ips-cip standard building program executive … building program executive summary ... submittal...

43
IPS Capital Improvements Program Standard Building Program Executive Summary Wil-Fra-Mar Building 320 East Vermont Street Indianapolis IN 46204-1640 317.263.6226 317.263.6224 (fax) www.schmidt-arch.com Division 15 - Mechanical Score Acceptable Notes 15010 - Basic Mechanical Requirements A/E Spec # Warranty Standard Project Warranty Submittal Samples for finish and color verification Record Drawings Product Data Shop Drawings Record Operating and Maintenance Manuals Special Comments or Conditions Certification All contractors shall be licensed to perform work in district area 15040 - Testing and Proof of Performance A/E Spec # Warranty Standard Project Warranty Submittal Test Reports Special Comments or Conditions Testing Schedule testing to allow a representative of the Owner to witness the test 1 = Meets Program Standards 2 = Generally Meets Program Standards 3 = Does not meet Program Standards Score Friday, April 08, 2005 rptSpecExecutiveSummary_ByDivision Page 1 of 43

Upload: phungdiep

Post on 12-Jun-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements Program

Standard Building ProgramExecutive Summary

Wil-Fra-Mar Building320 East Vermont StreetIndianapolis IN 46204-1640317.263.6226317.263.6224 (fax)www.schmidt-arch.com

Division 15 - Mechanical

Score Acceptable Notes

15010 - Basic Mechanical Requirements A/E Spec #

WarrantyStandard Project Warranty

SubmittalSamples for finish and color verificationRecord DrawingsProduct DataShop DrawingsRecord Operating and Maintenance Manuals

Special Comments or ConditionsCertificationAll contractors shall be licensed to perform work in district area

15040 - Testing and Proof of Performance A/E Spec #

WarrantyStandard Project Warranty

SubmittalTest Reports

Special Comments or ConditionsTestingSchedule testing to allow a representative of the Owner to witness the test

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 1 of 43

Page 2: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15050 - Basic Mechanical Materials and Methods A/E Spec #

WarrantyStandard Project Warranty

SubmittalShop DrawingsRecord DrawingsRecord Operating and Maintenance ManualsProduct DataSamples for finish and color verification

15060 - Basic Piping Materials and Methods A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct DataShop DrawingsRecord Operating and Maintenance ManualsSamples for finish and color verificationRecord Drawings

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 2 of 43

Page 3: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15100 - Valves A/E Spec #

WarrantyStandard Project Warranty

SubmittalShop DrawingsProduct Data

Approved ManufacturersCraneHammondGrinnellMilwaukeeStockhamKeystoneVitaulic Company of AmericaNIBCONexus Valve Specialties

Special Comments or ConditionsCoordinateCoordinate valve type with installation

Domestic Water ApplicationsFor domestic water applications: 2" and smaller - ball valves; 2-1/2" and larger - butterfly valves

15130 - Refrigerant Piping A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersRefrigerant Valves and SpecialtiesAlco Controls Div., Emerson ElectricHenry Valve CompanyParker-Hannifin Corporation, Refrigeration and Air Conditioning Div.Sporlan Valve Company

Quality AssuranceQualify brazing processes and brazing operators in accordance with ASME "Boiler and Pressure Vessel Code," Section IX, "Welding and Brazing Qualifications"

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 3 of 43

Page 4: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15135 - Meters and Gages A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct DataShop Drawings

Approved ManufacturersDirect Mount Dial ThermometersMarsh Instrument Co.; Unit of General SignalTrerice (H.O..) Co.Weiss Instruments, Inc.Miljoco Corporation

Glass ThermometersErnst Gage Co.Marshalltown Instruments, Inc.Trerice (H.O..) Co.Weiss Instruments, Inc.Miljoco Corporation

Pressure Gage CocksSame as for Pressure Gages

Pressure Gage Connector PlugsPeterson Equipment Co.Sisco

Pressure GagesAmetec/U.S. GaugeMarch Instrument Co.,; Unit of General SignalMarshalltown Instruments, Inc.Trerice (H.O..) Co.Weiss Instruments, Inc.Miljoco Corporation

Temperature Gage Connector PlugsPeterson Equipment Co.Sisco

Thermometers WellsSame as Thermometers

Special Comments or ConditionsCoordinateCoordinate valve type with installation

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 4 of 43

Page 5: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15140 - Support and Anchors A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersHangers and SupportsB-Line Systems, Inc.Carpenter and Patterson, Inc.Corner & Lada Co., Inc.Elcen Metal Products Co.Fee & Mason Mfg. Co.; Div. Figgie InternationalITT Grinnell Corp.NIBCO (Tolco pipe hanger and supports)

Roof Equipment SupportsCustom Curb, Inc.Pate Co.Thycurb Div.; Thybar Corp.

