO
N
P-3
450
VFD
450
VFD
PU
MP
ST
AT
IO
N
P-4
600A
3P
EXISTING PUMP STATION MCC
TO CSO EFFLUENT PUMPS
(CSO-PDP-020)
TO CSOTF MCC
EXISTING
2500KVA
TRANSFORMER
PULL BOX
EXISTING CITICO PUMP STATION ONE-LINE DIAGRAM
1500kW DIESEL
480/277V, 3 PHASE,
4 WIRE
2500A
3P
K1
EXISTING QUICK
CONNECT SWITCHGEAR
EXISTING TRAILER GENERATOR
480Y/277V, 3Ø, 4W, 3,000A, 65,000 AIC (MIN)
KEYED NOTES:
REMOVE PUMP FEEDER (2 SETS OF 500KCMIL PER PHASE) FROM CONDUIT
AND CABLE TRAY AND RE-FEED PUMP P-1 FROM NEW DISTRIBUTION
SWITCHBOARD. SEE DRAWING E603.
REMOVE THE FOLLOWING SERVICES AND RE-FEED AS INDICATED ON
DRAWING E602.
EXISTING PUMP STATION SERVICE - 8 SETS OF 4-500 KCMIL
CSOTF SERVICE - 2 SETS OF 4-350 KCMIL
CSO EFFLUENT PUMPS - 3 SETS OF 4-500 KCMIL
REMOVE GENERATOR SERVICE CONDUCTORS AFTER NEW GENERATOR IS
INSTALLED, TESTED AND FULLY OPERATIONAL.
7 SETS OF 4-500 KCMIL, 500 KCMIL GND, 3-1/2"C.
REMOVE QUICK CONNECT SWITCHGEAR AND DELIVER TO OWNER AFTER
NEW GENERATOR IS INSTALLED, TESTED AND FULLY OPERATIONAL.
REMOVE AND RE-FEED AS INDICATED ON DRAWING E602.
2 SETS OF 3-500 KCMIL, #2/0 GND, 3"C.
REMOVE EXISTING MCC BUCKET AND REPLACE OR MODIFY WITH FEEDER
BREAKER SIZE SHOWN AS NEW.
REMOVE MCC FEEDER AND INSTALL NEW NAMEPLATE TO IDENTIFY CIRCUIT
BREAKER AS SPARE.
NEMA 4X STAINLESS STEEL ENCLOSURE.
HACR RATED BREAKER.
1
2
3
4
5
1
4
5
2
3
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
601.D
WG
4/20/2017 2:13 P
M LP
IR
TLE
04/14/17
CABCMK CSH
EXISTING ONE-LINE
DIAGRAM
ELECTRICAL
95307
E601 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 30
0
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
30kVA
480-
120/240
LIG
HT
IN
G
PA
NE
L A
15KW
H-1
40A
3P
25A
3P
30A
3P
25A
3P
30A
3P
25A
3P
30A
3P
25A
3P
30A
3P
H-2
H-3
H-4
30A
3P
60A
3P
EL
EV
AT
OR
60A
3P
60A
3P
CR
AN
E
10kVA
480-
120/240
LIG
HT
IN
G
PA
NE
L B
15A
3P
15A
MCP
30A
3P
SU
MP
PU
MP
1
15A
MCP
30A
3P
SU
MP
PU
MP
2
15A
3P
SC
RE
EN
2
25A
3P
30A
3P
AH
U-1
45A
MCP
30A
3P
DU
CT
HE
AT
ER
AIR
CO
ND
EN
SE
R
UH
-1
(E
QU
IP
R
M)
25A
MCP
DR
Y W
EL
L
MA
U (F
-1
)
10
30A
3P
25A
MCP
WE
T W
EL
L
MA
U (F
-2
)
2
30A
3P
25A
MCP
DR
Y W
EL
L
BL
OW
ER
(E
F-2
)
7.5
30A
3P
15A
MCP
DR
Y W
EL
L
EX
HA
US
T F
AN
(E
F-6
)
3
30A
3P
25A
MCP
OD
OR
CO
NT
RO
L
(E
F-1
)
10
30A
3P
15KW 15KW 15KW
22
30KW
6
7
6 7 6 6 7
3
1
PS
-S
TR
-0
02
60A
3P
PS
-A
HU
-0
01
P-P
S-M
CC
-0
1
PS
-S
F-0
02
40A
3P
PS
-C
U-0
01
P-P
S-M
CC
-0
2
20A
3P
60A
3P
8
PS
-D
S-1
02
8
P-P
S-D
S1
02
-0
1
60A
3P
8
PS
-D
S-1
01
P-P
S-D
S1
01
-0
1
P-P
S-S
TR
00
2-0
1P
-P
S-M
CC
-0
3
9
9 9
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
REV
PS-SWG-010
AUTO
TRANSFER
CONTROL
(ATC)
PT(2)
480-120
CT(3)
3000/5
PT (2)
480-120
PT(2)
480-120
PT(2)
480-120
52-2
3000AF
3000AT
N.O.
