A: Model number B: Serial number C: Refrigerant D: Supply voltage & Locked rotor current E: Housing service pressure F: Factory charged lubricant G: Compressor frequency & Max Must trip cur- rent The compressor must only be used for its designed purpose(s) and within its scope of application (refer to «operating limits»). Consult Application guidelines and datasheet available from http://cc.danfoss.com Under all circumstances, the EN378 (or other applicable local safety regulation) requirements must be fulfilled. The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.7 bar) and hence cannot be connected as is; refer to the «assem- bly» section for further details. The compressor must be handled with caution in the vertical position (maximum offset from the vertical : 15°) E F C D A B G 15 20 25 30 35 40 45 50 55 60 65 70 -30 -25 -20 -15 -10 -5 0 5 10 15 20 30 - 90 Hz T C (°C) T 0 (°C) 50 - 90 Hz 50 - 90 Hz SH=6K Oil injection control valve Oil injection control assembly Oil injection control dismantling Remove the clip-on coil by using a screw driver. FRCC.EI.005.A3.02 © Danfoss Commercial Compressors 09/10 1 220V 2 A max Put the clip-on coil (1) with the gasket (2) over the valve body (3) on the compressor 4 5 6 32 1 Attach the connector (4) to the coil using the delivered accessories (5) and (6). Wire the connector as indicated. INSTRUCTIONS VSH COMPRESSORS R410A

Upload: others

Post on 09-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: InstruCtIons VsH ComprEssors · 2019-05-02 · 1 - Introduction These instructions pertain to the VSH Variable Speed scroll compressors used for A/C systems. They provide necessary

A: Modelnumber

B: Serialnumber

C: Refrigerant

D: Supplyvoltage&Lockedrotorcurrent

E: Housingservicepressure

F: Factorychargedlubricant

G: Compressorfrequency&MaxMusttripcur-

rent

Thecompressormustonlybeusedforitsdesigned purpose(s) and within its scope ofapplication(referto«operatinglimits»).ConsultApplicationguidelinesanddatasheetavailablefromhttp://cc.danfoss.com

Under all circumstances,theEN378(orotherapplicablelocal safety regulation)requirements must befulfilled.

The compressor is delivered undernitrogen gas pressure (between 0.3and 0.7 bar) and hence cannot beconnectedasis;refertothe«assem-bly» sectionforfurtherdetails.

The compressor must behandled with caution in thevertical position (maximumoffsetfromthevertical:15°)

E

F

C

D

A

B

G

15

20

25

30

35

40

45

50

55

60

65

70

-30 -25 -20 -15 -10 -5 0 5 10 15 20

30 - 90 HzT C(°

C)

T0 (°C)

50 -

90 H

z

50 - 90 Hz

SH=6KOilinjectioncontrolvalve

Oilinjectioncontrolassembly

Oilinjectioncontroldismantling

Removetheclip-oncoilbyusingascrew

driver.

FRCC.EI.005.A3.02©DanfossCommercialCompressors09/101

220V

2 A max

Puttheclip-oncoil(1)withthegasket(2)over

thevalvebody(3)onthecompressor

4 5 63 2 1

Attachtheconnector(4)tothecoilusingthe

deliveredaccessories(5)and(6).

Wiretheconnectorasindicated.

InstruCtIonsVsH ComprEssors

r410A

Page 2: InstruCtIons VsH ComprEssors · 2019-05-02 · 1 - Introduction These instructions pertain to the VSH Variable Speed scroll compressors used for A/C systems. They provide necessary

2 FRCC.EI.005.A3.02©DanfossCommercialCompressors09/10

Basic connections

- Depending on the frequency converter

version, the physical position of individual

connectorsmaydifferfrombelowdiagram.

- Alwaysmakesurethatthecompressortermi-

nalsT1,T2,T3areconnectedtothefrequency

converterterminals96,97,98respectively.

