![Page 1: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/1.jpg)
Year built:from 02/2010en_INT
Raxofix
Instructions for Use
![Page 2: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/2.jpg)
Raxofix 2 from 24
![Page 3: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/3.jpg)
Table of contents
1 About these instructions for use 4
1.1 Target groups 4
1.2 Labelling of notes 4
1.3 About this translated version 5
2 Product information 6
2.1 Standards and regulations 6
2.2 Intended use 8
2.2.1 Areas of use 8
2.2.2 Media 9
2.3 Product description 9
2.3.1 Overview 9
2.3.2 Pipes 10
2.3.3 Press connectors 14
2.3.4 Markings on components 14
2.3.5 Mixed installations 15
2.4 Information for use 15
2.4.1 Chemical resistance 15
3 Handling 17
3.1 Storage 17
3.2 Assembly information 17
3.2.1 Mounting instructions 17
3.2.2 Space requirements and intervals 18
3.2.3 Required tools 20
3.3 Assembly 21
3.3.1 Bending pipes 21
3.3.2 Shortening the pipes 22
3.3.3 Pressing the connection 23
3.3.4 Leakage test 24
3.4 Maintenance 24
3.5 Disposal 24
Table of contents
Raxofix 3 from 24
![Page 4: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/4.jpg)
1 About these instructions for useTrade mark rights exist for this document; for further information, go toviega.com/legal.
1.1 Target groupsThe information in this manual is directed at heating and sanitary pro‐fessionals and trained personnel.
Individuals without the abovementioned training or qualification are notpermitted to mount, install and, if required, maintain this product. Thisrestriction does not extend to possible operating instructions.
The installation of Viega products must take place in accordance withthe general rules of engineering and the Viega instructions for use.
1.2 Labelling of notesWarning and advisory texts are set aside from the remainder of the textand are labelled with the relevant pictographs.
DANGER! This symbol warns of possible life-threatening injury.
WARNING! This symbol warns of possible serious injury.
CAUTION! This symbol warns of possible injury.
NOTICE! This symbol warns of possible damage to property.
This symbol gives additional information and hints.
About these instructions for use
Raxofix 4 from 24
![Page 5: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/5.jpg)
1.3 About this translated versionThis instruction for use contains important information about the choiceof product or system, assembly and commissioning as well as intendeduse and, if required, maintenance measures. The information about theproducts, their properties and application technology are based on thecurrent standards in Europe (e. g. EN) and/or in Germany(e. g. DIN/DVGW).
Some passages in the text may refer to technical codes in Europe/Germany. These should serve as recommendations in the absence ofcorresponding national regulations. The relevant national laws, stand‐ards, regulations, directives and other technical provisions take priorityover the German/European directives specified in this manual: Theinformation herein is not binding for other countries and regions; as saidabove, they should be understood as a recommendation.
About these instructions for use
Raxofix 5 from 24
![Page 6: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/6.jpg)
2 Product information2.1 Standards and regulations
The following standards and regulations apply to Germany / Europe andare provided as a support feature.
Scope / Notice Regulations applicable in Ger‐many
Planning, execution, operationand maintenance of drinkingwater installations
DIN EN 1717
Planning, execution, operationand maintenance of drinkingwater installations
DIN 1988
Planning, execution, operationand maintenance of drinkingwater installations
VDI/DVGW 6023
Planning, execution, operationand maintenance of drinkingwater installations
Trinkwasserverordnung (TrinkwV)
Regulations from section: Fields of application
Product information
Raxofix 6 from 24
![Page 7: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/7.jpg)
Scope / Notice Regulations applicable in Ger‐many
Drinking water pipelines, cold:
n Pipe with protective pipe(grey), see line 4 and 5
n Pipe with 9 mm surroundinginsulation (grey), see line 1
n Pipe with 13 mm surroundinginsulation (grey), see line 2 and6
n Pipe with 26 mm surroundinginsulation (grey), see line 3
DIN 1988–200, Table 8
Drinking water pipelines, warm:
n Pipe with protective pipe(grey), see line 6
n Pipe with 13 mm surroundinginsulation (grey), see line 5
n Pipe with 26 mm surroundinginsulation (grey), see line 1
DIN 1988–200, Table 9
Heating systems:
n Pipe with 9 mm surroundinginsulation (grey), see line 7
n Pipe with 13 mm surroundinginsulation (grey), see line 5 and6
n Pipe with 26 mm surroundinginsulation (grey), see line 1
Heating systems in floor construc‐tion:
n Pipe with eccentric heat insu‐lation (grey), see line 1 or 7
EnEV, Anhang 5, Table 1
Scope / Notice Regulations applicable in Ger‐many
Requirements for material storage DIN EN 806-4, Chapter 4.2
Regulations from section: Pipes
Regulations from section: Storage
Product information
Raxofix 7 from 24
![Page 8: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/8.jpg)
Scope / Notice Regulations applicable in Ger‐many
Test on a system that is finishedbut not yet covered
DIN EN 806–4
Leakage test for water installa‐tions
ZVSHK-Merkblatt:"Dichtheitsprüfungen von Trink‐wasserinstallationen mit Druckluft,Inertgas oder Wasser"
Scope / Notice Regulations
Operation and maintenance ofdrinking water installations
DIN EN 806-5
2.2 Intended use
Coordinate the use of the system for areas of use and mediaother than those described with the Viega Service Center.
