installation instructions all nofirno …stenca.dk › upload › nofirno ›...

72
INSTALLATION INSTRUCTIONS ALL NOFIRNO ® (MULTI-) CABLE TRANSITS WE CARE SAFE T Y SEALIN G SYSTEM S TECHNOLOGY DEVELOPED BY BEELE ENGINEERING BV COMPOUNDING AND PRODUCTION IN THE ULTRA-MODERN MANUFACTURING FACILITIES IN AALTEN/THE NETHERLANDS UNDER A STRINGENT ISO 9001:2015 QUALITY SYSTEM MORE THAN 40 YEARS R&D ON QUALITY, DURABILITY & FUNCTIONALITY ® registered trade mark of BEELE Engineering ®

Upload: others

Post on 06-Jul-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS ALL NOFIRNO®

(MULTI-) CABLE TRANSITS

WE CARE

SAFETYSEALINGSYSTEMS

TECHNOLOGY DEVELOPED BY BEELE ENGINEERING BVCOMPOUNDING AND PRODUCTION IN THE ULTRA-MODERN

MANUFACTURING FACILITIES IN AALTEN/THE NETHERLANDS UNDER A STRINGENT ISO 9001:2015 QUALITY SYSTEM

MORE THAN 40 YEARS R&D ON QUALITY, DURABILITY & FUNCTIONALITY

® registered trade mark of BEELE Engineering

®

Page 2: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Copyright : BEELE Engineering BV/CSD International BV, Aalten, the Netherlands. Proprietary rights on all drawings and technical data released in this brochure. © 1997-2018

Edition : May 2018

Note : No part of this publication may be reproduced without explicit written approval of BEELE Engineering BV.

Research & Development : BEELE Engineering BV, Aalten, the Netherlands.

Note : Themanufacturerreservestherighttomakedimensionalanddesignmodifications withoutpriornotification.

® : ACTIFOAM, AQUASTOP, BEEBLOCK, BEEBOND, BEELE, BEELE WE CARE, BEESEAL, BEMITITE, BLOCKSTACK, CONDUCTON, CONTITITE, CONTROFIL, CRUSHER, CRUSHNOF, CSD, CSD THE SIMPLE SEAL SYSTEM, DRIFIL, DYNATITE, FIRAQUA, FIREQUAKE, FIRSTO, FISSIC, FIWA, FYLLOFYS, GLANDMOD,LEAXEAL,MULTI-ALL-MIX,NOFIRNO,profilesNOFIRNOgaskets,RAPIDTRANSITSYSTEM, REVITITE, RESITITE, RIACNOF, RISE, RISWAT, SEALING VALLEY, S,SLIPSIL,flangesSLIPSILplugs, ULEPSI, XATTAX and YFESTOS are registered trade marks of BEELE Engineering.

brochure code : installation NOFIRNO cable

Beele campus 45.000 m²building phase 1 started september 2017

ca. 300 meter

railway station College Schaersvoorde

Technasium

Page 3: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

1

WE CARE

SAFETYSEALINGSYSTEMS

Notonlyforstandardcellulosefires,butalsoforapplicationswithhighestfireandtightnessratings(up to HC and Jet Fires) the NOFIRNO® sealing system is used. The NOFIRNO® multi-cable transit sealing system is composed of NOFIRNO® insert (cable) sleeves in 29 different sizes, NOFIRNO® (multi-)fillersleevesin5differentsizesandNOFIRNO® sealant. The use of NOFIRNO®multi-fillersleevescontributestoeaseofinstallation.

Page 4: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

2

NOFIRNO® is absolutely HALOGEN FREE with zero VOC (volatiles organic compounds) according to TÜV report 89206405-01. Furthermore NOFIRNO® has a low smoke index and a high oxygen index (ISO 4589-2: 1996), and low flame spread characteristics according to IMO Resolution A.653(16).NOFIRNO® is a paste-like compound which is simple to use. NOFIRNO® has a balanced viscosity and can be applied overhead.

artic

le n

umbe

r 50.

0102

PRODUCT INFORMATION SEALANT01) colour red brown02) specificgravity 1.40±0.03g/cm3

03) curing of top layer 0.5 - 1 hour depending on temperature and air humidity04) service temperature -50 °C up to +180 °C05) tensile strength 1.5 MPa06) elongation at break 200%07) hardness 45 Shore A08) elastic deformation approx. 50%09) resistance UV, Ozone, arctic conditions10) ageing more than 20 years11) supplied in 310 ml cartridges12) storage to be stored cool and dry min/max temperature = +5/+30° C13) storage life guaranteed 6 months; when applied later than 6 months after date of manufacturing, curing and adhesive properties have to be checked before application

artic

le n

umbe

r 50.

0105

artic

le n

umbe

r 50.

0104

artic

le n

umbe

r 50.

0106

whiteblack blue grey

artic

le n

umbe

r 50.