52-2/a
CT(3)
3000/5
52-1
3000AF
3000AT
N.C.
52-1/a
52-4
3000AF
3000AT
N.C.
EXISTING
2500KVA
TRANSFORMER
XF-1
TO EPB
FUTURE
UTILITY
TRANSFORMER
XF-2
TO EPB
PS-GEN-090
1750kW DIESEL
480/277V, 3 PHASE,
4 WIRE, 0.8PF
TRIP
LSIG
TU
CT(3)
3000/5
PT (2)
480-120
8686
ATC
ATC
52-3
3000AF
3000AT
N.O.
52-3/a
ATC
BLKCLS
AUTO
SERVICE
1
SERVICE
2
TRANSFER CONTROL
SWITCH
A
V
TRIP
LSIG
TU
8686
TRIP
CLOSE
ATC
ATC
ATC
BLKCLS
TRIP
LSIG
TU
8686
TRIP
CLOSE
ATC
ATC
ATC
BLKCLS
TRIP
CLOSE
600A
3P
900A
3P
900A
3P
PU
MP
ST
AT
IO
N
P-2
450
VFD
PU
MP
ST
AT
IO
N
P-3
450
VFD
EX
IS
TIN
G
PU
MP
ST
AT
IO
N
MC
C
CS
O-P
DP
-
020
CS
OT
F
MC
C
A
V
A
V
GEN
CITICO PS ONE-LINE DIAGRAM
900A
3P
PU
MP
ST
AT
IO
N
P-4
450
VFD
800A
(3)
800A
3P
600A
(3)
600A
3P
900A
3P
BUS 1 - 480Y/277V, 3Ø, 4W, 3200A, 65,000 AIC (MIN) BUS 2 - 480Y/277V, 3Ø, 4W, 3200A, 65,000 AIC (MIN)
2500A
3P
480Y/277V, 3Ø, 4W, 3000A, 65,000 AIC (MIN)
PS-ATS-040
NEMA 12, 3P
600A, 30,000 AIC (MIN)
3000A
3P
EXISTING PUMP STATION SWITCHBOARD
2500A
3P
SP
AR
E
P-P
S-X
F1-01
P-P
S-G
EN
090-01
P-P
S-S
WG
010-02
P-P
S-S
WG
010-01
GND BUS
NEUT PAD
BONDING
JUMPER
#4/0 BC2
GND BUS
P-S
WB
D-01
P-P
S-S
WG
010-03
P-P
S-S
WG
010-04
04/14/17
CABCMK CSH
ONE-LINE DIAGRAM
ELECTRICAL
95307
E602 0
770-587-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
P-PS-SWBD020-01
P-P
S-A
TS
040-01
TRIP
LSIG
TU
CS
O-D
SW
-001
800A
3P
600A
3P
REFER TO
DRAWING E603 FOR
CONTINUATION TO
PS-SWBD-020
REFER TO
DRAWING E603 FOR
CONTINUATION
FROM PS-SWBD-020
(3)(3)
GENERAL NOTES:1. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR
CABLE SCHEDULE.
EXISTING
FUSED
SWITCH
10-4"C
(FOR FUTURE
UTILITY)
ARMS
ARMS
CPT
1
CPT
1
ARMS
KEYED NOTES:
1 REFER TO SPECIFICATIONS FOR CONTROL POWER
REQUIREMENTS AND ACCESSORIES TO BE PROVIDED.
TRIP
LSIG
TUARMS
TRIP
LSIG
TUARMS
TRIP
LSIG
TUARMS
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
12201 EBPS-PLC-060
1817
1615
15.5
10,000 SURFACE
6043208Y/120PS-PNL-040
10301860
MOUNTEDSYM. A.I.C. MIN.
WIRE AMP. MAINSPHASEVOLTSPANELBOARD
POLE
NO.
CIRCUIT
NO.
LOAD
SERVED
2
4
6
8
10
12
14
KVA
TOTAL CONNECTED LOAD:
13
11
9
7
5
3
1
Ø Ø
LOAD - VA
SERVED
LOAD
SIZE
WIRE
AMPS
TRIP
NO.
CIRCUIT
NO.
POLE
BA
3 20 12 EQUIPMENT ROOM LIGHTING
5 20 12 EBPS LIGHTING
7 20 12 EXTERIOR RECEPTACLES
-
20
-
SPARE
-
20
-
SPARE
15 30 SURGE PROTECTION DEVICE
4
-
-
-
-
-
-
AMP. MAIN BKR.
60
4.1
-
SPARE20
-
SPARE20
20
20
20
-
SPARE
-
SPARE
-
SPARE
20
20
-
SPARE
12
12
PS-BACP-001
SIZE
WIRETRIP
AMPS
12
1220
CØ
-
-
-
-
-
-
-
-
-
-
-
720
720
1000
500
310
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
603.D
WG
4/20/2017 2:06 P
M JR
EC
KA
RT
04/14/17
CABCMK CSH
ONE-LINE DIAGRAM
AND PANELBOARD
SCHEDULE
ELECTRICAL
95307
E603 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
KEYED NOTES:
1 CIRCUIT BREAKER AND WIRE SIZE IS INDICATED AS
APPROXIMATE. COORDINATE FINAL SIZING WITH SUPPLIED
EQUIPMENT.
