investigation of the coolnomix control system under western … · investigation of the coolnomix...
TRANSCRIPT
Investigation of the COOLNOMIX control system under Western Australia climatic conditions
A report submitted to the School of Engineering and Information Technology at Murdoch University, in partial fulfillment of the requirements for a
Bachelor of Engineering with Honours
Jovi Yu Xuan OH
SUPERVISOR
Dr. Jonathan Whale
Date: 18/11/2016
Declaration
I declare that this thesis is my own account of my research and contains as its main content work
which has not previously been submitted for a degree at any tertiary education institution
Signed: ________________________
iii
Abstract
COOLNOMIX is an intelligent control system which improves energy efficiency in refrigeration and air
conditioning systems by replacing the thermostat in a compressor driven cooling system. In the
traditional cooling system, most of the manufacturers do not take into account the hydraulic work of
the compressor. The compressor of a traditional cooling system continues running even if the
hydraulic work is done and space is already at its desired temperature. This wastes energy as 95% of
the costs of operating air conditioning and refrigeration systems come from the compressor itself.
This thesis aims to study the effectiveness of COOLNOMIX by doing some practical experiments to
investigate the amount of energy saved by COOLNOMIX and how COOLNOMIX is being affected by
Western Australia climatic conditions. Three different experiments have been investigated in this
thesis, which are practical experiment for air conditioning, practical experiment for refrigeration
system and existing experiment of a cooling system. Practical experiments were designed and
researched by installing COOLNOMIX product in air conditioners and a cool room at Murdoch
University and let it run for a period of time to investigate the energy saved and the system
performance under different climatic condition. The existing experiment of a cooling system is to
analyze the data of a cool room which already having installed COOLNOMIX product in real life.
The results of the air conditioning system experiment showed that the COOLNOMIX is saving 14% of
energy during hot weather and 20% of energy during cold weather. For the refrigeration system,
COOLNOMIX saves up to 53.5% of its original energy consumption.
iv
Acknowledgments
I would first like to acknowledge my thesis supervisor Dr. Jonathan Whale the senior lecturer in
Energy Studies and Renewable Energy Engineering at Murdoch University for all the supports and
help You were always there when I was lost and put me on the right track. Thank you for helping me
to go through all the problems I have faced.
I would also like to thank Mr. Jagpreet Walia the Industry supervisor of my thesis for his time and
guidance. Thank you for all the technical advice and knowledge you have given to me.
I am also grateful to Mr. Gary Higgins the General Manager of Assets and Maintenance at Murdoch
University for all the help for my project, this project would not have been done without your help.
Thank you for spending so much time to help me in solving my problems, contacting relevant
department and all the permission, advises and suggestions given.
I also wish to express my sincere thanks to all the relevant technicians that make this project
happened, especially Mr. Vlad Ugrinov the site supervisor of air master, thank you for always be
there for me when I need help for my experiment.
I would also like to acknowledge Ms. Caitlin Sweeney the Laboratory Technician at Murdoch
University for assistance with the equipment and the experiment data.
And I would also like to thank Professor Parisa Arabzadeh Bahri the unit coordinator of ENG470 for
all the reminders and supports you have given.
And also thanks to Murdoch University for the funding for this project.
I would also like to take this opportunity to express gratitude to one and all, who directly or
indirectly provide help to this project.
In particular, special thanks to Jose Loh for all the supports throughout the thesis.
v
Table of contents
Declaration .............................................................................................................................................. ii
Abstract .................................................................................................................................................. iii
Acknowledgments .................................................................................................................................. iv
Table of contents .................................................................................................................................... v
List of Figures ........................................................................................................................................ vii
List of Tables ......................................................................................................................................... vii
Table of Abbreviations ......................................................................................................................... viii
1 Introduction .................................................................................................................................... 1
2 Objective ......................................................................................................................................... 2
3 Literature review ............................................................................................................................. 3
3.1 Refrigeration ........................................................................................................................... 3
3.1.1 Vapour Compression Refrigeration System .................................................................... 3
3.2 Reversed Carnot cycle ............................................................................................................. 4
3.3 3.3 COOLNOMIX ...................................................................................................................... 6
3.3.1 COOLNOMIX components ............................................................................................... 7
3.3.2 Differences between Optimized Refrigerant Supply and Original Temperature Control
System 8
3.3.3 Pros and Cons ................................................................................................................ 10
3.4 Weather ................................................................................................................................ 10
3.4.1 Effects of weather on cooling system ........................................................................... 11
3.5 Cooling Load .......................................................................................................................... 12
3.6 Thermal comfort ................................................................................................................... 12
4 Practical Experiments & Existing Experiment ............................................................................... 13
4.1 Design .................................................................................................................................... 13
4.1.1 Consideration ................................................................................................................ 13
4.1.2 Air conditioning system ................................................................................................ 14
4.1.3 Refrigeration system ..................................................................................................... 18
vi
4.2 Pros and Cons of Linear test and Parallel test ...................................................................... 19
4.3 Methodology ......................................................................................................................... 20
4.4 Existing Experiment ............................................................................................................... 21
5 Results and Discussion .................................................................................................................. 22
5.1 Air Conditioning System ........................................................................................................ 22
5.1.1 Climate condition .......................................................................................................... 22
5.1.2 Cold Weather ................................................................................................................ 23
5.1.3 Hot Weather ................................................................................................................. 25
5.2 Refrigeration System ............................................................................................................. 27
5.3 Existing Experiment ............................................................................................................... 29
6 Economic Analysis ......................................................................................................................... 30
7 Conclusion ..................................................................................................................................... 31
8 Future Work .................................................................................................................................. 32
