iologik e1200 series users manual v6
DESCRIPTION
ilogic manualTRANSCRIPT
ioLogik E1200 Series User’s Manual
Sixth Edition, December 2011
www.moxa.com/product
© 2011 Moxa Inc. All rights reserved.
Reproduction without permission is prohibited.
ioLogik E1200 Series User’s Manual
The software described in this manual is furnished under a license agreement and may be used only in accordance with
the terms of that agreement.
Copyright Notice
Copyright ©2011 Moxa Inc.
All rights reserved.
Reproduction without permission is prohibited.
Trademarks
The MOXA logo is a registered trademark of Moxa Inc.
All other trademarks or registered marks in this manual belong to their respective manufacturers.
Disclaimer
Information in this document is subject to change without notice and does not represent a commitment on the part of
Moxa.
Moxa provides this document as is, without warranty of any kind, either expressed or implied, including, but not limited
to, its particular purpose. Moxa reserves the right to make improvements and/or changes to this manual, or to the
products and/or the programs described in this manual, at any time.
Information provided in this manual is intended to be accurate and reliable. However, Moxa assumes no responsibility for
its use, or for any infringements on the rights of third parties that may result from its use.
This product might include unintentional technical or typographical errors. Changes are periodically made to the
information herein to correct such errors, and these changes are incorporated into new editions of the publication.
Technical Support Contact Information
www.moxa.com/support
Moxa Americas
Toll-free: 1-888-669-2872
Tel: +1-714-528-6777
Fax: +1-714-528-6778
Moxa China (Shanghai office)
Toll-free: 800-820-5036
Tel: +86-21-5258-9955
Fax: +86-21-5258-5505
Moxa Europe
Tel: +49-89-3 70 03 99-0
Fax: +49-89-3 70 03 99-99
Moxa Asia-Pacific
Tel: +886-2-8919-1230
Fax: +886-2-8919-1231
Table of Contents
1. Introduction ...................................................................................................................................... 1-1 Product Model Information ................................................................................................................... 1-2 Product Features ................................................................................................................................ 1-2 Inside the Box .................................................................................................................................... 1-2 Product Specifications ......................................................................................................................... 1-3 Physical Dimensions ............................................................................................................................ 1-9 Hardware Reference .......................................................................................................................... 1-10
Panel Guide .............................................................................................................................. 1-10 LED Indicators .......................................................................................................................... 1-10
2. Initial Setup ...................................................................................................................................... 2-1 Hardware Installation .......................................................................................................................... 2-2
Connecting the Power .................................................................................................................. 2-2 Grounding the ioLogik E1200 ........................................................................................................ 2-2 Connecting to the Network ........................................................................................................... 2-2 Jumper Settings .......................................................................................................................... 2-3 I/O Wiring Diagrams .................................................................................................................... 2-3
Software Installation ........................................................................................................................... 2-5 Load Factory Defaults .......................................................................................................................... 2-5
3. Using the Web Console ...................................................................................................................... 3-1 Introduction to the Web Console ........................................................................................................... 3-2 Overview ........................................................................................................................................... 3-2 Network Settings ................................................................................................................................ 3-3
General Settings ......................................................................................................................... 3-3 Ethernet Configuration ................................................................................................................. 3-4
User-defined Modbus Addressing .......................................................................................................... 3-4 Default Address........................................................................................................................... 3-4
AOPC Server Settings .......................................................................................................................... 3-5 Tag Generation ................................................................................................................................... 3-5 I/O Settings ....................................................................................................................................... 3-6
DI Channels ................................................................................................................................ 3-6 DO Channels ............................................................................................................................... 3-7 AI Channels ................................................................................................................................ 3-8 AO Channels ............................................................................................................................. 3-10 RTD Channels ........................................................................................................................... 3-11 TC Channels ............................................................................................................................. 3-12
System Management ......................................................................................................................... 3-13 IP Accessibility .......................................................................................................................... 3-13 Network Connection................................................................................................................... 3-14 Firmware Update ....................................................................................................................... 3-14 Import System Configuration Settings ......................................................................................... 3-15 Export System Configuration Settings .......................................................................................... 3-15
Peer-to-peer Settings ........................................................................................................................ 3-15 Peer-to-peer Settings (1-50) ...................................................................................................... 3-15 Sample Configuration ................................................................................................................ 3-16 DO Safe Mode Settings .............................................................................................................. 3-16 AO Safe Mode Settings ............................................................................................................... 3-17
Change Password ............................................................................................................................. 3-17 Load Factory Defaults ........................................................................................................................ 3-17 Save/Restart .................................................................................................................................... 3-18
4. Using ioSearch .................................................................................................................................. 4-1 Introduction to ioSearch ...................................................................................................................... 4-2 ioSearch Main Screen .......................................................................................................................... 4-2
Main Screen Overview .................................................................................................................. 4-2 Main Items ........................................................................................................................................ 4-2
System ...................................................................................................................................... 4-2 Sort ........................................................................................................................................... 4-3 Quick Links ................................................................................................................................. 4-4
Main Function ..................................................................................................................................... 4-4 Locate ........................................................................................................................................ 4-4 Firmware Upgrade ....................................................................................................................... 4-4 Unlock ....................................................................................................................................... 4-5 Import ....................................................................................................................................... 4-5 Export ........................................................................................................................................ 4-6 Change IP Address ...................................................................................................................... 4-6 Batch TCP/IP Configuration on Multiple Devices ............................................................................... 4-6 Restart System ........................................................................................................................... 4-7 Reset to Default .......................................................................................................................... 4-8
Mass Deployment (Import) ........................................................................................................... 4-8 Mass Deployment (export) ........................................................................................................... 4-8
A. Modbus/TCP Default Address Mappings ............................................................................................ A-1 E1210 Modbus Mapping ....................................................................................................................... A-2 E1211 Modbus Mapping ....................................................................................................................... A-4 E1212 Modbus Mapping ....................................................................................................................... A-7 E1212 Modbus Mapping ..................................................................................................................... A-12 E1214 Modbus Mapping ..................................................................................................................... A-17 E1240 Modbus Mapping ..................................................................................................................... A-21 E1241 Modbus Mapping ..................................................................................................................... A-21 E1242 Modbus Mapping ..................................................................................................................... A-23 E1260 Modbus Mapping ..................................................................................................................... A-26 E1262 Modbus Mapping ..................................................................................................................... A-27
B. Network Port Numbers ...................................................................................................................... B-1 C. Factory Defaults ................................................................................................................................ C-1 D. Pinouts .............................................................................................................................................. D-1 E. FCC Interference Statement .............................................................................................................. E-1 F. European Community (CE) ................................................................................................................ F-1
1 1. Introduction
The ioLogik E1200 series is a stand-alone remote Ethernet I/O server that can connect sensors and on/off
switches for automation applications over Ethernet and IP-based networks.
The following topics are covered in this chapter:
Product Model Information
Product Features
Inside the Box
Product Specifications
Physical Dimensions
Hardware Reference
Panel Guide
LED Indicators
ioLogik E1200 Series Introduction
1-2
Product Model Information Model Description
ioLogik E1210 Remote Ethernet I/O with 2-port Ethernet switch and 16 DIs
ioLogik E1211 Remote Ethernet I/O with 2-port Ethernet switch and 16 DOs
ioLogik E1212 Remote Ethernet I/O with 2-port Ethernet switch, 8 DIs, and 8 DIOs
ioLogik E1214 Remote Ethernet I/O with 2-port Ethernet switch, 6 DIs, and 6 relays
ioLogik E1240 Remote Ethernet I/O with 2-port Ethernet switch and 8 AIs
ioLogik E1241 Remote Ethernet I/O with 2-port Ethernet switch and 4 AOs
ioLogik E1242 Remote Ethernet I/O with 2-port Ethernet switch and 4 AIs, 4DIs, and 4DIOs
ioLogik E1260 Remote Ethernet I/O with 2-port Ethernet switch and 6 RTDs
ioLogik E1262 Remote Ethernet I/O with 2-port Ethernet switch and 8 TCs
ioLogik E1210-T Ethernet remote I/O with 2-port Ethernet switch and 16 DIs, -40 to 75°C operating
temperature
ioLogik E1211-T Ethernet remote I/O with 2-port Ethernet switch and 16 DOs, -40 to 75°C operating
temperature
ioLogik E1212-T Ethernet remote I/O with 2-port Ethernet switch, 8 DIs, and 8 DIOs, -40 to 75°C
operating temperature
ioLogik E1214-T Ethernet remote I/O with 2-port Ethernet switch, 6 DIs, and 6 Relays, -40 to 75°C
operating temperature
ioLogik E1240-T Ethernet remote I/O with 2-port Ethernet switch and 8 AIs, -40 to 75°C operating
temperature
ioLogik E1241-T Ethernet remote I/O with 2-port Ethernet switch and 4 AOs , -40 to 75°C operating
temperature
ioLogik E1242-T Ethernet remote I/O with 2-port Ethernet switch, 4 AIs, 4 DIs, and 4 DIOs, -40 to 75°C
operating temperature
ioLogik E1260-T Ethernet remote I/O with 2-port Ethernet switch and 6 RTDs, -40 to 75°C operating
temperature
ioLogik E1262-T Ethernet remote I/O with 2-port Ethernet switch and 8 TCs, -40 to 75°C operating
temperature
Product Features • Built-in 2-port Ethernet switch for daisy-chain topologies.
• Free support of Moxa’s push-based Active OPC Server Lite.
Seamlessly connect to any SCADA system
Save 80% on network bandwidth
I/O response that’s seven times faster
• User-defined Modbus/TCP addressing
• MXIO programming library for Windows and WinCE VB/VC.NET and Linux C APIs
• Web configuration with Import/Export function
• Peer-to-peer transmission of I/O signals over Ethernet without controller
Inside the Box The ioLogik E1200 is shipped with the following items:
• ioLogik E1200 Remote Ethernet I/O Server.
• Document and Software CD.
• Quick Installation Guide.
