installation, operation, and maintenance instructions · performing maintenance. vapors could catch...

8
1 Morrison Bros. Co. - Dubuque, IA - 800-553-4840 918S--0142 PP rev8.12.13 ! 918S Single Channel Alarm The 918S is designed to provide a visible and audible alarm. The 918S may be used anywhere that a single set of normally open dry contacts are available. Two possible primary applications are use as an overfill alarm or as an interstitial alarm. 918D Dual Channel Alarm The 918D is designed to provide a visible and audible alarm. The 918D may be used anywhere that up to two sets of dry contacts are available. The 918D can be configured to respond to either Normally Open (default configuration) or Normally Closed contacts. Two possible primary applications for each channel are as an overfill alarm or as an interstitial alarm. 918Q Quad Channel Alarm The 918Q is designed to provide a visible and audible alarm. The 918Q may be used anywhere that up to four sets of dry contacts are available. The 918Q can be configured to respond to either Normally Open (default configuration) or Normally Closed contacts. Two possible primary applications for each channel are as an overfill alarm or as an interstitial alarm. Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill, which could result in property damage, environmental contamination, re, explosion, serious injury or death. Specifications The 918S, 918D and 918Q are intrinsically safe devices for use in Class I, Division L Group D. T4 Hazardous locations when powered by Morrison Bros. Co. battery pack part number 918S--0113 2B. WARNING: This is an intrinsically safe device and must be wired in accordance with National Electrical Code Article 500. This device and its wiring may not share any junction box, conduit, or raceway with any other type circuit or wiring. Do not perform live maintenance. Do not substitute components with anything other than Morrison Bros. Co. components. Care must be taken to avoid an ignition hazard from impact or friction with the enclosure. Entity Parameters for Channel Inputs SENS1 through SENS4 (Terminal J1): V OC = 3.9VDC I SC = 415mA Ca = 0.37μF La = 1.43μH P O = 1.2W Operating Temperature: -40°F to 140°F (-40°C to 60°C) Maximum Wiring Distance: Maximum wiring distance between Alarm and input device is 500 ft. 918 Series Alarm Installation, Operation, and Maintenance Instructions

Upload: others

Post on 24-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

1Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

!

918S Single Channel AlarmThe 918S is designed to provide a visible and audible alarm. The 918S may be used anywhere that a single set of normally open dry contacts are available. Two possible primary applications are use as an overfi ll alarm or as an interstitial alarm.

918D Dual Channel Alarm The 918D is designed to provide a visible and audible alarm. The 918D may be used anywhere that up to two sets of dry contacts are available. The 918D can be confi gured to respond to either Normally Open (default confi guration) or Normally Closed contacts. Two possible primary applications for each channel are as an overfi ll alarm or as an interstitial alarm.

918Q Quad Channel Alarm The 918Q is designed to provide a visible and audible alarm. The 918Q may be used anywhere that up to four sets of dry contacts are available. The 918Q can be confi gured to respond to either Normally Open (default confi guration) or Normally Closed contacts. Two possible primary applications for each channel are as an overfi ll alarm or as an interstitial alarm.

Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill, which could result in property damage, environmental contamination, fi re, explosion, serious injury or death.

Specifi cations

The 918S, 918D and 918Q are intrinsically safe devices for use in Class I, Division L Group D. T4 Hazardous locations when powered by Morrison Bros. Co. battery pack part number 918S--0113 2B.

WARNING: This is an intrinsically safe device and must be wired in accordance with National Electrical Code Article 500. This device and its wiring may not share any junction box, conduit, or raceway with any other type circuit or wiring. Do not perform live maintenance. Do not substitute components with anything other than Morrison Bros. Co. components. Care must be taken to avoid an ignition hazard from impact or friction with the enclosure.

Entity Parameters for Channel Inputs SENS1 through SENS4 (Terminal J1):

VOC = 3.9VDC ISC = 415mA Ca = 0.37μF La = 1.43μH PO = 1.2W

Operating Temperature:-40°F to 140°F (-40°C to 60°C)

Maximum Wiring Distance:Maximum wiring distance between Alarm and input device is 500 ft.

918 Series AlarmInstallation, Operation, and Maintenance Instructions

Page 2: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

2Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

!