8.1 Reversed Carnot Cycle .......................................................................................................... 32
8.2 Thermal Comfort Test ........................................................................................................... 33
8.3 Experiment Period ................................................................................................................ 33
9 References .................................................................................................................................... 34
10 APPENDIX .................................................................................................................................. 35
10.1 Appendix A ............................................................................................................................ 35
10.1.1 COOLNOMIX installation (AC-01) .................................................................................. 35
10.1.2 COOLNOMIX installation (AR-01) .................................................................................. 37
10.1.3 COOLNOMIX LED Indicator Description ........................................................................ 41
10.2 APPENDIX B calculation ........................................................................................................ 41
10.2.1 Payback Period (AC-01) ................................................................................................. 41
10.2.2 Payback Period (AR-01) ................................................................................................. 42
10.2.3 Appendix C .................................................................................................................... 43
vii
List of Figures
Figure 1 Vapor Compression Refrigeration Cycle ................................................................................... 3
Figure 2 P-V diagram of Reversed Carnot cycle ...................................................................................... 5
Figure 3 Model of Reversed Carnot Cycle ............................................................................................... 6
Figure 4 COOLNOMIX Components ........................................................................................................ 7
Figure 5 Building 126 Location .............................................................................................................. 15
Figure 6 Building 124 Location .............................................................................................................. 18
Figure 7 Ambient Temperature ............................................................................................................ 22
Figure 8 Results of Air Conditioning Systems (Cold Weather) .............................................................. 23
Figure 9 Results of Air Conditioning Systems (Hot Weather) ............................................................... 25
Figure 10 Results of Cool Room ............................................................................................................ 27
Figure 11 Results of Existing Experiment .............................................................................................. 29
Figure 12 COOLNOMIX AC-01 wiring .................................................................................................... 35
Figure 13 COOLNOMIX AC-01 Sensors Locations ................................................................................. 36
Figure 14 COOLNOMIX AC-01 Set Point Orientations........................................................................... 37
Figure 15 COOLNOMIX AR-01 Wiring ................................................................................................... 38
Figure 16 COOLNOMIX AR-01 Sensor Location..................................................................................... 39
Figure 17 COOLNOMIX AR-01 Set Point Orientation ............................................................................ 40
Figure 18 Model of Air conditioner for Practical Experiment ............................................................... 43
Figure 19 Model of Cool Room for Practical Experiment ..................................................................... 43
List of Tables
Table 1 Ambient Temperature in Western Australia [9] ...................................................................... 11
Table 2 Monitoring Equipment for Air Conditioners ............................................................................ 16
viii
Table 3 Monitoring Equipment for Cool Room ..................................................................................... 19
Table 4 Advantages and Disadvantages of Linear Test and Parallel Test ............................................. 20
Table 5 COOLNOMIX LED Flashing Sequence and Indication ............................................................... 41
Table of Abbreviations
kWh: Kilo Watt Hour
HVAC: Heating, Ventilation, and Air conditioning
LED: Light Emitting Diode
ORS: Optimized Refrigerant Supply
1
1 Introduction
In Australia, almost every single (99.8%) household has at least one refrigerator and also 41% of
the households in Western Australia were even having two or more refrigerators [3].
Furthermore, the research [3] also showed that over two-thirds (67%) of the households in
Australia had at least one air conditioner or cooler. This research proved that a big portion of
Australian households rely on cooling systems. However, both air conditioning systems and
refrigeration systems are electrical appliances that require electricity to run. A recent survey
found that estimated 24% of the Australian households’ electricity bills actually come from air
conditioner operation [1] and another 15% comes from refrigeration [2]. It means that the
electricity costs of these two cooling appliances are worth up to more than one-third (39%) of the
electricity bills. This is considered as an important area that needs to be focused on to reduce the
cost of electricity bills.
However, the best way to reduce the energy consumption of a cooling system is to focus on the
compressor in the refrigeration cycle because 95% of the energy consumption is actually from the
compressor. In this thesis, COOLNOMIX, an intelligent control system that focuses on improving
energy efficiency in air-conditioning and refrigeration systems by operating the compressor inside
a cooling system, is investigated to determine how this product saves energy under Western
Australia climatic conditions.
2
2 Objective
The main objective of this thesis is to investigate COOLNOMIX product under Western Australia
climatic conditions. As a build-up to achieve the main objective, the main objective was divided
into several smaller objectives listed below:
1. To investigate and compare the energy consumptions of both air conditioning and
refrigeration system, with and without the addition of COOLNOMIX product;
2. To investigate the room temperature of the researched rooms, with and without the
addition of COOLNOMIX product;
3. To investigate how the Western Australia climate affects the performances of the air
conditioning system, with and without the addition of COOLNOMIX product;
4. To investigate the economic savings of installing COOLNOMIX product.
3
3 Literature review
This chapter reviews the background of a cooling system and the technical information of
COOLNOMIX. This chapter also shows some research on the Western Australia climate.
3.1 Refrigeration
Refrigeration is known as a process that moves heat from one to another in controlled conditions.
However, according to the second law of thermodynamics, work is required in order to transfer
heat from a colder location to a hotter area. There are several systems that are able to do this,
but the Vapor Compression Refrigeration System is the system that is focused on in this thesis.
3.1.1 Vapour Compression Refrigeration System
Vapour compression refrigeration method, is the system that used most widely for air
conditioners and refrigerators, and the system is shown in figure 1:
Figure 1 Vapor Compression Refrigeration Cycle
A typical Vapour Compression Refrigeration cycle contains four different components: an
evaporator, a compressor, a condenser and an expansion valve. The evaporator is normally
placed inside the room and the condenser is placed outside the room.
Evaporator
Expansion
Valve
Condenser
Compressor
1 2
4 3
Vapor Vapor
Liquid Vapor + Liquid
Warm air Cold air
4
A Vapour Compression Refrigeration System can be considered as a flowing liquid cycle, where
liquid refrigerant is used as a medium that is able to absorb or remove heat and flows in the
system. A cooling cycle of this system works as following steps:
1. Heat is first absorbed by the refrigerant and the refrigerant turns into a thermodynamic
state known as saturated vapor at evaporator (4 - 1);
2. The saturated vapor enters the compressor and is compressed to a higher pressure state
known as superheated vapor (1 - 2);
3. The superheated vapor is then being cooled in the condenser and the heat is transferred
to the outside. The condensed refrigerant is now at the state known as saturated liquid
after cooling. (2 – 3);
4. The saturated liquid flows into expansion valve and the valve lowers the pressure of the
refrigerant. The refrigerant now becomes a cold mixture that contains both liquid and
vapor. (3 – 4);
5. The cold mixture is now entering the evaporator with low temperature (4 – 1).
A refrigeration cycle is now completed and the refrigerant repeats the cycle from step 1 to
step 5.
