Island operation withinduction generators
Olof Samuelsson
Industrial Electrical Engineering and Automation
![Page 2: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/2.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 2
Why induction generators?
• Hydropower– New small-scale plants often use IG– At renovation IG often replaces synchronous generator
• Windpower– Many Fixed-Speed Induction Generators installed
• Original question: Can IG contribute to island operation?• Modified question: Can island operation be based on IG alone?
![Page 3: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/3.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 3
Forsa power station
• Semi-Kaplan turbine 275 kW• Induction generator 315 kW, 400 V• Capacitors 3x50 kvar• Transformer 0.4/10 kV, 500 kVA• Customers connected to the transformer low voltage side
![Page 4: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/4.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 4
Grid connected operation
• Starting sequence– Gate starts to open– During opening
• Generator accelerates• Close breaker near synchronous speed• Generator energized
– Gate stops at fully open
• Power control by runner blade angle• Minimum output power is 80 kW
Gate
![Page 5: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/5.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 5
Reducing gate opening for low-load operation
0 200 400 600 80060
80
100
120
Time [s]
Act
ive
pow
er [k
W]
0 50 100 150Power [kW]
Runn
er p
ress
ure
H/H
max
Gate control not possible use dump load for low load operation
Angle increases
![Page 6: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/6.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 6
Black start of self-excited IG
• increases– generator is magnetized– voltage rises
• New method gives U and I without fixing
0
0
20
40
60
Spee
d [5
0(n/
n s)]
0 5 10 15 20-500
-250
0
250
500
Vol
tage
[V]
Time [s]
IG With loadC
![Page 7: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/7.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 7
Mechanical analogy
xkFL
i 1
dvFR
ui 1
Stator resistance neglected
capacitor - mass
load - damper
resistance – damper
voltage - speed
current - force
Rotor with inertia
dtdvmF
dtduCi
inductance - spring
flux - distance
power - power
load
capacitor
![Page 8: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/8.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 8
Black start• Remanence
– Offset Rr and m• increases
– Im(is) increases• 2x > kx
– mass moves outwards– Rr moves outwards– us increases
• k increases with x– Stable operating point
![Page 9: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/9.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 9
Loading and voltage control• No-load
– Re(is) = 0• Connecting load with constant
– slip increases– Re(is) increases– Im(is) decreases– mass moves inwards– us decreases
• m increases (STATCOM)– us increases
![Page 10: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/10.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 10
IG voltage and frequency coupled
• Slow voltage controlbetter than fast
• STATCOM affects bothspeed and voltage
• Voltage and frequencycontrol need to becoordinated
44
46
48
50
Spee
d [5
0(n/
n s)]
200
220
240
Vol
tage
[V]
900
1000
1100
Gate
[W]
0 20 40 60 80 100400
600
8001000
QS [v
ar]
Time [s]
![Page 11: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/11.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 11
Earthing of MV network
• Petersen coil earthing of MV busbar• Earthing at MV/LV transformer lost at islanding unearthed
CB
IGIf
IPetersen ICap
CB
RN+jXPet
![Page 12: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/12.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 12
Self-excited IG behavior at earth faults
• IG does not demagnetize
• Selective protection possible– Normal settings
• Unselective protection– More cable reduces V0– Upper limit to cable length– New method gives V0 in network at IG with D/Y transformer
0 2 4 6 8
x 10-6
0
0.5
V0 [p
u]
0 2 4 6 8
x 10-6
0
1
2
Ctot [F]I n
(%)
Rf = 5 k
![Page 13: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/13.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 13
Self-excited IG behavior at short-circuit• IG demagnetizes at any short-circuit• Fault current decays quickly – use undervoltage protection• STATCOM does not affect short-circuit current much
0.96 0.98 1 1.02 1.04 1.060
2
4
6
I a (p.u
.)
Three-phase short-circuit
0.96 0.98 1 1.02 1.04 1.060
0.5
1
time (s)STA
TCO
M C
urre
nts
(p.u
.)
ISTATCOM
IqId
without STATCOMwith STATCOM
![Page 14: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/14.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 14
Earth fault in LV network – normal situation
10kV
400V
400V10
kV
![Page 15: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/15.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 15
Earth fault in LV network – island operation
Reduced fault currentGrid connected - SEIG in island
Longer melting time
Undervoltage relay mayhave time to trip
Unselective disconnectionof SEIG for LV fault
0 50
0.5
1Voltages
V A [p
.u.]
0 2 4 60
0.5
1
V A [p
.u.]
time [s]
0 50
10
20
I f [p.u
.]
Currents
0 50
0.5
1
1.5
I f [p.u
.]
time [s]
ZLPh
+ZLPE
=0
ZLPh+ZLPE=0.8
![Page 16: Island operation IGsgemfinalreport.fi/files/SGEM Samuelsson island ig.pdf– New small-scale plants often use IG – At renovation IG often replaces synchronous generator • Windpower](https://reader033.vdocuments.us/reader033/viewer/2022060418/5f1538c550709a422a75f3ac/html5/thumbnails/16.jpg)
Lund University/ LTH/ Measurement Technology and Industrial Electrical Engineering/ IEA 16
References
J. Björnstedt, O. Samuelsson, ”Voltage and frequency control for island operated inductiongenerators,” CIRED seminar 2008: SmartGrids for Distribution, Frankfurt, 23-24 June 2008.
J. Björnstedt, O. Samuelsson, “Semi-Kaplan Turbine Controlling an Island Operated InductionGenerator,” NORDAC 2008 8th Nordic Distribution and Asset Management Conference,Bergen, Norway, 8-9 September 2008.
J. Björnstedt, “Island Operation with Induction Generators - Frequency and Voltage Control,”Licentiate thesis TEIE-1058, 2009, www.iea.lth.se/publications/publice.html
F. Sulla, O. Samuelsson, “Estimation of the zero sequence voltage on the D-side of a Dytransformer using one voltage transformer on the D-side,” Development in Power SystemProtection 2008, Glasgow, United Kingdom, 17-20 March, 2008.
F. Sulla, O. Samuelsson, “Analysis of Island-Operated Distribution Networks with DistributedInduction Generation under Fault Conditions,” UPEC 2008, 43rd International UniversitiesPower Engineering Conference, Padova, Italy, 1-4 September 2008.
F. Sulla, O. Samuelsson, “Short-Circuit Analysis and Protection of a MV Network in IslandOperation with Induction Generators,” NORDAC 2008 8th Nordic Distribution and AssetManagement Conference, Bergen, Norway, 8-9 September 2008.
F. Sulla, “Island Operation with Induction Generators - Fault Analysis and Protection,” Licentiatethesis TEIE-1059, 2009, www.iea.lth.se/publications/publice.html