    PowerLogicIONSetup 2.2Meter configuration software

    Device configuration guide

  • 7/24/2019 ION Setup Device Configuration Guide

    2/72

  • 7/24/2019 ION Setup Device Configuration Guide

    3/72

    Conventions used in this manualThissectiondescribesthesymbolsandterminologyusedinthismanual.

    Symbols

    DangerThisalertsyoutothingsthatmaycauseseriousinjurytoaperson.Onlyqualified,properlytrainedpersonnelshouldperformtheseprocedures.

    CautionThisalertsyoutothingsthatmaycauselossofdata,damagetoyourcomputeroryourdevices.

    NoteAnoteprovidesyouwithadditionalinformationthatyoumightwant

    toconsider.

    TipThisdrawsyourattentiontoinformationthatwillhelpyouperformataskmorequicklyoreasily.

  • 7/24/2019 ION Setup Device Configuration Guide

    4/72

    Terminology

    Clear Place the mouse cursor over the check box option, then click the mouse buttonso that the check mark is removed from the check box.

    Click Place the mouse cursor over the specified option or button, then press andrelease the mouse button.

    Double-click Place the mouse cursor over the specified option or button, then press andrelease the mouse button twice.

    Drag Hold down the mouse button while moving the mouse cursor to the appropriatelocation, then release the button.

    Enter Type the information, then press the ENTER or RETURN key.

    Point Position the mouse pointer over a submenu or menu command. For example,point to the File menu.

    Press Press the specified key or key combination on your keyboard, for example, pressCTRL+ALT+DEL.

    Right-clickPlace the mouse cursor over the button or item, then press and release the right

    mouse button1.

    1. Mouse button means the the primary mouse button (left, by default), while right mouse button

    means the secondary mouse button. This configuration can be switched for a left-handed user.

    SelectPlace the mouse pointer over the specified option or check box, then click themouse button. A selected check box receives a check mark; a selected radiobutton is marked with a dot.

    Type Type the information, but DO NOT press the ENTER or RETURN key.

  • 7/24/2019 ION Setup Device Configuration Guide

    5/72

    Contents

    Chapter 1 Introduction .................................................................. 7

    Before you begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Overview ............................................................. 8

    Quick start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    Serial site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    Modem site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    Ethernet sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    Ethernet gateway sites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    Chapter 2 E5600 socket-based energy meter ............................... 15

    E5600 meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16MetersetupthroughIRopticalport ..................................... 16

    MetersetupthroughRS485 ............................................ 18

    Firmware upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Meter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    Chapter 3 PM700 series power meter ......................................... 25

    PM700 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26UsingIONSetup ..................................................... 26

    PM700 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26BasicSetup .......................................................... 26

    Demand ............................................................. 27

    FrontPanelDisplay ................................................... 27

    I/OSetup ............................................................ 28

    OnboardAlarms ..................................................... 28

    SerialComms ........................................................ 30

    Chapter 4 PM800 series power meter ......................................... 31

    PM800 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    PM8ECCconsiderations ............................................... 32UsingIONSetup ..................................................... 33

    PM800 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34AlarmLog ........................................................... 34

    BasicSetup .......................................................... 34

    BillingLog ........................................................... 35

    Clock ............................................................... 36

    Comm ECCCard .................................................... 36

    Comm OnboardSerial ............................................... 36

    DataLog#1,DataLog#2,DataLog#3,DataLog#4 ....................... 37

  • 7/24/2019 ION Setup Device Configuration Guide

    6/72

  • 7/24/2019 ION Setup Device Configuration Guide

    7/72

    2009 Schneider Electric. All rights reserved. Page 7

    1 Introduction

    PowerLogicIONSetupsoftwareisameterconfigurationutilityavailablefromtheSchneiderElectricwebsiteatwww.powerlogic.com.

    ThisguideassumesyouknowhowtouseIONSetup,andhavereadandunderstoodtheinstallation,basicsetup,andallrelevantproceduresandwarningscontainedintheuserdocumentationforthedeviceyouwanttoconfigurewithIONSetup.

    Typically,basicsetupcanbeperformedthroughthemetersfrontpanelorremotedisplay. IONSetupismainlyusedforconfiguringadvancedfeaturesofthemeter,orforsettingupameterthatdoesnothaveafrontpanel/remotedisplay.

    DeviceconfigurationinstructionsusingIONSetupsoftwareareprovidedforthefollowing:

    PowerLogicE5600powermeter

    PowerLogicPM700seriespowermeter

    PowerLogicPM800seriespowermeter

    PowerLogicBCPM(Branchcircuitpowermeter)

    PowerLogicEnerceptmeter

    PowerLogicION6200powermeter

    FordetailedproceduresonsettingupotherIONdevices(suchasthePowerLogicION8600orPowerLogicION7550 / ION7650meters),refertothedevicespecificinstallationoruserguide.

    FordetailedinformationonusingIONSetupsoftware,refertotheonlinehelp.

  • 7/24/2019 ION Setup Device Configuration Guide

    8/72

    Chapter 1 - Introduction PowerLogic ION Setup device configuration guide

    Page 8 2009 Schneider Electric. All rights reserved.

    Before you beginBeforeusingIONSetup,makesureyouhavecompletedallrequiredinstallation,wiring,andbasicsetupforeachhardwaredevice(meters,communicationsconverters,modems,etc.).

    Security considerationsSomedevicesrequireadditionalconfigurationinordertoaccessandmodifycertainsetupparameters. Forexample,arevenueclassorhardwarelockedmetermustbeunlockedbeforeyoucanconfigureit.Refertothedevicesdocumentationforunlockingandbasicsetupprocedures.

    OverviewIONSetupsupportsvarioustypesofcommunications. Typically,devicesaregroupedaccordingtoasharedcommunicationslinktype(IONSetupreferstothesecommunicationslinksassites). WhencreatingyourIONSetupnetworkforthefirsttime,youwouldstartbyaddingasitetoyourworkstation,thenadddevicestothesite.

    NOTE

    Most ION devices use the 8N1 standard (8 data bits, no parity, 1 stop bit) for serial communications. To

    prevent communication errors, make sure all the devices on your serial communications loop are set to

    8N1 (i.e. make sure the devices serial communications parameter is set to No parity).

    Ethernet site

    Ethernet devices

    Ethernet Gateway

    Modem site

    RS-485 devices

    remote serial device

  • 7/24/2019 ION Setup Device Configuration Guide

    9/72

    PowerLogic ION Setup device configuration guide Chapter 1 - Introduction

    2009 Schneider Electric. All rights reserved. Page 9

    Quick startThefollowingsummarizesthestepsforaddingsitesanddevicesinIONSetup.

    1. Installandwireyourmeters,followingtheinstructionsandwarningsinthemeterspecificdocuments.

    2. Followtheinstructionsinthemeterinstallationmanualtoconfigurethebasiccommunicationsparametersforeachmeter(forexample,protocol,baudrate,parityanddeviceaddress/unitID).

    NOTE

    Make sure all the devices on the same RS-485 loop are set to the same baud rate, and their serial port

    parameters are set to 8N1.

    3. Ifusingacommunicationsconverterorgateway,configureitscommunicationsparameters,theninstallandwireittothemeter(s).

    4. StartION

    Setup

    and

    log

    on

    using

    network

    mode

    (i.e.,

    clear

    the

    Single ION device configuration modecheckbox). Thedefaultuserissupervisorandpasswordis0(zero).

    5. Addandconfigureyoursites. ForEthernetorEthernetGatewaysites,usethefollowingtabletosettheportnumber,asappropriate.

    6. AddeachmetertotheappropriatesiteinIONSetup.

    IP Port1

    1. Some meters support email (SMTP through port 25) and web pages (HTTP through port 80).

    Description (communications protocol, connection type)

    23 Telnet (used for meter diagnostics)

    502 Modbus TCP

    7700 ION (direct)

    7701 Modbus RTU through an ION meter

    7800 EtherGate simultaneously though available COM ports of an ION meter

    7801 EtherGate through COM1 of an ION meter

    7802 EtherGate through COM2 of an ION meter

    7803 EtherGate through COM3 of an ION meter

  • 7/24/2019 ION Setup Device Configuration Guide

    10/72

    Chapter 1 - Introduction PowerLogic ION Setup device configuration guide

    Page 10 2009 Schneider Electric. All rights reserved.

    Serial siteIfthedeviceisequippedwithanRS232port,youcanuseanRS232cabletodirectlyconnectthedevicetoanavailableserialportonthecomputer.

    Toconnecttomorethanoneserialdevice,youcanuseanRS232 to RS485communicationsconverter. TheRS232portontheconverterconnectstothecomputersserialport,andtheRS485portconnectstoupto32RS485devices.

    Makesuretheserialcommunications parametersaresetcorrectlyforeachdevice(forexample,protocol,baudrate,parityanduniquedeviceaddress/unitID).

    Adding a serial site in ION Setup1. RightclicktheworkstationiconandselectInsertItem.

    2. SelectSiteandclickOK.

    3. OntheGeneraltab,usetheNameboxtoenteranameidentifyingthisserialsite.

    UsetheCommLinkboxtoselectwhichserialportonthecomputeryouareusingtocommunicatewiththemeter(s).

    UsetheLinkSpeedboxtosettheserialportsbaudratetothesamevalueastheserialdevice(s).

    Fordirectserialcommunicationsthroughtheserialport(orthroughan

    RS232 to RS485communicationsconverter),setLinkTypetoRS232/RS

    485

    Direct.

    4. TheTimingsandPollingtabscontainotherserialcommunicationsparameters.Inmostcases,thedefaultsettingsdonotneedtobemodified.

    RS-232 to RS-485converter

    RS-485 devices(maximum 32)

  • 7/24/2019 ION Setup Device Configuration Guide

    11/72

    PowerLogic ION Setup device configuration guide Chapter 1 - Introduction

    2009 Schneider Electric. All rights reserved. Page 11

    Modem siteAmodemsiteconsistsofalocalmodemconnectedtothecomputersserialportandaremotemodemconnectedtooneormoreserialdevices.

    IONSetupusesthelocalmodemtodialtheremotemodemstelephonenumberandestablishcommunications.

    Adding a new serial or modem site in ION Setup

    1. RightclicktheworkstationiconandselectInsertItem.

    2. SelectSiteandclickOK.

    3. OntheGeneraltab,usetheNameboxtoenteranameidentifyingthismodemsite. Enterthephonenumberinthebox. SelectModem,thenusetheModemconfigurationbuttontosetupthecommunicationsport. Followthedirectionsprovided.

    4. TheTimingsandPollingtabscontainothercommunicationsparameters;youcanmodify. In mostcases,youdonotneedtochangethedefaultsettings.

    ModemGate featureSomeIONmetersareequippedwithaninternalmodemthatyoucansetupasa

    communicationsgatewaytoconnecttomultipleRS485devices(e.g.onaremotesite). Formoreinformation,refertothetechnicalnoteTheIONmeterasaModemGate.

    localmodem

    telephone line

    remotemodem

    RS-232 to RS-485converter

    RS-485devices

  • 7/24/2019 ION Setup Device Configuration Guide

    12/72

    Chapter 1 - Introduction PowerLogic ION Setup device configuration guide

    Page 12 2009 Schneider Electric. All rights reserved.

