installation manual - b
TRANSCRIPT
![Page 1: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/1.jpg)
Installation Manual - B
Providing equipment and services to manage controlled-temperature environments for food and other temperature-sensitive products, our Climate Control Technologies sector encompasses both transport and stationary refrigeration solutions. Our product brands include Thermo King®, a world leader in transport temperature control systems, and Hussmann®, a manufacturer of refrigeration and food merchandising equipment.
www.thermoking.com www.hussmann.com www.ingersollrand.com
©2008 Ingersoll-Rand Company Printed in U.S.A. on Recycled Paper
Trailer Edition (NAD) Multi-Temperature
SPECTRUMTM Evaporator Systems (SR-2)TK 53509-2-IM (Rev. 5, 01/12)
![Page 2: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/2.jpg)
Installation Manual - B
Trailer Edition (NAD)Multi-TemperatureSPECTRUM™ Evaporator Systems (SR-2)TK 53509-2-IM (Rev. 5, 01/12)
Copyright© 2006 Thermo King Corp., Minneapolis, MN, U.S.A.
![Page 3: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/3.jpg)
2
Printing History
Released (08/06)
Rev. 1 (01/07) Corrected wiring connections on pages 64-69.
Rev. 2. (04/07) Changed Installation Kit from 800117 to 800118 for configurations E, F and L only on page 9.
Rev. 3 (04/11) Updated art and text by replacing ORS fittings with solder fittings on S-2 and S-3 evaporators.
Rev. 4 (04/11) Pages 80-81 - Revised content of SYSTEM CHECK LIST and renamed it UNIT CHECK LIST.
Rev. 5 (01/12) Changed Installation Kit from 800118 to 800579 for configurations E, F and L only on page 9.
![Page 4: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/4.jpg)
3
Trailer Edition Installation Manual - B
for Multi-Temperature SPECTRUM Evaporator Systems (SR-2)
FOR HOST UNIT INSTALLATION INSTRUCTIONS SEE HOST UNIT INSTALLATION MANUALS
This manual is published for informational purposes only. Thermo King makes no representations warranties express or implied, with respect to
the information recommendations and descriptions contained herein. Information provided should not be regarded as all-inclusive or covering
all contingencies. If further information is required, Thermo King Corporation Service Department should be consulted.
Thermo King’s warranty shall not apply to any equipment which has been “so installed, maintained, repaired or altered as, in the manufacturer’s
judgment, to affect its integrity.”
Manufacturer shall have no liability to any person or entity for any personal injury, property damage or any other direct, indirect,
special, or consequential damages whatsoever, arising out of the use of this manual or any information, recommendations or
descriptions contained herein.
![Page 5: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/5.jpg)
4
Table of Contents
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Trailer Multi-Temperature SPECTRUM Selection Guide . . . . . . . . . . . . . . . . 8
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installation Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
S-2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
S-3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
S-2 + S-2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
S-3 + S-3 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Recovering Holding Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Important Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Installation S-2 or S-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Installation S-2 + S-2 or S-3 + S-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Host Tube Connections S-2 or S-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Host Tube Connections (Configuration X Only) . . . . . . . . . . . . . . . . . . . . . . 40
Host Tube Connections (Configuration Y Only) . . . . . . . . . . . . . . . . . . . . . . 42
Host Tube Connections (Configuration Z Only) . . . . . . . . . . . . . . . . . . . . . 44
Evaporator Tube Connections S-2 or S-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Evaporator Tube Connections S-2 + S-2 or S-3 + S-3 . . . . . . . . . . . . . . . . . 50
Evaporator Tube Connections S-3 + S-3 (Configuration X Only) . . . . . . . . 52
Evaporator Tube Connections S-3 (Configuration X Only) . . . . . . . . . . . . . 54
Evaporator Tube Connections S-3 + S-3 (Configuration Y Only) . . . . . . . . 56
Evaporator Tube Connections S-3 + S-3 (Configuration Z Only) . . . . . . . . 60
SB Host & Evaporator Wire Connections - Zone 2 . . . . . . . . . . . . . . . . . . . 64
SB Host & Evaporator Wire Connections - Zone 3 . . . . . . . . . . . . . . . . . . . 66
DE Host & Evaporator Wire Connections - Zone 3 . . . . . . . . . . . . . . . . . . . 68
Drain Hose Resistance Wire Installation Guide . . . . . . . . . . . . . . . . . . . . . . 70
Drain Hose Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Leak Check, Evacuation and Charging Procedures . . . . . . . . . . . . . . . . . . 74
Installing SPECTRUM Evaporator Covers . . . . . . . . . . . . . . . . . . . . . . . . . . 78
UNIT CHECK LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
![Page 6: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/6.jpg)
5
Safety Precautions
Caution
Thermo King Multi-Temp host units are shipped with a 35 kPa (5 psi) holding charge of R-404A. This
holding charge of approximately 1 kg (2 pounds) of refrigerant must be recovered.
The SPECTRUM remote evaporators are shipped with a 35-69 kPa (5-10 psi) holding charge of nitrogen.
This holding charge may be safely vented into the atmosphere.
SEVERE COMPRESSOR DAMAGE will result from operating the engine before completing the system
installation which includes: installing the components, recovering the host unit holding charge, releasing
the remote unit nitrogen holding charge, soldering the refrigeration lines, leak testing the system,
evacuation and clean-up, and charging the system.
Recover Refrigerant
At Thermo King, we recognize the need to preserve the environment and limit the potential harm to the
ozone layer that can result from allowing refrigerant to escape into the atmosphere.
We strictly adhere to a policy that promotes the recovery and limits the loss of refrigerant into the
atmosphere.
![Page 7: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/7.jpg)
6
Safety Precautions
The symbol appears next to a point that is particularly important:
DANGER: Addresses a circumstance that, if encountered, will
lead to death or serious injury.
WARNING: Addresses a circumstance that, if encountered, might
lead to death or serious injury.
CAUTION: Addresses a circumstance that, if encountered, may
cause damage to equipment or minor injury.
DANGER: Never operate the unit with the discharge valve closed
because it could cause the compressor to explode, causing death
or serious injury.
DANGER: Never apply heat to a sealed refrigeration system or
container because it could explode, causing death or serious
injury.
DANGER: Fluorocarbon refrigerants, in the presence of an open
flame or electrical short, produce toxic gases that are severe
respiratory irritants capable of causing death.
DANGER: Be careful when working with a refrigerant or
refrigeration system in any enclosed or confined area with a
limited air supply (i.e., a trailer, container or the hold of a ship).
Refrigerant tends to displace air and can cause oxygen depletion
which may result in death by suffocation.
WARNING: Always wear goggles or safety glasses. Refrigerant
liquid, refrigeration oil, and battery acid can permanently damage
the eyes (see First Aid under Refrigeration Oil).
WARNING: Keep your hands away from fans and belts when the
unit is running. This should also be considered when opening and
closing the compressor service valves.
WARNING: Make sure gauge manifold hoses are in good
condition. Never let them come in contact with a belt, fan motor
pulley, or any hot surface.
WARNING: Make sure all fasteners are torqued to specification
and are of correct length for their particular application.
WARNING: When using ladders to install or service refrigeration
systems, always observe the ladder manufacturer’s safety labels
and warnings. A work platform is the recommended method for
installations.
![Page 8: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/8.jpg)
7
Safety Precautions
Refrigerant
First Aid• FROSTBITE: In the event of frost bite, the objectives of First Aid are
to protect the frozen area from further injury, to warm the affected area
rapidly and to maintain respiration.
• EYES: For contact with liquid, immediately flush eyes with large
amounts of water and get prompt medical attention.
• SKIN: Flush area with large amounts of lukewarm water. Do not apply
heat. Remove contaminated clothing and shoes. Wrap burns with dry,
sterile, bulky dressing to protect from infection/injury. Get medical
attention. Wash contaminated clothing before reuse.
• INHALATION: Move victim to fresh air and use CPR or
mouth-to-mouth ventilation, if necessary. Stay with victim until arrival
of emergency medical personnel.
Refrigeration Oil
First AidIn case of eye contact, immediately flush with plenty of water for at least
15 minutes. CALL A PHYSICIAN. Wash skin with soap and water.
WARNING: Never drill holes in the unit unless absolutely
necessary. Holes drilled into the unit may weaken structural
components. Holes drilled into electrical wiring can cause fire or
explosion.
WARNING: Exposed coil fins are very sharp and can cause
painful lacerations.
WARNING: Regulators used on bottles of nitrogen gas must be
equipped with relief valves. The pressure in a bottle of nitrogen
gas is extremely high. It is high enough to cause components of
the refrigeration system to explode if the regulator malfunctions
or is set wrong. The relief valve provides a safe outlet in case the
regulated pressure exceeds the relief valve limit.
CAUTION: Recover the refrigerant (R-404A) holding charge
from the host unit prior to making any refrigeration tubing
connections to prevent personal injury!
CAUTION: Remove the nitrogen holding charge from the remote
evaporators prior to making any refrigeration tubing connections
to prevent personal injury!
WARNING: Although fluorocarbon refrigerants are classified as
safe refrigerants, certain precautions must be observed when
handling them or servicing a unit in which they are used. When
released to the atmosphere in the liquid state, fluorocarbon
refrigerants evaporate rapidly, freezing anything they contact.
WARNING: Avoid refrigeration oil contact with the eyes. Avoid
prolonged or repeated contact of refrigeration oil with skin or
clothing. Wash thoroughly after handling refrigeration oil to
prevent irritation.
![Page 9: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/9.jpg)
8
Trailer Multi-Temperature SPECTRUM Selection Guide
![Page 10: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/10.jpg)
9
Trailer Multi-Temperature SPECTRUM Selection Guide
MAXIMUM RECOMMENDED
DIMENSIONSInstallation
Kit(s)Tube Kits
Config.Max.
Dims.
S-3
900280
S-3 + S-3
900280 x 2
B A 17.4 ft. - 800116 818066
E A - 31.2 ft. 800116
800579
818067
* Note 1
F A - 28.0 ft. 800116
800579
818066
I A
B
4.1 ft.
31.2 ft.
-
-
800116 818066
J A - 4.1 ft. 800116
800117
818066
L A - 31.2 ft. 800116
800579
818067
*Note 1
N A 17.4 ft. - 800116
800117
818067
T A
B
31.2 ft.
4.1 ft.
