Disclosure to Promote the Right To Information Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public. इंटरनेट मानक !ान $ एक न’ भारत का +नम-णSatyanarayan Gangaram Pitroda “Invent a New India Using Knowledge” प0रा1 को छोड न’ 5 तरफJawaharlal Nehru “Step Out From the Old to the New” जान1 का अ+धकार, जी1 का अ+धकारMazdoor Kisan Shakti Sangathan “The Right to Information, The Right to Live” !ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह Bharthari—Nītiśatakam “Knowledge is such a treasure which cannot be stolen” IS 11527 (1985): Criteria for structural design of energy dissipators for spillways [WRD 9: Dams and Spillways]

Upload: others

Post on 06-Mar-2021

8 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

Disclosure to Promote the Right To Information

Whereas the Parliament of India has set out to provide a practical regime of right to information for citizens to secure access to information under the control of public authorities, in order to promote transparency and accountability in the working of every public authority, and whereas the attached publication of the Bureau of Indian Standards is of particular interest to the public, particularly disadvantaged communities and those engaged in the pursuit of education and knowledge, the attached public safety standard is made available to promote the timely dissemination of this information in an accurate manner to the public.

इंटरनेट मानक

“!ान $ एक न' भारत का +नम-ण”Satyanarayan Gangaram Pitroda

“Invent a New India Using Knowledge”

“प0रा1 को छोड न' 5 तरफ”Jawaharlal Nehru

“Step Out From the Old to the New”

“जान1 का अ+धकार, जी1 का अ+धकार”Mazdoor Kisan Shakti Sangathan

“The Right to Information, The Right to Live”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता है”Bhartṛhari—Nītiśatakam

“Knowledge is such a treasure which cannot be stolen”

“Invent a New India Using Knowledge”

है”ह”ह

IS 11527 (1985): Criteria for structural design of energydissipators for spillways [WRD 9: Dams and Spillways]

Page 2: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron
Page 3: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron
Page 4: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11627 .. '1985'

Indian Standard"CRITERIA F()R STR'U'er"URAL DESIGN O'FENERGY[)ISSll)i\'~·rORS F'()R SPJ.LL~rJ-\YS

J5i'

.' @ Cop)"lght 1986

..-}N D lA 'N S 'fA N'D A R D SIN S ~r I T U r J. 0 N'." ·M·A.NAX·BIIAVAN,.... 9 ··BAHAOUR SHAH ZAFAR MAllO

'. 'NHW pELH.ll10002

Gt ..7".. - November 1986

Page 5: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

Indian Standard

CRITERIA FOR STRUC'TURAL DESIGN OFENERGY DISSIPATORS FOR SPILLWAYS

Spillways Including Energy Dissipators Sectional Committee, DOC 54

ChairmanSHRI J. F. MISTRY

RepresentingIrrigation Department, Government of Gujarat,

Gandhinagar

SHRI B. DASS

CHIEF ENOINI=:ER ( PWD )

MembersSHRIR.K.AGOARWAL Irrigation Department, Government of Uttar

Pradesh, LucknowSHRI AMAR Sll'OH RAJPU r ( Alternate)

Dlt A. S. CHAWLA University of Roorkee ( WRDTe ), RoorkeeCHlI~F E~OINEbR. COO Irrigation Department, Government of Aodhra

Pradesh, HydcrabadSUP~ldNTrNnINGEl"QINEER ( [)AMS) ( Alternate)

CUII::F ENOI~EER Al\D DIRECTOR Maharashtra Engineering Research Institute,Nasik

Irrigation Department, Government of Karnataka,Mysore

SUPERINrENDI~O E!'~GIN[ER ( Dsstoxs ) ( Alternate)CHIEP ENOIl'EER/R-culn-DIREcTOR Irrigation & Power Research Institute, Punjab,

ChandigarhClUFF ENGINEER, THEIN DAM DESIGN Irrigation Department, Government of Punjab.

ChandigarhDIRECIOR ( SPILLWAYS & PO\\1F.R PI.,Al'T ) ( Alternate)

SHRI M. L. DAS Irrigation & Power Department, Government ofOrissa, Bhubaneshwar

Jrrigation & Waterways Directorate, Governmentof West Bengal, Calcutta

DIRr-cToR Central Water and Power Research Station, PuneSHIH R. M. KH"TSURIA ( Alternate)

DIRECTOR ( ("MDD-l ) Central Water Commission. New [)elhiKUMARI E. DIVATIA National Hydroelectric Power Corporation Ltd.

New DelhiSHRI N. C. DUOGAL The Concrete Association of India, Bombay

SHRI J. N. SUKHADWALLA ( Alternate)

( Contlnued on page 2 )

(~ Copyright 1986INDIAN STANDARDS INSTITUTION

This publication is protected under the Indian Copyright Act (XIV of 1957) andreproduction in whole or in part by any means except with written permission of thepublisher shall be deemed to be an infringement of copyright under the said Act.