    Ethernet sitesIfthedeviceisequippedwithanEthernetcommunicationscard,youcanuseanEthernetcabletoconnectittoyourlocalorwideareanetwork(LAN/WAN).

    MakesuretheEthernetcommunicationsparametersaresetcorrectlyforeachdevice(forexample,IP address,subnet mask,default gateway,media type).

    Adding a new Ethernet site in ION Setup

    1. RightclicktheworkstationiconandselectInsertItem.

    2. SelectSiteandclickOK.

    3. SelectEthernet,thenclickOK.

    4. TheTimingsandPollingtabscontainothercommunicationsparameters;youcanmodify. In mostcases,youdonotneedtochangethedefaultsettings.

    LAN / WAN

    Ethernetdevices

  • 7/24/2019 ION Setup Device Configuration Guide

    13/72

    PowerLogic ION Setup device configuration guide Chapter 1 - Introduction

    2009 Schneider Electric. All rights reserved. Page 13

    Ethernet gateway sitesAnEthernetgatewaydevicehasanEthernetporttocommunicatewiththecomputer(throughtheLAN/WAN)andprovidesoneormoreRS485portsforconnectionandcommunicationwithmultipleRS485devices(upto32devicesperloop). TypicalparametersyouconfigureontheEthernetgatewaydeviceinclude:

    Ethernetportsettings: IP address,subnetmask,defaultgateway

    Serialportsettings: Baudrate,parity,physicalinterface(2wireor4wire)

    NOTE

    For the Ethernet gateway devices serial port, set the baud rate to the same setting as all the RS-485

    devices connected to it. If the serial port parameter setting can be configured, set it to 8N1 (no parity).

    AdditionalsettingsmaybeavailablerefertothedocumentationthatcamewithyourEthernetgatewaydevice.

    EGX series considerationsThePowerLogicEGXseriesEthernetgatewaycanprovideEthernetaccessto

    multipleRS485devicesthatareconnectedtotheEGXsRS485port. AfterwiringtheRS485devicestotheEGX,useawebbrowsertologintotheEGX. BrowsetothedevicelistpageandentereachdevicethatisconnectedtotheEGXsRS485port. Settheappropriatedeviceaddressanddevicetypeforeachdevice. RefertotheEGXSeriesInstallationGuide.

    ForinstructionsonaddingametertotheEthernetgatewaysite,refertotheIONSetuponlinehelp.

    PM8ECC considerationsSimilartotheEGXseriesgateway,thePM8ECCEthernetcommunicationscard

    provides

    Ethernet

    access

    to

    multiple

    RS

    485

    devices

    that

    are

    connected

    to

    the

    PM8ECCsRS485port.AfterwiringtheRS485devicestothePM8ECC,useawebbrowsertologintothePM8ECC. BrowsetothedevicelistpageandentereachdevicethatisconnectedtothePM8ECCsRS485port. Settheappropriatedeviceaddressanddevicetypeforeachdevice. RefertothePM8ECCInstallationGuide.

    LAN / WAN

    RS-485devices

    Ethernetgatewaydevice

    Ethernet

    serial RS-485

  • 7/24/2019 ION Setup Device Configuration Guide

    14/72

    Chapter 1 - Introduction PowerLogic ION Setup device configuration guide

    Page 14 2009 Schneider Electric. All rights reserved.

    ION7550/ION7650 Modbus gatewayYoucanusetheION7550orION7650meterasanEthernetgatewaytomultipleModbusRTU(serial)devices.RefertotheEtherGatechapter(orsearchthetopicModbusgateway)intheION7550/ION7650UserGuide.

    Adding a new Ethernet gateway site in ION Setup

    1. RightclicktheworkstationiconandselectInsertItem.

    2. SelectSiteandclickOK.

    3. SelectEthernet,thenselecttheGatewaybox.

    4. IntheGatewayInfoboxes,entertheIPaddress,thentypeorselecttheappropriateportnumber. Forexample,select502forModbusTCPcommunications.

    5. TheTimingsandPollingtabscontainothercommunicationsparameters;youcanmodify. In mostcases,youdonotneedtochangethedefaultsettings.

  • 7/24/2019 ION Setup Device Configuration Guide

    15/72

    2009 Schneider Electric. All rights reserved. Page 15

    2 E5600 socket-based energy meter

    ThePowerLogicE5600isacosteffectiveSbasesocketmeterwithANSI C12.20Class 0.2accuracy.

    In This Chapter

    E5600 meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16MetersetupthroughIRopticalport ..................................... 16

    MetersetupthroughRS485 ............................................ 18

    Firmware upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Meter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

  • 7/24/2019 ION Setup Device Configuration Guide

    16/72

    Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide

    Page 16 2009 Schneider Electric. All rights reserved.

    E5600 meter setupTheE5600hastwoconfigurationoptions:viathemetersIRopticalportorthroughtheRS485connection.

    IfyouneedtochangeyourmetersdefaultRS485settingsyoumustfirstconnecttoyourmeterthroughtheIRopticalporttoconfigurethemetersRS485communicationssettings.Otherwise,yourmetercanbecompletelyconfiguredthroughtheRS485connection.RefertoDefaultRS485settingsonpage 22.

    NOTE

    Meter password protection can only be done through the IR optical port.

    Tools requiredPleaseensureyouhavethesethingsavailablebeforestartingtosetupyourE5600

    meter:

    Computer(loadedwithlatestversionofIONSetup)

    Optional:ANSIC12.19typeIIopticalprobe(refertotheE5600InstallationandOperation

    Guideforthemetersfrontopticalportspecifications)

    Optional:Strongmagnet(suchasarareearthorsimilarpermanentmagnet)

    NOTE

    Optional tools are required to communicate with your meter through the IR optical port.

    Meter setup through IR optical portTocommunicatewithyourmeterthroughtheIRopticalport,youmustconfigureyourcomputertousetheopticalprobe.YoucanthenconnecttheprobeandcommunicatetothemeterusingIONSetup.

    Computer configurationThisdescribeshowtoconfigurethecomputerscommunicationportforopticalprobecommunication,andhowtoidentifywhichportisbeingusedbytheopticalprobe.

    BeforestartingIONSetup,connecttheE5600metertoyourcomputerusinganANSIC12.19typeIIopticalprobe.IftheWindowsdriverfortheUSBopticalprobeisnotinstalled,Windowsdetectstheopticalprobeasnewhardwareandpromptsyoutosearchforacompatibledriver.Usetheinstallationdiscthatcamewiththeopticalprobetoinstallthedriver,ordownloadtheappropriatedriverfromtheopticalprobemanufacturerswebsite.

    OpenyourcomputersDeviceManagertoseewhichserialportnumberisassignedtotheopticalprobe:

  • 7/24/2019 ION Setup Device Configuration Guide

    17/72

    PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter

    2009 Schneider Electric. All rights reserved. Page 17

    1. RightclickMyComputerandselectManage.

    2. ExpandSystemToolsandselectDeviceManager.

    3. ExpandPorts.

    4. Notetheopticalprobesserialport#.

    5. ClosetheComputerManagementscreen.

    Meter communicationThisdescribeshowtoputthemeterintodiagnosticmodesothatitcanbeconfiguredthroughtheIRopticalportusingIONSetup.

    1. Putthemeterintodiagnosticmode.

    Toputthemeterintodiagnosticmode,holdastrongmagnetoverthemeter,approximatelyatthe12oclockposition,toactivatethereedswitch.Whenthereedswitchisactivated,themetersdisplaywillshowallsegments,then

    ablank

    screen,

    and

    then

    will

    start

    to

    display

    the

    diagnostic

    display

    sequence.

    DonotremovethemagnetfromthemetersreedswitchwhilecommunicatingthroughthemetersIRport.

    NOTE

    RS-485 (Modbus) data will not be updated while the meter is communicating via the front optical port.

    2. StartandlogontoIONSetupusingsingledeviceconfigurationmode(i.e.,makesuretheSingleIONdeviceconfigurationmodecheckboxisselected).

    12 oclock

  • 7/24/2019 ION Setup Device Configuration Guide

    18/72

    Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide

    Page 18 2009 Schneider Electric. All rights reserved.

    3. IntheConnectionTypedialog,selecttheopticalprobesserialportnumber.

    4. ClickOK.

    IONSetupattemptstoestablishaconnection(9600baud,ANSIprotocol)tothe

    device.Ifcommunicationattemptsfail,closeIONSetup,checktomakesurethereisgoodphysicalconnectionbetweenthecomputerandthemeterandensurethatthemagnetisactivatingthereedswitch.RestartIONSetupandtryconnectingtothedeviceagain.

    5. ConfiguretheE5600meter.Thesetupscreensaredetailedinthesection,MetersetupthroughRS485.

    Meter setup through RS-485ToconfigureyourmeterthroughRS485,youmustaddthemeterinIONSetup.Oncethemeterhasbeenadded,youcanconfigureyourmeterusingthesetupscreens.

    Adding the E5600 to a site1. IfyourmeterisconnectedthroughtheIRopticalport,exitIONSetupthen

    removethemagnetfromthemeter.

    2. MakesuretheE5600metersRS485portisconnectedtothecomputer(throughanRS232toRS485converteroranEthernetgatewaydevice).

  • 7/24/2019 ION Setup Device Configuration Guide

    19/72

    PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter

    2009 Schneider Electric. All rights reserved. Page 19

    3. StartandlogontoIONSetupusingnetworkmode(makesuretheSingleIONdeviceconfigurationmodecheckboxonthelogonpromptiscleared).

    4. CreateandconfigureanewsiteforyourE5600meter,oruseanexistingsiteifappropriate(i.e.,ifanexistingsitealreadyexistsandyouhavewiredtheE5600communicationsporttousethatcommunicationslink).RefertotheIntroductionsectionfordetailsonaddingsitesandmeters.

    5. AddtheE5600metertothesite.ForUnitID,entertheModbusaddressyousetforthedevice(refertoRS485Commonpage 22).

    6. ConfiguretheE5600meterssetupparameters.

    Basic SetupUsethisscreentoconfigurethemetersprimaryandsecondarytransformervalues.

    1. SelectthePTMultiplierparameterandclickEdit.

    2. ThePT/CTMultiplierSetupscreenappears.EnterthePTMultipliervalueand

    clickOK.

    ThePTMultiplierisapositiveintegerthatrepresentsthePTprimarytoPTsecondaryratio.Forexample,ifPTprimary=480VandPTsecondary=120V,thenPT Multiplier = 4.

    3. RepeatfortheCTMultiplierparameter.

    TheCTMultiplierisapositiveintegerthatrepresentstheCTprimarytoCTsecondaryratio.Forexample,ifCTprimary=500AandCTsecondary=5A,thenCTMultiplier=100

    ClickSendtosaveyourchangestothemeter.

    ClockTo manually set the meters local time

    1. SelecttheDate/TimeparameterandclickEdit.

    2. UsetheDatedropdownbuttontodisplaythecalendar.Youcanusetheleftorrightscrollbuttontochangethemonth.Clickthecalendardaytosetthemeterdate.

    3. Clickthehour,minute,secondorAM/PMsetting,thenusetheup/downscrollbuttons(oruseyourcomputerskeyboard)tochangethevalue.

    Thetimeinformationissenttothemeterexactlyasentered.Nocorrections(suchasDaylightSavingsTime)areappliedto,orsupportedbythemeter.