NOTE: Notify your sales representative if any of the above items are missing or damaged.
ioLogik E1200 Series Introduction
1-3
Product Specifications
ioLogik E1210
Inputs and Outputs Digital Inputs: 16 channels
Isolation: 3K VDC or 2K Vrms
Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (NPN, DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Wet Contact (PNP, DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type: 8 points per COM
Isolation: 3K VDC or 2K Vrms
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption: 110 mA @ 24 VDC
MTBF (mean time between failures) Time: 671,345 hrs
Database: Telcordia (Bellcore)
ioLogik E1211
Inputs and Outputs Digital Outputs: 16 channels
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Digital Output Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption: 208 mA @ 24 VDC
ioLogik E1200 Series Introduction
1-4
MTBF (mean time between failures) Time: 221,662 hrs
Database: Telcordia (Bellcore)
ioLogik E1212
Inputs and Outputs Digital Inputs: 8 channels
Configurable DIOs: 8 channels
Isolation: 3K VDC or 2K Vrms
Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (NPN, DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Wet Contact (PNP, DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type: 8 points per COM
Isolation: 3K VDC or 2K Vrms
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Digital Output Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption: 155 mA @ 24 VDC
MTBF (mean time between failures) Time: 179,098 hrs
Database: Telcordia (Bellcore)
ioLogik E1214
Inputs and Outputs Digital Inputs: 6 channels
Relay Outputs: 6 channels
Isolation: 3K VDC or 2K Vrms
Digital Input Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
ioLogik E1200 Series Introduction
1-5
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (NPN, DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Wet Contact (PNP, DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type: 6 points per COM
Isolation: 3K VDC or 2K Vrms
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Relay Output Type: Form A (N.O.) power relay
Contact Current Rating:
• Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage: 500 VAC
Relay On/Off Time: 1500 ms (Max.)
Initial Insulation Resistance: 1000 M ohms (min.) @ 500 VDC
Mechanical Endurance: 5,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance: 100 m ohms (max.)
Pulse Output: 0.3 Hz at rated load
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption: 188 mA @ 24 VDC
MTBF (mean time between failures) Time: 808,744 hrs
Database: Telcordia (Bellcore)
ioLogik E1240
Inputs and Outputs Analog Inputs: 8 channels
Analog Input Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current
Input Range: 0 to 10 VDC, 4 to 20 mA
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate (all channels): 12 samples/sec
Input Impedance: 10M ohms (min.)
Built-in Resistor for Current Input: 120 ohms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
ioLogik E1200 Series Introduction
1-6
Power Requirements Power Consumption:121 mA @ 24 VDC
MTBF (mean time between failures) Time: 474,053 hrs
Database: Telcordia (Bellcore)
ioLogik E1241
Inputs and Outputs Analog Outputs: 4 channels
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Analog Output Resolution: 12 bits
Output Range: 0 to 10 VDC, 4 to 20 mA
Voltage Output: 10 mA (max.)
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Load Resistor:
• Internal power: 400 ohms
• External 24V power: 1000 ohms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption: 194 mA @ 24 VDC
MTBF (mean time between failures) Time: 888,656 hrs
Database: Telcordia (Bellcore)
ioLogik E1242
Inputs and Outputs Analog Inputs: 4 channels
Digital Inputs: 4 channels
Configurable DIOs: 4 channels
Analog Input Type: Differential input
Resolution: 16 bits
I/O Mode: Voltage / Current
Input Range: 0 to 10 VDC, 4 to 20 mA
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate (all channels): 12 samples/sec
Input Impedance: 10M ohms (min.)
Built-in Resistor for Current Input: 120 ohms
Isolation: 3K VDC or 2K Vrms
Digital Input
ioLogik E1200 Series Introduction
1-7
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (NPN, DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Wet Contact (PNP, DI to GND):
• Off: 0 to 3 VDC
• On: 10 to 30 VDC
Common Type: 4 points per COM
Isolation: 3K VDC or 2K Vrms
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Digital Output Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-voltage Protection: 45 VDC
Over-current Protection: 2.6 A (4 channels @ 650 mA)
Over-temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption:139 mA @ 24 VDC
MTBF (mean time between failures) Time: 502,210 hrs
Database: Telcordia (Bellcore)
ioLogik E1260
Inputs and Outputs RTD Inputs: 6 channels
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
RTD Inputs Input Type:
•PT50, PT100, PT200, PT500 (-200 to 850°C)
•PT1000 (-200 to 350°C)
•Resistance of 310, 620, 1250, and 2200 ohms
Sampling Rate: 12 samples/sec (all channels)
Resolution: 0.1°C or 0.1 ohm
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance: 625K ohms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
ioLogik E1200 Series Introduction
1-8
Power Requirements Power Consumption: 110 mA @ 24 VDC
MTBF (mean time between failures) Time: 660,260 hrs
Database: Telcordia (Bellcore)
ioLogik E1262
Inputs and Outputs Thermocouple Inputs: 8 channels
Isolation: 3K VDC or 2K Vrms
Thermocouple Input Sensor Type: J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C),
S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)
Millivolt Type:
• Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on)
Sampling Rate: 12 samples/sec (all channels)
Resolution: 16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance: 10M ohms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Isolation: 3K VDC or 2K Vrms
Power Requirements Power Consumption: 118 mA @ 24 VDC
MTBF (mean time between failures) Time: 631,418 hrs
Database: Telcordia (Bellcore)
Common Specifications
LAN Ethernet: 2 x 10/100 Mbps switch ports, RJ45
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, HTTP
Power Requirements Power Input: 24 VDC nominal, 12 to 36 VDC
Physical Characteristics Wiring: I/O cable max. 14 AWG
Dimensions: 27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight: under 200 g
Installation: Din-rail or wall mounting
Environmental Limits Operating Temperature:
Standard Models: -10 to 60°C (14 to 140°F)
Wide Temp. Models:-40 to 75°C (-40 to 167°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
ioLogik E1200 Series Introduction
1-9
Standards and Certifications Safety: UL 508
EMI:
EN 55022
EN 61000-3-2
EN 61000-3-3
FCC Part 15 Subpart B Class A
EN 55024
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-8
EN 61000-4-11
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Green Product: RoHS, CRoHS, WEEE
Note: Please check Moxa's website for the most up-to-date certification status.
Warranty Warranty Period: 5 years (excluding ioLogik E1214)
Details: See www.moxa.com/warranty
*Note: Because of the limited lifetime of power relays, products that use this component are covered by a
2-year warranty.
Physical Dimensions
Unit=mm
ioLogik E1200 Series Introduction
1-10
Hardware Reference
Panel Guide
NOTE The reset button restarts the server and resets all settings to factory defaults. Use a pointed object such as a
straightened paper clip to hold in the reset button for 5 sec. The factory defaults will be loaded once the Ready
LED turns green again. You may then release the reset button.
LED Indicators
LED State Description
Power Amber System power is ON
OFF System power is OFF
Ready Green System is ready
Flashing Flashes every 1 sec when the Locate function is triggered
Flashing Flashes every 0.5 sec when the firmware is being upgraded
Flashing Cycle on/off period of 0.5 sec. represents “Safe Mode”
OFF System is not ready.
Port 1 Green Ethernet connection enabled
Flashing Transmitting or receiving data
Port 2 Green Ethernet connection enabled
Flashing Transmitting or receiving data
2 2. Initial Setup
This chapter describes how to install the ioLogik E1200.
The following topics are covered in this chapter:
Hardware Installation
Connecting the Power
Grounding the ioLogik E1200
Connecting to the Network
Jumper Settings
I/O Wiring Diagrams
Software Installation
Load Factory Default
ioLogik E1200 Series Initial Setup
2-2
Hardware Installation
Connecting the Power
Connect the 12 to 36 VDC power line to the ioLogik E1200’s terminal block on the top panel. If power is properly
supplied, the Power LED will glow a solid amber color.
ATTENTION
Disconnect the power cord before installing or wiring your ioLogik E1200.
Do not exceed the maximum current for the wiring
Determine the maximum possible current for each power wire and common wire. Observe all electrical codes
dictating the maximum current allowable for each wire size. If the current exceeds the maximum rating, the
wiring could overheat, causing serious damage to your equipment. For safety reasons, the wires attached to
the power should be at least 2 mm in diameter.
Grounding the ioLogik E1200
The ioLogik E1200 is equipped with a grounding point on the terminal block located on the top panel.
Connect the ground pin ( ) if earth ground is available.
Connecting to the Network
The ioLogik E1200 has two built-in Ethernet switch ports for connecting a standard direct or cross-over
Ethernet cable from RJ45 port to either the host PC or another ioLogik E1200 device. For initial setup of the
ioLogik E1200, it is recommended that the ioLogik E1200 be configured using a direct connection to a host
computer rather than remotely over the network.
Configure the host PC’s IP address to 192.168.127.xxx (where xxx ranges from 001 to 253). When using
Windows, you will need to do the configuration from the Control Panel.
ioLogik E1200 Default IP Address Default Netmask Default Gateway
192.168.127.254 255.255.255.0 None
Use the web console or ioSearch configuration utility to connect to the ioLogik E1200. Once the ioLogik E1200
has been detected, modify the settings as needed for your network environment, and then restart the server.
Refer to Chapters 3 and 4 or further details.
ioLogik E1200 Series Initial Setup
2-3
Jumper Settings
The ioLogik E1212, E1240, and E1242 require configuring the jumpers inside the enclosure. Remove the screw
on the back panel and open the cover to configure the jumpers.
DIO mode configuration is as follows (default is DO Mode)
Analog mode configuration is as follows (default is Voltage Mode)
I/O Wiring Diagrams
ATTENTION
Remove the screw on the back panel and open the cover to configure the jumpers.
ioLogik E1200 Series Initial Setup
2-4
ioLogik E1200 Series Initial Setup
2-5
Software Installation ioSearch is a search utility that helps the user locate ioLogik E1200 devices on the local network. Find the
ioSearch utility in the Document and Software CD under Software ioSearch, or download the latest version
from Moxa’s website.
1. Installing from the CD: Insert the Document and Software CD into the host computer. In the root directory
of the CD, locate and run SETUP.EXE. The installation program will guide you through the installation
process and install the ioSearch utility. You can also install the MXIO DLL library separately.
2. Open ioSearch: After installation is finished, run ioSearch from Start Program Files MOXA IO Server
Utility ioSearch
3. Search the network for the server: On the menu bar, select System Auto Scan Active Ethernet I/O Server.
A dialog window will pop up. Click Start Search to begin searching for the ioLogik E1200.
If multiple ioLogik E1200 units are installed on the same network, remember that each unit has the same
default IP address. You will need to assign a different IP address to each unit to avoid IP conflicts.
Load Factory Defaults There are three ways to restore the ioLogik E1200 to the factory default.
1. Hold the RESET button for 5 seconds.
2. Right click the specified ioLogik in the ioSearch utility and select “Reset to Default”.
3. Select “Load Factory Default” from the web console.
3 3. Using the Web Console
The ioLogik E1200’s main configuration and management utility is the built-in web console, which can be used
to configure a wide range of options.
