intuitech pilot module

4
INTUITECH, INC. | WWW.INTUITECH.COM | [email protected] | 1.801.487.9255 SALT LAKE CITY, UTAH, USA ü Pre-fabricated equipment enclosure minimizes onsite construction ü Ideal for Design-Build Projects ü Designed specifically for Intuitech pilot modules but can be adapted for other equipment ü Standard design complies with 2018 IBC for wind load, snow load, and seismic conditions for most locations ü Integrated piping and electrical corridor below floor level for connecting equipment ü Exterior electrical disconnect panel allows for a single electrical connection ü Interior electrical distribution panel with NEMA 4 rating ü Washdown-rated LED interior lighting ü Outdoor-rated LED exterior lighting ü Structural members constructed of hot- dipped galvanized steel for durability ü Walls and ceiling constructed of architectural metal-clad insulated panels ü Insulated floor with slip-resistant seamless Vinyl covering ü Optional laboratory module includes cabinets, chemically resistant countertop with 120V outlets, sink, and water heater Pilot Module Enclosure Intuitech Think it. Test it. Do it. R

Upload: others

Post on 10-Dec-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Intuitech Pilot Module

INTUITECH, INC. | WWW.INTUITECH.COM | [email protected] | 1.801.487.9255

SALT LAKE CITY, UTAH, USA

ü Pre-fabricated equipment

enclosure minimizes onsite

construction

ü Ideal for Design-Build Projects

ü Designed specifically for Intuitech

pilot modules but can be adapted

for other equipment

ü Standard design complies with

2018 IBC for wind load, snow load,

and seismic conditions for most

locations

ü Integrated piping and electrical

corridor below floor level for

connecting equipment

ü Exterior electrical disconnect panel

allows for a single electrical

connection

ü Interior electrical distribution panel

with NEMA 4 rating

ü Washdown-rated LED interior lighting

ü Outdoor-rated LED exterior lighting

ü Structural members constructed of hot-

dipped galvanized steel for durability

ü Walls and ceiling constructed of

architectural metal-clad insulated panels

ü Insulated floor with slip-resistant seamless

Vinyl covering

ü Optional laboratory module includes

cabinets, chemically resistant countertop

with 120V outlets, sink, and water heater

Pilot Module Enclosure

IntuitechThink it. Test it. Do it.

R

Page 2: Intuitech Pilot Module

All information presented in this data sheet is for configuration code E401112-2ED-0SD-1PS-HVAC-SVN.

See ordering section for other configurations.

Specifications

Voltage

Shipping Dimensions

Snow Load Design

Seismic Design

Outside Dimensions

240 / 480 V

Enclosure Empty Weight

41.8 X 11.0 X 11.5 ft

Maximum Equipment Weight

25500 lbs 11567 kg

40000 lbs 18144 kg

75 lbs/sf (ground), 55 lbs/sf (flat roof)

Ss:1.5, S1:0.6, Sds:1.2, Sd1:0.68, Class:D

42.9 X 11.0 X 11.5 ft 13062 X 3353 X 3508 mm

Frequency 60 Hz

12717 X 3353 X 3508 mm

Electrical Supply Single Phase

Wind Load Design 135 mph (3 sec gust, ultimate basis), Exposure Category C

Inside Dimensions 39.0 X 10.0 X 10.0 ft 11887 X 3048 X 3048 mm

Maximum Current 62.5 / 31.2 A

Equipment Configuration

End Door Clearance Height 95.2 in 2418 mm

End Door Clearance Width 70.5 in 1791 mm

10 GPM (38 L/min) Systems

§ Flocculation/Sedimentation Module

§ Ozonation Module (1 train)

§ Granular Media Filtration Module (4 filters)

§ Dissolved Air Flotation Module

§ Ozonation Module (1 train)

§ Granular Media Filtration Module (4 filters)

§ Flocculation/Sedimentation Module

§ Granular Media Filtration Module (4 filters)

§ Laboratory Module

§ Dissolved Air Flotation Module

§ Granular Media Filtration Module (4 filters)

§ Laboratory Module

§ Flocculation/Sedimentation Module

§ Dissolved Air Flotation Module

§ Granular Media Filtration Module (4 filters)

50 GPM (190 L/min) Systems

§ Flocculation/Sedimentation Module

§ MF/UF Module

A standard 40 foot (12.2 m) enclosure will accept the following common

configurations. Contact Intuitech for other configurations.

