installation instructions dcc series series 15...calculations published by the air conditioning...
TRANSCRIPT
© 2013, 2015-2017 5151 San Felipe St., Suite 500, Houston, TX 77056
www.daikinac.com
ATTENTION INSTALLING PERSONNEL:Prior to installation, thoroughly familiarize yourself withthis Installation Manual. Observe all safety warnings. Dur-ing installation or repair, caution is to be observed.
It is your responsibility to install the product safely and toeducate the customer on its safe use.
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
These installation instructions cover the outdoor installation ofsingle package heating and cooling units. See the SpecificationSheet applicable to your model for information regardingaccessories.
*NOTE: Please contact your distributor or our website for theapplicable Specification Sheet referred to in this manual.
Our continuing commitment to quality products may mean a change in specifications without notice.
DCC SERIESLIGHT COMMERCIAL PACKAGED HEATING AND COOLING UNIT15 to 25 TON
IndexReplacement Parts ................................................................ 2
Safety Instructions ................................................................ 2
General Information ............................................................. 2
Unit Location ........................................................................ 3
Clearances ............................................................................ 5
Roof Curb Post-Installation Checks ....................................... 6
Roof Top Duct Connections ................................................... 6
Rigging Details ...................................................................... 6
Electrical Wiring .................................................................... 7
Circulating Air and Filters ...................................................... 9
Condensate Drain Connection .............................................. 9
Startup, Adjustments, and Checks ...................................... 10
Airflow Adjustments ........................................................... 11
Motor Sheave Adjustments ................................................ 12
Maintenance ...................................................................... 13
Appendix A Blower Performance Data ................................ 15
Belt Drive - Standard ..................................................... 15
Belt Drive - High Static ................................................... 16
Appendix A Economizer Pressure Drop................................17
Appendix B Electrical Data .................................................. 18
Appendix C Unit Dimensions ............................................... 21
Appendix D Wiring Diagrams .............................................. 22
Wiring Diagrams for Models With DDC Controls.................. 29
Start-up Checklist ................................................................ 34
NOTE: 15 & 20 ton model shown in picture.25 ton model has 2 fans.
IOD-1003H
6/2017
INSTALLATION INSTRUCTIONS
2
THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
WARNING
REPLACEMENT PARTS
ORDERING PARTS
When reporting shortages or damages, or ordering repairparts, give the complete unit model and serial numbers asstamped on the unit’s nameplate.
Replacement parts for this appliance are available throughyour contractor or local distributor. For the location of yournearest distributor, consult the white business pages, theyellow page section of the local telephone book or contact:
EQUIPMENT SUPPORTDAIKIN NORTH AMERICA LLC
19001 KERMIER ROADWALLER, TEXAS 77484
855-770-5678
SAFETY INSTRUCTIONS
TO THE INSTALLER
Before installing this unit, please read this manual tofamiliarize yourself on the specific items which must beadhered to, including maximum external static pressure tounit, air temperature rise and minimum or maximum CFM.
Keep this literature in a safe place for future reference.
SHEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION.
CAUTION
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARNING
ONLY PERSONNEL THAT HAVE BEEN TRAINED TO INSTALL, ADJUST, SERVICE OR REPAIR (HEREINAFTER, “SERVICE”) THE EQUIPMENT SPECIFIED IN THIS MANUAL SHOULD SERVICE THE EQUIPMENT. THE MANUFACTURER WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU SERVICE THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT. IN ADDITION, IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE EQUIPMENT SPECIFIED IN THIS MANUAL, ONLY LICENSED PERSONNEL SHOULD SERVICE THE EQUIPMENT. IMPROPER INSTALLATION, ADJUSTMENT, SERVICING OR REPAIR OF THE EQUIPMENT SPECIFIED IN THIS MANUAL, OR ATTEMPTING TO INSTALL, ADJUST, SERVICE OR REPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
GENERAL INFORMATION
For complete information and installation instructions formodels with DDC controls, see manual DK-DDC-TGD-XXX
This unit is approved for outdoor installation ONLY. Rated perfor-mance is achieved after 72 hours of operation. Rated performanceis delivered at the specified airflow. See outdoor unit specifica-tion sheet for split system models or product specification sheetfor packaged and light commercial models. Specification sheetscan be found at www.daikinac.com for Daikin brand products.Within the website, please select the residential or commercialproducts menu and then select the submenu for the type of prod-uct to be installed, such as air conditioners or heat pumps, toaccess a list of product pages that each contain links to that model’sspecification sheet.
3
To assure that your unit operates safely and efficiently, it must beinstalled, operated, and maintained in accordance with these in-stallation and operating instructions, all local building codes andordinances.
EPA REGULATIONS
IMPORTANT: THE UNITED STATES ENVIRONMENTAL PROTECTION AGENCY (EPA)HAS ISSUED VARIOUS REGULATIONS REGARDING THE INTRODUCTION AND DISPOSAL
OF REFRIGERANTS IN THIS UNIT. FAILURE TO FOLLOW THESE REGULATIONS MAY
HARM THE ENVIRONMENT AND CAN LEAD TO THE IMPOSITION OF SUBSTANTIAL
FINES. BECAUSE REGULATIONS MAY VARY DUE TO PASSAGE OF NEW LAWS, WE
SUGGEST A CERTIFIED TECHNICIAN PERFORM ANY WORK DONE ON THIS UNIT.SHOULD YOU HAVE ANY QUESTIONS PLEASE CONTACT THE LOCAL OFFICE OF THE
EPA.
NATIONAL CODES
This product is designed and manufactured to permit installationin accordance with National Codes. It is the installer’s responsibil-ity to install the product in accordance with National Codes and/or prevailing local codes and regulations.
The heating and cooling capacities of the unit should be greaterthan or equal to the design heating and cooling loads of the areato be conditioned. The loads should be calculated by an approvedmethod or in accordance with ASHRAE Guide or Manual J - LoadCalculations published by the Air Conditioning Contractors ofAmerica.
Obtain from:
American National Standards Institute25 West 43rd Street, 4th Floor
New York, NY 10036
System design and installation should also, where applicable, fol-low information presented in accepted industry guides such as theASHRAE Handbooks. The manufacturer assumes no responsibilityfor equipment installed in violation of any code or regulation. Themechanical installation of the packaged roof top units consists ofmaking final connections between the unit and building services;supply and return duct connections; and drain connections (if re-quired). The internal systems of the unit are completely factory-installed and tested prior to shipment.
Units are generally installed on a steel roof mounting curb assem-bly which has been shipped to the job site for installation on theroof structure prior to the arrival of the unit. The model numbershown on the unit’s identification plate identifies the various com-ponents of the unit such as refrigeration tonnage, heating inputand voltage.
Carefully inspect the unit for damage. Any bolts or screws whichmay have loosened in transit must be re-tightened. In the eventof damage, the receiver should:
1. Make notation on delivery receipt of any visible damageto shipment or container.
2. Notify carrier promptly and request an inspection.3. In case of concealed damage, carrier should be notified as
soon as possible-preferably within 5 days.
4. File the claim with the following supporting documents:a. Original Bill of Lading, certified copy, or indemnity bond.b. Original paid freight bill or indemnity in lieu thereof.c. Original invoice or certified copy thereof, showing trade
and other discounts or reductions.d. Copy of the inspection report issued by carrier
representative at the time damage is reported to thecarrier. The carrier is responsible for making promptinspection of damage and for a thorough investigationof each claim. The distributor or manufacturer will notaccept claims from dealers for transportation damage.
NOTE: When inspecting the unit for transportation damage,remove all packaging materials. Recycle or dispose of the packagingmaterial according to local codes.
PRE-INSTALLATION CHECKS
Carefully read all instructions for the installation prior to installingunit. Ensure each step or procedure is understood and any specialconsiderations are taken into account before starting installation.Assemble all tools, hardware and supplies needed to complete theinstallation. Some items may need to be purchased locally.
UNIT LOCATION
TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.
WARNING
IMPORTANT NOTE: Remove wood shipping rails prior to installa-tion of the unit. See important note under Roof Curb InstallationOnly.
ALL INSTALLATIONS:
IMPORTANT NOTE: Unit should be energized 24 hours prior tocompressor start up to ensure crankcase heater has suffi-ciently warmed the compressors. Compressor damage mayoccur if this step is not followed.
NOTE: Appliance is shipped from factory for vertical ductapplication.Proper installation of the unit ensures trouble-free operation. Im-proper installation can result in problems ranging from noisyoperation to property or equipment damages, dangerous condi-tions that could result in injury or personal property damage. Givethis booklet to the user and explain it’s provisions. The user shouldretain these instructions for future reference.
• For proper operation and condensate drainage, the unitmust be mounted level.
• The flue outlet hood must be at least three feet above anyforced air inlet located within ten feet. The economizer/manual fresh air intake/motorized fresh air intake andcombustion air inlet mounted on the unit are not affectedby this restriction.
4
• Do not locate the unit in an area where the outdoor air(i.e. combustion air for the unit) will be frequentlycontaminated by compounds containing chlorine orfluorine. Common sources of such compounds includeswimming pool chemicals and chlorine bleaches, paintstripper, adhesives, paints, varnishes, sealers, waxes (whichare not yet dried) and solvents used during constructionand remodeling. Various commercial and industrialprocesses may also be sources of chlorine/fluorinecompounds.
• To avoid possible illness or death of the building occupants,do NOT locate outside air intake device (economizer,manual fresh air intake, motorized fresh air intake) tooclose to an exhaust outlet, gas vent termination, orplumbing vent outlet. For specific distances required,consult local codes.
• Allow minimum clearances from the enclosure for fireprotection, proper operation, and service access (see UnitClearances). These clearances must be permanentlymaintained.
• When the unit is heating, the temperature of the returnair entering the unit must be between 50°F and 100°F.
GROUND LEVEL INSTALLATIONS ONLY:
• When the unit is installed on the ground adjacent to thebuilding, a level concrete (or equal) base is recommended.Prepare a base that is 3” larger than the package unitfootprint and a minimum of 3” thick.
• The base should also be located where no runoff of waterfrom higher ground can collect in the unit.
ROOF TOP INSTALLATIONS ONLY:
• To avoid possible property damage or personal injury, theroof must have sufficient structural strength to carry theweight of the unit(s) and snow or water loads as requiredby local codes. Consult a structural engineer to determinethe weight capabilities of the roof.
• The unit may be installed directly on wood floors or onClass A, Class B, or Class C roof covering material.
• To avoid possible personal injury, a safe, flat surface forservice personnel should be provided.
• As indicated on the unit’s data plate, a minimum clearanceof 36” to any combustible material is required on the accessside of the unit. All combustible materials must be keptout of this area.
• This 36” clearance must also be maintained to insureproper combustion air flow. The combustion air intakemust not be blocked for any reason, including blockage bysnow.
• Adequate clearances from the unit to any adjacent publicwalkways, adjacent buildings, building openings oropenable windows must be maintained in accordance withNational Codes.
UNIT PRECAUTIONS
• Do not stand or walk on the unit.• Do not drill holes anywhere in panels or in the base frame
of the unit (except where indicated). Unit access panelsprovide structural support.
• Do not remove any access panels until unit has beeninstalled on roof curb or field supplied structure.
• Do not roll unit across finished roof without prior approvalof owner or architect.
• Do not skid or slide on any surface as this may damageunit base. The unit must be stored on a flat, level surface.Protect the condenser coil because it is easily damaged.
ROOF CURB INSTALLATIONS ONLY:
Before installing this unit...
IMPORTANT NOTE: This unit has been equipped with a shippingbrace under the compressor section that MUST BE REMOVED be-fore installing the unit on a roof curb.
Please follow the instructions below to remove brace.
WHEN UNIT IS SUSPENDED, BOARDS AND SHIPPING BRACE WILL DROP WHEN SCREWS ARE REMOVED. TO PREVENT PERSONAL INJURY, STAND CLEAR.REMOVE FORK HOLE BRACKETS, BOARDS AND SHIPPING BRACE FROM BOTTOMOF UNIT BEFORE PLACING UNIT ONTO CURB.
CAUTION
1. Remove wooden struts and shipping brace per installationinstructions. The struts are located in the fork holes andare used to protect the unit from damage while lifting withforks. The shipping brace is located underneath the unit(under compressors). Also remove the fork hole bracketsas shown in the following figure.
2. Locate and remove the end brackets as shown in thefollowing graphic.
5
LIFT OVER APPROXIMATECENTER OF UNIT
SPREADER BARSMUST BE USED WITHLIFTING STRAPS THATARE LESS THAN 16FEET LONG
REMOVE 2 BRACKETSON EACH END TOREMOVEWOODEN STRUTS
REMOVE 2 BRACKETSON EACH END TO
REMOVESHIPPING BRACE
3. Lift unit per the “Rigging Details” section of this manual,observing all warnings and cautions. When unit is lifted,boards and shipping brace will drop if screws have beenremoved. To avoid injury, STAND CLEAR.
4. Dispose of the boards and brace appropriately.
Curb installations must comply with local codes and should be donein accordance with the established guidelines of the National Roof-ing Contractors Association.
Proper unit installation requires that the roof curb be firmly andpermanently attached to the roof structure. Check for adequatefastening method prior to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and areshipped unassembled. Field assembly, squaring, leveling andmounting on the roof structure are the responsibility of the in-stalling contractor. All required hardware necessary for the as-sembly of the sheet metal curb is included in the curb accessory.
TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT.
WARNING
• Sufficient structural support must be determined prior tolocating and mounting the curb and package unit.
• Ductwork must be constructed using industry guidelines.The duct work must be placed into the roof curb beforemounting the package unit. Our full perimeter curbsinclude duct connection frames to be assembled with thecurb. Cantilevered type curbs are not available from thefactory.
• Curb insulation, cant strips, flashing and general roofingmaterial are furnished by the contractor.
The curbs must be supported on parallel sides by roof members.The roof members must not penetrate supply and return ductopening areas as damage to the unit might occur.
NOTE: The unit and curb accessories are designed to allow verticalduct installation before unit placement. Duct installation after unitplacement is not recommended.
ALL CURBS LOOK SIMILAR. TO AVOID INCORRECT CURB POSITIONING, CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY. INSTRUCTIONS MAY VARY IN CURB STYLES AND SUPERSEDES INFORMATION SHOWN.