The following topics are covered in this chapter:
Introduction to the Web Console
Overview
Network Settings
General Settings
Ethernet Configuration
User-defined Modbus Addressing
User-defined Modbus Addressing
Default Address
AOPC Server Settings
I/O Settings
DI Channels
DO Channels
AI Channels
AO Channels
RTD Channels
TC Channels
System Management
IP Accessibility
Network Connection
Firmware Update
Import System Config
Export System Config
Peer-to-peer Settings
Peer-to-peer Settings (1-50)
Sample Configuration
DO Safe Mode Settings
AO Safe Mode Settings
Change Password
Load Factory Default
Save/Restart
ioLogik E1200 Series Using the Web Console
3-2
Introduction to the Web Console The ioLogik E1200 web console is a browser-based configuration utility. When the ioLogik E1200 is connected
to your network, you may enter the server’s IP address in your web browser to access the web console.
The left panel is the navigation panel and contains an expandable menu tree for navigating among the various
settings and categories. When you click on a menu item in the navigation panel, the main window will display
the corresponding options for that item. Configuration changes can then be made in the main window. For
example, if you click on Network Settings in the navigation panel, the main window will show a page of basic
settings that you can configure.
You must click on the Submit button after making configuration changes. The Submit button will be located
at the bottom of every page that has configurable settings. If you navigate to another page without clicking the
Submit button, your changes will not be retained.
Submitted changes will not take effect until they are saved and the ioLogik E1200 is restarted! You
may save and restart the server in one step by clicking on the Save/Restart button after you submit a change.
If you need to make several changes before restarting, you may save your changes without restarting by
selecting Save/Restart in the navigation panel. If you restart the ioLogik E1200 without saving your
configuration, the ioLogik E1200 will discard all submitted changes.
Overview The Overview page contains basic information about the ioLogik E1200, including the model name, serial
number, firmware version, MAC address, and current IP address. Most importantly, you can see the current I/O
status by hitting the F5 key on the computer keyboard to refresh the page.
ioLogik E1200 Series Using the Web Console
3-3
Network Settings
General Settings
On the General Settings page, you can assign a server name and location to assist you in differentiating
between different ioLogik E1200 units. You may also configure the Modbus/TCP idle interval or enable the
Communication Watchdog function.
The Communication Watchdog activates Safe Mode after a specified amount of time has passed following a loss
of network connectivity. Safe Mode is designed especially for products that have output channels to output a
suitable value or status when the ioLogik E1200 cannot be controlled by a remote PC (due to network failure,
for example). By default, the Watchdog is disabled. Users can configure how each output channel responds on
the I/O Settings page.
To enable the Watchdog, check Enable connection watchdog, set the timeout value, and then restart the
server. With Watchdog enabled, the ioLogik E1200 will enter Safe Mode after there is a disruption in
communication that exceeds the specified time limit.
For easier location of devices when troubleshooting, enable the remote control of LEDs on the E1200 series
devices by selecting "Enable I/O Locate," to allow remote toggling of the "Ready" LED from off to flashing.
ioLogik E1200 Series Using the Web Console
3-4
Ethernet Configuration
On the Ethernet Configuration page, you can set up a static or dynamic IP address for the ioLogik E1200, and
configure the subnet mask and gateway address.
User-defined Modbus Addressing The input and output address can be configured in a different format on a specific settings page. Check the
“Enable User-defined Modbus Addressing” box, select the Modbus function, and then configure the start
address of each item.
ATTENTION
Disable the user-defined modbus addressing function if using the MXIO(.NET) library or using Active OPC
Server to control or monitor the ioLogik E1200’s I/O Status.
Default Address
On this settings page, you can view the default Modbus address for all I/O devices. The page only displays the
start address of each item. For example, if the DI Value starts from 10001, then the 1st DI channel’s Modbus
address is 10001 and the 2nd DI is 10002.
ioLogik E1200 Series Using the Web Console
3-5
AOPC Server Settings Refer to Active OPC user's manual for details.
Tag Generation RTag configuration of an ioLogik E1200 is specified by its web console. Open the browser and go to the Active
OPC Server Settings page.
Follow these steps to create the tag from the ioLogik E1200 to Active OPC Server Lite:
In the AOPC & I/O Settings page,
Check the “Enable Active OPC” box and specify the IP address where the Active OPC Server Lite is installed.
Select the I/O channels that need to be created in the Active OPC Server Lite.
Configure the Heartbeat Interval, if necessary.
Click the “Submit” button and click the Save/Restart button on the next page.
On the Create AOPC Tag page, click on the Create Tags button to push the tag configuration to Active OPC
Server Lite.
ioLogik E1200 Series Using the Web Console
3-6
Launch the Active OPC Server Lite program; tags will be automatically created.
Save the configuration of the Active OPC Server Ltie when exiting the program.
I/O Settings
DI Channels
The status of each DI (digital input) channel appears on the DI Channels page.
You can also configure each channel’s digital input mode and parameters by clicking on the channel. DI
channels can operate in DI mode or Event Counter mode.
ioLogik E1200 Series Using the Web Console
3-7
For Event Counter mode, configure “Lo to Hi,” “Hi to Lo,” or “Both” to trigger the counter. The counter should
be set to either start, or stop. If it is in stop mode, the counter can be activated by the Modbus command.
Make sure that the Counter Filter is not set to 0; otherwise, the counter will never be activated.
The alias name and the logic definition can also be configured on this page.
DO Channels
On the DO Channels page, configure each DO (digital output) channel by clicking on the channel. DO Channels
can operate in DO mode or Pulse Output mode. In DO mode, output is either on or off. In Pulse Output mode,
configure the low width and high width to generate a square wave.
The Power On Setting field is used to specify the channel’s configuration when the ioLogik E1200 is powered
on, and the Safe Status Setting field specifies the channel’s configuration when the ioLogik E1200 enters Safe
Mode. Note that Safe Status is controlled by the Connection Watchdog, which is disabled by default. If the
Connection Watchdog is disabled, the ioLogik E1200 will never enter Safe Mode and your Safe Status settings
will have no effect.
ioLogik E1200 Series Using the Web Console
3-8
Users may also configure the alias name and the logic definition on this page.
ATTENTION
Remove the screw on the back panel and open the cover to configure the jumpers for input or output selection
of the DIO channels. Refer to chapter 2 for detailed jumper settings.
AI Channels
The current status of each AI (analog input) channel can be viewed on the AI Channels page.
Click on a specific channel to enable or disable the AI channel by checking the “Enable AI Channel” box. The
Auto Scaling and Slope-intercept function of the AI value can be defined on this page.
ioLogik E1200 Series Using the Web Console
3-9
ATTENTION
Remove the screw on the back panel and open the cover to configure the jumpers to select voltage or current
measurement for the AI channels. Refer to chapter 2 for detailed jumper settings.
The Auto scaling function maps the original AI value linearly to a scaled value. Note that the scaled value’s
Modbus address differs from the original value.
The slope-intercept function is used to compensate when the measurement requires a slight adjustment.
ioLogik E1200 Series Using the Web Console
3-10
AO Channels
The current status of each AO (analog output) channel can be viewed on the AO Channel page.
Click on a specific channel to access the AO channel settings, and then select the “Enable AO Channel” box.
The Auto Scaling function of the AO value can be defined on this page.
The Auto scaling function maps the original AO output linearly to a scaled value. Note that the scaled value’s
Modbus address differs from the original value.
ioLogik E1200 Series Using the Web Console
3-11
RTD Channels
The current status of each RTD (Resistance Temperature Detector) channel can be viewed on the RTD Channel
page.
Click on a specific channel to access the RTD channel settings.
Select the “Enable RTD Channel” box and then select the sensor type that meets the physical attachment to the
ioLogik E1200.
ioLogik E1200 Series Using the Web Console
3-12
The ioLogik E1200 allows you to calibrate the temperature sensors. In each channel configuration section,
follow the instructions and click Calibrate button to start the RTD sensor calibration. Each calibration requires
around 30 seconds (per channel).
The ioLogik E1200 allows you to manually adjust the current temperature reading. In each channel
configuration section, select the channel, apply the offset value, and click the “Submit” button to perform the
task.
TC Channels
The current status of each TC (Thermocouple) channel can be viewed on the TC Channel page.
ioLogik E1200 Series Using the Web Console
3-13
Click on a specific channel to access the enabling or disabling of the TC channel. Select the “Enable TC Channel”
box and then select the sensor type that meets the physical attachment to the ioLogik E1200.
The ioLogik E1200 allows you to calibrate the temperature sensors. In each channel configuration section,
follow the instructions and click the “Calibrate” button to start the TC sensor calibration. Each calibration
requires about 30 seconds (per channel).
The ioLogik E1200 allows you to manually adjust the current temperature reading. In each channel
configuration section, select the channel, apply the offset value, and click the “Submit” button to perform the
task.
System Management
IP Accessibility
You can control network access to the ioLogik E1200 from the IP Accessibility page by only allowing access from
specific IP addresses. When the accessible IP list is enabled, a host’s IP address must be listed in order to gain
access to the ioLogik E1200.
ioLogik E1200 Series Using the Web Console
3-14
Specify a range of addresses by using a combination of an IP address and netmask, as follows:
To allow access to a specific IP address
Enter the IP address in the corresponding field; enter 255.255.255.255 for the netmask.
To allow access to hosts on a specific subnet
For both the IP address and netmask, use 0 for the last digit (e.g., 192.168.1.0 and 255.255.255.0).
To allow unrestricted access
Deselect the Enable the accessible IP list option.
Refer to the following table for additional configuration examples.
Allowed Hosts IP address/Netmask
Any host Disable
192.168.1.120 192.168.1.120 / 255.255.255.255
192.168.1.1 to 192.168.1.254 192.168.1.0 / 255.255.255.0
192.168.0.1 to 192.168.255.254 192.168.0.0 / 255.255.0.0
192.168.1.1 to 192.168.1.126 192.168.1.0 / 255.255.255.128
192.168.1.129 to 192.168.1.254 192.168.1.128 / 255.255.255.128
Network Connection
TCP connections from other hosts appear on the Network Connection page. This information can assist you with
managing your devices.
Firmware Update
Load new or updated firmware onto the ioLogik from the Firmware Update page.
ioLogik E1200 Series Using the Web Console
3-15
Import System Configuration Settings
Import a configuration into the ioLogik server from the Import System Config page. This function can be used
to duplicate settings between ioLogik servers. You will be prompted for the location of the configuration file (i.e.,
“ik1212.txt”).