-
-
800116
800117
818067
W
(DE)
A
B
4.1ft.
31.2 ft.
-
-
800119 818066
*Note 1
X A
B
-
17.4 ft.
31.2 ft.
-
800120 N/A
Y A
B
17.4 ft.
-
-
31.2 ft.
800121 N/A
Z A
B
-
-
-
31.2 ft.
800122 N/A
NOTE 1: Trailers 48 ft. and longer with configuration E, L or W requires supplemental
tube kit 880097.
NOTE 2: Transverse mounted evaporators configurations B, F, N and T requires one
drain kit 880041 for each evaporator.
![Page 11: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/11.jpg)
10
Required Tools
1. Safety Glasses
2. Tape Measure
3. Screwdrivers - Phillips and Straight Blade
4. Drill
5. Drill Bits
6. Hole Saw
7. Torque Wrench
8. Box and Open End Wrenches - 7/16”, 1/2”, 9/16”, 5/8”, 3/4”
9. 12” Adjustable Wrench
10. Crow’s Feet - 7/8”, 1”, 1-3/8”
11. Tap and Die Set (Europe only)
12. Wire Stripper
13. Wire Crimper - for insulated terminals
14. Electronic Leak Detector
15. Tube Benders
16. Tubing Cutter
17. Tubing Swages
18. Tubing Brushes
19. Scotch Brite Pads
20. Torch Set
21. 15% Silver Solder(203-364) & Flux (203-365)
22. Heat Shield
23. Manifold Set
24. Evacuation Station (TK-204-725)
25. Reclaiming Station
26. Refrigerant Oil
27. Refrigerant and Scale
28. Dry Nitrogen
29. Battery Charger (60 AMP minimum)
30. Mechanical Lift (modified drywall lift)
NOTE: Equipment such as scales, gauges, refrigerant leak detectors, and torque wrenches should be in good working condition and routinely calibrated
to assure accurate readings.
![Page 12: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/12.jpg)
11
Required Tools
BLANK PAGE
![Page 13: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/13.jpg)
12
Installation Components
1. Clamps
2. Screws
3. Pre-Bent Tubes
4. Copper Tees
5. Copper Couplings
6. Tube Insulation
7. Refrigerant Tubing (US Only)
8. Drain Hose
9. Copper Elbows
10. Drain Hose Tee
11. Mounting Spacer
12. Terminal Fork
13. Terminal Ring
14. Plastic Band Wraps
15. Jumper Strip
16. Electrical Harnesses
![Page 14: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/14.jpg)
13
Installation Components
![Page 15: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/15.jpg)
14
S-2 Dimensions
NOTE: All mounting locations must be correct to properly install the
SPECTRUM evaporator(s).
Mount all evaporators as close to one side wall as possible to minimize
drain tube length and reduce exposure to damage.
The minimum distance 1229.4 mm (48.4 in.) from the bulkhead to the front
of the evaporator must be maintained for proper operation.
A, B, C, D, E, and F indicate locations of solder fittings measured
vertically from the top of the evaporator and horizontally from the
evaporator mounting hole.
NOTE: See “96 in. Wide Trailer Installation Matrix” on pages 28
and 29.
![Page 16: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/16.jpg)
15
S-2 Dimensions
Reference: 1E02132 Sheet 1
WEIGHT = 43 kg (95 lb.)
![Page 17: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/17.jpg)
16
S-3 Dimensions
NOTE: All mounting locations must be correct to properly install the
SPECTRUM evaporator(s).
Mount all evaporators as close to one side wall as possible to minimize
drain tube length and reduce exposure to damage.
The minimum distance 1229.4 mm (48.4 in.) from the bulkhead to the front
of the evaporator must be maintained for proper operation.
A, B, C, D, E, and F indicate locations of solder fittings measured
vertically from the top of the evaporator and horizontally from the
evaporator mounting hole.
NOTE: See “96 in. Wide Trailer Installation Matrix” on pages 28
and 29.
![Page 18: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/18.jpg)
17
S-3 Dimensions
Reference: 1E02132 Sheet 2WEIGHT = 52 kg (115 lb.)
![Page 19: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/19.jpg)
18
S-2 + S-2 Dimensions
NOTE: All mounting locations must be correct to properly install the
SPECTRUM evaporator(s).
Mount all evaporators as close to one side wall as possible to minimize
drain tube length and reduce exposure to damage.
The minimum distance 1229.4 mm (48.4 in.) from the bulkhead to the front
of the evaporator must be maintained for proper operation.
A, B, C, D, E, and F indicate locations of solder fittings measured
vertically from the top of the evaporator and horizontally from the
evaporator mounting hole.
NOTE: See “96 in. Wide Trailer Installation Matrix” on pages 28
and 29.
![Page 20: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/20.jpg)
19
S-2 + S-2 Dimensions
WEIGHT = 43 kg (95 lb.) eachReference: 1E02132 Sheet 3
![Page 21: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/21.jpg)
20
S-3 + S-3 Dimensions
NOTE: All mounting locations must be correct to properly install the
SPECTRUM evaporator(s).
Mount all evaporators as close to one side wall as possible to minimize
drain tube length and reduce exposure to damage.
The minimum distance 1229.4 mm (48.4 in.) from the bulkhead to the front
of the evaporator must be maintained for proper operation.
A, B, C, D, E, and F indicate locations of solder fittings measured
vertically from the top of the evaporator and horizontally from the
evaporator mounting hole.
NOTE: See “96 in. Wide Trailer Installation Matrix” on pages 28
and 29.
![Page 22: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/22.jpg)
21
S-3 + S-3 Dimensions
WEIGHT = 52 kg (115 lb.) each
Reference: 1E02132 Sheet 4
![Page 23: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/23.jpg)
22
Recovering Holding Charge
NOTE: The host unit must be placed in the Evacuation Mode to open the
normally closed solenoid valves throughout this procedure. See “Leak
Check, Evacuation and Charging Procedures” on page 74.
1. Set refrigerant recovery device to recover R-404A vapor.
2. Recover refrigerant vapor from host unit to 0 kPa (0 psi) from receiver
outlet valve and suction service valve.
3. Remove the manifold gauge lines from receiver outlet valve and
suction service valve. Leave service valves open to port to act as vents.
NOTE: It is important to minimize the amount of time the tubes are
uncapped and open to ambient conditions. Always keep tubes capped
until ready to connect and solder.
4. Unsolder tube caps from hot gas, liquid, and suction lines on host unit.
NOTE: Some host units are supplied with two suction lines. Only remove
caps from both suction lines if required for your application.
CAUTION: Make sure holding charge from host unit has been
recovered before proceeding to prevent personal injury!
![Page 24: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/24.jpg)
23
Recovering Holding Charge
![Page 25: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/25.jpg)
24
Important Installation Notes
EVAPORATOR LOCATION
• The best airflow is achieved when the evaporator is installed an equal
distance from each side wall.
• It is recommended that moving bulkheads not be allowed closer than
1229.4 mm (48.4 in.) or 1 pallet + 4.00 inches from the evaporator
outlet (Detail I).
• The minimum clearance from the bottom to the top of the cargo and all
sides of the evaporator except the evaporator outlet should be 101 mm
(4.00 in.) (Detail I).
NOTE: This minimum clearance does not refer to the trailer LOAD
LINE.
• The evaporator should be located a minimum of 51 mm (2.00 in.) from
the trailer wall (Detail IlI).
DEFROST DRAINS
• The drain tube should be offset 35.5 mm (1.4 in.) from the mounting
holes (Detail II).
• The evaporator must be properly mounted to provide a slope towards
the drain. This is accomplished by adding one 3/8 in. and one 3/16 in.
washers on the drain side and only one 3/8 in. washer on the other side
at each mounting surface (Detail III).
• Defrost drains must exit the evaporator at a 45° angle and have a
minimum downward gradient of 267 mm (10.50 in.) from the trailer
ceiling to the top of the drain in the trailer wall (Detail III).
WALL DRAIN TUBE - (Details II and III)
• CPVC
• 1.00 in. ID (Inside Diameter)
ELECTRICAL WIRING
IMPORTANT: DO NOT CUT THE SENSOR HARNESSES
• All electrical harness must be secured by clamps at least every 600 mm
(24.00 in.).
• Additional harnesses (options, etc.) can be secured with tie bands to the
harnesses that are clamped in place.
![Page 26: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/26.jpg)
25
Important Installation Notes
![Page 27: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/27.jpg)
26
Important Installation Notes
TROUGH LOCATION - (Details IV - VII)
• The OEM and Dealer should discuss trough locations based on
application before the trailer is built.
• Only one trough is required.
• The trough should be located in such a way as to allow for proper
routing of the suction line(s). 3 compartment trailers may have two
suction lines in the trough.
• A ceiling trough is recommended. If that is not possible, a wall through
should be located to allow the lowest suction line to be at least 25 mm
(1.00 in.) above the remote evaporator suction line fitting once secured
to the trough.
REFRIGERANT TUBING and CONNECTIONS
• Thermo King Requires the use of bulk rolled refrigeration grade tubing
and tube benders to reduce fittings and solder joints where applicable.
• The use of large radius bends is preferred over copper fitting joints.
• It is important to minimize the amount of time the tubes are uncapped
and open to ambient conditions. Always keep tubes capped until ready
to connect and solder.
• Check tubes and copper fittings for obstructions prior to assembly.
• Use 15% silver solder for joining all remote refrigerant tubes.
• Suction and liquid tubes are to be insulated when outside the trough.
Hot gas tubes are to be 100% insulated.
• All refrigeration tubes must be secured by clamps at least every 600
mm (24.00 in.).
• All dual evaporator installations require two suction tubes
(Detail V, VII).
• Configuration X installations will require two suction tubes: 1-1/8 in.
for Zone 2 and 7/8 in. for Zone 3.
• Configuration Y installations will require two suction tubes: 7/8 in. for
Zone 2 and 1-1/8 in. for Zone 3.
• Configuration Z installations require 1-1/8 in. suction tubes for both
Zone 2 and Zone 3.
• All soldering of tubes should be done according to the best practices
soldering document, Section 16, of the Certi-Tech Professional
Manual.
• It is also required that nitrogen or another inert gas be used to purge the
tubes while soldering. This prevents oxidation and formation of scale
inside tubes.
IMPORTANT: The following procedure should be followed to correctly
purge the tubes with nitrogen when soldering.
