7/25/2019 Isolamento Kaimann Thermal Calculation Results
1/5
11/01/2016 Kaimann Thermal Calculation Results
http://www.kaiflex.co.uk/tools/ThermalResults.htm 1/5
Ambient Temperature: 5 C
Line Temperature: 30 C
Orientation: Horizontal
External Emissivity: 0.9 -
Wind Speed: 0 m/s
Results Summary
Kaimann Thermal Calculation Suite
Data entered by: Vasco Project ref: VascoMon Jan 11 2016 11:41:27 GMT+0000 (Hora padro de GMT)
Heat Flow: W/m
Insulation cant eliminate energy loss entirely but it can reduce it dramatically. In the table below each column represents
a different insulation thickness and the cells in that column show the heat ow (energy loss) in W/m when that insulation
thickness has been applied. As the thickness increases the energy loss is reduced but the most dramatic reductions
occur when the rst few mm of insulation are applied.
Steel Kaiex ST Class O
Pipe O.D Pipe N.B 0 9 13 19 25 32
mm mm mm mm mm mm mm mm
17.2 14 17.19 6.01 5.05 4.24 3.74 3.36
21.3 15 20.63 6.94 5.78 4.79 4.2 3.75
26.7 20 24.95 8.12 6.7 5.49 4.77 4.22
33.4 25 30.25 9.59 7.83 6.35 5.47 4.8
42.4 34 37.15 11.53 9.33 7.48 6.38 5.55
48.3 40 41.57 12.78 10.3 8.2 6.97 6.04
60.3 50 50.36 15.32 12.25 9.67 8.15 7
76.1 70 61.71 18.63 14.79 11.57 9.68 8.25
88.9 80 70.64 21.28 16.84 13.1 10.9 9.25
114.3 100 87.96 26.51 20.87 16.11 13.31 11.22
-
7/25/2019 Isolamento Kaimann Thermal Calculation Results
2/5
11/01/2016 Kaimann Thermal Calculation Results
http://www.kaiflex.co.uk/tools/ThermalResults.htm 2/5
141.3 125 105.97 32.03 25.12 19.29 15.86 13.29
168.3 150 123.62 37.51 29.35 22.45 18.39 15.35
219.1 200 156.16 47.76 37.27 28.37 23.13 19.19
273 250 189.81 58.55 45.62 34.62 28.13 23.25
323.9 300 221.09 68.69 53.47 40.5 32.83 27.08
355.6 350 240.9 75.03 58.37 44.17 35.77 29.46
406.4 400 271.5 85.08 66.17 50.01 40.45 33.26
457 450 301.66 95.06 73.91 55.82 45.1 37.04
508 500 331.75 105.09 81.7 61.66 49.78 40.85
610 600 391.2 125.06 97.23 73.32 59.13 48.44
660.4 641.4 419.88 134.86 104.85 79.06 63.73 52.18
711.2 692.2 449.01 144.76 112.55 84.85 68.37 55.96
762 743 510.5 154.63 120.24 90.63 73.01 59.73
812.8 793.8 544.54 164.49 127.92 96.41 77.65 63.5
863.6 844.6 578.57 174.34 135.59 102.18 82.28 67.27
914.4 895.4 612.6 184.17 143.25 107.95 86.91 71.03
1066.8 946.2 705.49 216.94 165.75 124.97 100.62 82.21
1117.6 1098.6 748.74 227.96 176.27 130.97 105.4 86.07
1498.6 1479.6 1004 304.86 235.5 176.31 141.32 115.02
1524 1505 1021.02 309.99 239.45 179.26 143.67 116.93
Surface temperatures: C
The surface temperature of insulation is different from the surface temperature of the pipe to which they are applied. As
the thickness of insulation is increased the surface temperature will become closer to the ambient temperature. In the
table below each column represents a different insulation thickness and the cells in that column show the surface
temperature when that insulation thickness has been applied.