Export System Configuration Settings
On the Export System Config page, you can save the ioLogik’s configuration into a file for backup or import into
another ioLogik server.
Peer-to-peer Settings
Peer-to-peer Settings (1-50)
The ioLogik E1200 supports up to 50 peer-to-peer mapping rules. You can configure the channel settings 10 at
a time. To enable the rules, either select the Enable All box to enable all 10 channels, or select the Enable box
individually for each rule. The Local Channel drop-down menu allows you to specify the channel of the ioLogik
E1200 to configure. Type the IP address and port number of a remote ioLogik E1200 in the Remote IP and
Remote Ports fields, respectively. The Remote Channel field is for you to select input channels of the remote
ioLogik E1200 when you select output channels in the Local Channel field. Set the Interval Time and On
change percentage on the local ioLogik E1200 that will trigger the transmission of a mapping signal to the
remote ioLogik E1200. The default local listen port number is 9020; this value can be set between 1 to 65535.
NOTE If you select a DI or AI channel in the Local Channel field, the Remote Channel field will be disabled. You need
to configure the DO or AO channel on the remote ioLogik E1200.
ioLogik E1200 Series Using the Web Console
3-16
Sample Configuration
The following is an example of configuring DO (Server IP: 192.168.127.253) to DI (Client IP: 192.168.127.252)
peer-to-peer functionality with two ioLogik E1200 devices.
Server settings:
Client settings:
Note: refer to the table below for maximum number of rules supported at different signal frequencies.
1 Hz 2 Hz 4 Hz 10 Hz 20 Hz
1 rule
10 rules
20 rules
30 rules
40 rules
50 rules
DO Safe Mode Settings
When a peer-to-peer rule on a local DO channel is not valid, the local DO channel will enter safe mode. You can
set the DO to be Hold Last, ON, or OFF in safe mode.
ioLogik E1200 Series Using the Web Console
3-17
AO Safe Mode Settings
When a peer-to-peer rule of the local AO channel is not valid, the local AO channel will enter safe mode. You can
either set the AO safe value from 0-4095 or enable Hold Last Status during Safe Mode.
Change Password For all changes to the ioLogik E1200’s password protection settings, you will first need to enter the old
password. Leave this blank if you are setting up password protection for the first time. To set up a new
password or change the existing password, enter your desired password under both New password and
Confirm password. To remove password protection, leave the New password and Confirm password
fields blank.
ATTENTION
If you forget the password, the ONLY way to configure the ioLogik E1200 is by using the reset button to load
the factory defaults.
Before you set a password for the first time, it is a good idea to export the configuration to a file when you have
finished setting up your ioLogik E1200. Your configuration can then be easily imported back into the ioLogik
E1200 if you need to reset the ioLogik E1200 due to a forgotten password or for other reasons.
Load Factory Defaults This function will reset all of the ioLogik E1200’s settings to the factory default values. All previous settings,
including the console password will be lost.
ioLogik E1200 Series Using the Web Console
3-18
Save/Restart If you change the configuration, do not forget to reboot the system.
4 4. Using ioSearch
This chapter describes ioSearch, which is used to search for and locate ioLogik E1200 units.
The following topics are covered in this chapter:
Introduction to ioSearch
ioSearch Main Screen
Main Screen Overview
Main Items
System
Sort
Quick Links
Main Function
Locate
Firmware Upgrade
Unlock
Import
Export
Change IP Address
Restart System
Reset to Default
ioLogik E1200 Series Using ioSearch
4-2
Introduction to ioSearch ioSearch is for locating or searching for an Logik E1200 on the physical network. The following functions are
supported by the ioSearch utility.
• Search for and locate ioLogik E1200 units.
• IP address configuration.
• Firmware upgrade for multiple ioLogik E1200 units (same model).
• Export configuration files from multiple ioLogik E1200 units.
• Import a configuration file to multiple ioLogik E1200 units (same model).
• Reset to default for multiple ioLogik E1200 units.
ioSearch Main Screen
Main Screen Overview
The main screen displays the result of the broadcast search of the ioLogik E1200.
ioSearch Main Screen
1. Title
2. Menu bar
3. Quick link
4. Navigation panel
5. Main window
Main Items
System
Several operations are possible from the System menu.
Auto Scan Active Ethernet I/O Servers will search for ioLogik servers on the network. When connecting for
the first time or recovering from a network disconnection, you can use this command to find I/O servers that
are on the network.
1
2
4
5 3
ioLogik E1200 Series Using ioSearch
4-3
Network Interface allows you to select a network to use, if the PC has multiple network adaptors installed.
Sort
The Sort menu allows the server list in the navigation panel to be sorted by ioLogik connection and server
(model).
ioLogik E1200 Series Using ioSearch
4-4
Quick Links
Quick links are provided to search for I/O servers on the network and sort the server list.
1 Automatically search the local network
2 Sort by ioLogik E1200’s IP address (connection)
3 Sort by ioLogik E1200 model
4 Locate an ioLogik E1200
5 Upgrade Firmware
6 Import settings
7 Export settings
8 Unlock an ioLogik E1200 which is password protected
9 Change IP Address of an ioLogik E1200
Main Function Right click on a particular ioLogik E1200 to view the ioSearch function menu.
Locate
The locate function helps users find a dedicated ioLogik on the network. When this function is triggered, the
ready LED on the selected unit will start to blink indicating its location.
Firmware Upgrade
The ioLogik E1200 supports a remote firmware upgrade function. Enter the path to the firmware file or click on
the icon to browse for the file. The wizard will lead you through the process until the server is restarted.
ioLogik E1200 Series Using ioSearch
4-5
Batch Upgrades on Multiple Devices of the Same Model
Batch firmware upgrades are possible on multiple devices of the same ioLogik model. To upgrade multiple models, press the “Shift” key, select “ioLogik”, and right click to process multiple firmware upgrades.
ATTENTION
Do not interrupt the firmware update process! An interruption in the process may result in your device
becoming unrecoverable.
Unlock
If an ioLogik E1200 is password protected, unlock the ioLogik E1200 by entering the password before using any
of the functions.
Import
Select this command to reload a configuration that was exported to a text file.
Importing one configuration file to multiple ioLogik E1200 units (same model) is allowed. To do this, press the
“Shift” key, select “ioLogik”, and then right click.
ioLogik E1200 Series Using ioSearch
4-6
Export
The export function is used to export the current configuration file of an ioLogik E1200. The export file format
will be ik12xx.txt where “xx” represents the model type of the ioLogik E1200.
Exporting multiple files for different models of ioLogik E1200 is allowed. The file format is ik12xx_MAC
Address.txt, where the xx represents the model types of the ioLogik E1200.
e.g., ik1214_00-90-E8-66-32-19.txt
To export multiple configuration files, select the ioLogik and right click to process this function.
Change IP Address
The Change IP Address function can be used to directly modify the IP Address, especially for first time
installation.
Changing the IP address for multiple ioLogik E1200’s is allowed. Select the ioLogik E1200 and then right click
to process this function.
Batch TCP/IP Configuration on Multiple Devices
Users can batch modify IP addresses, subnet masks, and gateways for devices of the same model from a single
window while submitting the changes at one time. First, select several devices of the same model, click the
right mouse button, and then click “Change IP Address” in the pop-up menu to launch a new window.
ioLogik E1200 Series Using ioSearch
4-7
The following screenshot shows the window used to modify IP addresses, subnet masks, and gateways. Users
can modify each item and click “Set” to confirm the modification, or click the “Advance” button to automatically
assign IP addresses incrementally.
After the “Advance” button is clicked, a window will pop up to allow users to use ioSearch to set the IP address
by MAC address. ioSearch will automatically set sequential IP addresses on the selected devices, with the
subnet mask and gateway set to the same value.
Restart System
Select this command to restart the selected ioLogik E1200.
Restarting multiple ioLogik E1200 units is allowed. Select the ioLogik E1200 and right click to process this
function.
ioLogik E1200 Series Using ioSearch
4-8
Reset to Default
Select this function to reset all settings, including console password, to factory default values.
Resetting multiple ioLogik E1200 units to the default configuration is allowed. Select the ioLogik E1200 and
right click to process this function.
Mass Deployment (Import)
Users can import E1200 series module information via ioSearch. Select this command to reload a configuration
from an exported .CSV file.
Mass Deployment (export)
Users can export E1200 series module information via ioSearch. The export file format will be
E1200_Series_List.
ioLogik E1200 Series Using ioSearch
4-9
A A. Modbus/TCP Default Address Mappings
The following topics are covered in this appendix:
E1210 Modbus Mapping
E1211 Modbus Mapping
E1212 Modbus Mapping
E1214 Modbus Mapping
E1240 Modbus Mapping
E1241 Modbus Mapping
E1242 Modbus Mapping
E1260 Modbus Mapping
E1262 Modbus Mapping
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
NOTE The Modbus/TCP ID of the ioLogik E1200 is set to “1” by default.
