institution of gas engineers and managers igem/tsp… up-11 ed3-draft for... · igem/up/11 edition...
TRANSCRIPT
IGEM/UP/11 Edition 3 Draft for comment
Founded 1863
Royal Charter 1929
Patron: Her Majesty the Queen
INSTITUTION OF GAS ENGINEERS AND MANAGERS IGEM/TSP/17/128
Founded 1863 IGEM/UP/11 Royal Charter 1929
Communication XXXX Patron Her Majesty the Queen
Gas installations for educational establishments DRAFT FOR COMMENT 1 This draft Standard IGEM/UP/11 Edition 3 has been prepared by a Panel under the
chairmanship of Phillip Wild.
2 This Draft for Comment is presented to Industry for comments which are required by
30th June 2017, and in accordance with the attached comment form.
3 This is a draft document and should not be regarded or used as a fully approved and
published Standard. It is anticipated that amendments will be made prior to
publication.
It should be noted that this draft Standard contains intellectual property
belonging to IGEM. Unauthorised copying or use by any unauthorised person
or party is not permitted.
4 This is a copyright document of the Institution of Gas Engineers and Managers.
Enquiries should be addressed in the first instance to:
Thomas Donnelly
IGEM
IGEM House
26-28 High Street
Kegworth
Derbyshire, DE74 2DA Tel: 0844 375 4436 Fax: 01509 678188
Email:[email protected]
IGEM/UP/11 Edition 3 Draft for comment
Founded 1863
Royal Charter 1929
Patron: Her Majesty the Queen
Attached is the Draft for Comment of IGEM/UP/11 Edition 3 and the associated comment form.
We wish to make it as easy as possible for those of you representing industry bodies to issue
the draft to your Members. You can either forward this email with attachment complete or
forward it without the attachment and invite them to visit our website via where the Draft and
http://www.igem.org.uk/technical-standards/standards-development/drafts-for-comment.aspx
Comment Form are posted.
Organisations to which this Draft has been circulated:
ORG REP AIGT JOHN BARRATT Association of Register Gas Installers TONY BRUNTON BSI/GSE/30 GAVIN JONES
BPEC Awaiting contact BRITISH GAS RICHARD HARPER CAPITA DAVID J SMITH CIBSE HYWEL DAVIES CIPHE TONI-LOUISE MATTHEWS CITB RAY EWART
DNO COLLAB FORUM CHRIS CLARKE EI MARK SCANLON
ENA CLARE CANTLE-JONES EUSKILLS IAN MOSS GISG MIKE LEPPARD GAS SAFE REGISTER JOHN STIRLING HSE ANDREW COX
HSE MARGARET GREGSON HSENI JULIAN RICHMOND B&ES (was HVCA) RUSSELL MOTT ICOM ROSS ANDERSON *Large Business Forum TREVOR SMALLPEICE MAMCoP Board KEAVY LARKIN NATIONAL GRID HILARY BUXTON
NGN MARTIN ALDERSON NICEIC CHRIS LONG OFGEM STEVE BROWN
Organisation of professional gas operatives
WIM RUTJES
PIG CHERYL BURGESS
EUA (was SBGI) STEVEN SUTTON
IGEM/UP/11 Edition 3 Draft for comment
Founded 1863
Royal Charter 1929
Patron: Her Majesty the Queen
ORG REP SGN PAUL DENNIFF UKLPG RICHARD HAKEEM WALES & WEST CHRIS CLARKE
YPN DAVID MCLEOD IGEM
COUNCIL LESLEY ECOB SPC LESLEY ECOB MEMB C ROSS MCART
AUDIT C CHRIS BIELBY
TCC CHRIS GORMAN GMC VIC TUFFEN GUC RICHARD MARROW Industrial Affiliates KEVIN RANSOM
IGEM/UP/11 Edition 3 Draft for comment
Founded 1863
Royal Charter 1929
Patron: Her Majesty the Queen
IGEM/UP/11 Edition 3 Communication xxxx
Gas installations for educational establishments
Draft for comment
IGEM/UP/11 Edition 3 Draft for comment
Price Code: C3S
© The Institution of Gas Engineers and Managers IGEM House
26-28 High Street Kegworth
Derbyshire, DE74 2DA Tel: 0844 375 4436
Fax: 01509 678198 Email: [email protected]
IGEM/UP/11 Edition 3 Communication xxxx
Gas installations for educational establishments
Draft for comment
Copyright © 201X, IGEM. All rights reserved
Registered charity number 214001
All content in this publication is, unless stated otherwise, the property of IGEM. Copyright laws
protect this publication. Reproduction or retransmission in whole or in part, in any manner,
without the prior written consent of the copyright holder, is a violation of copyright law.
ISBN XXX X XXXXXX XX X
ISSN XXX XXXX
Published by the Institution of Gas Engineers and Managers
Previous Publications:
Communication 1704 (2004) – 1st Edition
Communication 1744 (2010) – 2nd Edition
For information on other IGEM Standards visit our website, www.igem.org.uk
IGEM/UP/11 Edition 3 Draft for comment
IGEM, IGEM House, 26-28 High Street, Kegworth, Derbyshire, DE74 2DA Website: www.igem.org.uk.
CONTENTS
SECTION PAGE
1 Introduction 1
2 Scope 4
3 Legal and allied considerations 6
3.1 Health and Safety at Work etc. Act (HSWA) 6
3.2 Building Regulations and Standards 6
3.3 Confined Spaces Regulations 7
3.4 Construction, Design and Management Regulations (CDM) 7
3.5 Control of Asbestos Regulations 7
3.6 Control of Substances Hazardous to Health Regulations (COSHH) 7
3.7 Dangerous Substances and Explosive Atmospheres Regulations 8
(DSEAR)
3.8 Electricity at Work Regulations 8
3.9 Gas Appliances (Safety) Regulations 8
3.10 Gas Cooking Appliances (Safety) Regulations 8
3.11 Gas Safety (Installation and Use) Regulations (GS(I&U)R) 8
3.12 Gas Safety (Management) Regulations (GS(M)R) 9
3.13 Management of Health and Safety at Work Regulations (MHSWR) 10
3.14 Pressure Systems Safety Regulations (PSSR) 10
3.15 Provision and Use of Work Equipment Regulations (PUWER) 10
3.16 Reporting of Injuries, Diseases, and Dangerous Occurrences 11
Regulations (RIDDOR)
3.17 School Premises Regulations 2012 12
4 Competency 13
5 Location and selection 14
6 Gas pipework 15
7 Isolation of gas pipework and appliances 22
7.1 Emergency control valve (ECV) 22
7.2 Additional emergency control valves (AECVs) 23
7.3 Appliance isolation 26
8 Laboratories 27
9 Art, craft, design and technology 29
9.1 Fixed and non-moveable appliances 30
9.1.1 General 30
9.1.2 Selection of equipment or appliances 30
9.1.3 Installation of gas-fired equipment 30
9.1.4 Flues and chimneys 31
9.1.5 Special procedures for ceramic kilns 31
9.2 Portable equipment 31
9.2.2 Mobile LPG Benches 31
9.2.3 Selection 32
IGEM/UP/11 Edition 3 Draft for comment
IGEM, IGEM House, 26-28 High Street, Kegworth, Derbyshire, DE74 2DA Website: www.igem.org.uk.
9.2.4 Storage and siting of equipment 32
9.2.5 Use of equipment 32
10 Food technology rooms 34
11 Installing appliances 35
12 Ventilation 37
12.1 General 37
12.2 Flues 38
12.3 Food technology 39
12.4 Science laboratory – Additional requirements 40
13 Electrical supplies and wiring 42
14 Testing, commissioning and maintenance 43
15 Advice to be given to the user 44
16 Emergencies 45
APPENDIX
1 Glossary, acronyms and abbreviations, units 46
2 References 48
3 Diversity 52
TABLE
1 Installation standards for domestic appliances 35
FIGURE
1 Relative Natural Gas and Liquefied Petroleum Gas pressure levels for
educational establishments 2
2 Exposed PE pipework is not permitted 16
3 Suggested in-floor duct ventilation system where external
ventilation is not possible 17
4 Typical overhead boom system 19
5 Overhead boom system at false ceiling level 19
6 Gas pipework running through a ceiling void with joints,
showing location of vents 20
7 CSST pipework with route identity marking 21
8 Primary meter installation showing the ECV on the inlet (left hand) side 22
9 Additional emergency control valve 23
10 Example of a weep by-pass proving system 24
11 An example of a laboratory bollard 27
IGEM/UP/11 Edition 3 Draft for comment
IGEM, IGEM House, 26-28 High Street, Kegworth, Derbyshire, DE74 2DA Website: www.igem.org.uk.
12 An example of a high pressure gases warning sign 28
13 Methods of provision of cooker stability 36
IGEM/UP/11 Edition 3 Draft for comment
1
SECTION 1 : INTRODUCTION
1.1 This Standard supersedes IGEM/UP/11 Edition 2, Communication 1744, which is
obsolete.
1.2 This Standard has been drafted by a Panel appointed by the Institution of Gas
Engineers and Manager’s (IGEM’s) Gas Utilisation Committee, subsequently
approved by that Committee and has been approved by IGEM’s Technical
Coordinating Committee on behalf of the Council of IGEM.
1.3 This Standard provides requirements for those concerned with the design,
installation, operation and maintenance of gas pipework, systems and
appliances in educational establishments, including schools; colleges;
universities and training facilities. It brings together:
guidance, interpretation and clarification of Legislation, Standards and Codes
of Practice (CoPs) indicating the degree to which compliance is required,
including those items that are applicable, and
current best practice and design in the installation and use of Natural Gas
(NG) and Liquefied Petroleum Gas (LPG) installations.
1.4 This Standard sets down the minimum requirements for safety in educational
establishments, for architects, designers, science health and safety advisers,
teaching and technical staff, in the operation of their systems and equipment. It
is recognised that a risk assessment in some educational establishments may
indicate a need for additional features such as larger valve handles, more easily
accessible controls, signage in more than one language, in Braille or lower levels
of carbon dioxide (CO2) within the teaching areas for specific health reasons.
The responsibility for such measures lies with competent persons having
responsibility for the design of the installation. Note 1: It is recognised that specialist laboratory demonstration equipment may be used. In such
cases, a risk assessment is needed and the general principles of this Standard may be applied to ensure safety.
Note 2: Current standards for ventilation in teaching areas are covered in DfE Building Bulletin 101
(BB101).
1.5 IGEM/UP/11 Edition 3 has been prepared by IGEM’s Panel comprising
representatives from the Council of Gas Detection and Environmental Monitoring
(CoGDEM), CLEAPSS, Department for Education, Gas Safe Register and
consultants.
1.6 Responsibility for safety in local authority maintained establishments rests with
the local authorities. In foundation schools, voluntary aided schools, academies,
city technology colleges, universities and independent schools, such
responsibility rests with governing bodies or proprietors.
In Private Finance Initiative (PFI) establishments safety in respect of the
building and maintenance rests with the building provider, safety of the
occupants rests with the user, but there are areas where both parties have to
agree responsibilities. Any requirement in this Standard does not imply
Government commitment to the provision of extra resources or funds.
1.7 This Standard reflects current best practice. As a general principle, this
Standard does not duplicate national/international legislation or Standards.
However, where appropriate, additional guidance; interpretation and clarification
have been provided. Applicable references for Legislation, Standards etc. are
listed in Appendix 2.
1.8 Terms such as maximum operating pressure (MOP) and operating pressure (OP)
have been adopted to reflect gas pressure terminology used in European
IGEM/UP/11 Edition 3 Draft for comment
2
standards. IGEM/G/4 defines these terms. These terms will arise in all relevant
IGEM Standards in future and possibly in other Standards.
Note: For a new system of installation pipework, the onus is on the designer to establish both the maximum incidental pressure (MIP) and MOP. For an existing system of installation pipework, the onus is on the designer/owner of the system to ensure that any increase in pressure within the system will not result in OP exceeding MOP of the system and on the gas transporter/meter asset manager (GT/MAM) to ensure that any change in their pressure regimes due to fault conditions will not jeopardise the safety of the downstream system. This involves effective communication between the GTs/MAMs and system designers/owners (see Figure 1).
STP
MIP
MOP
(example)
SP
OP
Time
Pre
ssu
re
For NG: STP = strength test pressure typically 82.5 mbar MIP = maximum incidental pressure typically 75 mbar MOP = maximum operating pressure typically not exceeding 28 mbar SP = set point of the regulator typically 21 mbar OP = operating pressure typically 19 to 21 mbar Note 1: This is extracted from IGEM/TD/13 and simplified for the purposes of IGEM/UP/11. For LPG: STP = strength test pressure typically 165 mbar
MIP = maximum incidental pressure typically 150 mbar MOP = maximum operating pressure typically not exceeding 45 mbar SP = set point of the regulator typically 37 mbar OP = operating pressure typically 32 to 45 mbar Note 2: 1 mbar = 100 P
FIGURE 1 - RELATIVE NATURAL GAS AND LIQUEFIED PETROLEUM GAS
PRESSURE LEVELS FOR EDUCATIONAL ESTABLISHMENTS
1.9 This Standard makes use of the terms “must”, “shall” and “should”, when
prescribing particular procedures. Notwithstanding clause 1.12:
the term “must” identifies a requirement by law in Great Britain (GB) at the
time of publication
the term “shall” prescribes a procedure which, it is intended, will be
complied with in full and without deviation
the term “should” prescribes a procedure which, it is intended, will be
complied with unless, after prior consideration, deviation is considered to be
acceptable.