0111

concrete grey

WE CARE

SAFETYSEALINGSYSTEMS

Page 5: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

3

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

NOFIRNO® cable insert sleeves are used to separate cables inside the conduit opening. This allows for ease of application of the NOFIRNO® sealant in between and around the ducted cables. The NOFIRNO® cable sleeves are available in 29 sizes and in lengths of 60, 80, 110, 130, 140, 160 and 210 mm. The NOFIRNO® cable insert sleeves are split lengthwise and can therefore be placed around the cables in front of the conduit opening.

NOFIRNO® CABLE INSERT SLEEVES

cable insert sleeves are split lengthwiseOperating temperatures:-50 °C up to +180 °C

Page 6: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

NOFIRNO®

sleevecable

diametersleevelength

articlenumber

sleevelength

articlenumber

sleevelength

articlenumber

sleevelength

articlenumber

12/614/816/1018/1220/1422/1626/1828/2030/2232/2434/2636/2838/3042/3346/3649/3952/4255/4558/4862/5266/5670/6074/6478/6882/7286/7695/80100/85110/90

5 - 77 - 99 - 1111 - 1313 - 1515 - 1717 - 1919 - 2121 - 2323 - 2525 - 2727 - 2929 - 3232 - 3535 - 3838 - 4141 - 4444 - 4747 - 5151 - 5555 - 5959 - 6363 - 6767 - 7171 - 7575 - 7979 - 8484 - 8989 - 94

60

50.100050.100150.100250.100350.100450.100550.100650.100750.100850.100950101050.101150.101250.101350.101450.101550.101650.101750.101850.101950.102050.102150.102250.102350.102450.102550.102650.102750.1028

80

50.124050.124150.124250.124350.124450.124550.124650.124750.124850.124950125050.125150.125250.125350.125450.125550.125650.125750.125850.125950.126050.126150.126250.126350.126450.126550.126650.126750.1268

110

50.104050.104150.104250.104350.104450.104550.104650.104750.104850.104950105050.105150.105250.105350.105450.105550.105650.105750.105850.105950.106050.106150.106250.106350.106450.106550.106650.106750.1068

130

50.120050.120150.120250.120350.120450.120550.120650.120750.120850.120950121050.121150.121250.121350.121450.121550.121650.121750.121850.121950.122050.122150.122250.122350.122450.122550.122650.122750.1228

NOFIRNO® CABLE INSERT SLEEVES

all d

imen

sion

s in

mm

all d

imen

sion

s in

mm

all d

imen

sion

s in

mm

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

4

all d

imen

sion

s in

mm

NOFIRNO®

sleevecable

diametersleevelength

articlenumber

sleevelength

articlenumber

sleevelength

articlenumber

sleevelength

articlenumber

12/614/816/1018/1220/1422/1626/1828/2030/2232/2434/2636/2838/3042/3346/3649/3952/4255/4558/4862/5266/5670/6074/6478/6882/7286/7695/80100/85110/90

5 - 77 - 99 - 1111 - 1313 - 1515 - 1717 - 1919 - 2121 - 2323 - 2525 - 2727 - 2929 - 3232 - 3535 - 3838 - 4141 - 4444 - 4747 - 5151 - 5555 - 5959 - 6363 - 6767 - 7171 - 7575 - 7979 - 8484 - 8989 - 94

140

50.108050.108150.108250.108350.108450.108550.108650.108750.108850.108950109050.109150.109250.109350.109450.109550.109650.109750.109850.109950.110050.110150.110250.110350.110450.110550.110650.110750.1108

160

50.112050.112150.112250.112350.112450.112550.112650.112750.112850.112950113050.113150.113250.113350.113450.113550.113650.113750.113850.113950.114050.114150.114250.114350.114450.114550.114650.114750.1148

210

50.116050.116150.116250.116350.116450.116550.116650.116750.116850.116950117050.117150.117250.117350.117450.117550.117650.117750.117850.117950.118050.118150.118250.118350.118450.118550.118650.118750.1188

all d

imen

sion

s in

mm

all d

imen

sion

s in

mm

all d

imen

sion

s in

mm

WE CARE

SAFETYSEALINGSYSTEMS

Page 7: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

NOFIRNO®fillersleevesaresuppliedinmulti-setsof6,8and10sleeves,dependingontheouterdimensions of the sleeves. Single sleeves or smaller sets of sleeves can be torn off easily. To tear off sleeves from the multi-set, the procedure is to do this backwards/forwards and not sideways. This is because of the strength of the intermediate rubber parts.

NOFIRNO® MULTI-FILLER SLEEVES

fillersleevesarenotsplitlengthwiseOperating temperatures:-50 °C up to +180 °C

5

WE CARE

SAFETYSEALINGSYSTEMS

Page 8: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

NOFIRNO® MULTI-FILLER SLEEVES

fillersleevesaresuppliednon-splitOperating temperatures:-50 °C up to +180 °C N

OFI

RN

mul

ti-fil

ler s

leev

e 22

/15

art.

no. 8

0.50

70 fo

r 60

mm

leng

thar

t. no

. 80.

5076

for 8

0 m

m le

ngth

art.

no. 8

0.50

71 fo

r 110

mm

leng

thar

t. no

. 80.

5075

for 1

30 m

m le

ngth

art.

no. 8

0.50

72 fo

r 140

mm

leng

thar

t. no

. 80.