1. Midseat the suction and discharge service valves on the host
unit.
2. On one remote evaporator in each remote zone connect a 6 volt
lantern battery to the HGS and SOL terminals of the terminal
strip. This activates the Hot Gas Solenoid to allow nitrogen to
flow.
3. Connect a nitrogen supply hose to the access port on the same
remote evaporator that the battery was connected. Make sure
the supply hose fitting has a Schrader valve depressor to open
the Schrader valve on the access port.
4. Adjust the nitrogen flow to 5-10 CFH.
5. The nitrogen supply and lantern battery must be maintained
while soldering the remote and host unit connections.
![Page 28: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/28.jpg)
27
Important Installation Notes
NOTE: SIDE TROUGH ONLY Suction Line(s) must always be located at top of trough.
![Page 29: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/29.jpg)
28
Important Installation Notes
Host Unit Return Air
• In lane configurations, care must be taken to avoid the inner walls
obstructing return air to the host. Not only is host performance
impaired, but temperature management will suffer if return air does
not flow over the return air sensor.
Door Switches
• Door switches automatically turn off remote evaporators when the
corresponding door is opened. This avoids the entry of warm, moist
air into the load space. Door switches are recommended for all
multi-temp installations.
Door Curtains
• It is always recommended to use good quality insulated curtains on
all doors to limit the amount of warm, moist air from entering the
load space during door openings.
Full Length Lanes
• Always consider the use of an SB-III DE (Dual Evaporator) where
full length lanes are required. This is the most efficient and cost
effective solution for these demanding applications, and a product
unique to Thermo King.
96 in. Wide Trailer Installation MatrixNOTE: The installation of parallel S3+S3 on a 96” wide trailers may be too tight due to variations of trailer wall thicknesses. Since Spectrum evaporators
allow for the drain hose to exit the front, you can install a parallel S3+S3 based on the assumptions shown below.
THIS IS AN EXAMPLE, NOT A SPECIFICATION
THE TRAILER OEM AND DEALERS ARE EXPECTED TO VALIDATE THESE CALCULATIONS
ASSUMING THE DRAIN IS COMING OUT THE SIDE OF THE EVAPORATOR:
Trailer Width 96 96 96 96 96
Wall Thickness 4 3.5 3 2.5 2
Difference 88 89 90 91 92
Evaporator Clearance from Road Side Wall 2 2 2 2 2
Evaporator Clearance from Curb Side Wall 2 2 2 2 2
S3+S3 Width 86.81 86.81 86.81 86.81 86.81
Space Left-2.81 -1.81 -0.81
0.19
not ideal1.19
S2+S2 Width 59.85 59.85 59.85 59.85 59.85
Space Left 24.15 25.15 26.15 27.15 28.15
![Page 30: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/30.jpg)
29
Important Installation Notes
96 in. Wide Trailer Installation Matrix
ASSUMING THE DRAIN IS COMING OUT THE FRONT OF THE EVAPORATOR:
Trailer Width 96 96 96 96 96
Wall Thickness 4 3.5 3 2.5 2
Difference 88 89 90 91 92
Evaporator Clearance from Road Side Wall 1 1 1 1 1
Evaporator Clearance from Curb Side Wall 1 1 1 1 1
S3+S3 Width 86.81 86.81 86.81 86.81 86.81
Space Left-0.81
-0.19
not ideal1.19 2.19 3.19
S2+S2 Width 59.85 59.85 59.85 59.85 59.85
Space Left 24.15 25.15 26.15 27.15 28.15
ASSUMING THE DRAIN IS COMING OUT THE FRONT OF THE EVAPORATOR:
Trailer Width 96 96 96 96 96
Wall Thickness 4 3.5 3 2.5 2
Difference 88 89 90 91 92
Evaporator Clearance from Road Side Wall 0.5 0.5 0.5 0.5 0.5
Evaporator Clearance from Curb Side Wall 0.5 0.5 0.5 0.5 0.5
S3+S3 Width 86.81 86.81 86.81 86.81 86.81
Space Left0.19
not ideal1.19 2.19 3.19 4.19
S2+S2 Width 59.85 59.85 59.85 59.85 59.85
Space Left 27.15 28.15 29.15 30.15 31.15
![Page 31: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/31.jpg)
30
Important Installation Notes
Defrost Drain Tube Connector Installation
IMPORTANT: Follow the instructions below to prevent defrost drain
tube water leaks.
All Spectrum remote evaporators are equipped with a quick disconnect
fitting that connects the drain pan to the drain tubes (Detail I).
To properly install the tube make sure that the tube is fully inserted past the
O-ring and up to the stop inside the coupler (Detail II).
NOTE: The fitting will grip the tube before it seals with the o-ring.
When the tube is in the correct position the O-ring will seal and the teeth
will grip the tube keeping it in place. Check the fit by pulling on the tube(s)
to insure that it will not pull out of the fitting (Detail III).
To disconnect the tube from the fitting: press the collet into the fitting.
Hold the collect in place and pull the tube out. The fitting can be re-used.
Clean any burrs off the tube before re-inserting it into the fitting
(Detail IV).
![Page 32: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/32.jpg)
31
Important Installation Notes
![Page 33: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/33.jpg)
32
Important Installation Notes
![Page 34: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/34.jpg)
33
Important Installation Notes
![Page 35: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/35.jpg)
34
Installation S-2 or S-3
Ceiling Preparation
IMPORTANT: The trailer ceiling must be structurally strong enough to
support the weight of the S-2 evaporator(s) 43 kg (95 lb.) each or S-3
evaporator(s) 52 kg (115 lb.) each.
IMPORTANT: The ceiling must be flat and the mounting locations
correct for proper SPECTRUM evaporator installation. The foam
insulation in the ceiling must be removed from the evaporator mounting
area and aluminium spacers must be installed between the evaporator
mounting plate and trailer ceiling.
NOTE: If the trailer frame is other than aluminum, use mylar film
between aluminum spacer and frame.
• For ceiling mounting stud applications, weld a nut (same thread as
stud) onto a 44.45 mm (1.75 in.) hole saw and turn the nut onto the
mounting stud using a socket wrench (Detail I).
• For ceiling mounting bolt applications, weld a bolt (same thread as
tapped hole) onto a 44.45 mm (1.75 in.) hole saw and turn into the
tapped mounting hole using a socket wrench (Detail I).
• Alternative method is to remove the mounting studs or bolts and use a
hole saw with a standard pilot drill small enough to run up into the
threaded hole without damaging the threads. Reinstall mounting studs
or bolts.
Mounting Stud or Bolt Requirements
The mounting studs or bolts used to attach the evaporator(s) to the ceiling
must be 10.0 mm, (0.50 in., Grade 5, U.S. applications only), medium
carbon steel, 120000 PSI tensile strength, cadmium plate and dichromate
finish. Studs to extend below ceiling 38.0 mm (1.50 in.) to 50.1 mm (2.00
in.)
Evaporator Installation
IMPORTANT: The evaporator must be properly mounted to provide a
slope towards the drain. This is accomplished by adding one 3/8 in. and
one 3/16 in. washers on the drain side and only one 3/8 in. washer on the
other side at each mounting surface (Detail IV).
1. Remove evaporator cover to access mounting holes.
NOTE: The installation kit provides both metric and imperial nuts
and washers. Be sure to use the correct ones for your application.
Mounting Stud Installations
2. Install the aluminum spacers onto the ceiling mounting studs and raise
the evaporator into position. Secure the evaporator onto the mounting
studs with flat washers and locking nuts (Detail II). Torque to 81.3
N•m (60 ft-lb).
Mounting Bolt Installations
3. Install the mounting bolts, lock washers (installer supplied) and flat
washers onto the evaporator and raise into position. Install the
aluminium spacers and secure the evaporator to the ceiling
(Detail III). Torque to 81.3 N•m (60 ft-lb).
4. A properly installed evaporator will slope slightly toward the drain
tubes to allow for water drainage. Two additional washers are included
in the kit to help assist sloping the evaporator towards the drain
(Detail IV).
![Page 36: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/36.jpg)
35
Installation S-2 or S-3
![Page 37: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/37.jpg)
36
Installation S-2 + S-2 or S-3 + S-3
Ceiling PreparationIMPORTANT: The trailer ceiling must be structurally strong enough to
support the weight of the S-2 evaporator(s) 43 kg (95 lb.) each or S-3
evaporator(s) 52 kg (115 lb.) each.
IMPORTANT: The ceiling must be flat and the mounting locations
correct for proper SPECTRUM evaporator installation. The foam
insulation in the ceiling must be removed from the evaporator mounting
area and aluminium spacers must be installed between the evaporator
mounting plate and trailer ceiling.
NOTE: If the trailer frame is other than aluminum, use mylar film
between aluminum spacer and frame.
• For ceiling mounting stud applications, weld a nut (same thread as
stud) onto a 44.45 mm (1.75 in.) hole saw and turn the nut onto the
mounting stud using a socket wrench (Detail I).
• For ceiling mounting bolt applications, weld a bolt (same thread as
tapped hole) onto a 44.45 mm (1.75 in.) hole saw and turn into the
tapped mounting hole using a socket wrench (Detail I).
• Alternative method is to remove the mounting studs or bolts and use a
hole saw with a standard pilot drill small enough to run up into the
threaded hole without damaging the threads. Reinstall mounting studs
or bolts.
Mounting Stud or Bolt Requirements
The mounting studs or bolts used to attach the evaporator(s) to the ceiling
must be 10.0 mm, (0.50 in., Grade 5, U.S. applications only), medium
carbon steel, 120000 PSI tensile strength, cadmium plate and dichromate
finish. Studs to extend below ceiling 38.0 mm (1.50 in.) to 50.1 mm (2.00
in.)
Evaporator Installation
1. Remove evaporator cover to access mounting holes.
NOTE: The installation kit provides both metric and imperial nuts
and washers. Be sure to use the correct ones for your application.
Mounting Stud Installations
2. Install the aluminum spacers onto the ceiling mounting studs and raise
the evaporator into position. Secure the evaporator onto the mounting
studs with flat washers and locking nuts (Detail II). Torque to 81.3
N•m (60 ft-lb).
Mounting Bolt Installations
3. Install the mounting bolts, lock washers (installer supplied) and flat
washers onto the evaporator and raise into position. Install the
aluminium spacers and secure the evaporator to the ceiling
(Detail III).