3.2 Reversed Carnot cycle
The Carnot cycle is a theoretical thermodynamic cycle which first purposed by Nicolas Leonard
Sadi Carnot in 1824 [4]. Carnot cycle shows the thermodynamic cycle inside a heat pump and the
relationship between the conversion of heat and work. However, this thesis focuses on a cooling
system not a heat pump, so a Reversed Carnot Cycle is used instead. The reversed Carnot cycle is
similar to the Carnot Cycle but operated in different direction which shown in figure 2:
5
Figure 2 P-V diagram of Reversed Carnot cycle
Figure 2 shows a typical P-V graph of Reversed Carnot Cycle, where the points 1 -4 are referred to
figure 1 (Vapour Compression Refrigeration) in chapter 3.1.1. Similar to the steps discussed in
chapter 3.1.1, but a P-V graph of Reversed Carnot Cycle focuses on the pressure and volume of
refrigerant inside the cooling cycle at each stage. The P-V diagram can be understood as following
steps:
1 – 2: The vapor enters the compressor and is compressed isentropically, there is no heat
flow in or out the cooling system. In this stage the volume of the refrigerant is slightly
decreased and the pressure is increased significantly (T1);
2 – 3: Heat is expelled to the outside air isothermally at the condenser. In this stage the
volume of the refrigerant is decreased significantly and the pressure is slightly increased
(T2 = T3);
3 – 4: The vapor is now entering the expansion valve and expanded isentropically, no heat
exchange between the system and surrounding area. In this stage the volume of the
refrigerant is slightly increased and the pressure is decreased significantly (T3);
4 – 1: The heat is extracted from the room and the gas expands isothermally at the
evaporator, this is where the cooling takes place. In this stage, the volume of the
refrigerant is increased significantly and the pressure is slightly decreased. (T4 = T1). [5]
2
3
4
1
Volume
Pressure
6
Where:
T1 equals to the temperature at point 1, T2 equals to the temperature at point 2, etc.;
And also and ;
refers to the cool temperature and refers to the relatively hot temperature.
The steps of the P-V diagram can also be understood more easily as figure 3 below:
Figure 3 above shows the status of the refrigerant at each stage, where Q is the amount of
heat.
3.3 3.3 COOLNOMIX
COOLNOMIX is an intelligent control system designed to improve energy efficiency in both air
conditioning and refrigeration systems by using a unique control technology called Optimized
Refrigerant Supply (ORS). COOLNOMIX is having customers all around the world which having an
average 40% savings on air conditioners and an average 30% savings on refrigeration system from
the customers’ feedback [6].
Figure 3 Model of Reversed Carnot Cycle
1 2 3 4
Qin Qout
7
3.3.1 COOLNOMIX components
Figure 4 [12] below shows the components inside a COOLNOMIX product:
Figure 4 COOLNOMIX Components
These include:
AC power supply terminal - Connects to power supply
Set-point setting - Users are able to adjust the desired room temperature from here
Control relay terminal – This terminal is connected to the refrigeration unit and the
compressor operating signal is sent from here to the refrigeration unit
Supply air sensor – Installed at the evaporator fin to determine whether the unit has done
its hydraulic work (explanation refers to chapter 3 for hydraulic work)
Room temperature sensor – installed at the return air fin to measure the room
temperature
Diagnostics LED – Inform the COOLNOMIX conditions to users by flashing different lights
with different orders
8
Reset button – Reset the COOLNOMIX
Alarm switch – Alerts users if COOLNOMIX fails (can be silenced).
Note that there are two models of COOLNOMIX, which are the AC-01 (for air conditioning
systems) and AR-01 (for refrigeration systems). The main difference between the models is the
temperature set point.
The specific setting of a set point, connection of the control relay terminals, location of sensors
and LED signals are shown in Appendix A. [12]
3.3.2 Differences between Optimized Refrigerant Supply and Original Temperature
Control System
3.3.2.1 Original Temperature Control System
Over the past few decades, there was a lot of technology that significantly improved the cooling
system’s efficiency such as inverters, digital scroll etc. However, there is one thing that remains
unchanged, which is most of the cooling systems at the moment are using the thermostat as their
control system. In thermostat a control system, the operation of the compressor is normally
controlled by the thermostat using a crude logic: the compressor is turned ON if the sensor
detects that the room temperature is 1 °C higher than the set point, turned OFF if the sensor
detects that the room temperature is 1 °C lower than the set point. Depending on the load, the
location of sensor etc., the unit takes a certain amount of time to cool down the room
temperature by 2°C (from 1°C higher to 1°C lower than the set point).However, the compressor
will keep running during this period of time, the thermostat ignores what is actually happening
inside the unit, and this may cause the compressor run for a longer period of time, which is
unnecessary. [8]
9
3.3.2.2 Background - Air conditioner’s excess capacity
For a better understanding of how ORS works, the background of an air conditioner’s excess
capacity has to be understood. An air conditioner’s capacity is normally chosen to ensure it can
handle satisfactorily under different loads, which means that the air conditioner can run
continuously on the hottest day. At that situation, the refrigerant is boiling quickly in the
evaporator and the compressor manages to keep up with demand. However, in a cooler situation,
there is spare capacity in the unit and the compressor supplies the refrigerant at a faster rate
than the evaporator can boil. This is the situation where ORS can save energy, which will be
discussed in the chapter 3.3.2.3 below. [7]
3.3.2.3 Optimized Refrigerant Supply (ORS)
Optimized Refrigerant Supply is an advanced control system, which using two additional
temperature sensors shown in chapter 3.3.1 and a complex algorithm technology to monitor the
room temperature (thermodynamic) and refrigerant supply (hydraulic) performance of the
cooling system to improve compressor efficiency. Firstly, the ORS uses room temperature sensor
to evaluate the room temperature to ensure the temperature achieved the chosen set point. If
the sensor show that the room temperature is within +/- 0.5 °C of the setpoint, the supply air
sensor then allows the ORS to determine and predict whether the spare cooling capacity in the
evaporator is available and stops the compressor. On the other hand, when the compressor stops
working for a period of time, the condenser is relatively cooler and having lower pressure, while
the evaporator is relatively warmer and having higher pressure. Furthermore, when the
compressor starts, ORS always let it run at full rated so the compressor is possible to finish its
hydraulic work in less time. This technique uses the spare capacity to achieve the same
thermodynamic work by using less mechanical work, gives the compressor the most ideal
conditions to make the whole process more efficient. [7]
10
3.3.3 Pros and Cons
There are some pros and cons by installed COOLNOMIX such as:
Pros:
Saves energy – COOLNOMIX reduces unnecessary energy waste and increases system
efficiency by using ORS;
Easy to be installed – COOLNOMIX can be installed easily, normally within an hour
Improved stability of temperature – ORS is designed to control the room temperature
variation to be less than 0.5°C;
No other maintenance fees and operating costs – COOLNOMIX needs no other
maintenance fees and operating costs while running, but only electricity;
Immediate savings – COOLNOMIX starts to save energy once it is installed and runs
successfully;
Low risks – COOLNOMIX has a secure design to make sure the system is able to run as
usual if COOLNOMIX product fails.
