Integrated Smart Grid Performance Testing Jerry FitzPatrick and Tom Nelson National Institute of Standards and Technology Applied Electrical Metrology Group i-PCGRID March 29, 2017

Upload: others

Post on 20-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

Integrated Smart Grid Performance Testing

Jerry FitzPatrick and Tom NelsonNational Institute of Standards and Technology

Applied Electrical Metrology Group

i-PCGRID March 29, 2017

Page 2: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

2

Energy Independence and Security Act

NIST has “primary responsibility to coordinate development of a

framework that includes protocols and model standards for information management to achieve

interoperability of smart grid devices and systems…”

Page 3: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

An integrated Approach to Smart Grid Testing

• Performance + interoperability

• Multidisciplinary – combines expertise of different NIST projects and laboratories to work together on multiple aspects of Smart Grid R&D— high-power inverters and power conditioning systems

— microgrid operational interfaces

— PMUs, smart sensors

— cybersecurity

— advanced networks

— smart meters

3

Page 4: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

Virtual Instrument Computer

with Network and IEEE 488 Bus

Cards

Microgrid Controller, Interconnection, PCS

Under Test

LAN

Probes

Microgrid Interoperability Testbed

AC/DC Load Emulators

3 X 4.5 kW, 500 V (nonlinear, motor,

reactive, rectifier, …)

Microgrid

Controller, ESI, EMS

Power, Data, Meter options

LAN

IEEE 488

)))

Regenerative DC Emulators:

PV, Bat, DC Server

3 X 12 kW 600 V + 3 X 12 kW 120 V

Regenerative AC Grid Emulator

120 kW (phase, harmonics, transient faults, …)

SCADA

Battery Storage System Under Test

Power Electronics, Relays,

Sensors, Data Acquisition

Oscilloscope and

Network Analyzer

Utility

Network

Emulator

& DMS

Grid, Backup Gen, or CHP Emulators

3 X 12 kW (phase, harmonics, transient faults, …)

Other Smart Grid Generators,

Storage, Loads

Power wires

EMC

Storage EMS

EVSE or CES

Allen Hefner (NIST)4

NIST Smart Grid Testbed

Page 5: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

SGIP Smart Grid Interoperability

NISTMeasurement

Science

DOE/DOD Labs,Test & Certification

ESI, EMS, Microgrid& Storage functions

Virtual Instrument Computer

with Network and IEEE 488 Bus

Cards

Microgrid Controller, Interconnection, PCS

Under Test

LAN

Probes

Microgrid Interoperability Testbed

AC/DC Load Emulators

3 X 4.5 kW, 500 V (nonlinear, motor,

reactive, rectifier, …)

Microgrid

Controller, ESI, EMS

Power, Data, Meter options

LAN

IEEE 488

)))

Regenerative DC Emulators:

PV, Bat, DC Server

3 X 12 kW 600 V + 3 X 12 kW 120 V

Regenerative AC Grid Emulator

120 kW (phase, harmonics, transient faults, …)

SCADA

Battery Storage System Under Test

Power Electronics, Relays,

Sensors, Data Acquisition

Oscilloscope and

Network Analyzer

Utility

Network

Emulator

& DMS

Grid, Backup Gen, or CHP Emulators

3 X 12 kW (phase, harmonics, transient faults, …)

Other Smart Grid Generators,

Storage, Loads

Power wires

EMC

Storage EMS

EVSE or CES

Allen Hefner (NIST)5

NIST Smart Grid Testbed

Page 6: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

SGIP Smart Grid Interoperability

NISTMeasurement

Science

DOE/DOD Labs,Test & Certification

ESI, EMS, Microgrid& Storage functions

IT Networks, Cyber Security,EMC, Sensors & Smart Meters

Power ElectronicInterconnection

Equipment

Grid-InteractiveMicrogrid, DER & Smart Appliances

Virtual Instrument Computer

with Network and IEEE 488 Bus

Cards

Microgrid Controller, Interconnection, PCS

Under Test

LAN

Probes

Microgrid Interoperability Testbed

AC/DC Load Emulators

3 X 4.5 kW, 500 V (nonlinear, motor,

reactive, rectifier, …)