4. Install the second evaporator. Torque each evaporator’s mounting
hardware to 81.3 N•m (60 ft-lb).
5. A properly installed evaporator will slope slightly toward the drain
tubes to allow for water drainage (Detail IV).
NOTE: Two additional washers are included in the kit to help assist
sloping the evaporator towards the drain.
![Page 38: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/38.jpg)
37
Installation S-2 + S-2 or S-3 + S-3
![Page 39: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/39.jpg)
38
Host Tube Connections S-2 or S-3
1. Suction Line (s)
• SINGLE EVAPORATOR INSTALLATIONS - Install 7/8 in. x
7/8 in. coupling onto one suction tube of host unit. Fabricate 7/8
in. suction tube and install onto 7/8 in. coupling.
NOTE: The second suction tube remains capped.
• MULTIPLE EVAPORATOR INSTALLATIONS ONLY - Install
7/8 in. x 7/8 in. couplings onto each suction tube of host unit.
Fabricate 7/8 in. suction tubes and install onto each 7/8 in.
coupling.
2. Liquid Line - Install 3/8 in. x 1/2 in. coupling onto liquid tube of host
unit. Fabricate 1/2 in. liquid tube and install onto coupling.
3. Hot Gas Line - Install 5/8 in. x 5/8 in. coupling onto hot gas tube of
host unit. Fabricate 5/8 in. hot gas tube and install onto coupling.
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
NOTE: Ceiling trough shown, wall trough is similar.
Fittings Required
Item Description P/N
A 7/8 in. x 7/8 in. Coupling 553740
B 3/8 in. x 1/2 in. Coupling 552865
C 5/8 in. x 5/8 in. Coupling 556523
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction G58 G35
![Page 40: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/40.jpg)
39
Host Tube Connections S-2 or S-3
Single Evaporator
DE w/single or Parallel Evaporator(s)
Multiple Evaporators
![Page 41: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/41.jpg)
40
Host Tube Connections (Configuration X Only)
IMPORTANT: Configuration X installation requires two different size
suction tubes routed to the remote evaporators for proper operation:
• 1-1/8 in. suction tube from the host unit to the S3 + S3 remote
evaporators in Zone 2.
• 7/8 in. suction tube from the host unit to the S3 evaporator in
Zone 3.
• Due to the difficulty in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
1. Suction Line #1 - Install a 7/8 in. x 7/8 in. coupling onto the first
suction tube at the rear of the host unit. Fabricate a 7/8 in. tube, attach
onto coupling of suction tube and connect to 7/8 in. suction tube in
trough.
2. Suction Line #2 - Install a 7/8 x 1-1/8 in. coupling onto the second
suction tube at the rear of the host unit. Fabricate a 1-1/8 in. tube,
attach to coupling of suction tube and use 1-1/8 in. elbows to connect to
1-1/8 in. suction tube in trough.
3. Liquid Line - Install a 3/8 in. x 1/2 in. coupling onto liquid tube of the
host unit. Fabricate a 1/2 in. liquid tube and install onto the 1/2 in.
coupling.
4. Hot Gas - Install a 5/8 in. x 5/8 in. coupling onto the hot gas tube of the
host unit. Fabricate a 5/8 in. hot gas tube and install onto the 5/8 in.
coupling.
5. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
6. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required
Item Description P/N
A 7/8 in. x 7/8 in. Coupling 553740
B 7/8 in. x 1-1/8 in. Coupling 666022
C 1-1/8 in. x 1-1/8 in. Elbow 553682
D 3/8 in. x 1/2 in. Coupling 552865
E 5/8 in. x 5/8 in. Coupling 556523
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
Suction (1-1/8 in.) G66 G58
![Page 42: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/42.jpg)
41
Host Tube Connections (Configuration X Only)
![Page 43: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/43.jpg)
42
Host Tube Connections (Configuration Y Only)
IMPORTANT: Configuration Y installation requires two different size
suction tubes routed to the remote evaporators for proper operation:
• 7/8 in. suction tube from the host unit to the S3 remote
evaporator in Zone 2.
• 1-1/8 in. suction tube from the host unit to the S3 + S3
evaporators in Zone 3.
• Due to the difficulty in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
1. Suction Line #1 - Install a 7/8 x 1-1/8 in. coupling onto the first
suction tube at the rear of the host unit. Fabricate a 1-1/8 in. tube,
attach to coupling of suction tube and use 1-1/8 in. elbows to connect to
1-1/8 in. suction tube in trough.
2. Suction Line #2 - Install a 7/8 in. x 7/8 in. coupling onto the first
suction tube at the rear of the host unit. Fabricate a 7/8 in. tube, attach
onto coupling of suction tube and connect to 7/8 in. suction tube in
trough.
3. Liquid Line - Install a 3/8 in. x 1/2 in. coupling onto liquid tube of the
host unit. Fabricate a 1/2 in. liquid tube and install onto the 1/2 in.
coupling.
4. Hot Gas - Install a 5/8 in. x 5/8 in. coupling onto the hot gas tube of the
host unit. Fabricate a 5/8 in. hot gas tube and install onto the 5/8 in.
coupling.
5. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
6. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required
Item Description P/N
A 7/8 in. x 1-1/8 in. Coupling 666022
B 1-1/8 in. x 1-1/8 in. Elbow 553682
C 7/8 in. x 7/8 in. Coupling 553740
D 3/8 in. x 1/2 in. Coupling 552865
E 5/8 in. x 5/8 in. Coupling 556523
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
Suction (1-1/8 in.) G66 G58
![Page 44: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/44.jpg)
43
Host Tube Connections (Configuration Y Only)
![Page 45: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/45.jpg)
44
Host Tube Connections (Configuration Z Only)
IMPORTANT: Configuration Z installations require two 1-1/8 in.
suction tubes routed to the remote evaporators for proper operation:
• 1-1/8 in. suction tube from the host unit to the S3 + S3
evaporators in Zone 2.
• 1-1/8 in. suction tube from the host unit to the S3 + S3
evaporators in Zone 3.
• Due to the difficulty in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
1. Suction Line #1 - Install a 7/8 x 1-1/8 in. coupling onto the first
suction tube at the rear of the host unit. Fabricate a 1-1/8 in. tube,
attach to coupling of suction tube and use 1-1/8 in. elbows to connect
to 1-1/8 in. suction tube in trough.
2. Suction Line #2 - Install a 7/8 x 1-1/8 in. coupling onto the second
suction tube at the rear of the host unit. Fabricate a 1-1/8 in. tube,
attach to coupling of suction tube and use 1-1/8 in. elbows to connect
to 1-1/8 in. suction tube in trough.
3. Liquid Line - Install a 3/8 in. x 1/2 in. coupling onto liquid tube of the
host unit. Fabricate a 1/2 in. liquid tube and install onto the 1/2 in.
coupling.
4. Hot Gas - Install a 5/8 in. x 5/8 in. coupling onto the hot gas tube of
the host unit. Fabricate a 5/8 in. hot gas tube and install onto the 5/8
in. coupling.
5. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
6. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required
Item Description P/N
A 7/8 in. x 1-1/8 in. Coupling 666022
B 1-1/8 in. x 1-1/8 in. Elbow 553682
C 3/8 in. x 1/2 in. Coupling 552865
D 5/8 in. x 5/8 in. Coupling 556523
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (1-1/8 in.) G66 G58
![Page 46: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/46.jpg)
45
Host Tube Connections (Configuration Z Only)
![Page 47: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/47.jpg)
46
Evaporator Tube Connections S-2 or S-3
Zone 2 (Two Compartment Trailers)
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
1. Suction Line - Fabricate one 7/8 in. suction tube from host unit and
route in trough, install 7/8 in. x 7/8 in. elbow, attach 7/8 in. preformed
tube and connect to evaporator 7/8 in. fitting in Zone 2. Solder all
fittings.
2. Hot Gas Line - Fabricate a 5/8 in. hot gas tube from host unit and
route in trough, install 5/8 in. x 1/2 in. elbow, attach 1/2 in. preformed
tube and connect to evaporator 1/2 in. fitting in Zone 2. Solder all
fittings.
3. Liquid Line - Fabricate a 1/2 in. liquid tube from host unit and route
in trough, install 1/2 x 3/8 in. elbow, attach 3/8 in. preformed tube and
connect to evaporator 3/8 in. fitting in Zone 2. Solder all fittings
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for SINGLE Evaporator Installations
Item Description P/N
A 7/8 in. x 7/8 in. Elbow 553326
B 5/8 in. x 1/2 in. Elbow 665733
C 1/2 in. x 3/8 in. Elbow 554142
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction G58 G35
![Page 48: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/48.jpg)
47
Evaporator Tube Connections S-2 or S-3
Zone 2 (Two Compartment Trailers)
![Page 49: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/49.jpg)
48
Evaporator Tube Connections S-2 or S-3
Zones 2 & 3 (Three Compartment Trailers)
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
1. Suction Lines
• Fabricate two 7/8 in. suction tubes from host unit and route in
trough, install 7/8 in. x 7/8 in. elbows, attach one 7/8 in. preformed
tube to evaporator in Zone 2 and another to the evaporator in
Zone 3. Solder all fittings.
2. Hot Gas Lines
• Zone 2 - Fabricate a 5/8 in. hot gas tube from host unit and route in
trough, install 5/8 in. x 5/8 in. x 1/2 in. tee, attach a 1/2 in.
preformed tube and connect it to the evaporator in Zone 2.
• Zone 3 - From the tee, fabricate another 5/8 in. hot gas tube, attach
a 5/8 in. x 1/2 in. elbow and connect it to the 1/2 in. preformed tube
and to the evaporator in Zone 3. Solder all fittings.
3. Liquid Line
• Zone 2- Fabricate a 1/2 in. liquid tube from host unit and route in
trough, install 1/2 x 1/2 in. x 3/8 in. tee, attach 3/8 in. preformed
tube and connect it to the evaporator in Zone 2. Solder all fittings.
• Zone 3 - From the tee, fabricate another 1/2 in. liquid tube, attach
a 1/2 in. x 3/8 in. elbow and connect it to the 3/8 in. preformed tube
and to the evaporator in Zone 3. Solder all fittings.