5073

for 1

60 m

m le

ngth

ar

t. no

. 80.

5074

for 2

10 m

m le

ngth

NO

FIR

NO

® m

ulti-

fille

r sle

eve

10/4

art.

no. 5

0.03

01 fo

r 60

mm

leng

thar

t. no

. 50.

0361

for 8

0 m

m le

ngth

art.

no. 5

0.03

11 fo

r 110

mm

leng

thar

t. no

. 50.

0351

for 1

30 m

m le

ngth

ar

t. no

. 50.

0321

for 1

40 m

m le

ngth

art.

no. 5

0.03

31 fo

r 160

mm

leng

th

art.

no. 5

0.03

41 fo

r 210

mm

leng

th

NO

FIR

NO

® m

ulti-

fille

r sle

eve

18/1

2ar

t. no

. 80.

5050

for 6

0 m

m le

ngth

art.

no. 8

0.50

56 fo

r 80

mm

leng

thar

t. no

. 80.

5051

for 1

10 m

m le

ngth

art.

no. 8

0.50

55 fo

r 130

mm

leng

thar

t. no

. 80.

5052

for 1

40 m

m le

ngth

art.

no. 8

0.50

53 fo

r 160

mm

leng

th

art.

no. 8

0.50

54 fo

r 210

mm

leng

th

NO

FIR

NO

® m

ulti-

fille

r sle

eve

15/8

art.

no. 5

0.03

02 fo

r 60

mm

leng

thar

t. no

. 50.

0302

for 8

0 m

m le

ngth

art.

no. 5

0.03

62 fo

r 110

mm

leng

thar

t. no

. 50.

0352

for 1

30 m

m le

ngth

ar

t. no

. 50.

0322

for 1

40 m

m le

ngth

art.

no. 5

0.03

32 fo

r 160

mm

leng

th

art.

no. 5

0.03

42 fo

r 210

mm

leng

th

NO

FIR

NO

® m

ulti-

fille

r sle

eve

20/1

2ar

t. no

. 50.

0303

for 6

0 m

m le

ngth

art.

no. 5

0.03

63 fo

r 80

mm

leng

thar

t. no

. 50.

0313

for 1

10 m

m le

ngth

art.

no. 5

0.03

53 fo

r 130

mm

leng

thar

t. no

. 50.

0323

for 1

40 m

m le

ngth

art.

no. 5

0.03

33 fo

r 160

mm

leng

th

art.

no. 5

0.03

43 fo

r 210

mm

leng

th

to be used for smaller conduit openings

to b

e us

ed fo

r lar

ger c

ondu

it op

enin

gs

to b

e us

ed fo

r lar

ger c

ondu

it op

enin

gs

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

6

WE CARE

SAFETYSEALINGSYSTEMS

Page 9: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The tools needed for the installation are a steel brush, a tie-wrap cutter, a cutter for the nozzles of the sealantcartridges,flatnoseplierstoadjustthesetoffillers,afillersetadjuster,atoolforpressingthesealant layer in between the cables, cloths for cleaning and compression of the sealant layer, a cable cleaner, wet soap, a bucket with water and a professional sealant dispenser.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

7

WE CARE

SAFETYSEALINGSYSTEMS

Page 10: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

8

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The transit frames might be welded into the partition long before cable pulling will start. For this reason, the condition of the inside of the frame has to be checked when starting cable pulling. Before insertion of the NOFIRNO®cableandfillersleeves,theinsideofthetransitframeshastobecleaned, and any dirt, oil, grease and other residues or corrosion should be removed from the inside of the transit frame.Note:forfireresistantpenetrationsthemax.sizeofthetransitframeis600x300mmorequivalentof1800 cm².

WE CARE

SAFETYSEALINGSYSTEMS

Page 11: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

9

With a steel brush or by blasting, the corroded inner surface of the transit frame should be treated to remove these corroded spots. The excellent adhesive properties of the sealing system will be diminished by corroded surfaces.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 12: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The NOFIRNO®sealingsystemiscomposedofcableandfillersleeves,andlayersofsealant.Thesleeves are the backing on which the sealant is going to be applied. A 15 mm thick layer of sealant is applied at both sides of the penetration. Before welding the transit frame into the partition, check if thetransitframeisdeepenoughtobeinlinewiththecertificationofthesealingsystem(minimum160 mm). The NOFIRNO® sleeves are 30 mm shorter in length than the depth of the transit frame. Note: for high rated watertight penetrations, the transit frame should be either of a limited size or partitions should be placed inside the larger transit frames to divide the frame in smaller sections.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

10

WE CARE

SAFETYSEALINGSYSTEMS

Page 13: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The cables can be ducted through the transit frame in random order. It is most important that they are not pulled too tight so as not to hamper their separation when NOFIRNO® insert sleeves are inserted. Open transits at site allow for pulling more cables through than planned. Sealing the multi-cable penetrationwillthenbedifficultornotpossibleatall.Tangledcablesetscanmaketheinstallationofthesealingsystemextremelydifficult.Easeofinstallationstartswithorganizedpullingofthecablesthroughthe transit frames.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