Alarm Installation and Testing

WARNINGS• Fire Hazard – Death or serious injury could result from spilled liquids.• You must be trained to install or maintain this alarm. Stop now if you have not been trained.• Any modifi cation of this unit beyond what is outlined in this instruction will void product warranty. • For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside, above, or around the storage tank and piping area. Use all personal protective equipment required for working in the specifi c environment.• This device is intended to be used as an auxiliary warning to the operator of an abnormal condition of the system, such as a possible overfi ll situation and should not be the only system in place to prevent an unwanted condition, such as preventing a tank from overfi lling. It is the sole responsibility of the operator to continuously prevent any spillage regardless of the situation.• Tanks could be under pressure. Vapors could be expelled from tank vents, piping, valves or fi ttings while performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working on tank system.• Use a dampened cloth when cleaning the alarm enclosure to prevent static buildup and discharge.• The only battery approved for use with the 918 Series Alarm is the Morrison Bros. Co. battery pack part number 918S--0113 2B.• In the event of malfunction, contact Morrison Bros. Customer Service.

NOTE: As defi ned in Article 501 – Class 1 Locations of NFPA 70, this apparatus and its connected wiring are intrinsically safe. Under normal conditions this apparatus and its wiring cannot release suffi cient energy to ignite a specifi c ignitable atmospheric mixture by opening, shorting, or grounding.

WARNING: Interconnect wiring between the gauge and the alarm unit must be kept totally isolated and separate from any other wiring. This wiring must not share any junction box, conduit, raceway, or fi xtures with circuits other than those defi ned by NEC as being intrinsically safe for all Class 1 locations.

Location: NEC ARTICLE 501-3-CLASS 1 Locations exempt intrinsically safe enclosures in paragraph501-3(b)(1)(c), and therefore may be placed in the most convenient location but must be within reach of the operator and within audible range.

Mounting: Since a general purpose NEMA 4X enclosure is used to protect the alarm circuits and batteries, any mounting holes, conduit, or fasteners must be sealed in order to maintain the waterproof integrity of the enclosure. All penetrations into the enclosure must be made at the bottom of the alarm box.

Steps1.Run two oil and gas resistant wires from each input device to the location where the alarm box will be mounted. Do NOT attach the wires to the wires in the junction box of the input device(s) at this time. Although not required, it is recommended to run the wires in some type of conduit in order to protect them against possible damage and environmental conditions. It may be necessary to remove the junction box cover of the input device(s).2. Separate the two halves of the Alarm Unit box by loosening the Phillips head fasteners visible at the four corners of the front panel. Attach the rear half of the box to a suitable fi xture. Be sure to seal any penetrations made into the interior of the box to prevent moisture ingress.3. Install the new battery. a. Remove protective foam from the Alarm Circuit Board’s battery connector b. Carefully align the battery assembly over the three mounting points and the battery connector pins and press into place. Be sure that the new battery assembly is fully seated and secured by the mounting posts (see Figure 1).

Page 3: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

3Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

4. Test the alarm by pressing the Test/Cancel button on the front of the alarm box. a. Press and hold the “Test/Cancel” button while listening to the audible alarm and observing the Channel Alarm and BATTERY LOW indicators (see Figure 2).

b. The 918S/D/Q indicates the following: • Audible Alarm is loud and strong, sounding about one second on and one second off. • Channel Alarm Indicator(s) is(are) illuminated when the Audible Alarm is NOT sounding • BATTERY LOW indicator is NOT illuminated. c. If alarm does not sound, the Channel Alarm Indicator(s) do not illuminate or the BATTERY LOW indicator illuminates, replace the 918 Battery Assembly (see instructions, below). If the alarm still does not sound, the Channel Alarm Indicator(s) do not illuminate, or the BATTERY LOW indicator illuminates, replace the alarm box or call Morrison Bros. Co. Customer Service.5. Connect the two wires from each input device to the Input of the Alarm a. 918S: Insert the wires into the Alarm Circuit Board input connector (J1/SENS1) terminals and snug the screws down onto the wires. Verify that they are securely held in the connector by gently tugging on them.