Page 6: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

Irrigation Department. Government of Haryana,Chandigarh

Jaiprakash Associated Pvt Ltd, New Delhi

Irrigation Department, Government of UttarPradesh, Lucknow

Director General, lSI ( Ex-officio Member)

RepresentingConsulting Engineering Services (India) Pvt Ltd.

New DelhiPROP HARI KRISHNA ( Alt.rnat. )

DR JAGDISH NARAIN Institution of Engineers ( India), CalcuttaSHRJ S. P. JAIN Bhakra Beas Management Board, Nanaat

TownshipSf-IRI J. C. BASUR ( Alternate)

SHRI D. G. KADICADBSHRI A. B. ODAK ( Alternate)

SHRI H. K. KHOSLA

( Continued from page 1 )

Member'SHRI IC. K. FRAMJI

SHRI M. L. GUPTA ( Alternate)SSR' M. U. PUROHIT Irrigation Department, Government of Guiarat,

Gandhinagar

SHRI G. RAMAN,Director ( Civ EDII )

SHRI N. B. DESAI ( Alternate)SURI M. S. RAMA RAO Karnataka Power Corporation Ltd, BangalorcREPRESENTATIVE Irrigation Department, Government of Tamil

Nadu, MadrasSURI D. M. SAVUR The Hindustan Construction Co Ltd, Bombay

SHIH M. V. S. IYENQAR ( Alternate)SUPERINTENL>INO ENOINEER ( MD ) Irrigation Department, Government of Mahara­

shtra, BombaySHRI V. N. PENDSE ( Alternate I )KUMAR! PRATIM,\ NAIDU ( Alternate II )

SHRI C. D. THATrB Gujarat Engineering Research Institute, VadodaraSKRI B. K. RAO ( Alter1llJle)

DR R. S. VARSHNEY

Secretary

SHRI K. K. SHARMAJoint Director ( Civ Engg ), lSI

Adhoc Panel for Cirteria for Structural Design of Energy Dissipatorsfor Spillways, DOC S4 AP

SHRI V. G. LAQWANEAR

SHRI V. N. PSNDSB

Irrigation Department, Government of Mahara­shtra, Bombay

Irrigation Depanment, Government of Mahara­shtra, Bombay

2

Page 7: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

AMENDMENT NO.1 SEPTEMBER 1988TO

IS : 11517-1985 CRITERIA FORSTRUCTURAL DESIGN OF ENERGY DISSIPATORS

FOR SPILLWAYS

( }'n.J:f R, (/(UHf 4.3.4, Nne 3 ) - Substitute

, [ U'5 ( D! X rv + tb X 111) - ( D1 X ll' + Ji'e X Ib ) ) '.{OT

'O"5[(D2 X U')+(tbX U·')-(D)x W+Wc/h ) ] ' .

( DOC 54)

Printed at New India Printinl Pre s•• Kbut;a. tndb

Page 8: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 .. 1985

Indian Standard

CRITERIA FOR STRUCTURAL DESIGN OF.ENERGY DISSIPATORS FOR SPILLWAYS

o. FOR E W 0 R D

0.1 This Indian Standard was adopted by the Indian Standards Institutionon 20 November 1985, after the draft finalized by the Spillways IncludingEnergy Dissipators Sectional Committee had been approved by the CivilEngineering Division Council.

0.2 The design of downstream protection works or energy dissipators belowhydraulic structures occupies a vital place in the design and constructiondams, weirs and barrages. The problem of designing energy dissipators isessentially of reducing high velocity flow to a velocity low enough tominimize erosion of natural river bed. This reduction in velocity may beaccomplished by any, or a combination of the following, depending uponthe head, discharge intensity, tail water conditions and the type of bed rockor the bed material:

a) Hydraulic jump type stilling basins:

I) Horizontal apron type; and

2) Sloping apron type;

b) Jet diffusion and free jet stilling basins:

1) Jet diffusion basins;

2) Free jet stilling basins;

3) Hump stilling basins; and

4) Impact stilling basins;

c) Bucket type dissipators:

1) Solid and slotted roller buckets; and

2) Trajectory buckets ( ski jump, flip, etc );

d) Interacting jets and other special type of stilling basias.

3

Page 9: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985 .

0.3 In India, hydraulic jump type stilling basins and bucket type energydissipators are generally used for dissipation of energy depending on condi­tion of downstream tail water. Indian Standards have already been issuedfor criteria for hydraulic design of these two types of energy dissipators asunder:

IS : 4997-1968

IS : 7365-1974

Criteria for design of hydraulic jump type stillingbasins with horizontal and sloping apron

Criteria for hydraulic design of bucket type energydissipators

I. SCOPE

t.l This standard lays down criteria for structural design of variouscomponents of hydraulic jump type stilling basins and bucket type energydissipators below spillways and outlet works founded on rock.