11

WE CARE

SAFETYSEALINGSYSTEMS

Page 14: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The cable tie-wraps have to be removed to create enough play in between the cables to enable cleaning of the cables and to allow insertion of the NOFIRNO® cable sleeves in a later stage.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

12

WE CARE

SAFETYSEALINGSYSTEMS

Page 15: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Foradequatecleaningpurposes(whichisanimportantstep),thecablescouldbeliftedwithabandtocreatesufficientaccesstotheinnerwallofthetransitframe.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

13

WE CARE

SAFETYSEALINGSYSTEMS

Page 16: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Finalsealingofthecablepenetrationmaybequitesometimeaftercablepulling.Insuchasituation,the status of the inside of the transits frames has to be checked again when starting with the installation of the sealing system. Clean the inside of the transit frames thoroughly and remove any dirt, oil, grease and other residues or corrosion from the inside of the transit frame.

14

WE CARE

SAFETYSEALINGSYSTEMS

Page 17: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Clean and dry the cables thoroughly in a similar way. Any moisture, dirt or oil residues will have a negative impact on the adhesive properties of the NOFIRNO®sealanttobeappliedafterfillingthetransit frame.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

15

WE CARE

SAFETYSEALINGSYSTEMS

Page 18: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The cables have to be cleaned at the spot where the sealant is applied in a later stage. This means 15 mm at both sides of the transit. If feasible, it is of course easier to clean the cables over their full length inside the transit.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

16

WE CARE

SAFETYSEALINGSYSTEMS

Page 19: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Although the system is tested with the cables separated from the wall of the transit frame by the thickness of the NOFIRNO® cable sleeves, it is advisable to have a layer of NOFIRNO® multi-sleeves at the bottom of the transit frame prior to spread out the cables.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

17

WE CARE

SAFETYSEALINGSYSTEMS

Page 20: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

By lifting the cables the set(s) of NOFIRNO® multi-fillersleevescanbeeasilyplacedinsidethetransitframe.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

18

WE CARE

SAFETYSEALINGSYSTEMS

Page 21: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The cables are then separated as far as possible on top of the NOFIRNO®multi-fillersleeves.The application of the NOFIRNO®multi-fillersleevesunderneaththecablesmakestheapplicationofthesealantforfinalfinishingatthebottomofthetransitnotonlyeasierbutalsomoreeffective.NOFIRNO®multi-fillersleevesalsopreventthecablesfromtouchingthesteelframe,whichcanleadto shaving and damaging the cables.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

19

WE CARE

SAFETYSEALINGSYSTEMS

Page 22: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

NOFIRNO®cableinsertsleevesareseparatorsandnotprecisefillingparts.Applyingoversizedsleevesaroundthecableswillreducethefillingcapacityofthesealingsystem.Duetothefactthatthe NOFIRNO® rubber is very endothermic and is fully protected by the NOFIRNO® sealant, this will not,however,haveaninfluenceonthefireratingaslongthesleevesarenotextremelyoversized.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

20

WE CARE

SAFETYSEALINGSYSTEMS

Page 23: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

AprecisefitoftheNOFIRNO®cablesleevesaroundthecablesisnotrequired,howeveritisnotallowed to use undersized cable sleeves leaving a larger open space around the cable. See the tables on page 6.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

21

WE CARE

SAFETYSEALINGSYSTEMS

Page 24: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

NOFIRNO® cable sleeves are applied around each cable. The cable sleeves are split lengthwise and can therefore be placed around the cables in front of the conduit.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

22

WE CARE

SAFETYSEALINGSYSTEMS

Page 25: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Push the insert sleeves into the transit frame in such a way as to leave about 15 mm free space at thefrontandtheback.Atthisstage,andcertainlywithalowfillingrateofcables,theinsertiondoesnothavetobepreciseinthisregard.Adjustmentofthesetofsleevestothe15mmrecesscanbecarriedoutjustbeforeapplyingthesealant.However,withhigherfillingratesitmightbedifficulttocorrect afterwards.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

23

WE CARE

SAFETYSEALINGSYSTEMS

Page 26: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

TheremainingfreespaceintheconduitopeningisfilledwithNOFIRNO®fillersleevestype18/12,20/12 or 22/15 or a combination of these types. The smaller sleeves sizes 10/4 and 15/8 are used thefillsmalleropenspacespresentinthecompletesetoffillersleeves.Foreaseoffilling,theNOFIRNO®fillersleevesaresuppliednon-split.Theyaredeliveredalsoasmulti-fillersleeves(multi-sets of 6, 8 and 10 sleeves)whichisextremelyhelpfulforfillinglargeremptyspaces.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

24

WE CARE

SAFETYSEALINGSYSTEMS

Page 27: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

For later extensions, it is advisable to use NOFIRNO®singlefillersleeves,sincetheyareeasiertoremove when a new cable has to be ducted.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

25

WE CARE

SAFETYSEALINGSYSTEMS

Page 28: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

26

It is allowed to use one type of NOFIRNO®fillersleevesonlyoramixofalltypesofNOFIRNO®fillersleeves.