Microgrid

Controller, ESI, EMS

Power, Data, Meter options

LAN

IEEE 488

)))

Regenerative DC Emulators:

PV, Bat, DC Server

3 X 12 kW 600 V + 3 X 12 kW 120 V

Regenerative AC Grid Emulator

120 kW (phase, harmonics, transient faults, …)

SCADA

Battery Storage System Under Test

Power Electronics, Relays,

Sensors, Data Acquisition

Oscilloscope and

Network Analyzer

Utility

Network

Emulator

& DMS

Grid, Backup Gen, or CHP Emulators

3 X 12 kW (phase, harmonics, transient faults, …)

Other Smart Grid Generators,

Storage, Loads

Power wires

EMC

Storage EMS

EVSE or CES

Allen Hefner (NIST)6

NIST Smart Grid Testbed

Page 7: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

PAP 24: Microgrid Operational Interfaces

Task 5: Smart Microgrid ControllerInformation Models

IEC 61850 Series:CIM, MultiSpeak

Task 4: Regulatory Framework

a) State

b) Federal

c) NARUC

Task 0:Scoping Document

Define microgridstandards needs

Task 1: Use Cases:Functional + Interactive

EPRI DERMSDefine requirements

for different scenarios

Task 6: Microgrid Controller and Interconnection Equipment Test

Controller Test – IEEE P2030.8; Info exchange; Interconnection;

Safety; System Impact

Task 3: Unified microgrid-EMS controller standard

Task 2: Microgrid Interconnection standard for grid-interaction

Info exchanges Requirements

IEEE 1547 Series

IEEE P2030.7

Allen Hefner (NIST)

7

Page 8: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

8

• Grid is highly distributed and complex—Increasing diversity of device, resource, and control

• Uncertainty is growing—Growing numbers and increasing dynamics of variables lessen

the likelihood of well-behaved, predictable system

—Legacy models and tools incapable of addressing the growing uncertainty

• Progress needed across multiple dimensions—New grid models

—Networked measurements

—Diversified applications

—Expanding customer base

Uncertainty is a dominant challenge

Page 9: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

9

Uncertainty representation in sensor standards

Dynamic State Estimation Additive White Gaussian models

Monitoring and Protection Confidence intervals

Fault Localization Bayesian inference

Harmonic Estimation Mixed Gaussian models

Load modeling Markov models

Parameter estimation Set theoretic models

Closed loop control of feeders Stochastic optimization

There are several applications being considered for PMUs in the distribution circuit. Each of these applications use a different representation of uncertainty.

PMU standards currently specify the error budget for the sensor but there is no explicit measure of uncertainty.

Differentiating error vs. uncertainty and formally specifying uncertainty of sensor measurements and corresponding models will greatly aid in the ability of designers and operators to propagate uncertainty through multiple interacting components and to develop confidence in system level performance.

Vp

2

✓PE

M E

Page 10: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

10

Characterizing cyber vulnerabilities by physical impact

Human

Operators

SCA

DA

Mas

ter

SCA

DA

Mas

ter

Control Center

RTU RTU

PMUs

WAMPAC PDC

Power System

Bad

Dat

a D

etec

tor

When sensors or sensor aggregators

are attacked, the primary impact of the

attack is on the state estimator.

Inaccurate state estimates in turn may

result in bad control decisions.

Attacker Model and Bad Data Detection in Control Center

• Scenario: Attacker injects malicious data a to corrupt analog measurements in the power grid

• First characterize the set of undetectable malicious data a

Page 11: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

11

• Right figure shows QoSrequirements for a set of applications identified in the OpenSG Smart Grid Requirements matrix, as an outcome of Smart Grid Interoperability Panel (SGIP) Priority Action Plan 2 (PAP02)

• This calls for the study of future network technologies and architectures (5G, etc.) to support smart grid and other CPS

Varying QoS Requirements for Smart Grid Applications

Figure: Major Smart Grid Use Cases, Categorized by Latency and Reliability Requirements David Griffith,

Michael Souryal, and Nada Golmie (NIST), “Wireless Networks for Smart Grid Applications,” Chapter in

Book, Titled “Smart Grid Communications and Networking,” Cambridge University Press,