    4. ClickOKthenSendtosetthedateandtime.

    NOTE

    The E5600s front panel display shows hours and minutes in 24 hour clock format.

  • 7/24/2019 ION Setup Device Configuration Guide

    20/72

    Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide

    Page 20 2009 Schneider Electric. All rights reserved.

    DemandDemandistheaveragepowerconsumptionoverafixedtimeperiod(demandperiod),typically15 minutes.

    1. SelectIntervalLengthparameterandclickEdit.

    2. Selecteither

    Block

    Demand

    or

    Sliding

    Window

    Demand.

    BlockDemand:SelecttheBlockLengthfromthedropdownlist.

    SlidingWindowDemand:SelecttheappropriatePeriod/SubIntervalfromthedropdownlist.Forexample,ifyourequirea30minuteintervalbrokenintotwoperiodsof15minuteseach,select2x15minutes.

    3. ClickOKthenSendtosaveyourchangestothemeter.

    Device LabelsSelectDeviceIdentificationandclickEdit.TypethedevicelabelfortheE5600meterintheEnterDeviceIdentificationbox.Thedevicelabelcanbe1 18ASCII

    characters.

    ClickOKthenSendtosaveyourchangestothemeter.

    Energy PulsingEnergypulsingtransitionsthedigitaloutputKYrelay(fromlowhigh,orhighlow)eachtimethesourceenergyparameterincreasesbytheKevalue.TherearetwodigitaloutputsontheE5600.

    Enable

    UsethistoenableordisableenergypulsingforthatKYrelay.

    Source

    UsethistoselecttheenergymeasurementforKYrelaypulsing.

    Ke Value

    Usethistosettheamountthatthesourcemustincreasebeforethedigitaloutputtransitions.Youmustsetthistoanumericvaluebetween0.001and16,inordertoenableenergypulsingthroughthedigitaloutput.

    NOTE

    If Ke is zero (0) the associated KY relay is disabled. You must enter a valid Ke value (between 0.001 and

    16) before you can enable the associated KY relay.

    1. Selectaparameter(Enable,SourceorKeValue),thenclickEdit.

    2. Modifytheparameterbyenteringtherequiredvalueorselectinganoptionfromthedropdownlist.

    3. ClickOKthenSendtosaveyourchangestothemeter.

  • 7/24/2019 ION Setup Device Configuration Guide

    21/72

    PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter

    2009 Schneider Electric. All rights reserved. Page 21

    Front Panel DisplayConfigurethefollowingtospecifyhowmanydatascreensaredisplayedonthefrontpanel,andthetimedurationforeachdisplayedscreen.

    # of Displays

    Youcan

    configure

    amaximum

    of

    six

    (6)

    display

    screens:

    1. Select#ofDisplays,thenclickEdit.

    2. UsetheDisplayEditorwindowtoedit,addordeletethedisplayedparameters.

    Toeditthedisplayedparameter,selectit,thenclickEdit.IntheDisplayScreenSetupwindow,usetheParameterboxtoselectthequantityyouwanttodisplay.UsetheIndicatorboxtoassignathreecharacterlabelforthedisplayedparameter.

    Toaddanewdisplayscreen,clickNew. SettheParameterandIndicatorasdescribedabove.

    Todeleteadisplayscreen,selectitthenclickDelete.

    3. ClickExittoreturntotheFrontPanelDisplaysetupscreen,thenclickSendtosaveyourchangestothemeter.

    Display On Time

    Youcanconfigureadurationfrom1secondto15seconds.

    1. SelectDisplayOnTime,thenclickEdit.

    2. EntertheDisplayOnTimeinthespaceprovidedandclickOK,thenclickSendtosendyourchangestothemeter.

    Meter ResetsUsethissetupscreentoenableordisableresetfunctionsforthemeter.

    1. SelectaresetparameterthenclickEdit.

    PeakDemandReset:clearspeakdemandvalues.

    MasterReset:clearsalldemandandenergyvalues,andclearstheloadprofile.

    EnergyReset:clearsallenergyaccumulatedvalues(total,delievered,recieved).

    2. UsethedropdownboxtoselectResetorNoReset,thenclickOK.

    ClickSend

    to

    save

    your

    changes

    to

    the

    meter.

  • 7/24/2019 ION Setup Device Configuration Guide

    22/72

    Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide

    Page 22 2009 Schneider Electric. All rights reserved.

    RS-485 CommUsethissetupscreentoconfiguretheE5600metersRS485communicationssettings.

    Default RS-485 settings

    NOTE

    Changing RS-485 Comm parameters while communicating through the RS-485 port will cause you to

    lose communications with your meter.

    Modbus Address

    Usethistosetthedeviceaddress(unitID)fortheE5600meter.TheallowableModbusaddressrangeis1to247.MakesuretheModbusaddressisuniquetoeachdeviceonthatRS485loop.

    Baud Rate

    UsethistosetthebaudrateforRS485communications.MakesurealldevicesconnectedonthesameRS485looparesettothesamebaudrate.

    Parity

    Makesurethecommunicationslink(site)andalldevicesconnectedtothatsitearesettothesameparitysetting.

    NOTE

    For serial sites the parity must be set to no parity (Parity = None) for ION Setup to communicate. For

    other site types, the meters RS-485 parity must match the site parity.

    1. Selectaparameter(ModbusAddress,BaudRateorParity)andclickEdit.

    2. Aparametereditingscreenappears.EntertheappropriatevalueintothefieldorusethedropdownlistsandclickOK.

    3. ClickSendtosaveyourchangestothemeter.

    Parameter Value

    Modbus Address Displayed on meter front panel

    Baud Rate 9600 bps

    Parity No parity or None

  • 7/24/2019 ION Setup Device Configuration Guide

    23/72

    PowerLogic ION Setup device configuration guide Chapter 2 - E5600 socket-based energy meter

    2009 Schneider Electric. All rights reserved. Page 23

    Firmware upgradeYoucanupgradetheE5600communicationcardsfirmwarethroughtheRS485port.

    1. MakesureallnecessaryinformationfromtheE5600meterhasbeenrecorded.

    2. SavetheE5600firmwareupgradefiletoyourcomputerdesktoporalocalfolder.

    3. RightclicktheE5600metericonandselectProperties.

    4. ClicktheToolstab,thenclickFirmwareUpgrade.

    5. Apromptdisplays,alertingyouthatallrecordeddataforthedevicewillbereset.ClickOKtoproceed.

    NOTE

    During firmware upgrade the meters I/O may de-energize or change state.

    6. Navigateto

    the

    location

    where

    you

    saved

    the

    firmware

    upgrade

    file,

    select

    it

    thenclickOpen.

    7. EntertheIONSetuppasswordtoupgradethefirmware.

    NOTE

    Do not have any other communications taking place on your RS-485 network while your meter is going

    through a firmware upgrade.

    Whileyourmeterisundergoingafirmwareupgradeitwillcontinuetomeasureandlogdata,butitwillnotupdaterealtimedisplayedvaluesuntiltheupgradeiscompleted.

  • 7/24/2019 ION Setup Device Configuration Guide

    24/72

    Chapter 2 - E5600 socket-based energy meter PowerLogic ION Setup device configuration guide

    Page 24 2009 Schneider Electric. All rights reserved.

    Meter protectionMeterprotectioncanbeconfiguredonlythroughthefrontopticalport.SeeMetersetupthroughIRopticalportonpage 16forconnectiondetails.StartIONSetupinsingledevicemode.

    Password-protecting the meter1. DoubleclickMeterProtection.

    2. SelectProtectionLockoutthenclickEdit.

    3. Typeanumericpasswordinthebox,thenclickEnable.Makesureyoudonotloseorforgetthepassword,asthisistheonlywaytodisableprotectionlateron.

    4. ClickSendtosavethechangestothemeter.

    WithapasswordprotectedE5600meter,youcanstillmakechangestothesesetupscreensthroughtheRS485connection(theseparametersarenotprotectedfrom

    modifications):

    FrontPanelDisplay

    RS485Comm

    Disabling password protectionWhentheE5600meterispasswordprotected,youmustenterthecorrectpasswordwhenyouarepromptedthefirsttime.Otherwise,theprotectedparametersaredisplayedasreadonly.

    NOTE

    Do not lose or forget your password. If you lose your password and need to modify the locked

    parameters, a factory reconfiguration is required, which will reset your meter to its factory defaults and

    destroy all logged data.

  • 7/24/2019 ION Setup Device Configuration Guide

    25/72

    2009 Schneider Electric. All rights reserved. Page 25

    3 PM700 series power meter

    ThePM700seriesmeterisacompact,versatileandcosteffectivepowermeter. It issimpletouseandhasabrightLCDdisplayforimprovedvisibilityinpoorlightingconditions. Themetercanbeusedforstandalonemeteringapplications,incustompanels,switchboards,switchgear,gensets,motorcontrolcenters,orUPSsystems.

    Someofthefeaturesincludedarepower,demand,energy,powerfactor,andfrequencymeasurements. PM700seriesmetersalsohaveIEC6205321Class 1andIEC6205322Class 0.5S(PM750only)accuracycertificationforbasicsubbillingandcostallocation.

    Formoreinformation,refertothemeterdocumentationavailablefromwww.powerlogic.com.

    In this chapter

    PM700 series meter setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26UsingIONSetup ..................................................... 26

    PM700 series setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26BasicSetup .......................................................... 26

    Demand ............................................................. 27

    FrontPanelDisplay ................................................... 27I/OSetup ............................................................ 28

    OnboardAlarms ..................................................... 28

    SerialComms ........................................................ 30

  • 7/24/2019 ION Setup Device Configuration Guide

    26/72

    Chapter 3 - PM700 series power meter PowerLogic ION Setup device configuration guide

    Page 26 2009 Schneider Electric. All rights reserved.

    PM700 series meter setupBeforeusingIONSetup,makesureallthecommunications settingsforthePM700seriesmeterhasbeenconfigured,asexplainedinthemeterdocumentation.

    NOTEThe procedures described here only apply to the meter models that are equipped with communications

    (i.e., the PM710 and PM750 meters, but not the PM700 and PM700P).

    ThePM700seriesmeterusesModbusRTUprotocoltocommunicatethroughitsRS485serialcommunicationsport.

    Devicecommunicationssettings: MakesureallthedevicesonthesameRS485looparesettothesamebaudrateandparity. RecommendedsettingforparityisNone(no parity).

    Deviceaddress(unitID)settings: Makesurethedeviceaddress(unitID)isuniqueforeachdeviceinagivenRS485loop(range=1to247forModbus

    devices).

    Using ION SetupUseNetworkModeinIONSetuptoaddandconfigurethePM700seriesmeter(i.e., cleartheSingleIONdeviceconfigurationmodecheckboxontheLogonscreen).

    RefertotheIntroductionsectionforinformationonaddingsitesandmeters.

    PM700 series setup screensThefollowingsectionsdescribewhatsetupscreensareavailableonthePM700seriesmeter. Somesetupparametersonlyapplytoparticularmodelsrefertoyourmeterdocumentationfordetailsonsupportedfeatures.