Saddles and ShieldsElcen Metal Products Co.Pipe Shields, Inc.

Quality AssuranceComplianceProvide products which are UL-listed and FM approvedProvide products which comply with applicable codes

Special Comments or ConditionsAnchorsNo lead-based anchors

CoordinateCoordinate support type with installation

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 5 of 43

Page 6: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15190 - Mechanical Identification A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersBrady (W. H.) Co.; Signmark Div.Seton Name Plate Co.Brimar Industries, Inc.

Quality AssuranceCoordinateCoordinate valve tag schedule with installation

Special Comments or ConditionsValve ChartsValve charts shall be laminated before framing

Valve Tag ChartMount valve tag chart on wall as noted in drawings

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 6 of 43

Page 7: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15240 - Drainage and Vent Systems A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersJay R. Smith Mfg. Co.Josam Mfg. Co.Wade/Tyler Pipe; Subs. Of Tyler Corp.Watts Drainage ProductsZurn Industries Inc.; Hydromechanics Div.MIFAB Manufacturing, Inc.

Special Comments or ConditionsPipe ApplicationsIn return air plenums use no-hub cast-iron piping.Storm Drain Piping Above Ground, Within Building, PVC Type DWVSanitary Drain and Vent Piping Above Ground, within Building, Service weight cast-ironSanitary Drain and Vent Piping Below Ground, within Building, Service weight cast-ironStorm Srain Piping Below Ground, Within Building, Service weight cast-iron.

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 7 of 43

Page 8: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15250 - Mechanical Insulation A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersArmstrong World Industries, Inc.Certainteed Corp.Knaut Fiber Glass GmbHManville Corp.Owens-Corning Fiberglass Corp.Pittsburgh Coming Corp.Rubatex Corp.

Quality AssuranceThe products of only one manufacturer shall be used for each particular insulation

Special Comments or ConditionsCoordinateCoordinate insulation type with drawings

Lined DuctworkNo lined ductwork (exception: downstream of VAV terminal unit, for sound attenuation)

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 8 of 43

Page 9: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15300 - Fire Protection System A/E Spec #

WarrantyStandard Project Warranty

Special Product WarrantyEmergency Repair ServiceContractor shall provide emergency repair service for the system, within 24 hours of a request by the Owner during the Warranty Period

SubmittalOperation and Maintenance ManualsProduct DataContractor's Material & Test CertificationsShop Drawings prepared in accordance with NFPA 13Calculations stamped by a registered Engineer

ReviewsSubmittals shall be reviewed by the Owner prior to return to the Contractor

Approved ManufacturersBackflow PreventerAmmes Model 3000 SS

Fire Department Connection (where applicable)Potter-Roemer, Inc.

Fire Protection ValvesNIBCO

Fire PumpsPeerlessAurora

Swing Check ValvesReliable Kennedy Victaulic

SystemReliable Automatic Sprinkler Co., Inc.Viking SprinklerMullerKennedy ValveMilwaukeeVictaulic Company of AmericaPotter-Rowmer, Inc.NotifierPotter Electric Signal

Tamper SwitchesPotter

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 9 of 43

Page 10: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

Water Check ValvesReliable Kennedy

Waterflow SwitchesPotter Viking

Quality AssuranceExperienceInstaller shall have been in the Fire Protection business doing work of similar size for at least 5 years.

Manufactured in USAll fire protection components and equipment shall be manufactured in the United States.