2. NOTATIONS

2.1 For the purpose of this standard, the following notations shall have themeaning indicated against each and as shown in Fig. 1 :

AI., = Anchor depth

Al t = Area of steel

a = Area of bar

b = Width of tooth

D1 = Depth of flow at the beginning of the jump measured perpen­dicular to the floor

Da = Depth conjugate (sequent) to D1 for horizontal apron

D3 = D2 + floor slab thickness

d = Effective depth

d. = Diameter of anchor hole

db = Diameter of bar

dt ::::: Depth of bucket at invert elevation

Ft = Tensile yield strength of steel with factor of safety 1·2

FbI = Permissible bond stress between steel and grout

4

Page 10: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527- 1'85

dtSOLID ROLLER BUCKET

dt

SLOTTED ROLLER BUCKET

STILLING BASIN

FIG. 1 DEFINITION SKETCH

Fbi == Permissible bond stress between ground and rock

g = Acceleration due to gr~vity

H c:: Head of water

hb c:: Height of basin block

L .=- Length of anchor

n == Number of anchors per rn'

q .' == Discharge in~.Dsi~y "R cs Radius of bucket

Sb CI Spacingbetween basin \>locks. ;

s

Page 11: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11S27- 1985

Tw = Tail water depth

tb = Thickness of stilling basin floor

tw = Width of bucket lip

Ub = Uplift head = Tw +. dt

V = Velocity of flow

W = Density of water

We = Density of concrete

Wr = Density of rock

Wa ::.:.: Width of basin block

ex == Ratio of bucket thickness at invert elevation to radius of

bucket = ~

P = Ratio of uplift head Ub to radius of bucket

; Angle between vertical and any radial line within exit anglefor bucket

~e - Exit angle of the bucket

ei = Inlet angle of the bucket

<fat = Permissible tensile stress of steel

3. TERMINOLOGY

3.0 For the purpose of this standard, the following definitions shall apply.

3.1 Hydraulic Jump Type Stilliog Basin - A stilling basin in which energyis dissipated by hydraulic jump principle.

3.Z Length of Stilling Basia - Dimension of the basin in the direction ofBow.

3.3 Width of Stilliog Basin - Dimension of the basin perpendicular to thedirection of main flow.

3.4 Cbute Blocks - Blocks provided at the entrance of the stilling basin tostabilize the formation of hydraulic jump, to increased effective depth, tobreak up flow into a number of water jets, to create turbulence and to liftthe jets off the floor to reduce basin length.

6

Page 12: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : lt527 • 1985

3.5 Basin Blocks or Baffle Blocks - Obstructions set in the path of highvelocity water, such as piers, on the apron of an overflow dam, weir or dropand to dissipate energy thereby preventing scour downstream to controlthe position of hydraulic jump.

3.6 End Sill - A vertical, stepped sloped or dentated wall constructed atthe downstream end of a stilling basin. It may be rectangular, trapezoidal,Hornsby, Schoklits, Smetana or Rehbock type.

3.7 -End Weir - Sharp or broad crested weir constructed at the end ofstilling basin floor to maintain adequate tail water level for all discharge.

3.8 Key Wall -- Small solid wall downstream of end weir penetrating infoundation to prevent retrogression.

3.9 Solid Roller Bucket Dissipator -- A bucket type energy dissipaterwhich consists or a bucket like apron with a concave profile of considerableradius and a lip which deflects the high velocity flow away from thestream bed and upward forming elliptical hydraulic rollers, namelysubmerged rollers in the bucket, and ground rollers downstream of thebucket. Energy dissipation is accomplished by the interaction of the sub­merged roller in the bucket and the high turbulence created on the watersurface above and below the bucket. Suitable when the tail water depth ismoderately in excess of that required for the formation of a hydraulic jump.

3.10 Slotted Roller Bucket - A bucket type energy dissipater in which thelip wall is made up of alternate teeth and slots and below which a slopingapron is provided. This construction of the bucket materially reduces theintensity of surface boil and ground rollers.

3.t1 Trajectory Bucket --- A type of energy dissipator, employed in caseswhere the tail water depth is less than that required for the formation ofhydraulic jump, by throwing water away from the toe of the dam in theform of projectile into the air.

4. STRUCTURAL DESIGN OF STILLING BASIN FLOOR

4.1 General -- The basin floor elevation is generally decided on basis offoundation conditions and the length of the basin is decided on basis ofhydraulic considerations in accordance with IS : 4997-1968* and breadthdepends on number of openings and piers on spillway crest.

4.2 Design Forces .- The basin floor slab is subjected to hydrostatic uplift,pounding and vibrations from hydrodynamic forces in the hydraulic jump.On a yielding foundation, it may suffer differential settlement, therefore the

·Criteria for design of hydraulic jump type stilling basins with horizontal and slopingapron.

7

Page 13: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 • 1985

basin floorslab shall be designed for the stresses induced due to aboveforces.

4.3 Floor Slab Anchorages - Following two extremeconditions may prevailand critical of the two conditions shall be considered for design.

4.3.1 Casei - Stilling basin operating during spillway design flood asshown in Fig. 2. Water surface over slab at hydraulic jump profile fordesign discharge, that is spillway operating at MWL.