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for SINGLE Evaporator Installations
Item Description P/N
A 7/8 in. x 7/8 in. Elbow 553326
B 5/8 in. x 1/2 in. Elbow 665733
C 1/2 in. x 3/8 in. Elbow 554142
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 7/8 in. x 7/8 in. Elbow 553326
B 5/8 in. x 5/8 in. x 1/2 in. Tee 660620
C 5/8 in. x 1/2 in. Elbow 665733
D 1/2 in. x 1/2 in. x 3/8 in. Tee 552181
E 1/2 in. x 3/8 in. Elbow 554142
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction G58 G35
![Page 50: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/50.jpg)
49
Evaporator Tube Connections S-2 or S-3
Zone 2 & 3 (Three Compartment Trailers)
![Page 51: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/51.jpg)
50
Evaporator Tube Connections S-2 + S-2 or S-3 + S-3
Zone 2 (Two Compartment Trailers)
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
NOTE: You must connect one suction line from the host to each
evaporator.
1. Suction Line #1- Fabricate a 7/8 in. suction tube from host unit and
route in trough, install 7/8 in. x 7/8 in. elbow, attach 7/8 in. preformed
tube and connect to the first evaporator 7/8 in. fitting in Zone 2. Solder
all fittings.
2. Suction Line #2 - Fabricate a second 7/8 in. suction tube from host
unit and route in trough, install 7/8 in. x 7/8 in. elbow, attach 7/8 in.
preformed tube and connect to the second evaporator 7/8 in. fitting in
Zone 2. Solder all fittings.
3. Hot Gas Line - Fabricate a 5/8 in. hot gas tube from host unit and
route in trough, install 5/8 in. x 5/8 in. elbow, fabricate a 5/8 in. tube,
connect to 5/8 in. x 1/2 in x 1/2 in tee and attach 1/2 in. preformed tube
and connect to evaporator 1/2 in. fitting in Zone 2. Solder all fittings.
4. Liquid Line - Fabricate a 1/2 in. liquid tube from host unit and route
in trough, install 1/2 in. x 1/2 in. elbow, fabricate a 1/2 in. tube, connect
to 1/2 in. a 3/8 in. x 3/8 in. tee, attach 3/8 in. preformed tubes and
connect to evaporator 3/8 in. fitting in Zone 2. Solder all fittings.
5. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
6. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 7/8 in. x 7/8 in. Elbow 553326
B 5/8 in. x 5/8 in. Elbow 552187
C 5/8 in. x 1/2 in. x 1/2 in. Tee 611044
D 1/2 in. x 1/2 Elbow 551483
E 1/2 in. x 3/8 in. x 3/8 in. Tee 611042
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction G58 G35
![Page 52: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/52.jpg)
51
Evaporator Tube Connections S-2 + S-2 or S-3 + S-3
Zone 2 (Two Compartment Trailers)
![Page 53: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/53.jpg)
52
Evaporator Tube Connections S-3 + S-3 (Configuration X Only)
ZONE 2
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
NOTE: Due to the difficultly in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
NOTE: You must connect one suction line from the host to each
evaporator.
1. Liquid Line - Fabricate 1/2 in. liquid tube from the host unit and route
in the trough:
• install 1/2 in. x 1/2 in. x 1/2 in. tee, fabricate a 1/2 in. tube and route
in the trough to Zone 3.
• from the 1/2 in. x 1/2 in. x 1/2 in. tee, fabricate a 1/2 in. tube, attach
to a 1/2 in. x 3/8 in. x 3/8 in. tee and 3/8 in. tube and connect to the
3/8 in. fitting of the 1st evaporator in Zone 2. Solder all fittings.
• from the 1/2 in. x 3/8 in. x 3/8 in. tee, fabricate a 3/8 in. tube and
connect to the 3/8 in. fitting of the 2nd evaporator in Zone 2. Solder
all fittings.
2. Suction Line ZONE 2 - Fabricate a 1-1/8 in. suction tube from the
host unit and route in the trough:
• install 1-1/8 in. x 7/8 in. x 7/8 in. tee, attach a 7/8 in. tube and
connect to the 7/8 in. fitting of the 2nd evaporator in Zone 2. Solder
all fittings.
• from the 1-1/8 in. x 7/8 in. x 7/8 in. tee, install a 7/8 in. 90 degree
elbow, attach a 7/8 in. tube and connect to the 7/8 in. fitting of the
1st evaporator in Zone 2. Solder all fittings.
3. Suction Line ZONE 3 - Fabricate a 7/8 in. suction tube from the host
unit and route in the trough to the Zone 3.
4. Hot Gas - Fabricate a 5/8 in. hot gas tube from the host unit and route
in the trough:
• install 5/8 in. x 5/8 in. x 5/8 in. tee, fabricate a 5/8 in. tube and route
in the trough to Zone 3.
• from the 5/8 in. x 5/8 in. x 5/8 in. tee, attach a 5/8 in. x 1/2 in. x 1/2
in. tee and 1/2 in. tube and connect it to the 1/2 in. fitting of the 1st
evaporator in Zone 2. Solder all fittings.
• From the 5/8 in. x 1/2 in. x 1/2 in. tee, attach a 1/2 in. tube and
connect it to the 1/2 in. fitting of the 2nd evaporator in
Zone 2. Solder all fittings.
5. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
6. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 1/2 in. x 1/2 in. x 1/2 in. Tee 552296
B 1/2 in. x 3/8 in. x 3/8 in. Tee 611042
C 1-1/8 in. x 7/8 in. x 7/8 in. Tee 558968
D 7/8 in. x 90° Street Elbow 553325
E 5/8 in. x 5/8 in. x 5/8 in. Tee 550904
F 5/8 in. x 1/2 in. x 1/2 in. Tee 611044
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
Suction (1-1/8 in.) G66 G58
![Page 54: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/54.jpg)
53
Evaporator Tube Connections S-3 + S-3 (Configuration X Only)
ZONE 2
![Page 55: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/55.jpg)
54
Evaporator Tube Connections S-3 (Configuration X Only)
ZONE 3
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
1. Suction Line - Fabricate a 7/8 in. suction tube from the host unit and
route in the trough, install 7/8 in. x 7/8 in. elbow, attach 7/8 in.
preformed tube and connect to the evaporator 7/8 in. fitting in Zone 3.
Solder all fittings.
2. Liquid Line - Fabricate a 1/2 in. liquid tube from the 1/2 in. tee from
(Zone 2) evaporator unit, route in the trough, install 1/2 in. x 3/8 in.
elbow, attach 3/8 in. preformed tubes and connect to the evaporator 3/8
in. fitting in Zone 3. Solder all fittings.
3. Hot Gas - Fabricate a 5/8 in. hot gas tube from the 5/8 in. tee from
(Zone 2) evaporate unit, route in the trough, install 5/8 in. x 1/2 in.
elbow, attach 1/2 in. preformed tube and connect to the evaporator 1/2
in. fitting in Zone 3. Solder all fittings.
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
NOTE: Ceiling trough shown, wall trough is similar.
Fittings Required for SINGLE Evaporator Installations
Item Description P/N
A 7/8 in. x 7/8 in. Elbow 553326
B 1/2 in. x 3/8 in. Elbow 554142
C 5/8 in. x 1/2 in. Elbow 665733
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
![Page 56: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/56.jpg)
55
Evaporator Tube Connections S-3 (Configuration X Only)
ZONE 3
![Page 57: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/57.jpg)
56
Evaporator Tube Connections S-3 + S-3 (Configuration Y Only)
ZONE 2
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
NOTE: Due to the difficultly in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
IMPORTANT: You must connect one suction line from the host to each
evaporator
1. Suction Line - Fabricate a 7/8 in. suction tube from the host unit and
route in the trough:
• install 7/8 in. x 7/8 in. elbow, attach a 7/8 in. tube and connect to the
7/8 in. fitting of the evaporator in Zone 2. Solder all fittings.
2. Hot Gas - Fabricate a 5/8 in. hot gas tube from the host unit and route
in the trough:
• install 5/8 in. x 5/8 in. x 5/8 in. tee, fabricate a 5/8 in. tube and route
in the trough to Zone 3.
• from the 5/8 in. x 5/8 in. x 5/8 in. tee, attach a 5/8 in. x 1/2 in. x 1/2
in. tee and 1/2 in. tube and connect it to the 1/2 in. fitting of the
evaporator in Zone 2. Solder all fittings.
3. Liquid Line - Fabricate 1/2 in. liquid tube from the host unit and route
in the trough:
• install 1/2 in. x 1/2 in. x 1/2 in. tee, fabricate a 1/2 in. tube and route
in the trough to Zone 3.
• from the 1/2 in. x 1/2 in. x 1/2 in. tee, fabricate a 1/2 in. tube, attach
to a 1/2 in. x 3/8 in. x 3/8 in. tee and 3/8 in. tube and connect to the
3/8 in. fitting of the evaporator in Zone 2. Solder all fittings.
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 7/8 in. x 7/8 in. Elbow 553326
B 5/8 in. x 5/8 in. x 5/8 in. Tee 550904
C 1/2 in. x 1/2 in. x 1/2 in. Tee 552296
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
![Page 58: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/58.jpg)
57
Evaporator Tube Connections S-3 + S-3 (Configuration Y Only)
ZONE 2
![Page 59: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/59.jpg)
58
Evaporator Tube Connections S-3 + S-3 (Configuration Y Only)
ZONE 3
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
NOTE: Due to the difficultly in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
IMPORTANT: You must connect one suction line from the host to each
evaporator.
1. Suction Line - Fabricate a 1-1/8 in. suction tube from the host unit
and route in the trough:
• install 1-1/8 in. x 7/8 in. x 7/8 in. tee, and use 7/8 in. elbows to
connect the 7/8 in. tubes to the 7/8 in. fittings of each evaporator in
Zone 3. Solder all fittings.
2. Hot Gas - Fabricate a 5/8 in. hot gas tube from the host unit and route
in the trough:
• install 5/8 in. x 5/8 in. x 5/8 in. tee, and connect the 5/8 in. tubes to
the 5/8 in. fittings of each evaporator in Zone 3. Solder all fittings.
3. Liquid Line - Fabricate 1/2 in. liquid tube from the host unit and route
in the trough:
• install 1/2 in. x 1/2 in. x 1/2 in. tee, and connect the 1/2 in. tubes to
1/2 in. fittings of each evaporator in Zone 3. Solder all fittings.