Steel Kaiex ST Class O
Pipe O.D Pipe N.B 0 9 13 19 25 32
mm mm mm mm mm mm mm mm
-
7/25/2019 Isolamento Kaimann Thermal Calculation Results
3/5
11/01/2016 Kaimann Thermal Calculation Results
http://www.kaiflex.co.uk/tools/ThermalResults.htm 3/5
17.2 14 30 11 9.4 8.1 7.4 6.8
21.3 15 30 11.3 9.6 8.3 7.5 6.9
26.7 20 30 11.5 9.8 8.4 7.6 7.1
33.4 25 30 11.8 10.1 8.6 7.8 7.2
42.4 34 30 12 10.3 8.8 8 7.3
48.3 40 30 12.1 10.4 8.9 8 7.4
60.3 50 30 12.4 10.6 9.1 8.2 7.5
76.1 70 30 12.6 10.8 9.3 8.3 7.7
88.9 80 30 12.7 10.9 9.4 8.4 7.7
114.3 100 30 12.9 11.1 9.5 8.6 7.9
141.3 125 30 13.1 11.3 9.7 8.7 8
168.3 150 29.9 13.2 11.4 9.8 8.8 8.1
219.1 200 29.9 13.4 11.5 9.9 8.9 8.2
273 250 29.9 13.5 11.7 10 9.1 8.3
323.9 300 29.9 13.6 11.8 10.1 9.1 8.4
355.6 350 30 13.7 11.8 10.2 9.2 8.4
406.4 400 30 13.8 11.9 10.2 9.2 8.4
457 450 30 13.8 12 10.3 9.3 8.5
508 500 30 13.9 12 10.3 9.3 8.5
610 600 30 14 12.1 10.4 9.4 8.6
660.4 641.4 30 14 12.1 10.4 9.4 8.6
711.2 692.2 30 14.1 12.2 10.5 9.4 8.6
762 743 30 14.1 12.2 10.5 9.5 8.7
812.8 793.8 30 14.1 12.2 10.5 9.5 8.7
863.6 844.6 30 14.2 12.3 10.6 9.5 8.7
914.4 895.4 30 14.2 12.3 10.6 9.5 8.7
1066.8 946.2 29.7 13.9 12.3 10.6 9.6 8.8
-
7/25/2019 Isolamento Kaimann Thermal Calculation Results
4/5
11/01/2016 Kaimann Thermal Calculation Results
http://www.kaiflex.co.uk/tools/ThermalResults.htm 4/5
1117.6 1098.6 30 14 12.1 10.6 9.6 8.8
1498.6 1479.6 30 14 12.1 10.5 9.5 8.7
1524 1505 30 14 12.1 10.5 9.5 8.7
Calculated -Value: W/mK
The thermal conductivity (-value) of insulation is temperature dependent and will change as the temperature changes. In
the table below each column represents a different insulation thickness and the cells in that column show the calculated
thermal conductivity when that insulation thickness has been applied (given the exact calculated temperature of the
insulation).
Steel Kaiex ST Class O
Pipe O.D Pipe N.B 0 9 13 19 25 32
mm mm mm mm mm mm mm mm
17.2 14 0.037 0.036 0.036 0.0359 0.0359 0.0358
21.3 15 0.037 0.0361 0.036 0.0359 0.0359 0.0358
26.7 20 0.037 0.0361 0.036 0.0359 0.0359 0.0359
33.4 25 0.037 0.0361 0.036 0.0359 0.0359 0.0359
42.4 34 0.037 0.0361 0.036 0.0359 0.0359 0.0359
48.3 40 0.037 0.0361 0.036 0.0359 0.0359 0.0359
60.3 50 0.037 0.0361 0.036 0.036 0.0359 0.0359
76.1 70 0.037 0.0361 0.036 0.036 0.0359 0.0359
88.9 80 0.037 0.0361 0.036 0.036 0.0359 0.0359
114.3 100 0.037 0.0361 0.0361 0.036 0.0359 0.0359
141.3 125 0.037 0.0362 0.0361 0.036 0.0359 0.0359
168.3 150 0.037 0.0362 0.0361 0.036 0.0359 0.0359
219.1 200 0.037 0.0362 0.0361 0.036 0.0359 0.0359
273 250 0.037 0.0362 0.0361 0.036 0.036 0.0359
323.9 300 0.037 0.0362 0.0361 0.036 0.036 0.0359
355.6 350 0.037 0.0362 0.0361 0.036 0.036 0.0359
406.4 400 0.037 0.0362 0.0361 0.036 0.036 0.0359
-
7/25/2019 Isolamento Kaimann Thermal Calculation Results
5/5
11/01/2016 Kaimann Thermal Calculation Results
http://www.kaiflex.co.uk/tools/ThermalResults.htm 5/5
457 450 0.037 0.0362 0.0361 0.036 0.036 0.0359
508 500 0.037 0.0362 0.0361 0.036 0.036 0.0359
610 600 0.037 0.0362 0.0361 0.036 0.036 0.0359
660.4 641.4 0.037 0.0362 0.0361 0.036 0.036 0.0359
711.2 692.2 0.037 0.0362 0.0361 0.036 0.036 0.0359
762 743 0.037 0.0362 0.0361 0.036 0.036 0.0359
812.8 793.8 0.037 0.0362 0.0361 0.036 0.036 0.0359
863.6 844.6 0.037 0.0362 0.0361 0.036 0.036 0.0359
914.4 895.4 0.037 0.0362 0.0361 0.036 0.036 0.0359
1066.8 946.2 0.037 0.0362 0.0361 0.036 0.036 0.0359
1117.6 1098.6 0.037 0.0362 0.0361 0.036 0.036 0.0359
1498.6 1479.6 0.037 0.0362 0.0361 0.036 0.036 0.0359
1524 1505 0.037 0.0362 0.0361 0.036 0.036 0.0359
All thermal insulation calculations are made in accordance with EN ISO 12241 and other industry standard methods where applicable. These standardised
methods may not take into account all variables and are highly reliant on the quality of the variables entered. As such results should be considered indicativeonly and Kaimann cannot be held liable for the use of recommendations given by this program alone.