Such terms may have different meanings when used in legislation, or Health and
Safety Executive (HSE) Approved Code of Practice (ACoPs) or guidance, and
reference needs to be made to such statutory Legislation or official guidance for
information on legal obligations.
IGEM/UP/11 Edition 3 Draft for comment
3
1.10 It is now widely accepted that the majority of accidents in industry are in some
measure attributable to human as well as technical factors in the sense that
actions by people initiated or contributed to the accidents, or people might have
acted better to avert them.
It is therefore necessary to give proper consideration to the management of
these human factors and the control of risk. To assist in this, it is recommended
that due regard be paid to HSG48.
1.11 The primary responsibility for compliance with legal duties rests with the
employer. The fact that certain employees, for example, “responsible
engineers”, are allowed to exercise their professional judgement does not allow
employers to abrogate their responsibilities. Employers must:
have done everything to ensure, as far as is reasonably practicable, that
there are no better protective measures that can be taken other than relying
on the exercise of professional judgement
have done everything to ensure, so far as is reasonably practicable, that
“responsible engineers” have the skills, training, experience and personal
qualities necessary for the proper exercise of professional judgement
have systems and procedures in place to ensure that the exercise of
professional judgement by “responsible engineers” is subject to appropriate
monitoring and review
not require “responsible engineers” to undertake tasks which would
necessitate the exercise of professional judgement that is beyond their
competence. There should be written procedures defining the extent to
which “responsible engineers” can exercise their judgement. When
“responsible engineers” are asked to undertake tasks which deviate from
this, they should refer the matter for higher review.
These principles equally apply to designated/delegated employees, contractors,
etc.
1.12 Notwithstanding clause 1.10, this Standard does not attempt to make the use of
any method or specification obligatory against the judgement of the responsible
engineer. Where new and better techniques are developed and proved, they
should be adopted without waiting for modification to this Standard.
Amendments to this Standard will be issued when necessary, and their
publication will be announced in the Journal of IGEM and other publications as
appropriate.
1.13 Requests for interpretation of this Standard in relation to matters within its
scope, but not precisely covered by the current text, should be addressed to
Technical Services, IGEM, IGEM House, 26-28 High Street, Kegworth,
Derbyshire, DE74 2DA or emailed to [email protected] and will be
submitted to the relevant Committee for consideration and advice, but in the
context that the final responsibility is that of the engineer concerned. If any
advice is given by or on behalf of IGEM, this does not relieve the responsible
engineer of any of his or her obligations.
1.14 This Standard was published in XXXXXXX.
IGEM/UP/11 Edition 3 Draft for comment
4
SECTION 2 : SCOPE
2.1 This Standard covers the design, installation, operation, and maintenance of gas
pipework, systems and appliances used for teaching purposes in educational
establishments including schools; colleges; universities and training facilities. Note: IGEM/UP/1101 provides guidance on the operational issues for gas systems and appliances.
2.2 This Standard assumes general compliance with other relevant Standards such
as IGEM/UP/2, IGE/UP/1 (or IGE/UP/1A or IGE/UP/1B as appropriate),
IGEM/UP/12, BS 6891, BS 6172 and BS 6173 and provide additional
requirements as considered necessary in educational establishments.
2.3 This Standard applies to new construction and replacement of, or extension to,
servicing, maintenance of existing installations. It is not retrospective, but it is
recommended that existing installations be modified to meet this Standard,
when appropriate. Note: Standards rarely cover the retrospective issue of existing installations. They can, however,
set a basis for consideration of performance upon which a risk assessment can be developed.
2.4 This Standard covers:
piped gas supplied from gas distribution systems such as a NG distribution
system or a LPG central bulk storage system
piped gas supplied through independent LPG supplies i.e. either a cylinder or
an individual bulk storage vessel
portable LPG systems and appliances, see also Sub-section 9.2
portable temporary LPG heaters, see Sub-Section 11.1.
2.5 This Standard applies to 1st, 2nd and 3rd family gases, as defined in BS EN 437. Note: 1st, 2nd and 3rd family gases can be heavier than air. 2nd family gases include lighter than air
gases such as NG and manufactured substitutes (hereafter referred to as NG). 3rd family gases include heavier than air gases such as LPG and sometimes further defined as
propane or butane and in the vapour phase.
2.6 This Standard does not cover gas installations in an individual domestic
dwelling integral with an educational establishment. However, the installation of
domestic gas appliances in an educational establishment itself is covered.
This Standard does not cover piped supplies to or from oxygen or acetylene
systems. In such cases reference needs to be made to HSE Guidance HSG 139 -
The safe use of compressed gases in welding, flame cutting and allied
processes.
This Standard does not cover liquid fuel systems, appliances and flues however
many of the risks associated with gas systems will also apply to liquid fuel
systems and similar standards of safety need to be applied. Advice for storage
and use of bottled gases and other gases used for educational purposes are
covered in CLEAPSS guidance.
Note: Gas meter installations are not covered in this Standard. IGEM/GM/6, IGEM/GM/8 or BS 6400 apply as appropriate.
2.7 This Standard does not cover the primary design requirements for central
heating and domestic hot water plant for which reference to IGEM/UP/10 is
necessary. However it does address automatic isolation valves (AIVs) and other
safety features for educational establishments.
2.8 This Standard does not cover central catering installations for which reference to
BS 6173 is necessary.
IGEM/UP/11 Edition 3 Draft for comment
5
2.9 This Standard does not cover the installation and use of specialist test and
demonstration apparatus. For such apparatus, a competent person is required to
ensure the apparatus is fit for purpose. In addition, such apparatus may only be
operated by a competent person.
2.10 This Standard does not cover training and assessment facilities for gas
operatives.
2.11 All pressures are gauge pressures unless otherwise stated.
2.12 Italicised text is informative and does not represent formal requirements.
2.13 Appendices are informative and do not represent formal requirements unless
specifically referenced in the main sections via the prescriptive terms “must”,
“shall” or “should”.
IGEM/UP/11 Edition 3 Draft for comment
6
SECTION 3 : LEGAL AND ALLIED CONSIDERATIONS
This Standard is set out against a background of Legislation in force in GB at the time of
publication (see Appendix 2). Similar considerations are likely to apply in other countries and
reference to appropriate national Legislation will be necessary.
Appendix 2 lists Legislation, guidance notes and Standards etc. which are identified within this
Standard as well as further items of Legislation that may be applicable.
Where Standards are quoted, equivalent national or international Standards etc. equally may
be appropriate.
Unless otherwise stated, the latest version of the referenced document should be used.
3.1 HEALTH AND SAFETY AT WORK ETC. ACT (HSWA)
HSWA applies to all persons involved with work activities, including employers,
the self-employed, employees, designers, manufacturers, suppliers etc. as well
as the owners of premises. It places general duties on such people to ensure, so
far as is reasonably practicable, the health, safety and welfare of employees and
the health and safety of other persons such as members of the public who may
be affected by the work activity.
3.2 BUILDING REGULATIONS AND STANDARDS
a) England and Wales (as Amended)
Building Regulations are Statutory Instruments that must be followed when
engaged in any building work. They are written in a format of broad
Regulations, setting out simple requirements in a Separate Schedule. Suggested
ways of complying with these Regulations are contained in Approved
Documents.
The Approved Documents that apply to gas work are:
A (Structure)
B (Safety in Fire)
F (Ventilation)
G (Hygiene)
J (Heat producing Appliances)
L (Conservation of Fuel and Power)
M (Access to and use of buildings)
P (Electrical Safety).
b) Building Standards (Scotland) Regulations and Amendments
The Building Standards (Scotland) are written directly as Regulations within the
Statutory Instrument. The Regulations can be satisfied:
by compliance with Technical Standards published by the Scottish Office
conforming with the provisions of “deemed to satisfy” documents, for
example British Standards
other equivalent means.
c) Northern Ireland (as amended)
The Regulations can be satisfied:
by compliance with Technical Standards
IGEM/UP/11 Edition 3 Draft for comment
7
conforming with the provisions of “deemed to satisfy” documents, for
example British Standards
other equivalent means.
3.3 CONFINED SPACES REGULATIONS
These Regulations apply to a wide range of confined spaces. The supplier or
designer of an enclosure and equipment within it is required to perform a risk
assessment of the enclosure with respect to safe access and egress and to give
clear instructions to operators on access/egress as well as to what actions to
take in the event of a gas alarm occurring. Employers and the self-employed
should prevent entry into confined spaces unless avoidance is not reasonably
practicable and unless there is a system of work which renders the work safe.
They are also required to have specific emergency arrangements in place. More
information on the Regulations is given in L101. A free leaflet, INDG 258, is also
available.
3.4 CONSTRUCTION, DESIGN AND MANAGEMENT REGULATIONS (CDM)
CDM impose duties on designers, clients (and their agents), developers,
planning supervisors and principal contractors. Not all the Regulations apply to
all construction projects. Further information is given in L153. For a notifiable
project (as defined in CDM) the planning supervisor must notify HSE before
construction work commences. Construction includes the alterations, repair,
redecoration, maintenance, decommissioning or demolition of a structure. It
also covers installation, commissioning, maintenance or removal of gas services.
3.5 CONTROL OF ASBESTOS REGULATIONS
3.5.1 These Regulations set out standards for the identification, monitoring and
assessment of work that may expose workers to asbestos and the measures
needed to control the risk.
3.5.2 Employers cannot carry out any work that exposes, or is likely to expose,
employees to asbestos unless an assessment of that exposure risk has been
made. Employers have to set out steps to be taken to prevent, or reduce to the
lowest level reasonably practicable, that exposure. Employers have to carry out
medical surveillance of employees if they work over a certain time limit.
3.5.3 The Regulations impose a duty on those with responsibilities for the repair and
maintenance of non-domestic premises to find out if there are, or may be,
asbestos containing materials within them; to record the location and condition
of such materials and assess and manage any risk from them, including passing
of any information about their location and condition to anyone likely to disturb
them.
3.5.4 Further information is available in HSG 227. Other associated ACoPs are L127
and L143. In addition, advice is also available in HSE’s Asbestos Task manual.
3.6 CONTROL OF SUBSTANCES HAZARDOUS TO HEALTH REGULATIONS
(COSHH)
3.6.1 COSHH, which reinforce existing statutory obligations under HSWA, impose a
duty on employers to protect employees against risks to health, whether
immediate or delayed arising from exposure to substances hazardous to health,
either used or encountered, as a result of a work activity. They also impose
certain duties on employees.
3.6.2 Under COSHH, work must not be carried out which is liable to expose employees
to hazardous substances unless the employer has made a suitable and sufficient
IGEM/UP/11 Edition 3 Draft for comment
8
assessment of the risk created by the work and the steps that need to be taken
to comply with COSHH. After assessing the risk, it is necessary to inform
employees of the risks and to carry out the appropriate training and instruction
to ensure the risks are minimised. In certain cases, control measures such as
ventilation or personal protective equipment may be necessary and where
provided they must be used.
3.7 DANGEROUS SUBSTANCES AND EXPLOSIVE ATMOSPHERES
REGULATIONS (DSEAR)
DSEAR are concerned with protection against risks from fire, explosion and
similar events arising from dangerous substances used or present in the
workplace. DSEAR require that risks from dangerous substances are assessed,
eliminated or reduced. They contain specific requirements to be applied where
an explosive atmosphere may be present and require the provision of
arrangements to deal with accidents, emergencies etc. and provision of
information, training and safe use of dangerous substances. DSEAR also require
the identification of pipelines and containers containing hazardous substances.
The following publications contain details of DSEAR and their application:
L138
INDG 370.
3.8 ELECTRICITY AT WORK REGULATIONS
3.8.1 These Regulations apply to a wide range of electrical work, from overhead
power lines to the use of office computers and batteries and include work on gas
equipment using electrical energy.
3.8.2 They are concerned with the prevention of danger from electric shock, electric
burn, electrical explosion or arcing or from fire or explosion initiated by electrical
energy.
3.8.3 They impose duties on every employer, employee and self-employed person and
require that persons engaged in electrical work be competent or be supervised
by competent persons. Note: A ‘‘Memorandum of Guidance on the Electricity at Work Regulations, 1989’’ is available
from HMSO and gives useful information on the Regulations. Further advice is contained in HSR25.
3.9 GAS APPLIANCES (SAFETY) REGULATIONS
Until 1992, the safety of consumers using gas appliances offered for sale in the
United Kingdom (UK) was covered, generally, by the Consumer Protection Act
and specifically, by the Gas Cooking Appliance (Safety) Regulations and the
Heating Appliances (Fireguard) Regulations. The Gas Appliances (Safety)
Regulations introduced specific requirements, for all gas appliances which must
be met before the product can be sold. All new appliances must carry CE
marking and be endorsed for use in the UK.
3.10 GAS COOKING APPLIANCES (SAFETY) REGULATIONS
These Regulations give specific requirements on installing cookers which may be
second hand or already belong to the customer.
3.11 GAS SAFETY (INSTALLATION AND USE) REGULATIONS (GS(I&U)R)
3.11.1 GS(I&U)R are relevant statutory provisions of HSWA setting out general and
detailed requirements dealing with the safe installation, maintenance and use of
gas systems, including gas fittings, appliances and flues.
IGEM/UP/11 Edition 3 Draft for comment
9
3.11.2 GS(I&U)R address both NG and LPG (see Appendix 4 for properties of gases).
3.11.3 GS(I&U)R place responsibilities on those installing, servicing, maintaining or
repairing gas appliances, pipework etc. as well as suppliers and users of gas.