    Basic Setup

    System Type

    Selectthe

    option

    that

    describes

    how

    your

    PM700

    series

    meter

    is

    wired

    to

    the

    electricalservice. RefertothePM700seriesmeterinstallationguidefordetailsonthedifferentsystemtypes.

    PT Ratio

    Selecttheappropriatescalevalue(multiplier)forthePTprimary. Fordirectconnect,selectNo PTs.

  • 7/24/2019 ION Setup Device Configuration Guide

    27/72

    PowerLogic ION Setup device configuration guide Chapter 3 - PM700 series power meter

    2009 Schneider Electric. All rights reserved. Page 27

    PT Primary

    EnterthevalueforthePTprimary,inVolts.

    PT Secondary

    SelectthevalueforthePTsecondary.

    CT PrimaryEnterthevaluefortheCTprimary,inAmps.

    CT Secondary

    SelectthevaluefortheCTsecondary.

    Service Frequency

    Selectthesystemfrequencyoftheelectricalservice.

    DemandDemandistheaveragepowerconsumptionoverafixedtimeinterval(demandperiod),typically15 minutes.

    Demandvaluesarecalculatedforeachsubinterval,thenaveragedoverthenumberofsubintervalsthatmakeupthedemandperiod.

    Thermal Dmd Period (mins)

    Enterthelengthofthedemandperiod,inminutes.

    Block Dmd Period (mins)

    Enterthelengthofeachrollingblockperiod(subinterval),inminutes.

    Block # of Sub-Intervals

    Enterthenumberofsubintervalsusedforcalculatingdemand

    NOTE

    Refer to the PM700 series documentation for details on how the meter calculates demand.

    Front Panel Display

    Display ModeSelectIECorIEEEconventionfordisplayingdataonthePM700seriesmetersdisplaypanel.

  • 7/24/2019 ION Setup Device Configuration Guide

    28/72

    Chapter 3 - PM700 series power meter PowerLogic ION Setup device configuration guide

    Page 28 2009 Schneider Electric. All rights reserved.

    I/O SetupRefertothePM700seriesmeterdocumentationforI/Odescriptionsandconfigurationdetails.

    Digital Out KY

    Label: ThisfieldidentifiestheKYdigitaloutput.

    Mode: SelecttheKYdigitaloutputmodeofoperation.

    ExternalControlconfigurestheoutputtobecontrolledbyacommandsentoverthecommunicationslink.

    PMAlarmconfigurestheoutputtobecontrolledbythepowermeterinresponsetoasetpointcontrolledalarmcondition.

    kWhoutpulsesetsthemetertogenerateafixeddurationpulseoutputthatcanbeassociatedwiththekWhconsumption. UsethePulseWeightregistertoenterhowmanykWhoutoftheloadareassociatedwitheachpulseoftheKYdigitaloutput. ThenusethePulseDurationboxtoselectthepulsewidth(inmilliseconds)foreachkWhpulse.

    Digital In S1 and S2 (PM750 only)

    Label: Thisfieldidentifiesthedigitalinput.

    Mode: SelecttheoperationmodefortheSIdigitalinput:

    Forsimpleon/offdigitalinputoperation,selectNormal.

    SelectDemandIntervalSyncPulseiftheSIdigitalinputisconfiguredasthedemandsyncinput.

    Onboard AlarmsTheOnboardAlarmssetupscreenallowsyoutomakechangesto15preconfiguredalarms(13standardalarmsand2digitalinputalarms). RefertothePM750

    Reference

    Manualforalistingofthesealarms.

    Setting a preconfigured standard alarm1. SelectAllAlarms,thenclickEdit.

  • 7/24/2019 ION Setup Device Configuration Guide

    29/72

    PowerLogic ION Setup device configuration guide Chapter 3 - PM700 series power meter

    2009 Schneider Electric. All rights reserved. Page 29

    2. IntheAlarmSetupscreen,selectthestandardalarmyouwanttoset.

    Enable: Selectthischeckboxtoenablethealarm

    Label: Ifrequired,usethisboxtorenametheselectedalarm

    SetpointPickup: Enterthemagnitudeabove(forOver)orbelow(forUnder)thatdefinesthealarmONcondition,thenintheDelayboxenterthenumberofsecondsthealarmONconditionneedstobetruebeforethealarmisactivated.

    SetpointDropout: Enterthemagnitudebelow(forOver)orabove(forUnder)thatdefinesthealarmOFFcondition,thenintheDelayboxenterthenumberofsecondsthealarmOFFconditionneedstobetruebeforethealarmisdeactivated.

    NOTE

    Pay special attention to the multipliers for Setpoint Pickup and Setpoint Dropout settings, and adjust thevalues if needed.

    AssociateOutput: Selectthischeckboxtoassociatethealarmconditionwithanoutput(e.g.,themetersdigitaloutput).

    Redefining a preconfigured alarm

    Youcanredefineapreconfiguredalarmbychangingthealarmcondition(OverorUnder)and/orselectingadifferentalarmsourceorinput. MakesureyouupdatetheLabelfieldasappropriate.

    Forexample,

    Status

    Input

    On

    can

    mean

    the

    alarm

    is

    activated

    when

    the

    digital

    inputisswitchedon,whileStatusInputOffcanmeanthealarmisactivatedwhenthedigitalinputisswitchedoff.

    ConditionAlarm sourceor input

    Multiplier

  • 7/24/2019 ION Setup Device Configuration Guide

    30/72

    Chapter 3 - PM700 series power meter PowerLogic ION Setup device configuration guide

    Page 30 2009 Schneider Electric. All rights reserved.

    Setting a preconfigured digital input alarm1. SelectAllAlarms,thenclickEdit.

    2. IntheAlarmSetupscreen,selectthedigitalinputyouwanttoconfigureforalarming.

    Enable: Selectthischeckboxtoenablethealarm

    Label: Ifrequired,usethisboxtorenametheselectedalarm

    AssociateOutput: Selectthischeckboxtoassociatethealarmconditionwithanoutput(e.g.,themetersdigitaloutput)

    Redefining a preconfigured digital input alarm

    Youcanredefineapreconfiguredalarmbychangingthealarmcondition. StatusInputOnmeansthealarmisactivatedwhenthedigitalinputisswitchedon,whileStatusInputOffmeansthealarmisactivatedwhenthedigitalinputisswitchedoff.

    Serial Comms

    Modbus Address

    ThisdisplaystheModbusaddress(unitID)ofthemeter.

    Baud Rate

    Thisdisplaysthemetersbaudratesetting.

    ConditionAlarm source

    or input

  • 7/24/2019 ION Setup Device Configuration Guide

    31/72

  • 7/24/2019 ION Setup Device Configuration Guide

    32/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 32 2009 Schneider Electric. All rights reserved.

    PM800 series meter setupBeforeusingIONSetup,makesureallthecommunications settingsforthePM800seriesmeterhavebeenconfigured,asexplainedinthemeterdocumentation.

    ThePM800seriesmeterusesModbusRTUprotocoltocommunicatethroughitsRS485serialcommunicationsport.

    Devicecommunicationssettings: MakesureallthedevicesonthesameRS485looparesettothesamebaudrate. Also,makesureparityissettoNone(no parity)inordertocommunicatewithIONSetup.

    Deviceaddress(unitID)settings: Makesurethedeviceaddress(unitID)isuniqueforeachdeviceinagivenRS485loop(range=1to247forModbusdevices).

    ThePM800seriesmeterscanalsobeequippedwiththeoptionalEthernetCommunicationsCard,whichprovidesEthernetcommunicationscapabilityandEthernetGatewayfunctionalitytothedevice. ThegatewayusesModbusTCP/IP

    protocolto

    communicate

    on

    the

    Ethernet

    port

    and

    Modbus

    RTU

    on

    the

    serial

    port.

    PM8ECC considerationsIfyourPM800seriesmeterisequippedwiththePM8ECCEthernetcommunicationcard,youcancommunicatetothemeterdirectlythroughitsEthernetport.

    NOTE

    Refer to the PM8ECC documentation for instructions on how to set up the device parameters such as

    Ethernet & TCP/IP settings.

    Adding the PM800 series meter as an Ethernet device1. StartIONSetupinNetworkMode(i.e.cleartheSingleIONdevice

    configurationmodecheckboxwhenyoulogon). YoumustaddandconfigureanEthernetsiteiftherearenoEthernetsitesonyourIONSetupnetwork.

    2. RightclicktheEthernetsiteiconandselectInsertItem. SelectMeterandclickOK.

  • 7/24/2019 ION Setup Device Configuration Guide

    33/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 33

    3. TypeadescriptivenameforyourPM800seriesmeter. Selectthetypeofdevice(i.e.,PM800series).TypetheIPaddressofthePM8ECC. IntheIP Portbox,type502. SelectGroup. ClickOK.

    Setting up the PM8ECC as an Ethernet gateway

    Youcan

    set

    up

    the

    PM8ECC

    as

    an

    Ethernet

    gateway

    this

    allows

    you

    to

    communicatewithRS485serialdevicesonthePM8ECCserialport,throughthePM8ECCsEthernetport. MakesurethecommunicationssettingsforalldevicesintheRS485looparesetupproperly(seePM800seriesmetersetuponpage 32).ForRS485wiringinstructions,refertothePM800seriesdocumentation.

    EachserialdeviceontheRS485loopmustbeaddedtothePM8ECCsdevicelistbyusingthewebbrowsertoaccessthePM8ECCwebpages. RefertothePM8ECCdocumentationfordetails.

    1. StartIONSetupinNetworkMode(i.e.,cleartheSingleIONdeviceconfigurationmodecheckboxwhenyoulogon).

    2. Addanew

    site.

    Select

    Ethernet,

    then

    select

    the

    Gateway

    box.

    3. Inthe

    Gateway

    Info

    boxes,

    enter

    the

    IP

    address

    of

    the

    PM8ECC.

    In

    the

    IP Port

    box,type502. ClickOK.

    NOTE

    The IP Port must be set to 502 for Modbus TCP communication.

    Using ION SetupUseNetworkModeinIONSetuptoaddandconfigurethePM800seriesmeter(i.e., cleartheSingleIONdeviceconfigurationmodecheckboxontheLogonscreen).

    RefertotheIntroductionsectionforinformationonaddingsitesandmeters.

  • 7/24/2019 ION Setup Device Configuration Guide

    34/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 34 2009 Schneider Electric. All rights reserved.

    PM800 series setup screensThefollowingsectionsdescribethePM800seriesmeterssetupscreens.

    NOTE

    Some setup screens only apply to particular models (e.g., waveform capture for the PM870), while other

    screens apply only to installed options (such as the Comm - ECC setup screen for meters equipped with

    the optional PM8ECC Ethernet communications card). Refer to your meter documentation for details on

    supported features.

    Alarm Log

    Status

    Selecttheappropriateoptiontoenableordisablealarmlogging.

    Basic Setup

    System Type

    SelecttheoptionthatdescribeshowyourPM800seriesmeteriswiredtotheelectricalservice. RefertothePM800seriesmeterdocumentationfordetails.

    Primary Scale Factor

    Selecttheappropriatescalevalue(multiplier)forthePTprimary. Fordirectconnect,selectNo PTs.

    PT PrimaryEnterthevalueforthePTprimary,inVolts.

    PT Secondary

    SelectthevalueforthePTsecondary.