WE CARE

SAFETYSEALINGSYSTEMS

Page 29: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Thesmalleropeningsarenowfilledwithpartsofthesetsofmulti-fillersleeves.Totearoffsleevesfromthe multi-set, the procedure is to do this backwards/forwards and not sideways. This is because of the strength of the intermediate rubber parts.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

27

WE CARE

SAFETYSEALINGSYSTEMS

Page 30: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Withaflatnosepliers,NOFIRNO®singlefillersleevesareinsertedintheremainingsmalleropenspacesinthesetoffillers.Averytightfitofthefillingisvitaltotheperformanceofthesealingsystem.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

28

WE CARE

SAFETYSEALINGSYSTEMS

Page 31: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Withapieceofwoodmarkedwiththerequired15mmdepth,orwiththebyBEELEEngineeringdevelopedaluminumadjuster,thesetoffillerscanbeadjustedtotherequired15mmrecessinsidethetransit.UseaplastichammertoadjustthesetoffillersleeveswiththeNOFIRNO®adjuster.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

29

WE CARE

SAFETYSEALINGSYSTEMS

Page 32: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Thefillersetcanbefurtheradjustedwiththeaidofaflatnosepliers.Singlefillersleevessometimesmightbe inserted too deep. A ca. 15 mm free space at the front and back of the sealing system (+/- 2 mm tolerance is acceptable) is a must to obtain optimum sealing capacity of the sealing system.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

30

WE CARE

SAFETYSEALINGSYSTEMS

Page 33: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Before applying the NOFIRNO®sealant,itisadvisabletoperformafinalcheckonthepackingofinsertandfillersleeves.Atightfitofthewholesetofsleeves,intherequiredratio,isnotonlyvitalforthemechanicalstabilityofthesealingsystem,butalsoforthefirestoppingproperties.Afinalcheckshouldthereforebeapartofqualitycontrol.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

31

WE CARE

SAFETYSEALINGSYSTEMS

Page 34: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Final smoke, gas and watertight sealing of the NOFIRNO® multi-cable transits is achieved with the application of NOFIRNO® sealant. NOFIRNO® sealant has proven excellent performance with regard tomechanicalandfireresistancerequirements.TheNOFIRNO® sealing system has been successfully exposed to severe pressure, shock and vibration tests.

32

WE CARE

SAFETYSEALINGSYSTEMS

Page 35: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Cuttheinjectionnozzlesofthecartridgesinanangledwaytocreateamediumsizeddispersingopening.Thiswillimprovetheflowofthesealantinbetweenthesetofcables.Furthermore,itisadvisabletouseprofessionalsealantguns.Handfatigueisprevented,andanoptimumflowofthesealant is obtained. For larger penetrations, electric or pneumatic dispensers should be used.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

33

WE CARE

SAFETYSEALINGSYSTEMS

Page 36: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

A 15 mm thick layer of NOFIRNO® sealant is applied at each side of the NOFIRNO® multi-cable transit. NOFIRNO® sealant has an engineered viscosity, preventing the sealant from sagging and also allow-ingforaperfectflowofthesealantbetweenthecablesduringinjection.Formulti-cabletransitswithahighfillingrate,longernozzlesareavailableforthesealantcartridges.People with sensitive skin should use gloves when working with NOFIRNO®. Please refer to the Safety Data Sheet for more information.

34

WE CARE

SAFETYSEALINGSYSTEMS

Page 37: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Themulti-cabletransitshouldbeoverfilledwithNOFIRNO® sealant, because some sealant will be pushed into the empty spaces between the NOFINO® sleeves around the cables, and into the hollow NOFIRNO®(multi)fillersleevesduringfurtherfinishing.Thiswillcontributealsotoobtainhighertightness ratings. Skin formation of the sealant takes place after ca. 10-15 minutes. In case of larger transits with a low cablefillingrate,donotapplymoresealantthancanbefinishedwithinthistime-frame.

35

WE CARE

SAFETYSEALINGSYSTEMS

Page 38: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

To smooth the surface of the NOFIRNO® sealant layer, a cloth is sprayed with water. This prevents the sealant from sticking to the cloth. Note: do not use soap water! Soap water will have a negative impact on the adhesive properties of the sealant.

36

WE CARE

SAFETYSEALINGSYSTEMS

Page 39: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Theclothisthenusedtopressdownthesealantlayerflushwiththeendofthetransitframe.Itisof utmost importance to ensure that the sealant is compressed very tightly so that the sealant is compressed into all empty spaces of the set of NOFIRNO® sleeves, including partially into the hollowfillersleeves.Thelargertheadhesivesurfacesofthesealant,thehighertheperformanceofthe system.Note: do not use soap water! Soap water will have a negative impact on the adhesive properties of the sealant.