- Thecompressormotorcablemustbeshielded

andthearmouredpartmustbeconnectedto

groundonbothcableends;atthesideofthe

compressor and at the side of the frequency

converter.

- UseanEMCcableglandforcableinstallationand

perfectgrounding;Themetallicterminalboxof

thecompressorhasapaint-freesurfacearound

theconnectionholeforbetterconductivity.

- A low pressure safety switch is mandatory to avoid compressor vacuum operation.

- Atstart-up,verfiythatthecompressorrotates

intherightdirectionandpumps.

230 V~

2 A maxRE

LAY

1

L1 91 L1 W 98 T3L2 92 L2 V 97 T2L3 93 L3 U 96 T1

95 PE PE 99

39 39 Ana out COM42 42 Ana out +50 50 Ana in +10 V NC 0353 53 Ana in 0 ± 10 V NO 0254 54 Ana in 0 ± 10 V COM 0155 55 Ana in COM

NC 06NO 05

12 12 +24V COM 0413 13 +24V18 18 Dig in19 19 Dig in27 27 Dig in/out29 29 Dig in/out32 32 Dig in N- RS485 69 6933 33 Dig in P+ RS485 68 6820 20 Dig in COM COM RS485 61 6137 37 Dig in

RE

LAY

2CDS3

02Legends:Ana: Analogue

Dig: Digital

in: Input

out: Output

COM: Common

NC: Normally-closed

NO: Normally-open

Openloop Processloop91,92,93: 3Phasemainsinput X X95: Earth X X39,42 Analogueoutput - -50: Analogueinput - -53: PLC+(0to10V) X -54: Sensor- - X55: PLC- X -12: HP/LPswitch X X12: ExternalOn/Off(NO) X X13: Factorybridgedto37 X X13: Sensor+ - X18: ExternalOn/Off(NO) X X19: Digitalinput - -27: HP/LPswitch(NC)/safetydevices X X29: Digitalinput/output - -32,33 Digitalinput - -20: DigitalinputCommon - -37: Factorybridgedto13 X X98: TocompressorterminalT3 X X97: TocompressorterminalT2 X X96: TocompressorterminalT1 X X99: Tocompressorearthconnection X X02,01: Relay1tooilsolenoidvalve X X06,05,04: Relay2 - -69,68: RS485Bus - -61: RS485BusCommon - -

- Optionalconnection X :Mandatoryconnection

TheCDS302frequencyconverterisfactorypre-

set with parameters for the open loop control

principle. The process loop control principle

canbeselectedbychangingparametersinthe

«Quickmenu».

Open loop:0-10Vcontrol

Frequencyconverterinslavemode

Process loop:

4-20mAcontrol

FrequencyconverterunderownPIDcontroller

Instructions

Page 3: InstruCtIons VsH ComprEssors · 2019-05-02 · 1 - Introduction These instructions pertain to the VSH Variable Speed scroll compressors used for A/C systems. They provide necessary

1-IntroductionThese instructions pertain to the VSH VariableSpeedscrollcompressorsusedforA/Csystems.They provide necessary information regardingsafetyandproperusageofthisproduct.

2–Handlingandstorage • Handle the compressor with care. Use the

dedicatedhandlesinthepackaging.Usethecompressor lifting lug and use appropriateandsafeliftingequipment.

• Store and transport the compressor in anuprightposition.

• Storethecompressorbetween-35°Cand55°C. • Don’texposethecompressorandthepacka-

gingtorainorcorrosiveatmosphere.

3–SafetymeasuresbeforeassemblyNeverusethecompressorinaflammable

atmosphere.

• The compressor ambient temperature maynotexceed50°Cduringoff-cycle.

• Mount the compressor on a horizontal flatsurfacewithlessthan3°slope.

• The compressor can only be supplied by afrequencyconverter.Makesurethatthefrequencyconverteristhededicatedoneforthecompressor(power size and voltage: input & output).Parameter1.13ofthefrequencyconverterliststhepossiblecombinationsofcompressors,frequencyconvertersandrefrigerants.