    CT Primary

    EnterthevaluefortheCTprimary,inAmps.

    CT Secondary

    SelectthevaluefortheCTsecondary.

    Service FrequencySelectthesystemfrequencyoftheelectricalservice.

    Nominal Voltage

    Enterthenormalordesignedvoltageleveloftheelectricalservice,inVolts.

    Nominal Current

    Enterthenormalordesignedcurrentleveloftheelectricalservice,inAmps.

  • 7/24/2019 ION Setup Device Configuration Guide

    35/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 35

    Billing Log

    Status

    Selecttheappropriateoptiontoenableordisablethebillinglog.

    Interval (mins)Enterhowoften(inminutes)thebillingquantitiesshouldbelogged.

    Channels

    Thisallowsyoutoselectwhichparameterstoincludeinthebillinglog.

    1. SelectChannels,thenclickEdit.

    2. Toaddorremoveaparameterfromthebillinglog:

    Addingparameters: UnderAvailable,clickthe+signtoexpandanddisplayindividualparameters. Clickaparametertoselectit,thenclickthe

    buttontomovetheparametertoSelected.

    Removingparameters: UnderSelected,clicktheparameteryouwantto

    remove,thenclickthe button.

    3. ClickSendtosavethechangestothemeter. Thefollowingpromptappears:

    4. NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirm,orNotocancelandgobacktothepreviousdialog.

  • 7/24/2019 ION Setup Device Configuration Guide

    36/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 36 2009 Schneider Electric. All rights reserved.

    ClockTheClocksetupscreenallowsyoutosetthedateandtimeonthemeter.ClickEdittochangethedate/timesetting,thenclickSend.

    Comm - ECC CardThissectionappliestometersthatareequippedwiththeoptionalPM8ECCEthernetcommunicationscardmodule. Ifinstalled,thePM8ECCsettingscanbeviewedfromthefollowingsetupregisters:

    IP Address

    ThisdisplaystheIPaddressofthePM8ECC.

    Subnet Mask

    ThisdisplaystheEthernetsubnetmasksettingforthePM8ECC.

    GatewayThisdisplaystheEthernetgatewaysettingforthePM8ECC.

    Com3 Protocol

    ThisdisplaystheprotocolusedonthePM8ECCsserialport.

    Com3 Address

    ThisdisplaystheModbusaddressofthePM8ECCsserialport.

    Com3 Baud Rate

    ThisdisplaysthebaudratesettingofthePM8ECCsserialport.

    Com3 Parity

    ThisdisplaystheparitysettingofthePM8ECCsserialport.

    Comm - Onboard Serial

    Com1 Protocol

    Thisdisplaysthemetersserialcommunications protocolsetting(e.g.Modbus).

    Com1 Address

    Thisdisplays

    the

    Modbus

    address

    (unit

    ID)

    of

    the

    meter.

    Com1 Baud Rate

    Thisdisplaysthemetersbaudratesetting.

    Com1 Parity

    Thisdisplaysthemeterscommunicationsportparitysetting. TocommunicatewithIONSetup,thismustbesettoNone.

  • 7/24/2019 ION Setup Device Configuration Guide

    37/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 37

    NOTE

    The remote display adapter (PM8RDA) provides an additional serial communications port (COM2).

    However, this COM2 port becomes unavailable if you connect an Ethernet communications card

    (PM8ECC) to the meter.

    Data Log #1, Data Log #2, Data Log #3, Data Log #4

    Status

    Selecttheappropriateoptiontoenableordisablethedatalog.

    Interval

    Thisallowsyoutosettheloggingmodeandintervalforthedatalog.

    1. SelectInterval,thenclickEdit.

    2. UsetheModeboxtoselectOnlyOnEvent,Continuous,orStart/Stop(refertothemeterdocumentationformoreinformation). Enterhowoften(inminutes)theparametersshouldberecordedinthedatalog.

    3. ClickOK.

    ChannelsThisallowsyoutoselectwhichparameterstoincludeinthedatalog. ThesetupprocedureissimilartotheonedescribedintheBillingLogsection,underChannelsonpage 35.

    Device Labels

    Device Label

    Youcanusethistextfieldtoassignalabel(e.g.,anabbreviation)foryourmeter.

    Device NameplateYoucanusethistextfieldtodescribeyourmeter(e.g.,type,locationorotherdevicedetail).

  • 7/24/2019 ION Setup Device Configuration Guide

    38/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 38 2009 Schneider Electric. All rights reserved.

    EN50160 Setup

    EN50160 Evaluation

    SelecttheappropriateoptiontoenableordisabletheEN50160evaluationfeature.

    First Day of WeekSelectSundayorMondaytobethefirstdayoftheweek.

    Interruption (% Nominal)

    Enterthevaluethatdefineswhatconstitutesavoltageinterruption,expressedasapercentageofnominalvoltage.Forexample,ifInterruption(% Nominal)issetto1%,avoltageinterruptionisrecordedifthevoltagedropsbelow99%ofitsnominalvalue.

    Max Short Interruption (secs)

    Enterthelongesttimeduration,innumberofseconds,thatdefinesashortinterruption. Forexample,ifMaxShortInterruption(secs)issetto270seconds,

    avoltage

    interruption

    lasting

    longer

    than

    that

    time

    is

    considered

    along

    interruption.

    Slow Voltage Variations

    Enterthevaluethatdefinestheallowablerangeofslowvoltagevariations,expressedasapercentageofnominalvoltage(typically+/10%ofnominal).

    Voltage for 4-Wire Systems

    Selectwhetherthevoltagefora4wiresystemisexpressedasLinetoNeutralorLinetoLine.

    Frequency Configuration

    SelectSynchronousforasystemwithasynchronousconnectiontoaninterconnectedsystem,orUnsynchronousforasystemwithoutasynchronousconnectiontoaninterconnectedsystem.

    Formoreinformation,refertothePM800seriesReferenceManual.

    Energy & Demand

    Accumulated Energy

    Selecthowaccumulatedenergyvaluesshouldbestored(absoluteorsigned).

    Power Mode

    Selectwhichtechniqueisusedtocalculatedemandpower.

    Power Interval

    Enterthedurationofeachdemandinterval(forcalculatingdemandpower),inminutes.

  • 7/24/2019 ION Setup Device Configuration Guide

    39/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 39

    Power Sub-Interval

    Enterthedurationofeachsubinterval(fordemandpower),inminutes.

    Current Mode

    Selectwhichtechniqueisusedtocalculatedemandcurrent.

    Current IntervalEnterthedurationofeachdemandinterval(forcalculatingdemandcurrent),inminutes.

    Current Sub-Interval

    Enterthetimeperiodforeachsubinterval(fordemandcurrent),inminutes.

    Front Panel Display

    Language

    SelectwhichlanguageisdisplayedonthePM800seriesmetersLCDpanel.

    Date Format

    Selectyourdateformat(e.g.yy/mm/dd).

    Time Format

    Selectyourtimeformat(24houror12hourAM/PM).

    Phase Notation

    Selectyourlinephaselabelformat(A/B/C/Nor1/2/3/N).

    I/O SetupRefertothePM800seriesmeterdocumentationforI/Odescriptionsandconfigurationdetails.

    Digital Out KY

    Label: TypeanameidentifyingtheKYdigitaloutput.

    Mode: SelecttheKYdigitaloutputmodeofoperation:

    Normal:UsethismodefornormalON/OFFoperationoftheKYdigitaloutput.

    ForTimed

    or

    End

    of

    Demand

    Intervalmode,

    use

    the

    Hold

    Time

    register

    toenterhowmanysecondstheKYdigitaloutputremainsenergized.

    ForAbsolutekWhpulse,AbsolutekVARhpulseorkVAhpulsemode,usethePulseWeightregistertoenterhowmanyabsolutekWh(intoandoutoftheload),absolutekVARh(intoandoutoftheload)orkVAhareassociatedwitheachpulseoftheKYdigitaloutput.

    ForkWhinpulseorkVARhinpulsemode,usethePulseWeightregistertoenterhowmanykWhorkVARhintotheloadareassociatedwitheachpulseoftheKYdigitaloutput.

  • 7/24/2019 ION Setup Device Configuration Guide

    40/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 40 2009 Schneider Electric. All rights reserved.

    ForkWhoutpulseorkVARhoutpulsemode,usethePulseWeightregistertoenterhowmanykWhorkVARhoutoftheloadareassociatedwitheachpulseoftheKYdigitaloutput.

    Ifsettoanyoftheabovepulsemodes,theDigitalKYOutputwillpulsebasedonanenergyperpulsevalue. RefertothePM800seriesreferencemanualfordetailsondeterminingthevalueofthePulseWeightsetting.

    Control: ForNormal,LatchedorTimedmodeofoperation,selecthowtheKYdigitaloutputiscontrolled,i.e.,eitherExternallyControlledorcontrolledbypowermeteralarm(PMAlarm).

    NOTE

    For detailed descriptions on the different Mode and Control options, refer to the Relay Output Operating

    Modes section in the PM800 series reference manual.

    Digital In SI

    Label: TypeanameidentifyingtheSIdigitalinput.

    Mode: SelecttheoperationmodefortheSIdigitalinput. Fordetaileddescriptionsonthedifferentmodes,refertotheDigitalInputssectioninthePM800seriesreferenceManual.

    Normal:UsethismodefornormalON/OFFoperationofthedigitalinput.

    DemandIntervalSyncPulse: UsethismodetoconfiguretheSIdigitalinputasthedemandsyncinput(toreceiveademandsyncpulsefromautilitydemandmeter,forexample).

    ConditionalEnergyControl: UsethismodetoconfiguretheSIdigitalinputforconditionalenergycontrol.

    PulseWeight: ForNormalorInputMeteringmodeofoperation,enterthepulseweightassociatedwiththechangeofstateoftheinput.

    Units: ForNormalorInputMeteringmodeofoperation,selecttheunitofmeasurementassociatedwiththeSIdigitalinputpulse(ifapplicable).

    Optional I/O modulesThefollowingparametersapplytometersequippedwiththeoptionalI/Omodules. RefertothePM800seriesmeterdocumentationtoseewhichinputsandoutputsareavailableforthetypeofI/Omodule(s)installedonyourmeter.

    Relay A-R1, Relay A-R2, Relay B-R1, Relay B-R2

    Label: Typeanameidentifyingtherelayoutput.

    Mode: Selectwhichmodeofoperationtherelayoutputuses(Normal,Latched,Timed,orEndofDemandInterval).

    Control: ForNormal,LatchedorTimedmodeofoperation,selecthowtherelayoutputiscontrolled,i.e.,eitherExternallyControlled(RemotelyControlled)orPMAlarm(PowerMeterControlled).

    HoldTime: ForTimedandEndofDemandIntervalmodeofoperation,enterhowmanysecondstherelayremainsenergized.

  • 7/24/2019 ION Setup Device Configuration Guide

    41/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 41

    NOTE

    For detailed descriptions on the different modes of operation, refer to the Relay Output Operating

    Modes section in the PM800 series reference manual.

    ClickOK. Configuretheotherrelaysasrequired.

    Digital In A-S1, Digital In A-S2 Digital In A-S6,Digital In B-S1, Digital In B-S2 Digital In B-S6

    Label: Typeanameidentifyingthedigitalinput.