37

WE CARE

SAFETYSEALINGSYSTEMS

Page 40: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Due to the rapid skin formation of the sealant, smoothing should take place directly after compression of the sealant layer. As soon as skin formation takes place, a very neat smoothing of the sealant layer is not possible anymore.Note: the NOFIRNO® sealant is water repellent so that water will drip off. Neat smoothing is helpful in this respect. The NOFIRNO® sealant is also seawater, UV, ozone and weathering resistant and offers a durability of decades.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

38

WE CARE

SAFETYSEALINGSYSTEMS

Page 41: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The NOFIRNO® sealant between the cables is pressed down and smoothed by hand or with a spatula or putty knife. A special tool, developed by BEELE Engineering, with a PTFE compression/smoothing part is available. The sealant will not stick to the PTFE.

Compression and smoothing, especially in between the cables, is essential to obtain an effective gas and water tightness.

39

WE CARE

SAFETYSEALINGSYSTEMS

Page 42: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

A last check should be made to ensure that the sealant layer is pressed down tightly and that no larger open holes are visible. Air enclosure within the individual layer of sealant should be prevented during finishing,becausethiswouldhaveanegativeimpactontheperformanceofthesealantlayerunderfireexposure.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

40

WE CARE

SAFETYSEALINGSYSTEMS

Page 43: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The surface can be smoothed by hand. Just wet the hands thoroughly with soap and water. No dirty hands when working with NOFIRNO® and a very neat surface is the result. Note: this should only be a smoothing procedure. Do not pack or compress the sealant further when using soap water.

People with sensitive skin should use gloves when working with NOFIRNO®. Please refer to the Safety Data Sheet for more information.

41

WE CARE

SAFETYSEALINGSYSTEMS

Page 44: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Toobtainoptimumadhesionduringthecuringprocessofthesealant,allthecablesshouldbetightlyfixedatbothsidesofthetransit,ascloseaspossibletothetransit,andimmediatelyafterfinishingthetransit.Movement of the cables during the curing process will impair the adhesion process to the cable sheathings.Note: time needed for curing of the sealant is dependent on air humidity in combination with the environmentaltemperature.Itisadvisabletoplaceastickernearthefinishedtransit,statingthatthetransit has been recently installed, and should not be touched or damaged.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

42

WE CARE

SAFETYSEALINGSYSTEMS

Page 45: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Additional information:applyingthesealantonhighlyfilledmulti-cabletransitscanbequitecomplicated.The sealant can be applied in layers from the bottom to the top after cable pulling. Regardless, checkingifsufficientsealantisappliedinbetweensetsofcablesclosetoeachotherisamust.ThereflectivecolouroftheNOFIRNO® has the advantage that visual inspection of the sealant application in between cables is easier to perform.Waterandgastightnessisdependentonthequalityofthefinalsealing.Asisthecasewithanysystem,workmanship has a direct impact on the performance of the sealing system.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

43

WE CARE

SAFETYSEALINGSYSTEMS

Page 46: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Additional information: bundled cable sets are allowed in the NOFIRNO® multi-cable sealing system, using only a single NOFIRNO® insert sleeve around the bundle of cables. Note: see the approved installation drawings for details. Bundling is limited to approved maximum dimensions.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

44

WE CARE

SAFETYSEALINGSYSTEMS

Page 47: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The sleeve is then pushed into the transit leaving 15 mm free at front and backside.

Note: NOFIRNO® multi-cable transits with bundled cables are not approved for watertight partitions.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

45

WE CARE

SAFETYSEALINGSYSTEMS

Page 48: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Check for all certainty that the sealant has been well packed around the bundle of cables in order to ensureanappropriatedegreeofcoldsmoketightness.Whenexposedtofireand/orheat,theRISE® rubberwillimmediatelyreactandfilltheopeningsinbetweenthecablesandpreventspassageofsmokefromthefireside.TheNOFIRNO® rubber is highly endothermic and will not be consumed bythefire.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

46

WE CARE

SAFETYSEALINGSYSTEMS

Page 49: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The RISE® and NOFIRNO rubber grades of the sleeves and the NOFIRNO® sealant, which are compounded under strict conditions in our factory, are suitable for gas and water tight ducting, and for fireratedapplicationsaswell.TheNOFIRNO®sealantstaysflexibleattemperaturesof-50°C,allowingapplication in arctic environments. The NOFIRNO® multi-cable transits have excellent resistance to seawater, UV, ozone and weather. Based on the use of the high tech silicone composition of the NOFIRNO® sealant and rubber, the system offers excellent durability.

47

WE CARE

SAFETYSEALINGSYSTEMS

Water tight and air tightsealing systems for cabletransits

KIWA 90683-01 2690

MED CERTIFICATE50891/A0

Page 50: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

For A-class penetrations (which are insulated), the NOFIRNO® multi-cable transit frame needs to be insulated only at the insulated side of the bulkhead. No extra insulation needed in front of the transit and/or in between the cables. Tested with larger amounts LAN data cables (bundled as well), up to CLX high voltage cables up to 3 x 380 mm2 with an OD of 105 mm. Note: for the larger cable sizes, NOFIRNO® cable wraps have to be used. Also approved for A-0 class without any insulation.No metal parts are incorporated in the sealing system. The conduit frames cannot corrode inside due to the tight sealant layers at both sides of the transit. No CUI (Corrosion Underneath Insulation).