PipeCoordinate pipe specifications with use - NO THREADED THIN WALL OR LIGHT WALL PIPE WILL BE ALLOWED

Shop DrawingsShop Drawings shall include complete hydraulic calculations, certified by a registered engineer and reviewed and stamped by the Fire Marshal, the Owner's Insurance Underwriter and other local authority have jurisdictionPlans shall include: Floor Plans, flow test data used for the design of the system, vital area protected, detailed schematic of the sprinkler risers, complete schedule of products

ULAll devices, systems and materials shall be listed by UL for its intended use

Special Comments or ConditionsCoordinateCoordinate water source with Division 15 sections and local Water Utility requirementsCoordinate design criteria with building use and plans

Sprinkler HeadsSemi-recessed Chrome, bronze uprightSprinkler Heads are to be installed in the center of ceiling tile in lay-in type ceilings

TrainingUpon completion the Fire Protection Contractor shall provide the Owner with a minimum of 8 hours training in the proper operation and testing procedures of all fire protection components provided, furnished or installed.

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 10 of 43

Page 11: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15410 - Domestic Water Distribution Piping A/E Spec #

WarrantyStandard Project Warranty

SubmittalWelder's CertificationsProduct Data

Approved ManufacturersBackflow PreventersWatts Regulator Co.

Copper Joining SystemsRidgid/Viega ProPress

Dielectric UnionsPerfection Corp.Watts Regulator Co.Epco Sales, Inc.

High/Low Master Mixing ValveLawlerLeonardPowers HydroguardSymmons

Hydrants/BibbsJosam Mfg. Co.Jay R. Smith Mfg. Co.Wade/Tyler Pipe; Sub. Of Tylor Corp.Watts Drainage ProductsWoodford Mfg. Co.Zurn Industries Inc., Hydromechanics Div.

Individual Mixing ValvesLawlerLeonardPowers HydroguardSymmons

Pressure Regulating ValvesWatts Regulator Co.Bell & Gossett ITT

Shower Control Mixing Valves - Cast Brass BodyLawlerLeonardSymmonsPowers

Shower Control Mixing Valves - Concealed Mixing ValveLeonardPowers HydroguardSymmonsSpeakman Co.

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 11 of 43

Page 12: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

Vacuum BrakersWatts Regulator Co.Chicago Faucet Co.

Water Hammer ArrestersAmtrol, Inc.Josam Manufacturing Co.Jay R. Smith Mfg. Co.Wade/Tyler Pipe; Sub. of Tyler Corp.Watts Drainage ProductsZurn Industries Inc., Hydromechanics Div.PPP, Inc.MIFAB Manufacturing, Inc.

Quality AssuranceComplianceAll work shall comply with: ASME B 31.9 "building Services Piping", ASME "Boiler and Pressure Vessel Code," Section IX, "Welding and Brazing Qualifications" Indiana Plumbing Code

15425 - Acid Waste and Vent Piping System A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersLab-Line/Enfield Industrial CorporationR & G Sloane Mfg. Co.Orion Fittings Inc.Blucher-Josan - stainless steel pipingZurn IndustriesSpears "Labwaste" CPVC Corrosive Waste Drainage System Pipe

Quality AssuranceComplianceWork shall comply with Indiana Plumbing Code

Special Comments or ConditionsPipingIn return air plenums piping shall be PDVF piping or stainless steel piping

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 12 of 43

Page 13: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15440 - Plumbing Fixtures A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersDrinking FountainFiltrine Manufacturing

Electric Water CoolersElkayHawsHalsey-TaylorOasis

Faucets - AutomaticZurn Plumbing Products GroupChicago Faucet with concealed electric solenoid boxAmerican Standard with concealed electric solenoid boxSpeakman Co. with concealed electric solenoid box

Faucets - Non-AutomaticChicago Faucet Co.T & S BrassZurn Plumbing Products GroupSpeakman

Fixture SupportsJosam Mfg. Co.Jay R. SmithWattsZurn Industries, Inc.; Hydromechanics Div.

Floor Mounted Wash BasinsBradley with deck mounted 4" center set, sensor activated hard wired faucets. Use EXD Series.Willoughby Industries with deck mounted 4" center set, sensor activated hard wired faucets. Use AquaWave lavatory system for deck mounted faucets and floor kit.Acorn Engineering Company Meridian Series

Flush Valves (Automatic)Sloan Regal Pro Optima (#110 ES-S and #111 ES-S) Automatic Hardwired Sensor Operated Flush ValveZurn (#ZEMS6000AV) Hardwired Sensor Operated Flush Valve

Flush Valves (manual operation only)Sloan Regal ProZurn Model Z6000

Food Waste DisposersIn-Sink-Erator Model Pro 17

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 13 of 43

Page 14: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

Lavatories, Service Sinks, Urinals, Water ClosetsAmerican Standard; U.S. Plumbing ProductsKohler Co.Crane

Mop Basins (with stainless steel wall guards)E.L.. Mustee and Sons, Inc.FiatStern WilliamsAcorn Engineering CompanySwan Corp.