1---H

1 0 -]i.--~----~-~ ~,

T t;H

1FIG. 2 CASB I SHOWING UPLIFT FORCES

4.3.1 ClJSe II - Reservoir at FRL with gates closed when basin is empty( seeFig. 3 ).

NOTB - Case I is normally critical and same is considered for basin ftoor design.The design of anchors may also bechecked for Case II.

4.3.3 In view of drainage arrangements provided below the basin floor,it may be adequate to design floor slab with uplift force equal to 0'5( Da + tb) X W. Depth of water in stilling basin will fluctuate from D, to1>. as per jump profile. Provision of effective drainage system below stillingbasin floor is necessary.

4.3.4 The Dumber of anchors required in the upstream portion of apronshalJ be designed for unbalanced uplift equal to0·5 [ ( Da x W) + (tb X W) - ( D1 X W+ We tb ) j.

No. of anchors (,,)requited per ml [0'5 ( D. x W + Ib X W ) - ( D1 X W +We ;b )]

- Q X Ft,

8

Page 14: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

END WEIR

CONTRACTIONJOlt«

LINE OF ·DRAINS

FIG. 3 CASB II SHOWING UPLIFT FORCES

The number of bars will be rounded to next higher integer.

Spacing of anchors = r 1\J It

. Net upward forceActual force In each anchor = -- N f b

0.0 ars

~ l_~~.~.._(_~_2 ~. ~+~~~~.~...- (.Pt~±We!~__~_]n

Required bond length

or

Required bond length =

Actual force in each anchor.. _---....---. -~--·X---db-·--x .. ·Fb·~ .....~--- -.-------

Actual stress in each anchor'11: X d« x Fbi

The greater of the two should be adopted as anchor depth. The valuefor permissible bond stress will vary for different site conditions and pro­portion of grout. In absence of data assume following values for 1: 2grout proportion.

9

Page 15: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

whereFbl == permissible bond stress between steel and grout

= 6 kg/em'

Fbi = permissible bond stress between grout and rock

= 4 kg/em-( Bond length shall be checked for bond between steel andgrout and also for bond between rock and grout ).

db = diameter of bar.

d. == diameter of anchor hole.

4.3.5 Notwithstanding results of above calculations, minimum 3·0 mlong anchors shall be provided and dia of bar shall not be Jess than 25 mm.The diameter of hole into which anchors are placed and grouted shall benot Jess than 1·5 times diameter of anchor bar designed. The maximumspacing of anchor bars shall be 3 m centre to centre staggered in plan.

4.3.6 Check for Dislodging of Rock Mass Anchored Against upliftPressure - Length of anchors shall be sufficient to engage a conical mass ofrock with a vortex angle of 45° the submerged weight of which will with­stand the net upward force ( see Fig. 4 ).

ROCK CONERESISTINGUPWARD FORCE

l

- ..........--...-----.....--.-..~-- .........--z. GROUT 1:2

PROPORTIONFIG. 4 DBTAILS OP ANCHOR AND GROUT HOLB

10

Page 16: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

Total uplift pressure on plane 'ZZ' per unit areas shown in Fig. 4

= W ( D3 t tb + L)

Total uplift pressure per unit area == Weight of slab -t- weight of rock

(D'}. -1- tb )

W 2 + L =:=.: We X tb + Wr L

Therefore L == _!-l_'? W (!?~ ~ tb ) ~_We_~__!~ ..(Wr - W)

4.4 Basin Floor Slab Thickness - The thickness of floor slab depends onthe foundation conditions and magnitude of uplift forces. A slab of about600 mm thickness is the minimum recommended. Actual slab thicknessneeded shall be determined by analysing hydrostatic uplift and differentialfoundation movement.

4.4. t Floor Slab Reinforcement - In thick slabs on rock foundationsnormally covered with tail water, structural reinforcement is not necessaryexcept possibly in the baffles. Uplift on a slab should be taken care of byadequate anchors. The slab is divided into independent approximatelysquare panels by contraction joints parallel and perpendicular to channel orbasin centre line to avoid serious shrinkage and temperature cracking withthe use of nominal reinforcement which does not extend across the joints.Size of panel should be large enough to resist destorting hydrodynamicforces, at the same time the quantity of concrete in a panel may be manage­able to be completed by available machinery in one single stretch. Panelsshould be cast in alternate bays with construction joints.

4.4.2 The independent panels of slab are reinforced with small amountof steel to prevent harmful cracking resulting from shrinkage and tempera­ture stresses not relieved by contraction joints and on yielding foundationsto avoid possible cracking from differential settlement. Usually, a slab onunyielding foundation is reinforced in the top face only because bond bet­ween the concrete and rock at the bottom is relied on to distribute shrinkagecracks and to minimize bending stresses in the anchored slab for theassumed uplift head. The minimum amount of reinforcement for independentpanels on unyielding rocks is 20 mm q, bars at 300 mm centre-to-centreboth ways. Additional reinforcement shall be provided for unfavourablefoundation condition or for high hydrostatic uplift pressure.

