instruction manual model 120 / 122 — differential pressure...

2
INSTRUCTION MANUAL MODEL 120 / 122 — DIFFERENTIAL PRESSURE GAUGE Principle of Operation The Model 120 Differential Pressure Gauge is a rugged 150 mm dial, piston-type instrument with a Safe Working Pressure of 200 Kg/Cm². It is used to measure the pressure differential across filters, valves and other equipment. Model 122, is same as Model 120 gauge, except for its smaller dial size viz., 65 mm. Differential pressure is indicated by the travel of a free-floating precision piston with magnet (Fig.1) against a calibrated range spring, within the solid, high pressure housing. To indicate the pressure differential on the calibrated dial accurately, a magnet on the gauge pointer outside the housing tracks the magnetic piston inside the pressure housing. The ratings of the Reed Switch are Power : 3 Watts Maximum Current : 0.25 Amps Maximum Voltage : 120V AC / DC Caution : Do not exceed the above maximum limits. Product of Switching Voltage and Current shall not exceed the power rating. For loads above the switch rating, SWITZER Power Relay should be used. The power relay is used to control high loads (Fig.4) and is housed in a weatherproof enclosure. Sensor Magnet Pointer with Magnet 500 PSIG 500 PSIG COM NO NC Reed Switch Sensor Magnet Pointer with Magnet 500 PSIG 480 PSIG COM NO NC Reed Switch COM and NC closed COM and NO closed The switch option (Fig.2) can be used to switch an alarm or control circuit at any point. The switch is a hermetically Fig.2 sealed Reed Switch which is not affected by vibration or shock. It is directly actuated by the piston magnet in the gauge’s pressurised housing and therefore does not affect the accuracy of the gauge. One or two independently adjustable Reed Switches are available. The switches can be set with an external screw arrangement and setpoints are adjustable from 10% to 90% of the operating range of the gauge. The switch schematic is shown in Fig.3. N.O. at ZERO, closes on rising p Common N.C. at ZERO, opens on rising p 10" Flying Leads High Alarm U V | W | Low Alarm Switch at Zero Pressure Fig. 3 U V | W | N.O. Reed Switch N.C. Power Relay Module Case Ground Load ½" H.P. 10 A 120V AC Common Line N.O. 80 to 250V AC Fig. 4 Calibration This instrument has a piston finely machined and matched to the cylinder bore without a ‘O’ ring. So leak is permitted across the piston which will not exceed 15SCFH air at 100 PSID at ambient conditions. Therefore do not use a Comparator or a Deadweight tester for calibrating the instrument, but use a continuous air pressure source only. Connect the source to HP port and leave the LP port open to atmosphere and check calibration at approximately 30%, 50% and 70% of full-scale pressure. If necessary, loosen ‘O’ Ring Seal Piston with Magnet Seal Nut End Cap Range Spring Span Adj. Screw Fig.1 ‘O’ Ring Seal

Upload: others

Post on 28-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

INSTRUCTION MANUAL

MODEL 120 / 122 — DIFFERENTIAL PRESSURE GAUGE

Principle of Operation

The Model 120 Differential Pressure Gauge is a rugged150 mm dial, piston-type instrument with a Safe WorkingPressure of 200 Kg/Cm². It is used to measure the pressuredifferential across filters, valves and other equipment.

Model 122, is same as Model 120 gauge, except for itssmaller dial size viz., 65 mm.

Differential pressure is indicated by the travel of a free-floatingprecision piston with magnet (Fig.1) against a calibratedrange spring, within the solid, high pressure housing. Toindicate the pressure differential on the calibrated dialaccurately, a magnet on the gauge pointer outside thehousing tracks the magnetic piston inside the pressurehousing.

The ratings of the Reed Switch are

Power : 3 WattsMaximum Current : 0.25 AmpsMaximum Voltage : 120V AC / DC

Caution : Do not exceed the above maximum limits.Product of Switching Voltage and Current shallnot exceed the power rating.

For loads above the switch rating, SWITZER Power Relayshould be used. The power relay is used to control highloads (Fig.4) and is housed in a weatherproof enclosure.

SensorMagnet

Pointer withMagnet

500 PSIG 500 PSIG

COMNONC

Reed Switch

SensorMagnet

Pointer withMagnet

500 PSIG 480 PSIG

COMNONC

Reed SwitchCOM and NC closed COM and NO closed

The switch option (Fig.2) can be used to switch an alarm orcontrol circuit at any point. The switch is a hermetically

Fig.2

sealed Reed Switch which is not affected by vibration orshock. It is directly actuated by the piston magnet in thegauge’s pressurised housing and therefore does not affectthe accuracy of the gauge.

One or two independently adjustable Reed Switches areavailable. The switches can be set with an external screwarrangement and setpoints are adjustable from 10% to 90%of the operating range of the gauge. The switch schematicis shown in Fig.3.

