IRC 2012 Code Compliant Wood Framed Residential Details
Incorrect Installations of Connectors with code references and remedies, discussion.
![Page 2: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/2.jpg)
You can help to avoid this, by being diligent with inspections.
![Page 3: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/3.jpg)
Note to Attendees
• This presentation is intended to point out details referenced in IRC 2012 that pertain to wood framed structures relative to use of metal connectors.
• Some states and jurisdictions have adopted amendments to the IRC 2012 to provide local or state provisions that are unique to the state or local practices that may deviate from the wording in this presentation.
• MiTek Builder Products division encourages designers, builders, engineers and architects to contact the permitting agency for the local building code in effect for the selected construction site.
![Page 4: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/4.jpg)
![Page 5: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/5.jpg)
USP Structural Connectors is a product brand of MiTek USA, Inc.
• With roots beginning as TECO in 1933, the original connector company.
• With recognized names as Silver LumberLok, Kant Sag, Hughes, Semco.
• Acquired in 2011 by MiTek (a Berkshire Hathaway Subsidiary), the world’s leading truss design software and hardware firm.
• Complete line of products for residential and commercial construction.
![Page 6: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/6.jpg)
Watch this 90 second MiTek corporate video, “Together We Rise”
www.mii.com/page/open.asp?frames=no&pid=12431
![Page 7: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/7.jpg)
Learning Objectives
• Highlighting IRC code provisions pertaining to prescribed use of connectors and acceptable alternate methods.
• Examine table loads manufacturers use to identify capacities of various species of wood.
• Understand IRC Codes with regards to fasteners used in residential framing and reduced capacities for alternate fastener usage
• Viewing and evaluating photos of miss-installed connectors or incorrect application.– Open discussion of remedies including contacting
manufacturer for approval as installed or rejection.
![Page 8: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/8.jpg)
Notes Regarding Code Versions
This presentation has been created based on IRC 2012.
Several slides, (the next 3) may be omitted in certain enforcement jurisdictions based on the version of the International Residential Code in effect or due to amendments that have modified local or state codes.
![Page 9: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/9.jpg)
Notice of ViolationR113.2 in the IRC code
This refers to the authorization for the Building Official to serve notice on the PERSON RESPONSIBLE for the work performed, deviation from details on an approved plan or in violation of a permit or certificate that had been issued for that project.
This differs in that it is directed to the PERSON RESPONSIBLE for the work, not necessarily the OWNER.
![Page 10: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/10.jpg)
Stop Work Order ProvisionR114.1
This provision enables the building inspector or code enforcement official to notify the owner, owner’s agent or builder or tradesman to STOPwork immediately (in writing) and to identify the conditions that must be met in order for work to resume.
![Page 11: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/11.jpg)
Lawful ContinuanceR114.2
• This point of the code refers to the ability of the person who has ben notified to STOP WORK to perform the work necessary to remove the violation or unsafe condition.
• Any work other than that is subject to penalties provided by law.
![Page 12: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/12.jpg)
Not a tornado, just high winds south of Syracuse, NY in July of 2014
![Page 13: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/13.jpg)
Fastener Changes Affect Connector Performance
Catalog nail vs. Replacement Fastener
![Page 14: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/14.jpg)
Chapter 4: Wood Foundations
• R402.1.1 references Fasteners for use BELOW grade in wood foundations for plywood on exterior side of wood studs must be 304 or 316 Stainless Steel.
• Wood foundations must not use electro-plated nails or galvanized staples even in the above grade portions of a wood foundation. These are the most common type in air powered nailers.
![Page 15: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/15.jpg)
R403.1.6 Foundation Anchorage
• Foundation anchorage is clearly defined for exterior walls and for interior walls on monolithic slabs for walls part of a BRACED WALL PANEL on page 79.
• The anchor bolts must be min. ½” diameter and extend min. 7” into concrete of grouted cells of CMU. The next slide will help determine the appropriate length of the anchor bolt.
![Page 16: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/16.jpg)
What length anchor bolt?
• If the bolt has to be 7” into the concrete, the concrete has to be how thick at the outside edge? (8”?)
• And if it has to go thru 1 ½” sill plate and have threads enough for a washer and nut, 7” + 1 ½ + ½” for washer and nut= total minimum 9”
• Why are so many 6” anchor bolts are sold at the supply centers?
![Page 17: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/17.jpg)
Hmmm…Oops!
