installation manual eh99865401.pdf
TRANSCRIPT
-
7/27/2019 installation manual eh99865401.pdf
1/24
Installation manualAir conditioner(Split type) 1 English
AIR CONDITIONER (SPLIT TYPE)
Outdoor Unit
Model name:
RAV-SP240AT2-UL
Manuel d'installationClimatiseur(Type split) 23 Franais
Installation manual
For OUTDOOR USE only
Not accessible to the general public
Vente interdite au grand public
Kein ffentlicher Zugang
Non accessibile a clienti generici
No destinado al pblico en general
No acessvel ao pblico em geralNiet geschikt voor huishoudelijk gebruik
-
7/27/2019 installation manual eh99865401.pdf
2/24
-
7/27/2019 installation manual eh99865401.pdf
3/24
2
EN
Outdoor Unit Installation Manual
1 DIMENSION
3.0"(75)
2.8"(70)
15.0"(380)
1.8"(46)
6.7"(170)
4.7"(118)
15.1"(383)2.9"(74)
5.0"(128)
5-drain hole
0.8"(20) ~ 3.5"(88)
burring hole
A legs
23.6"(600)5.9"(150)
B legs2.4"(60)7.9"(200)
1.6"(40)
Details of A legs
0.7"
(17.5)
14.4"(365)
0.7"(17.5)
2.1"(54)
1.9"(48)
1.5"(39)
3.8"(96)
1.2"(30)
9.7"(247)
10.0"(255)
7"(178) 7" (178)2.4"(60)
2.7"(68) 20.4"(518)
7"(178)
12.9"(327)
21.0"(534)
22.9"(581)
5.8"(148)
6.5"(165)
35.4"(900) 12.6"(320)
35.0"(890)
15.7"(400)
3.4"(85)
2.0"(50)
2.2"(56)
5.1"(130)
0.7"(18) 2.3"(58)
3.9"(99)
Conduit hole( 0.9"(22) hole)
Drain hole
( 1.0"(25) burring hole)
1.3"(34)Air inlet
port
Air inletport
Air outletport
Mounting hole sold separately
(12 - 0.1"(3) emboss)
Refrigerant pipeconnecting port
0.4"(9.5) flareat liquid side
Refrigerant pipeconnecting port
0.6"(15.9) flareat gas side
0.3"(7)3.3"(83)
2.6"(65)
0.3"(7)
Z views
Z
Knockout for downward piping
Refrigerant piping hole
( 0.5"(12) ~ 0.7"(17) long hole)Mounting bolt hole
1.0"(24)
21.7"(550)2.0"(52)
1.6"(40)
0.5"(12)
Details of B legs
( 0.5"(12) ~ 0.7"(17) U-shape hole)Mounting bolt hole
Refrigerantpiping hole
3.7"(95)
2.2"(55)
0.5"(12) 2.5"(64)
2-EN
-
7/27/2019 installation manual eh99865401.pdf
4/24
-
7/27/2019 installation manual eh99865401.pdf
5/24
4
Outdoor Unit Installation Manual
EN
3 SYSTEM REQUIREMENTSPiping (Field supplied) Minimum refrigerant line length between the outdoor
unit and indoor unit is 16.5 (5 m)
Maximum pipe lengths
Figure of Single
Refrigerant sizes
Flare nuts and flaring
The flare nuts and flaring are different from those for
the conventional refrigerant.
Use the flare nuts supplied with the air conditioner or
those for R410A.
Before performing flaring, carefully read
REFRIGERANT PIPING
Insulation
Both lines need to be insulated. Use a minimum 0.4
(10 mm) wall thickness.
Refrigerant charge
* Caution during addition of refrigerantMax. amount of additional refrigerant is 1.8 lbs (800g).Charge the refrigerant accurately. Overcharging
may cause serious trouble with the compressor.* Minimum refrigerant pipe is 165(5 m).
This may cause a malfunction of the compressor orother devices.
Metering Device is an electronic EXV (PMV) inoutdoor unit.
Connecting power and controlcables (Field supplied)
The main power is supplied to the outdoor unit. The
field supplied connecting cables from the outdoor
unit to the indoor unit consist for 4 wires and provides
the power for the indoor unit as well as the
communication signal between the outdoor and
indoor unit.