• WheninstallingaVSH,useequipmentspecifi-callyreservedforHFCrefrigerantswhichwasneverusedforCFCrefrigerants.

• Usecleananddehydratedrefrigeration-gradecoppertubesandsilveralloybrazingmaterial.

• Usecleananddehydratedsystemcomponents. • Thepipingconnectedtothecompressormustbe

flexiblein3dimensionstodampenvibrations. • Makesuretheinstallationisequippedwithhigh-

pressuresafetycomponents(e.g.pressureswitch,pressurereliefvalve)topreventagainsttheburs-tingofpressure-containingcomponents.

4-Assembly • Slowly release the nitrogen holding charge

throughtheschraderport. • Connect the compressor to the system as

soon as possible to avoid oil contaminationfromambientmoisture.

• Avoidmaterialenteringintothesystemwhilecutting tubes. Never drill holes where burrscannotberemoved.

• Brazewithgreatcareusingstate-of-the-arttech-niqueandventpipingwithnitrogengasflow.

• Connect the required safety and control de-vices.Whentheschraderportisusedforthis,removetheinternalvalve.

5–Leakdetection Never pressurize the circuit with oxygen or

dryair.Thiscouldcausefireorexplosion.

• Donotusedyeforleakdetection. • Performaleakdetectiontestonthecomplete

system. • Thelowsidetestpressuremustnotexceed30bar. • Whenaleakisdiscovered,repairtheleakand

repeattheleakdetection.

6–Vacuumdehydration • Neverusethecompressortoevacuatethesystem. • ConnectavacuumpumptoboththeLP&HPsides. • Evacuatethesystemtoapressureof500µm

Hg(0.67mbar)absolute. • Donotuseamegohmmeternorapplypower

tothecompressorwhileitisundervacuumasthismaycauseinternaldamage.

7–Electricalconnections • Switchoffandisolatethemainpowersupply.

Seepreviouspageforwiringdetails. • The compressor is protected against excess

currentbythefrequencyconverter.Followlocalregulations regarding power line protection.Thecompressormustbeconnectedtoground.

• Allelectricalcomponentsmustbeselectedasperlocalstandardsandcompressorrequirements.

• Pleaserefertodrawingsfortypicalwiringconnec-tions and examine the specific wiring diagramlocatedinthefrequencyconverterpackage.Forfurtherdetails,refertotheapplicationguidelines.

• Followverycloselytheinstallationinstructionforthefrequencyconverter:

-Mounting:Thebaseframeofthefrequencyconverter must be very well fixed to thesupport to ensure a very good continuitybetweenthegroundpotentialofallelectricalpanelsandelectricalboxesofthesystem.

-Wiring:Allcontrolwireshavetobeofascreee-neddesign.Thecableforelectricalmotorsup-plyhastobeofashieldeddesignaswell.Cor-rectearthingoftheshieldcoverhastobedoneusingthemethodshownondrawings,everytimethisonehastobeearthedoneachendofthecables.Distinctcabletraysmustbeusedforcontrolandmotorsupply.

• The frequency converter ensures direct motorprotection and the factory set parameters aresuchtoprotect themotoroverallcurrentmal-functions.Anexternaloverloadisnotnecessary.

• Set the frequency converter parameters inaccordance with Danfoss recommendationsfortheCDS302frequencyconverterandVSHvariablespeedcompressor.

8–Fillingthesystem • Keepthecompressorswitchedoff. • Fill the refrigerant in liquid phase into the

outletsideofthecondenserorliquidreceiver.Thechargemustbeascloseaspossibletothenominalsystemchargetoavoidlowpressureoperationandexcessivesuperheat.

Compressor Refrigerantchargelimit(kg)VSH088 5.9VSH117 7.9VSH170 13.5

Abovethislimit;protectthecompressoragainstliquidflood-backwithapump-downcyclenotlowerthan2.3bar(g)orasuctionlineaccumu-lator.

