iq analyzer 6400/6600 series cutler-hammer power management products high end metering capabilities
TRANSCRIPT
IQ Analyzer6400/6600 Series
Cutler-HammerPower Management Products
High End Metering Capabilities
22
Available Available May 2000May 2000
New IQ Analyzer
6400/6600 6400/6600 SeriesSeries
33
Power Quality Monitoring
• Over 150 metered parameters for comprehensive diagnostics
• Assess trends, harmonics and waveforms to prevent process disruptions and equipment damage
• Isolate and diagnose power quality problems by analyzing historical metered data
• Control energy usage and costs via measurement, on-board data storage and time-of-use registers
IQ Analyzer
44
Revenue metering accuracy ANSI C12.16 ( 1% ) ANSI C12.20 ( 0.5% ) IEC 687 / Canada ( 0.5% ) Independent certification
Time Of Use Registers Expanded event storage UL/CUL/CE
(CSA applied for) New Display & Faceplate 4 Custom Display Screens
Overview
55
IQ Analyzer Key Features
• High-speed waveform capture– Programmable event triggers– 2 cycles @ 128 samples/cycle & 8 cycles @ 32
samples/cycle– 11 channels of voltage & current information are
saved– Local display of waveform (6600 series only)
• Measures current and voltage through 50th harmonic– Display harmonic spectrum on local display (6600
series only)
66
IQ Analyzer Key Features
• CBEMA/ITIC event display via PowerNet• dv/dt trigger captures subcycle voltage
disturbances (6600 series only)• Communication flexibility:
– INCOM via IPONI– Ethernet via EPONI & EPONIF– RS-232 via RS232PONI– Modbus via MPONI (Coming Soon!)
77
IQ Analyzer Key Features
• The IQ Analyzer stores 44 different minimum & maximum values including:– Current– Voltage– Power– Power Factor– Frequency– THD
88
IQ Analyzer Key Features
• On-board event data logging • Auxiliary I/O capabilities
– Analog Outputs (3) 0-20mA/4-20mA 1% accuracy
– Analog Input (1) 0-20mA/4-20mA 1% accuracy
– Digital Inputs (3) optically isolated +30Vdc– Digital Outputs (4) Form C contacts 10A @
240Vac
99
IQ Analyzer Key Features
• Monitors L-L, L-N, L-G and N-G voltage– PT ratios from 1:1 to 5,000:1
• Monitors phase, neutral and ground current– CT ratios from 5:5 to 10,000:5– Up to 40A continuous, 300A for 1 second
• Measures % Total Harmonic Distortion (THD) for current and voltage
1010
New Features• New Trending Capabilities
– 4 Independent trends– Up to 6 parameters per trend– Can chose from over 94 parameters – Total of 90K bytes of storage
• Single parameter every 15 min. for 234 days
– Independent memory allocation for each trend
– Used with PowerNet for CBEMA/ITIC curve plotting utility
1111
CBEMA Curve Utility
1212
New Features• New Trending Capabilities
– Sampling rate can be set from 8 cycles to 5040 minutes (3 1/2 days)
– Trend 1-3 can save data on a discrete input– Trend 4 can save data on an event– If the time period is set for an integer divisor
of 60 the period starts at the next full hour.
1313
New Features
• Data Logging Features– Time & Reason for last 504 Events– Any meter event is saved– New Status Change Indicators
• Time of Alarms• Power Up• Resets• Setting Changes• INCOM Connection
1414
New Features• In addition to the data logging of the
last 504 events last 10 Waveform Events are also stored
• The real time clock can be synchronized to the line to correct for long term errors (w/o PowerNet)
• Programmable CT Polarity Setting– Change CT polarity from calibration menu– Last event under “Power Factor”
1515
New Features
• Time Of Use (TOU) Energy Registers– 32 Schedules
• 8 Weekday - 8 Holiday• 8 Saturday - 8 Seasons• 8 Sunday
– Each schedule can change 9 times a day– 4 Different utility rates– Watt-hours, VAR-hours, VA-hours recorded
1616
New Features
• TOU Demands– Amps, Watts, VARS & VA
1717
Improvements• New Case
– Polycarbonate for higher durability & temperature
– Rugged outer edge– Reset button changed from red to blue
• New Display– Reverse mode, LED
backlit LCD– Yellow on black– High reliability
1818
Improvements
• Custom Screen Enhancements– Allows programming of 7 parameters
per screen– Now 4 custom screens– List of programmable items extended
• Clock• Min/Max Values since last trend• Magnitude THD (V and A)
– Displays each screen for 5 seconds
1919
New IQ Analyzer
• Old IQA6000/6200 catalog numbers replaced with new 6400/6600 series– IQA6410 - Separate Source PS– IQA6420 - DC PS– IQA6430 - Self Powered Three Phase PS– IQA6610 - Separate Source PS
w/waveform– IQA6620 - DC PS w/waveform– IQA6630 - Three Phase PS w/waveform
2020
• Instruction book changes to TD 17530B
• New Technical Data available– TD.17.02A.T.E
• New Color Brochure available– B.17C.01.S.E
Support Material
2121
Literature/Sales Tools/Getting Help
www.ch.cutler-hammer.com/pmp
Power Management Applications Support800.809.2772
Power Management Sales Managers
CHESS Power Automation Specialists
Product Guide - PG.17.01A.T.E
2222
Wrap UP
• Product Feedback• PMPC Support• Questions & Answers