System interconnection wire size must be AWG12.
Breaker must have a capacity specified in the
following table.
All wiring must comply with local electric codes and
NEC (National Electric Code) or CEC (Canadian
Electric Code).
Allowablepipe length
(ft (m))
Height difference(Indoor-outdoor H)
(ft (m))
Number ofbent portions
Total lengthL
Indoor unit:Upper
Outdoor unit:Lower 10 or less
1641 (50) 985 (30) 985 (30)
Liquid side Gas side
Outerdiameter
ThicknessOuter
diameterThickness
3/8(9.5 mm)
0.03(0.8 mm)
5/8(15.9 mm)
0.04(1.0 mm)
HL
Indoor Unit
Outdoor Unit
Length of refrigerantpipe connected to
indoor/outdoor unitAdditional refrigerant
165 - 985(5 - 30 m)
None
*985 - 1641(30 - 50 m)
Add 0.43 oz/ft (40 g/m) ofrefrigerant for piping that exceeds985 (30 m) up to 1641 (50 m).
Model RAV- SP240
Power supply 208/230 V, 60 Hz
MCA 24 A
MOCP (MAX Fuse/CB) 40 A
Breaker 25 A
System interconnection wires AWG12
MCA = Minimum Circuit AmpsMOCP =Maximum Over Protection Device Amps.
4-EN
-
7/27/2019 installation manual eh99865401.pdf
6/24
5
Outdoor Unit Installation Manual
4 PRECAUTIONS FOR SAFETYInstalling, starting up, and servicing air--conditioning equipment can be hazardous due to system pressures,
electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start--up, and service this equipment.Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should
be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached
to the equipment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby
when brazing. Use care in handling, rigging, and setting bulky equipment.
Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the
unit. Consult local building codes and National Electrical Code (NEC) for special requirements. Recognize safety
information. This is the safety--alert symbol . When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNINGsignifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which
may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which
will result in enhanced installation, reliability, or operation.
WARNING
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.Perform installation work properly according to the Installation Manual.Inappropriate installation may result in water leakage, electric shock or fire.
Be sure to ground the equipmentImproper grounding may cause an electric shock.Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
Turn off the main power supply switch or breaker before attempting any electrical work and maintenance.Make sure all power switches are off. Failure to do so may cause electric shock.Use an exclusive power circuit for the air conditioner. Use the rated voltage.
When moving the air conditioner for installation to another place, be very careful not to allow the specifiedrefrigerant (R410A) to become mixed with any other gaseous body into the refrigeration cycle.If air or any other gas mixes with the refrigerant, the gas pressure in the refrigeration cycle will become abnormallyhigh and it may result in the pipe bursting or personal injuries.
Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlockswitches.
Do not touch the intake or aluminium fins of the outdoor unit.Doing so may result in injury.
Tighten the flare nut with a torque wrench in the specified manner.Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result inrefrigerant leakage.
Install the air conditioner securely in a location where the base can sustain the weight of the unit adequately.
If refrigerant gas has leaked during the installation work, ventilate the room immediately.If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
After the installation work, confirm that refrigerant gas does not leak.If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas may begenerated.
Electrical work must be performed by a qualified electrician in accordance with the NEC or local code. Makesure the air conditioner uses an exclusive power supply.An insufficient power supply capacity or inappropriate installation may cause fire.
Use only the specified wiring during the unit installation. Ensure that all terminals are securely fixed, so
preventing any external forces having a negative effect on the terminals.
5-EN
-
7/27/2019 installation manual eh99865401.pdf
7/24
6
EN
Outdoor Unit Installation Manual
WARNING
When the air conditioner cannot cool or heat a room well, contact the dealer from whom you purchased theair conditioner as refrigerant leakage is considered as the cause.
In the case of repair that requires refill of refrigerant, ask service personnel about details of the repair.The refrigerant used in the air conditioner is harmless.Generally, the refrigerant does not leak. However, if the refrigerant leaks in a room and a heater or stove burner inthe room catches fire, it may generate toxic gas.When you ask service personnel for repairing refrigerant leakage, confirm that the leakage portion has beencompletely repaired.