2.2.1 Areas of useUse is possible in the following areas among others:
n Raxofix-PE-Xc/Al/PE-Xc pipes (dimensionally stable, with externaloxygen seal coat)– Drinking water installations– Heating systems– Compressed air systems
n Raxofix-PE-Xc pipes (flexible without external oxygen seal coat)– Drinking water installations
For planning, execution, operation and maintenance of potable waterinstallations, observe the applicable regulations, see Ä „Regulationsfrom section: Fields of application“ on page 6.
Inform your customer or the operator of the potable water installationthat the system has to be maintained on a regular basis, see Ä Chapter3.4 „Maintenance“ on page 24.
Regulations from section: Leakage test
Regulations from section: Maintenance
Drinking water installation
Maintenance
Product information
Raxofix 8 from 24
![Page 9: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/9.jpg)
2.2.2 MediaThe system is suitable for the following media, amongst others:
n Raxofix-PE-Xc/Al/PE-Xc pipes– Drinking water– Rainwater– Heating water– Compressed air
n Raxofix-PE-Xc pipes– Drinking water
Operating temperature max.
n Sanitary installations: TD 70 °C
n Heating installations: 80 °C (only with Raxofix-PE-Xc/Al/PE-Xc pipes)
Maximum operating pressure
n Sanitary installations: 1.0 MPa (10 bar)n Heating installations: 1.0 MPa (10 bar)
2.3 Product description2.3.1 Overview
The piping system consists of press connectors in connection with PE-Xc pipes and the corresponding press tools.
Fig. 1: Raxofix press connectors
The system components are available in the following dimensions:d 16 / 20 / 25 / 32 / 40 / 50 / 63.
Operating conditions
Product information
Raxofix 9 from 24
![Page 10: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/10.jpg)
2.3.2 PipesRaxofix plastic pipes are available as coiled bundle with and withoutprotective pipe, and with various insulation thicknesses. Dimensionallystable multilayer pipes are also available in 5 m lengths. The followingpipes are available from the system described:
Raxofix-PE-Xc/Al/PE-Xc Raxofix PE-Xc
dimensionally stable flexible
with external oxygen seal coat without external oxygen seal coat
d 16, 20, 25, 32, 40, 50, 63 d 16, 20
Raxofix-PE-Xc/Al/PE-Xc
Type of pipe d Areas of use
Pipe in rods 16, 20, 25, 32, 40,50, 63
Drinking water and heatinginstallations
Pipe without pro‐tective pipe
16, 20, 25, 32 Drinking water and heatinginstallations
Pipe with protectivepipe (grey)
16, 20 Drinking water and heatinginstallations1)
Pipe with 6 mmsurrounding insula‐tion (grey)
16, 20 Drinking water and heatinginstallations
Pipe with 9 mmsurrounding insula‐tion (grey)
16, 20, 25 Drinking water and heatinginstallations1)
Pipe with 13 mmsurrounding insula‐tion (grey)
16, 20 Drinking water and heatinginstallations1)
Pipe with 26 mmsurrounding insula‐tion (grey)
16, 20 Drinking water and heatinginstallations1)
Pipe with eccentricheat insulation(grey)
16, 20, 25 Heating pipes in floor con‐struction, integration in thefloor construction withoutcontinuous footfall sound
insulation1)
Pipe with eccentricheat insulation(grey)
16, 20 Heating pipes in floor con‐struction, integration in thefloor construction withoutcontinuous footfall sound
insulation1)
1) see Ä „Regulations from section: Pipes“ on page 7
Product information
Raxofix 10 from 24
![Page 11: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/11.jpg)
Raxofix-PE-Xc
Type of pipe d Areas of use
Pipe without pro‐tective pipe
16, 20 Drinking water installations
Pipe with protectivepipe (grey)
16, 20 Drinking water installa‐tions1)
Pipe with 9 mmsurrounding insula‐tion (grey)
16 Drinking water installa‐tions1)
1) see Ä „Regulations from section: Pipes“ on page 7
Only pipe clamps with chloride-free sound insulating inlays should beused to secure the pipes.
