![Page 1: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/1.jpg)
Installation instructionsfor contractors
VIESMANN
Vitoflame 300Type VHGBlue flame oil burnerwith oil pre-heatingfor Vitoladens 300-T, Vitola 200, type VX2A, andVitorondens 200-TRated output 18 to 33 kW
VITOFLAME 300
5724 105 UAE 5/2010 Dispose after installation.
![Page 2: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/2.jpg)
2
Please follow these safety instructions closely to prevent accidents and mate-rial losses.
Safety instructions explained
NoteDetails identified by the word "Note" con-tain additional information.
Target group
These instructions are exclusivelydesigned for qualified personnel.■ Work on gas appliances must only be
carried out by a qualified gas fitter.■ Work on electrical equipment must
only be carried out by a qualified elec-trician.
Regulations
Observe the following when working onthis system■ all legal instructions regarding the pre-
vention of accidents,■ all legal instructions regarding envi-
ronmental protection,■ the Code of Practice of relevant trade
associations,■ all current safety regulations as
defined by DIN, EN, DVGW, TRGI,TRF, VDE and all locally applicablestandards.
Working on the system
■ Isolate the system from the power sup-ply and check that it is no longer 'live',e.g. by removing a separate fuse or bymeans of a mains isolator.
■ Safeguard the system against unau-thorised reconnection.
■ When using gas as fuel, also close themain gas shut-off valve and safeguardagainst unauthorised reopening.
Safety instructions
5724
105
UA
E
![Page 3: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/3.jpg)
3
Installation sequenceFitting the burner to the boiler.............................................................................. 4Oil filter................................................................................................................. 5■ Oil filter for single line system........................................................................... 5■ Oil filter for two-line system............................................................................... 6Oil supply.............................................................................................................. 6Installing the oil supply as a single line system.................................................... 8■ Tank above oil burner pump............................................................................. 8■ Tank below oil burner pump.............................................................................. 9Installing the oil supply as a two-line system........................................................ 10■ Tank above oil burner pump............................................................................. 10■ Tank below oil burner pump.............................................................................. 11Electrical connections........................................................................................... 11Fitting the burner hood......................................................................................... 12Commissioning and adjustment........................................................................... 12
Index57
24 1
05 U
AE
![Page 4: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/4.jpg)
4
5.
6.
4.
3. 2.1.
7.
8.
4.
NoteSubject to the arrangement of the oil fil-ter, plug the oil supply fixing elementonto either the r.h. or l.h. side.
Fitting the burner to the boiler
5724
105
UA
E
![Page 5: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/5.jpg)
5
Oil filter for single line system
A Oil feed line from tankB To oil pump on burner
C From oil pump on burnerD Air vent valve
A Oil feed line from tankB To oil pump on burnerC From oil pump on burner
If installation is carried out according tothe single line system with a single linefuel oil filter R ⅜ (filter grade max. 40μm), we recommend the installation ofan automatic fuel oil air vent valve withintegral oil filter.
Oil filter57
24 1
05 U
AE
![Page 6: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/6.jpg)
6
Oil filter for two-line system
A Oil feed line from tankB To oil pump on burner
C From oil pump on burnerD Return to tank
Always install an R ⅜ fuel oil filter in theoil supply (filter grade max. 40 µm).
Oil supply
Please also observe the requirements of oil lines according to DIN 4755 or TRÖL(Technical Regulations for Oil Systems) [or local regulations] and any applicable reg-ulations concerning water pollution.If the oil supply needs to be converted from a two-line to a single line system, sizethe suction line diameter according to the table on page 8.For tanks below the oil burner pump, the difference in height H between the oil burnerpump and the foot valve inside the tank below must not be greater than:■ in single line systems: 4 m■ in two-line systems: 3.5 mGreater height differentials lead to noisy operation and pump wear (max. vacuum 0.3bar).
Oil filter (cont.)
5724
105
UA
E
![Page 7: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/7.jpg)
7
An oil feed pump is required if the suction head or maximum line run for tanks installedbelow the oil burner pump is greater than that shown in the following tables. Werecommend a stand-alone vacuum pump drive. If an oil pressure vessel drive isinstalled, the pressure at the inlet connection of the oil burner pump must not exceed1.5 bar, and the oil burner should be protected by an additional solenoid valve.A connecting cable for an external fuel valve is required to regulate the solenoid valve(accessory, see Vitotec pricelist).Solenoid valve line connection:
Accessory installation instructions
1. Size the oil line in accordance withthe following tables.
2. Install the oil line.
3. Disconnect the oil burner from the oilline before testing for leaks.
4. Check the oil line and oil filter forleaks using a leak testing kit (min. 5bar pressure).
NoteThe oil burner should not be connec-ted during these tests. All oil lines andjoints must be absolutely tight. Anyleaks in the suction line would draw inair, so that the oil spray would con-tinue to feed the burner.
5. Connect the oil burner to the oil line.
NoteIf an anti-lift valve is required to meet theregulations of your regional waterauthority and the tank fill level is higherthan the lowest point in the suction line,we recommend the installation of anelectrically operated anti-lift valve.
