Unified Thermal and Power Management in Server Enclosures
Niraj Tolia, Zhikui Wang, Manish Marwah, Cullen Bash, Parthasarathy Ranganathan, Xiaoyun Zhu*
*Now at VMware
![Page 2: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/2.jpg)
2005: $26.5 Billion
![Page 3: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/3.jpg)
“The cost of power and cooling is likely to exceed that of hardware…”
- Luiz Barosso, Google
![Page 4: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/4.jpg)
“In the data center, power and cooling costs more than the IT equipment it supports.”
- Christian L. Belady, Microsoft (former HP)
![Page 5: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/5.jpg)
Zephyr• Unified Power and Cooling Management
Contributions• Demonstrate how to do per-blade cooling• Save both cooling (21--30%) + system power (23--29%)
• Without impacting performance
![Page 6: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/6.jpg)
Compact DesignDense Compute and Storage
Blade Servers:
Workloads are Virtualized
![Page 7: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/7.jpg)
Compact DesignDense Compute and Storage
Blade Servers:
Workloads are Virtualized
![Page 8: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/8.jpg)
Web ServerOS
Hardware
Virtualization:
![Page 9: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/9.jpg)
VM MonitorHardware
Virtual Machine
WebServerOS
Virtualization:
![Page 10: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/10.jpg)
Virtual Machine
WebServerOS
OSVM MonitorHardware
VM MonitorHardware
Virtual Machine
App ServerOS
Virtualization:
![Page 11: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/11.jpg)
Virtual Machine
WebServerOS
OSVM MonitorHardware
VM MonitorHardware
Virtual Machine
App ServerOS
Virtualization:
![Page 12: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/12.jpg)
Virtual Machine
WebServerOS
OSVM MonitorHardware
VM MonitorHardware
Virtual Machine
App ServerOS
Virtualization:
![Page 13: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/13.jpg)
CPU P-states BladeEnclosure
PowerUtil
Temp.Zephyr
Min.Power
Tref
Utilref
Models
Fan Speed
VM Migr.Blade On/Off
Power ModelsTemperature Models
![Page 14: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/14.jpg)
0
50
100
150
200
250
0 20 40 60 80 100
Pow
er (
W)
Utilization
Power - P0Power - P4Power Model - P0Power Model - P4
Power Model: Single Blade
![Page 15: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/15.jpg)
Power Model: Single Fan
0 6000 12000 180000
50
100
150
200
Speed (RPM)
Pow
er (W
)
Measured Fan PowerFan Power Model
![Page 16: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/16.jpg)
Unfortunately, temperature models are significantly more complex.
Models don’t existsMany things affect temperatureInsufficient sensors in servers
Zonal Variations
![Page 17: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/17.jpg)
Fan No.
Blad
e N
o.
1 2 3 4 5 6 7 8 9 10
123456789
10111213141516
Zonal Variation: Fan Influence
![Page 18: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/18.jpg)
Temperature Models• Steady State Model−Assumes workloads, ambient environment is constant
• Transient Model−Finer-grained control in real-world environments
![Page 19: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/19.jpg)
Temperature Models• Steady State Model−Assumes workloads, ambient environment is constant
• Transient Model−Finer-grained control in real-world environments
![Page 20: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/20.jpg)
ZephyrBlade
Enclosure
PowerUtil
Temp.
Min.Power
Tref
Utilref
Models
Fan SpeedCPU P-statesVM Migr.
Blade On/Off
![Page 21: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/21.jpg)
ZephyrBlade
Enclosure
PowerUtil
Temp.
Min.Power
Tref
Utilref
Models
Fan SpeedCPU P-statesVM Migr.
Blade On/Off
FC
ECGC
![Page 22: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/22.jpg)
Group Controller (GC)• Goal: Minimize Power(Enclosure)
• Changes state every 10 minutes• Monitors Utilization, Inlet Temperature• Uses two-step optimization−Simulated Annealing for space search−Convex Optimization for Fan Cost + Blade Power Model
![Page 23: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/23.jpg)
Experimental Setup
Storage Array
Controller
Temp and Util. DataVM Migration
Fan Speed Control
16 Blades (4 cores)5 P-States
10 Fans, 64 Xen VMs
![Page 24: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/24.jpg)
0
50
100
150
200
250
300
IT
Pow
er (W
)Static Integral Predictive Zephyr Zephyr + On/Off
Cooling Power Savings
626
![Page 25: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/25.jpg)
System Power Savings
0
500
1000
1500
2000
2500
3000
3500
4000
IT
Pow
er (W
)Static Integral Predictive Zephyr Zephyr + On/Off
![Page 26: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/26.jpg)
Simulated Servers
239
34
68
102
136
170
204
120
154
190
222
256
290
0
50
100
150
200
250
300
0 20 40 60 80 100
Power Usage (W
)
Utilization
Real
EnergyProportional
PracticalNext-Gen
![Page 27: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/27.jpg)
Simulation: Tamb+15C &13 servers types
![Page 28: InterPack '09 ASME/Pacific Rim Technical Conference and Exhibition](https://reader034.vdocuments.us/reader034/viewer/2022051405/58a2d7071a28ab90228c1c08/html5/thumbnails/28.jpg)
Conclusions• Zephyr combines:−Concepts from Heat Transfer Theory with Systems
• Unified power and cooling management can save:−30% Cooling Power−29% Enclosure Power
Full Length Papers:www.hpl.hp.com/personal/Niraj_Tolia/