![Page 18: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/18.jpg)
Additional Details on Page 79
• Familiarize yourselves with the provisions for spacing –
1. 6’ min, 2 bolts per plate section
2. Must have one bolt not more than 12” from the end of each plate section.
• Please be aware that it is difficult to find load values assigned to the power of the anchor bolts. ???
![Page 19: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/19.jpg)
Is this good or bad? What is needed?
![Page 20: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/20.jpg)
Typical “J” Bolt Installation
This is not the only way to do it !
![Page 21: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/21.jpg)
Exceptions are allowed that provide equivalent anchorage to ½” J bolts
• Typical FA3 Foundation Anchor
• Anchored to form boards
![Page 22: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/22.jpg)
Other Style Alternates
• Wrap around plate • Thru a hole drilled in plate
![Page 23: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/23.jpg)
Is it Equivalent??
Manufacturers test products to assign values that engineers and designers rely upon.
![Page 24: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/24.jpg)
Does this hold down look OK?Is it missing anchor bolts?
![Page 25: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/25.jpg)
How about this one?
![Page 26: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/26.jpg)
Is this acceptable?
![Page 27: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/27.jpg)
Will this pass?
![Page 28: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/28.jpg)
Pier and Curtain Wall Straps
R404.5.1.3 on page 106 refers to the embedment, gauge of the strap and number
and size of nails needed to install
![Page 29: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/29.jpg)
Typical Floor Truss Layout
![Page 30: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/30.jpg)
Floor Joist span table from mycarpentry.com
Nominal Size
Spacing (o.c.)
Species and Grade of Lumber ( based on 40 lb / sq. ft. Live Load)
Southern Yellow Pine Southern Yellow Pine Douglas Fir Eastern Spruce
#1 grade (kiln dried) #2 grade #2 grade Structural
2" x 6"
12 11-4 10-3 10-11 10-1
16 10-4 9-4 9-11 9-2
24 9-0 7-9 8-8 7-11
2" x 8"
12 15-0 13-6 14-5 13-2
16 13-7 12-3 13-1 12-0
24 11-11 10-3 11-3 10-6
2" x 10"
12 19-1 17-3 18-5 16-10
16 17-4 15-8 16-9 15-3
24 15-2 13-1 14-6 13-4
2" x 12"
12 23-3 21-0 22-5 20-6
16 21-1 19-1 20-4 18-7
24 18-5 15-11 17-6 16-3
![Page 31: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/31.jpg)
Refer to the IRC table on page 115 of IRC 2012 for floor joist spans
• Code book ,IRC 2012, page 120 identifies floor framing, allowable girder spans, amount of bearing on wood or metal (1 ½”).
• R502.7 calls for full depth solid blocking for lateral restraint at supports.
• R502.7.1 identifies BRIDGING
• Cutting, notching and drilling of floor joists is clearly explained in R502.8
![Page 32: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/32.jpg)
Floors, R502.6 Bearing
• To paraphrase the section;
• The ends of each joist, beam or girder shall have at least 1- ½” of bearing on wood or metal, or by the use of approved joist hangers.
• There are code evaluated joist hangers for a wide range of applications and load bearing conditions and lumber and beam sizes.
![Page 33: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/33.jpg)
Example of Seat Depth
• Note the seat depth • “D” is seat depth
![Page 34: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/34.jpg)
EWP manufacturers spells out what can be done. Is this acceptable?
![Page 35: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/35.jpg)
Wood Floor Trusses are Covered in R502.11
• Refer to pages 120-123 in the IRC 2012 for specific matters related to floor trusses and the modification, alteration and required bracing.
• SBCA, and BCSI, Building Component Safety Information have free information related to bracing floor and roof trusses for safety.
![Page 36: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/36.jpg)
Introducing our other speakers…
![Page 37: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/37.jpg)
Floor Trusses Along a Girder Beam
![Page 38: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/38.jpg)
Good Floor Truss Example
![Page 39: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/39.jpg)
Manufacturers Test for Fewer Nails
This is a table from the USP Structural Connector’s table for minimum/maximum load values with fewer nails.
![Page 40: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/40.jpg)
Is this a good installation of a floor truss?
![Page 41: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/41.jpg)
Hanger Styles
• Face mount hangers • Top mount or top flange and specialty hangers.
![Page 42: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/42.jpg)
Specialty Hangers
• Some used for skewed angle joists.
• Some for purlins or saddle joists.