    Mode: Selectthedigitalinputmodeofoperation(Normal,DemandIntervalSyncPulse,ConditionalEnergyControl,orInputMetering).

    PulseWeight: ForNormalorInputMeteringmode,enterinthePulseWeightboxhowmanyunitsofameasuredorcalculatedquantityisassociatedwitheachpulse.

    Units: ForNormalorInputMeteringmode,selecttheunitsusedforthemeasuredorcalculatedquantity(ifapplicable).

    NOTE

    For detailed descriptions on the different modes of operation, refer to the Digital Inputs section in the

    PM800 series reference manual.

    Analog I/O

    RefertothePM800seriespowermeterinput/outputmoduleinstallationmanualforinstructionsonhowtosetuptheanaloginputs(Analog In AAI1,Analog In AAI2,Analog In BAI1,Analog In BAI2)andanalogoutputs(Analog Out AAO1,Analog Out AAO2,Analog Out BAO1,Analog Out BAO2):

    AnalogInputs

    Label: Thisnameidentifiesthespecificanaloginput.

    Units: Definestheunitsofthemonitoredanalogvalue.

    Scalefactor: Defineswhatmultiplierisusedonthemeasuredvalue.

    ReportRangeLowerLimit: Thisisthevaluethepowermeterreportswhentheinputreaches(ordropsbelow)thelowestvalidreading.

    ReportRangeUpperLimit: Thisisthevaluethepowermeterreportswhentheinputreaches(orexceeds)thehighestvalidreading.

    AnalogOutputs

    Label: Thisnameidentifiesthespecificanalogoutput. Outputregister: Definesthepowermeterregisterassignedtotheanalog

    output.

    LowerLimit: Thisistheminimumoutputcurrentthatthepowermetersendstotheanalogoutputwhentheregistervaluereaches(ordropsbelow)thelowerlimit.

  • 7/24/2019 ION Setup Device Configuration Guide

    42/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 42 2009 Schneider Electric. All rights reserved.

    UpperLimit: Thisisthemaximumoutputcurrentthatthepowermetersendstotheanalogoutputwhentheregistervaluereaches(orexceeds)theupperlimit.

    Input MeteringRefertothemeterdocumentationfordetaileddescriptionsonmeteringcapabilitiesandoptions.

    Demand Method

    Selectwhichmethodisusedforcalculatingdemand.

    Demand Interval

    Enterthetimeperiodforeachdemandinterval,inminutes.

    Demand Sub-Interval

    Enterthetimeperiodforeachdemandsubinterval,inminutes.

    Channel 1, Channel 2 Channel 5

    Beforeyoucanassociateadigitalinputtoachannel,youneedtosetupthedigitalinputforinputmeteringoperation. RefertoI/OSetuponpage 39fordetails.

    1. FromtheInputMeteringsetupscreen,selectoneoftheavailablechannels.

    2. IntheLabelfield,enteradescriptivenameforthechannel.

    3. Selecttheappropriateunitsandrate. Theunitsyouselectmustmatchtheunitsyouselectedforthedigitalinput(whenyouconfigureditforinputmetering).

    4. IntheAvailableInputscolumn,selectthedigitalinput,thenclickthebuttontomoveittotheAssignedInputscolumn.

    (Tounassigntheinput,selectitfromtheAssignedInputscolumn,thenclickthe button.)

    NOTE

    Usually, input metering applications also require one input to be set up for Demand Interval Sync Pulse,

    to allow customers to synchronize their demand intervals to the utility (typically, the pulse signal is

    provided by the utility). To set up an input for demand interval sync pulse, refer to I/O Setup on

    page 39.

    Meter ResetsToresetthemeter,doubleclickMeterInitthenselectReinitialize. ClickOK.

    ClickSendtoinitializethemeter. Attheprompt,clickYestoproceed,orNotoaborttheinitialization.

  • 7/24/2019 ION Setup Device Configuration Guide

    43/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 43

    NOTE

    Initializing a meter will reset or disable certain parameters. Make sure you read the warning prompt

    before proceeding.

    Metering StandardsHarmonic Distortion

    Selecthowtotalharmonicdistortioniscalculated.

    PF Sign Convention

    SelectwhichstandardsconventiontousefordisplayingPFsign.

    Voltage Harmonic Method

    Selecthowthemagnitudeofvoltageharmonicisdisplayed.

    Current Harmonic MethodSelecthowthemagnitudeofcurrentharmonicisdisplayed.

    Onboard Alarms/Events

    Standard

    Thisallowsyoutoconfigurethestandardalarms. SelectStandardthenclickEdit.

    Thenumberedlabels(onthedrawing)aredescribedbelow:

    1. Theleftcolumnliststhestandardalarms. Selectaniteminthislisttoeditit.

    12

    5

    3 4

    6

    9

    10

    7 8

    11

    12 13

  • 7/24/2019 ION Setup Device Configuration Guide

    44/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 44 2009 Schneider Electric. All rights reserved.

    2. Thetwoboxesatthetopliststhestandardalarmconditionandmeasurementthatdefinesthehighlightediteminalarmslist. Youcanusetheseboxestochangetheconditionandmeasurementforthisalarm.

    3. SelecttheEnableboxtoenabletheselected(highlighted)alarminthelist,orcleartheboxtodisablethealarm.

    4. The

    Label

    box

    identifies

    the

    name

    of

    the

    standard

    alarm.

    Use

    this

    box

    to

    renamethealarmasnecessary(e.g.,ifyouchangedtheconditionormeasurementforthestandardalarm).

    5. Enterthesetpointpickupvalue(absoluteorrelative,seeitem#7below)andthepickupdelay(inseconds).

    6. Enterthesetpointdropoutvalue(absoluteorrelative,seeitem#7below)andthedropoutdelay(inseconds).

    7. Tospecifyabsolutevaluesforthesetpointpickupanddropoutlimits,clear(uncheck)theRelative(%ofAvg)box. TospecifysetpointpickupanddropoutlimitsasapercentageaboveorbelowtheRMSaveragevalue(Avg),select(check)theRelative(%ofAvg)box.

    8. Usethe

    Priority

    box

    to

    set

    the

    alarm

    priority.

    9. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.

    10. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,orcleartheboxtodisablewaveformcaptureonalarm.

    11. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclickthe buttontomoveittotheSelectedcolumn. ClickOK.

    12. Tocreateanewalarm,clickAdd, thenspecifythealarmconditionandmeasurement,asdescribedintheprevioussteps.

    NOTEThere is a limit to the number of alarms you can create. The Addbutton is disabled once that limit is

    reached. In this case, you must delete an existing alarm before you can create a new one (or you can

    select an existing alarm and edit/configure it as necessary).

    13. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.

    Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:

  • 7/24/2019 ION Setup Device Configuration Guide

    45/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 45

    NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.

    Formoreinformationonconfiguringthealarms,refertothePM800seriesReferenceManual.

    Disturbance (PM870 only)Thisallowsyoutoconfigurethedisturbancealarms(i.e.voltagesagsandswells).SelectDisturbancethenclickEdit.

    Thenumberedlabels(onthedrawing)aredescribedbelow:

    1. Theleftcolumnliststhedisturbancealarms. Selectaniteminthislisttoeditit.

    2. Thetwoboxesatthetopliststhedisturbancealarmconditionandmeasurementthatdefinesthehighlightediteminalarmslist. Youcanusetheseboxestochangethecondition(sagorswell)andmeasurement(currentorvoltage)foraselectedalarm.

    3. SelecttheEnableboxtoenabletheselected(highlighted)alarminthelist,orcleartheboxtodisablethealarm.

    4. TheLabelboxidentifiesthenameofthedisturbancealarm. Usethisboxtorenamethealarmasnecessary(e.g.,ifyouchangedthecondition/measurementforthedisturbancealarm).

    5. Enterthesetpointpickupvalue(absoluteorrelative,seeitem#7below)andthe

    pickupdelay(innumberof

    cycles).

    6. Enterthesetpointdropoutvalue(absoluteorrelative,seeitem#7below)andthedropoutdelay(innumberofcycles).

    7. Tospecifyabsolutevaluesforthesetpointpickupanddropoutlimits,clear(uncheck)theRelative(%ofAvg)box. TospecifysetpointpickupanddropoutlimitsasapercentageaboveorbelowtheRMSaveragevalue,select(check)theRelative(%ofAvg)box.

    1 2

    5

    3 4

    6

    9

    10

    7 8

    11

    12 13

  • 7/24/2019 ION Setup Device Configuration Guide

    46/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 46 2009 Schneider Electric. All rights reserved.

    8. UsethePriorityboxtosetthealarmpriority.

    9. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.

    10. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,orcleartheboxifyoudonotwanttotriggerawaveformcaptureonalarm.

    11. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclickthe buttontomoveittotheSelectedcolumn. ClickOK.

    12. Tocreateanewalarm,clickAdd, thenspecifythealarmconditionandmeasurement,asdescribedintheprevioussteps.

    NOTE

    There is a limit to the number of alarms you can create. The Addbutton is disabled once that limit is

    reached. In this case, you must delete an existing alarm before you can create a new one (or you can

    select an existing alarm and configure it as necessary).

    13. Todelete

    an

    alarm,

    select

    itfrom

    the

    alarms

    list,

    then

    click

    Delete.

    Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:

    NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.

    Formoreinformationonconfiguringthealarms,refertothePM800seriesReferenceManual.

    Digital

    Thisallowsyoutoconfigurethedigitalinputalarms. SelectDigitalthenclickEdit.

  • 7/24/2019 ION Setup Device Configuration Guide

    47/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 47

    Thenumberedlabels(onthedrawing)aredescribedbelow:

    1. Theleftcolumnliststhedigitalinputalarms.Selectaniteminthislisttoeditit.

    2. Thisdefinesthealarmcondition.

    SelectStatusInputOntosetthealarmwhenthedigitalinputchangesfromofftoon.

    SelectStatusInputOfftosetthealarmwhenthedigitalinputchangesfromontooff.

    TheEndofincrementalenergyinterval(EndIncEnrInt), Endofdemandinterval(EndDmdInt)andPowerup/reset(PwrUp/Reset)

    alarmsare

    unary

    type

    alarms

    because

    they

    use

    internal

    signals

    from

    the

    powermeter,andcannotbechangedthroughthissetupscreen. Refertothemeterdocumentationformoreinformation.

    3. DependingontheI/Omoduleinstalledonyourmeter,thisallowsyoutoselectoneoftheavailabledigitalinputs. Notethatthisisnotconfigurableforunarytypealarmsseeitem#2above.

    4. SelecttheEnablecheckboxtoenabletheselected(highlighted)alarminthelist,orcleartheboxtodisablethealarm.

    5. TheLabelboxidentifiesthenameofthedigitalalarm. Typeinthisboxtorenamethealarmasnecessary.

    6. UsethePriorityboxtosetthepriorityfortheselectedalarm.

    7. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.

    8. SelecttheWaveformCapturecheckboxtotriggerawaveformcaptureonalarm,orcleartheboxto ifyoudonotwanttotriggerawaveformcaptureonalarm.

    9. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclickthe buttontomoveittotheSelectedcolumn. ClickOK.

    1

    2

    6

    4 5

    7

    8 9

    3

    10 11

  • 7/24/2019 ION Setup Device Configuration Guide

    48/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 48 2009 Schneider Electric. All rights reserved.