CAUTION
See the manual shipped with the roof curb for assembly and in-stallation instructions.
CLEARANCES
36”; minimumroof overhang
48” Min.
65”Min.*
48”Min.
48”Min.*
*In situations that have multiple units, a 48” minimum clearance isrequired between the condenser coils.
UNIT CLEARANCES
Adequate clearance around the unit should be kept for safety, ser-vice, maintenance, and proper unit operation. A total clearanceof 75” around this unit is recommended to facilitate possible blowerassembly, shaft, wheel replacement, coil, heat exchanger, electricheat and gas furnace removal. This unit must not be installed be-neath any obstruction. This unit should be installed remote fromall building exhausts to inhibit ingestion of exhaust air into theunit’s fresh air intake.
6
InsulatedPanels
Roof Curb Installation
ROOF CURB POST-INSTALLATION CHECKSAfter installation, check the top of the curb, duct connection frameand duct flanges to make sure gasket has been applied properly.Gasket should be firmly applied to the top of the curb perimeter,duct flanges and any exposed duct connection frame. If gasket isloose, re-apply using strong weather resistant adhesive.
PROTRUSION
Inspect curb to ensure that none of the utility services (electric)routed through the curb protrude above the curb.
IF PROTRUSIONS EXIST, DO NO ATTEMPT TO SET UNIT ON CURB.
CAUTION
ROOF TOP DUCT CONNECTIONSInstall all duct connections on the unit before placing the unit onrooftop.
RIGGING DETAILS
WARNING
TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHTPOSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATELIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN ANADEQUATE CABLE SLING.
DO NOT LIFT UNITS TWO AT A TIME. PROVISIONS FOR FORKS HAVE BEEN INCLUDED IN THE UNIT BASE FRAME. MINIMUM FORK LENGTH IS 72” TO PREVENT DAMAGE TO THE UNIT.
CAUTION
Provisions for forks have been included in the unit base frame. Noother fork locations are approved.
WARNING
TO PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONALINJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVEDWHEN INSTALLING THE UNIT.
• Unit must be lifted by the four lifting holes located at thebase frame corners.
• Lifting cables should be attached to the unit with shackles.• The distance between the crane hook and the top of the
unit must not be less than 60”.• Two spreader bars must span over the unit to prevent
damage to the cabinet by the lift cables. Spreader barsmust be of sufficient length so that cables do not come incontact with the unit during transport. Remove woodstruts mounted beneath unit base frame before settingunit on roof curb. These struts are intended to protectunit base frame from fork lift damage. Removal isaccomplished by extracting the sheet metal retainers andpulling the struts through the base of the unit. Refer torigging label on the unit.
Important: If using bottom discharge with roof curb, ductworkshould be attached to the curb prior to installing the unit. Ductworkdimensions are shown in Roof Curb Installation Instructions.
Refer to the Roof Curb Installation Instructions for proper curbinstallation. Curbing must be installed in compliance with the Na-tional Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging unit,center of gravity will cause condenser end to be lower than supplyair end.
SEE CAUTION BELOW
7
WHEN UNIT IS SUSPENDED, BOARDS AND SHIPPING BRACE WILL DROP WHEN SCREWS ARE REMOVED. TO PREVENT PERSONAL INJURY, STAND CLEAR.REMOVE FORK HOLE BRACKETS, BOARDS AND SHIPPING BRACE FROM BOTTOMOF UNIT BEFORE PLACING UNIT ONTO CURB.
CAUTION
To assist in determining rigging requirements, unit weights areshown as follows:
COMPRESSOR 1
COMPRESSOR 2
CGEV
APO
RAT
OR
CO
ILS
A
B
C
X D
Y
CORNER & CENTER OF GRAVITY LOCATIONS
Corner Weight - A 590 644 626
Corner Weight - B 482 525 464
Corner Weight - C 492 504 501
Corner Weight - D 401 412 518
Unit Shipping Weight 2080 2202 2377
Unit Operating Weight 1965 2085 2109
X (Inches) 60" 58" 64.3"
Y (Inches) 40" 40" 41.3"
DATA15 Tons 20 Tons 25 Tons
DCC Weights(lbs)
NOTE: These weights are without accessories installed.
TO PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT, DO NOT FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED.
CAUTION
Bring condenser end of unit into alignment with the curb. Withcondenser end of the unit resting on curb member and using curbas a fulcrum, lower opposite end of the unit until entire unit isseated on the curb. When a rectangular cantilever curb is used,care should be taken to center the unit. Check for proper align-ment and orientation of supply and return openings with duct.
RIGGING REMOVAL
TO PREVENT DAMAGE TO THE UNIT, DO NOT ALLOW CRANE HOOKS AND SPREADER BARS TO REST ON THE ROOF OF THE UNIT.
CAUTION
Remove spreader bars, lifting cables and other rigging equipment.
ELECTRICAL WIRING
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
HIGH VOLTAGE! TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, DO NOT TAMPER WITH FACTORY WIRING. THE INTERNAL POWER AND CONTROL WIRING OF THESE UNITS ARE FACTORY-INSTALLED AND HAVE BEEN THOROUGHLY TESTED PRIOR TO SHIPMENT. CONTACT YOUR LOCAL REPRESENTATIVE IF ASSISTANCE IS REQUIRED.
WARNING
TO PREVENT DAMAGE TO THE WIRING, PROTECT WIRING FROM SHARP EDGES. FOLLOW NATIONAL ELECTRICAL CODE AND ALL LOCAL CODES AND ORDINANCES. DO NOT ROUTE WIRES THROUGH REMOVABLE ACCESS PANELS.
CAUTION
CONDUIT AND FITTINGS MUST BE WEATHER-TIGHT TO PREVENT WATER ENTRY INTO THE BUILDING.
CAUTION
For unit protection, use a fuse or HACR circuit breaker that is inexcess of the circuit ampacity, but less than or equal to the maxi-mum overcurrent protection device. DO NOT EXCEED THE MAXI-MUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE.
All line voltage connections must be made through weatherprooffittings. All exterior power supply and ground wiring must be inapproved weatherproof conduit.
The main power supply wiring to the unit and low voltage wiringto accessory controls must be done in accordance with these in-structions, the latest edition of the National Electrical Code (ANSI/NFPA 70), and all local codes and ordinances.
The main power supply shall be three-phase, three wire. The unitis factory wired for the voltage shown on the unit’s data plate.
8
NOTE: If supply voltage is 208V, all leads on primary oftransformer(s) must be moved from the 230V to the 208V tap.
Main power wiring should be sized for the minimum circuitampacity shown on the unit’s data plate. Size wires in accordancewith the ampacity tables in Article 310 of the National ElectricalCode. If long wires are required, it may be necessary to increasethe wire size to prevent excessive voltage drop. Wires should besized for a maximum of 3% voltage drop.
CAUTION
TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USEONLY COPPER CONDUCTORS.
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION
NOTE: A weather-tight disconnect switch, properly sized for theunit total load, must be field or factory installed. An external fieldsupplied disconnect may be mounted on the exterior panel.
Ensure the data plate is not covered by the field-supplieddisconnect switch.
• Some disconnect switches are not fused. Protect thepower leads at the point of distribution in accordance withthe unit’s data plate.
• The unit must be electrically grounded in accordance withlocal codes or, in the absence of local codes, with the latestedition of the National Electrical Code (ANSI-NFPA 70). Aground lug is provided for this purpose. Size groundingconductor in accordance with Table 250-95 of the NationalElectrical Code. Do not use the ground lug for connectinga neutral conductor.
• Connect power wiring to the electrical middle contactorwithin the main control box of power block, if equipped.
Low VoltageTerminal Strip
Thermostat wiringfor all unitsconnect to lowvoltage strip
GroundLug
Line voltage connectsto power block onCoolers and the 230vGas Packs
Line voltage connectsto middle contactoron 460v and 575vGas Packs(or power blockif equipped)
Power Block(Coolers &230V Gas PacksOnly)
Field wiring entersfrom this direction
POWER AND LOW VOLTAGE BLOCK LOCATIONS
Route fieldcontrol wiringthroughgrommet
Field connectionforcontrol wiringatterminal block
HIGH
Ground Lug
LOWField wiringenters fromthis direction
Fieldconnectionforline voltage
25 TON POWER AND LOW VOLTAGE BLOCK LOCATIONS
NOTE: Depending on the options installed, the location of the com-ponents may vary in some models.
9
FAILURE OF UNIT DUE TO OPERATION ON IMPROPER LINE VOLTAGE OR WITH EXCESSIVE PHASE UNBALANCE CONSTITUTES PRODUCT ABUSE AND MAY CAUSE SEVERE DAMAGE TO THE UNIT ELECTRICAL COMPONENTS.
WARNING
Areas Without Convenience Outlet
It is recommended that an independent 115V power source bebrought to the vicinity of the roof top unit for portable lights andtools used by the service mechanic.
NOTE: Refer to local codes for requirements. These outlets canalso be factory installed.
UNITS INSTALLED ON ROOF TOPS
Main power and low voltage wiring may enter the unit throughthe side or through the roof curb. Install conduit connectors at thedesired entrance locations. External connectors must be weath-erproof. All holes in the unit base must be sealed (including thosearound conduit nuts) to prevent water leakage into building. Allrequired conduit and fittings are to be field supplied.
Supply voltage to roof top unit must not vary by more than 10% ofthe value indicated on the unit’s data plate. Phase voltage unbal-ance must not exceed 2%. Contact your local power company forcorrection of improper voltage or phase unbalance.
ELECTRICAL ENTRANCE LOCATIONS
Unit is equipped with Single Point Power Block and Low VoltageBlock.
LOW VOLTAGE CONTROL WIRING
1. A 24V thermostat must be installed for unit operation. Itmay be purchased with the unit or field -supplied.Thermostats may be programmable or electromechanicalas required.
2. Locate thermostat or remote sensor in the conditionedspace where it will sense average temperature. Do notlocate the device where it may be directly exposed tosupply air, sunlight or other sources of heat. Followinstallation instructions packaged with the thermostat.
3. Use #18 AWG wire for 24V control wiring runs notexceeding 75 feet. Use #16 AWG wire for 24V control wiringruns not exceeding 125 feet. Use #14 AWG wire for 24Vcontrol wiring runs not exceeding 200 feet. Low voltagewiring may be National Electrical Code (NEC) Class 2 wherepermitted by local codes.
4. Route thermostat wires from sub-base terminals to theunit. Control wiring should enter through the duct panel(dimple marks entrance location). Connect thermostat andany accessory wiring to low voltage terminal block TB1 inthe main control box.
NOTE: Field-supplied conduit may need to be installed dependingon unit/curb configuration. Use #18 AWG solid conductor wirewhenever connecting thermostat wires to terminals on sub-base.DO NOT use larger than #18 AWG wire. A transition to #18 AWGwire may be required before entering thermostat sub-base.
NOTE: Refer to unit wiring diagrams for thermostat hookups.
CIRCULATING AIR AND FILTERS
DUCTWORK
The supply duct from the unit through a wall may be installed with-out clearance. However, minimum unit clearances must be main-tained (see “Clearances” section). The supply duct should be pro-vided with an access panel large enough to inspect the air cham-ber downstream of the heat exchanger. A cover should be tightlyattached to prevent air leaks.
Ductwork dimensions are shown in the roof curb installationmanual.
If desired, supply and return duct connections to the unit may bemade with flexible connections to reduce possible unit operatingsound transmission.
CONDENSATE DRAIN CONNECTION
CONDENSATE DRAIN CONNECTION
A 1” female NPT drain connection is supplied on the end of thecondensate pan, with an alternative connection on the bottom ofthe pan. An external trap must be installed for proper condensatedrainage
STANDARDSIDE DRAIN
DRAIN PLUG(FACTORY-INSTALLED)
Drain Pan (Side View)
10
NOTE: Trap should be deep enough to offset maximumunit static difference. A minimum 4” trap is recommended.
Drain Plug Roof Curb
See NOTE
Base Rail
Open Vent 2” Min
DRAIN CONNECTION
Install condensate drain trap as shown. Use 1” drain line and fit-tings or larger. Do not operate without trap.
HORIZONTAL DRAIN
Drainage of condensate directly onto the roof may be acceptable;refer to local code. It is recommended that a small drip pad ofeither stone, mortar, wood or metal be provided to prevent anypossible damage to the roof.
CLEANING
Due to the fact that drain pans in any air conditioning unitwill have some moisture in them, algae and fungus will growdue to airborne bacteria and spores. Periodic cleaning isnecessary to prevent this build-up from plugging the drain.
STARTUP, ADJUSTMENTS, AND CHECKS
HIGH VOLTAGE!
OND THE FRAME OF THIS UNIT TO THE BUILDING ELECTRICAL GROUND BY USE OF THE GROUNDING TERMINAL PROVIDED OR OTHER ACCEPTABLE MEANS. DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT.
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK, B
WARNING
PRE-STARTUP INSTRUCTIONS
TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY, DO NOT START THE UNIT UNTIL ALL NECESSARY PRE-CHECKS AND TESTS HAVE BEEN PERFORMED.
CAUTION
Prior to the beginning of Startup, Adjustments, and Checks proce-dures, the following steps should be completed in the building.
MOVING MACHINERY HAZARD!TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH, DISCONNECT POWER TO THE UNIT AND PADLOCK IN THE “OFF” POSITION BEFORE SERVICNG FANS.
WARNING
HEATING STARTUP
On new installations, or if a major component has been replaced,the operation of the unit must be checked.
Check unit operation as outlined in the following instructions. Ifany sparking, odors, or unusual sounds are encountered, shut offelectrical power and recheck for wiring errors, or obstructions inor near the blower motors. Duct covers must be removed beforeoperating unit.
The Startup, Adjustments, and Checks procedure provides a step-by-step sequence which, if followed, will assure the proper startupof the equipment in the minimum amount of time. Air balancingof duct system is not considered part of this procedure. However,it is an important phase of any air conditioning system startup andshould be performed upon completion of the Startup, Adjustments,and Checks procedure. The Startup, Adjustments, and Checks pro-cedure at outside ambients below 55°F should be limited to a readi-ness check of the refrigeration system with the required final checkand calibration left to be completed when the outside ambientrises above 55°F.