E1210 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
00257 0x0100 1 bit CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
00258 0x0101 1 bit CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
00259 0x0102 1 bit CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
00260 0x0103 1 bit CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
00261 0x0104 1 bit CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
00262 0x0105 1 bit CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
00263 0x0106 1 bit CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
00264 0x0107 1 bit CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
00265 0x0108 1 bit CH8 DI Counter Operate Status 0: Stop 1: Start(R/W)
00266 0x0109 1 bit CH9 DI Counter Operate Status 0: Stop 1: Start(R/W)
00267 0x010A 1 bit CH10 DI Counter Operate Status 0: Stop 1: Start(R/W)
00268 0x010B 1 bit CH11 DI Counter Operate Status 0: Stop 1: Start(R/W)
00269 0x010C 1 bit CH12 DI Counter Operate Status 0: Stop 1: Start(R/W)
00270 0x010D 1 bit CH13 DI Counter Operate Status 0: Stop 1: Start(R/W)
00271 0x010E 1 bit CH14 DI Counter Operate Status 0: Stop 1: Start(R/W)
00272 0x010F 1 bit CH15 DI Counter Operate Status 0: Stop 1: Start(R/W)
00273 0x0110 1 bit CH0 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00274 0x0111 1 bit CH1 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00275 0x0112 1 bit CH2 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00276 0x0113 1 bit CH3 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00277 0x0114 1 bit CH4 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00278 0x0115 1 bit CH5 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00279 0x0116 1 bit CH6 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
0 : Return illegal data value(0x03)
00280 0x0117 1 bit CH7 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00281 0x0118 1 bit CH8 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00282 0x0119 1 bit CH9 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00283 0x011A 1 bit CH10 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00284 0x011B 1 bit CH11 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00285 0x011C 1 bit CH12 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00286 0x011D 1 bit CH13 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00287 0x011E 1 bit CH14 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00288 0x011F 1 bit CH15 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
10001 0x0000 1 bit CH0 DI Value,0=OFF,1=ON (Read only)
10002 0x0001 1 bit CH1 DI Value,0=OFF,1=ON (Read only)
10003 0x0002 1 bit CH2 DI Value,0=OFF,1=ON (Read only)
10004 0x0003 1 bit CH3 DI Value,0=OFF,1=ON (Read only)
10005 0x0004 1 bit CH4 DI Value,0=OFF,1=ON (Read only)
10006 0x0005 1 bit CH5 DI Value,0=OFF,1=ON (Read only)
10007 0x0006 1 bit CH6 DI Value,0=OFF,1=ON (Read only)
10008 0x0007 1 bit CH7 DI Value,0=OFF,1=ON (Read only)
10009 0x0008 1 bit CH8 DI Value,0=OFF,1=ON (Read only)
10010 0x0009 1 bit CH9 DI Value,0=OFF,1=ON (Read only)
10011 0x000A 1 bit CH10 DI Value,0=OFF,1=ON (Read only)
10012 0x000B 1 bit CH11 DI Value,0=OFF,1=ON (Read only)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
10013 0x000C 1 bit CH12 DI Value,0=OFF,1=ON (Read only)
10014 0x000D 1 bit CH13 DI Value,0=OFF,1=ON (Read only)
10015 0x000E 1 bit CH14 DI Value,0=OFF,1=ON (Read only)
10016 0x000F 1 bit CH15 DI Value,0=OFF,1=ON (Read only)
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30017 0x0010 1 word CH0 DI Counter Value Hi- Word (Read only)
30018 0x0011 1 word CH0 DI Counter Value Lo- Word (Read only)
30019 0x0012 1 word CH1 DI Counter Value Hi- Word (Read only)
30020 0x0013 1 word CH1 DI Counter Value Lo- Word (Read only)
30021 0x0014 1 word CH2 DI Counter Value Hi- Word (Read only)
30022 0x0015 1 word CH2 DI Counter Value Lo- Word (Read only)
30023 0x0016 1 word CH3 DI Counter Value Hi- Word (Read only)
30024 0x0017 1 word CH3 DI Counter Value Lo- Word (Read only)
30025 0x0018 1 word CH4 DI Counter Value Hi- Word (Read only)
30026 0x0019 1 word CH4 DI Counter Value Lo- Word (Read only)
30027 0x001A 1 word CH5 DI Counter Value Hi- Word (Read only)
30028 0x001B 1 word CH5 DI Counter Value Lo- Word (Read only)
30029 0x001C 1 word CH6 DI Counter Value Hi- Word (Read only)
30030 0x001D 1 word CH6 DI Counter Value Lo- Word (Read only)
30031 0x001E 1 word CH7 DI Counter Value Hi- Word (Read only)
30032 0x001F 1 word CH7 DI Counter Value Lo- Word (Read only)
30033 0x0020 1 word CH8 DI Counter Value Hi- Word (Read only)
30034 0x0021 1 word CH8 DI Counter Value Lo- Word (Read only)
30035 0x0022 1 word CH9 DI Counter Value Hi- Word (Read only)
30036 0x0023 1 word CH9 DI Counter Value Lo- Word (Read only)
30037 0x0024 1 word CH10 DI Counter Value Hi- Word (Read only)
30038 0x0025 1 word CH10 DI Counter Value Lo- Word (Read only)
30039 0x0026 1 word CH11 DI Counter Value Hi- Word (Read only)
30040 0x0027 1 word CH11 DI Counter Value Lo- Word (Read only)
30041 0x0028 1 word CH12 DI Counter Value Hi- Word (Read only)
30042 0x0029 1 word CH12 DI Counter Value Lo- Word (Read only)
30043 0x002A 1 word CH13 DI Counter Value Hi- Word (Read only)
30044 0x002B 1 word CH13 DI Counter Value Lo- Word (Read only)
30045 0x002C 1 word CH14 DI Counter Value Hi- Word (Read only)
30046 0x002D 1 word CH14 DI Counter Value Lo- Word (Read only)
30047 0x002E 1 word CH15 DI Counter Value Hi- Word (Read only)
30048 0x002F 1 word CH15 DI Counter Value Lo- Word (Read only)
30049 0x0030 1 word DI Value (Ch0~15)
Bit0 = Ch0 DI Value (0=OFF, 1=ON)
………
Bit15 = Ch15 DI Value (0=OFF, 1=ON)
E1211 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
00001 0x0000 1 bit CH0 DO Value 0: Off 1: On
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
00002 0x0001 1 bit CH1 DO Value 0: Off 1: On
00003 0x0002 1 bit CH2 DO Value 0: Off 1: On
00004 0x0003 1 bit CH3 DO Value 0: Off 1: On
00005 0x0004 1 bit CH4 DO Value 0: Off 1: On
00006 0x0005 1 bit CH5 DO Value 0: Off 1: On
00007 0x0006 1 bit CH6 DO Value 0: Off 1: On
00008 0x0007 1 bit CH7 DO Value 0: Off 1: On
00009 0x0008 1 bit CH8 DO Value 0: Off 1: On
00010 0x0009 1 bit CH9 DO Value 0: Off 1: On
00011 0x000A 1 bit CH10 DO Value 0: Off 1: On
00012 0x000B 1 bit CH11 DO Value 0: Off 1: On
00013 0x000C 1 bit CH12 DO Value 0: Off 1: On
00014 0x000D 1 bit CH13 DO Value 0: Off 1: On
00015 0x000E 1 bit CH14 DO Value 0: Off 1: On
00016 0x000F 1 bit CH15 DO Value 0: Off 1: On
00017 0x0010 1 bit CH0 DO Pulse Operate Status 0: Off 1: On
00018 0x0011 1 bit CH1 DO Pulse Operate Status 0: Off 1: On
00019 0x0012 1 bit CH2 DO Pulse Operate Status 0: Off 1: On
00020 0x0013 1 bit CH3 DO Pulse Operate Status 0: Off 1: On
00021 0x0014 1 bit CH4 DO Pulse Operate Status 0: Off 1: On
00022 0x0015 1 bit CH5 DO Pulse Operate Status 0: Off 1: On
00023 0x0016 1 bit CH6 DO Pulse Operate Status 0: Off 1: On
00024 0x0017 1 bit CH7 DO Pulse Operate Status 0: Off 1: On
00025 0x0018 1 bit CH8 DO Pulse Operate Status 0: Off 1: On
00026 0x0019 1 bit CH9 DO Pulse Operate Status 0: Off 1: On
00027 0x001A 1 bit CH10 DO Pulse Operate Status 0: Off 1: On
00028 0x001B 1 bit CH11 DO Pulse Operate Status 0: Off 1: On
00029 0x001C 1 bit CH12 DO Pulse Operate Status 0: Off 1: On
00030 0x001D 1 bit CH13 DO Pulse Operate Status 0: Off 1: On
00031 0x001E 1 bit CH14 DO Pulse Operate Status 0: Off 1: On
00032 0x001F 1 bit CH15 DO Pulse Operate Status 0: Off 1: On
04097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04101 0x1004 1Bit CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04102 0x1005 1Bit CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04103 0x1006 1Bit CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04104 0x1007 1Bit CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04105 0x1008 1Bit CH8 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04106 0x1009 1Bit CH9 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04107 0x100A 1Bit CH10 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04108 0x100B 1Bit CH11 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04109 0x100C 1Bit CH12 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04110 0x100D 1Bit CH13 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04111 0x100E 1Bit CH14 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04112 0x100F 1Bit CH15 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04117 0x1014 1Bit CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04118 0x1015 1Bit CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
04119 0x1016 1Bit CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04120 0x1017 1Bit CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04121 0x1018 1Bit CH8 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04122 0x1019 1Bit CH9 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04123 0x101A 1Bit CH10 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04124 0x101B 1Bit CH11 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04125 0x101C 1Bit CH12 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04126 0x101D 1Bit CH13 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04127 0x101E 1Bit CH14 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04128 0x101F 1Bit CH15 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04129 0x1020 1Bit CH0 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04130 0x1021 1Bit CH1 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04131 0x1022 1Bit CH2 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04132 0x1023 1Bit CH3 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04133 0x1024 1Bit CH4 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04134 0x1025 1Bit CH5 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04135 0x1026 1Bit CH6 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04136 0x1027 1Bit CH7 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04137 0x1028 1Bit CH8 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04138 0x1029 1Bit CH9 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04139 0x102A 1Bit CH10 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04140 0x102B 1Bit CH11 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04141 0x102C 1Bit CH12 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04142 0x102D 1Bit CH13 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04143 0x102E 1Bit CH14 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04144 0x102F 1Bit CH15 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
E1212 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
DO Channel
00001 0x0000 1 bit CH0 DO Value 0: Off 1: On
00002 0x0001 1 bit CH1 DO Value 0: Off 1: On
00003 0x0002 1 bit CH2 DO Value 0: Off 1: On
00004 0x0003 1 bit CH3 DO Value 0: Off 1: On
00005 0x0004 1 bit CH4 DO Value 0: Off 1: On
00006 0x0005 1 bit CH5 DO Value 0: Off 1: On
00007 0x0006 1 bit CH6 DO Value 0: Off 1: On
00008 0x0007 1 bit CH7 DO Value 0: Off 1: On
00017 0x0010 1 bit CH0 DO Pulse Operate Status 0: Off 1: On
00018 0x0011 1 bit CH1 DO Pulse Operate Status 0: Off 1: On
00019 0x0012 1 bit CH2 DO Pulse Operate Status 0: Off 1: On
00020 0x0013 1 bit CH3 DO Pulse Operate Status 0: Off 1: On
00021 0x0014 1 bit CH4 DO Pulse Operate Status 0: Off 1: On
00022 0x0015 1 bit CH5 DO Pulse Operate Status 0: Off 1: On
00023 0x0016 1 bit CH6 DO Pulse Operate Status 0: Off 1: On
00024 0x0017 1 bit CH7 DO Pulse Operate Status 0: Off 1: On
DI Channel
00257 0x0100 1 bit CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
00258 0x0101 1 bit CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
00259 0x0102 1 bit CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
00260 0x0103 1 bit CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
00261 0x0104 1 bit CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
00262 0x0105 1 bit CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
00263 0x0106 1 bit CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
00264 0x0107 1 bit CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
00265 0x0108 1 bit CH8 DI Counter Operate Status 0: Stop 1: Start(R/W)
00266 0x0109 1 bit CH9 DI Counter Operate Status 0: Stop 1: Start(R/W)
00267 0x010A 1 bit CH10 DI Counter Operate Status 0: Stop 1: Start(R/W)
00268 0x010B 1 bit CH11 DI Counter Operate Status 0: Stop 1: Start(R/W)
00269 0x010C 1 bit CH12 DI Counter Operate Status 0: Stop 1: Start(R/W)
00270 0x010D 1 bit CH13 DI Counter Operate Status 0: Stop 1: Start(R/W)