3.11.4 GS(I&U)R define the gas supplier for both NG and LPG and ACoP L56 provides
guidance on those definitions in particular for the more complicated case of LPG
supplied from vessels and from cylinders.
3.11.5 GS(I&U)R define the type of work that requires persons carrying out such work,
or their employers, to be a ‘‘member of a class of persons approved by the
HSE’’. In United Kingdom, the Isle of Man and the Channel Islands this means
registration under the Gas Safe Register scheme. Note: Guidance on individual competencies required for persons carrying out gas work at
premises not covered by GS(I&U)R is given in L56.
3.11.6 The installer must check the safety of any appliance or pipework they install or
work on and take appropriate action where they find faults. Where the premises
are let or hired out, the landlord or hirer has special responsibilities to ensure
that any installer they use for the gas fitting, service or maintenance or safety is
a ‘‘member of a class of persons approved by the HSE’’ (see clause 3.11.5) and
is competent to carry out such work. If any serious fault is found the installer
must inform both the landlord/hirer, as well as the user so that such faults can
be rectified before further use.
3.11.7 GS(I&U)R place responsibilities on LPG suppliers to deal with escapes of LPG.
For NG, GS(M)R applies (See Sub-Section 3.12). Note: Advice on dealing with gas escapes is contained in IGEM/SR/29.
3.12 GAS SAFETY (MANAGEMENT) REGULATIONS (GS(M)R)
3.12.1 GS(M)R place specific duties on GTs, or their emergency service providers
(ESPs), for dealing with gas escapes of NG from pipes on their networks. Their
primary duty is to make the situation safe. They are responsible not only for
dealing with escapes from their own pipes, but also for dealing with escapes
from gas fittings supplied with gas from pipes on their network. In GS(M)R, the
term “gas escapes” includes escapes or emissions of carbon monoxide (CO) from
gas fittings. Responsibilities for gas escapes of LPG are outlined in GS(I&U)R
(see clause 13.11.7).
3.12.2 The ESP has specific duties to:
provide a continuously staffed and free telephone service to enable persons
to report gas escapes and
pass such reports on to the person who has the responsibility for dealing
with the escape.
In addition, there are duties imposed on gas suppliers and GTs to notify the ESP
should they, rather than the ESP receive a report of an escape from the
consumer.
3.12.3 GS(M)R require GTs to investigate fire and explosion incidents upstream of the
emergency control valve (ECV) and to send a report of the investigation to HSE.
GTs are also required to investigate fire and explosion incidents downstream of
the ECV but this is limited to establishing whether the seat of the fire or
explosion was in an appliance and if so which one or in the installation pipework.
IGEM/UP/11 Edition 3 Draft for comment
10
3.12.4 Responsibility for investigating RIDDOR reportable incidents (see Sub-Section
3.16) as a result of an escape of CO from incomplete combustion of gas from a
gas fitting, is placed on gas suppliers. HSE must be notified before such
investigations commence. Note: Advice on dealing with gas escapes is contained in IGEM/SR/29.
3.13 MANAGEMENT OF HEALTH AND SAFETY AT WORK REGULATIONS
(MHSWR)
In addition to specific duties under GS(I&U)R (see Sub-Section 3.11) MHSWR
impose a duty on employers and the self-employed to make assessments of
risks to the health and safety of employees, and non-employees affected by
their work. They also require effective planning and review of protective
measures.
3.14 PRESSURE SYSTEMS SAFETY REGULATIONS (PSSR)
3.14.1 PSSR impose duties on designers, importers, suppliers, installers and user or
owners to ensure that pressure systems do not give rise to danger. This is done
by the correct design, installation and maintenance, provision of information,
operation within safe operating limits and where applicable, examination in
accordance with a written scheme of examination drawn up or approved by a
competent person (as defined by PSSR).
3.14.2 Relevant fluids for the purpose of PSSR would be NG at a pressure greater than
0.5 bar and above atmospheric pressure or LPG (which is a liquid with a vapour
pressure greater than 0.5 bar and above at ambient temperature). A pressure
system would include bulk storage tanks, pipelines and protective devices but
not an LPG cylinder (transportable pressure receptacle). Once the pressure in
the pipework drops below 0.5 bar and the user/owner can show clear evidence
that the system does not contain and is not liable to contain, a relevant fluid
under foreseeable operating conditions then that part of the system is no longer
covered by the Regulations. This is likely to be the case after the pressure relief
valve associated with a pressure reducing valve which takes the pressure to
below 0.5 bar for example at the entry to a building. Note: The special requirements placed on protective devices in such systems (see paragraph
110b of L122). PSSR also apply to pipelines and their protective devices in which the pressure exceeds 2 bar (see Schedule 1 part 1 item 5 of L122).
3.14.3 More information is available in L122 and some information is presented in
INDG 261 and INDG 178.
3.15 PROVISION AND USE OF WORK EQUIPMENT REGULATIONS (PUWER)
3.15.1 Work equipment has a wide meaning and includes tools such as hammers,
laboratory apparatus, for example Bunsen burners, ladders, photocopiers, lifting
equipment and machinery for use at work.
3.15.2 PUWER place duties on employers in relation to selection, suitability,
maintenance, inspection, installation, instruction and training, prevention of
danger and control of equipment.
3.16.3 More information on PUWER is given in L22. Free leaflets include INDG 291 and
INDG 229.
IGEM/UP/11 Edition 3 Draft for comment
11
3.16 REPORTING OF INJURIES, DISEASES AND DANGEROUS OCCURRENCES
REGULATIONS (RIDDOR)
RIDDOR require employers, self-employed people or those in control of work
premises to report certain work related accidents, diseases and dangerous
occurrences.
3.16.1 Other people have duties to report certain gas incidents which may not appear
to be work related:
Death, major injury, lost consciousness, or been taken to hospital for
treatment to an injury arising out of the distribution, filling, import or supply
of NG or LPG are to be reported by the conveyor for NG and the filler,
importer or supplier for LPG
dangerous gas fittings (as defined in RIDDOR) should be reported by a
"member of a class of persons". Gas Safe registered engineers are to provide
details of any gas appliances or fittings that they consider to be dangerous,
to such an extent that people could die, lose consciousness or require
hospital treatment. The danger could be due to the design, construction,
installation, modification or servicing of that appliance or fitting, which could
cause:
an accidental leakage of gas
incomplete combustion of gas or
inadequate removal of products of the combustion of gas.
3.16.2 Major injuries, death and dangerous occurrences are to be notified immediately,
for example by telephone, to the enforcing authority by the “responsible person”
as defined by RIDDOR. Report can be made to the Incident Contact Centre:
for fatal and major injuries only, telephone on 0845 300 9923 (opening
hours Monday to Friday 8.30 am to 5 pm) and complete appropriate on-line
form
all other reports at HSE website www.hse.gov.uk
Complete the appropriate online report form listed below.
report of an injury
report of a dangerous occurrence
report of an injury offshore
report of a dangerous occurrence offshore
report of a case of disease
report of flammable gas incident
report of a dangerous gas fitting.
The form will then be submitted directly to the RIDDOR database and a copy
issued to the person making the report.
On-line written reports are to be submitted within the required timescale (10
days, or 14 days for dangerous gas fittings). Other reports need to be made as
soon as practicable and within 10 days of the incident.
3.16.3 INDG 453 contains detailed guidance on RIDDOR, including a full list of injuries
etc. that need reporting.
3.16.4 IGEM/GL/8 provides guidance on the reporting and investigation of gas-related
incidents.
IGEM/UP/11 Edition 3 Draft for comment
12
3.17 SCHOOL PREMISES REGULATIONS 2012
3.17.1 The Education Act 1996 places a duty on the Secretary of State for Education to
prescribe standards for the premises of all maintained schools in England and
Wales. The Regulations apply to nursery, community, community special,
foundation, foundation special and voluntary schools and to pupil referral units.
Those for England are set out in The School Premises (England) Regulations
2012 (SPRs) and they apply to all existing and new schools maintained by a
local authority. The Education (School Premises) Regulations 1999 continue to
apply to maintained schools in Wales.
3.17.2 The Education Act 2002 (as amended by the Alternative Provision Academies
and 16 to 19 Academies (Consequential Amendments to Subordinate
Legislation) (England) Order 2012) and the Education (Independent School
Standards) (England) (Amendment) Regulations 2012 empowers the Secretary
of State to prescribe standards for the premises of independent schools, which
include Academies (including alternative provision Academies) and Free Schools.
These are set out in Part 5 of The Education (Independent School Standards)
(England) Regulations 2014 (ISS).
While there continues to be two sets of school premises Regulations in place,
their requirements are now identical in England and all types of schools now
have to meet the same standards.
IGEM/UP/11 Edition 3 Draft for comment
13
SECTION 4 : COMPETENCY
4.1 Persons who design gas installations must have a knowledge and understanding
of the Regulations and Standards that apply to ensure that the completed plans
will produce a safe and satisfactory installation. The design shall also ensure
safe operation and maintenance. A competent person is also someone who has
sufficient training and experience or knowledge and other qualities that allow
them to safely perform a task. The level of competence required will depend on
the complexity of the situation and the particular risks associated with the task.
4.2 Persons who install or maintain gas pipework, systems and appliances in
educational establishments must be competent to do so and compliance with
GS(I&U)R must be achieved where those Regulations apply.
4.3 All gas works must be carried out by a business or self-employed person(s) that
is a ‘‘member of a class of persons approved by (see clause 3.11.5).
4.4 Teaching staff who operate a gas fired appliance shall be trained on the safe use
and operation of the appliance. Persons who do not satisfy clause 4.3 must not
perform work on gas pipework and appliances. Changing LPG cylinders and
cartridges is not considered to be ‘‘work’’ under GS(I&U)R. but they must still be
able to perform the work in a safe manner.
IGEM/UP/11 Edition 3 Draft for comment
14
SECTION 5 : LOCATION AND SELECTION
5.1 Appliances and associated equipment/controls shall be selected such that they
are suitable and safe for their operation and maintenance by persons with a
wide range of abilities.
5.2 Appliances shall be located in rooms/spaces that are suitable and safe for their
operation and maintenance.
5.3 Type A and Type B space or water heating appliances shall not be located within
a teaching area. Type C appliances for space or water heating should not be
located within a teaching area unless suitably protected against contact with hot
surfaces, interference and physical damage as required by a risk assessment.
Note: For emergency heating for example short term use of LPG cabinet heaters or electric
space heating to be supported by a risk assessment.
5.4 The construction of nearby surfaces shall be able to withstand the weight of
appliances, the temperatures generated when in use. Provision shall be made for
the safe disposal of any waste liquids associated with the operation and use of
the appliance (e.g. condensates).
5.5 Openings from rooms (floors, walls and ceilings) shall be sealed to prevent the
transmission of any gases or combustion product to other occupied spaces.
IGEM/UP/11 Edition 3 Draft for comment
15
SECTION 6 : GAS PIPEWORK
6.1 Installation pipework shall be installed in accordance with IGEM/UP/2. Gas
system operating pressures shall not exceed 50 mbar except in special
circumstances for specialised experimental equipment or where LPG cartridges
are used. In such cases a full risk assessment covering the safe provision of gas
shall be carried out, see IGEM/UP/16.
6.2 NG pipework shall have a design pressure drop from the outlet of the meter
installation to the point of use, isolation valve or gas tap, as appropriate not
exceeding 1 mbar for NG. LPG pipework shall have a design pressure drop from
the outlet of a meter installation or pressure vessel installation to the point of
use, isolation valve or gas tap, as appropriate not exceeding 2 mbar for.
Note 1: It may be appropriate to have higher pressure drops for a NG system of OP exceeding 25 mbar, or an LPG system of an OP exceeding 45 mbar for propane and 35 mbar for butane.
Note 2: IGEM/UP/2 contains the relevant requirements.
6.3 When sizing pipework, if it is proposed to make allowance for diversity of usage
due consideration shall be given to safety in the event of all appliances being
used at once e.g. that they all continue to operate safely. Note 1: For example, a laboratory may have 60 gas taps but a design maximum of 30 students.
Each may be operating a Bunsen burner so the design load could be 30 Bunsen burners. Allowance could also be made for extra pupils and the design might then be for 40 Bunsen burners in use. Similarly, if there are 30 gas cookers, it is unlikely that they will all be in use at the same time and for example a 70% load diversity could be applied.
Note 2: See IGE/GL/1 and BS 6400 for further information about diversity. Note 3: Due account of the additional pressure drops across AIVs, check meters and non-return
valves (NRVs) need to be taken into consideration to ensure the maximum design pressure drop is not exceeded.
6.4 Pipework shall be readily identified to indicate it carries a fuel gas. This shall be
achieved by fully painting with Ochre yellow to BS 4800 08 C 35 or Primrose
yellow to BS 4800 10 E 53 colours or by banding the pipe (which does not have
to be painted) with GAS marker tape or in accordance with BS 1710.
LPG pipework shall be permanently marked “LPG” at valves and major changes
of direction/tees. Note 1: IGEM/UP/2 contains more information. Note 2: Safety warning signs will be black lettering on a yellow background. Further guidance is
given in L64.
The installation and siting of any LPG storage vessel shall comply with UKLPG
Codes of Practice and HSE Guidance. The location shall make due allowance for
the separation distances from buildings, boundaries and property lines, the
proximity of nearby and overhead cables, access for delivery and installation
vehicles.