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 1-1/8 in. x 7/8 in. x 7/8 in. Tee 558968
B 7/8 in. x 7/8 in. Elbow 553326
C 5/8 in. x 5/8 in. x 5/8 in. Tee 550904
D 1/2 in. x 1/2 in. x 1/2 in. Tee 552296
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
Suction (1-1/8 in.) G66 G58
![Page 60: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/60.jpg)
59
Evaporator Tube Connections S-3 + S-3 (Configuration Y Only)
ZONE 3
![Page 61: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/61.jpg)
60
Evaporator Tube Connections S-3 + S-3 (Configuration Z Only)
ZONE 2
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
NOTE: Due to the difficultly in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
IMPORTANT: You must connect one suction line from the host to each
evaporator.
1. Liquid Line - Fabricate 1/2 in. liquid tube from the host unit and route
in the trough:
• install 1/2 in. x 1/2 in. x 1/2 in. tee, fabricate a 1/2 in. tube and route
in the trough to Zone 3.
• from the 1/2 in. x 1/2 in. x 1/2 in. tee, fabricate a 1/2 in. tube, attach
to a 1/2 in. x 3/8 in. x 3/8 in. tee and 3/8 in. tube and connect to the
3/8 in. fitting of the 1st evaporator in Zone 2. Solder all fittings.
• from the 1/2 in. x 3/8 in. x 3/8 in. tee, fabricate a 3/8 in. tube and
connect to the 3/8 in. fitting of the 2nd evaporator in Zone 2.Solder
all fittings.
2. Suction Line ZONE 2 - Fabricate a 1-1/8 in. suction tube from the
host unit and route in the trough:
• install 1-1/8 in. x 7/8 in. x 7/8 in. tee, attach a 7/8 in. tube and
connect to the 7/8 in. fitting of the 2nd evaporator in Zone 2. Solder
all fittings.
• from the 1-1/8 in. x 7/8 in. x 7/8 in. tee, install a 7/8 in. 90 degree
elbow, attach a 7/8 in. tube and connect to the 7/8 in. fitting of the
1st evaporator in Zone 2. Solder all fittings.
3. Suction Line ZONE 3 - Fabricate a 1-1/8 in. suction tube from the
host unit and route in the trough to the Zone 3.
4. Hot Gas - Fabricate a 5/8 in. hot gas tube from the host unit and route
in the trough:
• install 5/8 in. x 5/8 in. x 5/8 in. tee, fabricate a 5/8 in. tube and route
in the trough to Zone 3.
• from the 5/8 in. x 5/8 in. x 5/8 in. tee, attach a 5/8 in. x 1/2 in. x 1/2
in. tee and 1/2 in. tube and connect it to the 1/2 in. fitting of the 1st
evaporator in Zone 2. Solder all fittings.
• From the 5/8 in. x 1/2 in. x 1/2 in. tee, attach a 1/2 in. tube and
connect it to the 1/2 in. fitting of the 2nd evaporator in Zone 2.
Solder all fittings.
5. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
6. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 1/2 in. x 1/2 in. x 1/2 in. Tee 552296
B 1/2 in. x 3/8 in. x 3/8 in. Tee 611042
C 1-1/8 in. x 7/8 in. x 7/8 in. Tee 558968
D 7/8 in. x 90° Street Elbow 553325
E 5/8 in. x 5/8 in. x 5/8 in. Tee 550904
F 5/8 in. x 1/2 in. x 1/2 in. Tee 611044
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
Suction (1-1/8 in.) G66 G58
![Page 62: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/62.jpg)
61
Evaporator Tube Connections S-3 + S-3 (Configuration Z Only)
ZONE 2
![Page 63: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/63.jpg)
62
Evaporator Tube Connections S-3 + S-3 (Configuration Z Only)
ZONE 3
IMPORTANT: Clean all tubes and fittings prior to installation and
soldering.
NOTE: Due to the difficultly in bending and forming 1-1/8 in. copper
tubing, elbows and fittings may be used as shown.
NOTE: You must connect one suction line from the host to each
evaporator.
1. Suction Line - Fabricate a 1-1/8 in. suction tube from the host unit
and route in the trough:
• install 1-1/8 in. x 7/8 in. x 7/8 in. tee, and use 7/8 in. elbows to
connect the 7/8 in. tubes to the 7/8 in. fittings of each evaporator in
Zone 3. Solder all fittings.
2. Hot Gas - Fabricate a 5/8 in. hot gas tube from the host unit and route
in the trough:
• install 5/8 in. x 5/8 in. x 5/8 in. tee, and connect the 5/8 in. tubes to
the 5/8 in. fittings of each evaporator in Zone 3. Solder all fittings.
3. Liquid Line - Fabricate 1/2 in. liquid tube from the host unit and route
in the trough:
• install 1/2 in. x 1/2 in. x 1/2 in. tee, and connect the 1/2 in. tubes to
1/2 in. fittings of each evaporator in Zone 3. Solder all fittings.
4. Insulation should be added to all visible segments of suction and liquid
tubes not covered by the trailer trough cover. Hot gas tubes should be
covered 100%.
5. Secure all tubing with provided clamps. Maximum separation should
be 600 mm (24.00 in.) between clamps.
Fittings Required for MULTIPLE Evaporator Installations
Item Description P/N
A 1-1/8 in. x 7/8 in. x 7/8 in. Tee 558968
B 7/8 in. x 7/8 in. Elbow 553326
C 5/8 in. x 5/8 in. x 5/8 in. Tee 550904
D 1/2 in. x 1/2 in. x 1/2 in. Tee 552296
Tubing Clamps Required
Tube With Insulation W/O Insulation
Liquid G42 G14
Hot Gas G42 N/A
Suction (7/8 in.) G58 G35
Suction (1-1/8 in.) G66 G58
![Page 64: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/64.jpg)
63
Evaporator Tube Connections S-3 + S-3 (Configuration Z Only)
ZONE 3
![Page 65: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/65.jpg)
64
SB Host & Evaporator Wire Connections - Zone 2
ZONE 2 - SINGLE EVAPORATORS1. Connect ZONE 2-Sensor Harness (1E33293) at host unit (Detail I).
• Route harness into evaporator and connect to mating three
connectors (Detail II).
• DO NOT CUT THE SENSOR HARNESS! Loop excess harness
back on its self and secure with cable ties (Detail III).
2. Connect ZONE 2-Control Harness (1E33290) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (DH2,
SLS2, LLS2, HGS2 and SC2), attach terminal connectors and
connect to terminal block (Detail IV).
3. Connect ZONE 2-Fan 1 Harness (1E33414) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM21 and
CH21), attach terminal connectors and connect to terminal block
and ground stud (Detail IV).
4. Connect ZONE 2-Fan 2 Harness (2C25318) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM22 and
CH), attach terminal connectors and connect to terminal block and
ground stud (Detail IV).
S-3 EVAPORATORS ONLY5. Connect ZONE 2 -Fan 3 Harness (2C25319) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM23 and
CH), attach terminal connectors and connect to terminal block and
ground stud (Detail IV).
ZONE 2 - PARALLEL EVAPORATORS1. Connect ZONE 2-Sensor Harness (1E33293) at host unit (Detail I).
• Route harness into the first evaporator only and connect to mating
three connectors (Detail II).
NOTE: Although sensors are present in both evaporators, the harness is
connected to one evaporator only.
• DO NOT CUT THE SENSOR HARNESS! Loop excess harness
back on its self and secure with cable ties (Detail III).
2. Connect ZONE 2-Control Harness (1E33290) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (DH2,
SLS2, LLS2, HGS2 and SC2), attach terminal connectors and
connect to terminal block (Detail V).
3. Connect ZONE 2-Fan 1 Harness (1E33414) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (FM21
and CH21), attach terminal connectors and connect to terminal
block and ground stud (Detail V).
4. Connect ZONE 2-Fan 2 Harness (2C25318) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (FM22
and CH), attach terminal connectors and connect to terminal block
and ground stud (Detail V).
S-3 EVAPORATORS ONLY5. Connect ZONE 2 -Fan 3 Harness (2C25319) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (FM23
and CH), attach terminal connectors and connect to terminal block
and ground stud (Detail V).
6. Interconnect Harness (1E39857) is used with both S-2 and S-3
evaporators.
• Route harness into the first evaporator and connect wires (HGS,
SLS, LLS, FM1, FM2, FM3, DH, SC, CH, CH and CH) to terminal
block and ground studs (Detail V).
• Route harness into the second evaporator and connect wires (HGS,
SLS, LLS, FM1, FM2, FM3, DH, SC, CH, CH and CH) to terminal
block and ground studs (Detail V).
7. Secure all harnesses with adequate clamps or ties.
![Page 66: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/66.jpg)
65
SB Host & Evaporator Wire Connections - Zone 2
![Page 67: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/67.jpg)
66
SB Host & Evaporator Wire Connections - Zone 3
ZONE 3 - SINGLE EVAPORATORS
1. Connect ZONE 3-Sensor Harness (1E33292) at host unit (Detail I).
• Route harness into evaporator and connect to mating three
connectors (Detail II).
• DO NOT CUT THE SENSOR HARNESS! Loop excess harness
back on its self and secure with cable ties (Detail III).
2. Connect ZONE 3-Control Harness (1E33291) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (DH3,
SLS3, LLS3, HGS3 and SC3), attach terminal connectors and
connect to terminal block (Detail IV).
3. Connect ZONE 3-Fan 1 Harness (1E33417) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM31 and
CH31) attach terminal connectors and connect to terminal block
and ground stud (Detail IV).
4. Connect ZONE 3-Fan 2 Harness (2C25320) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM32 and
CH), attach terminal connectors and connect to terminal block and
ground stud (Detail IV).
S-3 EVAPORATORS ONLY
5. Connect ZONE 3 -Fan 3 Harness (2C25321) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM33 and
CH), attach terminal connectors and connect to terminal block and
ground stud (Detail IV).
ZONE 3 - PARALLEL EVAPORATORS1. Connect ZONE 3-Sensor Harness (1E33292) at host unit (Detail I).
• Route harness into the first evaporator only and connect to mating
three connectors (Detail II).
NOTE: Although sensors are present in both evaporators, the harness is
connected to one evaporator only.
• DO NOT CUT THE SENSOR HARNESS! Loop excess harness
back on its self and secure with cable ties (Detail III).