00271 0x010E 1 bit CH14 DI Counter Operate Status 0: Stop 1: Start(R/W)
00272 0x010F 1 bit CH15 DI Counter Operate Status 0: Stop 1: Start(R/W)
00273 0x0110 1 bit CH0 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00274 0x0111 1 bit CH1 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00275 0x0112 1 bit CH2 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
00276 0x0113 1 bit CH3 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00277 0x0114 1 bit CH4 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00278 0x0115 1 bit CH5 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00279 0x0116 1 bit CH6 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00280 0x0117 1 bit CH7 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00281 0x0118 1 bit CH8 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00282 0x0119 1 bit CH9 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00283 0x011A 1 bit CH10 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00284 0x011B 1 bit CH11 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00285 0x011C 1 bit CH12 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00286 0x011D 1 bit CH13 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00287 0x011E 1 bit CH14 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00288 0x011F 1 bit CH15 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
14097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14101 0x1004 1Bit CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14102 0x1005 1Bit CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14103 0x1006 1Bit CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14104 0x1007 1Bit CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14105 0x1008 1Bit CH8 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14106 0x1009 1Bit CH9 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14107 0x100A 1Bit CH10 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14108 0x100B 1Bit CH11 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14109 0x100C 1Bit CH12 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14110 0x100D 1Bit CH13 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14111 0x100E 1Bit CH14 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14112 0x100F 1Bit CH15 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14117 0x1014 1Bit CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14118 0x1015 1Bit CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14119 0x1016 1Bit CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14120 0x1017 1Bit CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14121 0x1018 1Bit CH8 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14122 0x1019 1Bit CH9 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14123 0x101A 1Bit CH10 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14124 0x101B 1Bit CH11 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14125 0x101C 1Bit CH12 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14126 0x101D 1Bit CH13 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14127 0x101E 1Bit CH14 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14128 0x101F 1Bit CH15 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
34097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34103 0x1006 1word CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34104 0x1007 1word CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34105 0x1008 1word CH8 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34106 0x1009 1word CH9 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34107 0x100A 1word CH10 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34108 0x100B 1word CH11 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34109 0x100C 1word CH12 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
34110 0x100D 1word CH13 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34111 0x100E 1word CH14 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34112 0x100F 1word CH15 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34119 0x1016 1word CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34120 0x1017 1word CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34121 0x1018 1word CH8 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34122 0x1019 1word CH9 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34123 0x101A 1word CH10 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34124 0x101B 1word CH11 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34125 0x101C 1word CH12 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34126 0x101D 1word CH13 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34127 0x101E 1word CH14 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34128 0x101F 1word CH15 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
44097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44103 0x1006 1word CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44104 0x1007 1word CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44105 0x1008 1word CH8 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44106 0x1009 1word CH9 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44107 0x100A 1word CH10 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44108 0x100B 1word CH11 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44109 0x100C 1word CH12 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44110 0x100D 1word CH13 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44111 0x100E 1word CH14 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44112 0x100F 1word CH15 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44119 0x1016 1word CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44120 0x1017 1word CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44121 0x1018 1word CH8 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44122 0x1019 1word CH9 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44123 0x101A 1word CH10 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44124 0x101B 1word CH11 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44125 0x101C 1word CH12 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
44126 0x101D 1word CH13 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44127 0x101E 1word CH14 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44128 0x101F 1word CH15 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44129 0x1020 1word CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44130 0x1021 1word CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44131 0x1022 1word CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44132 0x1023 1word CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44133 0x1024 1word CH4 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44134 0x1025 1word CH5 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44135 0x1026 1word CH6 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44136 0x1027 1word CH7 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44137 0x1028 1word CH8 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44138 0x1029 1word CH9 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44139 0x102A 1word CH10 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44140 0x102B 1word CH11 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44141 0x102C 1word CH12 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44142 0x102D 1word CH13 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44143 0x102E 1word CH14 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44144 0x102F 1word CH15 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
E1212 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
DO Channel
00001 0x0000 1 bit CH0 DO Value 0: Off 1: On
00002 0x0001 1 bit CH1 DO Value 0: Off 1: On
00003 0x0002 1 bit CH2 DO Value 0: Off 1: On
00004 0x0003 1 bit CH3 DO Value 0: Off 1: On
00005 0x0004 1 bit CH4 DO Value 0: Off 1: On
00006 0x0005 1 bit CH5 DO Value 0: Off 1: On
00007 0x0006 1 bit CH6 DO Value 0: Off 1: On
00008 0x0007 1 bit CH7 DO Value 0: Off 1: On
00017 0x0010 1 bit CH0 DO Pulse Operate Status 0: Off 1: On
00018 0x0011 1 bit CH1 DO Pulse Operate Status 0: Off 1: On
00019 0x0012 1 bit CH2 DO Pulse Operate Status 0: Off 1: On
00020 0x0013 1 bit CH3 DO Pulse Operate Status 0: Off 1: On
00021 0x0014 1 bit CH4 DO Pulse Operate Status 0: Off 1: On
00022 0x0015 1 bit CH5 DO Pulse Operate Status 0: Off 1: On
00023 0x0016 1 bit CH6 DO Pulse Operate Status 0: Off 1: On
00024 0x0017 1 bit CH7 DO Pulse Operate Status 0: Off 1: On
04097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04101 0x1004 1Bit CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04102 0x1005 1Bit CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04103 0x1006 1Bit CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04104 0x1007 1Bit CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04117 0x1014 1Bit CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04118 0x1015 1Bit CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04119 0x1016 1Bit CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04120 0x1017 1Bit CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04129 0x1020 1Bit CH0 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04130 0x1021 1Bit CH1 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04131 0x1022 1Bit CH2 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04132 0x1023 1Bit CH3 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04133 0x1024 1Bit CH4 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04134 0x1025 1Bit CH5 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
04135 0x1026 1Bit CH6 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
04136 0x1027 1Bit CH7 DO Clear P2P Output Safe Status Write: 1= clear status
Read: always zero
DI Channel
00257 0x0100 1 bit CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
00258 0x0101 1 bit CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
00259 0x0102 1 bit CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
00260 0x0103 1 bit CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
00261 0x0104 1 bit CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
00262 0x0105 1 bit CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
00263 0x0106 1 bit CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
00264 0x0107 1 bit CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
00265 0x0108 1 bit CH8 DI Counter Operate Status 0: Stop 1: Start(R/W)
00266 0x0109 1 bit CH9 DI Counter Operate Status 0: Stop 1: Start(R/W)
00267 0x010A 1 bit CH10 DI Counter Operate Status 0: Stop 1: Start(R/W)
00268 0x010B 1 bit CH11 DI Counter Operate Status 0: Stop 1: Start(R/W)
00269 0x010C 1 bit CH12 DI Counter Operate Status 0: Stop 1: Start(R/W)
00270 0x010D 1 bit CH13 DI Counter Operate Status 0: Stop 1: Start(R/W)
00271 0x010E 1 bit CH14 DI Counter Operate Status 0: Stop 1: Start(R/W)
00272 0x010F 1 bit CH15 DI Counter Operate Status 0: Stop 1: Start(R/W)
00273 0x0110 1 bit CH0 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00274 0x0111 1 bit CH1 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00275 0x0112 1 bit CH2 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00276 0x0113 1 bit CH3 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00277 0x0114 1 bit CH4 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00278 0x0115 1 bit CH5 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00279 0x0116 1 bit CH6 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00280 0x0117 1 bit CH7 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
00281 0x0118 1 bit CH8 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00282 0x0119 1 bit CH9 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00283 0x011A 1 bit CH10 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00284 0x011B 1 bit CH11 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00285 0x011C 1 bit CH12 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00286 0x011D 1 bit CH13 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00287 0x011E 1 bit CH14 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00288 0x011F 1 bit CH15 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
10001 0x0000 1 bit CH0 DI Value,0=OFF,1=ON (Read only)
10002 0x0001 1 bit CH1 DI Value,0=OFF,1=ON (Read only)
10003 0x0002 1 bit CH2 DI Value,0=OFF,1=ON (Read only)
10004 0x0003 1 bit CH3 DI Value,0=OFF,1=ON (Read only)