TEMPORARY HEATING OR COOLING
If the unit is to be used for temporary heating or cooling, a “Startup,Adjustments, and Checks” must first be performed in accordancewith this manual. After the machines are used for temporary heat-ing or cooling, inspect the coils, fans, and motors for unaccept-able levels of construction dust and dirt and install new filters.
CONTRACTOR RESPONSIBILITY
The installing contractor must be certain that:
• All supply and return air ductwork is in place, properlysealed and corresponds with installation instructions.
• All thermostats are mounted and wired in accordancewith installation instructions.
• All electric power, all gas, hot water or steam lineconnections, and the condensate drain installation havebeen made to each unit on the job. These main supplylines must be functional and capable of operating all unitssimultaneously.
• All filters are in place.
ROOF CURB INSTALLATION CHECK
Inspect the roof curb for correct installation. The unit and curbassembly should be level. Inspect the flashing of the roof mount-ing curb to the roof, especially at the corners, for good workman-ship. Also check for leaks around gaskets. Note any deficiencies ina separate report and forward to the contractor.
11
OBSTRUCTIONS, FAN CLEARANCE AND WIRING
Remove any extraneous construction and shipping materials thatmay be found during this procedure. Rotate all fans manually tocheck for proper clearances and that they rotate freely. Check forbolts and screws that may have jarred loose during shipment tothe job site. Retighten if necessary. Re-tighten all electrical con-nections.
FIELD DUCT CONNECTIONS
Verify that all duct connections are tight and that there is no airbypass between supply and return.
FILTER SECTION CHECK
Remove filter section access panels and check that filters are prop-erly installed. Note airflow arrows on filter frames.
PRE-STARTUP PRECAUTIONS
It is important to your safety that the unit has been properlygrounded during installation. Check ground lug connection in maincontrol box for tightness prior to closing circuit breaker or discon-nect switch. Verify that supply voltage on line side of disconnectagrees with voltage on unit identification plate and is within theutilization voltage range as indicated in Appendix C Electrical Data.
System Voltage - That nominal voltage value assigned to a circuitor system for the purpose of designating its voltage class.
Nameplate Voltage - That voltage assigned to a piece of equip-ment for the purpose of designating its voltage class and for thepurpose of defining the minimum and maximum voltage at whichthe equipment will operate.
Utilization Voltage - The voltage of the line terminals of the equip-ment at which the equipment must give fully satisfactory perfor-mance. Once it is established that supply voltage will be main-tained within the utilization range under all system conditions,check and calculate if an unbalanced condition exists betweenphases. Calculate percent voltage unbalance as follows:
Three Phase Models Only
3) PERCENT VOLTAGE UNBALANCE
2) MAXIMUM VOLTAGE DEVIATIONSFROM AVERAGE VOLTAGE
1) AVERAGE VOLTAGE
HOW TO USE THE FORMULA:EXAMPLE: With voltage of 220, 216, and 2131) Average Voltage = 220+216+213=649 / 3 = 2162) Maximum Voltage Deviations from Average Voltage = 220 - 216 = 4
3) Percent Voltage Unbalance = 100 x = = 1.8%
Percent voltage unbalance MUST NOT exceed 2%.
4216
400216
= 100 X
AIRFLOW ADJUSTMENTSThe drive on the supply fan is typically set in the middle of theRPM range. The drive motor sheave pitch diameter is field adjust-able for the required airflow. Refer to the following “DriveAdjustments” section.
When the final adjustments are complete, the current draw of themotor should be checked and compared to the full load current
rating of the motor. The amperage must not exceed the servicefactor stamped on the motor nameplate. The total airflow mustnot be less than that required for operation of the electric heatersor the furnace.
If an economizer is installed, check the unit operating balance withthe economizer at full outside air and at minimum outside air. Uponcompletion of the air flow balancing, we recommend replacingthe variable pitched motor sheave with a properly-sized fixedsheave. A matching fixed sheave will provide longer belt and bear-ing life and vibration free operation. Initially, it is best to have avariable pitched motor sheave for the purpose of airflow balanc-ing, but once the balance has been achieved, fixed sheaves main-tain alignment and minimize vibration more effectively.
NOTE: Airflow setting below 300 CFM/ton is not recommended,as evaporator freezing or poor unit performance is possible. For2-speed models, airflow adjustments must be made with theevaporator fan motor operating at high speed (in 2nd stage cool-ing or in heat mode). 2-Speed models have a “V” in 11th digit ofthe model number (e.g. DCC300XXX3V).
SET EVAPORATOR FAN RPMActual RPM’s must be set and verified with a tachometer or strobelight. Refer to Appendices A and B for basic unit fan RPM. Referalso to “Airflow” section of this manual. With disconnect switchopen, disconnect thermostat wires from terminals Y and W. Thiswill prevent heating and mechanical cooling from coming on. Placea jumper wire across terminals R and G at TB1 terminal block. Closedisconnect switch; evaporator fan motor will operate so RPM canbe checked.
EVAPORATOR FAN ROTATION CHECK (THREE PHASE MODELS ONLY)Check that fan rotates clockwise when viewed from the drive sideof unit and in accordance with rotation arrow shown on blowerhousing. If it does not, reverse the two incoming power cables atSingle Point Power Block. In this case, repeat bearing check.
Do not attempt to change load side wiring. Internal wiring assuresall motors and compressors will rotate in correct direction onceevaporator fan motor rotation check has been made.
ELECTRICAL INPUT CHECK
Make preliminary check of evaporator fan ampere draw and verifythat motor nameplate amps are not exceeded. A final check ofamp draw should be made upon completion of air balancing ofthe duct system (see Appendix C).
BELT DRIVE MODELS ONLYBEARING CHECK
Prior to energizing any fans, check and make sure that all setscrewsare tight so that bearings are properly secured to shafts.
TENSION AND ALIGNMENT ADJUSTMENT
Correct belt tension is very important to the life of your belt. Tooloose a belt will shorten its life; too tight, premature motor andbearing failure will occur. Check you belt drive for adequate “run-in” belt tension by measuring the force required to deflect the
12
belt at the midpoint of the span length. Belt tension force can bemeasured using a belt tension gauge, available through most beltdrive manufacturers.
SPAN LENGTH t*DEFLECTION
FORCE
h
C
dH
D
*Apply force to the center of the span.
t = Span length, inchesC = Center distance, inchesD = Larger sheave diameter, inchesd = Smaller sheave diameter, inchesh = Deflection height, inches
BELT DRIVE Used New15 Ton B, BX Standard 4.3 to 5.5 5.5 ± .5 8.2 ± .5 1/4 ± 1/1620 Ton25 Ton
B, BA Standard 4.3 to 5.5 5.5 ± .5 8.2 ± .5 1/4 ± 1/16
MODELTYPE DEFLECTION
FORCE (lbs)SHEAVE
DIAMETER (in)
DEFLECTION (in)
DRIVE BELT TENSION ADJUSTMENT
RECOMMENDED POUNDS OF FORCE PER BELT
New V-belts will drop rapidly during the first few hours of use.Check tension frequently during the first 24 hours of operation.Tension should fall between the minimum and maximum force. Todetermine the deflection distance from a normal position, mea-sure the distance from sheave to sheave using a straightedge or acord. This is your reference line. On multiple belt drives, an adja-cent undeflected belt can be used as a reference.
MOTOR SHEAVE ADJUSTMENTS
VL, VM & 2VP VARIABLE PITCH KEY TYPE MOTOR SHEAVES
The driving and driven motor sheaves should be in alignment witheach other and the shafts parallel.
VL & VM SHEAVES ADJUSTMENT
1. Loosen set screw “B” using a 5/32" Allen key.2. Making half or full turns from closed position, adjust
sheave pitch diameter for desired speed. DO NOT OPENMORE THAN SIX FULL TURNS.
3. Tighten set screw “B” securely over flat.4. Carefully put on belts and adjust belt tension. DO NOT
FORCE BELTS OVER GROOVES.5. Ensure all keys are in place and the set screws tight before
starting drive. Recheck set screws and belt tension after24 hours service.
NOTE: Future adjustments should be made by loosening the belttension and increasing or decreasing the pitch diameter of thesheave by half or full turns as required. Readjust belt tension beforestarting drive.
C
B
VL & VM
NOTE: Do not operate sheave with flange projecting beyond thehub end.
REFRIGERATION SYSTEM
The unit is equipped with a thermal expansion valve as a metering device.
Ensure the hold-down bolts on the compressor are secure and havenot vibrated loose during shipment. Check that vibration grom-mets have been installed. Visually check all piping for damage andleaks; repair if necessary. The entire system has been factorycharged and tested, making it unnecessary to field charge. Factorycharges are shown on the unit’s namelate. To confirm charge lev-els or, if a leak occurs and charge needs to be added to the system,it is recommended to evacuate the system and recharge refriger-ant to unit nameplate specifications. This unit has been rated inthe cooling mode at the AHRI rated conditions of: Indoor (80°db /67°wb) and outdoor (95°db). While operating at this condition,the subcooling should range from 12° to 15° F for each refrigera-tion circuit, for 15 and 20 ton models. Subcooling for 25 ton mod-els should be from 16° to 19° F for circuit 1, and from 12° to 15° Ffor circuit 2.
START-UP PROCEDURE AND CHECKLIST
Begin with power turned off at all disconnects.
1. Turn thermostat system switch to “Cool,” and fan switchto “Auto” and turn temperature setting as high as it willgo.
2. Inspect all registers and set them to the normal openposition.
3. Turn on the electrical supply at the disconnect.
4. Turn the fan switch to the “ON” position. The blowershould operate after a 7-second delay.
5. Turn the fan switch to “Auto” position. The blower shouldstop after a 65 second delay.
13
6. Slowly lower the cooling temperature until first stage COOL(LOW COOL) starts. The blower, both fans, and first stagecompressor should now be operating. Allow the unit torun 10 minutes, make sure cool air is being supplied bythe unit.
7. Lower the cooling temperature further until second stageCOOL (HIGH COOL) starts. The blower, both fans, and bothcompressors should now be operating. Allow the unit torun 10 minutes, make sure cool air is being supplied bythe unit.
8. Turn the temperature setting to the highest position,stopping the unit. The indoor blower will continue to runfor 65 seconds.
9. Turn the thermostat system switch to “OFF” anddisconnect all power when servicing the unit.
START-UP PROCEDURE AND CHECKLIST FOR 2 SPEED MODELS:
Models with a V in the 11th position of the model number.
For 2 speed models, the indoor blower will operate on low speedwhen in “Fan Only” mode or while in first stage “Cooling” mode.Unit will operate on high speed in “Heating” mode and while insecond stage “Cooling” mode.
The start-up procedure is the same as for “Air Conditioning Start-up Procedure” with the understanding that in Step 6, the indoorblower will run at low speed (~1175 motor rpm) and in Step 7, theindoor blower will operate at high speed (~1775 motor rpm).
LOW AMBIENT COOLING NOTES:
For 15 and 20 ton models: While in the Cooling Mode, to preventfrost from forming on the evaporator while the unit is operating inoutdoor temperatures of 65°F or lower, it is recommended that alow ambient kit (LAKT-03) is used. This is strongly recommendedfor 2 Speed models due to the lower airflow while in the firststage of cooling. To further protect the compressor from damageduring low ambient conditions, a Freezestat Kit (FSK01) can beadded that turns the compressor off when the evaporatortemperature drops too low.
For 25 ton models: The 25 ton units are equipped with a controlthat shuts off one condenser fan when the outdoor temperatureis 44° F or below. This is to assist low ambient cooling down to24°. An optional Low Ambient kit, LAKT05, is required below 24°which will enable reliable cooling to occur to a minimum ambienttemperature of zero °F.
It is recommended that all single speed models be equipped witha Freezestat kit, FSK02A, to provide extra protection for thecompressor from damage that may occur during periods of lowambient operation. For 25 ton 2 Speed Models only, the freezestatcomes as standard equipment.
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
FINAL SYSTEM CHECKS
10. Check to see if all supply and return air grilles are adjustedand the air distribution system is balanced for the bestcompromise between heating and cooling.
11. Check for air leaks in the ductwork. See Sections on AirFlow Adjustments.
12. Make sure the unit is free of “rattles”, and the tubing inthe unit is free from excessive vibration. Also make suretubes or lines are not rubbing against each other or sheetmetal surfaces or edges. If so, correct the trouble.
13. Set the thermostat at the appropriate setting for coolingand heating or automatic change over for normal use.
14. Be sure the Owner is instructed on the unit operation, filter,servicing, correct thermostat operation, etc.
MAINTENANCE
HIGH VOLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
TO PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE, REFER TO THIS MANUAL. FOR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
WARNING
14
SHEET METAL PARTS, SCREWS, CLIPS AND SIMILAR ITEMS INHERENTLY HAVE SHARP EDGES, AND IT IS NECESSARY THAT THE INSTALLER AND SERVICE PERSONNEL EXERCISE CAUTION.
CAUTION
Preventive maintenance is the best way to avoid unnecessary ex-pense and inconvenience. Have this system inspected at regularintervals by qualified service personnel, at least twice a year. Rou-tine maintenance should cover the following items:
1. Tighten all belts, set screws, and wire connections.2. Clean evaporator and condenser coils mechanically or with
cold water, if necessary. Usually any fouling is only mattedon the entering air face of the coil and can be removed bybrushing.
3. Lubricate motor bearings.4. Align or replace belts as needed.5. Replace filters as needed (see below).6. Check for blockage of condensate drain.7. Check power and control voltages.8. Check running amperage.9. Check operating temperatures and pressures.
10. Check and adjust temperature and pressure controls.11. Check and adjust damper linkages.12. Check operation of all safety controls.13. Examine gas furnaces (see below and the User’s
Information Manual).14. Check condenser fans and tighten set screws.
FILTERS
CAUTION
TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OFEQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINTBUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIRFILTER INSTALLED IN THE RETURN AIR SYSTEM.
Every application may require a different frequency of replace-ment of dirty filters. Filters must be replaced at least every three(3) months during operating seasons.