Cons:
Fixed temperature set point – COOLNOMIX has its own set point setting component
which shown in chapter 3.3.1. Users can only change the desired temperature from there,
which might be inconvenient for some users;
System limitations – COOLNOMIX only works on cooling only system, which is not be
suitable for reversed cycle units (the unit that can be changed between heating or
cooling).
3.4 Weather
Western Australia is a state, which has a most diverse climate in the country due to its huge size.
Western Australia’s climate can be separated by regional and seasonal (only extreme weather,
11
summer and winter is focused in this thesis in order to get the maximum and minimum
temperature throughout the year) as follows:
Region Season Average daily
Maximum
Temperature (°C)
Average daily
Minimum
Temperature (°C)
Perth weather Summer 30 18
Winter 18 6
South West and
Margaret River
weather
Summer 27 15
Winter 12 3
North West and
Broome weather
Summer 39 24
Winter 27 12
Table 1 Ambient Temperature in Western Australia [9]
From the data shows from table 1 above, Western Australia’s average daily temperature changes
between 3 °C and 39 °C (extreme weather can be lower than 3 °C or higher than 39°C).
3.4.1 Effects of weather on cooling system
As mentioned in chapter 3 before, a compressor of a cooling system will start running if the
thermostat detected the space temperature is higher than the set point limit and needs cooling.
On the other hand, if the ambient temperature (temperature of the surrounding/outside the
room) is actually way lower than the set point limit, the compressor will not work and the air
conditioner (cooling only) will be blowing the cold air only.
12
3.5 Cooling Load
A load of a cooling system can be defined as the heat that needs to be removed from the area to
maintain a constant area temperature and humidity. The ASHRAE handbook of fundamentals [10]
shows that heat gains for a space affected by the following six components:
Solar radiation through transparent surfaces;
Heat conduction through exterior roofs and walls;
Heat conduction through floors, ceilings, and interior partitions;
Heat generated in the room by appliances, such as lights, occupants etc.;
Energy transfer through ventilation and infiltration of outdoor air;
External Interruption.
3.6 Thermal comfort
Thermal comfort is defined as “a condition of mind which expresses satisfaction with the thermal
environment” [11], which can be understood as the occupants’ satisfaction with the surrounding
thermal conditions. Thermal comfort is always the first priority to be considered in an air
conditioning system. However, there are six important factors contributing to thermal comfort,
which are:
Air temperature – Temperature of air surrounding the occupant;
Metabolic rate – Energy generated from the human body;
Clothing insulation – the amount of thermal insulation an occupant wears;
Radiant temperature – Weighted average of all the temperatures of surfaces surrounding
the occupant;
Relative humidity – percentage of water vapor in the air;
Air velocity – Air moment rate in the space. [11]
13
4 Practical Experiments & Existing Experiment
In this chapter, three experiments are discussed to investigate the COOLNOMIX’s performances
on each system, which is practical experiment for air conditioning system, practical experiment
for refrigeration system and existing experiment for refrigeration system. COOLNOMIX products
are installed in chosen sites and run for a certain period of time to determine:
How does a COOOLNOMIX product affect a cooling system’s performance;
How does a COOOLNOMIX product affect the room temperature;
How does Western Australia ‘s climate affect the COOLNOMIX ORS’ operations;
How much energy does COOLNOMIX save in the practical experiments.
4.1 Design
Selecting a suitable site and design the experiments were the most time-consuming tasks to be
accomplished throughout this thesis. However, before selecting a suitable site for both the
experiments, several considerations were discussed in the following parts.
4.1.1 Consideration
4.1.1.1 Load management
In each experiment, the methods of motoring were separated into two periods, which were test
period and control period. Test period refers to the period without the addition of COOLNOMIX
and the control period refers to the period where COOLNOMIX has been installed in the system.
Therefore, load management for both periods must be able to be controlled to be as similar as
possible in order to get more reliable results.
4.1.1.2 Thermal comfort
For the air conditioning experiment, thermal comfort of the occupants is considered before
choosing an experiment site. Facilities Management at Murdoch University is more concerned
with the thermal comfort level of the air conditioners’ users.
14
4.1.2 Air conditioning system
4.1.2.1 Site Selection
After several discussions with the Facilities Management Office at Murdoch University, two
empty classrooms in old Murdoch College (building 126, which is shown in Figure 5 below) were
used for this experiment. There are some reasons why these rooms were chosen as below:
Air conditioners – Both rooms have identical air conditioners with the same model, size
and similar performance (refer to APPENDIX C for specifications);
Room sizes – Both rooms have a very similar room size, so the cooling loads of the rooms
are similar to each other;
Room design – Both rooms are empty classrooms with exactly the same interior design,
so the heat conducted through the floors, ceilings, and interior partitions are similar with
each other;
Room location – The rooms are located next to each other, so the heat conducted
through roofs or walls is expected to be similar;
Ethical issues – Both rooms are empty classrooms that are not in-use. Therefore, ethical
issues such as thermal comfort are not considered.
15
Figure 5 Building 126 Location
A COOLNOMIX unit is then installed in one of the air conditioners by following the installation
manual (refer to APPENDIX A) and both air conditioners are running for a period of time.
However, the experiment is running under some other conditions as follows:
All windows are closed to prevent ventilation;
Only one curtain of each room is open to ensure similar amount of solar radiation
passed through the transparent surfaces;
Air conditioners of both rooms are set as COOLING ONLY and running 24 hours per
day;
No one entered or used the rooms during the experiment to prevent any other
external interruption.
16
From all the load controls shown above, it can be said that both rooms have been running under
similar conditions.
4.1.2.2 Monitoring Equipment
After the suitable site and air conditioners were selected, the next step of the experiment was
monitoring. The monitoring equipment used is shown in table 2 below:
Equipment Quantity
Temperature data logger 1 for each room, 2 in total
Power meter clamp 1 for each air conditioner, 2 in total
Transmitter 1 for each air conditioner, 2 in total
Engage Hub 1 in total
Table 2 Monitoring Equipment for Air Conditioners
Table 2 shows the monitoring equipment used in this experiment, where one temperature data
logger is placed in each room (at the place where student normally sit) to monitor the room
temperature of the space.