MANUFACTURER SUPPLIED CABLE.
NEMA 4X STAINLESS STEEL ENCLOSURE.
HACR RATED BREAKER.
PS-HVAC-CP-001
EQUIPMENT ROOM RECEPTACLES
6
2
20
20
AMPS (MAX Ø)
EM
P
UM
P
BA
CK
UP
ST
AT
IO
N
EB
PS
-P
-1
02
150
VFD
EM
B
AC
KU
P
PU
MP
ST
AT
IO
N
EB
PS
-P
-1
01
150
VFD
SP
AR
E
300A
3P
300A
3P
600A
3P
480V, 3Ø, 3W, 3000A MAIN BUS, 65,000 AIC (MIN)
PS-SWBD-020
PU
MP
ST
AT
IO
N
P-1
450
VFD
900A
3P
30A
3P
P-P
S-S
WB
D02
0-0
2
P-P
S-S
WB
D02
0-04
P-P
S-S
WB
D02
0-05
PS-XF-040
480V-208Y/120V
15KVA XFMR
PU
MP
S
TA
TIO
N
LIG
HT
IN
G P
AN
EL
PS
-P
NL
-0
40
GND BUS
#4/0 BC2
EB
PS
-
VF
D-10
1
EB
PS
-
VF
D-1
02
P-P
S-S
WB
D0
20
-0
6P
-P
S-X
F0
40
-0
1
OC
S-E
F-0
01
90A
3P
P-P
S-S
WB
D02
0-0
3
40
SPD
30A
3P
2500A
3P
P-P
S-S
WG
010
-0
2
REFER TO DRAWING
E602 FOR
CONTINUATION
FROM PS-SWG-010
P-PS-SWBD020-01
CITICO PS ONE-LINE DIAGRAM
30A
3P
EB
PS
-G
RC
P-1
01
P-P
S-S
WB
D0
20
-0
7
30A
3P
EB
PS
-G
RC
P-1
02
P-P
S-S
WB
D0
20
-0
8
30A
3P
EB
PS
-G
RC
P-1
03
P-P
S-S
WB
D0
20
-0
9
EB
PS
-S
G-0
01
1/2
20A
3P
P-P
S-S
WB
D0
20
-1
0
EB
PS
-S
G-0
02
1/2
20A
3P
P-P
S-S
WB
D0
20
-11
EB
PS
-S
G-0
03
1/2
20A
3P
P-P
S-S
WB
D0
20
-1
2
EB
PS
-S
G-0
04
1
20A
3P
P-P
S-S
WB
D0
20
-1
3
40A
3P
EB
PS
-B
C-0
01
P-P
S-S
WB
D0
20
-1
4
EB
PS
-S
F-0
02
3/4
20A
3P
P-P
S-S
WB
D0
20
-1
6
20A
3P
EB
PS
-S
F-0
01
P-P
S-S
WB
D0
20
-1
5
1
60A
3P
PS
-G
EN
-0
90
SE
RV
IC
E P
AN
EL
P-P
S-S
WB
D0
20
-1
7
20A
3P
EB
PS
-S
P-0
01
P-P
S-S
WB
D0
20
-1
8
1
40A
3P
PS
-P
AC
-0
01
P-P
S-S
WB
D0
20
-1
9
REFER TO
DRAWING E602 FOR
CONTINUATION
TO PS-ATC-040
SP
AC
E
300A
3P
1
EB
PS
-S
TR
-0
02
P-E
BP
S-S
TR
00
2-0
1
P-E
BP
S-V
FD
10
1-0
1
P-E
BP
S-V
FD
10
2-0
1
OC
S-S
TR
-0
01
P-O
CS
-S
TR
00
1-0
1
1
1
EB
PS
-S
TR
-00
1
P-E
BP
S-S
TR
00
1-0
1
360
500
GENERAL NOTES:1. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR
CABLE SCHEDULE.