Dirty filters are the most common cause of inadequate heating orcooling performance. Filter inspection should be made at leastevery two months; more often if necessary because of local condi-tions and usage.
Dirty throwaway filters should be discarded and replaced with anew, clean filter.
Disposable return air filters are supplied with this unit. See theunit Specification Sheet or Technical Manual for the correct sizeand part number. To remove the filters, remove the filter accesspanel on return side of the unit.
CABINET FINISH MAINTENANCE
Use a fine grade automotive wax on the cabinet finish to maintainthe finish’s original high luster. This is especially important in in-stallations with extended periods of direct sunlight.
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)The coil with the outside air flowing over it should be inspectedannually and cleaned as frequently as necessary to keep the finnedareas free of lint, hair and debris.
CONDENSER FANS
Bearings on the condenser fan motors are permanently lubricated.No additional oiling is required.
LUBRICATION
The fan shaft bearings and the supply fan motor have grease fit-tings that should be lubricated during normal maintenance checks.
FUNCTIONAL PARTS
Refer to the unit Parts Catalog for a list of functional parts. Partsare available from your distributor.
15
APPENDIX A BLOWER PERFORMANCE DATABELT DRIVE - STANDARD
NOTES:
High static airflow requires installation of high static kit.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP0.2 --- --- --- --- --- --- --- --- --- --- 7203 2.18 6718 1.94
0.4 --- --- --- --- --- --- 7306 2.54 6777 2.14 6257 1.80 5711 1.66
0.6 --- --- 7477 2.97 6899 2.51 6323 2.10 5716 1.72 5103 1.39 ---
0.8 7112 2.96 6467 2.46 5795 2.01 5101 1.61 --- --- --- --- --- ---
1.0 5983 2.38 5190 1.89 --- --- --- --- --- --- --- --- --- ---
1.2 4426 1.71 --- --- --- --- --- --- --- --- --- --- --- ---
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 --- --- --- --- --- --- --- --- --- --- --- --- 9664 4.05
0.4 --- --- --- --- --- --- --- --- 9570 4.08 9197 3.82 8702 3.51
0.6 --- --- --- --- --- --- 9038 3.82 8460 3.46 7949 3.14 --- ---
0.8 --- --- 8171 2.93 7630 3.70 7068 2.79 --- --- --- --- --- ---
1.0 --- --- 7901 2.85 7203 3.42 --- --- --- --- --- --- --- ---
1.2 7344 4.35 --- --- --- --- --- --- --- --- --- --- --- ---
DCC240 STANDARD BELT DRIVE (includes 2 speed models at high speed)
ESP, In H2OTURNS OPEN
0 1 2 3 4 5 6
DCC180 STANDARD BELT DRIVE (includes 2 speed models at high speed)
ESP, In H2OTURNS OPEN
0 1 2 3 4 5 6
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 --- --- --- --- --- --- 10369 5.07 9748 4.41 9191 3.82 8683 3.28
0.4 --- --- 10802 6.00 10125 5.30 9484 4.62 8905 4.01 8386 3.46 7913 2.95
0.6 10519 6.20 9821 5.47 9193 4.81 8599 4.18 8062 3.61 7582 3.10 7143 2.63
0.8 9482 5.60 8839 4.93 8261 4.32 7714 3.74 7220 3.21 6777 2.74 --- ---
1.0 8446 5.01 7857 4.39 7329 3.83 6829 3.30 --- --- --- --- --- ---
1.2 7409 4.41 6876 3.85 --- --- --- --- --- --- --- --- --- ---
DCC300 STANDARD BELT DRIVE (includes 2 speed models at high speed)
ESP, In H2O
TURNS OPEN
0 1 2 3 4 5 6
16
APPENDIX A BLOWER PERFORMANCE DATABELT DRIVE - HIGH STATIC
NOTES:
High static airflow requires installation of high static kit.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.0 --- --- --- --- --- --- --- --- --- --- 7120 3.26 6223 2.55
1.2 --- --- --- --- --- --- --- --- 6927 3.39 5924 2.61 --- ---
1.4 --- --- --- --- --- --- 6739 3.52 5602 2.65 --- --- --- ---
1.6 --- --- --- --- 6587 3.69 5245 2.67 --- --- --- --- --- ---
1.8 --- --- 6419 3.84 4877 2.70 --- --- --- --- --- --- --- ---
2.0 6261 4.01 --- --- --- --- --- --- --- --- --- --- --- ---
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.0 --- --- --- --- --- --- --- --- 9090 5.79 8297 5.06 7479 3.62
1.2 --- --- --- --- --- --- 8774 5.60 7914 4.83 6989 4.07 --- ---
1.4 --- --- --- --- 8471 5.43 7549 4.63 --- --- --- --- --- ---
1.6 --- --- 8209 6.14 7194 4.45 --- --- --- --- --- --- --- ---
1.8 7967 6.02 6883 5.01 --- --- --- --- --- --- --- --- --- ---
2.0 6594 4.87 --- --- --- --- --- --- --- --- --- --- --- ---
DCC240 HIGH STATIC BELT DRIVE
ESP, In H2O
TURNS OPEN
0 1 2 3 4 5 6
DCC180 HIGH STATIC BELT DRIVE
ESP, In H2OTURNS OPEN
0 1 2 3 4 5 6
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.6 --- --- --- --- --- --- --- --- --- --- --- --- 11409 7.12
0.8 --- --- --- --- --- --- --- --- --- --- --- --- 10302 6.46
1.0 --- --- --- --- --- --- --- --- --- --- 10159 6.79 9195 5.79
1.2 --- --- --- --- --- --- --- --- 9990 7.11 8961 6.04 8087 5.13
1.4 --- --- --- --- --- --- 9789 7.39 8686 6.25 7763 5.29 6980 4.46
1.6 --- --- --- --- 9543 7.63 8357 6.40 7382 5.39 6566 4.53 --- ---
1.8 --- --- --- --- 7957 6.48 6925 5.41 6077 4.53 --- --- --- ---2.0 --- --- 7667 6.68 6370 5.34 --- --- --- --- --- --- --- ---2.2 7280 6.78 --- --- --- --- --- --- --- --- --- --- --- ---
DCC300 HIGH STATIC BELT DRIVE
ESP, In H2O
TURNS OPEN
0 1 2 3 4 5 6
17
APPENDIX A ECONOMIZER PRESSURE DROP
SCFM 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000
(In WG) 0.15 0.18 0.22 0.27 0.32 0.37 0.42 0.48 0.55 0.61 0.69 0.76
Airflow Pressure Drop of Downflow Economizer for 15 to 25 Ton Rooftop Units (100% Return Air)
18
APPENDIX B ELECTRICAL DATA
* Electric Heater kW rating: Rated at 240v for 208-230v units; 480v for 460v units
RLA LRA RLA LRA QTY HP FLA Type HP FLA Part # FLA FLA MCA MOP
- - - 71.5 / 71.5 90 / 90
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 86.5 / 98.1 90 / 100
EHK3-46 32.4 / 43.2 90.1 / 104 - 124 / 142 125 / 150
EHK3-60 43.3 / 57.6 120 / 139 - 162 / 151 175 / 175
- - 7.2 / 6.5 78.7 / 78.0 100 / 100
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 95.5 / 106 100 / 110
EHK3-46 32.4 / 43.2 90 / 104 7.2 / 6.5 133 / 150 150 / 150
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 171 / 159 175 / 175
- - - 76.1 / 76.1 100 / 100
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 92.3 / 104 100 / 110
EHK3-46 32.4 / 43.2 90.1 / 104 - 130 / 147 150 / 150
EHK3-60 43.3 / 57.6 120 / 139 - 167 / 156 175 / 175
- - 7.2 / 6.5 83.3 / 82.6 100 / 100
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 101 / 112 110 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 139 / 155 150 / 175
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 176 / 164 200 / 175
- - - 71.4 / 71.4 90 / 90
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 86.4 / 98.0 90 / 100
EHK3-46 32.4 / 43.2 90.1 / 104 - 124 / 141 125 / 150
EHK3-60 43.3 / 57.6 120 / 139 - 161 / 150 175 / 175
- - - - 7.2 / 6.5 78.6 / 77.9 100 / 100
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 95.4 / 106 100 / 110
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 133 / 150 150 / 150
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 170 / 159 175 / 175
- - - 34.6 45
EHK4-31 34.6 - 49.0 50
EHK4-46 52.0 - 70.8 80
EHK4-60 69.3 - 75.1 80
- - 3.3 37.9 50
EHK4-31 34.6 3.3 53.1 60
EHK4-46 52.0 3.3 74.9 80
EHK4-60 69.3 3.3 79.2 90
- - - 36.3 45
EHK4-31 34.6 - 51.1 60
EHK4-46 52.0 - 72.9 80
EHK4-60 69.3 - 77.2 90
- - 3.3 39.6 50
EHK4-31 34.6 3.3 55.3 60
EHK4-46 52.0 3.3 77.0 80
EHK4-60 69.3 3.3 81.3 90
- - - 34.3 45
EHK4-31 34.6 - 48.6 50
EHK4-46 52.0 - 70.4 80
EHK4-60 69.3 - 74.7 80
- - 3.3 37.6 45
EHK4-31 34.6 3.3 52.8 60
EHK4-46 52.0 3.3 74.5 80
EHK4-60 69.3 3.3 78.8 90
- - - 26.4 35
EHK7-31 28.9 - 41.4 45
EHK7-46 43.4 - 59.5 60
EHK7-60 57.8 - 63.1 70
- - 2.6 29.0 35
EHK7-31 28.9 2.6 44.6 45
EHK7-46 43.4 2.6 62.8 70
EHK7-60 57.8 2.6 66.3 7057.6
Standard -Belt Drive
3.00 4.20
-
28.8
43.2
57.6
-
28.8
43.2
57.6
DCC180XXX7B 575-3-60 9.0 78.0 9.0 78.0 3 0.33 0.67
Standard -Belt Drive
(High Speed)3.00 4.30
-
28.8
43.2
57.6
-
28.8
43.2
57.6
DCC180XXX4V 460-3-60 12.2 100.0 12.2 100.0 3 0.33 0.85
High Static -Belt Drive
5.00 6.30
-
28.8
43.2
57.6
-
28.8
43.2
57.6
DCC180XXX4H 460-3-60 12.2 100.0 12.2 100.0 3 0.33 0.85
Standard -Belt Drive
3.00 4.60
-
28.8
43.2
57.6
-
28.8
43.2
-
DCC180XXX4B 460-3-60 12.2 100.0 12.2 100.0 3 0.33 0.85
3 0.33 2.00Standard -Belt Drive
(High Speed)5.00 9.10DCC180XXX3V 208/230-3-60 25.0 164.0 25.0 164.0
2.00High Static -Belt Drive
5.00 13.80
-
-
-
-
DCC180XXX3H 208/230-3-60 25.0 164.0 25.0 164.0 3 0.33
3 0.33 2.00Standard -Belt Drive
3.00 9.20
Optional Electric HeatOptional Powered
Convienience OutletPower Supply
KW*
DCC180XXX3B 208/230-3-60 25.0 164.0 25.0 164.0
ModelNumber
ElectricalRating
CompressorCircuit 1
CompressorCircuit 2
Outdoor Fan Motor Indoor Fan Motor
- - - 27.3 35
EHK7-31 28.9 - 42.5 45
EHK7-46 43.4 - 60.6 70
EHK7-60 57.8 - 64.2 70
- - 2.6 29.9 35
EHK7-31 28.9 2.6 45.8 50
EHK7-46 43.4 2.6 63.9 70
EHK7-60 57.8 2.6 67.4 80
- - - 25.7 30
EHK7-31 28.9 - 40.5 45
EHK7-46 43.4 - 58.6 60
EHK7-60 57.8 - 62.2 70
- - 2.6 28.3 35
EHK7-31 28.9 2.6 43.8 45
EHK7-46 43.4 2.6 61.9 70
EHK7-60 57.8 2.6 65.4 7057.6
Standard -Belt Drive
(High Speed)3.00 3.50
-
28.8
43.257.6
-
28.8
43.2
57.6
DCC180XXX7V 575-3-60 9.0 78.0 9.0 78.0 3 0.33 0.67
High Static -Belt Drive
5.00 5.10
-
28.843.2
57.6
-
28.8
43.2
DCC180XXX7H 575-3-60 9.0 78.0 9.0 78.0 3 0.33 0.67
19
APPENDIX B ELECTRICAL DATA
* Electric Heater kW rating: Rated at 240v for 208-230v units; 480v for 460v units
RLA LRA RLA LRA QTY HP FLA Type HP FLA Part # FLA FLA M CA MOP
- - - 96.2 / 96.2 125 / 125
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 96.2 / 104 125 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 - 130 / 147 150 / 150
EHK3-60 43.3 / 57.6 120 / 139 - 167 / 156 175 / 175
EHK3-75 54.1 / 72.0 150 / 173 - 167 / 190 200 / 225
- - 7.2 / 6.5 103 / 103 125 / 125
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 103 / 112 125 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 139 / 155 150 / 175
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 176 / 164 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 7.2 / 6.5 176 / 198 200 / 225
- - - 103 / 103 125 / 125
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 103 / 112 125 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 - 138 / 156 150 / 175
EHK3-60 43.3 / 57.6 120 / 139 - 176 / 165 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 - 176 / 199 200 / 225
- - 7.2 / 6.5 110 / 109 125 / 125