4.4.3 On relatively yielding rock foundations, the independent floorpanels are subject to possible differential movement of adjacent blocks anda key at each transverse contraction joint ( extending into foundation underthe joint attached to the slab downstream and supporting the slab upstream

11

Page 17: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 .. 1985

from the joint) may be required to prevent the downstream side of a jointfrom being raised above the upstream side as water at high velocity strikingsuch a projection would increase the hydrostatic pressure in the joint andhence the uplift under the slab. The higher the velocity the more seriouswill be the condition resulting from such relative movement. The keys alsoincrease resistance to possible movement and serve as seepage cutoffs down..stream from transverse drains. For details of key 7.2.3 of IS: 5186..1969*may be referred.

4.4.4 Concrete and Reinforcement Cover - The concrete of M-l 5 gradeup to 40 m ( crest-apron level) and concrete of M-20 grade above 40 m fallshalt be provided. Chute floor and stilling basin slab shall have minimum100 mm cover for reinforcement.

4.5 Basin Blocks or Baffle Blocks ( Structural Provisions)

4.5.1 General - Location and optimum shape of baffle blocks shall bedecided on the basis of IS : 4997-1968t. The dimensions of the basinblocks are shown in Fig. 5. The purpose of the block is to dissipate energyand thereby to reduce the length of basin.

FIG. 5 BASIN BLOCK.

.Criteria for desiln of chute and side channel spillways.tCriteria for desigQ of hydraulic jump type .tilUD. basins with horizontal and

.Ioping aprOD.

12

Page 18: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 • 1985

hb == height of basin block,

Sb == spacing between the blocks.

Wb = width of block, and

DB '= conjugate depth.

4.5.2 Forces on Basin Blocks - Dynamic force against the upstream faceof the baffle blocks is approximately that of a jet impinging upon a planenormal to the direction of flow.

Force P acting at hb/2 = 2WA ( D1 + hV1 )

where

W = unit weight of water,

area of upstream face of block, and

specific energy of the flow entering the basin.

4.5.2.1 Negative pressure on the back face of the blocks will furtherincrease the total load. However, this may be neglected if above equationis used. Baffle block is to be designed as cantilever as shown in Fig. 6.

p

FIG. 6 FORCES ON BASIN BLOCK

4.5.3 Reinforcement - The reinforcement shall be calculated by thefollowing formula and placement of the reinforcement is shown in Fig. 7and 8.

Area of steel AI' == Ma.t. j. d.

13

Page 19: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527- 1985

LINKS ~20 mm (1300 c/c

MAIN STEEL BARSONE AT EACH ENDCORNER

FIG. 7 VERTICAL SECTION SHOWING GENERAL ARRANGBMENTOF REINFORCEMENT

FIG. 8 PLAN AT BOTTOM OF BLOC"

whereM = moment due to force P ( defined in 4.5.2 ),

hb==Px 2'

all = permissible tensile stress of steel, and

d = depth of block.

NOTB 1 - The bame block is tied into the floor slab by reinforcing steel in It.

Non 2 - All reinforcing steel in a baffleblock is placed minimum ISO mm tromthe exposed surface because of the possible erosive and cavitatio~action of tho hiahvelocity currents.

14

Page 20: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 • 1985

4.6 Chute Blocks- Nominal reinforcement of about 20 mm '" at 300etcboth ways may be provided on all exposed faces duly anchored in apronconcrete.

5. SPILLWAY BUCKET REINFORCEMENT

5.1 SoUd Roller Bucket - ( See Fig. 9 and 10).

CONTRACTIONJOINT

FOUNDATIONPROFILE

MAIN STEEL

-ADISTRIBUTION

STEEL

. TOE TRENCH

FIG.9 TYPICAL SECTION OF A BUCKET

5.1.1 Forces and Moments - Horizontal force on the bucket is due tochange in momentum and is given by the following formulae:

Total horizontal force on the lip ( F ) = WbVg ( 1 - cos '0)

. FXR(I-cose.)Moment of the horizcntal force about plane A-A, M:=; -----2-----

Effective depth d of bucket for resisting moment ( M )

d = V RI +<i~srne;--·-+--·t~T- R - effective cover

5.2 Reinforcement - Area of the steel Aet to resist moment M is given

Mby Al t = j rr:a.,. .a.

15

Page 21: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 • 19~

EFFECTIVEOEPTH,d

FIXEDV CGS (cIJ+d~)

FIG.IO FORCBS ON THB BUCKET DUB TO MOVING WATBR

Provide minimum steel ( along flow) 20 mm " at 300 c/c

Provide distribution steel = 20 percent of main steel. Minimum 16 mm",at 300 cjc

( Refer Fig. 9 ).