Observe the general rules of fixing technology:
n Do not use fixed pipelines as a support for other pipelines and com‐ponents.
n Do not use pipe hooks.n Observe distance to connectors.n Observe the expansion direction: Plan fixed and gliding points.
Make sure to affix the pipelines in such a way as to de-couple themfrom the installation body, so that they cannot transfer any structure-borne sound, resulting from thermal expansion or possible pressuresurges, onto the installation body or other components.
Observe the following fixing intervals:
Interval between the pipe clamps
d x s
[mm]
Horizontal
PE-Xc/Al/PE-Xcpipe [m]
Horizontal
PE-Xc pipe [m]
Vertical
PE-Xc/Al/PE-Xc [m]
Vertical
PE-Xc pipe [m]
16 x 2.2 1.00 0.55 1.30 0.75
20 x 2.8 1.00 0.60 1.30 0.80
25 x 2.7 1.50 - 1.95 -
32 x 3.2 2.00 - 2.60 -
40 x 3.5 2.00 - 2.60 -
50 x 4.0 2.50 - 3.25 -
63 x 4.5 2.50 - 3.25 -
Laying and fixing pipes
Product information
Raxofix 11 from 24
![Page 12: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/12.jpg)
Pipelines expand with heat. Heat expansion is dependent on the mate‐rial. Changes in length lead to tension within the installation. These ten‐sions must be equalised with suitable measures.
The following are effective:
n Fixed and gliding pointsn Expansion equalisation joints (expansion bends)
Heat expansion co-efficients of various pipe materials
Material Heat expansion co-effi‐cient ⍺ [mm/mK]
Example:
Length expansion withpipe lengths L = 20 m
and ΔT = 50 K [mm]
Raxofix-PE-Xc/Al/PE-Xc
0.03 30
Raxofix-PE-Xc 0.17 170
Calculation example PE-Xc pipe:
n Given: Temperature difference Δϑ = 50 K; Pipe length L = 8 m;Pipe ⌀ = 20 mm
n Required: Expansion bend length LBS
n Calculation:– Beginning in the left-hand diagram: From 50 K temperature dif‐
ference on the x-axis up to the characteristic line for the 8 mpipe length.
– Connect the intersection horizontally with the right-hand dia‐gram up to the intersection of the characteristic line for pipediameter 20 mm.
n Result: Read the value from the x-axis: LBS = 430 mm.
Length expansion
Length expansion and expansion bend length
Product information
Raxofix 12 from 24
![Page 13: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/13.jpg)
Fig. 2: PE-Xc – expansion bend length
1 - Length expansion ∆l [mm]2 - temperature difference ∆ϑ [K]3 - pipe length L [m]4 - Expansion bend length LBS [mm]
Calculation example PE-Xc/Al/PE-Xc pipe:
n Given: Temperature difference Δϑ = 50 K; Pipe length L = 8 m; Pipe⌀ = 20 mm
n Required: Expansion bend length LBS
n Calculation:– Beginning in the left-hand diagram: From 50 K temperature dif‐
ference on the x-axis up to the characteristic line for the 8 mpipe length.
– Connect the intersection horizontally with the right-hand dia‐gram up to the intersection of the characteristic line for pipediameter 20 mm.
n Result: Read the value from the x-axis: LBS = 480 mm.
Fig. 3: PE-Xc/Al/PE-Xc – expansion bend length
1 - Length expansion ∆l [mm]2 - temperature difference ∆ϑ [K]3 - pipe length L [m]4 - Expansion bend length LBS [mm]
Product information
Raxofix 13 from 24
![Page 14: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/14.jpg)
2.3.3 Press connectorsPress connectors are available in a number of shapes. An overview ofthe press connectors suitable for the system can be found in the cata‐logue.
Fig. 4: SC-Contur
Viega press connectors are equipped with the SC-Contur. The SC-Contur is a safety technology that is certified by the DVGW and ensuresthat the connector is guaranteed to be leaky in an unpressed state. Inthis way, inadvertently unpressed connections are noticed immediatelywhen filling the system.