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 110 / 120 125 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 147 / 164 150 / 175
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 185 / 173 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 7.2 / 6.5 185 / 207 200 / 225
- - - 96.4 / 96.4 125 / 125
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 96.4 / 104 125 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 - 130 / 148 150 / 150
EHK3-60 43.3 / 57.6 120 / 139 - 168 / 157 175 / 175
EHK3-75 54.1 / 72.0 150 / 173 - 168 / 191 200 / 225
- - 7.2 / 6.5 104 / 103 125 / 125
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 104 / 112 125 / 125
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 139 / 156 150 / 175
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 177 / 165 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 7.2 / 6.5 177 / 199 200 / 225
- - - 43.2 50
EHK4-31 34.6 - 51.1 60
EHK4-46 52.0 - 72.9 80
EHK4-60 69.3 - 77.2 90
EHK4-75 86.6 - 94.5 110
- - 3.3 46.5 60
EHK4-31 34.6 3.3 55.3 60
EHK4-46 52.0 3.3 77.0 80
EHK4-60 69.3 3.3 81.3 90
EHK4-75 86.6 3.3 98.6 110
- - - 46.3 60
EHK4-31 34.6 - 55.0 60
EHK4-46 52.0 - 76.8 80
EHK4-60 69.3 - 81.1 90
EHK4-75 86.6 - 98.4 110
- - 3.3 49.6 60
EHK4-31 34.6 3.3 59.1 60
EHK4-46 52.0 3.3 80.9 90
EHK4-60 69.3 3.3 85.2 90
EHK4-75 86.6 3.3 103 110
- - - 43.5 50
EHK4-31 34.6 - 51.5 60
EHK4-46 52.0 - 73.3 80
EHK4-60 69.3 - 77.6 90
EHK4-75 86.6 - 94.9 110
- - 3.3 46.8 60
EHK4-31 34.6 3.3 55.6 60
EHK4-46 52.0 3.3 77.4 80
EHK4-60 69.3 3.3 81.7 90
EHK4-75 86.6 3.3 99.0 110
28.8
43.2
57.6
72.0
-
28.8
43.2
57.6
72.0
-1 0.33 0.85
Standard -Belt Drive
5.00 6.60
28.8
43.2
57.6
72.0
DCC240XXX4V 460-3-60 16.0 140.0 16.0 140.0
-
28.8
43.2
57.6
72.0
-1 0.33 0.85
High Static -Belt Drive
7.50 9.40
28.8
43.2
57.6
72.0
DCC240XXX4H 460-3-60 16.0 140.0 16.0 140.0
-
28.8
43.2
57.6
72.0
-1 0.33 0.85
Standard -Belt Drive
5.00 6.30DCC240XXX4B 460-3-60 16.0 140.0 16.0 140.0
2.00Standard -Belt Drive
5.00 14.00
-
-
-
-
DCC240XXX3V 208/230-3-60 34.0 240.0 34.0 240.0 3 0.33
3 0.33 2.00High Static -Belt Drive
7.50 20.40DCC240XXX3H 208/230-3-60 34.0 240.0 34.0 240.0
0.33 2.00Standard -Belt Drive
5.00 13.80
-
-
Optional PoweredConvienience Outlet
Power Supply
KW *
DCC240XXX3B 208/230-3-60 34.0 240.0 34.0 240.0 3
ModelNumber
ElectricalRating
CompressorCircuit 1
CompressorCircuit 2
Outdoor Fan Motor Indoor Fan M otor Optional Electric Heat
- - - 34.9 45
EHK7-31 28.9 - 42.5 45
EHK7-46 43.4 - 60.6 70
EHK7-60 57.8 - 64.2 70
EHK7-75 72.3 - 78.7 90
- - 2.6 37.5 50
EHK7-31 28.9 2.6 45.8 50
EHK7-46 43.4 2.6 63.9 70
EHK7-60 57.8 2.6 67.4 80
EHK7-75 72.3 2.6 81.9 90
- - - 37.3 50
EHK7-31 28.9 - 45.5 50
EHK7-46 43.4 - 63.6 70
EHK7-60 57.8 - 67.2 80
EHK7-75 72.3 - 81.7 90
- - 2.6 39.9 50
EHK7-31 28.9 2.6 48.8 50
EHK7-46 43.4 2.6 66.9 70
EHK7-60 57.8 2.6 70.4 80
EHK7-75 72.3 2.6 84.9 100
- - - 35.0 45
EHK7-31 28.9 - 42.6 45
EHK7-46 43.4 - 60.8 70
EHK7-60 57.8 - 64.3 70
EHK7-75 72.3 - 78.8 90
- - 2.6 37.6 50
EHK7-31 28.9 2.6 45.9 50
EHK7-46 43.4 2.6 64.0 70
EHK7-60 57.8 2.6 67.6 80
EHK7-75 72.3 2.6 82.1 90
28.8
43.2
57.6
72.0
-
28.8
43.2
57.6
72.0
-1 0.33 0.67
Standard -Belt Drive
5.00 5.20
28.8
43.2
57.6
72.0
DCC240XXX7V 575-3-60 12.9 107.6 12.9 107.6
-
28.8
43.2
57.6
72.0
-1 0.33 0.67
High Static -Belt Drive
7.50 7.50
28.8
43.2
57.6
72.0
DCC240XXX7H 575-3-60 12.9 107.6 12.9 107.6
-
28.8
43.2
57.6
72.0
-1 0.33 0.67
Standard -Belt Drive
5.00 5.10DCC240XXX7B 575-3-60 12.9 107.6 12.9 107.6
20
APPENDIX B ELECTRICAL DATA
* Electric Heater kW rating: Rated at 240v for 208-230v units; 480v for 460v units
When using electric heat kit, use of the single point kit installed in the unit is required to meet UL requirements
UNITHEATER KIT
MODEL NUMBERMINIMUM CFM
DownshotHEATER KIT
MODEL NUMBERMINIMUM CFM
DownshotHEATER KIT
MODEL NUMBERMINIMUM CFM
Downshot
EHK3-31 5250 EHK4-31 5250 EHK7-31 5250
15 TON EHK3-46 5250 EHK4-46 5250 EHK7-46 5250
EHK3-60 5250 EHK4-60 5250 EHK7-60 5250
EHK3-31 7000 EHK4-31 7000 EHK7-31 7000
20 TON EHK3-46 7000 EHK4-46 7000 EHK7-46 7000
25 TON EHK3-60 7000 EHK4-60 7000 EHK7-60 7000
EHK3-75 7000 EHK4-75 7000 EHK7-75 7000
ATTENTION INSTALLING PERSONNEL Use only the heater kit specified for each model as dictated by the table above.
RLA LRA RLA LRA QTY HP FLA Type HP FLA Part # FLA FLA MCA MOP
- - - 132 / 132 175 / 175
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 132 / 132 175 / 175
EHK3-46 32.4 / 43.2 90.1 / 104 - 138 / 156 175 / 175
EHK3-60 43.3 / 57.6 120 / 139 - 176 / 165 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 - 176 / 199 200 / 225
- - 7.2 / 6.5 140 / 139 175 / 175
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 140 / 139 175 / 175
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 147 / 164 175 / 175
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 185 / 173 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 7.2 / 6.5 185 / 207 200 / 225
- - - 133 / 133 175 / 175
EHK3-31 21.6 / 28.8 60.0 / 69.3 - 133 / 133 175 / 175
EHK3-46 32.4 / 43.2 90.1 / 104 - 139 / 156 175 / 175
EHK3-60 43.3 / 57.6 120 / 139 - 176 / 165 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 - 176 / 199 200 / 225
- - 7.2 / 6.5 140 / 139 175 / 175
EHK3-31 21.6 / 28.8 60.0 / 69.3 7.2 / 6.5 140 / 139 175 / 175
EHK3-46 32.4 / 43.2 90.1 / 104 7.2 / 6.5 148 / 164 175 / 175
EHK3-60 43.3 / 57.6 120 / 139 7.2 / 6.5 185 / 173 200 / 175
EHK3-75 54.1 / 72.0 150 / 173 7.2 / 6.5 185 / 207 200 / 225
- - - 53.1 70
EHK4-31 34.6 - 55.0 70
EHK4-46 52.0 - 76.8 80
EHK4-60 69.3 - 81.1 90
EHK4-75 86.6 - 98.4 110
- - 3.3 56.4 70
EHK4-31 34.6 3.3 59.1 70
EHK4-46 52.0 3.3 80.9 90
EHK4-60 69.3 3.3 85.2 90
EHK4-75 86.6 3.3 103 110
- - - 53.8 70
EHK4-31 34.6 - 55.9 70
EHK4-46 52.0 - 77.6 80
EHK4-60 69.3 - 81.9 90
EHK4-75 86.6 - 99.2 110
- - 3.3 57.1 70
EHK4-31 34.6 3.3 60.0 70
EHK4-46 52.0 3.3 81.8 90
EHK4-60 69.3 3.3 86.1 90
EHK4-75 86.6 3.3 103 110
- - - 42.2 50
EHK7-31 28.9 - 45.5 50
EHK7-46 43.4 - 63.6 70
EHK7-60 57.8 - 67.2 80
EHK7-75 72.3 - 81.7 90
- - 2.6 44.8 50
EHK7-31 28.9 2.6 48.8 50
EHK7-46 43.4 2.6 66.9 70
EHK7-60 57.8 2.6 70.4 80
EHK7-75 72.3 2.6 84.9 100
- - - 42.9 50
EHK7-31 28.9 - 46.4 50
EHK7-46 43.4 - 64.5 70
EHK7-60 57.8 - 68.1 80
EHK7-75 72.3 - 82.6 100
- - 2.6 45.5 60
EHK7-31 28.9 2.6 49.6 60
EHK7-46 43.4 2.6 67.8 70
EHK7-60 57.8 2.6 71.3 80
EHK7-75 72.3 2.6 85.8 100
28.8
43.2
57.6
72.0
-
28.8
43.2
57.6
72.0
-1 1.00 1.50
Std & HighStatic -
Belt Drive7.50 8.20
28.8
43.2
57.6
72.0
DCC300XXX7V 575-3-60 14.7 100.0 14.7 100.0
-
28.8
43.2
57.6
72.0
-1 1.00 1.50
Std & HighStatic -
Belt Drive7.50 7.50
28.8
43.2
57.6
72.0
DCC300XXX7B 575-3-60 14.7 100.0 14.7 100.0
-
28.8
43.2
57.6
72.0
-1 1.00 1.85
Standard -Belt Drive
7.50 10.10
28.8
43.2
57.6
72.0
DCC300XXX4V 460-3-60 18.6 125.0 18.6 125.0
-
28.8
43.2
57.6
72.0
-1 1.00 1.85
Std & HighStatic -
Belt Drive7.50 9.40DCC300XXX4B 460-3-60 18.6 125.0 18.6 125.0
3.70Std & High
Static -Belt Drive
7.50 21.00
-
-
-
-
DCC300XXX3V 208/230-3-60 48.1 245.0 48.1 245.0 1 1.00
1 1.00 3.70Std & High
Static -Belt Drive
7.50 20.40
Optional Electric HeatOptional Powered
Convienience OutletPower Supply
KW*
DCC300XXX3B 208/230-3-60 48.1 245.0 48.1 245.0
ModelNumber
ElectricalRating
CompressorCircuit 1
CompressorCircuit 2
Outdoor Fan Motor Indoor Fan Motor
21
APPENDIX C UNIT DIMENSIONS
B
C
D
AB
C
D
A
VERTICAL DISCHARGE (TOP VIEW)
21” 60”
7”
48”
22”
NOTE: 15 & 20 ton models have 3 fans.25 ton models have 2 fans.
Model A B C D
15 Ton20 Ton
133-1/2" 88-7/32" 50-9/32" 5-5/32"
25 Ton 133-1/2" 88-7/32" 53-9/32" 5-5/32"
22
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS DCC180*/DCC240* 208-230, 460, 575 / 3 / 60 1 SPEEDAPPENDIX D WIRING DIAGRAMS
23
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
DCC180*/DCC240* 208-230, 460, 575 / 3 / 60 1 SPEEDWIRING DIAGRAMS
24
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
WIRING DIAGRAMS DCC180*/DCC240* 208-230, 460, 575 / 3 / 60 2 SPEED
25
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS DCC180*/DCC240* 208-230, 460, 575 / 3 / 60 2 SPEED
26
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
WIRING DIAGRAMS DCC300* 208-230, 460, 575 / 3 / 60 1 SPEED
0140L04899 -A
RD
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).2. THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS.
ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING
L1
L2
L3
T1
T2
T3
F1
F2
F3
L1
L2
L3
T1
T2
T3
COMP 1
COMP 2
L1
L2
L3
T1
T2
T3
L1
L2
L3
T1
T2
T3
RD
GY
BK
BK
BR
PU
BR
PU
BK
PU
BK
BR
YL
BK
BK
BK
BR
RD
PU
PU
BK
RD
RD
YL
PU
RD
PU
BR
RD
YL
PU
BR
PU
BK
BK
BK
BK
BK
BK
BKBK
BK
BK
3. 208/230V SUPPLY POWER UNITS ARE FACTORY CONNECTED TO THE CONTROL TRANSFORMER 240V TAP.MOVE WIRE CONNECTION FROM 240V TAP TO 208V TAP WHEN 208V POWER SUPPLY IS USED.
BR
PU
BK
LINEVOLTAGE
24V CNTLVOLTAGE
TR1
CCAS1
CMC 1
CCAS2
CMC 2
FB 1
CC2
CC1
PB
CCH1
CCH2
GY
BK
BK
BR
L1 L2 L3
GR
GR
4. SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS5. OPTIONAL; CB1,CB2,BC2 AND ASSOCIATED WIRING IS PRESENT ONLY WITH 2-SPEED EVAPORATOR MOTOR.
4
2,3
CM1
CM2
YL
BK
BR
PU
BK
BR
GR
GR1
2
3
1
2
3
1
2
3
1
2
3 PU
BK
BR
PU
BK
BRL1
L2
L3
L1
L2
L3
6. USE COPPER CONDUCTORS ONLY. UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS.THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT.
GND
RD
BK
BLOWER CONTACTOR
ELECTRONICBLOWER TIME DELAYRELAY
BC
EBTDR
PLM
OPTIONALHIGH VOLTAGE
BLOWER RELAY
COMPRESSORCONTACTOR RELAYCCR
COMPRESSORCONTACTOR
CONDENSERMOTORCOMPRESSOR
ECONOMIZEREVAPORATOR MOTOR
HIGHPRESSURE SWITCH
LOW PRESSURESWITCHPOWER DISTRIBUTION BLOCKFEMALEPLUG/ CONNECTOR
LOW VOLTAGE TERMINALBLOCK1
CONTROL TRANSFORMER(LINEVOLTAGE/24VAC)
CC
CMCOMP
ECONEM
HPS
LPSPBPLF
TB1
TR1
COMPONENT LEGEND
LOW VOLTAGE
LINE VOLTAGE
FIELD WIRING
LOW VOLTAGE
FACTORY WIRING
HIGH VOLTAGE
GR GREEN
WIRE CODE
BL BLUE
PU PURPLEPK PINK
WH WHITE
BK BLACK
RD RED
BR BROWN
OR ORANGE
YL YELLOW
GY GRAY
CIRCUIT BREAKER
CRANKCASEHEATER
BRCB
CCH
MALE PLUG/ CONNECTOR
LOW VOLTAGE TERMINALBLOCK 3TB3
CONDENSERMOTOR CONTACTORCMC
CC AUX SWITCHCCAS
CM/CCH/TR1FUSEBLOCKFB1EM FUSEBLOCKFB2
CM/CCH/TR1FUSESF1, F2, F3EM FUSESF4, F5, F6
L2
L3
L1
L2
L3
L1
L1 L2 L3
LINE VOLTAGE
YLRDBKPUOR
7
7. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL ELEC HEAT AND CONVENIENCE OUTLET WIRING DIAGRAMS.