However, the power meter clamp, transmitter and engage hub are the components of a
monitoring device named Efergy Engage Hub Kit and it works as below:
1. The power clamp is first installed at the air conditioner power supply and connected to a
transmitter;
2. The engage hub is connected to internet and pairs the transmitters nearby;
3. The transmitters read the connected clamps’ data and send the data to the paired engage
hub;
4. The engage Hub uploads the data to a database where users are able to monitor the data
in real time by using Internet access devices such as a phone, laptop, etc.
17
4.1.2.3 Monitoring Method
In this part of the experiment, since there are two air conditioners running under very similar
conditions, the parallel test is the better method to monitor the systems. The parallel test is a
monitoring method, which is normally used in COOLNOMIX testing while the customer has
multiple refrigerators or air conditioners of the same type, size and similar cooling loads. Parallel
test runs either air conditioners or refrigeration systems, with (control period) and without the
(test period) addition of COOLNOMIX together for a certain period of time. Users are able to
compare the differences between the two systems and calculate the energy saved by the addition
of COOLNOMIX product.
18
4.1.3 Refrigeration system
4.1.3.1 Site Selection
In this part of experiment for the refrigeration system, only one cool room (refer to appendix C
for the model) in Murdoch University is currently empty and free to do the experiment. This cool
room is located in old Murdoch College (building 124,which shown in Figure 6 below) and has not
been used for quite some time.
Figure 6 Building 124 Location
A COOLNOMIX unit was installed in the cool room by following the installation manual (refers to
Appendix A). And also the experiment is running under some other conditions as follows:
The cool room is running 24 hours per day;
No one entered or used the room to prevent any other external interruption.
19
4.1.3.2 Monitoring Equipment
Monitoring equipment used in this part of experiment is shown in table 3 below:
Equipment Quantity
Temperature data logger 1
Power meter clamp 1
Transmitter 1
Engage Hub 1
Table 3 Monitoring Equipment for Cool Room
The installation of the monitoring devices is same as steps mentioned in chapter 4.1.2.2.
4.1.3.3 Monitoring Method
Different from the air-conditioning system in chapter 4.1.2.3, the refrigeration system in this
chapter is run under linear test because there is only one cool room in this situation. The Linear
test is another monitoring method, which normally used in COOLNOMIX testing while the
customer has only one unit. Linear test first runs the system for a certain period of time (test
period) before installing COOLNOMIX, and then it runs the system for a same period of time with
the addition of COOLNOMIX (control period). Users are able to determine the energy savings by
comparing the energy consumption of the two different periods.
4.2 Pros and Cons of Linear test and Parallel test
The previous chapters show that different methods are used in different systems depend on the
conditions. However, there are some advantages and disadvantages of both methods showed in
table 4 below:
20
Linear test Parallel Test
Advantages Only one unit and one
measuring device are needed
Takes less period of time to
see the energy saving
potential
Loads and environmental
conditions are more likely
similar to both units
Disadvantages Takes longer period of time to
see the energy saving
potential
More than one unit and
measuring devices are needed
Loads and environmental
conditions may vary over time
Table 4 Advantages and Disadvantages of Linear Test and Parallel Test
Users are able to monitor the energy-saving potential of COOLNOMIX more effectively by using a
suitable monitoring method.
4.3 Methodology
In order to get the data for results analysis, the methods are shown as follows:
1. Collect the temperature of the rooms;
2. Collect the ambient temperature during the experiment period from Murdoch University
Weather Station;
3. Collect the energy consumptions of the systems for both the control period and test
period from the database;
4. Investigate the differences between control period and test period;
5. Match the energy consumptions of the control period and test period with the room
temperature and ambient temperature;
21
6. Investigate how the systems’ performance affects the room temperature;
7. Compare control period and test period to determine how much energy is saved.
4.4 Existing Experiment
In this experiment, an existing cool room with installed COOLNOMIX is used to investigate how
the product affects a cool room’s performance. This cool room is located in a restaurant named
Copper Chimney in Fremantle, where a COOLNOMIX is installed on 31st of August. However, all
the data of this cool room is provided from the industry supervisor, therefore only energy
consumption is recorded in this experiment.
22
5 Results and Discussion
5.1 Air Conditioning System
In this part of the experiment, both air conditioners (with and without the addition of
COOLNOMIX) are run and monitored from 26th of October to 6th of November.
5.1.1 Climate condition
Figure 7 Ambient Temperature
Figure 7 above shows the ambient temperature during the experiment period and also the set
points of both air conditioners were set at 23 °C. As mentioned in chapter 3.4.1, the compressor
of a cooling only air conditioner will stop running while the ambient temperature is lower than
the set point, unfortunately during the experiment period, most of the time the ambient
temperature were lower than the set point or very near to the set point due to the cold weather
0
5
10
15
20
25
30
35
40
25/10 27/10 29/10 31/10 02/11 04/11 06/11 08/11
Tem
pe
ratu
re (
°C)
Date
Ambient Temperature Ambient Temperature
Air conditioning setpoint
23
in Perth. On the other hand, Figure 7 shows that there was a day the ambient temperature is
significantly higher than the set point, which is 5th of November.
Therefore, the results were separated into two parts, cold weather (26th of October to 1st of
November) and hot weather (on 5th of November) which reflects winter period and summer
period in Western Australia respectively.
5.1.2 Cold Weather
Figure 8 Results of Air Conditioning Systems (Cold Weather)
Figure 8 shows the results of energy consumption of the air conditioners and the corresponding
room temperature in cold weather over time, where lines in blue color refer to the system with
installed COOLNOMIX and the lines in red color refer to the system without the addition of
0
50
100
150
200
250
300
350
400
450
500
0
5
10
15
20
25
26/10 27/10 28/10 29/10 30/10 31/10 1/11 2/11
Ene
rgy
Co
nsu
mp
tio
n (
Wm
)
Tem
pe
ratu
re (
°C)
Date
Energy consumptions and room temperatures of air conditioning systems with/without addition of COOLNOMIX
Temperature (with)
Temperature (without)
set point
Energy consumption (with)
Energy consumption (without)
24
COOLNOMIX. Furthermore, the two curve lines on the top of the graph show the temperature of
the room and the two straight lines on the middle show the energy consumption of the air
conditioner.