![Page 43: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/43.jpg)
Here is a good bridging example!Other styles accommodate individual
framing needs.
![Page 44: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/44.jpg)
Can you find any problems?
![Page 45: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/45.jpg)
This is not a trick,any issues here?
![Page 46: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/46.jpg)
Floor joist supported by a bolted header on a brick wall: Good or bad?
![Page 47: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/47.jpg)
C’mon Man !?
![Page 48: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/48.jpg)
Chapter 5-507 Decks
• We are pleased to advise that there is a separate 1.0 hour presentation devoted entirely to decks, deck footings, stair spans, joist spans etc.
• We will be pleased to address future opportunities to share Safe Residential Deck design and Construction,
• Now on to Walls, Chapter 6.
![Page 49: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/49.jpg)
Wood wall framing R602.1
• The walls are the intermediate component that carry the load path from roof structure to the floor and on to the foundation.
• The walls support the gravity loads of the roof and floors above as well as resist lateral forces imposed on the structure.
• The walls are wide areas (like sails) that will collect the effects of wind, whether it be straight line, tornadic or gusts of varying intensity.
![Page 50: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/50.jpg)
Wood framed walls… Cont’d
• This entire chapter is classic “how to do it correctly” and prescriptively.
• A frequently overlooked detail is the defined fasteners for a variety of substrates attached to studs and the stud to plate and built up studs and creating double top plates.
• IRC2012 references nail diameters that are common to power driven, NOT a typical “COMMON” nail diameter.
![Page 51: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/51.jpg)
Compliant fasteners for walls
• Built up studs-face nail 24”o.c. 10d 3”x.135
• Built up header, 2 piece w/1/2” spacer 16d 16”o.c. 3 ½”x.135
• Rafter or truss to plate toe nail 3-16d or 3 10d common nails, 2 on one side and one on opposite side
• Top or sole plate to stud end nail-2 - 16d 3 ½”x.135
• Sole plate to joist or blocking 16d – 16” o.c. defined as 3 ½” x .135
• Plywood panels ½” or < use 6d 2”x.113 6”o.c. edge and 12” o.c. field. Use 8d 2 ½”x.131 in roof plywood.
![Page 52: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/52.jpg)
Footnotes are important
• Particularly, note on page 151
• Point “d” 4x8 or 4x9 panels shall be applied vertically.
• Point “f” 110mph winds speeds call for deformed shank nails, ring or screw shank must be used where mean roof height is 25’ or more.
• Questions? Comments?
![Page 53: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/53.jpg)
Walls with minimal sheathing can be braced by using factory engineered panels
![Page 54: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/54.jpg)
Braced wall lines and Braced wall panels are an hour long
separate course
We invite you to consider setting aside approximately 90 minutes for a separate
Lateral Wall Bracing presentation
![Page 55: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/55.jpg)
How do we secure the braced wall panels to the foundation?
• One way is via Pre-Deflected Hold-downs
• Tension Ties are an accepted method and there are others.
![Page 56: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/56.jpg)
R602.10 Metal Wall Bracing is OK• Metal wall bracing is
acceptable in lieu of Let-in-Bracing (LIB)
• A saw kerf is cut into studs and a “T” is driven in and nailed off
• Some strapping products do not require a kerf.
![Page 57: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/57.jpg)
Will plumbers hanger strap suffice?
![Page 58: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/58.jpg)
Is this good, bad or just poor workmanship?
![Page 59: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/59.jpg)
Is this going to pass or fail?
![Page 60: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/60.jpg)
How about this one?
![Page 61: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/61.jpg)
What’s right or wrong?
![Page 62: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/62.jpg)
R602.6.1 Notching a Top Plate
• When a top plate is notched or cut to 50% or more of it’s width, it must be reinforced with a GALVANIZED strap of 16 ga, 1 ½” wide and extend 6” on each side.
• There is an exception for wood sheathed walls on the side of the notch. (rarely happens on that side) See the next slide.
![Page 63: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/63.jpg)
Typical reinforced top plate
• The code does not require a double strap as is indicated here, a single Galv. Strap nailed per code is adequate.
![Page 64: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/64.jpg)
Will this be allowed?
![Page 65: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/65.jpg)
Major manufacturers have solutions for notched top and bottom plates
• International code plate that is 5” x 16” galv.
• International code plate that is 5”x8” galv.