• Never leavethefillingcylinderconnectedtothecircuittoavoidoverfilling.

9–Verificationbeforecommissioning Use safety devices such as safety pressure

switchandmechanicalreliefvalveincomplian-cewithbothgenerallyandlocallyapplicablere-gulationsandsafetystandards.Ensurethattheyareoperationalandproperlyset.

Checkthatthesettingsofhigh-pressureswit-chesandreliefvalvesdon’texceedthemaximumservicepressureofanysystemcomponent.

• Alow-pressureswitchismandatorytoavoidva-cuumoperation.Minimumsetting1.5bar(g).

• Verifythatallelectricalconnectionsareproperlyfastened and in compliance with local regula-tions.

• A crankcase heater is not required. Thisfunction is integrated in the CDS302 whichprovides a calibrated DC current during offcyclestoheattheelectricalmotor.TheCDS302mustbeenergizedatleast12hoursbeforeini-tialstart-upandafterprolongedshutdown.

• Aftercomissioningitisstronglyrecommendedtokeepthefrequencyconverteralwaysenergized.

10–Start-up • Allservicevalvesmustbeintheopenposition. • BalancetheHP/LPpressure. • Energizethecompressor.Itmuststartpromptly. • If thecompressordoesn’tstart,verify that the

compressor is hooked up to the frequencyconverter;checkthepowerleadconnections.If these verifications reveal no abnormality,checkthemotorwindingswithanohmmeter.

• Check the frequency converter control pa-nel:Ifanyalarmisdisplayedcheckthewiringand in particular the polarity of the controlcables. Ifanalarm is shown, refer to the fre-quency converter application manual.Verifyinparticularthecombinationofcompressor,frequencyconverterandrefrigerant.

• Checkcurrentdrawandvoltagelevelsonthemains. The values for the compressor elec-tricalmotorcanbedirectlydisplayedonthefrequencyconvertercontrolpanel.

• Theoptimumcompressorsuctionsuperheatis around 6K. The maximum allowed super-heatis30K.

11–Checkwithrunningcompressor • Checkcurrentdrawandvoltage. • Check suction superheat to reduce risk of

slugging. • Observetheoillevelatstartandduringopera-

tiontoconfirmthattheoillevelremainsvisible.Excessfoaminginoilsightglassindicatesrefri-gerantonthesump.

• Monitortheoilsightglassfor1houraftersys-temequilibriumtoensureproperoilreturntothecompressor.Thisoilcheckhastobedoneoverthespeedrangetoguarantee:

-agoodoilreturnatlowspeedwithmini-mumgasvelocity.

- a good oil management at high speedwithmaximumoilcarryover.

• Respecttheoperatinglimits. • Checkalltubesforabnormalvibration.Move-

mentsinexcessof1.5mmrequirecorrectivemeasuressuchastubebrackets.

• Whenneeded,additionalrefrigerantintheliquidphasemaybeaddedinthelow-pressuresideasfaraspossiblefromthecompressor.Thecompressormustbeoperatingduringthisprocess.

• Donotoverchargethesystem. • Neverreleaserefrigeranttotheatmosphere. • Before leaving the installation site, carry out

a general installation inspection regardingcleanliness,noiseandleakdetection.

• Record type and amount of refrigerant chargeaswellasoperatingconditionsasareferenceforfutureinspections.

• Compressorfailuretobuilduppressure:Checkall bypass valves in the system to ensure thatnoneofthesehasbeenopened.Alsocheckthatallsolenoidvalvesareintheirproperposition.

• Abnormalrunningnoise:Ensuretheabsenceofanyliquidflood-backtothecompressorbymeansofmeasuringthereturngassuperheatandcom-pressorsumptemperature.Thesumpshouldbeatleast6Kabovethesaturatedsuctiontempera-tureundersteady-stateoperatingconditions.

• The high-pressure switch trips out: Checkcondenseroperations(condensercleanliness,fanoperation,waterflowandwaterpressurevalve,waterfilter,etc.).IfalltheseareOK,theproblem may be due to either refrigerantovercharging or the presence of a non-con-densable(e.g.air,moisture)inthecircuit.

