introduction protection
TRANSCRIPT
-
7/30/2019 Introduction Protection
1/15
Relay coil
Trip coil
CBCT
PT
Protection
-
7/30/2019 Introduction Protection
2/15
Main Features of Good Protective System
Reliability: It is defined as the probability that the system will functioncorrectly when required to act. It has two aspects (i) The system must
operate in the presence of a fault that is within its zone of protection and(ii) It must refrain from operating unnecessarily for faults outside its
protective zone or in the absence of a fault. A quantitative measure for
reliability is defined as follows:
-
7/30/2019 Introduction Protection
3/15
2 Security: security is a property used to characterize false
tripping on the relays. A relay is said to be secure if itdoes not trip when it is not expected to trip. It is the
degree of certainty that the relay will not operate
incorrectly:
-
7/30/2019 Introduction Protection
4/15
3 Sensitivity:
The protective system must have ability to detect the
smallest possible fault current. The smaller the currentthat it can detect, the more sensitive it is. One way to
improve sensitivity is to determine characteristic
signature of a fault. It is unique to the fault type and itdoes not occur in the normal operation.
For example, earth faults involve zero sequence current.
This provide a very sensitive method to detect earthfaults. Once, this signature is seen, abnormality is rightly
classified and hence appropriate action is initialized.
-
7/30/2019 Introduction Protection
5/15
4. Selectivity
It refers to the overall design of protective strategy wherein onlythose protective devices closest to a fault will operate to removethe faulty component. This implies a grading of protective device
threshold, timing or operating characteristics to obtain the desiredselective operation.
A relay should not confuse some peculiarities of an apparatus with afault. For example, transformer when energized can draw up to 20times rated current (inrush current) which can confuse, both overcurrent and transformer differential protection. Typically, inrush
currents are characterized by large second harmonic content.
-
7/30/2019 Introduction Protection
6/15
This discriminant is used to inhibit relay operationduring inrush, there by, improving selectivity in
transformer protection. Also, a relay should be smart enough, not just to
identify a fault but also be able to decide whether
fault is in its jurisdiction or not. For example, a relay for a feeder should be able to
discriminate a fault on its own feeder from faults on
adjacent feeders. This implies that it should detectfirst existence of fault in its vicinity in the system andthen take a decision whether it is in its jurisdiction.
-
7/30/2019 Introduction Protection
7/15
5.Dependability:
A relay is said to be dependable if it trips only when it is expected to trip. This
happens either when the fault is in it's primary jurisdiction or when it is
called upon to provide the back-up protection. However, false tripping ofrelays or tripping for faults that is either not within its jurisdiction, or
within its purview, compromises system operation. Power system may get
unnecessarily stressed or else there can be loss of service. Dependability is
the degree of certainty that the relay will operate correctly:
-
7/30/2019 Introduction Protection
8/15
A relay's zone of protection is a region defined by relay's jurisdiction. It is
shown by demarcating the boundary. This demarcation for differential
protection is quite crisp and is defined by CT's location. On the other hand,such boundaries for overcurrent and distance relays are not very crisp. It is
essential that primary zones of protection should always overlap to ascertain
that no position of the system ever remains unprotected. This overlap also
accounts for faults in the circuit breakers. To provide this overlap additional
CTs are required
Zone of Protection
-
7/30/2019 Introduction Protection
9/15
Terms Connected with Relays:
Operating torque: It is the torque which tends to close the contacts of the
relay.
Restraining torque: It is the torque which opposes the operating torque.
Pick up: It is defined as the threshold value of current, voltage etc. above
which relay will close its contact.
Reset: It is defined as the value of current, voltage etc. below which therelay will open its contacts and return to normal position.
Flag or Target: It is a device which indicates the operation of a relay.
Plug Setting Multiplier (PSM): It is the ratio of fault current in relay coil
to pick up current
PSM=Primary current
Relay Current setting CT ratio
-
7/30/2019 Introduction Protection
10/15
Classification of Relay
1. According to the function in the
protection scheme.(a) Main Relay: Responds to when any change in theactuating quantity .
(b) Auxiliary Relay: Controlled by other relay to performsome auxiliary function such as introduction of a delay,increasing number of contacts, passing a signal fromone relay to another, energizing a signal or an alarm
etc.(c) Signal relays: They function to register the operation
of some relay by flag indication, simultaneously it canalso actuate an audible alarm circuit.
-
7/30/2019 Introduction Protection
11/15
(2) According to their construction and
principle of operation:(a) Electromagnetic Attraction type: Operation depends
on the movement of an armature under the influence of
attractive force due to magnetic field set up by current
flowing through relay winding.
(b) Electromagnetic Induction type: operation depends
on the movement of a metallic disc or cylinder free torotate by the interaction of induced eddy currents and
the alternating magnetic field producing them.
-
7/30/2019 Introduction Protection
12/15
(c) Thermal Relays: Movement depends upon the actionof heat produced by the current flowing through the
element of the relay.
(d) Gas Operated Relays: It operates when a specified
amount of gas has accumulated.
(e) Static Relays: Semiconductor devices such as diodes,transistors, ICs etc. are used.
(f) Microprocessor based Relays: These relays are built
on the central processing unit like computers and varietyof functions can be achieved by mathematical
calculations based on algorithms.
-
7/30/2019 Introduction Protection
13/15
(3) According to applications:(a) Under / Over voltage, Under / Over current, under /
over freq. etc.
(b) Directional Relays: operation takes place when theapplied voltage and current assume a specific phase
displacement.
(c) Differential Relay: operation occurs at some specificphase and magnitude difference between two or more
electrical quantities.
(d) Distance Relay: Operation depends upon the ratio ofvoltage to current.
-
7/30/2019 Introduction Protection
14/15
(4) According to their time of operation(a) Instantaneous Relays: Operation occurs after a
negligibly small interval of time from the incidence of
the current or other actuating quantity which causesoperation.
(b) Definite time lag Relay: Operation takes place afterfixed time delay.
(c) Inverse time lag relay: Time of operation is inverselyproportional to magnitude of current or other quantitycausing operation.
(d) Inverse Definite Minimum Time (IDMT) lag Relay :The time of operation is inversely proportional to smaller
values of actuating quantity and tends to a minimumtime as the value increases without limit.
-
7/30/2019 Introduction Protection
15/15
(5) According to Number of operating
Quantities:(a) Single quantity relay
(b) Two quantity relay
(c) Multi quantity relay