7.5
EBPS-SPCP-101
SUMP PUMP
CONTROL PANEL
2
3
22
EBPS-PJB-100
P-E
BP
S-V
FD
10
1-0
1A
P-E
BP
S-V
FD
10
2-0
1A
#6 BC2
2
3
3
3 33
3
60A
3P
3
EB
PS
-D
S-1
01
60A
3P
3
EB
PS
-D
S-1
02
P-E
BP
S-D
S1
01
-0
1
P-E
BP
S-D
S1
02
-0
1
EX
IS
TIN
G
VF
D1
P-E
BP
S-S
PC
P1
01
-0
1
4
4
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
604.D
WG
4/20/2017 2:13 P
M LP
IR
TLE
04/14/17
SDAPMB ALW
SCADA ARCHITECTURE
DIAGRAM
***FILL IN DISCIPLINE***
95307
E604 0
77
0-5
87
-4
77
6
AL
PH
AR
ET
TA
, G
A 3
00
22
36
50
M
AN
SE
LL
R
OA
D, S
UIT
E 3
00
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
SCADA ARCHITECTURE DIAGRAM
CSO EFFLUENT PUMP STATION(EXISTING)
CSO-RTU-060
120VAC
FROM
POWER
PANEL
UPS
BATTERY
BACKUP
N
G
24VDC POWER
SUPPLY
24V (-)
24VDC
POWER
DISTRIBUTION
ETHERNET
SWITCH
TYPICAL LOOP
POWERED
INSTRUMENT
TYPICAL DIGITAL
AC INPUT CARD
N
G
N
G
N
24V (-)
24V (-)
N
G
120VAC
UPS POWER
DISTRIBUTION
N
N
G
TYPICAL
RTU
POWER SUPPLY
G
G
24V (-)
24V (-)
SPARE
NOTES:
1. THIS POWER DISTRIBUTION DIAGRAM IS TYPICAL.
QUANTITIES FOR INSTRUMENTS, I/O CARDS, POWER
SUPPLIES, AND OTHER DEVICES MAY VARY. INSTALL
QUANTITIES AS REQUIRED.TYPICAL PLC CABINET POWER DISTRIBUTION DIAGRAM
24V (-)
SPARE
TYPICAL RELAY
OUTPUT CARD
N
G
24V (-)
SPARE
SPARE
SURGE
PROTECTIVE
DEVICE
(TYPICAL)
TYPICAL
FIELD MOUNTED
INSTRUMENT POWERED
FROM PANEL
RTU
CSO FACILITY TELEMTRY PANEL(EXISTING)
RTU
PUMP STATION TELEMTRY PANEL(EXISTING)
CABINET
LIGHTS
PANEL AIR
VENTILATION
(AS REQUIRED)
UPS
OUTLET (GFCI)
SPARE
N
G
N
G
N
G
SPARE
DOOR INTERLOCKED
SWITCH (TYP)
SURGE
PROTECTION
DEVICE
RADIO
CSO-PLC-060
PLC
PLC
PLC
T-EBPS-PLC060-01
ETHERNET
SWITCH
PUMP STATIONCONTROL PANEL
(EXISTING)
EMERGENCY PUMP
STATION CONTROL
PANEL
(EBPS-PLC-060)
480/120V
CPT
GND
L2L1
X1 X2
FAN
CABINET FANS
(QUANTITY AS REQUIRED)
X1 X2
G
VFD
STOPPED
R
VFD
RUNNING
CR2
A
VFD
FAULT
VFD FAULT
VARIABLE FREQUENCY DRIVE
EBPS-VFD-101
RUN
DIGITAL
OUTPUTS
T1
T2
T3
TO CONTROL
RELAY
FAULT
TO PILOT
LIGHT AND
CONTROL
RELAY
DI4
DI5
DI3
DI2
DI1
PWR
DIGITAL
INPUTS
+10
DI6
SPARE
GND
AI1-
AI1+
COM
B
C
A
SPEED
POT
LOCAL
OFF
REMOTE
xoo
oox
START
STOP
SPARE
CR2
VFD
RUN RELAY
VFD RUN
CR2
TYPICAL SUBMERSIBLE PUMP VARIABLE FREQUENCY DRIVE SCHEMATIC DIAGRAM
T1
T2
T3
L1
L2
L3
GND GND
AI2-
AI2+
AO1-
AO1+
SPEED
CONTROL
FROM PLC
SPEED
INDICATION
TO PLC
oox
RUN STATUS
TO PLC
VFD FAULT
TO PLC
SYSTEM "IN-REMOTE"
TO PLC
MOTOR FAULT
TO PLC
STAR/STOP
RELAY
CR1
B R
CR1
oox
IN REMOTE
START/STOP
SPARE
SPARE
START/STOP
FROM PLC
CR2
VFD
FAULT RELAY
CR3
CR2
CR3
B
R
Y
BN
BL
O
C-EBPS-VFD101-01
Y
BN
BL
O
SPARE
SS1
SS1
SS1
I-EBPS-VFD101-02
I-EBPS-VFD101-01
START/STOP
FROM PLC
B
R
SPARE TERMINALS
TDR1
TDR2
PUMP
RELAY
MOISTURE
SENSORS
THERMAL
SWITCHES
MOISTURE
THERMAL
MOTOR OVERTEMP
RELAY SET @ 20 SEC.
SEAL LEAK RELAY
SET @ 20 SEC.