N.O. at ZERO, closes on rising p

Common

N.C. at ZERO, opens on rising p

10" Flying Leads

HighAlarm

UV|W|LowAlarm

Switch atZero

Pressure

Fig. 3

UV|W|

N.O.

ReedSwitch

N.C.

Power

Relay

Module

CaseGround

Load ½"H.P. 10 A120V AC

Common

LineN.O.

80 to250VAC

Fig. 4

Calibration

This instrument has a piston finely machined and matchedto the cylinder bore without a ‘O’ ring.

So leak is permitted across the piston which will not exceed15SCFH air at 100 PSID at ambient conditions.

Therefore do not use a Comparator or a Deadweight testerfor calibrating the instrument, but use a continuous air pressuresource only.

Connect the source to HP port and leave the LP port opento atmosphere and check calibration at approximately 30%,50% and 70% of full-scale pressure. If necessary, loosen

‘O’ RingSeal

Piston withMagnet

Seal Nut

End CapRange SpringSpan Adj. Screw

Fig.1

‘O’ RingSeal

the adjustment locknut, reset the adjustment screw andretighten locknut. Recheck calibration at 30%, 50% and70% of full-scale pressure.

Alarm Control Switch Adjustment

Switch setpoint is adjusted using the external adjustmentscrew (Fig.1). Turn screw clockwise to lower setpoint orcounter clockwise to raise setpoint. Turning screw 1/2 turnwill change the set point by approximately 1% of the full-scale.

INSTALLATION

Before Installation

Check gauge(s) against receiving paperwork; check forshipping damage and report immediately.

Model 120 / 122 Differential Pressure Gauges are fullyadjusted, calibrated and scaled to exact specifications beforeshipment, and are ready for immediate installation and use.The gauge may be line mounted to inlet and outlet pressureconnections, or flush mounted to a panel. An accessory isavailable to attach the gauge to a 2" support pipe for stanchionor wall mounting.

Tubing Connections

Connect the high pressure side of the system to the Highport and the low pressure side of the system of the Lowport of the gauge.

Note : A zero gauge reading when the system ispressurised, could indicate reversed High and Lowconnections.

Caution : When used in a high temperature system, thetubing to the gauge ports should be as long aspossible. To cool the fluid to less than200°F (90°C), a tube length of 6 feet is usuallyadequate to prevent high temperature fromdamaging the gauge.

Line Mounting

The gauge will be solidly supported if input nipples lessthan 3 inches in length are used. Use full-size 1/4" pipewhenever possible.

Panel Mounting (Fig.5)

1. Cut a 173.4 mm hole in panel.

2. Drill or punch 3 holes of 5.2 mm dia on 183.3 mm boltcircle diameter.

3. Remove 3 bezel screws.

4. Insert gauge into 173.4 mm hole from rear of panel.

5. Install and tighten 3 bezel screws through 3 holes drilledin Step 2.

Caution : The tubing connections to the gauge ports shouldbe of relatively flexible tubing, not rigid tubing.This will reduce the possibility of misalignmentbetween the mounted gauge and the tubing,during installation.

Disassembly

Before Attempting repairs

Contact SWITZER factory or nearest local office. Failure todo so will void any warranty

Bezel and Dial Chamber

1. Remove 3 bezel screws, bezel, lens /follower assembly,and lens gasket.

Remove two bridge-retaining screws, bridge and gaugepointer assembly.

Remove two dial-retaining screws and dial.

2. Separate dial chamber from pressure housing.

Pressure Housing

Caution : When tightening or loosening tubing connections,seal plug or adjustment locknut, secure pressurehousing using 1" wrench.

1. Turn off pressure to any tubing connected to gauge andremove tubing connections from gauge ports.

2. Loosen adjustment locknut and remove adjustment screwwith its ‘O’ ring.

3. Remove seal plug with its ‘O’ ring.

4. Using a pencil or wooden dowel, push the piston andspring out o the housing.

Reassembly

Before reassembling gauge, thoroughly clean the housing,piston and all metal parts with detergent solution or mildsolvent.

Caution : Do not use strong solvents (acetone, ether,toluene, etc.,) to avoid damage to dial or bezel.

Note : Use new seal ‘O’ rings when reassembling housing.

1. Lubricate ‘O’ rings and all sealing surfaces with siliconegrease and apply a thick film to the piston and housingcylinder.

2. Reassemble gauge by reversing disassembly procedure.

M16 × 1.5CableEntry

+0.5–0.0155.0 Ø

3 Holes

L.PH.P

120°

IM–1

20 R

ev.1

A(0

915)

Fig.5

5.5Ø at165.0 PCD

Switzer Process Instruments Pvt. Ltd.Switzer Process Instruments Pvt. Ltd.Switzer Process Instruments Pvt. Ltd.Switzer Process Instruments Pvt. Ltd.

REGD. OFFICE : 128, Sidco North Phase, Ambattur Estates, Chennai 600 098.

PH: 044– 26252017 / 26252018 FAX: 044–26248849

E-MAIL: [email protected]; [email protected]: www.switzerprocess.co.in