    10. Tocreateanewalarm,clickAdd, thenspecifythealarmtypeandselectthedigitalinput,asdescribedintheprevioussteps.

    11. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.

    Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:

    NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.

    Formoreinformationonconfiguringthealarms,refertothePM800seriesReferenceManual.

    Boolean

    ThisallowsyoutoconfiguretheBooleanalarms. SelectBooleanthenclickEdit.

    NOTE

    If you havent set up any Boolean alarms yet, click Addto create a Boolean alarm.

    1. SelectaBooleanalarmtoeditit.

    2. UsetheLabelboxtorenametheselectedBooleanalarm(e.g.AnyOvercurrent).

    3. Selectthetypeoflogicoperation(e.g.,LogicOR)youwanttousetotestforthealarmcondition.

    12

    4 5

    6 7

    3

    11 12

    8

    9 10

  • 7/24/2019 ION Setup Device Configuration Guide

    49/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 49

    4. ThisboxliststhealarmparametersusedfortheBooleanlogictest.

    5. ClickEdittoaddorremovealarmparameters.

    SelectanalarmparameterunderAvailable,thenclickthe buttontomoveittoSelected. Ifyouwanttoremoveaparameter,selectitunderSelected,thenclickthe button.

    6. Selectthe

    Enable

    check

    box

    to

    enable

    the

    selected

    (highlighted)

    alarm

    in

    the

    list,orcleartheboxtodisablethealarm.

    7. UsethePriorityboxtosetthepriorityfortheselectedalarm.

    8. UsetheDataLogscheckboxestoselectwhichonboarddatalog(s)areusedtorecordtheselectedalarm.

    9. SelecttheWaveformCaptureboxtotriggerawaveformcaptureonalarm,orcleartheboxifyoudonotwanttotriggerawaveformcaptureonalarm.

    10. Ifyouwanttotriggeradigitaloutputorrelayonanalarm,clicktheOutputbutton,selectoneoftheavailableoutputs,thenclick buttontomoveittoSelected. ClickOK.

    11. To

    create

    a

    new

    Boolean

    alarm,

    click

    Add,

    then

    specify

    the

    alarm

    type

    and

    select

    thedigitalinput,asdescribedintheprevioussteps.

    12. Todeleteanalarm,selectitfromthealarmslist,thenclickDelete.

    Tosavethechangestothemeter,clickSend. Dependingonthetypeofchanges,ameterresetmightoccur:

    NotethatclickingYeswillpowercycle(reset)thedevice. ClickYestoconfirmandproceedwithyourchanges,orNotocancelandgobacktothepreviousdialog.

  • 7/24/2019 ION Setup Device Configuration Guide

    50/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 50 2009 Schneider Electric. All rights reserved.

    Shift EnergyThisallowsyoutogroupenergyusageandcostaccordingtothreedifferenttimeshiftsinsidea24hourperiod(forexample,three8hourshifts).

    First Shift Start, Second Shift Start, Third Shift Start

    Usethesesettingstoselectwhattimethefirst,secondorthirdshiftstarts.

    Cost Scale Factor

    Selectthemultiplierusedwhencalculatingenergycost.

    First Shift Cost (per kWh), Second Shift Cost (per kWh), Third Shift Cost (per kWh)

    UsethesesettingstoenterthecostperkWhforeachshift.

    Billing Cycle Setup

    SelectthisthenclickEdittosetupthebillingcycle.

    UsetheMonthandDayboxestoselectmeterreadingdates. UsetheTimeofDayboxtoselectthehourthemeterreadingisperformed.

    Trending & Forecasting

    Feature Control

    Selecttheappropriateoptiontoenableordisablethisfeature.

    Register Trend Item

    Selectoneoftheavailablequantitiesyouwouldliketotrend,orselectUserDefined.

    User Defined Register

    Selectoneoftheavailableitemsfortrending.

    User Defined Scaling

    Selecttheappropriatemultiplierfortheitemselectedfortrending.

  • 7/24/2019 ION Setup Device Configuration Guide

    51/72

    PowerLogic ION Setup device configuration guide Chapter 4 - PM800 series power meter

    2009 Schneider Electric. All rights reserved. Page 51

    User Defined Label

    Enteradescriptivenameyouwantfortheitemselectedfortrending.

    Waveform CaptureWaveformcaptureissupportedonthePM850andPM870.ThePM870allowsyoutoselectandconfigurethewaveformcapture.

    Status

    Selecttheappropriateoptiontoenableordisablethisfeature.

    File Mode

    Selectwhichmethodisusedforstoringwaveforms:

    FIFO(firstinfirstout)modediscardstheoldestwaveformcapturewhenthewaveformstorageisfull.

    Fill

    and

    Hold

    mode

    keeps

    the

    oldest

    waveform

    capture

    and

    does

    not

    record

    newoneswhenthewaveformstoragebecomesfull.

    Channels (PM870 only)

    Thisallowsyoutoselectwhichinputsyouwanttosetupforwaveformcapture.SelectChannelsthenclickEdit.

    Dependingonyourwiringconfiguration,certaininputsbecomeN/A(notapplicable). Ifthisisthecase,IONSetupdisplaysthisprompt:

    1. Selectthevoltageand/orcurrentinputchannelsyouwanttocapture. ClickNext.

    2. Setthecaptureoptions:

    Samples/Cycle

    Duration(cycles)

    PreEventCycles

    MaxCaptureindicatesthemaximumnumberofrecordingsforwaveformcapture,andisshownforinformationalpurposeonly.

  • 7/24/2019 ION Setup Device Configuration Guide

    52/72

    Chapter 4 - PM800 series power meter PowerLogic ION Setup device configuration guide

    Page 52 2009 Schneider Electric. All rights reserved.

  • 7/24/2019 ION Setup Device Configuration Guide

    53/72

    2009 Schneider Electric. All rights reserved. Page 53

    5 BCPM (Branch circuit power meter)

    TheBCPM(Branchcircuitpowermeter)providesacosteffectivesolutionforelectricalloadmanagement. TheBCPMisdesignedtomeasurethecurrent,voltage,andenergyconsumptionofeachcircuitinapanelboard,includingthemainbreaker. Bycombiningthefunctionsoftwoboardsintoonedevice,theBCPMscurrentmonitoringcapabilityisincreased,providingsupportforupto92circuits(84 branchcircuits,plus8 auxiliarycircuits)onasingleboard. TheBCPMisavailableina42circuitor84circuitmodel.

    Theaccumulatedinformationcanbetransmittedthroughthecommunicationsinterfaceorviewedlocallythroughanoptionallocaldisplay. Dataupdatesoccurapproximatelyeverytwoseconds,providingtimelypreventativemaintenance

    information.Asacircuitapproachestheuserconfiguredthresholds,alarmindicatorsaretriggered,preventingcostlydowntimefromoverloadedcircuitsorloadfailures.

    Formoreinformation,refertotheBCPMinstallationguide.

    In this chapter

    BCPM setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54UsingIONSetup ..................................................... 54

    BCPM setup screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55BasicSetup .......................................................... 55

    AuxiliaryCTSizes .................................................... 55

    BranchCircuitCTSizes................................................ 55

    BreakerSizes ......................................................... 55

    DemandSetup ....................................................... 56

    InstantaneousCurrentAlarms.......................................... 56

    LatchingCurrentAlarms .............................................. 57

    VoltageAlarms....................................................... 60

  • 7/24/2019 ION Setup Device Configuration Guide

    54/72

    Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide

    Page 54 2009 Schneider Electric. All rights reserved.

    BCPM setupBeforeusingIONSetup,makesureallthecommunicationssettingsfortheBCPMhasbeenconfigured,asexplainedintheBCPMinstallationguide.

    TheBCPMusesModbusRTUprotocoltocommunicatethroughitsRS485serialcommunicationsport.

    Devicecommunicationssettings: MakesureallthedevicesonthesameRS485looparesettothesamebaudrate. MakesureParityswitchissettoOFF(i.e. no parity)foralldevices.

    Deviceaddress(unitID)settings: The2stripversionoftheBCPMusesoneModbusaddress,whilethe4stripversionusestwoModbusaddresses. Panel1usesthebaseaddressassetontheCommunicationsAddressDIPswitches.Panel2(forthe4stripversion)isautomaticallyassignedthedeviceaddressequaltoPanel1sbaseaddressplusone. Forexample,ifyousettheunitIDforPanel1to19,theunitIDforPanel2isautomaticallysetto20(i.e.,19+1).RefertotheBCPMinstallationguidefordetailsonusingtheDIPswitchestoset

    thedevice

    communications

    parameters.

    NOTE

    When setting up the device addresses for multiple BCPMs, make sure each address is unique AND does

    not cause address duplication or overlap between the BCPM devices.

    Device address considerationsSinceeachBCPMusestwodeviceaddresses,adoptingastandardforassigningBCPMdeviceaddressesishighlyrecommended.Forexample,youcanimplementadeviceaddressassignmentconventionthatspecificallyallowsonlyoddnumberedaddressesforagivenBCPM(i.e.,correspondingtoPanel 1). Usingthisconvention,anevennumbereddeviceaddresswillalwaysbePanel 2ofaparticularBCPM.

    BCPM device naming considerationsEachBCPMdeviceisaddedastwometersinIONSetup(i.e.,oneforPanel 1andtheotherforPanel 2). Forthisreason,itisrecommendedthatyouadoptaBCPMdevicenamingconventionsothateachhalfofagivenBCPMdevice(Panel 1,Panel 2)canbeeasilyidentified.

    Using ION Setup UseNetworkModeinIONSetuptoaddandconfiguretheBCPM(i.e.cleartheSingleIONdeviceconfigurationmodecheckboxontheLogonscreen).

    RefertotheIntroductionsectionforinformationonaddingsitesandmeters.

  • 7/24/2019 ION Setup Device Configuration Guide

    55/72

    PowerLogic ION Setup device configuration guide Chapter 5 - BCPM (Branch circuit power meter)

    2009 Schneider Electric. All rights reserved. Page 55

    BCPM setup screensThefollowingsectionsdescribewhatsetupscreensareavailableontheBCPM.Somesetupparametersonlyapplytoparticularmodelsrefertoyourmeterdocumentationfordetailsonsupportedfeatures.

    Basic Setup

    Configuration

    Selecttheconfigurationoptionthatmatcheshowthecurrentsensorstripsarearrangedandoriented. RefertotheBCPMinstallationguidefordetails.

    NOTE

    Make sure Configuration is set to the same value for each half of the BCPM (Panel 1, Panel 2).

    Location

    Typeanamethatidentifiesthepaneland/ordescribesitsphysicallocation.

    Auxiliary CT Sizes

    Auxiliary #1 (Amps) to Auxiliary #4 (Amps)

    ThesedefinetheAuxiliaryorMainsCTsize(typically200A). TypetheappropriatenumericvalueforeachauxiliaryCTinstalledinthepanel.Dependingonthemodeloptionordered,aBCPMcanhave4,8ornoinputsforauxiliaryCTs.IfanyoftheauxiliaryCTsarenotconnected,settheircorrespondingBreakerSize

    valuesto0(zero)inIONSetuptodisablealarmsforthoseunusedchannels.