ALARM
RESET
B R
BLO
PUMP
HOUSING
TDR1 TDR2
TDR1 TDR2
TSH
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
REV
KEYED NOTES:
1 CABLE SUPPLIED BY PUMP MANUFACTURER.
MONITORING UNIT, MOISTURE SENSORS, AND THERMAL SENSORS ARE PROVIDED
BY THE PUMP MANUFACTURER. INSTALL MONITORING UNIT IN THE PUMP
INSTRUMENT JUNCTION BOX (EBPS-IJB-100) AND COORDINATE WITH THE PUMP
MANUFACTURER FOR INTEGRATION OF SENSORS AND FINAL TERMINATIONS.
INSTALL AND LABEL MONITORING LIGHTS ON THE FACE OF THE VFD UNIT AS
INDICATED.
2
1
2
04/14/17
CABCMK CSH
CONTROL DIAGRAMS
SHEET 1 - EBPS VFD
ELECTRICAL
95307
E605 0
770-587-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
PUMP JUNCTION BOX
(EBPS-PJB-100)
PUMP JUNCTION BOX
(EBPS-IJB-100)
P-EBPS-VFD101-01
P-EBPS-VFD101-01A
1
C-EBPS-
VFD101-01A
P-EBPS-VFD101-02
C-EBPS-VFD101-02
FIELD TERMINAL
BLOCK (TYP)
P-EBPS-VFD101-01P-PS-SWBD020-04
CIRCUITS
TABLE OF CORRESPONDING DEVICES AND CIRCUITS
EBPS-VFD-101
P-EBPS-VFD102-01P-PS-SWBD020-05EBPS-VFD-102
EQUIPMENT
EBPS-PJB-100
EBPS-P-101
EBPS-P-102
P-EBPS-VFD101-01A
P-EBPS-VFD102-01A
P-EBPS-VFD101-02
P-EBPS-VFD102-02
C-EBPS-VFD101-01
C-EBPS-VFD102-01
C-EBPS-VFD101-02
C-EBPS-VFD102-02
I-EBPS-VFD101-01
I-EBPS-VFD102-01
I-EBPS-VFD101-02
I-EBPS-VFD102-02
A
A
MOTOR HIGH
TEMP
SEAL LEAK
ALARM
TDR1
TDR2
P-PS-SWBD020-04
C-EBPS-IJB100-02
C-EBPS-IJB100-01
B W
C-EBPS-VFD101-01
C-EBPS-VFD101-01
PUMP INSTRUMENT
JUNCTION BOX
(EBPS-PJB-100)
C-EBPS-IJB100-01
EBPS-IJB-100
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
REV
04/14/17
CABCMK CSH
CONTROL DIAGRAMS
SHEET 2
ELECTRICAL
95307
E606 0
770-587-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
480/120V
CPT
L1
L2
X2
X1
CR2
D04
(OL)
GND
GENERAL NOTES:REFER TO THE MECHANICAL DRAWINGS FOR THE
DESCRIPTIONS OF OPERATION.
1.
G
M
R
M
RUN STOP
OCS-EF-001 EXHAUST FAN STARTER DIAGRAM (OCS-STR-001)
SOLID-STATE
OVERLOAD RELAY
DO1
DIGITAL
OUTPUTS
DO2SPARE
DO3SPARE
SPARE
OVERLOAD
TO STARTER
DO4
(OL)
OVERLOAD
TO STARTER
13
14
23
24
33
34
95
96
97
98
C
I.4
I.3
I.2
C
I.1
DIGITAL
INPUTS
C
C
M1
RUN
STATUS
SPARE
OVERLOAD
RESET
SPARE
GND
MOTOR
T1
T2
T3
T1
T2
T3
L1
L2
L3
M
M1
START
P-P
S-S
WB
D020-3
MX
B
R
C-OCS-STR001-01
P-OCS-STR001-01
RUN
STATUS
7SP
COMMON
WARNING ALARM
COMMON
SHUTDOWN ALARM
R
B
BL
O
FIELD TERMINAL
BLOCK (TYP)
GENERATOR
PS-GEN-090
GENERATOR
START/STOP
3SP
R
B
1SP
R
B
C-PS-GEN090-01
B
R
C-PS-GEN090-03
PLC CABINET
EBPS-PLC-060
GENERATOR
E-STOP
PS-ES-090
C-PS-GEN090-02
GENERATOR AND SWITCHGEAR CONNECTION DIAGRAM
5SP
R
B
BN
Y
SWITCHGEAR
PS-SWG-010
M
CR2
STOP
MXTDR1
TDAE
0-5