6.5 Bulk storage should be secured from tampering by the use of lockable valve
covers or fenced compounds. Cylinder systems should be located inside locked
cages or ventilated lockers. Siting shall take account of safe access for refilling
bulk vessels and changing of cylinders.
LPG cylinders (other than cartridges) shall not be located within the building,
other than in a sealed and fire protected compartment located on/within the
outer building wall, that is accessible only from outside the building and
naturally ventilated solely to outside the building. See Sub-Section 9.2.4
mobile LPG benches. See also BB100 and UKLPG Cop 24 Part 6.
IGEM/UP/11 Edition 3 Draft for comment
16
6.6 For a piped gas supply to any burner provided with air, oxygen or other
extraneous gases under pressure a suitable device must be installed upstream
of the first control in the gas supply to each burner, group of burners or the
plant. Note 1: The suitable device may be a NRV. Note 2: This is a legal safety requirement and the installer needs to recommend that this valve be
included in an annual maintenance check.
Manual burners provided with air, oxygen or other extraneous gases under
pressure, such as on brazing hearths, shall be fitted with a NRV at each location
to protect the rest of the gas supply system.
6.7 The materials chosen for pipework shall be selected with regard to the ability to
withstand damage or unauthorised interference. Note: Concealed pipework routes or the use of steel pipes are typical options.
Copper and pliable stainless steel (CSST) pipework that is exposed or surface
mounted and is not protected against foreseeable damage shall not be used.
Where copper pipe is located in concealed locations, it shall preferably be joint
free or be brazed. Where not practicable it shall be jointed using capillary
fittings.
6.8 Polyethylene (PE) pipework shall not be installed in a building and shall not be
exposed when installed outside a building (see Figure 2 and more detailed
advice in IGEM/UP/2).
FIGURE 2 - EXPOSED PE PIPEWORK IS NOT PERMITTED
6.9 Any manual isolation valve shall be securely fitted with a valve handle. Note: Such handles and hence valves may be interfered with if located in a vulnerable location.
Nevertheless manual isolation valves need to be accessible for maintenance and where intended, for use in an emergency.
6.10 Any pipework system shall include isolation valves and local purge points at
intersections/branches.
IGEM/UP/11 Edition 3 Draft for comment
17
Note: This allows maintenance, repair and modification without the need to shut down the whole system.
Any purge connection should be at least R3/4 or 25% of the pipe size whichever
is the larger and these should be located at each end of any pipe section that
may need to be purged during commissioning or decommissioning.
6.11 Where pipework is located in a floor duct or ceiling space , either:
the duct or space shall be ventilated to outside air, or
the duct or space shall be ventilated into the room (see Figure 3 for lighter
than air gases) or
the duct or space shall be filled with dry inert material, such as dry washed
sand or crushed slate
for LPG systems in ducts, refer to IGEM/UP/2.
FIGURE 3 - SUGGESTED IN-FLOOR DUCT VENTILATION SYSTEM
WHERE EXTERNAL VENTILATION IS NOT POSSIBLE
6.12 Appliance Connections
6.12.1 Fixed appliances shall be connected to the gas supply using one of the methods
permitted by IGEM/UP/2.
6.12.2 Appliances which are required to be moved from time to time (e.g. for cleaning)
shall be connected using a flexible appliance connector a self-sealing plug/socket
complying with BS EN 15069 and one of the following methods, as appropriate:
a flexible hose complying with BS 669-1 for domestic cooking appliances
used in food technology settings
a flexible hose complying with BS 669-2 for domestic and commercial
equipment in a catering training setting
or a flexible hose complying with BS EN 14800.
6.12.2.1 Flexible appliance connectors shall:
be as short a reasonably practicable and not exceed 1.4m long
be located in an accessible position
be connected to the fixed gas installation pipework with self-sealing and
swivel plug/socket end connections
ventilator
floor screed
ventilated floor ductgas pipe
gas pipe passes throughsleeve
sleeve sealed at one end
IGEM/UP/11 Edition 3 Draft for comment
18
be protected by stainless steel restraint cables, fixed to a secure surface
such as a wall, floor, or fixed bollard of such length as will prevent the
flexible connection from being strained, excessively bent at its connections
or allowed to contact hot surfaces.
6.12.2.2 Restraint cables shall not be fixed to the gas pipework. In an overhead boom the
point of fixing should be as high as practicable to prevent hanging loops of the
restraining cable causing a hazard.
Note: For ease of use, it may incorporate a snap-shackle for simple connection to a boom or to
the building structure.
6.12.2.3 A self-sealing plug shall be connected to every self-sealing fitting to seal the
connection when not in use, unless there is a manual isolation valve fitted
immediately before the fitting.
6.12.2.4 Pliable corrugated stainless steel tubing shall not be used for connecting
moveable appliances.
6.12.3 Lightweight readily-moveable appliances such as laboratory Bunsen burners,
hand torches, small boiling rings, etc. that are fitted with a connection designed
to accept flexible tube by the manufacturer, and which are operated under
continual supervision may be connected to the gas supply using flexible rubber
tubing, under the following conditions:
the tubing shall be as short as reasonably practicable and not exceed 1.0m
long
such tubing may only be used when connecting to a bench top type
laboratory tap
where the outer diameter of the tube is 8mm or greater, the tube shall be
secured using a crimp or swaged or worm type clip providing that the
pressure does not exceed 50 mbar. Crimp or swaged type clips shall be
applied for pressures exceeding 50 mbar for all hoses.
Note: For these applications the flexible tubing may be natural or synthetic rubber and selection depends on the gas in use. Natural rubbers are not normally suitable for use with LPG or for NG above 50mbar. A synthetic rubber such as neoprene may be suitable for NG and LPG gases.
6.12.3.1 Flexible tubing used shall be subject to regular inspections and replaced after
five years’ service or before if showing signs of:
physical damage, such as cuts or abrasions, stretching, flattening, kinking
and where fitted, missing/worn sealing washers, damaged cylinder
connections
environmental deterioration such as stiffening, cracking, delamination of
outer covering, chemical degradation i.e. softening of outer coating by
contact with oil
failure such as – blistering, soft spots, rupture and, for preassembled end
fittings, corrosion or loosening of swaged fittings attaching hose.
If the tubing replacement date is not date marked by the manufacturer, the
installer should mark it with the year of replacement or record the replacement
date in the site technical file.
Note: This is normally 5 years but may be as long as 10 years, depending upon materials. See BS 6891.
6.13 Any overhead boom shall be directly ventilated into the room and sealed to
prevent gas ingress into the ceiling space (see Figures 4 and 5).
IGEM/UP/11 Edition 3 Draft for comment
19
FIGURE 4 - TYPICAL OVERHEAD BOOM SYSTEM
FIGURE 5 - TYPICAL OVERHEAD BOOM SYSTEM AT FALSE CEILING
LEVEL
IGEM/UP/11 Edition 3 Draft for comment
20
6.14 Any duct or ceiling void containing gas pipework shall be ventilated to ensure
that minor gas leakage does not cause the atmosphere within the duct or void to
become unsafe. Note 1: The level of ventilation is not intended to clear a major gas escape arising from damage or
failure of a gas pipe. Note 2: IGEM/UP/2 gives additional guidance on ventilation of pipework.
Pipework located in ceiling voids is a special safety issue in many old designs of
educational establishments. GS(I&U)R state that all pipework has to be in a
ventilated location. Any unventilated void containing gas pipework shall be
modified to include ventilation either to the outside air or internally to a
normally occupied space, such as a corridor. Note: Care will be needed to ensure that fire compartment walls/floors are not breached (see
relevant Building Regulations and Standards).
6.15 Where gas pipework is located within a ceiling space, the space shall be
ventilated along the route of the pipe normally near to joint locations.
FIGURE 6 - GAS PIPE RUNNING THROUGH A CEILING VOID WITH
JOINTS, SHOWING TYPICAL LOCATION OF VENTS
A ventilated grille panel should be located near to each joint. Where this is not
practicable, a gap of approximately 80 mm around the ceiling perimeter should
be applied (see Figure 6) Note 1: An alternative is to form a small horizontal duct within the ceiling space containing the
pipe and to ventilate this duct at each end with a grille free area of not less than 100 cm2
or 50% of the cross sectional area, whichever is the greater. Note 2: More detailed information on provision of duct ventilation is given in IGEM/UP/2.
6.16 Where an overhead gas pipework supply is to extend to portable equipment;
work benches or fume cupboards, the pipework shall be adequately supported
and fixed in such a way that it cannot “sway”.
For an overhead distribution boom containing a number of laboratory services,
each boom shall be fitted with a manual isolation valve to assist in the
maintenance of the equipment.
6.17 Where CSST is used in an unventilated space a separate sleeve i.e. not the
plastic cover to the stainless steel tube, shall be applied throughout its length
within the space.
Flanged joint
Screwed joint
IGEM/UP/11 Edition 3 Draft for comment
21
6.18 Each “run” of CSST pipework shall be indelibly and permanently marked at
locations along its route to discriminate the individual “runs” from each other
(see Figure 7). Note: For example, for science areas, label Lab 1 supply, Lab 2 supply, kitchen supply, etc.
6.19 CSST shall be supported throughout its route for example on cable trays (see
Figure 7). Note: Cable ties may also be used to secure horizontal “runs” of pipe.
FIGURE 7 - CSST PIPEWORK WITH ROUTE IDENTITY MARKING
LA
B 1
LA
B 2
LAB 3
CLA
SS 7
CLA
SS 8
WORKSHOP 1
WORKSHOP 2
LIBRARY
KITCHEN
DE
SIG
N S
TU
DIO
GYM
OFFIC
E
IGEM/UP/11 Edition 3 Draft for comment
22
SECTION 7 : ISOLATION OF GAS PIPEWORK AND APPLIANCES
7.1 ECV
7.1.1 An ECV must be provided by the GT and designated as the ECV to enable the
supply of gas to the premises to be shut off in the case of an emergency. It will
be situated at the end of the gas service and be upstream of any primary meter
installation. Note 1: For larger installations with twin stream regulators and possibly a meter by-pass, it may
be convenient to designate the inlet or outlet meter isolation valve as an additional emergency control valve (AECV) to satisfy requirements under GS(I&U)R for emergency control (see clause 6.2).
For LPG installations without a meter the ECV should be located near to the
outlet of the pressure vessel regulators.
7.1.2 The ECV must be operated by a key, lever or a hand-wheel which is securely
attached to the operating spindle of the control.
7.1.3 The ECV must be readily accessible for use in an emergency and the space
around it must be kept clear of stored items and flammable materials (see
Figure 8).
FIGURE 8 - PRIMARY METER INSTALLATION SHOWING THE ECV ON THE
INLET (LEFT HAND) SIDE
7.1.4 The means of operating the ECV shall be clearly and permanently marked or a
notice in permanent form shall be prominently displayed close by to indicate
whether the valve is open or closed. Note: The handle may be painted red to enable quick discrimination in an emergency.
7.1.5 Where vandalism or misuse is a possibility, access to the ECV may need to be
restricted by means of a locked door, cabinet etc. and the key held in a place of
security. In such circumstances a permanent notice shall be displayed near to
the lock indicating where the key may be readily obtained. Note: The problem of unauthorised entry renders it generally impractical to locate a manual
valve outside a building or even outside a self-contained area. In addition, the problems of unauthorised tampering with the valves may lead to hazardous situations.
Appropriate staff to be briefed on the location and operation of the ECV.
IGEM/UP/11 Edition 3 Draft for comment
23
7.2 ADDITIONAL EMERGENCY CONTROL VALVES (AECVs)
7.2.1 For use in an emergency situation an AECV shall be installed as near as
practicable to points where installation pipework enters each separate teaching
and preparation area (see Figure 9). Particular attention shall be given to
considerations of unauthorised use and accessibility in the event of an
emergency. Note: The use of a back-up AIV with manual reset may be a solution, see clause 7.2.3.
Relevant staff shall be trained on the location and operation of any AECV.
FIGURE 9 - ADDITIONAL EMERGENCY CONTROL VALVE
7.2.2 Any AECV shall:
be easy to operate and located in a readily accessible position for use by
teaching and technical staff. It shall not be located in a locked area such as
in a secure box or in another teaching or preparation area unless suitable
provisions are made for access in an emergency
if manually operated, be fitted with a suitable key, lever or hand-wheel
which is securely attached to the operating spindle
where the key or lever moves in the vertical plane, move to the “off”
position in a downward direction
be labelled or marked to show its open and closed positions (See Figure 9). Note: The handle may be painted RED to enable quick discrimination in an emergency.
A permanent notice shall be displayed near to the AECV position indicating that
immediately before and immediately after opening the AECV, a responsible
person should verify that all downstream manual valves/gas taps (including
those in fume cupboards) are turned off. Note: A similar notice will be needed if an AIV is installed for security reasons (see Note to
clause 7.2.1 and 7.2.3).
7.2.3 Where it is not practicable to install a manual isolation valve in a readily
accessible position or where it is required to interlock the gas supply with other
IGEM/UP/11 Edition 3 Draft for comment
24
safety systems such as air flow, fire or gas detection an automatic means of
isolation AIV shall be installed.
7.2.4 Automatic isolation valves (AIVs) in teaching areas
7.2.4.1 Where an AIV is required by clause 7.2.3 in gas supplies to teaching areas which
have appliances that are not fitted with flame safeguards, an automatic means
of proving that downstream valves of the burners/appliances are closed shall be
fitted (see Figure 10). This proving system should not supply more than one
teaching area. The system shall be such that it can only be reset by authorised
persons, for example with a key or a key code.