Do not install the air conditioner in a location that may be subjected to a risk of exposure to a combustiblegas.If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
Install the refrigerant pipe securely during the installation work before operating the air conditioner.If the compressor is operated with the valve open and without the refrigerant pipe, the compressor sucks air and therefrigeration cycle is over pressurized, which may cause a burst or injury.
When carrying out the pump-down work, shut down the compressor before disconnecting the refrigerantpipe.Disconnecting the refrigerant pipe with the service valve left open and with the compressor still operating will causeair, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possiblyresulting in rupturing, injury, etc.
CAUTION
Do not climb onto or place objects on top of the outdoor unit.You may fall or the objects may fall off of the outdoor unit and result in injury.
Wear heavy gloves during the installation work to avoid injury.
EQUIPMENT DAMAGE HAZARDFailure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must bea 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length isburied, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causesrefrigerant slugging and could possibly damage the compressor at start-up.
6-EN
-
7/27/2019 installation manual eh99865401.pdf
8/24
7
Outdoor Unit Installation Manual
5 INSTALLATION OF NEW REFRIGERANTAIR CONDITIONER
CAUTION
New Refrigerant Air Conditioner Installation THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY
OZONE LAYER.R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the workingpressure of R410A refrigerant is approx. 1.6 times as that of refrigerant R22. Accompanied with the adoption of the newrefrigerant, the refrigerant oil has also been changed. Therefore, during installation work, be sure that water, dust,former refrigerant, or refrigerant oil does not enter the new type refrigerant R410A air conditioner cycle.To prevent mixing of refrigerant or refrigerant oil, the sizes of connecting sections of charging port on main unit andinstallation tools are different from those of the conventional refrigerant units. Accordingly, special tools are required forthe new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittingsmade for R410A only, so that water and/or dust does not enter.
Required Tools/Equipment and Precautions for UsePrepare the tools and equipment listed in the following table before starting the installation work.
: R410A exclusive
: Generic
Tools/equipment Use
Manifold gauge* Vacuuming/charging refrigerantand operation checkCharging hose
Gas leak detector Gas leak check
Vacuum pump with backflowprevention function
Vacuum drying
Flare tool Flare machining of pipes Usable if dimensions are adjusted.
Bender Bending pipes
Refrigerant recovery equipment Refrigerant recovery
Torque wrench Tightening flare nuts 1/2 (12.7 mm) and 5/8 (15.9 mm)
Pipe cutter Cutting pipes
Brazing torch and nitrogencylinder
Braze pipes
Refrigerant charging scales Charging refrigerant
4 mm hexagon wrench Opening liquid valve
7-EN
-
7/27/2019 installation manual eh99865401.pdf
9/24
8
Outdoor Unit Installation Manual
EN
Installation Location
WARNING
Install the outdoor unit in a location that can supportthe weight of the outdoor unit.Insufficient durability may cause the outdoor unit to fall,which may result in injury.
CAUTION
Do not install the outdoor unit in a location that issubject to combustible gas leaks.Accumulation of combustible gas around the outdoorunit may cause a fire.
Install the outdoor unit in a location that meets thefollowing conditions. A well-ventilated location free from obstacles near the
air inlets and air outlet A location that does not increase the operating noise
or vibration of the outdoor unit A location that does not produce any drainage
problems from discharged water Location with easy access to power.
Do not install the outdoor unit in the followinglocation. A location with a saline atmosphere (coastal area) or
one that is full of sulfide gas (hot-spring area) (Special
maintenance is required.) A location subject to oil, vapor, oily smoke, orcorrosive gases
A location in which organic solvent is used A location where high-frequency equipment (including
inverter equipment, private power generator, medicalequipment, and communication equipment) is used(Installation in such a location may cause malfunctionof the air conditioner, abnormal control or problemsdue to noise from such equipment.)
A location in which the discharged air of the outdoorunit blows against the window of a neighboring house
A location where the operating noise of the outdoorunit is transmitted
When the outdoor unit is installed in an elevatedposition, be sure to secure its feet.
A location in which drain water poses any problems.
When an outdoor unit is installed in a location that isalways exposed to strong winds like a coast or onthe high stories of a building, one of the following isrecommended. Install the unit so that its discharge faces the wall of
the structure.Keep a distance 19.7 (500 mm) or more between theunit and wall.