48

WE CARE

SAFETYSEALINGSYSTEMS

Page 51: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Deck penetrations are also easy to install with the NOFIRNO® system. Remove any cable tie-wraps to providesufficientplayofthecableset.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

49

WE CARE

SAFETYSEALINGSYSTEMS

Page 52: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

To prevent the NOFIRNO® sleeves from sliding down the cables, the sleeve should be a bit undersized to the cable. This allows the sleeves to cling to the cables, preventing them from sliding down. The inner surface structure of the NOFIRNO® cable sleeves will hold the sleeves in place as well.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

50

WE CARE

SAFETYSEALINGSYSTEMS

Page 53: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

By making use of the NOFIRNO®multi-fillersleeves,setsandbundlescanbemadetoensuretightfittinginsidethetransit.WithNOFIRNO®singlefillersleeves,thefillingoflargerverticaltransitswillbemoredifficult.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

51

WE CARE

SAFETYSEALINGSYSTEMS

Page 54: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

52

With the Beele®adjusteroramarkedpieceofwood,thesetoffillersisadjustedinsidethetransit.The NOFIRNO® rubber grade and the NOFIRNO® sealant, which are compounded under strict conditions inourfactory,aresuitableforgasandwatertightducting,andforhighestfireratedapplicationsaswell.NOFIRNO®sleevesandsealantstayflexibleattemperaturesof-50°C,allowingapplicationinarcticenvironments even better than RISE®, and can be exposed to temperatures up to +180 °C as well.

WE CARE

SAFETYSEALINGSYSTEMS

Page 55: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The NOFIRNO®sealantcanbeappliedoverheadfordeck/floortransitswithoutdrippingorsagging.Forcabletransitswithahighfillingrate,longernozzlesforthesealantcartridgesareavailable.

53

WE CARE

SAFETYSEALINGSYSTEMS

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

Page 56: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

To smooth the surface of the NOFIRNO® sealant layer, a cloth is sprayed with water. This prevents the sealant from sticking to the cloth. Note: do not use soap water! Soap water will have a negative impact on the adhesive properties of the sealant.

People with sensitive skin should use gloves when working with NOFIRNO®. Please refer to the Safety Data Sheet for more information.

54

WE CARE

SAFETYSEALINGSYSTEMS

Page 57: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

For A-class penetrations (which are insulated), the NOFIRNO® multi-cable transit frame needs to be insulated only at the at the lower side of the deck. No extra insulation needed in front of the penetration and/or in between the cables. Tested with larger amounts LAN data cables (bundled as well), up to CLX high voltage cables with conductors up to 3 x 380 mm2 with an OD of 105 mm.Note: for the larger cable sizes, NOFIRNO® cable wraps have to be used.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM (DECK)

55

WE CARE

SAFETYSEALINGSYSTEMS

Page 58: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Flangedframeswithaflangeforbolting(60mmwideand6mmthick)withaholeconfigurationforfixation,canbeusedalsofortheNOFIRNO® multi-cable sealing system.

56

WE CARE

SAFETYSEALINGSYSTEMS

Page 59: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Theflangedtransitframesareboltedagainstthepartition.AfiresafeNOFIRNO® gasket has to be appliedbetweentheflangeofthetransitframeandthepartition.Thegasketshaveadesignedprofilingtoexcludetheneedforexcessivecompression(6-10Nmissufficient).Thereducedforcesontheprofiledrubbermaketheusualneedforretighteningfromtimetotimeathingofthepast.

57

WE CARE

SAFETYSEALINGSYSTEMS

Page 60: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

For A-class penetrations (which are insulated), the NOFIRNO® multi-cable transit frame needs to be insulated only at the insulated side of the bulkhead or at the lower side of the deck. No extra insulation needed in front of the penetration and/or in between the cables. Tested with larger amounts LAN data cables (bundled as well), up to CLX high voltage cables with conductors up to 3 x 380 mm2 with an OD of 105 mm.Note: for the larger cable sizes, NOFIRNO® cable wraps have to be used.

58

WE CARE

SAFETYSEALINGSYSTEMS

Page 61: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

AddingextracablesthroughafinishedNOFIRNO®multi-cabletransitisaneasyjob.WiththeuseofNOFIRNO®fillerandcablesleevesasseparators,nopermanentdeformationoftherubberpartswilloccur, and the cables are ducted individually. This means there is no need to disassemble the whole transit. Cut away the sealant layer at both sides of the penetration with a plastic knife or a hollow punch in a taperingshape,ataspotwherethereissufficientsparespacevisibleonthesurfaceofthesealantlayer.

59

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 62: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Remove one or more NOFIRNO®fillersleevestocreateafittingopeningforthecabletobeducted.

60

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 63: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

A cable is pulled through the free passage opening in the NOFIRNO® multi-cable transit. For adding cables, thereisinfactnomoredisassemblingneededthanremovingsomefillersleeves.Noextracostsfortheextension of the cable set other than some new sealant to be applied.

619

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 64: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Place a NOFIRNO® sleeve around the newly ducted cable. Push the insert sleeve into the conduit so that it is even with the other sleeves.