Battery fully seated

Fig. 2 Channel Alarm Indicators, Battery Low Indicator and Test/Cancel Button on the 918D

Fig. 1 Installing the Battery

Channel Alarm Indicators

Low Battery Indicator

Test/Cancel Button

Page 4: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

4Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

b. 918D/Q Connect the two wires from each input device to the two screw terminals for each channel input of the Channel Input Connector (see Figure 3).

c. Verify that they are securely held in the connector by gently tugging on them. Plug the connector onto the Channel Input pins of the Alarm Circuit Board (see Figure 4).

6. DIP Switch Confi guration (for 918D and 918Q) • For Normally Open Contact Input Devices: If the input devices to be connected to the 918D/Q utilize normally open contacts, verify that position 1of the DIP switch, SW1, is in the “OFF” position (see Figure 5). • For Normally Closed Contact Input Devices: If the input devices to be connected to the 918D/Q utilize normally closed contacts, place position 1 of the DIP switch, SW1, in the “ON” position (see Figure 5). The alarm will sound; silence by pressing the “Test/Cancel” button.

Strip off about ¼ inch (5mm) of insulation from the wire and dress the wire.

The Channel Input Connector Insert the wire fully into the connector & snug the screw.

Figure 3 Wiring the Channel Input Connector for the 918D and 918Q

Channel Input Connector

Channel Input Pins

Figure 4 Plug the Channel Input Connector onto the Channel Input Pins of the Alarm Circuit Board

Page 5: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

5Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

!

7. Reattach the front cover of the Alarm using the fasteners at the four corners of the cover. DO NOT OVERTIGHTEN. “Snug” the fasteners in place and verify that the cover is fully seated to the enclosure base.8. Test the connection at the alarm and wiring a. For Normally Open Contact Inputs: 918D/Q with SW1, position 1 in the OFF position and 918S: Short the two wires together at the input device end for each input device. This should cause the alarm to sound until the Test/Cancel button is pushed. If the alarm fails to sound, check the connections and the batteries and retest until results are satisfactory. Repeat for each channel. b. For Normally Closed Contact Inputs: 918D/Q with SW1, position 1 in the ON position: Short the two wires together and then separate the wires at the input device end for each input device. This should cause the alarm to sound until the Test/Cancel button is pushed. If the alarm fails to sound, check the connections and the batteries and retest until results are satisfactory. Repeat for each channel.9. Connect the wires from the alarm box to the wires of the input device(s) at the junction box for each device. Replace the junction box cover.10. It is recommended to simulate an alarm condition and manually trigger the alarm using input device(s) (Clock Gauge, fl oat switch or other dry contact device). If it does not, check wiring at junction box and verify that the installation procedure was performed correctly. The alarm can be silenced after being activated by pressing the Test/Cancel button.11. IMPORTANT: Install the included Warning Tag where it will be visible to the operator fi lling or unloading the tank that is fi tted with this alarm.

Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill, which could result in property damage, environmental contamination, fi re, explosion, serious injury or death.

Operation

The 918S may be used anywhere that a single set of normally open dry contacts are available. Two possible primary applications are use as an overfi ll alarm or as an interstitial alarm. These two uses are addressed below.

The 918D may be used anywhere that up to two set of dry contacts are available. The 918D can be confi gured to respond to either Normally Open (default confi guration) or Normally Closed contacts. Two possible primary applications for each channel are as an overfi ll alarm or as an interstitial alarm. These two uses are addressed below.

The 918Q may be used anywhere that up to four set of dry contacts are available. The 918Q can be confi gured to respond to either Normally Open (default confi guration) or Normally Closed contacts. Two possible primary applications for each channel are as an overfi ll alarm or as an interstitial alarm. These two uses are addressed below.

Use as an Overfi ll Alarm Use with the Morrison Brothers 918 Clock Gauge or other similar input device. 1. Prior to fi lling a tank, test for an existing overfi ll condition, the battery level and overall operation of the Alarm. a. Press and hold the “Test/Cancel” button while listening to the Audible Alarm and observing the Channel Alarm and BATTERY LOW Indicators.