5.3 Anchorage of Spillway Bucket - (See Fig. 11).

Assuming 50 percent of the uplift force (p -. r ffi ti draiN d e I ., - c.' rovrsion 0 e e~ rve ramage

et upwar rorce unit area - f'O system for bucket 18 essential)

1'. =R [0-5 QW - ~ CI -W {I- 1- \sin 2 ~e+sin2.9i )+! (B.+ el)}]U r C C (SID 60 +SID 8. )

Anchorage steel/unit area = Fa/ Fe

A., = :, [0'5 W~ - We ~ -

~ {l- i (sin 2 Be ~ sin 28. >. + i (8. + at )I]o _ ( sin e. + SID 8i )

16

Page 22: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

R

CONTRACTIONJOtNT

tUPLIFT

FOUNDATIONPROFilE

FIG. 11 UPLIFT AND BODY FORCES ON THE BUCKET

A 4-Number of anchors per m~, n= -. ~~- and spacing of anchors == .J.._ .a n

5.3.1 Length of Anchors - The length of anchor bars is governed by thebond strength and density of rock, the criteria being that the stresses onhorizonal plane passing through the bottom end of anchor bars should notbe more than permissible tensile stress in the rock (this is usually taken aszero except in hard sound rocks). A cone of rock having vertex angle of45° is assumed to be bonded to anchor bar. As the anchors are usuallyprovided at close spacing (0-75 m to 2'5 m clc ), the cones of bonded rockwill be overlapping ( see Fig. 12). It is, therefore, possible to consider theentire rock mass up to bottom end of anchors as countering the uplift forceson the plane Z -- Z without introducing significant errors.

S.3.1.t Considering the equilibrium of vertical forces on plane Z - Z,we have net upward force at the base of bucket/unit area + additionaluplift head ( for depth L ) bounded by planes AA and ZZ.

17

Page 23: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985 .

IUCKET

Z

CONE OF ROCK ASSUMEDTO BE ATTACHED TOANCHOR BARS

FIG. 12 ANCHOR BARS FOR COUNTERING UPLIFT

If L is the length of anchors below bucket foundation (that is, verticaldistance between planes AA and ZZ ).

On substitution, we get,

R [ 0-5 W ~- We «-We X { I _ 1( sin 2 8~tsin.2 e~_'-~_..!:.it.ge+9!1 } ]( SID 6e+sin 8. )

+ W.L. = WrL

where density of rock ( Wr ) is taken same as that of concrete ( We ).Re-arranging and substituting we have

A. t r;L = ----------Wr-W

The above equation has been derived on the basis that no tension ispermissible in the foundation rock. However, in sound and hard rocks,some tension can be allowed in rock to reduce anchor length.

18

Page 24: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - .985

If ar is the permissible tension in rock, then it can be seen that theabove equation gets modified as

L = _~~"-_ Ft - ~Wr -w

5.3.2 Check for B011d Length - Length of anchor bars obtained fromconsiderations of the preceding clause should be checked for bond failureas explained in 4.3.4 and 4.3.5.. The anchors are grouted in holes drilled bystandard drill bits, In addition to bond between bar and grout, bondbetween the grout and rock should also be checked which, in most cases, isthe weakest link.. The usual practice is to assume a bond strength of4 kg/ems between the grout and rock contract surface.

6. SLOTTED ROLLER BUCKET STRUCTURAL PROVISION

6.1 General

6.1.1 Dimensions of the roller bucket can be worked out on the basis ofIS : 7365-1975*. Definition sketch is shown in Fig. I. For anchordesign S.3 will be applicable. Provision of effective drainage system belowthe bucket is essential.

6.1.2 A vertical contraction joint perpendicular to the flow in the bucketis proposed at the invert elevation of the bucket and another vertical jointis given at junction of 8° and 16f) aprons as shown in Fig. 20. Generallyone panel consists of two teeth, one full slot and two half slots with trans­verse joints in between panels as shown in Fig. 13. With modificationsdifferent panel arrangements can also be adopted..

6.1.3 Discharge/m == q ;.:7.: Q/L rn3/s/m

where

Q total design discharge at MWL;L length of bucket spillway;V 4---i.---g-ff m/s;H = fall of water ( head) from MWL to bucket invert.

6.2 Design of Reinforcement for Bucket Tooth - ( Figure 14 shows defini­tion sketch of bucket tooth. )

6.2.1 Horizontal force on tooth above plane 'AB' is shown in Fig. 14.

F1

= W.q.V. (cos rp - cos 6.) X b (approx)g

-Criteria for hydraulic design of bucket type energy dissipators ( underrevts!0" ).

19

Page 25: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 • 1985.. 1l

The tooth has to be designed as a cantilever ( vertical) ,fixed at bottomAB ana b = width of bucket tooth at downstream end.