A means to stop the system in an emergency shall be positioned near the
teacher’s desk/board and either next to main light switches or at the exit from
the room. The stop device may need to be shielded unless in a protected
position. AIV Gas valves shall comply with BS EN 161. Note 1: It is recommended that valve proving systems be checked daily when in use and that the
teacher should turn the gas off by pressing the system stop button at the end of the
working day. It is advisable for the installer to fit a notice near the control system recommending that the stop button should be pressed at the end of the working day.
Note 2: Further guidance on valve proving systems is provided in IGEM/UP/2. Other gas proving
systems may be acceptable provided the general principles as outlined in IGEM/UP/2 are met. The operation of such systems is at the discretion of a responsible person based on risk assessment of the application.
Note 3: Valve proving systems are not required where all the downstream appliances are fitted
with full flame safeguard systems.
FIGURE 10 - EXAMPLE OF A WEEP BY-PASS PROVING SYSTEM
(see note 2 in clause 7.2.4.2)
7.2.4.2 Such automatic means of isolation shall in the event of a shut-down require
manual resetting to take place.
7.2.4.3 Fume cupboards may introduce particular hazards and shall be protected by the
laboratory pipework integrity system. In such cases an AIV should be fitted to
cover the fume cupboard which closes on isolation of the power to the fume
Gas flow
S.S.O.V.
Weep valve
Flowlimitingorifice
Gas pressure switch
IGEM/UP/11 Edition 3 Draft for comment
25
cupboard. Any Emergency Stop button should not normally stop the mechanical
extract system. The system may however need to be stopped in the event of fire
to prevent it spreading into the ductwork.
7.2.4.4 A permanent notice shall be displayed near to the services reset position
indicating that, immediately before and immediately after closing the AIV
system, a responsible person shall verify that all downstream manual isolation
valves/gas taps (including those in fume cupboards) are turned off.
7.2.4.5 In existing teaching areas where no automatic means of isolation is fitted
downstream of the laboratory or classroom AECV, a permanent notice shall be
fitted stating that all downstream gas valves serving individual burners or
appliances shall be checked to be in the off position prior to closing or opening
the isolation valve. In this case the AECV shall be located in a readily accessible
position for the teaching or support staff to operate.
7.2.5 Boiler/plant rooms
Note: Boiler/plant rooms within educational establishments are recommended to be treated as
areas of higher risk with respect to unauthorised entry and interference.
7.2.5.1 In addition to the requirements of IGEM/UP/10, the following additional safety
precautions are required for new educational establishments and where existing
boiler/plant rooms are to be upgraded or refurbished.
A means to automatically shut off the fuel supply in the event of a fire shall be
installed. This should include an emergency shut-off push button at the entrance
to the plant room/boiler house and for any gas system shut off shall be
accomplished by closure of a valve complying with BS EN 161. The system shall
isolate the electrical power to some or all the plant as considered appropriate. In
the event of an alarm condition, the system should require manual resetting. Note 1: Where shut down is the result of a power supply failure automatic resetting of the power
supply (local or remote) is permitted. Alternatively, a system of alarm notification to remote key holders may be used. The risk of interrupting power supplies to remote plant controlled by the boiler house control panel needs to be assessed and the plant designed
accordingly. Many modern package burners require local manual reset in the event of loss of power, as required by BS EN 676.
Note 2: Pipework integrity systems (see clause 7.2.4.3) are not normally required for modern
boiler/heating plant incorporating flame safeguard systems. Note 3: Many existing plant rooms/boiler houses are fitted with a manual isolation valve on the
fuel supply. The requirement for automatic isolation of the gas supply to new buildings is not intended to be retrospectively applied to existing buildings, except as may be necessary as part of the conclusions from a risk assessment.
Note 4: In the event of fire within a plant room which forms part of a main building it is
recommended that the general building fire alarm system is actuated.
7.2.5.2 A heat detection system should be installed and linked to the fire alarm system
to raise an alarm. Note: Heat detection is preferable to smoke detection in a plant/boiler room as smoke detection
is more likely to cause false alarms.
7.2.5.3 During the initial risk assessment the design shall be considered for potential
gas releases, including those that may be caused by vandalism. Secure locking
of boiler rooms may mitigate the risk and lessen the need for flammable gas
detectors. Note: The use of welded steel pipework will help limit the risk of gas releases.
Copper pipes and small unions may be a particular risk and should be avoided
as far as practicable.
IGEM/UP/11 Edition 3 Draft for comment
26
Gas pipework shall be supported as required by IGEM/UP/2.
7.2.5.4 Where required by clause 7.2.5.3, flammable gas detectors shall be mounted in
accordance with the manufacturer’s instructions and at locations where gas
leakage may accumulate for example:
for NG, the gas detectors be mounted at high level at or near the air grilles
for LPG, the detectors should be mounted at low level at or near air grilles
for biogas, the gas detectors should be mounted at high and at low level at
or near the air grilles.
The DSEAR risk assessment (see IGEM/UP/16) will recommend the frequency of
boiler room inspection visits to ensure the integrity of the gas pipework. Where
this frequency cannot be satisfied then gas detection shall be applied.
7.2.5.5 Where a risk assessment identifies that there is a risk of combustion products
passing from a boiler room/enclosure/space into an occupied space such as a
teaching area/corridor/office, a CO detection system shall be installed in the
occupied area. The CO detection system shall raise an alarm and shall isolate the
fuel supply to the appliance.
7.2.5.8 Where a plant/boiler room/enclosure/space connects directly to or is accessed
from a teaching area such as a cupboard in a classroom or corridor,
consideration shall be given to installing a flammable gas detection system. For
NG this should be at high level and for heavier than air gases this should be at
low level. The detection system(s) should raise an alarm and, it shall also isolate
the fuel supply.
7.3 APPLIANCE ISOLATION
7.3.1 A means shall be provided in an accessible location to manually isolate each
appliance from the gas supply.
7.3.2 A single manual isolation valve shall be provided in an accessible location to
isolate the gas supply from each group of appliances such as a group of gas
cookers. The valve shall be of the quick acting type for example a 90o operation
and shall be easily identifiable.
IGEM/UP/11 Edition 3 Draft for comment
27
SECTION 8 : LABORATORIES
For the purposes of this Standard, the term “laboratories” includes “preparation rooms”.
8.1 Laboratories should be designed as individual units with individual gas safety
controls for each unit.
8.2 Consideration shall be given, during the design of laboratories to the installation
of manual isolation valves at each bench or group of benches to enable easy
maintenance of bench top gas taps.
8.3 Where practicable, any gas tap shall be located above any table, bench or other
working surface. It shall not be located in a position such as the side of bench
etc. where it may be susceptible to mechanical damage or cause injury (see
Figure 11).
8.4 Any gas tap should be manufactured to BS 1552 and be so designed that it’s
‘‘on’’ and ‘‘off’’ positions can be readily identified. It should be of a design where
it is not possible to turn on the tap by accident for example be of drop lever or
press and turn design.
8.5 The body of any tap supplied by pipework passing through a worktop etc. shall
be designed such that it can be rigidly located for example by the use of
matching shaped holes cut in the worktop etc. such that rotation of the
complete tap is prevented.
8.6 Workbenches and bollards containing or supporting gas pipework shall be
anchored to the floor by corrosion resistant fixings. There shall be no movement
possible which could lead to degradation of pipework or compromise of pipework
seals. Stability shall be ensured by the installer and checked frequently
thereafter by laboratory staff as part of scheduled the gas safety checks.
Any substandard fixing which allows movement of the work bench or bollard
shall be replaced prior to use.
FIGURE 11 - AN EXAMPLE OF A LABORATORY BOLLARD
8.7 Where a modular bench assembly with gas taps/electrical supplies is to be
installed or where a gas supply is within a bench assembly adequate ventilation
shall be provided. For an internal bench of volume not exceeding 1 m³
ventilation of at least 20 cm² free area at both high and at low level shall be
allowed. This shall be increased pro rata per increase in volume.
IGEM/UP/11 Edition 3 Draft for comment
28
Ventilation of benches shall be to the outside or to normally occupied, ventilated
classrooms.
8.8 Where high pressure gas is used in conjunction with a gas burner such as
compressed air or oxygen a NRV of an approved type must be installed in the
gas supply to the laboratory, or at each location where the high-pressure gas is
to be used. Note: This is a legal safety requirement and this valve is to be included in an annual
maintenance check. A sign needs to be affixed to the meter installation (see Figure 12 for a safety label).
FIGURE 12 - AN EXAMPLE OF A HIGH PRESSURE GASES WARNING SIGN
8.9 Flammable gas detection systems should not normally be necessary in school
laboratories but where fitted they shall be resistant to the effects of flammable
solvents and chemicals that may lead to nuisance shutdowns. The requirement
for fitting a gas detection system should be the subject of a risk assessment.
8.10 Any LPG cylinder supplying gas to apparatus shall not be located inside a
building. Note: This does not apply to small LPG cartridges used within soldering/jewellery blow torches
or mobile science benches.
8.11 For fume cupboards, a risk assessment shall be performed to ascertain if the
gas supply and extract system needs to be interlocked.
Note: For fume cupboards having additional means of protection such as built in-explosion
reliefs or where the gas supply is part of the laboratory gas pipework integrity system, the gas supply may not require interlocking the gas and extract air systems. However, those using fume cupboards need to be instructed to ensure that gas burners are turned off when not in use and that gas flames are monitored whilst in use. A suitable sign may need to be displayed showing this information at the fume cupboard.
Before gas or air at elevated pressure or any
extraneous gas is used in conjunction with
the gas supply, the gas transporter must be
contacted as a non-return valve will probably
be required.
Gas transporter
WARNING NOTICE
NON-RETURN VALVES
IGEM/UP/11 Edition 3 Draft for comment
29
SECTION 9 : ART, CRAFT, DESIGN AND TECHNOLOGY
9.1 FIXED AND NON-MOVEABLE APPLIANCES
9.1.1 General
Gas-fired equipment used in art, craft and design and technology areas typically
includes ceramic kilns, small crucible melting furnaces, forge hearths, glue pots,
oxygen-assisted working flames for jewellery manufacture and small open
ended forge furnaces.
For this type of equipment, reference shall be made to IGEM/UP/12.
9.1.2 Selection of equipment or appliances
9.1.2.1 Subject to clause 9.1.2.2, all new equipment of heat input exceeding 50 kW
shall incorporate a flame safeguard device.
Where practicable, new equipment of heat input less than 50 kW shall
incorporate a flame safeguard device.
9.1.2.2 In the exceptional case when plant operates at temperatures in excess of
750°C, as a minimum a pipework integrity system should be fitted. The user
instructions should advise that such systems be under constant supervision (see
Note 2). Where this is not practicable a flame safeguard system shall be fitted. Note 1: Further guidance on pipework integrity systems is in clause 7.2.5.3. Note 2: In this context “constant supervision” means that a responsible person who is competent
to operate the equipment is in control at all times.
9.1.2.3 Thermo-electric flame safeguard systems should only be used on open burners
and shall not be used within kilns. Note: The heat emitted from a kiln wall could result in a thermo-electric flame safeguard system
remaining open when it should be closed.
9.1.2.4 Where burner start-up is programme-controlled any automatic gas burner shall
conform to BS EN 676 or IGEM/UP/12.
9.1.2.5 Any burner supplied with combustion air from a fan, compressor or cylinder
shall be fitted with a pressure/flow sensor/switch in the air stream to detect air
flow (see the attached note). Failure of the flow of air shall result in immediate
closure of two electrically-operated gas safety shut-off valves (SSOVs) in the
supply to the burner(s). The valves shall be manufactured to BS EN 161. Note: Any burner firing in the open such as a brazing torch or a burner fitted to an appliance of
less than 7 kW nett heat input (7.5 kW gross) may not need to be fitted with flame safeguard safety controls, subject to risk assessment.
9.1.2.6 Wherever practicable the gas/air ratio shall be controlled to ensure that rich
firing does not occur unless by design (as in the case of ceramic kilns (see
clause 9.1.5)). Note: Rich firing may lead to the production and leakage of CO into the teaching space should
there be a fault on the flue system.
9.1.3 Installation of gas-fired equipment
9.1.3.1 Equipment shall be installed, operated and maintained in accordance with the
manufacturer’s instructions. The instructions should include, where applicable:
guidance on the siting of the appliance
IGEM/UP/11 Edition 3 Draft for comment
30
ventilation requirements
chimney/flueing requirements
operating instructions, including purging
maintenance instructions. Note: Further advice is given in BS 4163.
9.1.3.2 Further control measures may be required in specific circumstances. These
should be identified from risk assessment by the designer/installer. Appliances
not fitted with a flame safeguard device shall be manually supervised during
operation.
9.1.3.3 Any furnace or kiln should be sited away from general work areas and, where
practicable, be located in a separate room or area subject to the provision of
adequate supervision. It should be situated on a load-bearing floor.
Suitable protective measures shall be provided to protect persons being accidentally
injured by hot surfaces.
Plant controls shall be located in safe places.
9.1.3.4 There shall be adequate clearance between the equipment and the ceiling and
around the equipment to allow safe access for maintenance, servicing and the
free movement of air.
The floor, ceiling and walls adjacent to a kiln should be made of or covered with
a non-combustible material.
9.1.3.5 Combustible materials should not be stored near nor be allowed to accumulate
around any appliance.
9.1.3.6 Where a flame safeguard system is not fitted to any burner with an air fan, or
where oxygen is used an NRV must be fitted in the gas supply to the equipment
to prevent air or oxygen inadvertently entering the gas pipework.