• Thelow-pressureswitchtripsout:Checkevapo-ratoroperations(coilcleanliness,fanoperations,water flow, water filter, etc.), liquid refrigerantflow and pressure drops (solenoid valve, filterdryer,expansionvalve,etc.),refrigerantcharge.

• Low refrigerant charge: The correct refrigerantchargeisgivenbytheliquidsightglassindication,the condenser deltaT in relation to the refrige-rant pressure tables (pressure-temperature), thesuperheatandthesub-cooling,etc.(ifadditional

FRCC.EI.005.A3.02©DanfossCommercialCompressors09/10 3

Instructions

Page 4: InstruCtIons VsH ComprEssors · 2019-05-02 · 1 - Introduction These instructions pertain to the VSH Variable Speed scroll compressors used for A/C systems. They provide necessary

chargeisdeemednecessary,refertosection8).

• Compressorshortcycling:Thenumberofcy-

clesshallneverexceed12startsperhour.

12-Maintenance

Internal pressure and surface temperature

aredangerousandmaycausepermanentinjury.

Maintenance operators and installers require

appropriate skills and tools. Tubing and com-

presssor upper shell temperature may exceed

100°Candcancausesevereburns.

Ensure that periodic service inspections to

ensuresystemreliabilityandasrequiredbylocal

regulationsareperformed.

Topreventsystemrelatedcompressorproblems,

followingperiodicmaintenanceisrecommended:

• Verifythatsafetydevicesareoperationaland

properlyset.

• Ensurethatthesystemisleaktight.

• Checkthecompressorcurrentdraw.

• Confirmthatthesystemisoperatinginaway

consistent with previous maintenance re-

cordsandambientconditions.

• Check that all electrical connections are still

adequatelyfastened.

• Keepthecompressorcleanandverifytheab-

senceofrustandoxidationonthecompres-

sorshell,tubesandelectricalconnections.

• Check the internal temperature of the fre-

quencyconverteronitsdisplayandthecoo-

lingairflow.

• Faultsareloggedinthefrequencyconverter

memoryandcanbedisplayed.Thiscanhelp

to evaluate and improve parameters of the

frequencyconverterorofthesystemitself.

13-Warranty

Alwaystransmitthemodelnumberandserialnum-

berwithanyclaimfiledregardingthisproduct.

Usethefaultmemoryofthefrequencyconver-

ter to recover the fault descriptions before ini-

tializingthesystemandevenbeforeshuttingoff

thepower.

Theproductwarrantymaybevoidinfollowing

cases:

• Absenceofnameplate.

• External modifications; in particular, drilling,

welding,brokenfeetandshockmarks.

• Compressoropenedorreturnedunsealed.

• Rust, water or leak detection dye inside the

compressor.

• Useofarefrigerantorlubricantnotapproved

byDanfoss.

• Any deviation from recommended instruc-

tionspertainingtoinstallation,applicationor

maintenance.

• Useinmobileapplications.

• Useinexplosiveatmosphericenvironment.

• Nomodelnumberorserialnumbertransmit-

tedwiththewarrantyclaim.

14–Disposal

Danfossrecommendsthatcompressors,frequen-

cy converters and compressor oil should

berecycledbyasuitablecompany.

DanfossCommercialCompressorshttp://cc.danfoss.comDanfosscanacceptnoresponsibilityforpossibleerrorsincatalogues,brochuresandotherprintedmaterial.Danfossreservestherighttoalteritsproductswithoutnotice.Thisalsoappliestoproductsalreadyonorderprovidedthatsuchalterationscanbemadewithoutsubsequentialchangesbeingnecessaryinspecificationsalreadyagreed.Alltrademarksinthismaterialarepropertyoftherespectivecompanies.DanfossandtheDanfosslogotypearetrademarksofDanfossA/S.Allrightsreserved.