Bending moment M = PI X ~ where h = height of tooth as shown inFig. 14.

u/s B

CQNTbRACTIONJ tNT

~--- I ----.j..f APRON(ON,E PANEL)

FJo.13 PLAN SHOWING PANEL WITH Two TEETH

PIG. 14 DBPlNITlQN SXlrfCIl OF BUCKET TQOT"

20

Page 26: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

6.2.2 Area of steel ( As! ) = M

IS : 11527 • 1985

where

d = effective depth =.f (R cos cP )a+( R sin 80+0'05 R )1 - R - cover

a) Main steel ( to be provided along curve ), and

b) Distribution steel =..: 20 percent of main steel (to be provided inportion below plane AB in Fig. 14).

NOTE 1 - Check that minimum reinforcement is 20 mm t/J, 7 numbers per tooth.

NOTE 2 - Cover in radial direction should be minimum 80 mm,

6.2.3 Design ofLinks for Tooth - Provide 20 mm t/J link reinforcementat 300 mm clc around tooth in the direction perpendicular to flow. Distri..bution steel for links shall be provided on three side faces of tooth and shallbe 20 rom tp at 300 rom clc.

6.3 Design of Reinforcement for 8°AproD - Provide nominal reinforcementas under:

a) Along flow (main steel) :::= 20 mm f/J at 300 mm clc, and

b) Perpendicular to flow (distribution steel) = 16 mm rP at 300 mmcl«.

6.4 Desigo of Reinforcement for 16'" Apron - Horizontal force on 16° apron

F~ = ~J:!':.q!:,! (cos 8° - cos 16° )g

where

b1 VVa -~

b, - width of slot at entry

ba width of slot at exit

The horizontal force on apron is due to change in direction as above

and it acts at ~s above apron level (kg = size of 16° apron ).

B di h'Jen 109 moment = F'/, x 2

Area of steel = B.M. Al tCsst.j:d2 =

21

Page 27: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

~

MA

INST

EEL,~

liN

KS

APR

ON

(Cla

use

6-'

)(C

lau

se6'

2·)

DIS

TRIB

UTI

ON

ST

EE

L16

°A

PR

ON

(Cla

use

6-!-

)

FIG

.15

RE

Il\'F

OR

CB

ME

NT

DE

TA

ILS

FOR

BU

CK

ET

,T

OO

TH

AN

DA

PRO

N

... rn ­... ~ • .... I til

Page 28: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

whered. == effective depth for 16° apron = ha cos 16° - cover

NOTE - Minimum steel shall be provided as mentionedin 6.3.

6.5 Sample calculations are given in Appendix A.

APPENDIX A

( Clause 6.5 )

SAMPLE CALCULATIONS FOR SLOT1'ED ROLLER BUCKET

1) Exit angle 6e = 45° 5) Radius of bucket =--:; 9-0 m

2) Length of bucket = 237·0 m 6) Invert level of bucket = R_L. 403·50 m

3) Discharge e at MWL 1) Junction of 8° and 16° apron= 14 501 cumecs = R.L. 404-37 m

4) Width of tooth at dis end 8) MWL = R. L. 434-800 m= 1-125 m

. 14 501DIscharge q = 237 == 61-18Scumecs

Say q = 62 cumecs/maccording to 6.1.3.

V=V2gH

= V 2><-9;81 x 31·30 = 24·781 m/s

where H = Fall of water ( head) from MWL to bucket invert( 434·800 - 403·50 ) = 31·30 m

A-I. DESIGN OF REINFORCEMENT FOR BUCKET TOOTH

Horizontal force on tooth above plane AB

FI = W.q.V ( cos", - cos 45") x bg

23

Page 29: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 - 1985

according to 6.2.1

h ..L Radius - (junction of 8° and 16° apron - invert level)were cos 'f' = Radius

9 - ( 404·37 - 403-5 ):;..~_. --·--·--'9----

... ; = 25-4°

_ F - 1 000 x 62 x 24·78 x 0-1962 x 1-125_. 1 - 9-81

F1 :::-- 34 568·1 kg

Horizontal ( water) Force :-..: F1

acting at a distance 4- from bottom.

h ='-= 1-765 m ( height of tooth)

hB.M. ~ F1 X 2- (6.2.1)

=:= 30 506-35 kgm

Effective depth d = v' (R cos if> )2 + (R sin 6e + 0·05 R )1 - R -cover

.'. d = 152 em

Area of steel All ~ B.M. ( see 6.2.2 )a.t- j.d-

30 506-35 x 100== 1 J50 x 0·84 X 152

20·78 cn12

Provide 20 mm eP bars, 7 numbers per tooth,

Distribution steel 20 percent of main steel = 4·4 cms

Provide 12 rom '" bars at the rate of 250 mm clc below plane AB.

Design of Links - Provide 20 mm l' link reinforcement at 300 mm c/oaround tooth in the direction perpendicular to flow. Distribution steel forlinks shall be provided on three side faces of tooth and shall be 20 mm p at300 mm clc.

24

Page 30: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IS : 11527 • 1985

A·1. DESIGN OF REINFORCEMENT FOR 80 APRON

Provide nominal reinforcement as under:

a) Along flow = 20 mm c/J 300 mm c/c.

b) Perpendicular to flow = 16 mm ~ at 300 mm elc.