UK, 2012, ISBN: 9781107014138

Use CasesCMSG: Customer Information / Messaging

DDCS: Dispatch Distributed Customer

Storage

DRDLC: Demand Response-Direct Load

Control

DSDRC: Demand Response-Centralized

Control

FCIR: Fault Clear, Isolation, and Reconfigure

FDAMC: Field Distribution Automation

Maintenance-Centralized Control

FPU: Firmware/Program Update

IDCS: Islanded Distributed Customer Storage

ME: Meter Events

MR: Meter Reading

ORM: Outage Restoration Management

PHEV: Plug-in Hybrid Electric Vehicle

PNA: Premise Network Administration

PP: Prepay Price

SS: Service Switch

VVC: Volt/VAR-Centralized Control

Page 12: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

• Synchrometrology is the scientific study of time-synchronized measurement.

• The NIST Synchrometrology Lab supports U.S. competitiveness and economic security through research and standards development in the field of time synchronized measurements in electric power generation, transmission, and distribution.—Co-funded by Departments of Commerce

and Energy.

• Ongoing Projects:—Reducing measurement uncertainty in

preparation for future requirements.

—Collaborate in the assessment of the impact of errors in synchronized measurement on power system applications.

—Collaborate in development of voluntary consensus standards and guides:• IEEE Standards Association

• International Electrotechnical Commission.

—Collaborate in the development of conformity assessment methods.

Synchrometrology for the electric power system

12

Page 13: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

13

• Two years ago, NASPI formed thePMU Applications RequirementsTask Force—NASPI-wide, about 40 members

PMU Application Requirements

• NASPI, NIST, and PNNL collaborated on a white paper which is published by NASPI today. Provides guidelines and terminology for assessing application needs

• Work is in progress at NIST, collaboratingwith PNNL, WSU, GE, BPA and othervendors, academics, and utilities tocreate an open source composableapplication testing framework.

Framework front panel and Visualization App

Page 14: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

14

• Models are relied upon throughout the power system.

• We compare measurements of “actual values” against model predictions to help validate the model—But how actual are the “actual values?”

• And how bad can they be before there is a problem?

Model Validation

Credit: Sandia National Laboratory

• NERC requires models to be validated– Many policies, reports and papers have

been published on the topic.

• What is the impact of synchronized measurement error on model validation?

Page 15: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

15

• GPS is known to be vulnerable to unintentional or intentional interference.

• If time sync becomes mission critical it must have redundant and differently routed sources.

Alternatives to GPS for wide area time distribution

Credit: Resilient Navigation and Timing Foundation

NIST-Microsemi-CenturyLink PTP over Fiber

WWVB

Alternative sources• GPS is known to be vulnerable to unintentional or intentional interference.

• If time sync becomes mission critical it must have redundant and differently routed sources.

Page 16: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

16

Conformance and Interoperability TestingIncreasing Interoperability

PICS

Certification Test Specification• Plug-fests

Certification Test Harness• Conformance

Tests

Interoperability Tests• Interop Test System• Deployment testing

• Collaborate with industry to accelerate the development of test programs for smart grid standards• Support industry test programs through test methods development• Participate in plug-fest and interoperability test events• Build awareness and encourage adoption of test programs to enhance interoperability

Source: Bob Noseworthy, et. al Draft 1588 Power Profile Conformance Test Suite Specification. University of New Hampshire Interoperability Lab.

Page 17: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

17

• NIST supports PMU conformity assessment by establishing traceability for IEEE ICAP Conformity Assessment Program

Conformity Assessment & Traceability

Yi-hua Tang, JosephsonArray and Zener Diode Richard Steiner, Multimeter

Calibration System

Jerry Stenbakken calibratingThe PMU Calibrator Calibration System

Ya-Shian Li-Baboud, TimingSource Calibration

Steve Jefferts and Tom Heavener, NIST-F2 Cesium fountain atomic clock Allen Goldstein, taking a break from

calibrating calibrators

Page 18: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

Thank you!

18

Page 19: Integrated Smart Grid Performance Testing...Mar 29, 2017  · Microgrid Interoperability Testbed AC/DC Load Emulators 3 X 4.5 kW, 500 V (nonlinear, motor, ]À U ](] UY Microgrid Controller,

NBS, NIST, and the development

of the electric power industry