Install the unit so that the discharge is at a right anglerelative to the wind direction.
Use wind baffle. Produce those parts in the field. When outside temperature conditions are 23 F (-5
C) or lower and unit is running in cooling mode.
19.7" (500 mm)
Strong wind
Strong wind
Wind baffle
Wind baffle
8-EN
-
7/27/2019 installation manual eh99865401.pdf
10/24
-
7/27/2019 installation manual eh99865401.pdf
11/24
10
Outdoor Unit Installation Manual
EN
Barriers in front and back of unit
Open above and to the right and left of the unit.
The height of an barrier in both the front and rear of the
unit, should be lower than the height of the outdoor
unit.
Standard installation1. Single unit installation
2. Multiple unit installation
a. Intake and supply parallel
b. Intake and supply in line
Open above and to the right and left of the unit.
The height of an obstacle in both the front and
rear of the unit should be lower than the height
of the outdoor unit.
Standard installation
Installation of Outdoor Unit Before installation, check the strength and horizontal
of the base so that abnormal sounds do not
emanate.
According to the following base diagram, fix the base
firmly with the anchor bolts.
(Anchor bolt, nut: 3/8 (M10) x 4 pairs)
1) Field fabricate a snow or an ice stand for the
unit using the above dimension.
2) Place snow or ice stand on a foundation/pad
and secure it to the foundation/pad and secure
it to the foundation/pad by anchor bolts.
5.9
(150)
ormore
39
.4(1000)
or
more
11.8 (300) or more
11.8 (300)
or more
39.4
(1000)
ormore
7.9
(200)
ormore
39.4(1000)or more
11.8(300) ormore
59.1(1500)or more
78.7(2000)or more
7.9(200)or more
Drain hole
Drainnipple mounting hole
Drain hole
5.9 (150)20.7 (525)
1.8 (45)
23.6 (600)
15.8
(400)
14.4
(365)
5.9 (150)
NOTE
When the outdoor unit is anchored directly on
the foundation/pad (cooling only protrude a
minimum of 6 (15 mm)).
0.6 (15 mm) or less
10-EN
-
7/27/2019 installation manual eh99865401.pdf
12/24
11
Outdoor Unit Installation Manual
3) Place unit on stand. Make sure it is level and
fasten securely to the stand.
As shown in the figure below, install the
foundation and vibration-proof rubber pads to
directly support the bottom surface of the fixing
leg that is in contact with the bottom plate of the
outdoor unit.
When installing the foundation for an outdoor
unit with downward piping, consider the piping
work.
When water is to be drained through the drain hose,
attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner diameter:
0.6 (16 mm)) sold on the market. Also seal the
screws securely with silicone material, etc., to
prevent water from leaking.
Some conditions may cause condensation or
dripping of water.
When collectively draining discharged water
completely, use a drain pan.
For ReferenceIf a heating operation is to be continuously performed
for a long time under the condition that the outdoor
temperature is 32 F (0 C) or lower, draining defrosted
water may be difficult due to the bottom plate freezing,
resulting in trouble with the cabinet or fan.
GOOD
Mounting leg
Foundation
GOOD
NO GOOD
Foundation
Foundation
If only the end of themounting leg issupported, it maydeform.
Do not supportthe outdoor unitonly with themounting leg.
Bottom plateof outdoor unit
Support the bottom surface of themounting leg that is in contact withand underneath the bottom plate ofthe outdoor unit.
Drain nippleWaterproof rubber cap(5pcs.)
Waterproof rubber cap
Drain nipple
11-EN
-
7/27/2019 installation manual eh99865401.pdf
13/24
12
Outdoor Unit Installation Manual
EN
6 REFRIGERANT PIPINGPiping connections are inside the front panel of the unit
and the front panel and pipe cover needs to be
removed before piping and wiring connections aremade.
Piping can enter the outdoor unit from the back, from
the side or from the bottom as shown
1. Remove the front panel of the unit.
2. Remove the pipe cover.
3. Remove the appropriate knockout dependingon the orientation of the piping.
* Be sure to wear heavy work gloves while working.4. Remove the burrs from the knockout opening
and use the factory supplied protective edgeguard material around the opening to protect thepiping and the wiring.