Viega ensures that inadvertently unpressed connections during installa‐tion become visible when the system is filled.
n with wet leakage test in the pressure range from 0.1–0.65 MPa (1.0–6.5 bar)
n with dry leakage test in the pressure range from 22 hPa–0.3 MPa(22 mbar–3.0 bar)
2.3.4 Markings on components
The pipe markings contain important information regarding the qualityand certification of the pipes. Their meaning is as follows:
n manufacturern System namen pipe materialn size / wall thicknessn certification and operating temperatures
SC-Contur
Pipe marking
Product information
Raxofix 14 from 24
![Page 15: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/15.jpg)
Fig. 5: Marking
The green dot shows that the press connector is equipped with theSC-Contur and that the system is suitable for drinking water.
2.3.5 Mixed installationsAll Raxofix pipes may only be mounted using original accessories, Rax‐ofix connectors with SC-Contur and the corresponding press tools. Usewith components of other plastic piping systems, such as e. g. SanfixFosta, is not permitted.
Please contact the Viega Service Center for questions on this subject.
2.4 Information for use2.4.1 Chemical resistance
NOTICE! Damage to material due to aggressive chemicalsAggressive chemicals, especially those containing solvents,may cause material damage and leaks. This may lead towater damage.
– Prevent contact between the system components andaggressive chemicals.
Markings on press connectors
Product information
Raxofix 15 from 24
![Page 16: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/16.jpg)
NOTICE! Material damage due to impermissible leakage detectionagentsImpermissible leakage detection agents may cause materialdamage and leaks. This may lead to water damage.
– Use only leakage detection agents approved by themanufacturer for use on PPSU material.
– Observe the manufacturer's notes on processing.
Product information
Raxofix 16 from 24
![Page 17: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/17.jpg)
3 Handling3.1 Storage
For storage, comply with the requirements specified in the applicableregulations, see Ä „Regulations from section: Storage“ on page 7:
n Store rods on even, clean surfaces.
3.2 Assembly information3.2.1 Mounting instructions
NOTICE! Material damage due to thread locker containing solvents!Thread lockers containing solvents can lead to materialdamage and leaks in plastic parts of pipe connections. Thismay lead to water damage.
– As a sealant, only use commercially available hemptogether with thread sealing paste or certified sealingtape for potable water.
– Please contact the Viega Service Center if you have anyquestions.
System components may, in some cases, become damaged throughtransportation and storage.
n Check all parts.n Replace damaged components.n Do not repair damaged components.n Contaminated components may not be installed.
Checking system components
Handling
Raxofix 17 from 24
![Page 18: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/18.jpg)
3.2.2 Space requirements and intervals
Space requirement type 2 (PT2), PT3-EH, PT3-AH, Pressgun 4B, 4E, 5
d 16 20 25 32 40 50 63
a [mm] 14 18 23 28 34 38 45
b [mm] 45 49 58 75 88 94 108
Space requirement Picco, Pressgun Picco
d 16 20 25 32 40
a [mm] 16 17 23 29 32
b [mm] 46 49 57 70 79
Space requirement type 2 (PT2), PT3-EH, PT3-AH, Pressgun 4B, 4E, 5
d 16 20 25 32 40 50 63
a [mm] 19 21 27 33 39 44 52
b [mm] 37 38 38 50 56 58 67
c [mm] 65 70 73 86 97 103 118
Space requirement Picco, Pressgun Picco
d 16 20 25 32 40
a [mm] 20 21 27 34 38
b [mm] 33 32 35 44 46
c [mm] 60 63 72 79 88
Space requirement type 2 (PT2), PT3-EH, PT3-AH, Pressgun 4B, 4E, 5
d 16 20 25 32 40 50 63
a [mm] 19 22 27 33 39 44 52
b [mm] 65 70 73 86 97 103 118
c [mm] 139 146 149 186 209 219 252
Pressing between pipelines
a
b
Pressing between pipe and wall
a
cb
Pressing in wall slots
a
b
100
c
Handling
Raxofix 18 from 24
![Page 19: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/19.jpg)
Space requirement Picco, Pressgun Picco
d 16 20 25 32 40
a [mm] 20 21 27 34 38
b [mm] 60 63 72 79 88
c [mm] 126 127 142 167 180
NOTICE! Leaky press connections due to pipes being too short!If two press connectors are to be mounted onto a pipewithout an interval, the pipe must not be too short. If thepipe is not inserted up to the prescribed insertion depth inthe press connector during pressing, the connection maybecome leaky.