A-3. DESIGN OF REINFORCEMENT FOR 160 APRON

Horizontal force on 16° apron .

t: W.q.V2 (8° 160 )1'2 == -- cos - cosg

according to 6.4.

where

0·838 x 24·780·450 = 46·145 rnJs

.', F2 = 8458 kg

h'JB.M. = F2 X -2

where h2 is rise of 16° apron == I· 3 In

1·3... B.M. = 8458 X -2-

:---= 5498 kg.m

ASl = ~ .. B.'1-___ (see 6.4 )Gst j.d 2

where d'A ..-..~ (h;? cos 16° - cover) = 1·25 - 0-1 = 1·15 m

549 800.. A!at = Tl50 X -0·84 X 115 :-:-: 4·95 em"

Min Steel provided - a) Along flow = 20 mm tP at 300 mmc/c

b) Perpendicular to flow = 16 mm r/> at 300 mm cie.

25

Page 31: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

IN1'ERNAnONAL" SYSTEM 01' UNITS (81 UNITS)

.... tJDItI

QuAN11TY UNIT SYMBOL

Lenpb metre mMass kilogram qTime second •Electric current ampere AThermodynamic kelvin K

temperatureLuminous Intensity candela cdAmount of substance mole mol

Suppl...tarJ UDits

QUAN11TY UNrr SYMBOL

Plane angle radian radSolid angle steradiaD II"

Den,ed Uolts

QUANTrrY Ulm SYMBOL DBPlNlnON

Force newton N 1 N 11:II 1 kg.m/s-Energ)' joule J I J =- 1 N.mPower watt W I W e= 1 u«Flux weber Wb 1 Wb == 1 V.sFlux density tesla T 1 T C:::I 1 WhIm·Frequency hertz Hz I Hz at 1 cis (8-')Electric conductance siemena S 1 S c:a 1 A/VElectromotive force volt V 1 V == 1 W/APressure, 8tre81 pascal Pa I Pa CI!II 1 N/ml

Page 32: IS 11527 (1985): Criteria for structural design of energy ...IS : 4997-1968 IS : 7365-1974 Criteria for design of hydraulic jump type stilling basins with horizontal and sloping apron

.:(8). I N D tAN S TAN 0 AR 0 81 N 8 TI ru T ION

36 2499

{l~~:~, .{...41. ". '.2.442.. :41' 2'5' 19.41 29 16

HeadquartersJ

Manak Bhavan, g.8ahadur Shah Zafaf'Marg, r"EW OELH'I 110002Telephones: 3.31 01 31, 3 31 1.3 75 Telegrams: Manaksanstha

( Common to all Offices)Tetepbon«

6 3292 9·5.Re·glol1s/ Of/lees;·.Wes·terri ; Manakalaya~E9 MIDC,r\l1arol, Andheri ( East J.

, SO'MBAY 400093fEastern : 1/14 C. L T. Scheme VII M, V-t. p. Road,

. ; Maniktola t CALCUTTA 700054Northern: SeQ 446..446, Sector 35-C,

CHANDIGARH 160036'. Southern: C. I. T. Campus, MADRAS 600113

53627

22 10 S3 .

{2-S3 48

.2.63 4922 48 05 .

6 '27 16

. . ~

'-{O'3471, .698'32".

:{.. 21' ,6.8 76 .'.' 21. 82 92

623055227

PatJ.iputra Industrial Estate, PATNA 800013Hantex Bldg ( 2nd Floor I. Rly Station Road,

TRlVANDR.UM 6950'01Inspection Offics ( With Sale Point ):Institution of Engineera (India) Building, 1332ShivajiNagar, 5 :24 36

PUNE4109Q5 . ,

117/4188 SarvOdaY8 Nag~r,.KANPUR 208.005'

Stanch Of/ices:·Pushpak'; Nurmohamed Shaikh Margl Khanpur,

AHMADABAD 3800~Ol

'F·B·lock. Unity.Bldg, Narasimharaja Square,BANGALORE 660002

Gangotri Complex. 5th Floor, Bhadbhada Road, T. T. Nagar,BHOPAL 462003

PJofNo. 82/83, Lewis Road, B~~UBANES'HWAR75100'263/5 Ward No. 29, R. G. Barua Road",

6th l3ylane, GUWAHATf 781003··6"S"5·6C L. N. Gupta Marg (Nampally Station Road),

HYDERABAD 60·0001 -Rr4.Yudhist~r.Marg, C Schemet·JAIPUR 3·02005

~-'--'~-"--'..... , '.' ." ..

·.Sat... ·Off·ica In SQ,illbayla 'I Novelty' :C~.mb.'••..Graftf -·~O.d, . 8$ $5 ~88.omba.y:400007, .: . ". '

. tS·,t•• Offl<:8,ln Calcutt. laat..5 Chowringh••.Approach. P•.O•. P,incep 27 £8·00 .St,.et. C.. lcutte100012