MIN
CR1
B
R
C-O
CS
-S
TR
001-07
CR2
A
LOSS OF
VENTILATION
CR1
DUCT SMOKE
DETECTOR
B
R
C-O
CS
-S
TR
001-06
CR1 CR1
B R
W
CLOSE OPEN
COM
SMOKE
DAMPER
C-O
CS
-S
TR
001-04
C-OCS-
STR001-04
START/STOP
INTERLOCK
TO EBPS-STR-001
CR2
C-OCS-STR001-05
ODOR CONTROL
SYSTEM FAIL
TO PLC/RTU
MX
B
R
C-OCS-STR001-02
START/STOP
INTERLOCK
TO EBPS-STR-002
MX
B
R
C-OCS-STR001-03
START/STOP
INTERLOCK
TO PS-STR-002
TDR1
(1 MIN)
SS-
OCS-
EF-001
CR2
RESET
CR2
C-E
BP
S-S
TR
001-01
CR2
C-P
S-S
TR
002-01
CR2
C-E
BP
S-S
TR
002-01
EBPS-SG-001
EBPS-SG-002
EQUIPMENT
P-PS-SWBD010-10
P-PS-SWBD010-11
EBPS-SG-003 P-PS-SWBD010-12
CIRCUITS
EBPS-SG-004 P-PS-SWBD010-13
C-EBPS-SG001-01
C-EBPS-SG002-01
C-EBPS-SG003-01
C-EBPS-SG004-01
TABLE OF CORRESPONDING DEVICES AND CIRCUITS
SLIDE GATE CONNECTION DIAGRAM
EBPS-SG-001
P-PS-SWBD020-10
CLOSE
STATUS
TO PLC
OPEN
STATUS
TO PLC
(TYPICAL FOR SLIDE GATES EBPS-SG-002, EBPS-SG-003
AND EBPS-SG-004)
C-EBPS-SG001-01
DO4
(OL)
1
KEYED NOTE:
CONTACT OPENS UPON PRESENCE OF FLOW.1
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
REV
04/14/17
CABCMK CSH
CONTROL DIAGRAMS
SHEET 3
ELECTRICAL
95307
E607 0
770-587-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
RUN
R
M OL
CR2M
OCS-EF-001
INTERLOCK
o
o
x
x
o
o
HAND
AUTO
SUPPLY FAN MOTOR STARTER CONTROL DIAGRAM (EBPS-STR-002)
CR2TO OCS-STR-001
C-EBPS-STR002-01
B
R
B
R
STOP
G
M
FAULT
A
CR2
OFF
C-OCS-
STR001-02
480/120V
CPT
X2
X1
GND
OL
MX
C-OCS-
STR001-02
CR1 A
P-P
S-P
NL040-06
ELE
CT
R
OO
M
HIG
H T
EM
P
SW
IT
CH
EQ
UIP
R
OO
M
HIG
H T
EM
P
SW
IT
CH
A
CR2
CR2
RESET
AHU UNIT
SMOKE
DETECTOR
CR2 CR2
CLOSE OPEN
COM
AHU UNIT
SMOKE
DAMPER
A
CR3
CR3
RESET
PAC UNIT
SMOKE
DETECTOR
CR3 CR3
CLOSE OPEN
COM
PAC UNIT
SMOKE
DAMPER
CR2
TO
PS-AHU-001
SHUTDOWN
C-HVACCP-01
B
R
PS-HVAC-CP-001 HVAC SYSTEMS ALARM PANEL
CR1
HVAC SYSTEMS
ALARM TO
PLC/RTU
C-HVACCP-03
B
R
CR3
TO
PS-PAC-001
SHUTDOWN
C-HVACCP-02
B
R
CR2 CR3
FAULT
A
CR2 CR1
CR2M
OCS-EF-001
INTERLOCK
o
o
x
x
o
o
HAND
AUTO
TYPICAL 480V SUPPLY FAN CONTROL WIRING DIAGRAM(WITH SMOKE DETECTION AND DAMPER)
CR2TO OCS-STR-001
C-EBPS-STR001-01
B
R
B
R
TABLE OF CORRESPONDING DEVICES AND CIRCUITS
RUN
R
M
STOP
G
M
STARTEREQUIPMENT
EBPS-SF-001 EBPS-STR-001
CIRCUITS
OFF
C-OCS-
STR001-01
C-EBPS-STR001-01
480/120V
CPT
X2
X1
GND
OL
CR1
DUCT
SMOKE
DETECTOR
B
R
C-E
BP
S-S
TR
001-02
CR1 CR1
B R
W
CLOSE OPEN
COM
SMOKE
DAMPER
C-E
BP
S-S
TR
001-03
C-E
BP
S-
ST
R001-03
PS-SF-002 PS-STR-002 C-PS-STR002-01
C-OCS-STR001-01
C-OCS-STR001-03
C-EBPS-STR001-02
C-PS-STR002-02
C-EBPS-STR001-03
C-PS-STR002-02
MX
C-OCS-
STR001-01