5. Remove the flare nut from the service valve onoutdoor unit. Insert the flare nut into the fieldpiping, and flare the pipe.Bend the pipe approx. 90 degree with a pipebender for side and rear piping.
6. When the piping connections are complete re-install the pipe cover.
Flaring
1. Cut the pipe with a pipe cutter.
Be sure to remove burrs that may cause a gasleak.
2. Insert the supplied flare nut into the pipe, and then
flare the pipe.
As the flaring sizes of R410A differ from those of
refrigerant R22, the flare tools newly manufactured
for R410A are recommended.
However, the conventional tools
can be used by adjusting the
projection margin of the copper
pipe.
Projection margin in flaring : B (Unit : in (mm))Rigid (Clutch type)
Flaring diameter size : A (Unit : in (mm))
* In case of flaring for R410A with theconventional flare tool, pull the tool outapprox. 0.02 (0.5 mm) more than that forR22 to adjust it to the specified flare size.The copper pipe gauge is useful foradjusting the projection margin size.
Rearward
Pipe cover
Sideward
Downward
Rear
Front panel
Side
Bottom
Pipe cover
The pipe cover is easily mounted by cutting off
the slit at the lower part of the pipe cover.
Outer diameter ofcopper pipe
R410A toolused
Conventionaltool used
R410A0.04 - 0.06(1.0 - 1.5)
3/8 (9.5)0 - 0.02 (0 - 0.5)
5/8 (15.9)
Outer diameter of copper pipe A
3/8 (9.5) 0.52 (13.2)
5/8 (15.9) 0.78 (19.7)
B
+0-0.02" (0.4)
A
12-EN
-
7/27/2019 installation manual eh99865401.pdf
14/24
13
Outdoor Unit Installation Manual
Tightening of FlareConnections
1. Align the centers of the flare connections and fully
tighten the flare nuts with your fingers.
2. Use two wrenches to loosen or tighten the flare nut
on the gas service valve as shown in the figure.
Use only one wrench to loosen or tighten the flare
not on the liquid service valve.
The final tightening with a torque wrench should be
to the specifications shown in table below.
Unit : ftlbs (Nm)
After the installation work, be sure to check for gasleaks of the pipe connections with nitrogen.
CAUTION
1. Do not put the crescent wrench on the chargeorifice or cover.The valve may be broken.
2. If applying excessive torque, the nut may breakaccording to some installation conditions.
Pressure of R410A is higher than that of R22
(Approx. 1.6 times).
Therefore, using a torque wrench, tighten the flare
pipe connecting sections that connect the indoor/
outdoor units at the specified tightening torque.
Incomplete connections may cause not only a gas
leak, but also trouble with the refrigeration cycle.
Outer diameter of copper pipe Tightening torque
3/8 (9.5 mm) 24 - 31 (33 - 42)
5/8 (15.9 mm) 50 - 60 (68 - 82)
Flare nut
Loosened
Tightened
Piping valve
Cap
Valve at liquid side
Cover
Piping valveCap
Tightened
Flare nut
Loosened
Valve at gas side
Charge orifice
Do not apply refrigerant oil to the flared
surface.
Cover
NO GOOD
Charge orifice
13-EN
-
7/27/2019 installation manual eh99865401.pdf
15/24
14
Outdoor Unit Installation Manual
EN
7 ELECTRICAL CONNECTIONSWARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result inpersonal injury or death. The unit cabinet must have an uninterrupted or
unbroken ground to minimize personal injury if anelectrical fault should occur. The ground may consistof electrical wire or metal conduit when installed inaccordance with existing electrical codes.
Before performing service or maintenance, be suremain power switch is turned OFF.
CAUTION
All wiring and connections must comply with NEC, CEC,local codes.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damageor improper operation. Unit failure as a result of operation on improper line
voltage or excessive phase imbalance constitutesabuse and may cause damage to electricalcomponents.
Wrong wiring may cause a burn-out of some electricalparts.
Do not damage or scratch the conductive core or innerinsulator of the power and inter-connecting wireswhen peeling them.