POWER DIAGRAMDCC300 ***(3,4,7)
PLMPLF
PLMPLF
PU
YL
L1
L2
L3
T1
T2
T3
LAC MC
8
YL
BK
BR
BK
BR
YL
T3 T2 T1
L1
L2
L3
T1
T2
T3
EM
GY
BL
YL
RD
BL
BK
OR
RD
YL
BK
OR
GY
F4
F5
F6
RD
BK
OR
RD
BK
OR
BC1
BC 2
FB 2YL (11)
BK (1)
BK (2)
BK (3)
YL (13)
YL (12)
GR
5
L1
L2
L3
T1
T2
T3
L1
L2
L3
T1
T2
T3
L1
L2
L3
T1
T2
T3
RD
BK
OR
RD
BK
OR
CONDENSERMOTOR RELAYCMR
FM EVAPORATOR FREEZESTATMODULE
LACMC LOW AMBIENT CONDENSERMOTORCONTACTOR
LAM LOW AMBIENTMODULELAR LOW AMBIENT RELAY
LOW AMBIENT TIMERLAT
8. IF LOW AMBIENT KIT INSTALLED, DISCONNECT CONDENSER MOTOR WIRES (BK,BR,YL) FROM CMC1 (T1,T2,T3)AND CONNECT TO CORRESPONDING BK,BR,YL WIRES ON LOW AMBIENT HARNESS (INSULATED MALE QUICK CONNECT).ALSO CONNECT LOW AMBIENT HARNESS WIRES (BK,BR,YL) (INSULATED FEMALE QUICK CONNECT) TO T1,T2,T3 ON CMC1.
BK
GY
BK
BK
BK
BR
RD
RDPU PU
CB1HIGH
SPEED
CB2LOW
SPEED
BR
27
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS DCC300* 208-230, 460, 575 / 3 / 60 1 SPEED
28
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
WIRING DIAGRAMS DCC300* 208-230, 460, 575 / 3 / 60 2 SPEED
0140L04764-A
3A
1 3
4 2CC1
CMC1
CC2
CMC2
1234
12
1234
12
AUX2-IOCCE-GND
EXH1AUX1-O
Y2-IY2-OY1-I
CR
Y1-O
12
MATMAT
12
OATOAT
12
S-BUSS-BUS
123
1234
IAQ 2-10IAQ COMIAQ 24V
ACT COMACT 24V
GRDLUG
MAS
OD ENTH
ECONACT
ECON PLMECON MODULE
ECONPLF
ECON SHRTPLM
PLM 3
PLF 3
CCR1
TB3
PU
BL
BL
PU
YL
GR
BL
TB3
BL
SUPPLY (LINE)VOLTAGE
24 VAC
TR1
2 2
CONTROLS DIAGRAMDCC300***(3,4,7) V
2SPD EM
3
3GR
EBTDR
(NO)
(NC)COM
G
R
XFMR-R XFMR-C
C
SPEEDUP
M1
M2
7
6
BL
HPS1 LPS1
HPS2 LPS2
PU
YL
PU
YL
PU
YL
PU
5 6
1 3
4 2
CCR2
5 6
1
2
3
FM1
1
2
1
2
1
2
3
FM2
1
2
1
2
-t°
-t°
1
2
3
1
2
1
2-t°
1 3
4 2
LAR
5 6
LAM2
T1
T2
LATT6
LA CMC
1
2
3
1
2
1
2
-t°
LAM1
1 3
4 2
CMR
5 6 BK
BK
BK
BKBL
BL
OR
BK
YL
BK
RD BL
BLWH WH
WH
BL
GY
WH
WH
OR
OR
WH
WHBL
BR
OR
OR
WH
WH
RD
RD
RD
RDBL
BK
BL
BR
12 3
123
R CS1S2YIY2GW1 W2
TB1
FIELDCONTROL
WIRINGCLASS 2
4
1 2 3 4 5 6 7 8 9
HEAT PLF
BRWH
BL
GR RD PU
PU
YL
YL
BK
5
BLRD
RD
BL
YL
BL
RD
YL
BL
BL
YL
YL
PU
PU
BLOR
PU
BL
GR
GR
RD
RD
RD
RD
GY
YL
YL
PU
YL
PU
PU
GR
PU
PU
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OFINSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).
2. IF OPTIONAL ECONOMIZER IS INSTALLED, REMOVE ECON SHRTPLM AND CONNECT ECON PLM TO ECON PLF.
3. TB3 LOW VOLTAGE TERMINAL BLOCK.4 TERMINALS FOR 24VACPWR (RD,BK,BR WIRE) AND 6 TERMINALS FOR 24VAC COM (BL WIRE).
4. CONNECTIONS SHOWN ARE FOR 1-STAGE HEAT OPERATION.WHEN 2-STAGE OPERATION IS REQUIRED REMOVE WH JUMPER WIRE
CONNECTING W2 TO W1 ON TB1.
5. IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RD JUMPERWIRE CONNECTING S1 TO S2 ON TB1 AND MAKE THE FOLLOWING WIRE
CONNECTIONS: RD WIRE TO S1,BR WIRE TO TB3 (24V/PWR),BL WIRETO TB3 (24V/COM).
NOTES:
BL
BL
BL BR WH PU RD
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
YL
WH RD
1
2
3
4
5
6
7
8
9
RD
BL
RD
GY
BL
YLPU RD
BRWH GR RD RD
6. EBTDR RELAY ENERGIZES 7 SEC AFTER 24VAC IS APPLIED TO "G". THE RELAY DE-ENERGIZES65 SEC AFTER 24VAC IS REMOVED FROM "G".
7. EBDTR RELAY DELAYS WILL DECREASE TO APPROX 3-5 SECWHEN "SPEEDUP" IS SHORTED TO "C".
8. IF LOW AMBIENT KIT IS INSTALLED, CONNECT GY WIRE FROM LAM2-3TO CMR-4. ALSO CONNECT BL COM WIRES FROM LAT-T6 AND LAM2 -2TO TB3 (24V COM).
RD
OR8BL
GY
RD
BL
BL
8
BL
ECON OPTION
LOW AMBOPTION
BL
PU
PU
BK
RD RD
RD
GY
GYYL
RD
RD
BL
GR
GR GR
PU
ORBKYLRD
BL
BR GR RD RD PU YL
YLPUBRWH GR RD RD RD
BC2LOW SPEED
BC1HIGH SPEED
BL
BL
BR2
BL
YLPU
WH
YL
GR
PU
BL
BL
1 3
4 2
5 6
BR1
1 3
4 2
5 6
BK
BK
GR
BL
BR
BR
BL BL
YL
BR BR
BKGR
GR
BL
YLYL
YL
BL
GY
BL
OR
WH
WHWH YL
YL
BL
YLOR
BK
PU
BL
BL
BL
YL
BK
BL
BL
BL
BL
BL
BL
WH
WH
WH
BL
WH
WHWH
WH
WH
BL
BK
THERMOSTAT WIRING
Y1
TB1
W
G
W
PK
RD
Y1
R
OR
BL
GR
C
2 STAGE COOLING
WH
OO
Y2
C
G
R
YL
PK
RD
OR
BR
STAT
Y2SEN2
SEN1
7
18
8
17
6
16 B
R
Y
Y
AUX B
AUX A
10
9
B
R
Y
Y
SENSOR 1
SENSOR 2
B
R
Y
Y
B
R
Y
Y
SMOKE DETECTOR
SMK DETOPTION
24VA
C/D
C
PK
BL 5
PLF PLM
PLF PLM
PLF PLM
PLF PLM
9. LAT ON/OFF TIME SETTINGS :ON -TIME (LEFT COLUMN) : 2,8 = ON
OFF -TIME (RIGHT COLUMN) : 8 = ONALL OTHER DIP SWITCHES = OFF
9
29
WIRING DIAGRAMS FOR MODELS WITH DDC CONTROLSFor complete information and installation instructions for models with DDC controls,
see manual DK-DDC-TGD-XXX
30
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
WIRING DIAGRAMS
BKBK
RD
RD
OR
T1
0140L05763-A
POWER WIRING DIAGRAMDCC(180-240)
DDC
LOW VOLTAGE
HIGH VOLTAGE
FIELD WIRING
LOW VOLTAGE
FACTORY WIRING
HIGH VOLTAGE
GR GREEN
WIRE CODE
BL BLUE
PU PURPLEPK PINK
WH WHITE
BK BLACK
RD RED
BR BROWN
OR ORANGE
YL YELLOW
GY GRAY
YL/PK YELLOW WITHPINK STRIPE
BL/PK BLUE WITHPINK STRIPE
OPTIONAL LOW VOLTAGE
OPTIONAL ACCESSORIES OR FIELD SUPPLIED
BLOWER CONTACTORBC
COMPRESSORCONTACTOR
COMPRESSOR
ECONOMIZER
HIGHPRESSURE SWITCH
POWER DISTRIBUTION BLOCKFEMALEPLUG/CONNECTOR
TERMINALBLOCK(24V SIGNAL)
CC
COMP
ECON
HPS
PBPLF
TB
COMPONENT LEGEND
CIRCUIT BREAKERCB
TR
GND
BCS BLOWER CURRENT SWITCHBM BLOWERMOTOR
CFS CLOGGED FILTERSWITCHCF CONDENSERFAN
DAT DISCHARGEAIRTEMPERATURESENSORDDC DIRECT DIGITAL CONTROL
CO2 CARBONDIOXIDESENSOR
FC FAN CAPACITOR
EQUIPMENTGROUNDGV GAS VALVE
EXF EXHAUSTFAN
IAH INDOORAIRHUMIDITYSENSOR
LOW PRESSURESWITCHLPS
RSS REMOTE START/STOP
OAT OUTDOOR AIRTEMPERATURESENSOROAH OUTDOOR AIRHUMIDITYSENSOR
LDS LOADSHEDDING
SPCTEMP SPACE TEMPERATURESENSOR
TRANSFORMER
ALRM ALARM
HGRH HOT GAS REHEAT
SMK SMOKEDETECTOR
ALS AUXILIARY LIMIT SWITCH
IIC INTEGRATED IGNITION CONTROLLS LIMIT SWITCH
FS FLAME SENSE
PLM MALE PLUG/CONNECTOR
L1
L2
L3
T1
T2
T3
COMP 1
BM
L1
L2
L3
T1
T2
T3
RD
GY
BL
YL
RD
BL
BK
OR
RD
YL
BK
OR
GY
OR
RD
OR
RD
YL
BK
CCAS1
BC1
BC 2
CC1
PB
CCH1
GR
L1 L2 L3
GR
5
GND
L2
L3
L1
L1 L2 L3
LINE VOLTAGE
RD
7
L1
L2
L3
T2
T3
CB2LOW
SPEED
L1
L2
L3
T1
T2
T3
CB1HIGH
SPEED
L1
L2
L3
T1
T2
T3
RDBK
RD
BK
OR
LINEVOLTAGE
TR1
4
2,3
BK
OR
RD
ORBKBK RD OR OR
OR
KBYG
BKBK
CF1
CF3BR
PUPU
BR
BK
CF2
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).2. THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS.
ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING3. 208/230V SUPPLY POWER UNITS ARE FACTORY CONNECTED TO THE CONTROL TRANSFORMER 240V TAP.
MOVE WIRE CONNECTION FROM 240V TAP TO 208V TAP WHEN 208V POWER SUPPLY IS USED.4. SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS5. OPTIONAL; CB1,CB2,BC2 AND ASSOCIATED WIRING IS PRESENT ONLY WITH 2-SPEED EVAPORATOR MOTOR.6. USE COPPER CONDUCTORS ONLY. UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS.
THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT.7. SEE ACCESSORY KIT LITERATURE FOR OPTIONAL CONVENIENCE OUTLET WIRING DIAGRAM.