CR2
CR1
RESET
OL
B R
W
C-P
S-H
VA
CC
P-09
B R
W
B
R
C-PS-
HVACCP-05
B
R
B
R
B
R
C-PS-
HVACCP-05
C-PS-
HVACCP-06
C-PS-
HVACCP-06
PS-T-001
C-PS-
HVACCP-07
C-PS-
HVACCP-07
PS-T-002
C-PS-
HVACCP-04
C-PS-
HVACCP-04
C-PS-HVACCP-09
C-P
S-H
VA
CC
P-08
C-PS-HVACCP-08
BREAKER SHALL BE
SIZED BY PANEL FABRICATOR
EBPS-GRCP-101
GRINDER CONNECTION DIAGRAM
DRUM MOTOR
P-EBPS-GRCP101-01P-PS-SWBD020-07
CIRCUITS
TABLE OF CORRESPONDING DEVICES AND CIRCUITS
EBPS-GRCP-101
P-EBPS-GRCP102-01P-PS-SWBD020-08EBPS-GRCP-102
EQUIPMENT
EBPS-GRJB-101
EBPS-GRJB-101
EBPS-GR-101
EBPS-GR-102
1
GRINDER MOTOR
10
DRUM MOTOR
1
EBPS-GR-101
P-EBPS-GRCP103-01P-PS-SWBD020-09EBPS-GRCP-103 EBPS-GRJB-101 EBPS-GR-103
P-EBPS-GRCP101-02
P-EBPS-GRCP102-02
P-EBPS-GRCP103-02
P-EBPS-GRCP101-03
P-EBPS-GRCP102-03
P-EBPS-GRCP103-03
P-EBPS-GRCP101-01A
P-EBPS-GRCP102-01A
P-EBPS-GRCP103-01A
P-EBPS-GRCP101-02A
P-EBPS-GRCP102-02A
P-EBPS-GRCP103-02A
P-EBPS-GRCP101-03A
P-EBPS-GRCP102-03A
P-EBPS-GRCP103-03A
C-EBPS-GRCP101-01
C-EBPS-GRCP102-01
C-EBPS-GRCP103-01
C-EBPS-GRCP101-02
C-EBPS-GRCP102-02
C-EBPS-GRCP103-02
C-EBPS-GRCP101-01
P-PS-SWBD020-07
EBPS-GRCP-102
C-EBPS-GRCP102-01
P-PS-SWBD020-08
P-EBPS-GRCP101-01
P-EBPS-GRCP101-02
P-EBPS-GRCP101-03
C-EBPS-GRCP101-02
P-EBPS-GRCP102-01
P-EBPS-GRCP102-02
P-EBPS-GRCP102-03
C-EBPS-GRCP102-02
P-EBPS-GRCP101-01A
P-EBPS-GRCP101-02A
P-EBPS-GRCP101-03A
EBPS-GRJB-101
DRUM MOTOR
1
GRINDER MOTOR
10
DRUM MOTOR
1
EBPS-GR-102
P-EBPS-GRCP102-01A
P-EBPS-GRCP102-03A
P-EBPS-GRCP102-03A
KEYED NOTES:
1 MANUFACTURER SUPPLIED CABLE.
NEMA 4X STAINLESS STEEL ENCLOSURE.
PROVIDE NECESSARY POWER
DISTRIBUTION BLOCKS AND TERMINAL
BLOCKS TO LAND MANUFACTURER
SUPPLIED CABLES AND INSTALLED
CONDUCTORS BETWEEN THE GRINDER
CONTROL PANEL AND THE INDIVIDUAL
GRINDERS.
1
1
2
2
GRINDER
ALARM TO
PLC/RTU
GRINDER
START/STOP
FROM PLC
GRINDER
ALARM TO
PLC/RTU
GRINDER
START/STOP
FROM PLC
GRINDER
RUN TO
PLC
GRINDER
IN REMOTE
TO PLC
EBPS-GRCP-103
C-EBPS-GRCP103-01
P-PS-SWBD020-09
P-EBPS-GRCP103-01
P-EBPS-GRCP103-02
P-EBPS-GRCP103-03
C-EBPS-GRCP103-02
EBPS-GRJB-101
DRUM MOTOR
1
GRINDER MOTOR
10
DRUM MOTOR
1
EBPS-GR-103
P-EBPS-GRCP103-01A
P-EBPS-GRCP103-02A
P-EBPS-GRCP103-03A
1
2
GRINDER
ALARM TO
PLC/RTU
GRINDER
START/STOP
FROM PLC
GRINDER
RUN TO
PLC
GRINDER
IN REMOTE
TO PLC
GRINDER
RUN TO
PLC
GRINDER
IN REMOTE
TO PLC
PROJECT NO:
DATE:
SHEET TITLE
SHEET
THIS LINE IS ONE INCH
LONG WHEN PLOTTED FULL SCALE
THIS DRAWING MUST BE USED IN CONJUNCTION
WITH THE APPLICABLE OR GOVERNING TECHNICAL
SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS.