OFF ON

Position 1

Figure 5 Confi guring Input Mode with DIP Switch Position 1

DIP Switch, SW1

Page 6: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

6Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

!

b. If an overfi ll condition already exists when the “Test/Cancel” button is pressed, the Channel Alarm Indicator associated with the alarm condition will illuminate prior to the sounding of the Audible Alarm associated with the “Test” mode. (see Figure 2) c. The 918S/D/Q indicates the following: • Audible Alarm is loud and strong, sounding about one second on and one second off. • Channel Alarm Indicator(s) is(are) illuminated when the Audible Alarm is NOT sounding • BATTERY LOW indicator is NOT illuminated.2. If an overfi ll occurs while fi lling the tank, the Channel Alarm Indicator associated with the overfi ll condition will fl ash and the Audible Alarm will sound. a. The alarm can be acknowledged and silenced by pressing the “Test/Cancel” button on the front of the Alarm. b. If the alarm is not silenced by the operator, the 918S/D/Q will continue in the alarm state for no more than 10 minutes at which point it will silence itself.

Use as in Interstitial Alarm1. Should the contacts associated with an interstitial switch be activated, the Alarm will immediately go into an alarm state; it will sound the Audible Alarm and illuminate the Channel Alarm Indicator associated with the alarm condition. 2. If the alarm is not silenced manually by pressing the “Test/Cancel” button, the 918S/D/Q will continue in this alarm state for no more than 10 minutes at which point it will silence itself. 3. To check for an alarm state once the Alarm has silenced itself, press and hold the “Test/Cancel” button while observing the Channel Alarm Indicator(s). a. If there is an interstitial alarm state, the Channel Alarm Indicator(s) associated with the alarm state will illuminate for one second prior to sounding the Audible Alarm associated with the “Test Mode.” b. If there is not an interstitial alarm, then the Channel Alarm Indicator(s) will not illuminate prior to the sounding of the Audible Alarm associated with the “Test Mode.”

Maintenence

WARNINGS• Fire Hazard – Death or serious injury could result from spilled liquids.• You must be trained to install or maintain this alarm. Stop now if you have not been trained.• Any modifi cation of this unit beyond what is outlined in this instruction will void product warranty. • For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside, above, or around the storage tank and piping area. Use all personal protective equipment required for working in the specifi c environment.• This device is intended to be used as an auxiliary warning to the operator of an abnormal condition of the system, such as a possible overfi ll situation and should not be the only system in place to prevent an unwanted condition, such as preventing a tank from overfi lling. It is the sole responsibility of the operator to continuously prevent any spillage regardless of the situation.• Tanks could be under pressure. Vapors could be expelled from tank vents, piping, valves or fi ttings while performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working on tank system.• Use a dampened cloth when cleaning the alarm enclosure to prevent static buildup and discharge.• The only battery approved for use with the 918 Series Alarm is the Morrison Bros. Co. battery pack part number 918S--0113 2B.• In the event of malfunction, contact Morrison Bros. Customer Service.

There are two scheduled maintenance operations:• MONTHLY: Test the battery level and overall operations of the Alarm (see 2 below)• YEARLY: Check the Enclosure for water ingress (see 3 below)

Battery replacement instructions are in 4 below.

Page 7: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

7Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

Steps 1. If necessary, clean the alarm box with a damp cloth.2. Test the battery level and overall operation of the Alarm no less than once per month. a. Press and hold the “Test/Cancel” button while listening to the audible alarm and observing the Channel Alarm and BATTERY LOW indicators. b. The 918S/D/Q indicates the following: • Audible Alarm is loud and strong, sounding about one second on and one second off. • Channel Alarm Indicator(s) is(are) illuminated when the Audible Alarm is NOT sounding • BATTERY LOW indicator is NOT illuminated. c. If alarm does not sound or the BATTERY LOW indicator illuminates, replace the 918 Battery Assembly (see instructions in 4 below). If the alarm still does not sound replace the alarm box or call Morrison Bros. Co Customer Service. d. Inspect the warning tag located near the tank fi ll or off-loading area. If the tag is damaged or diffi cult to read, contact Morrison Bros. at (800) 553-4840 for a free replacement tag.3. Check the Enclosure for water ingress no less than once per year. a. Carefully open the 918S/D/Q alarm enclosure by loosening the Phillips head fasteners at the four corners of the cover. b. Inspect the interior of enclosure to determine if any water has infi ltrated the enclosure. If water has infi ltrated the enclosure, take corrective action to seal the points of ingress. c. Inspect the electronics for corrosion. If there is corrosion present on the electronic assembly(ies)