2. Connect ZONE 3-Control Harness (1E33291) at host unit (Detail I).
• Route harness into the first evaporator, cut to length, strip ends
(DH3, SLS3, LLS3, HGS3 and SC3), attach terminal connectors
and connect to terminal block (Detail V).
3. Connect ZONE 3-Fan 1 Harness (1E33417) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (FM31
and CH31) attach terminal connectors and connect to terminal
block and ground stud (Detail V).
4. Connect ZONE 3-Fan 2 Harness (2C25320) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (FM32
and CH), attach terminal connectors and connect to terminal block
and ground stud (Detail V).
S-3 EVAPORATORS ONLY5. Connect ZONE 3 -Fan 3 Harness (2C25321) at host unit (Detail I).
• Route harness into first evaporator, cut to length, strip ends (FM33
and CH), attach terminal connectors and connect to terminal block
and ground stud (Detail V).
6. Interconnect Harness (1E39857) is used with both S-2 and S-3
evaporators.
• Route wires (HGS, SLS, LLS, FM1, FM2, FM3, DH, SC, CH, CH,
and CH) into first evaporator, cut to length, strip ends, attach
terminal connectors and connect to terminal block and ground stud
(Detail V).
• Route wires (HGS, SLS, LLS, FM1, FM2, FM3, DH, SC, CH, CH,
and CH) into second evaporator, cut to length, strip ends, attach
terminal connectors and connect to terminal block and ground stud
(Detail V).
7. Secure all harnesses with adequate clamps or ties.
![Page 68: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/68.jpg)
67
SB Host & Evaporator Wire Connections - Zone 3
![Page 69: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/69.jpg)
68
DE Host & Evaporator Wire Connections - Zone 3
ZONE 3 - SINGLE EVAPORATOR
1. Connect ZONE 3-Sensor Harness (1E37605) at host unit (Detail I).
• Route harness into evaporator and connect to mating three
connectors (Detail II).
• DO NOT CUT THE SENSOR HARNESS! Loop excess harness
back on its self and secure with cable ties (Detail III).
2. Connect ZONE 3-Control Harness (1E33291) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (DH3,
SLS3, LLS3, HGS3 and SC3), attach terminal connectors and
connect to terminal block (Detail IV).
3. Connect ZONE 3-Fan 1 Harness (1E33417) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends
(FM31 and CH31) attach terminal connectors and connect to
terminal block and ground stud (Detail IV).
4. Connect ZONE 3-Fan 2 Harness (2C25320) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM32 and
CH), attach terminal connectors and connect to terminal block and
ground stud (Detail IV).
S-3 EVAPORATORS ONLY
5. Connect ZONE 3 -Fan 3 Harness (2C25321) at host unit (Detail I).
• Route harness into evaporator, cut to length, strip ends (FM33 and
CH), attach terminal connectors and connect to terminal block and
ground stud (Detail IV).
6. Secure all harnesses with adequate clamps or ties.
![Page 70: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/70.jpg)
69
DE Host & Evaporator Wire Connections - Zone 3
![Page 71: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/71.jpg)
70
Drain Hose Resistance Wire Installation Guide
All SPECTRUM Evaporators
IMPORTANT: The following information is provided as a guide to help
ensure the proper routing of the drain hose resistance wires. You should
supplement this guide with whatever other documentation is required for
your facility.
Drain Hose Resistance Wire Installation Guide
1. Remove the resistance wire from the evaporator drain tube and pull the
wire out straight.
2. Locate the evaporator defrost drain furthest from the trailer wall (i.e. in
the middle of the trailer), and measure 33.00 in. (838 mm) of the
resistance wire from the drain pan outlet (Detail I).
NOTE: 20.00 in. (508 mm) for S-2 evaporators.
3. Bend the resistance wire at this point and double it over (Detail II).
4. After doubling the resistance wire over (Step #3) take the excess wire
and insert it back into the evaporator drain tube (Detail III).
5. Insert the doubled over end of the resistance wire into the drain Tee or
90 degree connector (Detail IV) and then into the crossover drain tube
(Detail V).
NOTE: The use of either white or blue drain tubes is acceptable when
interconnecting multiple evaporators.
6. Attach the drain Tee or 90 degree connector to the evaporator drain
tube and push the connector on firmly to engage the O-ring (Detail VI).
7. Pull the resistance wire through the interconnecting drain tube as far as
possible and make sure it is not bunched up (Detail VII).
8. Insert the other resistance wire into the other drain Tee connector and as
shown (Detail VIII).
IMPORTANT: At no time should resistance wires from one side of the
drain pan overlap the resistance wires from the other side.
9. Attach the interconnecting drain tube to the opposite Tee connector by
pushing the Tee connector on firmly to engage the O-ring (Detail IX).
10. Attach the Tee connector to the evaporator drain tube by pushing the
Tee connector on firmly to engage the O-ring (Detail X).
11. Attach and route the evaporator drain tube over to the trailer wall drain.
Insert the resistance wire into the trailer wall drain and pull it as far
down the wall drain as possible (Detail XI).
IMPORTANT: Only one resistance wire should be installed in the
wall defrost drain tube. Only the resistance wire from the drain tube
closest to the wall should be installed in the trailer drain tube.
![Page 72: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/72.jpg)
71
Drain Hose Resistance Wire Installation Guide
All SPECTRUM Evaporators
![Page 73: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/73.jpg)
72
Drain Hose Installation
All SPECTRUM Evaporators
IMPORTANT: DO NOT CUT RESISTANCE WIRES!
NOTE: For proper drainage the drain hose must slope down
continuously from the evaporator to the wall drains with no kinks or
droop.
NOTE: See “Important Installation Notes” on pages 30- 33 and “Drain
Hose Resistance Wire Installation Guide” on pages 70- 71 for detailed
instructions on the proper installation procedures of the drain hose and
resistance wires.
NOTE: Make sure drain tubes are properly seated on tube fittings before
mounting to evaporator.
For S-2 and S-3 Applications
1. Route resistance wires from the evaporator through the plastic drain
hoses and insert the entire length of one resistance wire into each
wall drain tube (Detail I).
2. Connect the single drain hose to the wall drain tube using a short piece
of plastic drain hose and clamp as required (Detail I).
3. Replace drain t-fitting with elbow fitting. (Detail I).
For S-2 + S-2 and S-3 + S-3 Applications
4. Route resistance wires from the evaporator through the plastic drain
hoses and insert the entire length of one resistance wire into each
wall drain tubes (Detail II).
5. Connect each drain hose to each wall drain tube using a short piece of
plastic drain hose and clamps as required (Detail II).
For Wall Mounted Tube Applications (Detail III)
Insert the entire length of one resistance wire into each wall drain tube.
Connect the plastic drain hose from the evaporator.
For Wall Mounted Channel Applications (Detail IV)
Insert the entire length of one resistance wire into each plastic drain
hose. Feed the plastic drain hose down through the wall channel until it
exits the bottom of the trailer.
Optional Drain Hose Support (Detail V)
The use of the optional drain hose support bracket is recommended when
the evaporator is mounted sideways (transverse).
Front Drain Hose Applications (Detail VI)
Install drain t-fittings to allow drain tube to exit the front of the evaporator,
insert the entire length of one resistance wire into each drain hose, and
route hose out the front of the cover to the wall drain.
![Page 74: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/74.jpg)
73
Drain Hose Installation
All SPECTRUM Evaporators
![Page 75: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/75.jpg)
74
Leak Check, Evacuation and Charging Procedures
Set-up Unit
The SR-2 Multi-Temp microprocessor must be placed in the Evacuation
Test mode to evacuate and charge the unit. When the microprocessor is in
the Evacuation Test mode it opens all the normally closed solenoid valves
in the refrigeration system. This allows the refrigeration system to be
evacuated properly. Refer to the appropriate Diagnostic Manual for
complete information about the microprocessor. Use the following
procedure to set-up the unit and place the microprocessor in the Evacuation
Test mode:
1. Press the ON key to turn the unit on.
2. Before the unit starts, press the MENU key. The first screen in the
Main Menu (either the Language or Alarms Display) will appear.
3. Press the EXIT key and the unlabeled soft key at the same time, and
hold them down for 5 seconds to enter the Maintenance Menu. The first
Maintenance Menu feature will appear.
4. Press the NEXT (or BACK) key to scroll through the Maintenance
Menu features until the Evacuation Test mode appears.
5. Press the SELECT key to enter the Evacuation Test mode.
6. Connect a battery charger to the unit battery. The battery charge must
have an output of at least 15 amperes. This will maintain the charge
level of the battery during the time required to evacuate and charge the
unit. The Evacuation Test mode is used to open unit valves as required
for evacuation. Failure to connect a battery charger may result in the
battery voltage falling too low to reliably operate the microprocessor
and valves.
7. The microprocessor is now in the Evacuation Test mode. The
refrigeration system is set-up for leak checking, evacuation and
charging.
![Page 76: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/76.jpg)
75
Leak Check, Evacuation and Charging Procedures
Leak Check SystemNOTE: Refer to Diagnosing Thermo King Refrigeration Systems
(TK-5984-10) for leak detection procedures.
1. Connect leak test gas (R-404A) supply to center hose of gauge
manifold.
2. Attach gauge manifold hoses to suction and discharge service valves.
3. Open suction and discharge valves and pressurize system to 25 psi with
leak test gas. Monitor system pressure for one minute.
4. If pressure drops rapidly, there is a large leak. Do not continue until
large leak is identified and corrected. If pressure does not change or
drops slowly, add enough leak test gas to raise system up to bottle
pressure.
5. Check connections made during installation for leaks using electronic
leak detector.
6. Recover test gas to repair leaks. System must be vented while repairing
solder joint leaks. Pressurize system and check again after a leak has
been repaired.
7. If no leaks are found, recover test gas to 0 psi.
Evacuating the System
NOTE: The use of the Thermo King Evacuation Station (P/N 204-725 or
204-744) and Evacuation Station Operation and Field Application
Instruction (TK-40612-2) is required.
1. Be sure all refrigerant has been recovered from the unit.
2. Connect a vacuum pump and gauge manifold for three-point
evacuation to the suction service valve, discharge service valve, and
receiver tank outlet valve.
3. Verify proper operation of the Evacuation Station as shown in the
Evacuation Station Operation Manual (TK-40612).
4. Start the vacuum pump and mid-seat the suction service valve,
discharge service valve, and receiver tank outlet valve.
5. Install service valve stem caps with seals and tighten them. The valve
stems should remain capped while evacuating the unit.