Field wiringThe dashed lines show field wiring.
System interconnection wire size must be AWG12.
Breaker must have a capacity specified in the
following table.
All wiring must comply with local electric codes and
NEC (National Electric Code) or CEC (Canadian
Electric Code).
Connect the system interconnection wires (indoor to
outdoor) to the identical terminal numbers on the
terminal block of each unit.
Incorrect connection may cause a failure.
1. With the front panel removed the electrical control
box is exposed at the top right corner of the unit.
2. Terminate the field wiring conduit (if used) at the
conduit connection holes provided.
3. Route the field power wires and the systeminterconnection wires as shown on the following
pages. Terminate the wires at field wiring terminal
blocks located immediately below the electrical
control box.
Electric parts box
Conduit connection
holes
Piping knockoutPipe cover
Front pane
Electric control box
Field wiringterminalblocks
Conduit connectionholes
Front panel
Piping knockoutFront Pipe cover
Valve mountingbracket
Model RAV- SP240
Power supply 208/230 V, 60 Hz
MCA 24 A
MOCP (MAX Fuse/CB) 40 A
Breaker 25 A
System interconnection wires AWG12
MCA = Minimum Circuit AmpsMOCP =Maximum Over Protection Device Amps.
L1
L2
L1
L2
S
L1
L2
S
Inputpower
(Field powersupply)
(Systeminterconnection wires)
ground
Outdoor unit Indoor unit
Remotecontroller
circuit breaker
208/230 V~,60 Hz
14-EN
-
7/27/2019 installation manual eh99865401.pdf
16/24
15
Outdoor Unit Installation Manual
Wiring1. Remove the front panel and remove the front pipe
cover.
2. Remove the wire cover from back of the front pipe
cover.
3. Pass the wires through the conduit connection holes
and attach the conduit connecters.
4. Connect the wires to the terminal blocks and fix the
wires to the wiring guide with the 2 included banding
band.
L1 L2L1 L2 S
Field power supplyterminal block
Field powersupply wires
Ground screw
Systeminterconncectionterminal block
Ground screw
Banding band
Systeminterconnectionwires
Remove the 4screws.
Front pipe cover
Cable coverWire cover
Conduit connector
Terminal block
Do not make thewires slack in thissection.
Fix with the 2banding band.
Wire guide
15-EN
-
7/27/2019 installation manual eh99865401.pdf
17/24
16
Outdoor Unit Installation Manual
EN
5. Pass the wires through the wiring guide of the front
pipe cover and adjust the wire lengths.
6. Attach the wire cover and hold the wires with the
wiring guide hooks.Do not clip or damage the wires with the cover.
7. Attach the front pipe cover with 4 screws.
8. Connect 2 conduits.
Wiring guide
Fix with a screw.
Hook
Wire cover
Fix with 4screws
conduit
16-EN
-
7/27/2019 installation manual eh99865401.pdf
18/24
17
Outdoor Unit Installation Manual
8 EVACUATE AND DEHYDRATE THESYSTEM
CAUTION
UNIT DAMAGE HAZARDFailure to follow this caution may result in equipmentdamage or improper operation.Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor heat exchanger should
be evacuated using the recommended deep vacuum
method of 500 microns. The alternate triple evacuation
method may be used if the procedure outlined below is
followed. Always break a vacuum with dry nitrogen.
SYSTEM VACUUM ANDCHARGE
Using Vacuum Pump
1. Completely tighten flare nuts A, B, C, D, connect
manifold gage charge hose to a charge port of the
low side service valve.
2. Connect charge hose to vacuum pump.
3. Fully open the low side of manifold gage.
4. Start vacuum pump.5. Evacuate using either deep vacuum or triple
evacuation method.
6. After evacuation is complete, fully close the low sideof manifold gage and stop operation of vacuum
pump.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump
capable of pulling a vacuum of 500 microns and a
vacuum gage capable of accurately measuring this
vacuum depth. The deep vacuum method is the most
positive way of assuring a system is free of air and
liquid water.
Triple Evacuation Method
The triple evacuation method should only be used
when vacuum pump is only capable of pumping down
to 28 in. of mercury vacuum and system does not
contain any liquid water.