Safety Shower/Eye WashBradleyEnconHawesSpeakmanGuardian Equipment

Showers (Individual) with single tempered waterSymmonsPowersLeonardAcorn Engineering Company

Showers (multihead) with single tempered waterAcornBradleyWiloughby

Stainless Steel SinksElkay Mfg. Co.Just Mfg. Co.

Water Closet SeatsBemis Mfg. Co.Beneke Corp.Olsonite Corp., Olsonite SeatsChurch

Quality AssuranceComplianceAll fixtures shall comply with the Americans With Disabilities Act (ADA)

Special Comments or ConditionsCoordinateCoordinate fixture model numbers with IPS Master Specifications

FaucetsGooseneck faucets to be used with Owner approval only

Approved ProductsFaucets - AutomaticZurn AquaSense Hardwired Sensor Operated Lavatory Faucet with cover plate and P6900-BX enclosure box

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 14 of 43

Page 15: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

Faucets - Non-AutomaticZurn Aquaspec

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 15 of 43

Page 16: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15450 - Plumbing Pumps A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersCompact Bronze Cartridge CirculatorsArmstrong Pumps, Inc.Grundfos Pumps Corp.ITT Bell & GossettTaco, Inc.

Constant Speed Booster Pump PackageTaco, Inc.Armstrong Pumps, Inc.ITT Bell & GossettPeerless PumpsFlo-Pak

Duplex Submersible Sewage Ejector PumpsAurora PumpsHydromantic Pumps, a Marley Pump Co.Peerless PumpWeil Pump Co.Zoeller Pump Co.Tramco

Duplex Submersible Sump PumpsAurora PumpsHydromantic Pumps, a Marley Pump Co.Weil Pump Co.Zoeller Pump Co.Grundfos Pumps Corp.Armstrong Pumps, Inc.Zurn

In-Line Bronze-fitted CirculatorsAmtrol, Inc.Armstrong Pumps, Inc.ITT Bell & GossettTaco, Inc.

Quality AssuranceDomestic booster pump system shall be tested at 0%, 25%, 50%, 75% and 100% of full load capacity at scheduled suction and discharge pressureAll plumbing pumps shall be factory assembled, wired and tested, prior to shipment

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 16 of 43

Page 17: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15455 - Water Softeners A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersAqua SystemsEntinCulligan

Special Comments or ConditionsSoftener shall operate on a timer control.Softeners shall be fully charged with fresh salt and mineral at Building Substantial Completion

15460 - Gas-Fired Water Heaters A/E Spec #

WarrantyStandard Project Warranty

Special Product Warranty5 year from date of project Substantial Completion

SubmittalProduct Data

Approved ManufacturersLochinvar Copper Fin II with storage tankA.O. Smith Copper Fin (85% efficiency) with storage tankRBIBradford White Corp.

Quality AssuranceHeater shall be A.G.A. approved and meet or exceed ASRAE 90-75

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 17 of 43

Page 18: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15470 - Domestic Water Filtrating Equipment A/E Spec #

WarrantyStandard Project Warranty

Special Product WarrantyThe Filter System shall carry a 15 year non-prorated warranty from date of project Substantial Completion

SubmittalProduct Data

Approved ManufacturersAqua Systems (RO Central System) for drinking waterFiltrine Manufacturing Company

Special Comments or ConditionsSystem IncludesCirculating Pump and MotorFilter System

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 18 of 43

Page 19: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15471 - Pool Water Treatment System A/E Spec #

WarrantyStandard Project Warranty

Special Product Warranty1 year on-site service warranty from date of project Substantial Completion shall be provided by Manufacturer's Representative2 year limited warranty from date of project Substantial Completion on parts and on pH ad HRR sensors

SubmittalProduct Data

Quality AssuranceStart-UpManufacturer's Representative shall perform initial Start-up of Water Treatment System at site.