62

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 65: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Cleananddrythenewlyductedcablethoroughlyandrefilltheopeninginthesealantlayeratbothsidesof the transit with NOFIRNO® sealant. The fresh sealant adheres very well to the already cured sealant. Finish the new sealant layer in the same way as done for the initial sealant layer.

63``

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 66: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Note: time needed for curing of the sealant is dependent on air humidity in combination with the environmental temperature.

64

INSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

WE CARE

SAFETYSEALINGSYSTEMS

Page 67: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

ThespaceinsidethetransitframeisfilledwithNOFIRNO®fillersleevestype22/15.Foreaseoffilling,theNOFIRNO®fillersleevesaresuppliednon-split.Multi-fillersleeves(setof10)arepreferredforfillinglargerspaces.Filling the conduit frame with NOFIRNO®multi-fillersleevesstartswithstackingthemulti-setontopofeach other and to place rolled-up sets of multi-sleeves in the corners.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® BLIND TRANSIT SEALING SYSTEM

65

WE CARE

SAFETYSEALINGSYSTEMS

Page 68: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

Before applying the NOFIRNO®sealant,itisadvisabletoperformafinalcheckonthepackingofthefillersleeves.Atightfitofthewholesetofsleevesintherequiredratioisnotonlyvitalfortheme-chanicalstabilityofthesealingsystem,butalsoforthefirestoppingproperties.Afinalcheckshouldthereforebeapartofqualitycontrol.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® BLIND TRANSIT SEALING SYSTEM

66

WE CARE

SAFETYSEALINGSYSTEMS

Page 69: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

The NOFIRNO rubber grade of the sleeves and the NOFIRNO® sealant, which are compounded under strictconditionsinourfactory,aresuitableforgasandwatertightducting,andforfireratedapplicationsas well. The NOFIRNO®sealantstaysflexibleattemperaturesof-50°C,allowingapplicationinarcticenvironments. The NOFIRNO® blind transits have excellent resistance to seawater, UV, ozone and weather. Based on the use of the high tech silicone composition of the NOFIRNO® sealant and rubber, the system offers excellent durability.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® BLIND TRANSIT SEALING SYSTEM

67

WE CARE

SAFETYSEALINGSYSTEMS

Page 70: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

For A-class penetrations (which are insulated), the NOFIRNO® blind transit frame needs to be insulated only at the insulated side of the bulkhead or the lower side of the deck. No extra insulation needed in front of the transit.A-0 blind transits to be insulated as for A-60 200 mm around.

Also approved for deck penetrations.

INSTALLATION INSTRUCTIONS FOR NOFIRNO® BLIND TRANSIT SEALING SYSTEM

68

WE CARE

SAFETYSEALINGSYSTEMS

Page 71: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

STATE-0F-THE ART MULTI-CABLE TRANSIT

SEALING SYSTEMS

CONTROFILMULTI-CABLE TRANSITS

CET-A-SIL

RISE®

• For fire, gas, smoke and watertight sealing of multi-cable penetrations.

• Compact system. No precise fitting parts.• No metal parts, no corrosion. • Most cost-effective way of installation.• No pre-engineering or special conduit frames. • No restrictions on cable types and sizes, no

insulation in front of the penetration needed. • Adding or removing cables an easy matter.• RISE® EXTEND-A-FRAME for upgrading block

systems - doubles the usable space!• RISE® CONDUCTON® for EMC penetrations -

high attenuation values - no galvanic corrosion - no aging.

• Proven - for new and upgraded installations.• The system of choice in shipyards worldwide for

more than 25 years!

NOFIRNO®

• System technology based on RISE®. • Even easier installation.• Even higher pressure ratings. • Jet Fire tested for harshest applications.• A-0 and H-0 up to A-60 and H-120.• Breakthrough - bundled cable sets approved.• The system of choice for highest fire ratings

and harshest environment!

CONTROFIL®

• Newest technology for cable ducting and sealing. • Newest rubber technology - CRUSHNOF® rubber.• Shorter conduit depths - flexible composition.• Prevents overfilling of cable transits.• Fire tight - watertight.• Breakthrough - controlled filling of transits.• The system of choice for neat cable routing in

installations.

CET-A-SIL®

• Multi-gland system for electrical cabinets. • Modular system - sealing plugs and modules.• Suitable for IP 68 rated equipment.• Watertight up to 4 meter water column. • No compression on cable sheathings.• No metal parts - no corrosion - no O-rings.• Breakthrough - no disassembling to add cables.• The alternative system for cable glands.

69

Page 72: INSTALLATION INSTRUCTIONS ALL NOFIRNO …stenca.dk › upload › Nofirno › installation_NOFIRNO_cable.pdfINSTALLATION INSTRUCTIONS FOR NOFIRNO® MULTI-CABLE TRANSIT SEALING SYSTEM

BEELE Engineering bvBeunkdijk 11 - 7122 NZ AALTEN - THE NETHERLANDS

Tel. +31 543 461629 - Fax +31 543 461786 - E-mail: [email protected]: https://www.beele.com, sealingvalley.com and fissiccoating.com

BEELE ENGINEERING:A COMPANY DEDICATED TO SAFETY

FOR OVER 40 YEARS

WE CARE