    Branch Circuit CT Sizes

    Channel #1 (Amps) to Channel #42 (Amps)

    ThesedefinetheChannelorBranchCTsize. Theseregistersarenotconfigurable,butarepresettoafixedvalueof100 A.

    Breaker Sizes

    Auxiliary #1 (Amps) to Auxiliary #4 (Amps)

    ThesedefinetheAuxiliaryorMainsbreakersize(typically225A). Typetheappropriatenumericvalueforeachauxiliarybreakerinthepanel. Forunused

    breakers,setthevalueto0(zero)todisablealarmsforthosechannels.

    Channel #1 (Amps) to Channel #42 (Amps)

    ThesedefinetheChannelorBranchbreakersize(typically20A). Typetheappropriatenumericvalueforeachchannelbreakerinthepanel. Forunused

  • 7/24/2019 ION Setup Device Configuration Guide

    56/72

    Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide

    Page 56 2009 Schneider Electric. All rights reserved.

    breakers,settheircorrespondingbreakersizevaluesto0(zero)todisablealarmsforthoseunusedchannels.

    Demand Setup

    Demandis

    the

    average

    power

    consumption

    over

    afixed

    time

    interval

    (demand

    period),typically15 minutes. Demandvaluesarecalculatedforeachsubinterval,thenaveragedoverthenumberofsubintervalsthatmakeupthedemandperiod.

    Number of Sub-intervals

    Typethenumberofsubintervalsusedforcalculatingdemand(default=1).

    Sub-interval Length (secs)

    Typethenumberofsecondsforeachsubinterval(default=900seconds).

    Instantaneous Current AlarmsTheinstantaneouscurrentalarmsetupparametersdefinethemaximum(highalarm)andminimum(lowalarm)limitsforallbranchandmaincircuitsmonitored

    bytheBCPM. InstantaneouscurrentalarmsareONonlyifthealarmconditionsaremet. ThesealarmsareautomaticallyturnedOFForclearedwhencircuitcurrentiswithinthenormalrange.

    High Alarm Threshold

    Typetheinstantaneouscurrentvalue,expressedasapercentageofthebreakersize(default=60%). Whenthecircuitcurrentexceedsthatvalue,thehighcurrentalarmisactivated.

    Example: Ifthethresholdissetto60%,thehighalarmwouldbeactivatedwhen

    instantaneouscurrentfora20Abreakerexceeds12A(i.e.,20 A x 0.60).

    Low Alarm Threshold

    Typetheinstantaneouscurrentvalue,expressedasapercentageofthebreakersize(default=5%). Whenthecircuitcurrentfallsbelowthatvalue,thelowcurrentalarmisactivated.

    Example: Ifthethresholdissetto5%,thelowalarmwouldbeactivatedwheninstantaneouscurrentfora20Abreakerdropsbelow1A(i.e.,20 A x 0.05).

    Hysteresis

    Typethevalue,expressedasapercentageofthealarmthreshold,thatdefineshow

    muchthe

    circuit

    current

    must

    fall

    below

    the

    High

    alarm

    threshold

    or

    rise

    above

    the

    LowalarmthresholdtodeterminethealarmsOFFstate(default=5%). Todisabletheinstantaneouscurrentalarms,setHysteresistozero(0%).

    Example: Ifhysteresisissetto5%,theOFFstateforahighalarmthresholdof12 Awouldbeat11.4 Aandbelow(i.e.,12Aminus(12Ax0.05)),whiletheOFFstateforalowalarmthresholdof1 Awouldbeat1.005 Aandabove(i.e.,1Aplus(1 A x 0.05)).

  • 7/24/2019 ION Setup Device Configuration Guide

    57/72

    PowerLogic ION Setup device configuration guide Chapter 5 - BCPM (Branch circuit power meter)

    2009 Schneider Electric. All rights reserved. Page 57

    Latching Current AlarmsThelatchingcurrentalarmsetupparametersdefinethealarmdelay(timer)andthreshold(limit)forallbranchandmaincircuitsmonitoredbytheBCPM.LatchedalarmsremainONuntiltheuserresetsorclearsthealarms.

    Thealarm

    delay

    setting

    defines

    how

    many

    seconds

    acircuit

    needs

    to

    be

    in

    an

    alarm

    state(i.e.,exceedsthehighorhighhighalarmthreshold,orfallsbelowtheloworlowlowalarmthreshold)beforethealarmisactivated. Areturntonormal(nonalarm)stateisinstantaneous,sothealarmdelaytimerisresetifthecurrentinthecircuitreturnstonormalstatebeforethetimerexpires.

    Thealarmthresholdsettingdefinesthelimitforahighcurrentorlowcurrentalarmstate,expressedasapercentageofthebreakersize.

    High-High Alarm Delay (s)

    TypethenumberofsecondsthecurrentinacircuitneedstobecontinuouslyabovetheHighHighAlarmThresholdbeforetheHighHighalarmisactivated(default = 10 s).

    High Alarm Delay (s)

    TypethenumberofsecondsthecurrentinacircuitneedstobecontinuouslyabovetheHighAlarmThresholdbeforetheHighalarmisactivated(default =10 s).

    Low Alarm Delay (s)

    TypethenumberofsecondsthecurrentinacircuitneedstobecontinuouslybelowtheLowAlarmThresholdbeforetheLowalarmisactivated(default = 10 s).

    Low-Low Alarm Delay (s)

    Typethenumberofsecondsthecurrentinacircuitneedstobecontinuouslybelow

    theLow

    Low

    Alarm

    Threshold

    before

    the

    Low

    Low

    alarm

    is

    activated

    (default = 10 s).

    Zero Current Alarm On Time (s)

    Typethenumberofsecondsthecurrentinacircuitneedstostayabovethelowlowalarmthresholdlevelbeforethelatchingalarmsarearmed/enabled(default = 10 s).

    Zero Current Alarm Delay (s)

    TypethenumberofsecondsthecurrentinacircuitneedstobebelowtheLowLowAlarmThresholdlevelbeforetheZerocurrentalarmisactivated(default = 30 s).

    High-High Alarm Threshold (%)TypethelimitfortheHighHighcurrentalarmstate,expressedasapercentageofthebreakersize(default = 70%). Forexample,theHighHighalarmthresholdfora20Abreakeris14A(i.e.,20 x 0.70). Todisablethisalarm(forallchannels)setitsthresholdvalueto0%.

    High Alarm Threshold (%)

    TypethelimitfortheHighcurrentalarmstate,expressedasapercentageofthebreakersize(default = 60%). Forexample,theHighalarmthresholdfora20 A

  • 7/24/2019 ION Setup Device Configuration Guide

    58/72

    Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide

    Page 58 2009 Schneider Electric. All rights reserved.

    breakeris12A(i.e.,20 x 0.60). Todisablethisalarm(forallchannels)setitsthresholdvalueto0%.

    Low Alarm Threshold (%)

    TypethelimitfortheLowcurrentalarmstate,expressedasapercentageofthebreakersize(default = 7.5%). Forexample,theLowalarmthresholdfora20 A

    breakeris

    1.5 A

    (i.e.,

    20 x 0.075).

    To

    disable

    this

    alarm

    (for

    all

    channels)

    set

    its

    thresholdvalueto0%.

    Low-Low Alarm Threshold (%)

    TypethelimitfortheLowLowcurrentalarmstate,expressedasapercentageofthebreakersize (default = 2.5%). Forexample,theLowLowalarmthresholdfora20 Abreakeris0.5 A(i.e.,20 x 0.025). Todisablethisalarm(forallchannels)setitsthresholdvalueto0%.

    Latching alarm examples

    Example 1

    1. CurrentrisesaboveLL(lowlowalarmthreshold)thisstartsthezerocurrentalarmONtimer.

    2. CurrentdropsbelowLLbeforethezerocurrentalarmONtimeperiodends,soalarmingisnotenabled. ThezerocurrentalarmONtimerisreset.

    3. CurrentrisesaboveLL thisstartsthezerocurrentalarmONtimer.

  • 7/24/2019 ION Setup Device Configuration Guide

    59/72

    PowerLogic ION Setup device configuration guide Chapter 5 - BCPM (Branch circuit power meter)

    2009 Schneider Electric. All rights reserved. Page 59

    4. Currentremainsabovethelowlowalarmthreshold,beyondthetimeperiodspecifiedbythezerocurrentalarmONtimesettingthisenablesthelatchingalarms(alllatchingalarmsarearmed).

    5. CurrentrisesaboveH(highalarmthreshold)thisstartsthehighalarmdelaytimer.

    6. Current

    rises

    above

    HH

    (high

    high

    alarm

    threshold)

    this

    starts

    the

    high

    high

    alarmdelaytimer.

    7. CurrentdropsbelowHHbeforethehighhighalarmdelayperiodends,sothehighhighalarmdelaytimerisreset.

    8. Highalarmislatchedattheendofthehighalarmdelaytimeperiod.

    Example 2

    1. CurrentrisesaboveLL(lowlowalarmthreshold)thisstartsthezerocurrentalarmONtimer.

    2. Currentremainsabovethelowlowalarmthreshold,beyondthetimeperiodspecifiedbythezerocurrentalarmONtimesettingthisenablesthelatching

    alarms(alllatchingalarmsarearmed).

    3. CurrentdropsbelowL(lowalarmthreshold)thisstartsthelowalarmdelaytimer.

    4. CurrentdropsbelowLL(lowlowalarmthreshold)thisstartsthelowlowalarmdelaytimerandthezerocurrentalarmdelaytimer.

    5. LowalarmislatchedattheendoftheLdelay(lowalarmdelay)timeperiod.

  • 7/24/2019 ION Setup Device Configuration Guide

    60/72

    Chapter 5 - BCPM (Branch circuit power meter) PowerLogic ION Setup device configuration guide

    Page 60 2009 Schneider Electric. All rights reserved.

    6. LowlowalarmislatchedattheendoftheLLdelay(lowlowalarmdelay)timeperiod.

    7. Currentremainsbelowthelowlowalarmthreshold,beyondthetimeperiodspecifiedinthezerocurrentalarmdelaytimesetting,thuslatchingthezerocurrentalarm.

    Voltage AlarmsThevoltagealarmsetupparametersdefinethealarmdelay(timer)andthreshold(limit)forvoltageinputsmonitoredbytheBCPM(ifyourBCPMmodeloptionsupportsit).

    Thealarmdelaysettingdefineshowmanysecondsavoltageinputneedstobeinanalarmstate(i.e.exceedstheovervoltagealarmthreshold,orfallsbelowtheundervoltagealarmthreshold)beforethealarmisactivated. Areturntonormal(nonalarm)stateisinstantaneous,sothealarmdelaytimerisresetifthevoltagereturnstonormalstatebeforethetimerexpires.

    Thealarmthresholdsettingdefinesthelimitforahighvoltageorlowvoltagealarmstate,expressedasapercentageofthebreakersize. Todisableanalarm,setitsthresholdvalueto0 (zero) Volts.

    Over Voltage Delay (s)

    TypethenumberofsecondsthevoltageneedstobecontinuouslyabovetheOverVoltageThresholdlevelbeforetheOverVoltagealarmisactivated.

    Under Voltage Delay (s)

    TypethenumberofsecondsthevoltageneedstobecontinuouslybelowtheUnderVoltageThresholdlevelbef