![Page 66: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/66.jpg)
Roof-Ceiling Construction, Chapter 8
• Manufacturers make a variety of rafter connections to accommodate framing styles preferences
• R802.2 refers to framing details apply to roofs with 3/12 minimum pitch or greater.
• Where the pitch is less than 3/12, joist and rafter supports shall be designed as beams
• Collar ties or ridge straps to resist wind uplift must be connected in the upper 1/3 of the attic space.
![Page 67: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/67.jpg)
Ceiling joist and rafter spans tables are included on pages 379-398
• Spans differ with lumber species.
• 2x6 ceiling joist 16”o.c. of #3 Hem fir is 13’9” whereas same size #2 SYP is 17’8” these are maximum spans used as an example.
• It is crucial to verify the grade of lumber in use, some suppliers accept a grade lower to attempt to have a price advantage at the expense of safety.
![Page 68: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/68.jpg)
Rafter table comparisonthis example is from table R802.5.1(4)
• This assumes a dead load of 10 psf. and 16”o.c. and a ground snow load of 30 psf.
• The tables have many varying conditions included for environmental conditions.
• 2x8 #3 Hem-Fir span is 11’5” max
• 2x8 #2 SYP rafter span is 16’2” maximum
![Page 69: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/69.jpg)
Many framing practices drive the variety of connectors available.
• R802.3.1 both dwgs. • Manufacturers address I-Joists for rafters too
![Page 70: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/70.jpg)
Rafter/Truss to plate connection loads
• Note the different load capacities with various species of wood.
![Page 71: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/71.jpg)
There is a wide variety of Rafter/Truss to Plate Connectors
![Page 72: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/72.jpg)
R802.9 Framing of openings
• This section details the framed openings into an attic or area over ceiling joists.
• When the header joist is 6’ of greater, approved hangers must be used for the header to trimmer joists.
![Page 73: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/73.jpg)
Framed Opening
Does this conform?
![Page 74: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/74.jpg)
R802.10 Wood Trusses
• Have any of you witnessed or seen the aftermath of a truss roof collapse during construction?
• Bracing is required!!!!!!
• Per R802.10.1, truss design drawings must include permanent truss member bracing locations.
• R802.10.3 says trusses must be braced to prevent rotation, see the note related to SBCA.
![Page 75: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/75.jpg)
Plans for safety
• Using steel straps • More steel braces
![Page 76: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/76.jpg)
SBCA Building Component Safety Information guide
![Page 77: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/77.jpg)
Roof Tie Downs R802.11
• Trusses must resist wind uplift.
• Toe nailing is acceptable in CERTAIN instances.
– Some jurisdictions require toe-nail inspection if used.
• Please see the table in chapter 6 R602.3.(1)
• Individual rafters must be attached to supporting wall assemblies to resist loads imposed by various wind speeds as shown in table R802.11
![Page 78: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/78.jpg)
Girder Roof Ties
• Uplift girder tie (double) on left, corner on right
![Page 79: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/79.jpg)
Other Wall Types
• 4 Ply on masonry
![Page 80: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/80.jpg)
Looks nice, is it good?
![Page 81: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/81.jpg)
Skewed Connections
![Page 82: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/82.jpg)
Is this a good rafter strap?
![Page 83: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/83.jpg)
“High Five” to the person who can identify this malady!
![Page 84: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/84.jpg)
Special devices for maintaining dimensional integrity
This allows for trusses to move up and down with snow or other loads while keeping aligned O.C. on the NON BEARING plate.
![Page 85: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/85.jpg)
They don’t make a connector for that !
• Don’t believe it !
• We hear about the local metal shop making connectors to hold weird beams and angles, welded right there near the site, based on the information given.
• It’s about this long, about this high and spans about 13 feet.
• It will hold about X , are you comfortable with (about) engineering. Major manufacturers can solve most applications as long as an engineer can provide accurate dimensions and calculate the loads imposed on the joint.
![Page 86: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/86.jpg)
![Page 87: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/87.jpg)
![Page 88: IRC 2012 Code Compliant Wood Framed Residential details · unique to the state or local practices that may deviate from the wording in this presentation. •MiTek Builder Products](https://reader033.vdocuments.us/reader033/viewer/2022060218/5f0677d67e708231d41824d0/html5/thumbnails/88.jpg)
Questions or Comments?
• Any particular area you would like to visit?
• Can you share brief examples of errors in framing and how you helped get it fixed?
Thank you for taking the time to share and explore the code’s requirements that can result in safer-stronger-survivable-structures.