TrainingManufacturer's Representative shall train customer on-site, to ensure proper equipment implementation.Manufacturer's Service Representative shall be trained by manufacture and receive factory authorization at a minimum schedule of every two years

Special Comments or ConditionsCoordinateCoordinate with Division 13, Special Construction, Section 15472 Controller for Pool Water Chemistry, Division 16, Electrical

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 19 of 43

Page 20: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15472 - Controller for Pool Water Chemistry A/E Spec #

WarrantyStandard Project Warranty

Special Product Warranty2 year limited warranty on parts and on pH ad HRR sensors from date of project Substantial CompletionWarranties shall begin at the date of project Substantial Completion1 year on-site service warranty from date of project Substantial Completion shall be provided by Manufacturer's Representative

SubmittalProduct Data

Quality AssuranceStart-UpManufacturer's Representative shall perform initial Start-up of Water Chemistry System at site.

TrainingManufacturer's Representative shall train customer on-site, to ensure proper equipment implementation.

Special Comments or ConditionsCoordinateCoordinate with Division 13, Division 16 Electrical

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 20 of 43

Page 21: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15480 - Compressed Air Systems A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersIngersoll-Rand Co.Quincy

Special Comments or ConditionsAir compressor shall provide oil free air and shall be equipped with automatic blowdown.Mount units on vibration isolators which have been anchored to substrate, in accordance with manufacturer's instructionsInstall units on 4" high reinforced concrete pad 4" larger on each side than compressor base

15490 - Natural Gas System A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct DataWelder's Certifications

Approved ManufacturersGas Line Pressure RegulatorsEquimeter (formerly Rockwell)FisherMaxatroll

ValvesJenkins Bros.Lunkenheimer Co.NIBCO, Inc.Powell Co.Stockham

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 21 of 43

Page 22: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15510 - Hydronic Piping A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersVitaulic Company of AmericaGrinnell Co.Viega "Rigid Propress System" (Contract to require contractor to provide IPS with a new set of tools necessary to join each size pipe in the system.)

Special Comments or ConditionsCoordinateCoordinate with Division 15 section "Pipe Applications"

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 22 of 43

Page 23: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15515 - Hydronic Specialties A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersAir SeparatorsAmtrol, IncArmstrong Pumps, Inc.Bell & Gossett ITT; Fluid Handling Div.SpirothermTaco, Inc.

Air Vents (manual and automatic)Armstrong Machine WorksBell & Gossett ITT; Fluid Handling Div.SpirothermSpirax SarcoTaco, IncNexus Valve Specialties

Automatic Flow Control ValvesAutoFlow-Flow Design Inc.Griswold ValveNexus Valve Specialties

Calibrated Balance ValvesBell & Gossett ITT; Fluid Handling Div.Taco, Inc.Armstrong Pumps, Inc.Nexus Valve Specialties

Combined Pressure-Temperature Relief ValvesBell and Gossett ITT; Fluid Handling Div.Spirax SarcoWatts Regulator Co.

Diaphragm-Type Compression TanksArmstrong Pumps, Inc.Bell & Gossett ITT; Fluid Handling Div.Taco, Inc.Wessells

Hydronic PumpsArmstrong Pumps, Inc.

Liquid Heat Transfer PumpsArmstrong Pumps, Inc.

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 23 of 43

Page 24: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

Pump Suction DiffusersAmtrol, IncArmstrong Pumps, Inc.Bell & Gossett ITT; Fluid Handling Div.Taco, Inc.Victaulic Company of America

Quality AssuranceComplianceAll materials shall comply with ASME standards, State and Local Codes

Special Comments or ConditionsComplianceBoiler and Pressure Vessels shall comply with ASME Section VIII, Division 1

15520 - Steam and Condensate Piping A/E Spec #

WarrantyStandard Project Warranty

SubmittalWelding testing reportsWelder's CertificationsProduct Data

Approved ManufacturersAir VentsMueller Steam SpecialtyArmstrongSpirax/Sarco

Safety Relief ValvesKunkleSpirax/Sarco

Steam TrapsHoffman Specialty ITT

StrainersArmstrongSpirax/SarcoMueller Steam Specialty

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 24 of 43

Page 25: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15540 - HVAC Pumps A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersBase-Mounted End Suction PumpsBell & Gossett ITT; Fluid Handling Div.Peerless PumpTaco, Inc.Armstrong