Page 3: Intuitech Pilot Module

1

Membrane Roof

2

Lifting Point

3 Rain Gutter

4 Hooded Air Intake

5

Alarm Beacon

7

Entry / Egress Door

8

9 Hooded Exhaust Fan

13

Transformer

14 Interior Lighting

15

Elec. Corridor (below floor)16

Piping Corridor (below floor)

10

HVAC Unit

11

Electrical Disconnect Panel

17

Piping Connection Port

General Arrangement Drawings

Dimensions: feet [mm]

6

Exterior Lighting

12

Signal Panel

FRONT VIEW

BACK VIEW

RIGHT VIEW

LEFT VIEW

TOP SECTION VIEW RIGHT SECTION VIEW

3

4

3

9

2 11

5

6

7

Electrical Distribution Panel

8

10

11

12

14

14

1517

7 13

151617

16

16

Page 4: Intuitech Pilot Module

Version 10.8.20 © 2020 Intuitech, Inc. – All rights reserved

Our standard pilot enclosure can be configured as shown below. It can also be customized to meet specific requirements for

an additional cost. Please contact Intuitech for more information.

Ordering

E

Width: 10, 11, 12 (feet)Height: 12 (feet)

Options:HVAC (heating/air conditioning)SVN (supplemental ventilation)PLC (programmable controller)CSB (cellular signal booster)LAB (laboratory module)

End Door: 0 (none), 1 (single door), 2 (double door), 3 (roll-up door)Side Door: 0 (none), 1 (single door), 2 (double door), 3 (roll-up door)

Length: 20, 30, 40 (feet)

-- E D - S D - P S

Power Source: 1 (single phase 240/480V), 3 (three phase 480V)

FWS (folding wall shelves)SMD (smoke detectorOZD (ozone gas detector)HSD (H2S gas detector)CLD (chlorine gas detector)

Wall-mount HVAC unit including a 2.5 ton air conditioner, a 5 kW heater, and a

barometrically-operated fresh air damper capable of introducing outdoor air at a flow

rate of 300 CFM (510 m3/hr), complying with IMC 2015 for occupied spaces.

HVAC

SVN

PLC

CSB

LAB

FWS

SMD

OZD

HSD

CLD

Supplemental ventilation system includes a variable speed exhaust fan with a

maximum flow rate of 1350 CFM (2294 m3/hr), a removable/washable intake screen,

barometrically-operated intake and exhaust shutters, and stainless steel rain hoods.

Programmable Logic Controller (PLC) and Human-Machine Interface (HMI) installed in

the power distribution panel. Used for automating enclosure control functions such as

closing an inlet valve when a pipe fails or turning on the supplemental ventilation fan

when an ambient gas concentration exceeds defined safety limit.

Cellular signal booster/repeater and omnidirectional antenna installed on the interior

and a Yagi directional antenna installed on the exterior. The medal-clad wall panels of

the enclosure reduce cellular signal strength significantly. This option will boost the

cellular remote access units on pilot modules as well as personal cell phones.

Laboratory grade cabinets with a chemical resistant phenolic countertop, sink and

faucet, under-the-sink electric water heater, and GFCI-protected power strip. Standard

lengths are 4 feet (1219 mm), 6 feet (1829 mm), and 8 feet (2438 mm) long.

Eight 46 inch (2268 mm) long by 12 inch (305 mm) deep stainless steel shelves

attached to the interior walls. Shelves fold flush into wall when not in use.

Smoke detector triggers an audible alarm when smoke is detected. When included

with the PLC option the pilot skids will automatically shutdown and an alarm will be

annunciated on the exterior beacon and transmitted by text or email.

Gas detectors display ambient gas concentration. When included with the SVN and

PLC options and the concentration exceeds the exposure limit, the pilot skids will

shutdown, the exhaust fan will run at the maximum flow rate, and an alarm will be

annunciated on the exterior beacon and transmitted by text or email.

Options