IS CAN Bus – CiA DSP 103 V 1.0. Low Cost, Intrinsically Safe Transducer Bus Enabling NeSSI Gen II Rick Ales Swagelok Company. Analyzer. 10 Meters. V. A. P. T. MPC Gen II Architecture. Ethernet. Remote Operator Station. Hazardous Area Class 1 Div 1 (Zone 1). IS NeSSI Bus. Flow - PowerPoint PPT Presentation

TRANSCRIPT

© 2006 Swagelok Company.

IS CAN Bus – CiA DSP 103 V 1.0

Low Cost, Intrinsically Safe Transducer Bus Enabling NeSSI Gen II

Rick Ales Swagelok Company

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

MPC Gen II Architecture

V TPA

NeSSI Device Sample System

FlowSensors

Sensor Analyzer Manager SAM

IS NeSSI Bus

Remote Operator Station

Ethernet

Analyzer

Hazardous Area Class 1 Div 1 (Zone 1)

10 Meters

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

IS and the Ignition Curve

Voltage = Frequency-1 * Distance

24V = Frequency-1 * 2000M

9.5V = Frequency-1 * 10M

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

IS CAN Major Parameters

• The CAN physical layer ISO11898-1,2 & CiA301• Co-cabled 10m max Single power source only • 3.3V Driver 1/3 the Power • Power bus specification P+F RSD2-PSD-EX4.43• M12 or M8 Connectors 2 Power and 2 CAN wires• Area Classification Class 1 Div 1 (Zone 1)

Entity Parameters

VOC (V) ISC (A) Groups CO (uF) LO (uH)

   A, B (IIC) (Acetylene & Hydrogen) 0.8 10

9.5Vdc 1.0 A C (IIB) (ethylene) 2.4 40

    D (IIA) (propane) 6.4 80

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

IS CAN Physical Layer Topology

4 Circuits 8.5 Watts each

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

NeSSI Gen II Architecture

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

Gen II NeSSI Bus Open Standard

www.can-cia.org

CiA 103 DSP V1.0

April 2007

© 2006 Swagelok Company. Swagelok confidential. For internal use only.

Ex Harmonization

Div 2 Zone 2

Div 1 Zone 1

Zone 0UL 913 specifies all Div 1Equipment meet Zone 0Requirements in 2012