Horizontal Split Case PumpsArmstrong

Inline Centrifugal PumpsBell & Gossett ITT; Fluid Handling Div.Peerless PumpTaco, Inc.Armstrong

Packaged Steam Condensate PumpsSkidmoreHoffman

Vertical Multi-Stage PumpsArmstrong

Vertical Sump PumpsArmstrong

Vertical Turbine PumpsArmstrong

Special Comments or ConditionsProvide electronic adjustable overloads protectionProvide phase loss protection

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 25 of 43

Page 26: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15555 - Fuel-Fired Boilers A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersCondensing BoilerAercoViessmann Manufacturing Company

Gas BurnerGordon-Piatt

Scotch-Marine Firetube BoilerBurnham Corp.; Hydronics Div.Hurst Boiler Co.Kewanee Boiler Corp.Superior Boiler Works, Inc.

Wetback/Burner Package BoilerCleaver Brooks

Special Comments or ConditionsAdditional Accessories for Cast-Iron BoilerWater Level Control (McDonnal-Miller)1-1/2" side inspection openings with plugsLow water cutoff and feeder combinationBarometric damperTankless heaterFlow switch (Press. Dif.)

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 26 of 43

Page 27: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15575 - Breechings, Chimneys, and Stacks A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersAll Steel, Positive Pressure, Double Wall VentsAMPCOMetal-Fab, Inc.Selkirk (Metalbestos)ScheblerStacks, Inc., Div. Of Air Management, Inc.Van Packer

Double Wall Metal VentsMetal-Fab, Inc.AMPCOGeneral Products Co., Inc.Hart & CooleyMetal-Fab, Inc.Selkirk (Metalbestos)

Special Comments or ConditionsMaintain all lightning protection on existing stacks

Condensing Boiler VentsCondensing Boiler Vents to be stainless steel

CoordinateCoordinate wall thickness with size of vent

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 27 of 43

Page 28: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15670 - Split System Condensing Unit A/E Spec #

WarrantyStandard Project Warranty

Special Product Warranty5 year from manufacturer from date of project Substantial Completion

SubmittalProduct Data

Approved ManufacturersBryantCarrierLennoxTraneYork

Quality AssuranceComplianceCondensing units shall meet or exceed the minimum COP/Efficiency levels as prescribed in ASHRAE 90AUnits shall comply with ASHRAE Standards

Special Comments or ConditionsUnits shall be installed on a 4 inch thick reinforced concrete padDo not use condensate removal lift kitsCondensing coils shall be constructed of copper tubing/Aluminum fin

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 28 of 43

Page 29: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15680 - Water Chillers A/E Spec #

WarrantyStandard Project Warranty

Special Product Warranty5 year from manufacturer from date of project Substantial Completion for replacement compressors

SubmittalProduct Data

Approved ManufacturersAir-Cooled Water ChillerCarrier CorporationTraneMcQuayYorkMultistack

Water-Cooled Centrifugal ChillerNot to be used in CIP projects

Quality AssuranceManufacturer shall have factory trained servicemen to supervise the evacuation, charging and start-up of the units for final operationThe unit manufacturer's serviceman shall provide and complete the manufacturer's check, test, and start forms. One copy shall be sent to the Architect/Engineer and one copy to the manufacturer's factory.Supplier shall provide all material (including refrigerant) and labor required to evacuate, charge, and accomplish the check, test, and start procedure as recommended by unit manufacturer

Special Comments or ConditionsUnits shall be installed on a reinforced concrete pad minimum of 7 1/2" thick and extending 6 " beyond unitRotary screw air-cooled chillers to be used

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 29 of 43

Page 30: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15710 - Factory-Fabricated Cooling Tower A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersBaltimore Aircoil Co., Inc.Evapco, Inc.Marley (The) Cooling Tower Co.