DISC. LEAD: DESIGNER: CHECKER:
RE
VD
AT
ER
EV
IS
IO
N D
ES
CR
IP
TIO
N
1
A
B
C
D
E
F
2 3 4 5 6 7 8
CITY O
F CH
ATTAN
OO
GA, TN
CITICO
PU
MP RELIABILITY IM
PRO
VEM
EN
TS
CO
NSEN
T D
ECREE PRO
GRAM
REV
Z:\C
LIE
NT
S\W
TR
\C
HA
TT
AN
OO
GT
N\95307_C
IT
IC
OR
ELIA
B\D
ES
IG
N\C
AD
D\E
LE
C\P
RO
D_D
WG
S\95307 E
608.D
WG
4/20/2017 2:04 P
M LP
IR
TLE
04/14/17
CABCMK CSH
CONTROL DIAGRAMS
SHEET 4
ELECTRICAL
95307
E608 0
770-5
87-4776
ALP
HA
RE
TT
A, G
A 30022
3650 M
AN
SE
LL R
OA
D, S
UIT
E 300
%%
%%
%%
%%
%%
ISSU
ED
FO
R CO
NSTRU
CTIO
N5/15/17
0
I-PS-AIC001-01
ALARM
CR3
CR1
H2S GAS
DETECTION
CONTROLLER
PS-AIC-001
(CLASSIFIED
AREAS)
o
x
x
o
AUTO
TEST
SS1
L
NGND
GAS DETECTION ALARM TO
EBPS-PLC-060
SEE BELOW
TOXIC GAS
DETECTOR
(PS-AE-1)
CR1
R R
CR1
CR2
PS-IL-1 PS-IL-4
BUILDING ALARM CONTROL PANEL (PS-BACP-001) CONNECTION DIAGRAM
#12 AWG
#12 AWG
DO1
FAULT
C-PS-BACP001-02
TOXIC GAS
DETECTOR
(PS-AE-2)
12
0V
AC
(P
-P
S-P
NL040-02)
ALARM
CR2
H2S GAS
DETECTION
CONTROLLER
PS-AIC-002
(UNCLASSIFIED
AREAS)
o
x
x
o
AUTO
TEST
SS1
L
NGND
#12 AWG
DO1
FAULT
CR2
ALARM
CR3
COMBUSTIBLE
GAS
DETECTION
PS-AIC-003
(CLASSIFIED
AREAS)
o
x
x
o
AUTO
TEST
SS1
L
NGND
#12 AWG
DO1
FAULT
A
PS-IL-2
INDICATION
LIGHT (TYP)
CR3
CR2CR1
PS-HGD-001
(CLASSIFIED
AREAS)
DO1
PS-HGD-002
(UNCLASSIFIED
AREAS)
DO1
PS-CGD-001
(CLASSIFIED
AREAS)
DO1
GAS DETECTION FAILURE
TO EBPS-PLC-060
C-PS-BACP001-01
#14 JUMPER
#14 JUMPER
I-PS-AIC002-01
TOXIC GAS
DETECTOR
(PS-AE-3)
TOXIC GAS
DETECTOR
(PS-AE-4)
ELEC ROOM
I-PS-AIC001-02
TOXIC GAS
DETECTOR
(PS-AE-5)
EQUIPMENT
ROOM
I-PS-AIC003-01
COMBUSTIBLE
GAS
DETECTOR
(PS-AE-6)
COMBUSTIBLE
GAS
DETECTOR
(EBPS-AE-1)
SEE BELOW SEE BELOW
SEE
BEL
OW
FO
R C
ON
TIN
UA
TIO
N
SEE
AB
OVE
FO
R C
ON
TIN
UA
TIO
N
GENERAL NOTES:
KEYED NOTES:
1 INSTALL BELDEN PART NUMBER 83606 6/C #20 SHIELDED INSTRUMENT
CABLE FOR TOXIC GAS SENSORS.
INSTALL BELDEN PART NUMBER 63706 6/C #16 SHIELDED INSTRUMENT
CABLE FOR COMBUSTIBLE GAS SENSORS.
REFER TO CABLE SCHEDULE FOR FIELD WIRING TO INDICATION LIGHTS.
1. ALL INDICATION LIGHT WIRING SHALL BE #12 AWG.
2. REFER TO SPECIFICATIONS SECTION 26 05 19 FOR CABLE SCHEDULE.
3. ALL WIRING SHALL BE #14 AWG UNLESS NOTED OTHERWISE.
21
I-PS-AIC002-021
I-PS-AIC002-031
1
1
I-PS-AIC003-022
#12 AWG #12 AWG
2
AUTO TEST
TOXIC GAS
PS-AIC-001
AUTO TEST
TOXIC GAS
PS-AIC-002
AUTO TEST
COMBUSTIBLE GAS
PS-AIC-003
PS-BACP-001 PANEL ELEVATION
NOT TO SCALE
CR3
TOXIC
GAS
INDICATION
COMBUSTIBLE
GAS
INDICATION
A
PS-IL-5
G
PS-IL-3
G
PS-IL-6
R
G
A
INDICATION LIGHT LENSE COLORS:
GREEN LENSE COLOR
RED LENSE COLOR
AMBER LENSE COLOR
NO ALARM
CONDITION
PRESENT
GR A
NORTH AND SOUTH ENTRANCEINDICATION LIGHT MOUNTING DETAIL
NOT TO SCALE
RGS CONDUIT
(SIZE AS REQUIRED)
JUNCTION
BOX
MYERS HUB (TYP)
3
3 3 3