9.1.4 Flues and fume extraction ductwork
9.1.4.1 Any flue or chimney shall be installed in accordance with the appropriate
requirements of IGEM/UP/10.
9.1.4.2 Any extract canopy over a gas appliance shall be constructed of appropriate
materials, for example of stainless steel. Any combustion gas extract duct from
furnaces and ovens should be treated as a flue, it’s routing and termination shall
be in accordance with IGEM/UP/10.
9.1.4.3 Flues/chimneys shall not pass through normally occupied spaces (such as
teaching spaces, offices, meeting rooms) within buildings unless enclosed within
sealed builders ducts ventilated externally to the building.
Boilers and air heaters shall not be installed in teaching spaces or in in spaces
accessible from teaching spaces.
Where these requirements are impractical, a carbon monoxide alarm system
shall be installed in the space unless other precautions can be taken as the
result of a risk assessment covering safety and environmental issues. Where CO
alarm systems are installed they shall comply with BS EN 45544 Part 3.
Note: UP/10 and BS 5440 include advice on the provision of means for access for inspection.
IGEM/UP/11 Edition 3 Draft for comment
31
9.1.5 Special procedures for ceramic kilns
9.1.5.1 For certain glazes incomplete combustion is deliberately produced. In such
situations the degree of rich firing shall be properly controlled. The rich gas
firing part of the firing cycle shall only be permitted when the combustion
chamber temperature exceeds 750oC.
9.1.5.2 For a natural draught kiln where rich gas firing is produced by restricting the
flue-way, any shutter or damper used for this purpose shall not close the flue by
more than 70% of the cross-sectional area.
9.1.5.3 A CO detection system shall be installed for all fuel types. The detection system
should both raise an alarm and isolate the fuel supply to the burners.
9.1.5.4 Explosion relief panels should be fitted where flame protection is not installed or
rich gas firing is not controlled. Reference should be made to IGEM/UP/12.
9.1.5.5 A flame safeguard device capable of operating over the complete range of
lean/rich gas mixtures used to provide the required atmospheres shall be fitted
to any kiln that is left in operation unattended particularly overnight.
9.2 PORTABLE EQUIPMENT
9.2.1 Portable appliances include mobile benches, Bunsen burners and similar low
energy output appliances that can be connected to worktop taps and are under
operator supervision while in use. Normally a flame safeguard device is not
required for such equipment. Bunsen burners mounted directly onto gas cartridges (maximum content
0.45 kg) shall not be used unless secured to a worktop and stability is ensured.
9.2.2 Mobile LPG benches
9.2.2.1 The following minimum requirements should be applied to the design of mobile
benches used in teaching areas. Other designs may be permissible providing
safety is not adversely affected. Such deviations should be recorded in the Risk
Assessments.
Note 1: Commercial Butane or butane/propane mixtures are the preferred gases for these
applications.
Note 2: The preferred design for gas supplies to benches is that they shall be supplied from gas cartridges having a maximum capacity of 0.45kg and fitted with self-sealing threaded connections.
9.2.2.2 Gas connections shall either be metallic or dated flexible tubing complying with
BS 3212 (not exceeding 500 mm) and secured with permanent clamp type
fittings. Any internal gas pipework within a bench shall be located such that it is
not exposed to damage when in use.
If the gas storage is located within the bench:
be located within a separate enclosure
an LPG leakage alarm shall be located at low level within the bench
ventilation shall be fitted in the base and the top of the cupboard each of
200 cm2
combustible/flammable materials shall not be stored within the bench.
9.2.2.3 The cartridge should be securely mounted on the outside of the bench and
protected from impact damage.
IGEM/UP/11 Edition 3 Draft for comment
32
9.2.3 Selection
Where applicable to the appliance type, any new equipment shall be CE marked.
9.2.4 Storage and siting of equipment
9.2.4.1 Equipment shall be stored, sited, operated and maintained in accordance with
the manufacturer's instructions.
LPG cartridges shall only contain commercial butane or commercial propane or
mixtures thereof and shall be of a type incorporating a self-sealing threaded
connection. Pierce-able cartridges shall not be used. LPG cartridges shall not
exceed 0.45 kg capacity.
9.2.4.2 LPG cartridges shall be checked for leakage before being stored and before use.
Small blowtorches must only be used in safe locations where there is no risk of
fire or explosion (e.g. presence of flammable gases or liquids).
Heatproof gloves should be available for handling the work. Blowtorches shall
ONLY be dismantled (e.g. to change burner nozzles or replace cartridges) by, or
under the supervision of a competent person and ONLY in a well ventilated area
away from sources of ignition.
LPG cartridges shall be stored in a ventilated locked cabinet of non-combustible
materials with at least 30 minutes fire resisting construction, secured in position
and kept locked (see also clause 5.5). It should preferably be located outside
the building or shall be adequately ventilated at both high and low levels directly
to outside the building and have explosion relief provision or gas leakage
detection alarms. Stored cartridges shall not exceed 7.5 kg in total and shall not
be stored in the same space as flammable materials or liquids.
Burners directly attached to gas cartridges shall be removed to secure storage
after use in a place which is: secure (e.g. locked); well-ventilated, away from
ignition sources, combustible materials and escape routes, in a safe position or
in a fire-resistant structure. Gas cartridges shall be removed to secure storage
during holiday periods.
9.2.4.3 Cylinders stored in buildings should not be located near exits, stairways used for
the safe egress of occupants.
9.2.4.4 Equipment should be securely stored away from the general work areas. Note: Ideally, equipment would be located in a separate room or area.
9.2.5 Use of equipment
9.2.5.1 At least once a year all equipment shall be subjected to a detailed inspection
and checks to ensure no gas leakage.
9.2.5.2 LPG cartridges shall be checked for leakage after use.
Note: See CLEAPSS document MRAT 1.018 and CLEAPSS publication L164, Portable Laboratory
Gas Burners.
Small LPG cartridge blowtorches shall only be used in safe locations where there
is no risk of fire or explosion. (e.g. presence of flammable gases or liquids).
Heat proof gloves should be available for handling the work. Blowtorches shall
ONLY be dismantled (e.g. to change burner nozzles or replace cartridges) by
competent persons and ONLY in a safe location.
IGEM/UP/11 Edition 3 Draft for comment
33
9.2.5.3 User refillable LPG blow torches/burners shall only be refilled by competent
persons and in the open air away from any ignition source. Protective clothing
and eye protection shall be worn as advised in the manufacturer’s instructions.
Note: LPG liquids can cause severe cold burns.
9.2.5.4 Combustion equipment shall be stable in use and not pose a safety risk to
persons.
IGEM/UP/11 Edition 3 Draft for comment
34
SECTION 10 : FOOD TECHNOLOGY ROOMS
10.1 These spaces are generally categorised as those for vocational training
(generally part of career training) and as food rooms (generally as part of
normal education). Any gas fired cooking appliance shall be installed in
accordance with its relevant installation Standard, for example BS 6172,
BS 4163 and BS 6173. Note: Food rooms will normally contain domestic appliances whereas commercial catering
appliances may be found where vocational training takes place.
10.2 Any new gas appliance shall be CE marked and shall incorporate an ignition
device on all its burners.
10.3 Any oven or similar enclosed burner equipment shall incorporate a flame
safeguard device.
10.4 Each area containing a gas cooking appliance shall be provided with adequate
ventilation for the safety of occupants and the gas appliance, see
Sub-Section 12 (for further advice, see BB101).
10.5 Where LPG blowtorches are used, refer to Sub-Section 9.2.
IGEM/UP/11 Edition 3 Draft for comment
35
SECTION 11 : INSTALLING APPLIANCES
11.1 The installation of any:
hot water boiler exceeding 70 kW heat input
steam boiler
storage water heater
warm air heater exceeding 70 kW heat input
LPG mobile cabinet heater;
shall be in accordance with IGEM/UP/10, BS 5440 Parts 1 & 2 and any additional
manufacturer’s instructions.
Installation of hot water boilers of between 70 kW and 1.8 MW net heat input
shall also be installed to BS 6644.
Where applicable to the appliance type, any new appliance shall be ‘‘CE’’
marked. Note: The location of a fuel fired heating appliance within a teaching area is not preferred. Small
LPG cabinet heaters complying with BS EN 449 may be used in emergencies for which adequate ventilation is essential.
11.2 Any radiant heater shall be installed in accordance with BS 6896, IGEM/UP/10
and any additional manufacturer’s instructions.
11.3 Any radiant tube heater shall be installed in accordance with BS EN 416-1,
IGEM/UP/10 and any additional manufacturer’s instructions.
11.4 Any commercial catering appliance shall be installed in accordance with the
manufacturer’s instructions and BS 6173.
11.5 Any domestic gas appliance shall be installed in accordance with the
manufacturer’s instructions and the relevant Standards shown in Table 1.
APPLIANCE TYPE STANDARD
Fires, convector heaters, fire/back boilers
and decorative fuel effect gas appliances
BS 5871-1, 2, 3, 4
Water heaters BS 5546
Central heating boilers BS 6798
Ducted warm air heaters BS 5864
Cookers BS 6172
Tumble dryers BS 7624
TABLE 1 - INSTALLATION STANDARDS FOR DOMESTIC APPLIANCES
IGEM/UP/11 Edition 3 Draft for comment
36
11.6 Unless otherwise stated in the manufacturer’s instructions a free standing
domestic cooking appliance using a flexible connector shall be fitted with a
stability device secured positively to the rear of the appliance and to the fabric
of the building. Note 1: Typical devices are shown in Figure 13. In the arrangement shown the stability bracket is
adjusted to give the smallest practical clearance between the bracket and the bottom engagement slot in the rear of the appliance. The stability chain needs to be kept as short as practicable and fixed positively to the rear of the appliance and to the structure.
Note 2: Such devices are essential to minimise the risk of free standing cookers tipping over for
example by students pushing down on open drop down oven doors.
FIGURE 13 - METHODS OF PROVISION OF COOKER STABILITY
11.7 Where CO alarm systems are installed they shall comply with BS EN 45544: 3.
CO detection should not be regarded as a means to negate the obligation of the
educational establishment to ensure appliances and flues are maintained so as
to ensure an acceptable level of performance.
Note 1: An educational establishment is regarded as a workplace, it is acknowledged that not all domestic type detectors and alarms complying with BS EN 50291-1 will be suitable for these applications unless the manufacturer specifically warrants this and confirms it will at least alarm at the workplace exposure limits. The action taken when in alarm should be determined by the level of assessed risk and environmental conditions within the room or space to be protected.
Note 2: IGEM/UP/1101 details the actions to be taken by teachers when alarms sound.
Stability U-bolt
Wall or floor mounted stability brackets are available to provide a minimum practical space of 87 mm between the cooker and the wall.
IGEM/UP/11 Edition 3 Draft for comment
37
SECTION 12 : VENTILATION AND FLUES
12.1 GENERAL
12.1.1 Ventilation shall be designed to provide adequate ventilation for occupants and
to dilute fumes and water vapour generated from combustion processes, for
example during use of Bunsen burners, LPG blow torches and cooking.
12.1.2 Purpose provided permanent ventilation shall be fitted to provide sufficient fresh
air for combustion and climate control for all gas appliances used for educational
purposes. It may also be necessary to remove noxious fumes and control
condensation. Where Type A gas fired appliances are in use a maximum CO2
level of 2800 ppm, is considered acceptable. Note 1: BS 5440-2 may also be used for guidance purposes for small domestic sized installations. Note 2: Advice is also given in DfE publication BB101 – Guidelines of ventilation, thermal comfort
and indoor air quality in schools. As part of the design specification for educational premises ventilation is also required to limit the concentration of CO2 in all teaching and learning areas.
Where it is necessary to leave a door or window open during operation of heat
producing appliances such as kilns then, for additional climate control CO2
monitoring of the environment shall be installed.
High levels of CO2 in spaces containing Type A gas fired appliances shall cause a
visual or audible alarm at 2800 ppm. For new and refurbished installations, high
levels of CO2 shall also cause an alarm at 2800 ppm and shut down of the gas
supply/appliances at 5000 ppm.
12.1.3 For a new installation, if a mechanical system is used for gas safety purposes in
teaching areas to either extract the products of combustion or to provide
combustion air, means shall be provided to monitor the correct provision of air
supplies, for example by air flow monitoring using air pressure switches or, by
fan motor power monitoring. Failure shall lead to shut-down of the gas supply or
burners.
12.1.4 A canopy hood and duct, to extract excess heat to atmosphere, should be fitted
to all gas kilns. Where reasonably practicable the ducting should lead to the
outside of the building in as short and direct a route as possible. The effect on
the operation of the appliance of mechanical ventilation, extraction fans, air
recirculation fans and canopy hoods/ducts shall be considered. The appliance
shall be tested with a number of relevant ventilation scenarios.
12.1.5 If mechanical ventilation is provided for climate control only, provision of an
interlock shall be considered as part of a risk assessment.
12.1.6 Any extract ventilation system shall not adversely affect the safe operation of
any Type B appliance. Note 1: This includes appliances in adjacent spaces, for example boiler rooms with connecting
doors into a catering area. Note 2: “Flued appliances” includes open flued appliances, gas tumble dryers with external vents.
12.1.7 Ventilation shall be designed to provide adequate ventilation for occupants and
to dilute fumes and water vapour generated from combustion processes, for
example during experiments using Bunsen burners, LPG blow torches and
cooking.