BK
HVTB HIGHVOLTAGE TERMINALBOARD
BK
BK
BK
BR
PUPU
BR
BK BKBK
BR
PUPU
FC1
BR
BK BK
PU
BR
BK BK
RD
RD
BK CFHVTB
BK
RD
OROR
COMP 2
L1
L2
L3
T1
T2
T3OR
RD
YL
BK
CCAS 2
CC2
CCH2
GR
L2
L3
L1
RD
OR
OR
BR BK
BKBK
RD
OROROR
RD
BK
BKBK
OROR
OR
RD
BK
RD
FC2
PU
BRRD
RD
FC3
PUBR
RD
BK
BK
RD
OR
BKBK
BK
OR
OR
OR
BK
OR
RD
BK
RD
OR
BK
BK
OR
RD OR OR
BK BK RD OR OR
BK RD OR
RD OR
CCAS COMPRESSCONTACTOR AUXILIARY SWITCHCCH CRANKCASEHEATER
DCC180*/ DCC240* 208-230, 460, 575 / 3 / 60 1&2 SPEED
31
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS
BC
CC1
CC2
ECON
XS(CLASS2)
BK
DA
BCS
OAT
ESPSCS
TB1 T124VAC
CFS
RSS
LDS
CO2
T2
T3
T4
T5
LPS1
HPS2
HPS1
LPS2
BL/PK
BL/PK
YL/PK
YL/PK
PK
BK
BK
GND24 VAC(PWR)
OAHVOUT (DC)
GND24VAC(COM)
24 VAC(PWR)
VOUT (DC)
VOUT (DC)24 VAC(PWR)
IAH
GND
BI8
BI5
121110
1
COM3-8RLY8
BI1BI2BI3BI4
BI7
BR
RDCOM3-8
RLY7RLY6RLY5RLY4RLY3
COM1
PU
(OAT)
(DFT)(CFS)
(EMER)(FAN PROV)
(HEAT 2)(HEAT 1)
BI6 (SHED)
RLY1RLY2COM2
(24V IN)(ECON PWR)
(EXF)(ALRM)
(ECON DMPR)
(OAH)
(ISOL GND)
(CO2)
2345678
123456789
DDC (CLASS2)
(ECON FB)
C(CLASS2)TB2
DAT
(COMP2 OUT)(COMP1 OUT)(COMP1 IN)
(COMP2 IN)
YL
YL
4
21
65
3
987
HTR PLF2
WHBR
654321AO1
AO2AO3AO4GNDGND
AG
SPCTEMPTEMP
GNDSTPT OFFSET
BK
PU
RD
BK
PUBK BK
WH WH
PK
WHBR
GR
GR
BR
BL
WH
87654321
9AI3
AI8AI7AI6AI5AI4
AI1AI2
AGNDAGND
10
WH WH
PLF
WH
WH
BL
4
5
-t°
3
BAC NET3T-21(BAC
NET)R+
SH
RD
BL
BL
CONTROL WIRING DIAGRAMDCC(180-240)****B
DDC
(SPC TMP)
(SUPPLY AIR TMP)
(SPC HUM)
(COMP PRESS 1)
(BLOWER STAGE 1)
(COMP PRESS 2)
(SPC SLIDE ADJ)
(RMT STRT/STP)
-t°
0140L05762-A
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES.
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX.INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT.
IF OPTIONAL ELECTRIC HEAT IS INSTALLED, CONNECT HTR PLF2 TO ACCESSORY HEAT PLUG IN HEAT COMPARTMENT.
SEE POWER DIAGRAM FOR CONTROL TRANSFORMER (TR1) HIGH VOLTAGE CONNECTIONS.
2
3
4
5
PU
BR
BL
BL
RD
GR
SMK/EMG TR1
PUYL
PU
BL/PK
BL/PK
YL
PK
YL/PKPK
YL/PK YLPK
YL
PU
BLRD
GR
24V
RD
LINE VOLTAGE
PK
PKPKPKPK
YL BK
YL PKPU
PK
PK
RD
BK
GR
BLYL
PU BL
BL
YL
BLBLBK
BL
BL
4
21
65
3
EXF CNTL RLYTWISTEDPAIR
GRD10VDC
ALRM CNTL RLY
GRD10VDC
BR
RD
WH
RD
RD
BR
GRGR
GR
GR BK
BK
PU
PUPU
PU
PU
PUPU
BK
BK
YL
YL
PU
PU
PU PUYL
PKPKPK
PK BL
BLBL
BLBL
BL
BL
2
2
RDRD RD
GRRD
RD
PURD
BKRD
BK
BR
BR
BR
GR
BL
6
6
PKBL
BL
BL
GND
24VAC
1
2
PK
PK
PK
DCC180*/ DCC240* 208-230, 460, 575 / 3 / 60 1 SPEED
32
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
WIRING DIAGRAMS
CC1
CC2
ECON
XS(CLASS2)
BK
DA
BCS
OAT
ESPSCS
TB1 T124VAC
CFS
RSS
LDS
CO2
T2
T3
T4
T5
LPS1
HPS2
HPS1
LPS2
BL/PK
BL/PK
YL/PK
YL/PK
PK
BK
BK
GND24 VAC(PWR)
OAHVOUT (DC)
GND24VAC(COM)
24 VAC(PWR)
VOUT (DC)
VOUT (DC)24 VAC(PWR)
IAH
GND
BI8
BI5
121110
1
COM3-8RLY8
BI1BI2BI3BI4
BI7
BR
RDCOM3-8
RLY7RLY6RLY5RLY4RLY3
COM1
PU
(OAT)
(CFS)
(EMER)(FAN PROV)
(HEAT 2)(HEAT 1)
BI6 (SHED)
RLY1RLY2COM2
(24V IN)(ECON PWR)
(EXF)(ALRM)
(ECON DMPR)
(OAH)
(ISOL GND)
(CO2)
2345678
123456789
DDC (CLASS2)
(ECON FB)
C(CLASS2)TB2
DAT
(COMP2 OUT)(COMP1 OUT)(COMP1 IN)
(COMP2 IN)
YL
YL
4
21
65
3
987
HTR PLF2
WHBR
654321AO1
AO2AO3AO4GNDGND
AG
SPCTEMPTEMP
GNDSTPT OFFSET
BK
PU
RD
BK
PU
BK
WH WH
PK
WHBR
GR
GR
BR
BL
WH
87654321
9AI3
AI8AI7AI6AI5AI4
AI1AI2
AGNDAGND
10
WH WH
PLF
WH
WH
BL
4
5
-t°
3
BAC NET3T-21(BAC
NET)R+SH
RD
BL
BL
CONTROL WIRING DIAGRAMDCC(180-240)****V
DDC
(SPC TMP)
(SUPPLY AIR TMP)
(SPC HUM)
(COMP PRESS 1)
(BLOWER STAGE 1)
(COMP PRESS 2)
(SPC SLIDE ADJ)
(RMT STRT/STP)
-t°
0140L05824-A
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (AT LEAST 105° C). USE COPPER CONDUCTORS ONLY.USE N.E.C. CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS.
IF OPTIONAL SMOKE DETECTOR IS INSTALLED, REMOVE RED JUMPER WIRE CONNECTIONS TB1-XS TO TB1-ES.
DISCHARGE AIR TEMPERATURE SENSOR SHIPPED WITH UNIT IN CONTROL BOX.INSTALL AND CONNECT PER THE ATTACHED INSTRUCTIONS/WIRING DIAGRAM.
IF OPTIONAL ECONOMIZER IS INSTALLED, CONNECT ECON PLF TO ECONOMIZER. ECONOMIZER PLUG LOCATED IN THE RETURN AIR COMPARTMENT.
IF OPTIONAL ELECTRIC HEAT IS INSTALLED, CONNECT HTR PLF2 TO ACCESSORY HEAT PLUG IN HEAT COMPARTMENT.
SEE POWER DIAGRAM FOR CONTROL TRANSFORMER (TR1) HIGH VOLTAGE CONNECTIONS.
2
3
4
5
PU
BR
BL
BL
RD
GR
SMK/EMG TR1
PUYL
PU
BL/PK
BL/PK
YL
PK
YL/PKPK
YL/PK YLPK
YL
PU
BLRD
GR
24V
RD
LINE VOLTAGE
PK
PKPKPKPK
YL BK
YL PKPU
PK
PKRD
BK
GR
YL
PU
BL
YL
BL
BL
BK
PK
BL
BL
4
21
65
3
EXF CNTL RLYTWISTEDPAIR
GRD10VDC
ALRM CNTL RLY
GRD10VDC
BR
RD
WH
RD
RD
BR
GRGR
GR
GR BK
BK
PU
PUPU
PU
PU
PUPU
BK
BK
YL
YL
PU
PU
PU PUYL
PK
PKPKPK PKPK BL
BLBL
BLBL
BL
BL
2
2
RDRD RD
GRRD
RD
PURD
BKRD
BK
BR
BR
BR
GR
BL
6
6
PK
BC1(HI SPD)
BK
BC2(LO SPD)
BL
BL
BR BR
BR
BR
(BLOWER STAGE 2)
BL
BL
BLBL
BL
GND
24VAC
1
2
DCC180*/ DCC240* 208-230, 460, 575 / 3 / 60 2 SPEED
33
HIG
H V
OLT
AG
E!D
ISC
ON
NEC
T A
LL P
OW
ER B
EFO
RE
SER
VIC
ING
OR
INST
ALL
ING
TH
ISU
NIT
. M
ULT
IPLE
PO
WER
SO
UR
CES
MAY
BE
PRES
ENT.
FA
ILU
RE
TOD
O S
O M
AY C
AU
SE P
RO
PER
TY D
AM
AG
E, P
ERSO
NA
L IN
JURY
OR
DEA
TH.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
WIRING DIAGRAMS DCC300* 208-230, 460, 575 / 3 / 60 1&2 SPEED
78 6 5 4 3 2 1
014
0L06
606-
A
T1 T2LAT T6
136
5
42
LAR
1 2
1 2
1 2 3LAM
2P
LMP
LF
-t W
LA C
MC
LOW
AM
BO
PTIO
NL3
L2L1
1 2
1 2
1 2 3LAM
1P
LMP
LF
CM
R
24
56 3
1
7
HIG
HS
PE
ED
CB
1
T3T2T1
L3L2L1
BC
1
EM
T3T2T1
L3L2L1
T1T2
T3LA
C M
C T3T2T1
L3L2L1
PLF
PLM
FB 2
F6F5F4
321
321
FB 1
CM
C2
CM
C1 T3T2T1
L3L2L1
CM
1
F3F2F1
T3T2T1
L3L2L1
RDBR
PU
BK
BR
BK
BK
BR
BK
BR PU
GR
BK
BR
YL
BK YL
BR
BK
PU
PU
PU
BK
BK
RD
OR
BK RD
OR
BK
RD
OR
YL
(11)
YL
(13)
YL
(12)
GR
BL
BL
PU
PU
PU
GY
GY
GY
BK BK
BK BK
PU
(CLA
SS
2)
BK
BC
S
OA
T
PS
CS
TB1
CFS
RSS
LDS
CO
2
SM
K /E
MG
2
BK
LPS1
HPS
2
YL
HP
S1
LPS
2
PU
BL/
PK
BL/
PK
YL/
PK
YL/
PK
YL/
PK
YL/
PK
PK
BK
BK
YL
PU
YL
GN
D24
VA
COA
HV
OU
T (D
C)
GN
D24
VA
C (C
OM
)24
VA
C
VO
UT
(DC
)
VO
UT
(DC
)
24 V
ACIAH G
ND
BI8
BI5
CO
M3-
8R
LY8
BI1
BI2
BI3
BI4
BI7
GN
D
24V
AC
BR
RD
CO
M3-
8
RLY
7R
LY6
RLY
5R
LY4
RLY
3
CO
M1
BL
PU
PU
OA
T
CFS
EM
ER
GE
NC
Y S
HU
TDO
WN
FAN
PR
OV
SW
HE
AT/S
TG2
HEA
T/S
TG1
YL
BI6
LOA
D S
HE
D
RLY
1R
LY2
CO
M2
24V
RLY
EX
F (S
SR
)/VFD
ALR
M (S
SR
)
EC
ON
DM
PR
OA
H
SP
C T
MP
CO
2 S
EN
SO
R
DD
C (
CLA
SS
2)
EC
ON
FE
ED
BA
CK
C
GR
(CLA
SS
2)TB
2
DA
T
CO
MP
/STG
2C
OM
P/ST
G1
24V
RLY
1
24V
RLY
2
YL
EC
ON
AO
1 A
O2
AO
3 A
O4
GN
DG
ND
WH
AG
SP
CTE
MP TE
MP
GN
DS
TPT
OFF
SE
T
GR
BR
BR
BK
BK
PU
PU
GR
GRB
RB
R
BR
GR
BR
BR
GR
RD
RD
RD
BL
BL
BL
BL
PU
PKPK
PU
YL
BK
RD
BK
BK
BK
BL/
PK
PU
PU YL
PU
PU
YL
PU
WH
PK
WH
WH
PK
WH
BR
ALR
M-
+
EX
F-
+
GR
GR
AI3
AI8
AI7
AI6
AI5
AI4
AI1
AI2
AG
ND
AG
ND
GR
WH
WH
PU
BK
PU
PLF
WH
BL
TR1
5
RD
BL
4
-t�
3
BA
C N
ET
T-B
AC
NE
TR
+S
H
+-
HG
RH
BR
BL
BL
PU
PU
GR
GR
GR
BL
BL
BL
BL
RD
65
43
21
BR
BR
BR
BRBR
BL
RDRD
BL
RD
BR
BR
BL
BL
24V
CN
TLV
OLT
AG
E
LIN
EV
OLT
AG
E
RD
BL
RD
BL
BL
SU
PP
LY A
IR T
MP
MO
D H
GR
H
SP
C H
UM
CO
MP
PR
ESS
SW
1
BLO
WE
R/S
TG1
CO
MP
PR
ES
S S
W2
SP
C S
LID
E A
DJ
RM
T S
TRT/
STP
BK
-t�
FSW
24V
ACR
D
RD
T1T2
T3T4
1 2
1 2
1 2 3
FM2
PLM
PLF
-t W
1 2
1 2
1 2 3
FM1
PLM
PLF
-tW
YL
BLO
WE
R/S
TG2/
EX
F
CO
ND
FA
N(S
)R
EV V
ALVE
/LA
T
DE
FRO
ST
SW
(ES
)
BK
YL BL BK
RD
RD
RD
RD
OR
OR
OR
OR
WH
WH
WH
WH
BLPU
BK
YL
PU
PU
PU
BL
BL
BL
BK
BK
RD
RD
YL
BL
BK
BL
BK
1 1
1 2
RD
RD
PK
PK
PK
RD
RD
RD
RD
PK
BR
BR
BK
BR
BK
BR B
K
BR
YL
RD
RD
RD
BK
BK
BK
BK
BL
BL
BLBL
9
T3T2T1
L3L2L1
LOW
SP
EE
D
CB
2
T3T2T1
L3L2L1
BC
2B
R BK
RD
OR
YL
BL
GY
YL
BL
GY
BK
(1)
BK
(3)
BK
(2)
PU
PU
BL
BL
BL
BL
BL
BL
BL
BL
8
13
8
L3L2
L1
L1 L3
L2
GN
D
L1C
CH
2
CC
H1
PB
CC
1
CC
2
CC
AS
2
CC
AS
1
PU
T3T2T1
L3L2L1
CO
MP
1
RD
LIN
E V
OLT
AG
EL3
L2L1
PH
ASE
MO
NIT
OR
10
YL
BK RD
YL
BK
RD
PU
BK
BK
GY
GY
GY
BK
BK
GR
BK
PU
BK
BK
BL
PU
BL
BK
BR
PU
BL
BL
101 2
1 1
PK
PK