The results in Figure 8 show that both room temperatures are always lower than the set point
during this period, which means the compressors in air conditioners are more likely not working
but still consuming some tiny amount of energy to keep the air flowing. However, the results also
show that there is always 1 °C difference between each room. The results show that there is a
significant difference between both air conditioners which is the air conditioner with installed
COOLNOMIX is always consuming less energy than another air conditioner. It is believed that
while the COOLNOMIX sensors detected the room temperature is lower than the set point limit,
COOLNOMIX ORS fully shut down the compressor. Conversely, the original air conditioner is still
consuming some energy to keep the compressor running at a very low rated power. This tiny
difference of operation of the compressor is suspected to be the reason that why the air
conditioner without the addition of COOLNOMIX is consuming more energy and the
corresponding room temperature is always slightly higher than another room’s temperature.
After calculating the results, the air conditioner without the addition of COOLNOMIX consumed
5.82 kWh of energy per day and the air conditioner with installed COOLNOMIX consumed 4.65
kWh of energy per day in this experiment. The calculated results show that the COOLNOMIX
technology saved around 1.17kWh of energy per day, which is about 20% of its original energy
consumption.
25
5.1.3 Hot Weather
Figure 9 Results of Air Conditioning Systems (Hot Weather)
Similar to chapter 5.1.2, Figure 9 shows the results of energy consumption of the air conditioners
and the corresponding room temperature in hot weather on 5th of November, where lines in blue
color refer to the system with installed COOLNOMIX and the lines in red color refer to the system
without the addition of COOLNOMIX. Furthermore, the two lines on the top of the graph show
the temperature of the room and the other two lines on the bottom show the energy
consumption of the air conditioner.
The result shows the performance differences between the two air conditioners can be clearly
seen. On this day, the energy consumptions and room temperature of the spaces are similar to
the results shown in Figure 9 before 09:00. However, at around 09:00 (green line), both air
0
5
10
15
20
25
30
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
19:12:00 0:00:00 4:48:00 9:36:00 14:24:00 19:12:00 0:00:00
Tem
pe
ratu
re (
°C)
Ave
rage
En
erg
y co
nsu
mp
tio
n (
kWh
)
TIme
Energy consumptions and room temperatures of air conditioning systems with/without addition of COOLNOMIX
Average energyconsumption(without)
Average energy consumption(with)
9:00:00
26
conditioners’ sensors detected that the room temperature has met the set point and the room
needs cooling. At this stage, the compressors inside both air conditioners started working in order
to cool down the room, but Figure 9 shows that the patterns of energy consumptions in both air
conditioners are totally different, which can be explained as follows:
The air conditioner without addition of COOLNOMIX (Red line) – In this air conditioner,
when the temperature met the set point limit, the compressor started working for a
period of time in order to cool down the room temperature, however the results show
that the room temperature of the room after cooling is not the desired set point that the
users looking for, the room temperature changing around +2°C of the desired set point;
Air conditioner with addition of COOLNOMIX (Blue line) – In this air conditioner, when the
temperature met the set point limit, the compressor which is controlled by ORS started
running at full load for a small amount of time and the compressor stopped when the
COOLNOMIX supply air sensor detected that the compressor had done its hydraulic work.
The cold and sufficient refrigerant inside the cooling cycle has then absorbed the heat
from the room slowly to control the room temperature as stable as possible until the ORS
detected that the compressor needs to be started again in order to stabilize the room
temperature, this is what happened at 20:00 in Figure 9. Comparing the room
temperature of this room with the room without the addition of COOLNOMIX, this
temperature of this room are more stable and always within +/-1°C of the desired set
point.
By using the different operation methods of compressors, the energy consumptions of these two
air conditioners are found to be different. On this day, the air conditioner without the addition of
COOLNOMIX consumed 16.3 kWh of energy in total but the air conditioner with installed
COOLNOMIX consumed 14kWh of energy, which means the COOLNOMIX product saved 2.3 kWh
on that day which is about 14% of the original energy consumption.
27
5.2 Refrigeration System
Figure 10 Results of Cool Room
Figure 11 above shows the results energy consumption and its corresponding room temperature
of the cool room. Different from the air conditioners, climatic conditions of Western Australia are
not considered for a refrigeration system because as mentioned in chapter 3.4, most of the time
the ambient temperature of Western Australia will not get lower than a refrigeration system’s set
point. The results in Figure 10 can be separated into two parts: the data in blue color on the left
refers to the cool room with the addition of COOLNOMIX and the data in red color on the right
refers to the cool room without the addition of COOLNOMIX. For both parts, the data on the top
refers to the room temperature of cool rooms and the data on the bottom refers to the energy
-10
-8
-6
-4
-2
0
2
4
6
8
10
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
25/10/16 27/10/16 29/10/16 31/10/16 2/11/16 4/11/16 6/11/16
Max
.Te
mp
era
ture
(°C
)
Ave
rage
Po
we
r co
nsu
mp
tio
n (
Kw
h)
Date
Power consumption / Room temperature of Cool room with COOLNOMIX ON/OFF
Power consumption (with)
Power consumption (without)
Max.Tempreature (with)
Max.Tempreature (without)
set point
28
consumptions of cool rooms. This experiment of the cool room had been running for 8 days, 4
days with COOLNOMIX and 4 days without COOLNOMIX product.
In this result, the differences between energy consumptions of the cool rooms are found difficult
to be investigated from the trends. However, Figure 10 shows there is a significant difference in
room temperature between the systems: the room temperature of the original cool room
(without COOLNOMIX) is always higher than the set point, which it can be defined as this is a bad
performing cool room that can’t meet the desired set point. Surprisingly, when a COOLNOMIX is
installed and run with the cool room successfully, the room temperature of the cool room is more
stable and is controlled within -2°C of the desired set point. It is suspected that the COOLNOMIX
sensors detected that the cool room was always above the set point limit, it ran the compressor
at full load for the most of the time to make sure the room temperature is at the preferable
temperature (3°C).
In this linear test experiment, the energy saved by COOLNOMIX product can be calculated by
comparing the total energy consumptions of the test period and control period with the same
amount of time. In this experiment, the test period consumed an average of 11 kWh of energy
per day and the control period consumed an average of 12kWh of energy per day. The
COOLNOMIX in this experiment made the cool room consumed an extra 1kWh per day, which is
about 8.1% of its original energy consumption.