12.1.9 Any ventilation system in a teaching area shall be designed not to exceed noise
levels of given in Building Bulletin 93 available
IGEM/UP/11 Edition 3 Draft for comment
38
https://www.gov.uk/government/publication/bb93-acoustic-design-of-schools-
performance-standards.
Note: Additional information is available in BB93.
12.2 FLUES
12.2.1 Gas appliances shall be fitted with a flue system complying with BS 5440 Part 1
or IGEM/UP/10.
Canopy and/or flue systems shall be applied to appliances located in Art, Craft,
Design and Technology areas that may exhaust offensive or dangerous odours,
CO and other potentially dangerous gases. Such appliances will include forges,
ceramic kilns, melting furnaces. See IGEM/UP/10 and the manufacturer’s
installation instructions. Where odours and exhaust gases may cause a nuisance
special attention needs to be given to flue termination and the potential need for
gaseous incinerators.
Note: Consideration of noise impact on teaching areas may be needed when selecting canopies
and/or extraction systems.
12.2.2 For a natural draught kiln, where rich gas firing is produced by restricting the
flue-way, any shutter or damper used for this purpose shall not close the flue by
more than 70% of the cross-sectional area.
12.2.3 Where there is a draught diverter in the flue and under fault conditions,
products of combustion could enter the room the installer shall recommend that
regular checks be undertaken to ensure the effectiveness of the flue and the
ventilation of nearby spaces.
12.2.4 Any ducted exhaust system from equipment shall be connected to a permanent
exhaust discharge system. Where this is not practicable the exhaust shall not
discharge gases in such concentrations that may lead to danger to any person.
The provision of ventilation shall be in accordance with the equipment
manufacturer’s instructions.
12.2.5 Consideration shall be given to the location of fixed CO detection in rooms
through which the ductwork that contains combustion gases passes.
Where a horizontal or vertical flue passes through a teaching/occupied area, a
CO detection system shall be fitted and designed to cause an alarm condition.
This does not apply to chimneys/flues contained within sealed vertical ventilated service ducts (fire compartment) that are ventilated externally to the occupied
spaces.
Where CO detection systems are required by clause 7.2.5.5 or 12.2.4 they shall
comply with BS EN 45544: 3.
Note: IGEM/UP/10 also provides advice on pressure testing of linings.
12.2.6 The appliance manufacturer/designer shall be consulted prior to the installation
of a flue damper and where possible these shall be selected from those
specifically designed or intended for that make of appliance.
Any flue damper shall be installed in accordance with IGEM/UP/10 and shall be
maintained in good working order and its operation checked regularly.
It shall not be possible to completely close a damper controlling draught while
fuel is reaching the burner. Note: This can be achieved by cutting away part of the damper so that with the damper in the
fully closed position one third of the cross-sectional area of the flue remains open, by
IGEM/UP/11 Edition 3 Draft for comment
39
fitting a stop that prevents the damper from being more than two thirds closed or by interlocking the damper operation with the fuel supply.
12.3 FOOD TECHNOLOGY
12.3.1 The ventilation system shall be such to ensure that, under normal conditions the
teaching environment with appliances operating, should not exceed 2800 ppm
of CO2 at 1.5 m above floor level with an automatic shutdown of the gas supply
at 5000 ppm.
The designer shall declare the design appliance operating conditions to meet
this CO2 level which information shall be contained within the site technical
file/handover documents.
12.3.2 Where a single catering cooker is installed in a food room with a total heat input
not exceeding 70 kW, the ventilation requirements shall comply with BS 5440-2.
Where practicable, the use of a cooker hood above the appliance is
recommended and if mechanical extract ventilation is installed clause 12.3.4
shall be applied.
12.3.3 For installations of multiple catering appliances in a vocational training area, the
ventilation shall comply with BS 6173 and shall be interlocked as specified in
IGEM/UP/19.
For existing installations in food technology (home economics) rooms exceeding
one domestic cooker, where the ventilation requirements for new installations
cannot be met, CO2 monitoring shall be fitted. It shall provide an alarm condition
at not more than 2800 ppm to warn the teaching staff to increase ventilation
and where practicable, an automatic shutdown of the gas supply at 5000 ppm.
12.3.4 Where mechanical supply and/or extract ventilation is used in conjunction with
Type A flueless cooking appliances (typical gas cookers) a means shall be
provided to monitor the correct provision of air supplies, for example by air flow
monitoring using air pressure switches; by fan motor power monitoring or by
CO2 monitoring. Failure shall lead to shut-down of the gas supply to the
cooker(s) (see IGEM/UP/19).
A valve proving system, shall be fitted where an automatic isolation is installed
and flame safeguard devices (FSDs) are not fitted to all appliances.
12.3.5 Canopies applied to catering appliances in vocational training areas shall be
constructed from non-combustible materials and fabricated so as not to
encourage accumulation of dirt or grease, nor allow condensation to drip from
the canopy. Their design shall provide suitable access for cleaning and grease
filter cleaning/replacement (see BESA specification DW/172). Experience will
indicate how often cleaning is needed.
12.3.6 The design and performance of canopies shall ensure as far as practicable, the
efficient removal of cooking fumes and as far as possible, prevent them from
passing through the breathing zone of the students and teaching staff.
Note: When designing food technology canopy locations the sight lines need to be considered for
teaching staff and students.
12.3.7 Canopies above domestic cooking appliances should be designed to have a flow
rate exceeding 150 m3/h (42l/s) per appliance. Canopies above 2 or more
commercial cooking appliances should be designed according to DW/172.
The amount of air to extract via the canopies should be calculated, for example,
the air velocities over the hood face specified for individual items should be
added up to give the total air movement. Further advice is available in DW/172.
IGEM/UP/11 Edition 3 Draft for comment
40
12.3.8 Where canopies are not used for example ventilated ceilings, the ventilation
rates shall be calculated by a competent designer taking account of room sizes
and usages. Note: Additional information can be found in BB101 and CLEAPSS guidance.
12.3.9 Extract and supply air ventilation systems shall not adversely affect the safe
operation of any flued type B appliance, including appliances in adjacent places
(for example boiler rooms with connecting doors into the catering area). Flued
appliances in this respect, includes open flued appliances, gas tumble dryers
with external vents and room sealed appliances regardless of fuel.
12.3.10 Where CO2 monitors are employed as part of the ventilation control or alarm
strategy; the monitors shall be placed in an area that reflects the general CO2
levels within the gas cooker working area. Typically, they should be fitted
horizontally between 1 m and 3 m from the cooking areas and approximately
2.5 m above floor level. They should not be located in high velocity air streams
such as close to the edge of a canopy or adjacent to an air supply or extract
position.
12.4 SCIENCE LABORATORIES – ADDITIONAL REQUIREMENTS
12.4.1 The ventilation system shall be able to dilute combustion exhaust gases to an
acceptable level. Note 1: Simple measurements of gas consumption indicate that a Bunsen burner typically uses
2 litres of methane per minute. A litre of methane, if burnt with an adequate supply of oxygen, produces a litre of CO2.
Note 2: In ten minutes a Bunsen burner will generate 2 x 10 x 10-3 m3 = 0.02 m3 of CO2.
Therefore, 15 Bunsen burners will produce 0.3 m3 of CO2.
12.4.2 In most laboratories and preparation rooms, some form of mechanical
ventilation should be required at least some of the time to deal with pollutant
loads, the heat gain and water vapour produced by Bunsen burners as well as
other equipment and solar gains.
System design to deal with pollutants generated by science experiments
conducted in the open laboratory should assume a room volume of 200 m3 and
at a minimum exhaust flow rate of 4 l/s/m2 for a typical science laboratory.
However, if the ceiling height is lower than 2.7 m, a higher ventilation rate
should be required to achieve the same air change rate.
The design should wherever possible use the heat gains from occupancy and
equipment to warm the incoming air. Note 1: Hybrid mechanical/natural ventilation systems, rather than full mechanical ventilation
systems will probably be the most economical solution. Note 2: Risk assessments by CLEAPSS and the DfE have resulted in the minimum exhaust rates
given in BB 101 for science rooms. The rates depend on the floor area and the type of room.
12.4.3 Where ducted fume cupboards are used, there shall be an adequate supply of
incoming air to compensate for the extraction when the cupboard is in use. All
fume cupboards should be installed and used in accordance with the DfE BB101,
CLEAPSS Guide G9 and BS EN 14175 Part 2 guidelines.
12.4.4 For existing installations in science laboratories, where the ventilation
requirements for new installations cannot be met, CO2 monitoring shall be fitted.
It shall provide an alarm condition at not more than 2800 ppm to warn the
teaching staff to increase ventilation and where practicable, an automatic
shutdown of the gas supply at 5000 ppm.
IGEM/UP/11 Edition 3 Draft for comment
41
Where CO2 monitors are employed as part of the ventilation control or alarm
strategy; the monitors shall be placed in an area that reflects the general CO2
levels within the laboratory. They should not be located in high velocity air
streams such as close to or adjacent to an air supply or extract position.
IGEM/UP/11 Edition 3 Draft for comment
42
SECTION 13 : ELECTRICAL SUPPLIES AND WIRING
13.1 The electrical wiring installation to appliances shall comply with BS 7671 and
any specific requirements of the equipment manufacturer. See requirements to
satisfy DSEAR (see clauses 3.7 and 14.8). Note: Guidance can be found in IGEM/UP/16.
13.2 Any gas appliance and associated electrical components in the gas supply shall
be suitable for use with the supply voltage and have an adequate power rating
for the application.
13.3 Overload and fault protection systems shall have the correct rating for the
application.
13.4 Suitable methods of electrical isolation shall be provided in readily accessible
locations away from exposure to, damp surfaces, hot surfaces or combustion
products.
13.5 Appliances that need to be moved for cleaning shall be connected with plugs
and sockets.
IGEM/UP/11 Edition 3 Draft for comment
43
SECTION 14 : TESTING, COMMISSIONING AND MAINTENANCE
14.1 Any person employed for testing, commissioning or maintenance must be
competent to carry out the work (see Section 4).
14.2 Gas installation pipework shall be tested, purged, and commissioned in
accordance with IGE/UP/1, IGE/UP/1A, IGEM/UP/1B, and BS 5482-1, as
appropriate.
14.3 Any domestic sized gas appliance shall be tested, commissioned and maintained
in accordance with the manufacturer’s instructions and the relevant Standard
(see clause 11.5 and Table 1).
14.4 Any non-domestic plant shall be tested, commissioned and maintained in
accordance with IGEM/UP/4, IGEM/UP/10 and the manufacturer’s instructions.
14.5 Maintenance shall be performed at any time that teaching or maintenance staff
consider it to be necessary. Tests shall be performed on a planned basis to
verify that the desired levels of CO2 are being achieved e.g. by using a simple
hand held instrument.
14.6 All gas appliances, pipework, single ventilation and flue systems shall be
maintained on a regular basis (see GS(I&U)R and PUWER) and the period
between such maintenance shall be no greater than one year unless specifically
stated otherwise in the manufacturer’s instructions.
During appliance maintenance, the correct operation of all controls and safety
devices shall be verified. It shall also be ensured that the appliance is in a safe
condition for use within a teaching establishment.
At least once a year, all portable equipment shall be subject to a more detailed
safety inspection to ensure no gas leakage. Note: Reference needs to be made to the manufacturer’s instructions.
The correct operation of all mechanical ventilation (supply and extract) systems,
ducted filter systems, interlocks and safety systems shall be verified during
maintenance. Interlock and safety systems shall be maintained at periods not
greater than those specified by the manufacturer, and shall be undertaken at
least annually.
14.7 Exhaust systems (other than flues within chimneys) shall be subject to regular
detailed inspection and service (typically annually and at least every 14 months)
to ensure no gas leakage and the system is working correctly.
14.8 The risk assessment shall be prepared to meet the requirements of DSEAR, this
will require inspection of joints on gas pipework and controls systems. Typically,
this will require an annual inspection of pipework using combustible gas leakage
detector or leak detection fluid. The application of regular pressure (tightness)
testing on an annual basis is not normally necessary and five yearly checks
should be adequate.
14.9 When testing ambient air concentrations, a suitably certified and calibrated gas
analyser shall be used. Reference should also be made to BS 7967-5 (in course
of preparation). Note 1: DSEAR is retrospective and requires every occupier of every commercial premises to
perform a risk assessment to demonstrate which if any parts of the system require the installation and use of equipment suitable for a hazardous area, normally referred to as Zone 1 or Zone 2.
Note 2: The requirements for maintenance of pipework systems can be found in IGEM/UP/2.
IGEM/UP/11 Edition 3 Draft for comment
44
SECTION 15 : ADVICE TO BE GIVEN TO THE USER
15.1 The correct operation of any appliance and associated safety system shall be
demonstrated by the installer/commissioning engineer to a person having
responsibility for the safe operation of the equipment within the educational
establishment. Note: Detailed advice for the user is given in IGEM/UP/1101.
15.2 All user, installation and maintenance instructions provided by the manufacturer
shall be given to the responsible person and left on site. These shall form the
basis of any training and written start up, shut down and emergency procedures
and maintenance.
All instructions should be kept in a site manual/file.
15.3 Comprehensive written instructions, outlining the correct start up and shut down
procedures as well as those for the safe operation of any appliance (including
emergency procedures) and maintenance, should be clearly displayed in a
prominent position next to the appliance together with a list of those persons
responsible for it.
The “User Instructions” shall advise that persons who operate equipment shall
be trained to do so, or this shall be included in the displayed instructions as
above.