Refer to Triple Evacuation Method chart and proceed
as follows:
1. Pump system down to 28 in. of mercury and allow
pump to continue operating for an additional 15minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system
and open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1
hr. During this time, dry nitrogen will be able to
diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in the chart.
System will then be free of any cotaminants and
water vapor.
Service Valve
Indoor UnitC
D
A
B
RefrigerantLow Side
High Side
Outdoor Unit
Service Valve
Manifold
500 microns
Manifold Gage
Low side valve
Charge hose
High side valve
Charge hose
Vacuum pump
Low side valve
500
0
1000
1500
2000
2500
3000
3500
4000
4500
5000
1 2 3 4 5 6 7
LEAK IN
SYSTEM
VACUUM TIGHT
TOO WET
TIGHT DRY
SYSTEM
Deep Vacuum Graph
MICRONS
MINUTES
17-EN
-
7/27/2019 installation manual eh99865401.pdf
19/24
18
Outdoor Unit Installation Manual
EN
Triple Evacuation Method chart
Final Tubing Check
IMPORTANT:
Check to be certain factory tubing on both indoor and
outdoor unit has not shifted during shipment. Ensure
tubes are not rubbing against each other or any sheet
metal. Pay close attention to feeder rubes, making surewire ties on feeder tubes are secure and tight.
Open service valves
Open or close the valve.
Liquid side
Open the valve with a 4 mm hexagon wrench.
Gas side
While the valve is fully opened, after the screwdriver
has reached the stopper, do not apply torque
exceeding 4 ftlbs (5 Nm). Applying excessive
torque may damage the valve.
Valve handling precautions
Open the valve stem until it reaches the stop.
It is unnecessary to apply further force.
Securely tighten the cap with a torque wrench. Cap tightening torque
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
CHECK FOR TIGHT, DRY SYSTEM(IF IT HOLDS DEEP VACCUM)
RELEASE CHARGE INTO SYSTEM
Valve size3/8 (9.5 mm) 24 - 31 ftlbs (33 - 42 Nm)
5/8 (15.9 mm) 15 - 18 ftlbs (20 - 25 Nm)
Charge port 10 - 13 ftlbs (14 - 18 Nm)
Valve unit
Charge orifice
Using a straight bladescrewdriver, turn it 90counter clockwise untilthe valve is fully open(against the stop).
Flare nut
Handle position
Fully closed Fully opened
Stop pin
Main stopper
18-EN
-
7/27/2019 installation manual eh99865401.pdf
20/24
19
Outdoor Unit Installation Manual
9 FINISHINGAfter the refrigerant pipe, inter-unit wires, and drain pipe have been connected, make sure they are supported and
fixed in place for the entire length.
Keep the power wires and system interconnection wires away from all factory wiring and piping.
10TEST RUN Turn on the circuit breaker at least 12 hours before starting the system to preheat the compressor and
prevent damage.
To protect the compressor, power is supplied from the 208/230 VAC input to the unit to preheat the compressor.
Check the following before starting a test run:
That all pipes are connected securely without leaks.
That the valve is open.
If the compressor is operated with the valve closed, the outdoor unit will become over pressurized, which maydamage the compressor or other components.
If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may
cause a burst or injury.
Operate the air conditioner using the correct procedure as specified in the Owners Manual.
11PERIODIC MAINTENANCE For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/
outdoor units are strongly recommended.
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be
cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualifiedservice person.
Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and even
compressor failure.
19-EN
-
7/27/2019 installation manual eh99865401.pdf
21/24
20
Outdoor Unit Installation Manual
EN
12TROUBLESHOOTINGYou can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition
to using the check codes displayed on the wired remote controller of the indoor unit.
Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remotecontroller of the indoor unit are described in the Installation Manual of the indoor unit.
Verifying Fault code status (Outdoor controlboard)
1. Check that DIP switch SW803 is set to off.
2. Record the states (on or off) of LED 800 to LED 804
(Display mode 1).
3. Press SW800 for at least 1 second. The LED status
changes to display mode 2.
4. Since display mode 1 covers multiple faults with the
same code display, mode 2 must also be used to
determine the final fault. Use the status recorded for
LED 800 to LED 804 in display mode 1 (Item 2
above) and combine it with the status for the same
LEDs in display mode 2 (Item 3 above) to determine
the complete fault code using the chart below.