Note that the reasons explained in this experiment of the cool room are just possible reasons and
that is not clearly understood why it consumed more energy instead of saving. The data did not
meet the expected results of using this setup, but this might contribute to future researchers who
will do this experiment with this cool room.
29
5.3 Existing Experiment
Figure 11 Results of Existing Experiment
Figure 11 above shows the daily energy consumption of another cool room in Copper Chimney
from 10th of July to 24th of September. In this experiment, COOLNOMIX was installed on 1st of
August until 8th of August and the cool room continue running on 9th of August after the
installation. The results show that the daily energy consumption during the test period (before
COOLNOMIX installation) is significantly higher than the daily energy consumption during the
control period (after COOLNOMIX installation).
The test period was assumed to be 22 days, from the 10th of July to 31st of July, the total energy
consumption during the test period is 895 kWh after calculated. In the other hand, the control
period is assumed to be 22 days also, which is 9th of August to 30th of August, the total energy
consumption during this period is calculated as 416 kWh. The results show that the cool room
saved 478 kWh of energy in total, 21.7 kWh per day during this experiment, which is around
53.5% of his original energy consumption, after installing COOLNOMIX unit.
0
10
20
30
40
50
60
70
29-Jun 9-Jul 19-Jul 29-Jul 8-Aug 18-Aug 28-Aug 7-Sep 17-Sep 27-Sep 7-Oct
ENe
rgy
Co
nsu
mp
tio
n (
kWh
)
Date
Energy consumption of Cool room Energy consumption
30
6 Economic Analysis
From all the results got in chapter 5, the payback period of a COOLNOMIX unit can be estimated
by using assumptions as follows:
Tariff – Assume Synergy Home Plan (A1) tariff is used for a typical household, and the
charges of electricity are AUD 26.4740 cents per unit (kWh); [12]
Operating hours – Assume air conditioner operates 7 days a week and 9 hours per day
(9am – 6pm). Assume refrigerator or cool room operates 7 days a week and 24 hours per
day;
Operating months – Assume air conditioner is only needed for 6 months (summer and
spring). Assume refrigerator or cool room is needed in every season;
COOLNOMIX unit price – A single COOLNOMIX unit costs around AUD 500.
Note that the assumptions made by considering cooling only air conditioners, normally cooling
only air conditioners are not used during cold weather (or switched to heating).
By using the same devices and results in chapter 5, the payback period for an AC-01 unit is 12
years, and the payback period for an AR-01 unit is 2.86 months (calculations shown in APPENDIX
B)
31
7 Conclusion
In conclusion, it can be said that the experiments achieved the project objectives. COOLNOMIX
product does save energy consumption and control the stability of the temperature by using its
ORS technology. This experiment is designed specifically with some considerations taken into
account. The experiment covers implementation in the refrigeration unit as well as air
conditioning units. Specific methodology steps were laid out and implemented to produce
reliable experimental results. The results of the experiments show that in air conditioning system,
COOLNOMIX saved 20% of the energy during cold weather and 14% of the energy during hot
weather without sacrificing the room temperature. In addition, in the existing experiment for a
cool room at the restaurant, the COOLNOMIX saved up to 53.5% of the energy and even have a
payback period of 2.86 months, which is considered as a huge success. From the result in this
thesis, it shows that COOLNOMIX is a potential energy saving product that worth investigating.
However, there are some limitations and conditions that caused these results not reliable during
the experiment such as:
No ambient temperature for the Copper Chimney experiment;
No details of cooling load for the Copper Chimney experiment;
No details of the Copper Chimney’s cool room;
The data of air conditioning system practical experiment during hot period is from a
single day.
32
8 Future Work
This chapter shows some future works that can be done to improve the depth of this project,
along with some suggestions and recommendations
8.1 Reversed Carnot Cycle
Draw a P-V diagram of Reversed Carnot Cycle is the best way to understand how a COOLNOMIX
affects the operation of the compressor and also the whole cooling system. However, in order to
draw the cycle, several monitoring devices have to be installed inside the cooling system. The
recommended method and equipment is shown as follows:
Pressure Meter – Pressure meters must be able to read the pressure of the refrigerant
(fluids/gas) inside the cooling system. Install the pressure meters at the four points of the
cooling systems, which mentioned in chapter 3.2 above. This monitoring method helps
the users to investigate what is happening with the refrigerant inside the cooling system,
and also how does the performance change with the addition of COOLNOMIX unit;
Temperature meter – Similar to the pressure meter, the temperature meters should be
installed at those four points and must be able to read the temperature of the
refrigerant.
Using the data above, the P-V diagram of Reversed Carnot Cycle can be drawn, where the volume
of refrigerant can be calculated by using ideal gas law. Meters with built-in batteries and data
loggers are recommended in this experiment to prevent wiring mess. If the next user is planning
to do this experiment in Murdoch University, it is recommended to discuss with Facilities
Management at Murdoch University to get the approval for this installation as early as possible,
because safety and ethical issues have to be considered before installing external product into
university’s property.
33
8.2 Thermal Comfort Test
In an air conditioning system, thermal comfort is always the first priority to be considered.
However, in this thesis, the experiment is prevented from dealing with the thermal comfort issues
because this is the first time Murdoch University doing the experiment with COOLNOMIX product,
Facilities Management at Murdoch University is unsure if the COOLNOMIX unit reduces the
thermal comfort of the room users. However, the next student who continues this experiment is
recommended to do the experiment in some in use classrooms or lecture theaters to test the
thermal comfort level of the air conditioner with and without the addition of COOLNOMIX.
8.3 Experiment Period
As mentioned before, Australia weather, climate and ambient temperature keep changing all over
the year, and also an air conditioner is not running if the temperature is lower than the set point
limit. It is recommended to run this project for a longer period of time (the best is over a year) to
investigate how a COOLNOMIX unit affects the performance of the air conditioners more reliably
under different types of climate in Western Australia.
34
9 References
[1]"How Much Electricity Does My Air Conditioner Use?", Canstar Blue, 2016. [Online]. Available:
http://www.canstarblue.com.au/appliances/cooling-heating/air-conditioners/how-much-electricity-does-
aircon-use/. [Accessed: 17- Nov- 2016].