Quality AssuranceCertificationCertify Tower wind resistance to withstand pressure indicated in any directionCertify Tower earthquake resistance against loading as indicated

Special Comments or ConditionsNot to be used in CIP projects

15720 - Evaporative Closed-Circuit Cooler A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersRecoldEVAPCOBaltimore Air CoilIMECO

Special Comments or ConditionsNot to be used in CIP projects

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 30 of 43

Page 31: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15755 - Heat Exchangers A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersShell & Tube Heat ExchangersArmstrongB & G Taco

Water-To-Water Plate Heat ExchangerAlfa-LavalBaltimore Air CoilMuellerPolaris

Quality AssuranceComplianceASME Compliance: Construct heat exchanger in accordance with ASME Boiler and Pressure Vessel Code, Section VIII "Pressure Vessels", Division-1.

Manufacturer's QualificationsFirms regularly engaged in manufacture of heat exchanger, of types, materials, and size required, whose products have been in satisfactory use in similar service for not less than 5 years.

Pressure VesselsA manufacturer's data report for Pressure Vessels, Form No. U-1 as required by the provisions of the ASME Code Rules, is to be furnished for the Owner through the Engineer

Special Comments or ConditionsInstall on 4" concrete housekeeping pad as indicated, locate with required clearance for servicing.

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 31 of 43

Page 32: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15775 - Electric Heating Cables A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersThermon

15780 - Rooftop Units A/E Spec #

WarrantyStandard Project Warranty

Special Product WarrantyCompressors5 year from date of project Substantial Completion

Heat Exchanger10 years from date of project Substantial Completion

SubmittalProduct Data

Approved ManufacturersCarrier CorporationTraneMcQuayYork

Quality AssuranceEnergy Efficiency RatioEqual to or greater than prescribed by ASHRAE 90.1, "Energy Efficient Design of New Buildings except Low- Rise Residential buildings."

Special Comments or ConditionsEquipment Rail Curb HeightMinimum of 24 inches

Perimeter Roof Curb HeightMinimum of 16 inches

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 32 of 43

Page 33: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15830 - Terminal Units A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersBaseboard RadiationCarrier CorporationSlant/Fin Corp.Sterling RadiatorTrane (The) Co.Vulcan Radiator Co.RittlingEngA (no fiberglass lining)

Cabinet HeatersAmerican Air Filter Co.Carrier CorporationInternational Environmental Corp.McQuay Inc.Trane (The) Co.Young Radiator Co.RittlingRosemexEngA (no fiberglass lining)

CoilsAmerican Air FilterCarrier CorporationHeatcraft Coil CompanyMcQuay Inc.Trane (The) Co.York Div.USA Coil & Air (wall thickness .035 or greater)RosemexEngA

ConvectorsRittling

Face & By-PassEngA Lamiflo (no fiberglass lining)

Fan-Coil UnitsAmerican Air Filter Co.Carrier CorporationInternational Environmental Corp.McQuay Inc.Trane (The) Co.Enviro-Tec (Series HP, VF, and HL only)EngA (no fiberglass lining)

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 33 of 43

Page 34: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

Unit HeaterCarrier CorporationMcQuay Inc.Modine Mfg. Co.Sterling RadiatorTrane (The) Co.RittlingRosemexEngA (no fiberglass lining)

Unit VentilatorsAmerican Air Filter Co.Carrier CorporationTrane (The) Co.McQuayEngA Unit Ventilators (no fiberglass lining)

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 34 of 43

Page 35: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15835 - Electric Terminal Units A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersArchitectural Wall HeatersQ-MarkRedd-I

Baseboard RadiationErincraftQ-MarkRedd-I

Electric Duct HeatersBrasch Manufacturing Co.IndeecoAirthermDell Corporation/HetrixRedd-I

Electric Unit HeatersBrasch Manufacturing Co.ErincraftIndeecoTraneQ-MarkRedd-I

Quality AssuranceUL ComplianceProvide electrical components for terminal units which have been listed and labeled by UL

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 35 of 43

Page 36: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15855 - Air Handling Units A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersAir Handling UnitsAAONAir EnterprisesBryantCarrier CorporationDesChamps Laboratories, Inc.Governair CorporationHaakonLoren Cook Company McQuayPaceTemptrolTraneYorkGreenheckVentrolEnviro-TecAmerican Energy ExchangeEngA (Heat Recovery - Heat Wheels, Heat Pipes, Plate Exchangers)

Primary Air/Heat RecoveryCarrier CorporationRenewAireSemcoTraneXetex

Special Comments or ConditionsProvide factory installed base rail to support all sections of unitsInstall floor-mounted air handling units on 4" housekeeping pads

