ISOLATOR

Page 2: Isolator by Anuj

Standards Referred

IEC 62271-102 (High Voltage Switch gear and control

gear)

IEC 61128 (Alternating current disconnectors – Bus-

transfer current switching by disconnectors)

IEC 60060-1 (High-voltage test techniques)

IS: 9921 (Alternating current disconnectors)

IEC 60694 (Common Specifications For High-Voltage

Switchgear and Controlgear Standards)

Page 3: Isolator by Anuj

Purpose of Isolators

Used to isolate the circuit under no load

conditions.

Used for isolation of networks for small

switching currents (<0.5 A) and also for

commutation currents.

Cannot be used to make or break the

circuit.

It is used in addition to Circuit Breakers.

Page 4: Isolator by Anuj

Types of Isolators

Horizontal centre Break isolator (Two column Rotary Disconnector) (72.5KV – 765 KV)

Horizontal Double break Isolator( Three column rotary Disconnector) (12 KV – 765 KV)

Vertical Break Isolator( Two column Vertical Break Disconnector) (<25KV)

Knee Type Isolator (33KV – 765KV)Pantograph Isolator( Single column

Disconnector)(145KV – 765KV)

Page 5: Isolator by Anuj

Horizontal centre break Isolator

Page 6: Isolator by Anuj
Page 7: Isolator by Anuj

Horizontal Double break Isolator

Page 8: Isolator by Anuj
Page 9: Isolator by Anuj

Vertical Break Disconnector

Page 10: Isolator by Anuj
Page 11: Isolator by Anuj

Knee Type

Page 12: Isolator by Anuj
Page 13: Isolator by Anuj

Pantograph Insulator

Page 14: Isolator by Anuj
Page 15: Isolator by Anuj
Page 16: Isolator by Anuj

Operating Mechanism

Motor Operating MechanismSpur Gear followed by Worm Gear is installed for smooth operation and self locking

Manual with Gear MechanismHand operation with Worm Gear is used for self locking capability

Manual OperationHand operation using lever is

practiced

Page 17: Isolator by Anuj

Spur Gear Worm Gear

Page 18: Isolator by Anuj

Earth Switch

Connected between line conductor and

earth.

Usually mounted on frame of isolator.

Interlocked mechanically and electrically

with isolators

Page 19: Isolator by Anuj

Single Coloumn Earth Switch

Page 20: Isolator by Anuj

TerminologyParticulars Data for 400

KV

Rated Current under site conditions at 50ºC ambient

2000/3150Amp.

Rated Short Circuit current of Isolator and E/S for 1 sec.

50KA(rms)

Rated dynamic short circuit withstand current of Isolator and E/S.

125 KA(peak)

Rated Mechanical terminal Load

Dielectric Withstand Capacity 520 KVrms

One min. power freq. withstand voltagei. Against Groundii. Against Isolating Distance

520KVrms610KVrms

1.2/50 µsec. Impulse withstand voltagei. Against Groundii. Against Isolating Distance

1425KV(peak)1450(+240)KV(peak)

Corona Extinction Voltage 320 KVrms

Operating Time Less than 12 Sec.

Page 21: Isolator by Anuj