Oil supply (cont.)
5724
105
UA
E
![Page 8: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/8.jpg)
8
Tank above oil burner pumpH
A Foot valveB Fuel oil filter
C Fuel oil air vent
Suction head H Max. line run in m*1
at a suction line internal diameterin m 4 mm 5 mm*2 6 mm+4.0 100 100 100+3.5 95 100 100+3.0 89 100 100+2.5 83 100 100+2.0 77 100 100+1.5 71 100 100+1.0 64 100 100+0.5 58 100 100
NoteThe basis for sizing the pipework isDIN 4755, Appendix A, version 11.2004,or the values from the TRÖL (TechnicalRegulations for Oil Systems).
*1 A total pressure drop of 0.35 bar is assumed, based on fuel oil EL with 6.0 cSt (DIN51603-1) including 4 pipe bends, 1 shut-off valve, 1 foot valve and 1 fuel oil filter.
*2 Not in c.
Installing the oil supply as a single line system
5724
105
UA
E
![Page 9: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/9.jpg)
9
Tank below oil burner pump
H
A Foot valveB Fuel oil filter
C Fuel oil air vent
Suction head H Max. line run in m*1
at a suction line internal diameterin m 4 mm 5 mm*2 6 mm0 52 10 100–0.5 46 100 100–1.0 40 97 100–1.5 33 81 100–2.0 27 66 100–2.5 21 51 100–3.0 15 36 75–3.5 9 21 44–4.0 — 6 12
NoteThe basis for sizing the pipework isDIN 4755, Appendix A, version 11.2004,or the values from the TRÖL (TechnicalRegulations for Oil Systems).
*1 A total pressure drop of 0.35 bar is assumed, based on fuel oil EL with 6.0 cSt (DIN51603-1) including 4 pipe bends, 1 shut-off valve, 1 foot valve and 1 fuel oil filter.
*2 Not in c.
Installing the oil supply as a single line… (cont.)
5724
105
UA
E
![Page 10: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/10.jpg)
10
Two-line systems not in c.
Tank above oil burner pump
H
A Foot valve B Fuel oil filter
Suction head H Max. line run in m*1
at a suction line internal diameterin m 6 mm 8 mm 10 mm+4.0 33 100 100+3.5 31 98 100+3.0 29 91 100+2.5 27 85 100+2.0 25 79 100+1.5 23 72 100+1.0 21 66 100+0.5 19 60 100
NoteThe basis for sizing the pipework isDIN 4755, Appendix A, version 11.2004,or the values from the TRÖL (TechnicalRegulations for Oil Systems).
*1 A total pressure drop of 0.35 bar is assumed, based on fuel oil EL with 6.0 cSt (DIN51603-1) including 4 pipe bends, 1 shut-off valve, 1 foot valve and 1 fuel oil filter.
Installing the oil supply as a two-line system
5724
105
UA
E
![Page 11: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/11.jpg)
11
Tank below oil burner pump
H
A Foot valve B Fuel oil filter
Suction head H Max. line run in m*1
at a suction line internal diameterin m 6 mm 8 mm 10 mm0 17 53 100–0.5 15 47 100–1.0 13 41 99–1.5 11 34 84–2.0 9 28 68–2.5 7 22 53–3.0 5 15 37–3.5 — 9 22
NoteThe basis for sizing the pipework isDIN 4755, Appendix A, version 11.2004,or the values from the TRÖL (TechnicalRegulations for Oil Systems).
Electrical connections
NoteNever interchange connections "L 1" and"N" at the power supply terminals of thecontrol unit.*1 A total pressure drop of 0.35 bar is assumed, based on fuel oil EL with 6.0 cSt (DIN
51603-1) including 4 pipe bends, 1 shut-off valve, 1 foot valve and 1 fuel oil filter.
Installing the oil supply as a two-line system (cont.)
5724
105
UA
E
![Page 12: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/12.jpg)
12
NoteOnly for balanced flue operation:Before installing the burner hood, con-nect the inlet adaptor of the balancedflue accessory to the burner.
Accessory installation instruc-tions for balanced flue opera-tion.
41
3.
5.
2.
4.
1.
A Burner plug fA B Burner type plate
Commissioning and adjustment
Service instructions.
Fitting the burner hood
5724
105
UA
E
![Page 13: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/13.jpg)
13
57
24 1
05 U
AE
![Page 14: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/14.jpg)
14
5724
105
UA
E
![Page 15: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/15.jpg)
15
57
24 1
05 U
AE
![Page 16: Installation instructions Type VHG VIESMANN...Isolate the system from the power sup-ply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a mains](https://reader034.vdocuments.us/reader034/viewer/2022042322/5f0c43537e708231d43488a4/html5/thumbnails/16.jpg)
16
Viessmann Werke GmbH&Co KGD-35107 AllendorfTelephone: +49 6452 70-0Fax: +49 6452 70-2780www.viessmann.com 57
24 1
05 U
AE
Sub
ject
to te
chni
cal m
odifi
catio
ns.
Prin
ted
on e
nviro
nmen
tally
frie
ndly
,ch
lorin
e-fre
e bl
each
ed p
aper