10005 0x0004 1 bit CH4 DI Value,0=OFF,1=ON (Read only)
10006 0x0005 1 bit CH5 DI Value,0=OFF,1=ON (Read only)
10007 0x0006 1 bit CH6 DI Value,0=OFF,1=ON (Read only)
10008 0x0007 1 bit CH7 DI Value,0=OFF,1=ON (Read only)
10009 0x0008 1 bit CH8 DI Value,0=OFF,1=ON (Read only)
10010 0x0009 1 bit CH9 DI Value,0=OFF,1=ON (Read only)
10011 0x000A 1 bit CH10 DI Value,0=OFF,1=ON (Read only)
10012 0x000B 1 bit CH11 DI Value,0=OFF,1=ON (Read only)
10013 0x000C 1 bit CH12 DI Value,0=OFF,1=ON (Read only)
10014 0x000D 1 bit CH13 DI Value,0=OFF,1=ON (Read only)
10015 0x000E 1 bit CH14 DI Value,0=OFF,1=ON (Read only)
10016 0x000F 1 bit CH15 DI Value,0=OFF,1=ON (Read only)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
14097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14101 0x1004 1Bit CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14102 0x1005 1Bit CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14103 0x1006 1Bit CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14104 0x1007 1Bit CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14117 0x1014 1Bit CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14118 0x1015 1Bit CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14119 0x1016 1Bit CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14120 0x1017 1Bit CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34103 0x1006 1word CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34104 0x1007 1word CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34119 0x1016 1word CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34120 0x1017 1word CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30018 0x0011 1 word CH0 DI Counter Value Lo- Word (Read only)
30019 0x0012 1 word CH1 DI Counter Value Hi- Word (Read only)
30020 0x0013 1 word CH1 DI Counter Value Lo- Word (Read only)
30021 0x0014 1 word CH2 DI Counter Value Hi- Word (Read only)
30022 0x0015 1 word CH2 DI Counter Value Lo- Word (Read only)
30023 0x0016 1 word CH3 DI Counter Value Hi- Word (Read only)
30024 0x0017 1 word CH3 DI Counter Value Lo- Word (Read only)
30025 0x0018 1 word CH4 DI Counter Value Hi- Word (Read only)
30026 0x0019 1 word CH4 DI Counter Value Lo- Word (Read only)
30027 0x001A 1 word CH5 DI Counter Value Hi- Word (Read only)
30028 0x001B 1 word CH5 DI Counter Value Lo- Word (Read only)
30029 0x001C 1 word CH6 DI Counter Value Hi- Word (Read only)
30030 0x001D 1 word CH6 DI Counter Value Lo- Word (Read only)
30031 0x001E 1 word CH7 DI Counter Value Hi- Word (Read only)
30032 0x001F 1 word CH7 DI Counter Value Lo- Word (Read only)
30033 0x0020 1 word CH8 DI Counter Value Hi- Word (Read only)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
30034 0x0021 1 word CH8 DI Counter Value Lo- Word (Read only)
30035 0x0022 1 word CH9 DI Counter Value Hi- Word (Read only)
30036 0x0023 1 word CH9 DI Counter Value Lo- Word (Read only)
30037 0x0024 1 word CH10 DI Counter Value Hi- Word (Read only)
30038 0x0025 1 word CH10 DI Counter Value Lo- Word (Read only)
30039 0x0026 1 word CH11 DI Counter Value Hi- Word (Read only)
30040 0x0027 1 word CH11 DI Counter Value Lo- Word (Read only)
30041 0x0028 1 word CH12 DI Counter Value Hi- Word (Read only)
30042 0x0029 1 word CH12 DI Counter Value Lo- Word (Read only)
30043 0x002A 1 word CH13 DI Counter Value Hi- Word (Read only)
30044 0x002B 1 word CH13 DI Counter Value Lo- Word (Read only)
30045 0x002C 1 word CH14 DI Counter Value Hi- Word (Read only)
30046 0x002D 1 word CH14 DI Counter Value Lo- Word (Read only)
30047 0x002E 1 word CH15 DI Counter Value Hi- Word (Read only)
30048 0x002F 1 word CH15 DI Counter Value Lo- Word (Read only)
30049 0x0030 1 word DI Value (Ch0~15)
Bit0 = Ch0 DI Value (0=OFF, 1=ON)
………
Bit15 = Ch15 DI Value (0=OFF, 1=ON)
34097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34103 0x1006 1word CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34104 0x1007 1word CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34119 0x1016 1word CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34120 0x1017 1word CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
DO Channel
40033 0x0020 1 word DO all Value (Ch0~15)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
………
Bit15 = Ch15 DO Value (0=OFF, 1=ON)
44097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44103 0x1006 1word CH6 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44104 0x1007 1word CH7 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
44114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44119 0x1016 1word CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44120 0x1017 1word CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44129 0x1020 1word CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44130 0x1021 1word CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44131 0x1022 1word CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44132 0x1023 1word CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44133 0x1024 1word CH4 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44134 0x1025 1word CH5 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44135 0x1026 1word CH6 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44136 0x1027 1word CH7 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
E1214 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
DO Channel
00001 0x0000 1 bit CH0 DO Value 0: Off 1: On
00002 0x0001 1 bit CH1 DO Value 0: Off 1: On
00003 0x0002 1 bit CH2 DO Value 0: Off 1: On
00004 0x0003 1 bit CH3 DO Value 0: Off 1: On
00005 0x0004 1 bit CH4 DO Value 0: Off 1: On
00006 0x0005 1 bit CH5 DO Value 0: Off 1: On
00017 0x0010 1 bit CH0 DO Pulse Operate Status 0: Off 1: On
00018 0x0011 1 bit CH1 DO Pulse Operate Status 0: Off 1: On
00019 0x0012 1 bit CH2 DO Pulse Operate Status 0: Off 1: On
00020 0x0013 1 bit CH3 DO Pulse Operate Status 0: Off 1: On
00021 0x0014 1 bit CH4 DO Pulse Operate Status 0: Off 1: On
00022 0x0015 1 bit CH5 DO Pulse Operate Status 0: Off 1: On
04097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
04099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04101 0x1004 1Bit CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04102 0x1005 1Bit CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04117 0x1014 1Bit CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04118 0x1015 1Bit CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04129 0x1020 1Bit CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04130 0x1021 1Bit CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04131 0x1022 1Bit CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04132 0x1023 1Bit CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04133 0x1024 1Bit CH4 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04134 0x1025 1Bit CH5 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
DI Channel
00257 0x0100 1 bit CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
00258 0x0101 1 bit CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
00259 0x0102 1 bit CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
00260 0x0103 1 bit CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
00261 0x0104 1 bit CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
00262 0x0105 1 bit CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
00273 0x0110 1 bit CH0 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00274 0x0111 1 bit CH1 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00275 0x0112 1 bit CH2 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00276 0x0113 1 bit CH3 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
00277 0x0114 1 bit CH4 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00278 0x0115 1 bit CH5 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
10001 0x0000 1 bit CH0 DI Value,0=OFF,1=ON (Read only)
10002 0x0001 1 bit CH1 DI Value,0=OFF,1=ON (Read only)
10003 0x0002 1 bit CH2 DI Value,0=OFF,1=ON (Read only)
10004 0x0003 1 bit CH3 DI Value,0=OFF,1=ON (Read only)
10005 0x0004 1 bit CH4 DI Value,0=OFF,1=ON (Read only)
10006 0x0005 1 bit CH5 DI Value,0=OFF,1=ON (Read only)
14097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14101 0x1004 1Bit CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14102 0x1005 1Bit CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14117 0x1014 1Bit CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14118 0x1015 1Bit CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30001 0x0000 2 word CH0 Read AO Scaling Value (float)
30002 0x0001 2 word CH1 Read AO Scaling Value (float)
30003 0x0002 2 word CH2 Read AO Scaling Value (float)
30004 0x0003 2 word CH3 Read AO Scaling Value (float)
30017 0x0010 1 word CH0 DI Counter Value Hi- Word (Read only)
30018 0x0011 1 word CH0 DI Counter Value Lo- Word (Read only)
30019 0x0012 1 word CH1 DI Counter Value Hi- Word (Read only)
30020 0x0013 1 word CH1 DI Counter Value Lo- Word (Read only)
30021 0x0014 1 word CH2 DI Counter Value Hi- Word (Read only)
30022 0x0015 1 word CH2 DI Counter Value Lo- Word (Read only)
30023 0x0016 1 word CH3 DI Counter Value Hi- Word (Read only)
30024 0x0017 1 word CH3 DI Counter Value Lo- Word (Read only)
30025 0x0018 1 word CH4 DI Counter Value Hi- Word (Read only)
30026 0x0019 1 word CH4 DI Counter Value Lo- Word (Read only)
30027 0x001A 1 word CH5 DI Counter Value Hi- Word (Read only)
30028 0x001B 1 word CH5 DI Counter Value Lo- Word (Read only)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
30049 0x0030 1 word DI Value (Ch0~5)
Bit0 = Ch0 DI Value (0=OFF, 1=ON)
………
Bit5 = Ch5 DI Value (0=OFF, 1=ON)
34097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44101 0x1004 1word CH4 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44102 0x1005 1word CH5 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44117 0x1014 1word CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44118 0x1015 1word CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44129 0x1020 1word CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44130 0x1021 1word CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44131 0x1022 1word CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44132 0x1023 1word CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44133 0x1024 1word CH4 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44134 0x1025 1word CH5 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
41025 0x0400 1 word CH0 AO RAW Value
41026 0x0401 1 word CH1 AO RAW Value
41027 0x0402 1 word CH2 AO RAW Value
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
41028 0x0403 1 word CH3 AO RAW Value
40033 0x0020 1 word DO all Value (Ch0~5)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
………
Bit5 = Ch5 DO Value (0=OFF, 1=ON)
E1240 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30001 0x0000 1 word CH0 Read AI Value
30002 0x0001 1 word CH1 Read AI Value
30003 0x0002 1 word CH2 Read AI Value
30004 0x0003 1 word CH3 Read AI Value
30005 0x0004 1 word CH4 Read AI Value
30006 0x0005 1 word CH5 Read AI Value
30007 0x0006 1 word CH6 Read AI Value
30008 0x0007 1 word CH7 Read AI Value
30009 0x0008 1 word CH0 Read AI Scaling Value Hi (float)
30010 0x0009 1 word CH0 Read AI Scaling Value Low (float)
30011 0x000A 1 word CH1 Read AI Scaling Value Hi (float)
30012 0x000B 1 word CH1 Read AI Scaling Value Low (float)
30013 0x000C 1 word CH2 Read AI Scaling Value Hi (float)
30014 0x000D 1 word CH2 Read AI Scaling Value Low (float)
30015 0x000E 1 word CH3 Read AI Scaling Value Hi (float)
30016 0x000F 1 word CH3 Read AI Scaling Value Low (float)
30017 0x0010 1 word CH4 Read AI Scaling Value Hi (float)
30018 0x0011 1 word CH4 Read AI Scaling Value Low (float)
30019 0x0012 1 word CH5 Read AI Scaling Value Hi (float)
30020 0x0013 1 word CH5 Read AI Scaling Value Low (float)
30021 0x0014 1 word CH6 Read AI Scaling Value Hi (float)
30022 0x0015 1 word CH6 Read AI Scaling Value Low (float)
30023 0x0016 1 word CH7 Read AI Scaling Value Hi (float)
30024 0x0017 1 word CH7 Read AI Scaling Value Low (float)
E1241 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
04097 0x1000 1Bit CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04098 0x1001 1Bit CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04099 0x1002 1Bit CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04100 0x1003 1Bit CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
04113 0x1010 1Bit CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04114 0x1011 1Bit CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04115 0x1012 1Bit CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