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 36 of 43

Page 37: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15870 - Exhaust Fans A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersBelt Driven Roof Exhaust FansGreenheckPennJenn IndustriesLoren Cook CompanyAcme Engineering & Manufacturing

Direct Drive Wall FansGreenheckPennJenn IndustriesLoren Cook CompanyAcme Engineering & Manufacturing

In-line Exhaust FansGreenheckPennJenn IndustriesLoren Cook CompanyAcme Engineering & Manufacturing

Special Comments or ConditionsRoof CurbsMinimum shall be 16"

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 37 of 43

Page 38: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15890 - Low Pressure Ductwork A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct DataRecord DrawingsDimensioned Layout

Approved ManufacturersIndustry Standard

Special Comments or ConditionsComplianceShall comply with SMACNA Standards

15895 - Flexible Ductwork A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersIndustry Standard

Special Comments or ConditionsUse a metal 90º elbow at diffuser

ComplianceShall comply with SMACNA Standards

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 38 of 43

Page 39: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15900 - Variable Frequency Drives (VFDs) A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersHoneywellABB

15902 - Sound Attenuators A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct DataShop Drawings

Approved ManufacturersRuskin

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 39 of 43

Page 40: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15910 - Ductwork Accessories A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersIndustry StandardNailor IndustriesGreenheck

Special Comments or ConditionsComplianceShall comply with SMACNA Standards

ProductsVolume DampersGravity Backdraft DampersFire DampersCombination fire-Smoke DamperDuct Access DoorsTurning VanesWall Louvers

15930 - Variable Volume Terminal Units A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersCarrier CorporationEnvironmental Technology, Inc.PriceTitusTrainNailor IndustriesKrueger

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 40 of 43

Page 41: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15940 - Diffusers, Registers, and Grills A/E Spec #

WarrantyStandard Project Warranty

SubmittalProduct Data

Approved ManufacturersTitusPriceKruegerAnemostatNailor Industries

Special Comments or ConditionsProductsDrum LouversExhaust RegistersPanel DiffusersReturn GrillesSupply RegistersTransfer Grilles

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 41 of 43

Page 42: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15970 - Temperature Control Systems A/E Spec #

WarrantyStandard Project Warranty

SubmittalAuto-CAD compatible as-built DrawingsSystem schematics with sequencesProgramming disk for Owner useProduct Data10 copies of submittalsEquipment data cut sheetsValve and damper schedulesOperation and Maintenance Manuals

Approved ManufacturersSiemens Building Technologies - System 600 APOGEE, Installation by branch officeJohnson Controls - Metasys, Installed by branch officeAndoverAlerton TechnologiesTraneCarrier CorporationStaefa Control SystemHoneywell InternationalInvensys Automation Systems

Quality AssuranceProvide compatible systems in renovation/addition projectsProvide required testing and repair to system

Special Comments or ConditionsRelated DivisionsDivision 01000 General and Special ConditionsDivision 15000 MechanicalDivision 16000 Electrical

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 42 of 43

Page 43: IPS-CIP Standard Building Program Executive … Building Program Executive Summary ... Submittal Samples for finish ... Ridgid/Viega ProPress Dielectric Unions Perfection Corp

IPS Capital Improvements ProgramStandard Building ProgramExecutive Summary

Division 15 - Mechanical

Score Acceptable Notes

15990 - Adjusting and Balancing A/E Spec #

WarrantyStandard Project Warranty

SubmittalFinal ReportReport Forms

Approved ManufacturersManufacturers/ContractorsFulton Air Balance, Inc.Johnson Controls, Inc.MSB Mechanical Systems BalancingBledsoe Environmental Systems Testing, Inc

Special Comments or ConditionsWork IncludedBalance domestic hot water return loopsAdjust individual outlets for proper air movementAdjust terminal units to deliver design air quantitiesAdjust fans to deliver, return or exhaust design air quantities to or from each space.Adjust volume dampers, diffusers, grills, and registers to proper design airflowAdjust supply, return, exhaust, and relief dampersBalance hydronic systems and pumps to design flows

1 = Meets Program Standards2 = Generally Meets Program Standards3 = Does not meet Program Standards

Score

Friday, April 08, 2005rptSpecExecutiveSummary_ByDivisionPage 43 of 43