• Take corrective action to seal the enclosure from further water ingress. • Contact Morrison Bros. Co. for further action.

d. Reattach the front cover of the Alarm using the Phillips head fasteners at the four corners of the cover. DO NOT OVERTIGHTEN. “Snug” the fasteners in place and verify that the cover is fully seated to the enclosure base. e. Perform step 2 above to verify the battery level and overall operation of the Alarm. 4. If the “BATTERY LOW” indicator illuminates at any time, replace the internal battery by performing the following steps: CAUTION: The following steps should be followed being sure that there is no possibility of fl uid ingress into the alarm enclosure.

a. Carefully open the 918S/D/Q alarm enclosure by loosening the Phillips head fasteners at the four corners of the cover. b. Disconnect input device(s) from the Alarm Circuit Board • 918S: Loosen the screws securing the input device wiring to the input screw connector J1 and gently pull the wires free. • 918D/Q: Unplug the channel connector from the Alarm Circuit Board. If the Alarm has been confi gured to work with Normally Closed Contacts, the Alarm may go into the alarm state. Silence this by pressing the “Test/Cancel” button. c. Place the front cover (which includes the Alarm Circuit Board and the Battery Assembly) on a stable, fi rm surface. d. Gently squeeze the tabs as shown in Figure 6 that secure the battery assembly in place while carefully lifting on the battery assembly at the three mounting locations. Lift just enough to bring the battery assembly circuit board above the latching point of the fasteners.

Page 8: Installation, Operation, and Maintenance Instructions · performing maintenance. Vapors could catch fi re or cause an explosion. Avoid sparks, open fl ame, or hot tools when working

8Morrison Bros. Co. - Dubuque, IA - 800-553-4840

918S--0142 PP rev8.12.13

!

e. Once the battery assembly has been released from all three retaining fasteners, lift the battery assembly straight up and off of the Alarm Circuit Board. f. Install the new battery by carefully aligning the battery assembly over the three mounting points and the battery connector pins and pressing into place as shown in Figure 1. Be sure that the new battery assembly is fully seated and secured by the mounting posts.

NOTE: If this is a 918D/Q which has been confi gured to operate with Normally Closed Contacts, the Alarm should go into the alarm state; silence this by pressing the “Test/Cancel” button.

g. Test the Alarm by pressing and holding the “Test/Cancel” button while listening to the audible alarm and observing the Channel Alarm and BATTERY LOW indicators (see Figure 2). h. The 918S/D/Q indicates the following: • Audible Alarm is loud and strong, sounding about one second on and one second off. • Channel Alarm Indicator(s) is(are) illuminated when the Audible Alarm is NOT sounding • BATTERY LOW indicator is NOT illuminated. i. If alarm does not sound, the Channel Alarm Indicator(s) do not illuminate or the BATTERY LOW indicator illuminates, replace the alarm box or call Morrison Bros. Co. Customer Service. j. Connect the input device(s) to the Alarm Circuit Board • 918S: Insert the wires into the Alarm Circuit Board input connector (J1/SENS1) terminals and snug the screws down onto the wires. Verify that they are securely held in the connector by gently tugging on them. • 918D/Q Connect the two wires from each input device to the two screw terminals for each channel input of the Channel Input Connector (see Figure 3). k. Reattach the front cover of the Alarm using the Phillips head fasteners at the four corners of the cover. DO NOT OVERTIGHTEN. “Snug” the fasteners in place and verify that the cover is fully seated to the enclosure base. l. It is recommended to simulate an alarm condition and manually trigger the alarm using input device (Clock Gauge, fl oat switch or other dry contact device). If it does not, check wiring at junction box and verify that the installation procedure was performed correctly. The alarm can be silenced after being activated by pressing the Test/Cancel button.

Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill, which could result in property damage, environmental contamination, fi re, explosion, serious injury or death.

Figure 6 Removing the Battery Assembly

Locking tab securing the Battery Assembly