04116 0x1013 1Bit CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
04129 0x1020 1Bit CH0 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04130 0x1021 1Bit CH1 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04131 0x1022 1Bit CH2 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04132 0x1023 1Bit CH3 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
14097 0x1000 1Bit CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098 0x1001 1Bit CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099 0x1002 1Bit CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100 0x1003 1Bit CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113 0x1010 1Bit CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114 0x1011 1Bit CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115 0x1012 1Bit CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116 0x1013 1Bit CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
30001 0x0000 2 word CH0 Read AO Scaling Value (float)
30002 0x0001 2 word CH1 Read AO Scaling Value (float)
30003 0x0002 2 word CH2 Read AO Scaling Value (float)
30004 0x0003 2 word CH3 Read AO Scaling Value (float)
34097 0x1000 1word CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
34098 0x1001 1word CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
34099 0x1002 1word CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
34100 0x1003 1word CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
34113 0x1010 1word CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
34114 0x1011 1word CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
34115 0x1012 1word CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
34116 0x1013 1word CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
41025 0x0400 1 word CH0 AO RAW Value
41026 0x0401 1 word CH1 AO RAW Value
41027 0x0402 1 word CH2 AO RAW Value
41028 0x0403 1 word CH3 AO RAW Value
44097 0x1000 1word CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
44098 0x1001 1word CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
44099 0x1002 1word CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
44100 0x1003 1word CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
44113 0x1010 1word CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
44114 0x1011 1word CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
44115 0x1012 1word CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
44116 0x1013 1word CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
44129 0x1020 1word CH0 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44130 0x1021 1word CH1 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44131 0x1022 1word CH2 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44132 0x1023 1word CH3 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
E1242 Modbus Mapping
0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference Address Data Type Description
DO Channel
00001 0x0000 1 bit CH0 DO Value 0: Off 1: On
00002 0x0001 1 bit CH1 DO Value 0: Off 1: On
00003 0x0002 1 bit CH2 DO Value 0: Off 1: On
00004 0x0003 1 bit CH3 DO Value 0: Off 1: On
00017 0x0010 1 bit CH0 DO Pulse Operate Status 0: Off 1: On
00018 0x0011 1 bit CH1 DO Pulse Operate Status 0: Off 1: On
00019 0x0012 1 bit CH2 DO Pulse Operate Status 0: Off 1: On
00020 0x0013 1 bit CH3 DO Pulse Operate Status 0: Off 1: On
DI Channel
00257 0x0100 1 bit CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
00258 0x0101 1 bit CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
00259 0x0102 1 bit CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
00260 0x0103 1 bit CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
00261 0x0104 1 bit CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
00262 0x0105 1 bit CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
00263 0x0106 1 bit CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
00264 0x0107 1 bit CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
00273 0x0110 1 bit CH0 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00274 0x0111 1 bit CH1 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00275 0x0112 1 bit CH2 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
00276 0x0113 1 bit CH3 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00277 0x0114 1 bit CH4 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00278 0x0115 1 bit CH5 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00279 0x0116 1 bit CH6 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
00280 0x0117 1 bit CH7 DI Clear Count Value
Read Always return:0
Write: 1 : Clear counter value
0 : Return illegal data value(0x03)
04097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
04113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
04129 0x1020 1Bit CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04130 0x1021 1Bit CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04131 0x1022 1Bit CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
04132 0x1023 1Bit CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
1xxxx Read Only Coils (Function 2)
Reference Address Data Type Description
DI Channel
10001 0x0000 1 bit CH0 DI Value,0=OFF,1=ON (Read only)
10002 0x0001 1 bit CH1 DI Value,0=OFF,1=ON (Read only)
10003 0x0002 1 bit CH2 DI Value,0=OFF,1=ON (Read only)
10004 0x0003 1 bit CH3 DI Value,0=OFF,1=ON (Read only)
10005 0x0004 1 bit CH4 DI Value,0=OFF,1=ON (Read only)
10006 0x0005 1 bit CH5 DI Value,0=OFF,1=ON (Read only)
10007 0x0006 1 bit CH6 DI Value,0=OFF,1=ON (Read only)
10008 0x0007 1 bit CH7 DI Value,0=OFF,1=ON (Read only)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
DO Channel
14097 0x1000 1Bit CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14098 0x1001 1Bit CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14099 0x1002 1Bit CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14100 0x1003 1Bit CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
14113 0x1010 1Bit CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14114 0x1011 1Bit CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14115 0x1012 1Bit CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
14116 0x1013 1Bit CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
DI Channel
30017 0x0010 1 word CH0 DI Counter Value Hi- Word (Read only)
30018 0x0011 1 word CH0 DI Counter Value Lo- Word (Read only)
30019 0x0012 1 word CH1 DI Counter Value Hi- Word (Read only)
30020 0x0013 1 word CH1 DI Counter Value Lo- Word (Read only)
30021 0x0014 1 word CH2 DI Counter Value Hi- Word (Read only)
30022 0x0015 1 word CH2 DI Counter Value Lo- Word (Read only)
30023 0x0016 1 word CH3 DI Counter Value Hi- Word (Read only)
30024 0x0017 1 word CH3 DI Counter Value Lo- Word (Read only)
30025 0x0018 1 word CH4 DI Counter Value Hi- Word (Read only)
30026 0x0019 1 word CH4 DI Counter Value Lo- Word (Read only)
30027 0x001A 1 word CH5 DI Counter Value Hi- Word (Read only)
30028 0x001B 1 word CH5 DI Counter Value Lo- Word (Read only)
30029 0x001C 1 word CH6 DI Counter Value Hi- Word (Read only)
30030 0x001D 1 word CH6 DI Counter Value Lo- Word (Read only)
30031 0x001E 1 word CH7 DI Counter Value Hi- Word (Read only)
30032 0x001F 1 word CH7 DI Counter Value Lo- Word (Read only)
30049 0x0030 1 word DI Value (Ch0~7)
Bit0 = Ch0 DI Value (0=OFF, 1=ON)
Bit7 = Ch7 DI Value (0=OFF, 1=ON) ………
Bit8 to 15 = reserved
30513 0x0200 1 word CH0 Read AI RAW Value
30514 0x0201 1 word CH1 Read AI RAW Value
30515 0x0202 1 word CH2 Read AI RAW Value
30516 0x0203 1 word CH3 Read AI RAW Value
30521 0x0208 2 word CH0 Read AI Scaling Value (float)
30522 0x0209 2 word CH1 Read AI Scaling Value (float)
30523 0x020A 2 word CH2 Read AI Scaling Value (float)
30524 0x020B 2 word CH3 Read AI Scaling Value (float)
DO Channel
34097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
34113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
34116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference Address Data Type Description
40033 0x0020 1 word DO all Value (Ch0~3)
Bit0 = Ch0 DO Value (0=OFF, 1=ON)
Bit3 = Ch3 DO Value (0=OFF, 1=ON) ………
Bit4 to 15 = reserved
44097 0x1000 1word CH0 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44098 0x1001 1word CH1 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44099 0x1002 1word CH2 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44100 0x1003 1word CH3 DO P2P Connect Status 0=OFFLINE, 1=ONLINE
44113 0x1010 1word CH0 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44114 0x1011 1word CH1 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44115 0x1012 1word CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44116 0x1013 1word CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
44129 0x1020 1word CH0 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44130 0x1021 1word CH1 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44131 0x1022 1word CH2 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
44132 0x1023 1word CH3 DO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
E1260 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
31537 0x0600 1 word CH0 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31538 0x0601 1 word CH1 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31539 0x0602 1 word CH2 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31540 0x0603 1 word CH3 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31541 0x0604 1 word CH4 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
31542 0x0605 1 word CH5 Read RTD Value
Range 0~65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
ioLogik E1200 Series Modbus/TCP Default Address Mappings
A-
E1262 Modbus Mapping
3xxxx Read Only Registers (Function 4)
Reference Address Data Type Description
32049 0x0800 1 word CH0 TC Minimum Value Hi Word
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
32050 0x0801 1 word CH0 TC Minimum Value Lo Word
Hi+Lo Range: 0~4294967295
Unit:0.1 (Celsius, Fahrenheit) 0.0001(mV)
32051 0x0802 1 word CH1 TC Minimum Value Hi Word
32052 0x0803 1 word CH1 TC Minimum Value Lo Word
32053 0x0804 1 word CH2 TC Minimum Value Hi Word
32054 0x0805 1 word CH2 TC Minimum Value Lo Word
32055 0x0806 1 word CH3 TC Minimum Value Hi Word
32056 0x0807 1 word CH3 TC Minimum Value Lo Word
32057 0x0808 1 word CH4 TC Minimum Value Hi Word
32058 0x0809 1 word CH4 TC Minimum Value Lo Word
32059 0x080A 1 word CH5 TC Minimum Value Hi Word
32060 0x080B 1 word CH5 TC Minimum Value Lo Word
32061 0x080C 1 word CH6 TC Minimum Value Hi Word
32062 0x080D 1 word CH6 TC Minimum Value Lo Word
32063 0x080E 1 word CH7 TC Minimum Value Hi Word
32064 0x080F 1 word CH7 TC Minimum Value Lo Word
32065 0x0810 1 word CH8 TC Minimum Value Hi Word
32066 0x0811 1 word CH8 TC Minimum Value Lo Word
B B. Network Port Numbers
ioLogik E1200 Network Port Usage Port Type Usage
80 TCP Web console service
502 TCP Modbus/TCP communication
68 UDP BOOTP/DHCP
4800 UDP Auto search
69 UDP Export/import configuration file
9900 TCP Active OPC Server Lite
9950 TCP Active OPC Server Lite
9020 (default) TCP Peer-to-peer
C C. Factory Defaults
ioLogik E1200 series products are configured with the following factory defaults:
Default IP address 192.168.127.254
Default Netmask 255.255.255.0
Default Gateway 0.0.0.0
Communication watchdog Disable
Modbus/TCP Alive Check On
Modbus/TCP Timeout Interval 60 sec
DI Mode DI
Filter time 100 ms
Trigger for counter Lo to Hi
Counter status Stop
DO Mode DO
DO Safe Status Disable
Power on status Disable
Low width for pulse 1 ms (1.5 s for relay)
Hi width for pulse 1 ms (1.5 s for relay)
Output pulses 0 (continuous)
DIO Mode DO
AI Mode Voltage
Scaling and Slop-Intercept Disable
Password N/A
Server Name N/A
Server Location N/A
AO Mode Voltage
Scaling Disable
D D. Pinouts
Pin assignment of Terminal Blocks
E E. FCC Interference Statement
Federal Communication Commission Warning! This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part
15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received, including interference that may cause
undesired operation.
These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the user will be required to correct the interference at his own expense.
F F. European Community (CE)
This is a Class A product. In a domestic environment, this product may cause radio interference in which case
the user may be required to take adequate measures.