IGEM/UP/11 Edition 3 Draft for comment
45
SECTION 16 : EMERGENCIES
16.1 Each teaching establishment shall prepare an Emergency Procedure to deal with
gas incidents in order to comply with health and safety Legislation.
16.2 Means shall be provided for the gas supply to a teaching area to be quickly
isolated in an emergency, either by an emergency stop facility or by closure of a
manual gas valve. Relevant staff shall be made aware of the location of all such
valves and how to operate them.
Note: Detailed advice for the user is given in IGEM/UP/1101.
16.3 Staff shall be made aware that any smell of gas shall be acted upon immediately
by system isolation, opening windows and doors and by NOT operating any
electrical switch/device. Staff shall be made aware that any continuing smell of
gas must be immediately reported to the gas emergency services e.g. 0800 111
999 for NG.
For potential escapes of LPG contact the supplier, this information typically is
provided on the vessel or adjacent to a storage vessel or recorded in the
emergency plan.
16.4 Where LPG is used, emergency procedures shall provide guidance on preventing
and dealing with liquid leakages, fire/explosion and cold burns.
IGEM/UP/11 Edition 3 Draft for comment
46
APPENDIX 1 : GLOSSARY, ACRONYMS, ABBREVIATIONS AND UNITS
A1.1 GLOSSARY
All definitions are given in IGEM/G/4 which is freely available by downloading a printable
version from IGEM’s website www.igem.org.uk.
Recommended and legacy gas metering arrangements are given in IGEM/G/1 which is freely
available by downloading a printable version from IGEM’s website www.igem.org.uk.
A1.2 ACRONYMS AND ABBREVIATIONS
ACOP Approved Code of Practice
AECV additional emergency control valve
AIV automatic isolation valve
CDM Construction (Design and Management) Regulations
CE European Community
CLEAPSS Consortium of Local Education Authorities for the Provision of Science Services
CO carbon monoxide
CO2 carbon dioxide
CoP Code of Practice
COSHH
CSST
Control of Substances Hazardous to Health Regulations
corrugated stainless steel tube
DfEE
DSEAR
Department of Education and Employment
Dangerous Substances and Explosive Atmospheres Regulations
ECV emergency control valve
ESP emergency service provider
FSD
GB
flame safeguard device
Great Britain
GS(I&U)R Gas Safety (Installation and Use) Regulations
GS(M)R Gas Safety (Management) Regulations
GT gas transporter
HMSO Her Majesty's Stationary Office
HSE Health and Safety Executive
HSWA
HVCA
Health and Safety at Work etc. Act
Heating and Ventilating Contractors Association
IGEM Institution of Gas Engineers and Managers
LPG liquefied petroleum gas
MAM meter asset manager
MHSWR Management of Health and Safety at Work Regulations
MIP maximum incidental pressure
MOP maximum operating pressure
NG Natural Gas
NRV non-return valve
OP operating pressure
PE
PFI
PSSR
polyethylene
Private Finance Initiatives
Pressure Systems Safety Regulations
PUWER Provision and Use of Work Equipment Regulations
RIDDOR Reporting of Injuries, Diseases and Dangerous Occurrences Regulations
SP set point
SSOV safety shut-off valve
STP strength test pressure
UK United Kingdom
UKLPG UKLPG.
IGEM/UP/11 Edition 3 Draft for comment
47
A1.3 UNITS
l/s/m2 litres per second per square metre
cm2
dB
kW
L
square centimetre
decibel
kilowatt
litre
L s-1 litre per second
mm
m
m3
m3 h-1
mbar
mol
mol m3 h-1
m s-1
MJ m-3
millimetre
metre
cubic metre
cubic metre per hour
millibar
mole
mole cubic metre per hour
metre per second
megajoule per cubic metre
Pa Pascal
ppm part per million
v/v volume per volume
A1.3 SYMBOLS
oC o
degree Celsius
degree
% percentage
IGEM/UP/11 Edition 3 Draft for comment
48
APPENDIX 2 : REFERENCES
This Standard is set out against a background of Legislation in force in GB at the time of
publication. Similar considerations are likely to apply in other countries and reference to the
appropriate national Legislation will be necessary.
This Appendix lists all Legislation, standards, Codes of Practice and related recommendations
referenced in this Standard, as well as other items of Legislation that may be applicable.
A2.1 STATUTORY INSTRUMENTS
Consumer Protection Act 1987
Gas Act 1995
Health and Safety at Work etc. Act 1974
Asbestos (Prohibition) Regulations 1992
Building Regulations for England and Wales 2002
Building Standards (Scotland) Regulations 1990
Building (Amendment) Regulations (Northern Ireland) 2006
Confined Spaces Regulations 1997
Construction (Design and Management) Regulations 2015
Control of Asbestos Regulations 2006
Control of Substances Hazardous to Health Regulations 1994
Dangerous Substances and Explosive Atmospheres Regulations 2002
Electricity at Work Regulations 1989
Gas Appliances (Safety) Regulations 1995
Gas Cooking Appliances (Safety) Regulations 1995
Gas Safety (Installation and Use) Regulations 1998
Gas Safety (Management) Regulations 1996
Heating Appliances (Fireguards) Regulations 1991
Management of Health and Safety at Work Regulations 1992
Pressure Equipment Regulations 1999
Pressure Systems Safety Regulations 2000
Provision and Use of Work Equipment Regulations 1992
Reporting of Injuries, Diseases and Dangerous Occurrences Regulations
2013
School Premises Regulations 2012
The Education (Independent School Standards) England Regulations 2003
Water Supply (Water Fittings) Regulations 1999
Workplace (Health, Safety and Welfare) Regulations 1992.
A2.2 HSE APPROVED CODES OF PRACTICE AND GUIDANCE
CAIS10 Ventilation of kitchens in catering establishments
HSR25 Electricity at Work Regulations. Guidance
HSG48 Reducing error and influencing behaviour
HSG227 A comprehensive guide to managing asbestos in premises
HSG258 Controlling Airborne Contaminates at Work
L21 Management of Health and Safety at Work. ACOP and
Guidance
L22 Safe Use of Work Equipment. ACOP and Guidance
IGEM/UP/11 Edition 3 Draft for comment
49
L56 Safety in the Installation and Use of Gas Systems and
Appliances. ACOP and Guidance
L64 The Health and Safety (Safety Signs and Signals)
Regulations 1996. Guidance
L73 Reporting of injuries, Diseases and Dangerous Occurrences
Regulations. Guidance
L80 Gas Safety (Management) Regulations. Guidance
L101 Safe work in confined spaces
L122 Safety in pressure Systems. Pressure Systems Safety
Regulations 2000. ACOP
L127 The management of asbestos in non-domestic premises.
ACOP
L138 Dangerous Substances and Explosive Atmospheres
Regulations 2002. ACOP and Guidance
L143 Working with materials containing asbestos. ACOP and
guidance
L153 Construction (Design and Management) Regulations 2015.
Guidance.
INDG178 Written Schemes of Examination
INDG229 Using Work Equipment Safely
INDG258 Controlling airborne contaminants at work
INDG261 Pressure Systems - safety and you
INDG291 Simple guide to the Provision and Use of Work Equipment
Regulations
INDG370 Fire and explosion; How safe is your workplace? A short
guide to the Dangerous Substances and Explosive
Atmospheres Regulations 2002
PM5 Automatically Controlled Steam and Hot Water Boilers.
A2.3 BRITISH STANDARDS (abbreviated titles)
BS 669-1 Flexible hoses, end fittings and sockets. Specification
metallic flexible hoses for domestic appliances
BS 699-2 Flexible hoses, end fittings and sockets. Specification for
corrugated metallic hoses for catering appliances
BS 1552 Taper plug valves
BS 4163 Health and Safety for Design and Technology in Schools
and Similar Establishments - Code of Practice
BS 4250 Commercial butane and commercial propane
BS 4800 Specification for paint colours for building purposes
BS 5440 Flues and ventilation
Part 1: Flues
Part 2: Ventilation
BS 5482 Butane and propane gas burning installations
BS 5546 Installation of hot water supplies for domestic purposes
BS 5864 Installation and maintenance of gas-fired ducted air
heaters
BS 5871 Installation and maintenance of gas fires
BS 6172 Installation of gas cookers
BS 6173 Installation of catering appliances
BS 6400 Domestic gas meter installations
IGEM/UP/11 Edition 3 Draft for comment
50
BS 6501 Strip-wound hoses and assemblies
BS 6644 Installation of gas fired hot water boilers between 70 kW
and 1.8 MW net heat input
BS 6798 Installation of gas fired boilers not exceeding 70 kW
BS 6891 Installation of low pressure gas pipework of up to 35 mm
diameter
BS 6896 Installation of gas fired overhead radiant heaters
BS 7624 Installation of tumble dryers
BS 7671 IEE Wiring Regulations
BS 7967-5 Measurement of carbon monoxide and carbon dioxide and
the performance of gas fired equipment
BS EN 161 Automatic shut-off valves
BS EN 416-1 Single burner gas-fired overhead radiant tube heaters for
non-domestic use
BS EN 437 Test gases, test pressure, appliance categories
BS EN 676 Automatic forced draught burners
BS EN 13792 Colour coding of taps and valves for use in laboratories
BS EN 14800 Corrugated safety metal hose assemblies for domestic
appliances
BS EN 15069 Safety gas connection valves for metal hose assemblies for
domestic appliances.
A2.4 IGEM
IGE/UP/1 Strength and tightness testing and direct purging of
Edition 2 industrial and commercial gas installations
IGE/UP/1A Strength and tightness testing and direct purging of small
Edition 2 low pressure industrial and commercial Natural Gas
installations
IGEM/UP/1B Tightness testing and purging of domestic sized Natural
Edition 2 Gas installations
IGEM/UP/2 Gas installation pipework, boosters and compressors on
Edition 3 industrial and commercial premises
IGEM/UP/4 Commissioning of gas fired plant on industrial and
Edition 3 commercial premises
IGEM/UP/10 Installation of gas appliances in industrial and commercial
Edition 4 premises
IGEM/UP/1101 Guidance on gas installations for the management and
staff within educational establishments
IGEM/UP/12 Application of burners and controls to gas fired process
plant
IGEM/UP/19 Design and application of interlock devices and associated
systems used with gas appliance installations in
commercial catering establishments
IGEM/GM/6 Specification for LP diaphragm and RD meter installations
with capacities exceeding 6 m3 h-1 but not exceeding
1076 m3 h-1
IGE/GM/8 Non-domestic meter installations, capacity exceeding
Part 1 6 m3 h-1 and inlet pressures not exceeding 38 bar
IGEM/GM/8 Non-domestic meter installations. Locations, housing and
Part 2 compounds. Edition 2
IGEM/UP/11 Edition 3 Draft for comment
51
IGEM/GM/8 Non-domestic meter installations. Fabrication, installation,
Part 3 testing and commissioning. Edition 2
IGEM/GM/8 Non-domestic meter installations. Operation and
Part 4 maintenance. Edition 2
IGEM/GM/8 Non-domestic meter installations. Notices and labels.
Part 5 Edition 2
IGE/SR/25 Hazardous area classification of Natural Gas installations
IGEM/SR/29 Dealing with gas escapes
IGEM/TD/13 Pressure regulating installations
IGEM/G/4 Definitions for the gas industry
IGEM/IG/1 Standards of training in gas work.
A2.5 UKLPG note that text uses Cop not CoP
UKLPG CoP 1 Design installation and operation of vessels located above
ground
UKLPG CoP 7 Storage of full and empty LPG cylinders and cartridges
UKLPG CoP 22 LPG Piping system design and installation
UKLPG CoP 24 Use of LPG cylinders
UKLPG CoP 25 LPG Storage and distribution systems
UKLPG TM 62 Checking LPG pipework (withdrawn).
A2.6 DEPARTMENT FOR EDUCATION ENGLAND
Building Bulletin 80 Science Accommodation in Secondary Schools. A
Design Guide, School Building and Design Group,
DfES
Building Bulletin 81 Design and Technology Accommodation in
Secondary Schools, DfES
Building Bulletin 100 Design for Fire Safety in Schools, School Building
and Design Group, DfES
Building Bulletin 101 Guidelines on ventilation, thermal comfort and
indoor air quality in schools Ventilation of School
Buildings
CLEAPPS Guide G225 Local exhaust ventilation in Design & Technology
CLEAPPS Guide G9 Fume cupboards in Schools, School Building and
Design Group, DfES. Note: These bulletins are available at http://www.cleapss.org.uk
A2.7 OTHERS
Health and Safety: Responsibilities and Powers. DfES
Compliance monitoring in Local Authority Premises, Federation of Property
Societies.
IGEM/UP/11 Edition 3 Draft for comment
52
APPENDIX 3 : DIVERSITY
IGEM/UP/2 permits pipework designers to apply diversity when sizing pipework systems. It
does however retain the caveat that the design needs to be such as to ensure the safe
operation of all appliances. Diversity is an issue for multi-appliance systems and is widely used
by Distribution companies when designing gas mains systems to housing estates.
In teaching establishments, diversity may be an issue with regards pipe sizing in supplies to
laboratories and domestic cooking areas where not all gas appliances will operate at any one
time and even then they will not operate at full load. There are no definitive rules for
designing with diversity. In a teaching area, account will need to be taken of the maximum
number of students present as well as the numbers of points of use.
It has to be remembered that the difference in installed cost between a 40 and a 50 mm pipe
are small in which case diversity may not lead to any real savings.
IGEM/UP/11 Edition 3 Draft for comment
53
BLANK PAGE