Minimum interval elbow and coupling: type 2 (PT2), PT3-EH, PT3-AH,Pressgun 4B, 4E, 5
d 16 20 25 32 40 50 63
amin
[mm]36 36 46 44 57 57 60
bmin
[mm]46 50 62 74 94 112 124
Minimum interval elbow and coupling: Pressgun Picco, Picco
d 16 20 25 32 40
amin [mm] 36 36 46 46 57
bmin [mm] 46 50 62 74 94
Minimum interval elbow and T-piece: type 2 (PT2), PT3-EH, PT3-AH,Pressgun 4B, 4E, 5
d 16 20 25 32 40 50 63
amin
[mm]36 36 46 44 57 57 60
bmin
[mm]46 50 62 73 94 108 124
Interval between the pressings
Handling
Raxofix 19 from 24
![Page 20: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/20.jpg)
Minimum distance elbow and T-piece: Pressgun Picco, Picco
d 16 20 25 32 40
amin [mm] 36 36 46 44 57
bmin [mm] 46 50 62 73 94
For the Z dimensions, refer to the respective product page in the onlinecatalogue.
3.2.3 Required toolsThe use of original Viega tools or equivalent tools is recommended forinstallation.
The following tools are required for production of a press connection:
Hand or electric saws or angle grinders are not permitted.
n press machine with constant pressing forcen suitable Raxofix press jaw for PE-Xc systemsn pipe shear (model 5341) for dimensions 16–25 mmn pipe cutters (model 2191) for dimensions 32–63 mmn bending tool (model 5331 or 5331.2)
Z dimensions
Handling
Raxofix 20 from 24
![Page 21: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/21.jpg)
Fig. 6: Press tool
Recommended Viega press machines:
n Pressgun 5n Pressgun Piccon Pressgun 4E / 4Bn Piccon Type PT3-AHn Type PT3-H / EHn Type 2 (PT2)
3.3 Assembly3.3.1 Bending pipes
Raxofix multilayer pipes in the dimensions 16–32 mm can be bent byhand with a bending radius of 5 x d or with a bending tool with the fol‐lowing radii:
Bending at the connector can lead to the pipe breaking.
d Bending radius x d
16 2.0
20 2.3
Handling
Raxofix 21 from 24
![Page 22: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/22.jpg)
d Bending radius x d
25 3.0
32 3.5
40 4.0
50 4.5
63 4.5
The recommended bending tools for dimensions d 16 and 20 are themodels 5331 and 5331.2.
3.3.2 Shortening the pipesFor information about tools, also see Ä Chapter 3.2.3 „Requiredtools“ on page 20.
Cut the protective pipe to length using the protective pipe cutter(model 5341).
Cut the pipe to length using a pipe shear.
Replace worn blades (model 5341.6).
Make sure that the cut surface is clean and straight.
Dimensions 16–25 mm
Dimensions 32–63 mm
Handling
Raxofix 22 from 24
![Page 23: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/23.jpg)
Cut the pipe to length using a pipe cutter (model 2191).
3.3.3 Pressing the connectionPush the pipe into the press connector until the pipe end is visible inthe inspection window.
Check the insertion depth in the inspection window.
Open the press jaw and place at a right-angle onto the connector.Carry out the pressing process.
Observe the intervals in section Ä Chapter 3.2.2 „Space require‐ments and intervals“ on page 18.
ð Connection is pressed.
Handling
Raxofix 23 from 24
![Page 24: Instructions for Use - viega.com · Some passages in the text may refer to technical codes in Europe/ ... insulation (grey), see line 1 n Pipe with 13 mm surrounding insulation (grey),](https://reader033.vdocuments.us/reader033/viewer/2022041702/5e4221e838c22f5d107c7464/html5/thumbnails/24.jpg)
3.3.4 Leakage test
NOTICE! Also refer to the information for use on leakage detectionagents, see Ä Chapter 2.4.1 „Chemical resistance“on page 15.
The installer must perform a leakage test before commissioning.
Carry out this test on a system that is finished but not yet covered.
Observe the applicable regulations, see Ä „Regulations from section:Leakage test“ on page 8.
The leakage test pursuant to the applicable regulations must also becarried out for non-potable water installations, see Ä „Regulations fromsection: Leakage test“ on page 8.
Document the result.
3.4 MaintenanceObserve the applicable regulations for the operation and maintenanceof drinking water installations, see Ä „Regulations from section: Mainte‐nance“ on page 8.
3.5 DisposalSeparate the product and packaging materials (e. g. paper, metal,plastic or non-ferrous metals) and dispose of in accordance with validnational legal requirements.