PK
BK
BK
24V
RLY
BR
BL
BL
BK
PU
PU
YL
YL
YL
RD
RD
RD
YL BK OR
GY
BL
WH
OR
BK
YLR
D
OR
BK YL
RD
BL
BL
BLBL
GY
BL
WH
WH
WH
WH
WH
-tW
WH
WH
RD
BL
BL
GY
BK
RD
L2L3
YL
PU
BK
RD
BL
BL
GY
BL
BR
WH
PU
YL
RD
RD
RD
YL
YLR
D
RD
RD
BK
RD
T5X
SD
AE
S
BL
BL
PK
RD
BK
BK
RD
RD
BK
BL
PU
YL
GR
L1 L3
L2T3T2T1
L3L2L1
CO
MP
2
PU
RD
BK
PU
PU
GY
GY
L3L2
L1
PLF
PLM321
321C
M2
GR
BK
BR
PU
BK
BR
PU
BR
BK
BL
GY
BK
RD
BR
BL
OR
BK
RD
OR
BK
BK
BK
RD
RD
RD
OR
PU
YL
RD
BK
BR
BK
BR P
UBR
PO
WE
R &
CO
NTR
OL
WIR
ING
DIA
GR
AM
DC
C(3
00) *
**(3
,4,6
,7) (
B, V
)D
DC
GR
GR
EE
N
WIR
E C
OD
E
BL
B
LUE
PU
PU
RPL
EP
K
P
INK
WH
WH
ITE
BK
BLA
CK
RD
RE
D
BR
BR
OW
N
OR
OR
AN
GE
YL
Y
ELLO
W
GY
GR
AY
BLO
WE
R C
ON
TAC
TOR
BC
CO
MP
RES
SO
R C
ON
TAC
TOR
CO
MP
RES
SO
R
EC
ON
OM
IZE
R
HIG
H P
RE
SSU
RE
SW
ITC
H
PO
WE
R D
ISTR
IBU
TIO
N B
LOC
KFE
MAL
E P
LUG
/CO
NN
EC
TOR
TER
MIN
AL B
LOC
K (2
4V S
IGN
AL)
CC
CO
MP
EC
ON
HP
S
PB PLF
TB
CO
MPO
NEN
T LE
GEN
D
CIR
CU
IT B
RE
AKE
RC
B GN
D
BC
SBL
OW
ER
CU
RR
EN
T S
WIT
CH
CFS
CLO
GG
ED
FIL
TER
SW
ITC
H
DAT
DIS
CH
AR
GE
AIR
TEM
PE
RA
TUR
E S
EN
SOR
DD
CD
IRE
CT
DIG
ITA
L C
ON
TRO
L
CO
2C
AR
BON
DIO
XID
E S
EN
SOR
FCFA
N C
AP
AC
ITO
R
EQU
IPM
EN
T G
RO
UN
D
EXF
EXH
AU
ST
FAN
IAH
IND
OO
R A
IR H
UM
IDIT
Y S
EN
SO
R
LOW
PR
ESS
UR
E S
WIT
CH
LPS
RS
SR
EM
OTE
STA
RT/
STO
P
OA
TO
UTD
OO
R A
IR T
EMP
ER
ATU
RE
SE
NSO
RO
AH
OU
TDO
OR
AIR
HU
MID
ITY
SE
NS
OR
LDS
LOA
D S
HE
DD
ING
SP
CTE
MP
SP
AC
E TE
MP
ER
ATU
RE
SE
NS
OR
YL/P
K
YEL
LOW
WIT
H
P
INK
STR
IPE
BL/P
K
BLU
E W
ITH
PIN
K S
TRIP
E
ALR
MA
LAR
M
HG
RH
HO
T G
AS
RE
HEA
T
SM
KSM
OK
E D
ETE
CTO
R
H
IGH
VO
LTA
GE
FIEL
DW
IRIN
G
L
OW
VO
LTA
GE
FAC
TORY
WIR
ING
OPT
ION
AL
AC
CES S
OR
I ES
OR
FIE
LD S
UP P
LIED
CO
MPO
N EN
TS
OPT
ION
AL L
OW
VO
LTA
GE
NO
TES
:
2 3 4 5
PS
PR
ESS
UR
E S
WIT
CH
FMFR
EE
ZE S
TAT
MO
DU
LE
H
IGH
VO
LTA
GE
L
OW
VO
LTA
GE
PLM
MAL
E P
LUG
/CO
NN
EC
TOR
6
7 8 9 10 11 12
FSW
FLO
AT
SW
ITC
H
PM
PH
ASE
MO
NIT
OR
CO
ND
EN
SE
R M
OTO
RC
M
CR
AN
K C
ASE
HE
ATE
RC
CH
CO
ND
EN
SE
R M
OTO
R C
ON
TAC
TOR
CM
C
CC
AU
X S
WIT
CH
CC
AS
FU
SE
BLO
CK
FB
CO
ND
EN
SE
R M
OTO
R R
ELA
YC
MR
LAC
MC
LOW
AM
BIE
NT
CO
ND
EN
SE
R M
OTO
RC
ON
TAC
TOR
LAM
LOW
AM
BIE
NT
MO
DU
LELA
RLO
W A
MB
IEN
T R
ELA
YLO
W A
MBI
EN
T TI
ME
RLA
T
EV
AP
OR
ATO
R M
OTO
RE
M
I
F LO
W A
MB
IEN
T K
IT IS
INS
TALL
ED
, DIS
CO
NN
EC
T C
ON
DE
NS
ER
M
OTO
R W
IRE
S F
RO
M C
MC
1 (T
1, T
2, T
3) A
ND
CO
NN
EC
T TO
C
OR
RE
SP
ON
DIN
G (B
K, B
R, Y
L) W
IRE
S W
ITH
QU
ICK
CO
NN
EC
T
TE
RM
INA
LS F
RO
M L
AC
MC
(T1,
T2,
T3)
. CO
NN
EC
T (B
K, B
R, Y
L)
FR
OM
LA
C M
C (L
1, L
2, L
3) T
O C
MC
1 (T
1, T
2, T
3).
I
F LO
W A
MB
IEN
T K
IT IS
INS
TALL
ED
, CO
NN
EC
T G
Y W
IRE
FR
OM
L
AM
2 - 3
TO
CM
R -4
. ALS
O C
ON
NE
CT
BL
CO
M W
IRE
S F
RO
M L
AT-
T
6 A
ND
LA
M2
-2 T
O T
B 2
(24V
CO
M).
O
PTI
ON
AL;
CB
1, C
B2,
BC
2 A
ND
AS
SO
CIA
TED
WIR
ING
IS P
RE
SE
NT
O
NLY
WIT
H 2
-SP
EE
D E
VA
PO
RAT
OR
MO
TOR
. WH
EN
PR
ES
EN
T, B
K
WIR
E F
RO
M D
DC
CO
NTR
OLL
ER
INS
TALL
ED
ON
BC
2 A
ND
BR
WIR
E
FR
OM
DD
C IN
STA
LLE
D O
N B
C1.
I
F 3
PH
AS
E L
INE
VO
LTA
GE
MO
NIT
OR
IS IN
STA
LLE
D,C
ON
NE
CT
P
HA
SE
MO
NIT
OR
L1,
L2,
L3
TO T
HE
UN
IT P
OW
ER
BLO
CK
R
ES
PE
CTI
VE
LY. A
LSO
, RE
MO
VE
JU
MP
ER
WIR
E C
ON
NE
CTI
ON
S
TB
1 - E
S T
O T
B1-
PM
.
I
F FL
OA
T S
WIT
CH
IS IN
STA
LLE
D, R
EM
OV
E J
UM
PE
R W
IRE
C
ON
NE
CTI
ON
S T
B1-
PM
TO
TB
1 - F
SW
.
I
F FR
EE
ZE P
RO
TEC
TIO
N M
OD
ULE
IS IN
STA
LLE
D, R
EM
OV
E J
UM
PE
R
CO
NN
EC
TIO
NS
TB
1- P
S T
O T
B1
- FM
1 A
ND
TB
1 - F
M1
TO T
B1
- FM
2.
L
AT
ON
/OFF
TIM
E S
ETT
ING
S:
O
N -
TIM
E (L
EFT
CO
LUM
N) :
2,8
= O
N
OFF
- TI
ME
( R
IGH
T C
OLU
MN
) : 8
= O
N
ALL
OTH
ER
DIP
SW
ITC
HE
S O
FF
1. R
EPL
AC
EME
NT
WIR
E M
US
T BE
SA
ME
SIZ
E A
ND
TY
PE O
FIN
SU
LATI
ON
AS
OR
IGIN
AL
(AT
LEA
ST10
5� C)
. US
E C
OP
PE
RC
ON
DU
CTO
RS
ON
LY.
U
SE
N.E
.C. C
LAS
S 2
WIR
E F
OR
ALL
LO
W V
OLT
AGE
FIE
LDC
ON
NE
CTI
ON
S.
IF O
PTIO
NAL
SM
OK
E D
ETE
CTO
R IS
INST
ALL
ED
, REM
OV
E R
ED
JUM
PE
R W
IRE
CO
NN
EC
TIO
NS
TB1
-XS
TO
TB1-
ES
.
DIS
CH
AR
GE
AIR
TEM
PE
RAT
UR
E S
EN
SOR
SH
IPPE
D W
ITH
UN
IT IN
CO
NTR
OL
BO
X.IN
STA
LL A
ND
CO
NN
EC
T P
ER
THE
ATT
AC
HE
DIN
STR
UC
TIO
NS
/WIR
ING
DIA
GR
AM.
IF O
PTI
ON
AL
EC
ON
OM
IZE
R IS
INST
ALL
ED
, CO
NN
EC
T E
CO
N P
LF T
OE
CO
NO
MIZ
ER
. EC
ON
OM
IZE
RP
LUG
LO
CAT
ED IN
TH
E R
ETU
RN
AIR
CO
MP
AR
TME
NT.
(208
/230
)V U
NIT
S: I
F U
NIT
UTI
LIZE
S 2
08V
SU
PPLY
PO
WE
R, M
OV
ETR
1/2
HIG
HV
OLT
AGE
RE
D W
IRE
FR
OM
TH
E 2
40V
TE
RM
INAL
TO
TH
E20
8V T
ER
MIN
AL
460V
, 575
V U
NIT
S: R
ED
WIR
E C
ON
NE
CTE
DTO
AP
PR
OP
RIA
TE H
IGH
VO
LTAG
E IN
PU
TTE
RM
INAL
ON
TR1/
2
IF O
PTIO
NAL
ELE
CTR
IC H
EA
T IS
INST
ALLE
D, C
ON
NE
CT
HTR
PLF
2 TO
AC
CE
SSO
RY
HE
AT P
LUG
IN H
EA
T C
OM
PA
RTM
EN
T.
13
TRTR
AN
SFO
RM
ER
TB1-
T1
FM
1 (F
RE
EZE
MO
NIT
OR
1)
TB1-
T2
FM
2 (F
RE
EZE
MO
NIT
OR
2)TB
1-T3
P
M (P
HAS
E M
ON
ITO
R)
TB1-
T4
FS
W (F
LOAT
SW
ITC
H)
TB1-
T5
UN
USE
D
RD
1
9
BL
BL
BL
BL
BL
BL
BL
BL
6
HTR
PLF
2
PK
PU YL P
UB
L/P
KY
L
34
Start-up Checklist*Store in job file
Pre Start-Up(Check each item as completed)
Verify all packaging material has been removed.
Remove all shipping brackets per installation instructions.
Verify the job site voltage agrees with the unit serial plate.
Verify condensate connection is installed per installation instructions.
Verify proper clearance around the unit for safety, service, maintenance and proper unit operation.
Verify proper weatherproofing of all ductwork, roof curbs and electrical connections.
Check that the flue screen is in place.
Check gas piping for leaks.
Verify gas pressure to the unit is within the range specified on the serial plate.
Check to ensure that all fans, pulleys and wheels are secure.
Check for proper belt tension and alignment per installation instructions.
Check refrigerant piping for rubbing and leaks. Repair if necessary.
Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges.
Check all electrical connections and terminals. Tighten as needed.
Verify that the crankcase heaters have been energized for 24 hours.
Verify the scroll compressor(s) are rotating in the right direction.
Verify all accessories are installed and operating correctly.
Check filters and replace if necessary.
Verify the installation of the thermostat.
9/2014
Date: ___________________________________
Model Number: ___________________________________
Serial Number: ___________________________________
Technician: ___________________________________
Location: __________________________________________
__________________________________________
__________________________________________
Unit #: __________________________________________
35
Start-up Checklist
L1 - L2 L2 - L3 L3 - L1
L1 L2 L3
L1 L2 L3
L1 L2 L3
Fan 1 Fan 2 Fan 3
IN. W.C.
IN. W.C.
IN. W.C.
RPM
DB WB
DB WB
DB WB
DB
IN. W.C.
IN. W.C. (Low Fire) IN. W.C. (High Fire)
PSIG °F
°F
PSIG °F
°F
PSIG °F
°F
PSIG °F
°F
PSIG °F
PSIG °F
PSIG °F
PSIG °F
BLOWER EXTERNAL STATIC PRESSURE
Return Air Static Pressure
Supply Air Static Pressure
Supply Voltage
Circuit 1 Compressor Amps
Circuit 2 Compressor Amps
Blower Amps
Condenser Fan Amps
ELECTRICAL
Total External Static Pressure
Blower Wheel RPM
TEMPERATURES
Outdoor Air Temperature
Return Air Temperature
Cooling Supply Air Temperature
Discharge Circuit 1
Heating Supply Air Temperature
PRESSURES
Gas Inlet Pressure
Gas Manifold Pressure
Suction Circuit 1
Suction Circuit 2
Discharge Circuit 2
Superheat (Orifice System)
Superheat (Orifice System)
Subcooling (TXV System)
Subcooling (TXV System)
Discharge Circuit 1
Discharge Circuit 2
(HEAT PUMP ONLY)
Suction Circuit 1
Suction Circuit 2
Start-Up(Insert the values as each item is completed.)