[2]"Energy saving tips", Synergy, 2016. [Online]. Available: https://www.synergy.net.au/Your-home/Save-
energy/Energy-saving-tips. [Accessed: 17- Nov- 2016].
[3]"4602.0.55.001 - Environmental Issues: Energy Use and Conservation, Mar 2008", Abs.gov.au, 2008.
[Online]. Available:
http://www.abs.gov.au/AUSSTATS/[email protected]/39433889d406eeb9ca2570610019e9a5/0E43C98B32A7FE85
CA25750E00109A1D. [Accessed: 17- Nov- 2016].
[4]"Vapor-compression refrigeration", En.wikipedia.org. [Online]. Available:
https://en.wikipedia.org/wiki/Vapor-compression_refrigeration. [Accessed: 17- Nov- 2016].
[5]"Reverse Carnot Cycle Efficiency | Matt Evans", Mtdevans.com. [Online]. Available:
http://mtdevans.com/projects/physics-problems/reverse-carnot-cycle-efficiency/. [Accessed: 17- Nov- 2016].
[6]P. Michel, "Cool News", Watt Solutions, 2016. [Online]. Available:
http://www.wattsolutions.com.au/news/. [Accessed: 17- Nov- 2016].
[7]"How Coolnomix Works | OZWIDE POWER", Ozwidepower.com.au. [Online]. Available:
http://www.ozwidepower.com.au/how-coolnomix-works/. [Accessed: 17- Nov- 2016].
[8]"How COOLNOMIX® Works", Watt Solutions, 2016. [Online]. Available:
http://www.wattsolutions.com.au/how-coolnomix-works/. [Accessed: 17- Nov- 2016].
[9]"Australian Climate Averages - Maximum, Minimum & Mean Temperature maps", Bom.gov.au, 2016.
[Online]. Available:
http://www.bom.gov.au/jsp/ncc/climate_averages/temperature/index.jsp?maptype=1&period=win#maps.
[Accessed: 17- Nov- 2016].
[10]2009 ASHRAE handbook, 1st ed. Atlanta, GA.: ASHRAE, 2009.
[11]Developing an adaptive model of thermal comfort and preference, 1st ed. 1998.
[12]Maximizing sales, performance and installation instructions, 5th ed. COOLNOMIX General Guide AC-
01/AR-01, 2014.
[13]"Synergy Home Plan® (A1) tariff", Synergy, 2016. [Online]. Available:
https://www.synergy.net.au/Your-home/Energy-plans/Home-Plan-A1. [Accessed: 17- Nov- 2016].
35
10 APPENDIX
10.1 Appendix A
10.1.1 COOLNOMIX installation (AC-01)
1. The COOLNOMIX AC-01 power supply terminal is connected to the same mains source
with the air conditioner;
2. The air conditioners used in the practical experiment are controlled directly by a
mechanical thermostat, so the wiring method of the COOLNOMIX AC-01 is called Direct
Control Method, where the COOLNOMIX AC-01 control relay terminals are connected in
SERIES with the thermostat wire which control the compressor shown in Figure 12 [12]
below:
Figure 12 COOLNOMIX AC-01 wiring
36
3. The COOLNOMIX AC-01 supply air sensor is installed in the air supply outlet as close as
possible to the evaporator fin without touching it as the blue arrow shown in Figure 13;
4. The COOLNOMIX AC-01 room temperature sensor is installed in the air supply outlet as
close as possible to the evaporator fin without touching it as the red arrow shown in
Figure 13; [12]
Figure 13 COOLNOMIX AC-01 Sensors Locations
5. The COOLNOMIX AC-01 unit set point can be adjusted by following the orientation shown
in Figure 14. [12]
37
Figure 14 COOLNOMIX AC-01 Set Point Orientations
10.1.2 COOLNOMIX installation (AR-01)
1. The COOLNOMIX AR-01 power supply terminal is connected to the same mains source
with the cool room;
2. The COOLNOMIX AR-01 control relay terminals are connected as shown in Figure 15 [12]
below:
38
Figure 15 COOLNOMIX AR-01 Wiring
3. The COOLNOMIX AR-01 supply air sensor is installed inside the fins of the return air side
(usually near the bottom of the evaporator), but not touching the copper fluid pipes, only
aluminum fins, as shown in Figure 16 [12]:
39
Figure 16 COOLNOMIX AR-01 Sensor Location
4. The COOLNOMIX AR-01 room temperature sensor is placed a few inches away from the
return air side of evaporator and stay up high;
40
5. The COOLNOMIX AR-01 unit set point can be adjusted by following the orientation shown
in Figure 17; [12]
Figure 17 COOLNOMIX AR-01 Set Point Orientation
6. Note that for the COOLNOMIX AR-01:
Automatically timed defrost devices must be disabled
Timer that controls a heating coil for evaporator ice melting must be bypassed
Timer that turns off air circulation fans must be bypassed
If the existing temperature controller has a thermistor sensor for detecting ice build-
up, it can generally be left untouched, as a properly functioning AR-01 will prevent
any ice build-up, only auxiliary timers must be bypassed [12]
41
10.1.3 COOLNOMIX LED Indicator Description
COOLNOMIX LED flashing sequence and their indication is shown in table 5 [12] below:
LED flashing Sequence Phase Indication
Flashing GREEN Starting up, or Wait a minimum of 3 minutes to
gather data for start up
Gathering room
temperature and supply air
temperature data
Waiting for room temperature
and supply air temperature to
turn on the compressor
Steady GREEN with Flashing red Compressor started Waiting for the room
temperature and supply air
temperature data to be met to
turn off the compressor
Continuous RED Fault Failure detected, audible alarm
will work if activated
No LED ON Power Failure Check circuit breaker or fuse. If
air conditioner continues
running and no LED is working,
there may be a fault with
COOLNOMIX
Table 5 COOLNOMIX LED Flashing Sequence and Indication
10.2 APPENDIX B calculation
10.2.1 Payback Period (AC-01)
From the results, AC-01 saved 2.3 kWh a day and the annual saving can be calculated as:
42
And the pay pack period can be calculated as:
10.2.2 Payback Period (AR-01)
From the results, AR-01 saved 21.7 kWh a day and the annual saving can be calculated as:
And the pay pack period can be calculated as:
43
10.2.3 Appendix C
Figure 18 Model of Air conditioner for Practical Experiment
Figure 19 Model of Cool Room for Practical Experiment