Verifying Fault code status stored inmemory (Outdoor control board)
1. Check that DIP switch SW803 is set to on.
2. Record the states (on or off) of LED 800 to LED 804
(Display mode 1).
3. Press SW800 for at least 1 second. The LED status
changes to display mode 2.
4. Since display mode 1 covers multiple faults with the
same code display, mode 2 must also be used to
determine the final fault. Use the status recorded for
LED 800 to LED 804 in display mode 1 (Item 2
above) and combine it with the status for the same
LEDs in display mode 2 (Item 3 above) to determine
the complete fault code using the chart below.
NOTE
An outside air temperature (TO) sensor error can be
checked only when an error occurs.
No. CauseDisplay mode 1 Display mode 2
D800 D801 D802 D803 D804 D800 D801 D802 D803 D8041 Normal
2 Discharge (TD) sensor error { { {
3 Heat exchanger (TE) sensor error { { {
4 Heat exchanger (TL) sensor error { { {
5 Outside air temperature (TO) sensor error { { {
6 Suction (TS) sensor error { { {
7 Heat sink (TH) sensor error { { {
8Outdoor temperature sensor (TE/TS) connectionerror
{ { {
9 Outdoor EEPROM error { { {
10 Compressor lock { {
11 Compressor lock { {
12 Current detection circuit error { {
13 Thermostat for compressor activated { {
14Model data not set(on the service P.C. board) { { {
15 MCU-MCU communication error { { {
16 Discharge temperature error { { { {
17Abnormal power(open phase detected or abnormal voltage) { { { {
18 Heat sink overheat{ { { {
19 Gas leak detected { { { {
20 4-way valve reverse error { { { {
(:OFF {:ON :Flashing)
20-EN
-
7/27/2019 installation manual eh99865401.pdf
22/24
21
Outdoor Unit Installation Manual
* The LEDs and DIP switches are located on the lower left of the P.C. board of the outdoor unit.
21 High pressure release operation { { { {
22 Outdoor fan motor error { { { {
23 Compressor driver short-circuit protection { { { {
24 Position detection circuit error in one-line display { { { {
No. CauseDisplay mode 1 Display mode 2
D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
(:OFF {:ON :Flashing)
SW801
SW804
SW800
LEDON 12
3
4
SW803
ON 1
2
3
4
SW802
ON 1
2
3
4
D800
D801
D802D803
D804
D805
D800
D801
D802D803
D804
D805
Enlarged viewof LEDs
21-EN
-
7/27/2019 installation manual eh99865401.pdf
23/24
22
EN
Outdoor Unit Installation Manual
13UNIT PUMP DOWN Use the pump down switch SW801 on the P.C. board of the outdoor unit to pump down the unit.
Procedure1. Turn on the power of the air conditioner.
2. Select the FAN mode for indoor unit operation with the remote controller.
3. Set SW804 on the P.C. board of the outdoor unit to all OFF, and then press SW801 for 1 second or more. The
air conditioner enters the forced cooling mode for up to 10 minutes.
Pump down the unit during this 10 minutes.
4. Upon completion of pump down the unit, close the valve and press SW801 for at least 1 second to stop
operation.
5. Turn off the power.
DANGER
Be careful of electric shock because the P.C. board has an electrical current running through it.
14POWER SAVE Power save can be set by setting SW802 dip switch.
Procedure
1. Turn on the SW802 dip switch 2 to activate Power save.
Power save controls reducing compressor periodicity (by approx. 10%) depending on the indoor unit heatexchanger temperature in heating operation
* All switches are OFF as factory default.
CAUTION
Do not touch SW802 dip switch 1, 3 and 4.If any changes are made, the unit may not work properly.
Refrigerantrecovery switchSW801
Optionalconnector CN610
Special operationselect switchSW804
Existing pipeswitch SW802
P.C. boardPump downswitchSW801
Optional connectorCN610
Special operationselect switchSW804
Power save switchSW802
P.C. board
1
2
3
4
ON
SW802
... Power save setting
22-EN
-
7/27/2019 installation manual eh99865401.pdf
24/24