6. Evacuate the unit to 500 microns, or the lowest achievable level
between 500 and 1,000 microns.
7. Continue to evacuate the unit for one additional hour after reaching 500
microns, or the lowest achievable level between 500 and 1,000
microns. This insures complete evacuation of the remote evaporators
and lines.
8. Close the Evacuation Station valve nearest the vacuum pump (V1) to
isolate the vacuum pump from the system. Turn the vacuum pump off.
9. Observe the micron gauge. The system pressure should remain below
2000 microns for 5 minutes. If the pressure does not hold, check for
leaks (if a leak is suspected) or continue evacuation (if system is not
dry).
10. Restart the vacuum pump, open the Evacuation Station valve nearest
the vacuum pump (V1) and repeat steps 6, 8, and 9 as required until
system pressure remains below 2000 microns for 5 minutes.
11. When system pressure remains below 2000 microns for 5 minutes,
restart the vacuum pump and open the Evacuation Station valve nearest
the vacuum pump (V1).
12. With the vacuum pump running, back seat the suction service valve.
Replace the valve cap, re-close the Evacuation Station valve nearest the
vacuum pump (V1), and stop the vacuum pump.
13. Close valve V4. The unit is ready to charge.
NOTE: Do not exercise the service valves with the unit in a deep vacuum
unless the vacuum pump is operating.
CAUTION: Do not evacuate the system until it is leak free. A unit
with less than full refrigerant charge should be leak checked and
all leaks must be repaired
![Page 77: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/77.jpg)
76
Leak Check, Evacuation and Charging Procedures
Charging the SystemNOTE: The unit must be left in the Evacuation Test.
1. Insure that all compartment bulkheads are open. Ceiling mounted
bulkheads should not be stored close to the evaporator outlets as this
will restrict airflow.
2. Before charging system, make sure the refrigerant lines from the gauge
manifold to the refrigerant supply bottle have been evacuated or
purged, the suction service valve is back seated, and the discharge
service valve and receiver tank outlet valve are still open.
3. Set the refrigerant supply bottle for liquid. Open the gauge manifold
hand valve and add a partial charge of R-404A. Add 14 lb (6.4 kg) to a
unit with one remote evaporator. Add 15 lb (6.8 kg) to a unit with two
remote evaporators. Do not add more than this. The remainder of
charge will be added through suction service valve while unit is
running.
4. Close the gauge manifold hand valve.
5. Back seat (close) the receiver tank outlet valve and discharge service
valve.
6. Exit the Evacuation Test by turning the unit Off and then back On.
7. Turn all zones On and set all zone set points for the lowest possible
temperature to insure that all zones run in Cool mode. Allow the unit to
start.
8. Front seat the suction service valve and allow the compressor to pump
down to 1 to 3 psi (7 to 21 kPa). Stop the unit.
9. Remove the evacuation manifold hoses from the receiver tank outlet
valve, the discharge service valve, and the suction service valve.
Replace and tighten the service port and valve stem caps on the
receiver tank outlet valve.
10. Attach the gauge manifold (with the refrigerant supply bottle still
connected) to the compressor. Attach the low side gauge to the suction
service valve. Mid-seat the suction service valve. Attach the high
pressure gauge on to the discharge service valve. Open the discharge
service valve to monitor the discharge pressure.
11. Turn the unit On, turn all zones On (with all zone set points set to the
lowest possible temperature), and allow the unit to start.
12. Observe the suction pressure and slowly open the gauge manifold hand
valve to allow liquid refrigerant to flow into the suction service valve.
Control the liquid flow so the suction pressure increases 20 to 25 psi
(138 to 172 kPa). Maintain a discharge pressure of 325 to 400 psi (2241
to 2758 kPa).
13. Add refrigerant until the ball in the receiver tank sight glass rises to the
middle of the sight glass, then close the gauge manifold hand valve.
Make sure the liquid level does not rise above the top of the sight glass.
14. Continue to operate the unit and monitor the sight glass until all
compartment temperatures are at or below 0 F (-18 C).
15. Check the position of the ball in the receiver tank sight glass. If the
liquid level has dropped, add liquid refrigerant until the level stabilizes
near the middle of the sight glass. Do not exceed the recommended
refrigerant charge for the unit model.
16. Close the hand valve on the refrigerant supply bottle.
17. Back seat the discharge service valve.
18. Open both hand valves on the gauge manifold.
19. Front seat the suction service valve and allow the compressor to pump
down to 1 to 3 psi (7 to 21 kPa). Stop the unit.
20. Remove the gauge line from the suction service valve and cap the
service port.
21. Remove the gauge line from the discharge service valve and cap the
service port.
22. Back seat the suction service valve and cap the valve stem.
23. Cap the valve stem on the discharge service valve.
24. Secure all the gauge lines to the gauge line anchors.
25. Record total unit charge on all serial plates.
![Page 78: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/78.jpg)
77
Leak Check, Evacuation and Charging Procedures
A. V-4
B. V-3
C. V-2
D. V-1
E. Thermistor
F. Two Stage Vacuum Pump
G. To AC Power
H. Micron Gauge
I. Correct Refrigerant Level
![Page 79: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/79.jpg)
78
Installing SPECTRUM Evaporator Covers
Installing Covers
1. Install FRONT COVER into support channel of evaporator.
Secure with screws.
2. Install BACK COVER into support lip of front cover.
Secure with screws.
![Page 80: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/80.jpg)
79
Installing SPECTRUM Evaporator Covers
![Page 81: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/81.jpg)
80
UNIT CHECK LIST
UNIT CHECK LIST
Visually inspect the unit for transit and handling damage. File claim
with delivery carrier.
Install the unit as outlined in the Thermo King Installation Manual.
If the unit has a separate fuel tank add 10 gallons of fuel to the tank.
BEFORE STARTING THE UNIT
Check battery and battery cable installation.
Inspect fuel line routing checking for rubbing, chaffing or laying on
hot surfaces.
Visually inspect the unit for the following: Loose or improperly
fitting bolts, brackets, hardware, hose connections and hose routing.
Inspect all wiring connections and routing.
Check defrost drain hoses and kazoos.
Check unit mounting hardware for tightness.
Check compressor and engine mounts.
Check compressor clutch if equipped.
Install refrigeration gauge manifold. (Multi-Temp units only)
Check engine oil level.
Check condenser and evaporator section for cleanliness and signs of
refrigerant leaks.
Check front bulkhead and air chute if equipped.
Check damper door, bushings and springs.
MULTI-TEMP UNITS (REMOTE EVAPORATORS)
Check evaporator(s) sections for cleanliness.
Leak test interconnecting tubing.
Check for damage, loose or missing bolts and hardware on remote
evaporator(s).
Check for proper installation of drain tubes, drain kazoos and drain
tube heater wires.
Check for properly routed refrigerant lines wiring harnesses for
remote evaporator(s). Check for properly routed harnesses for remote
controller.
Check for proper installation of remote evaporator guards if
equipped.
Check remote harness wiring plugs in the host evaporator.
Check wiring, connections, and terminals in the remote
evaporator(s).
Check compartment bulk head(s) for proper fit if equipped.
START AND RUN UNIT (ON MULTI-TEMP UNITS START ONLY THE HOST UNIT)
Check for proper oil pressure, coolant temperature, oil, fuel, or
coolant leaks.
Check alternator charge.
Cycle the unit and ensure the unit functions in the correct modes and
the mode indicators are working.
Set for continuous run with thermostat set point at 32 F (0 C) and run
the unit to 32 F (0 C).
![Page 82: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/82.jpg)
81
UNIT CHECK LIST (continued)
Observe and record refrigerant operating pressures in relation to
ambient and box temperatures.
Verify the readings above are correct for the conditions.
When box reaches 32 F (0 C) check calibration of thermostat,
thermometer and data logger.
Run unit for 30 minutes at 32 F (0 C). During this period check for
correct cycling.
Reset thermostat to 50 F (10 C).
Check throttling valve while in the heat cycle.
Check operation of Modulation system if equipped.
For Single Temp units perform a controlled check of the refrigerant
level. For Multi-temps check the charge per multi-temp unit
procedures.
MULTI-TEMP UNITS
Install the compartment bulk head(s) if equipped.
Check for correct rotation of remote evaporator fans.
Check for correct cycling and operation of remote evaporator fans.
ALL UNITS
Initiate and check defrost operation and termination. Check operation
and adjustment of damper door and remote fans. Each zone on
multi-temps must be checked for proper operation.
Set the unit for Cycle Sentry Operation.
Check for proper operation of all door switches.
Remove the compartment bulk head(s) if equipped.
Set the unit for continuous run. Continue to run the unit with the back
doors open, alternating between high speed cool and heat until at
least 6 hours (10 hours preferred) are shown on the engine run time
hour meter to ensure complete break in of the engine, time for the
belts and other moving parts to take out the initial tension and
adjustment.
ELECTRIC STANDBY OPERATIONAL CHECKS
Test AC electrical contacts and connections by connecting to AC
power and running.
Check for correct electric motor rotation.
Cycle thermostat and check for correct modes of operation.
Power source not available to test AC.
STOP UNIT
On Multi-temp units leak test interconnecting tubing.
Check and readjust all belt tensions using TK belt gauge 204-427.
Check for oil, fuel, coolant, refrigerant and exhaust leaks.
Check engine oil and coolant level.
Check entire unit for loosened hardware and fittings.
Check and adjust all skin, door and panels for correct alignment and
operation.
Complete the commissioning registration process.
Release unit.
![Page 83: Installation Manual - B](https://reader030.vdocuments.us/reader030/viewer/2022013018/61d114796dc18c21fb2b355a/html5/thumbnails/83.jpg)
Installation Manual - B
Providing equipment and services to manage controlled-temperature environments for food and other temperature-sensitive products, our Climate Control Technologies sector encompasses both transport and stationary refrigeration solutions. Our product brands include Thermo King®, a world leader in transport temperature control systems, and Hussmann®, a manufacturer of refrigeration and food merchandising equipment.
www.thermoking.com www.hussmann.com www.ingersollrand.com
©2008 Ingersoll-Rand Company Printed in U.S.A. on Recycled Paper
Trailer Edition (NAD) Multi-Temperature
SPECTRUMTM
Evaporator Systems (SR-2)TK 53509-2-IM (Rev. 5, 01/12)