installation, commissioning, testing and trouble shooting

3

Click here to load reader

Upload: waelhaddad12

Post on 14-Dec-2015

8 views

Category:

Documents


2 download

DESCRIPTION

Installation, Commissioning, Testing and Trouble shooting

TRANSCRIPT

Page 1: Installation, Commissioning, Testing and Trouble Shooting

   

 

                                

 

INSTALLATION, COMMISSIONING,  TESTING AND TROUBLESHOOTING     

 

LINEAR TEMPERATURE SENSING CABLE ‐ INSTALLATION GUIDANCE NOTES   

 The PROLINE type TH digital  linear heat sensor cable employs 2 x tin plated copper coated steel conductors which are twisted and tensioned during manufacture to ensure maximum physical contact for alarm signaling.  During  installation  it  is highly recommended that a degree of tension  is maintained on the cable as  it  is un‐reeled and that only the length being fixed locally be reeled off at any one time.  This will ensure ease and efficiency of installation.  Installation of the sensor cable is recommended at ‐10C or above.  Continuous operation at ‐30C has been UL tested and ‐40C/‐40F by F.M.  The Linear Heat Detector must be  installed without “tees or spurs”  in accordance with applicable sections of NFPA 70 National  Electrical  Code,  NFPA  72  National  Fire  Alarm  Code,  local  recognized  and  adopted  Fire  detection  system standards or authority having jurisdiction.  For space/open area risk applications the heat sensor cable may be installed at ceiling level within 500mms – 20 inches – of the ceiling.  The Linear heat sensor also has the benefit of being suitable for  installation close to the point of risk.   Care must always be taken to ensure the sensor cable presents no physical obstruction to routine maintenance or repair of  the  protected  risk,  as  this may  result  in  the  removal  of  the  sensor  cable  for  such work without  is  subsequent replacement.  On  smooth  ceilings  the  distance  between  detector  runs  shall  not  exceed  the  U.L.  Listed    10.6metes  or  35ft recommended spacing.  With sensor cable runs closest to outer walls at 50 percent of the listed spacing.  When  linear  detection  systems  are  used  to  activate  extinguishing  systems  –  special  spacing  guidelines may  also  be applicable to the specific hazard protected.  Professional  fire  engineering  judgement must  be  applied  in  determining  final  detector  location  and  spacing  on  all installations.  Where  required  2  conductor  short  term  fireproof  interconnecting  cable may be  installed between  risk  area  located linear heat sensor cable and remotely installed interface unit.  Maximum 50 ohms resistance where Proline ZI interface units are used.  HAZARDOUS AREA USAGE  PROLINE interface units MUST always be installed within a site designated SAFE area using end user or authority having jurisdiction acceptable short term fire‐proof  interconnecting cable between the  interface and hazardous area  installed Eexe junction box and linear heat sensor cable.  An MTL 7758+ zener barrier – BASEEFA certification BAS01ATEX7217/Ex01E2219, ATEX certified MTL02ATEX7700BX or Pepperl + Fuchs GmbH Z757 – ATEX approval BAS01ATEX7005 Issue 7 is to be connected between the interface unit and interconnecting or linear heat sensing cable.   

  

                                

Page 2: Installation, Commissioning, Testing and Trouble Shooting

   

 

                                    

PRODUCT COMMISSIONING PROCEDURES     

PASSIVE CHECKS  Visually inspect the linear heat sensor cable to re‐confirm correct alarm  temperature  rating  has  been  supplied  and  installed  in accordance with customer specification.    Check  EACH  sensor  cable  for  mechanical  damage  and  that correct fixing Devices have been utilized with maximum spacing’s between  fixings  kept  in  accordance  with  manufacturers’ recommendations.  Ensure the sensor cable  is not  installed against sharp edges and that all bends do not exceed specified minimum bend radius  Verify correct installation location of the sensor cable.  Inspect ALL sensor cable  joints and terminations to ensure they are  correctly  installed  and  appropriate  for  the  application  and local environment  Ensure  the correct end of  line  resistor value has been used  for the  interface  or  central  control  equipment  to  which  it  is connected.  Check  correct wiring  connection  of  the  sensor  cable  for  open circuit  fault/trouble  and  short  circuit  fire/alarm  signaling.    This should be either:  

a. Directly to a Central Fire Alarm Control Panel b. Via end user acceptable interconnecting cabling c. Through a PROLINE supplied ZI interface unit 

 

ACTIVE CHECKS PLEASE  DISABLE  ASSOCIATED  EXTINGUISHING  SYSTEM OPERATION  OR  CENTRAL  FIRE  STATION  SIGNALLING  PRIOR TO CARRYING OUT THE FOLLOWING: REMEMBER TO RE‐ENABLE THE SAME UPON COMPLETION OF CHECKS.  Check  sensor  cable  conductor  resistance  is  within  the manufacturing specification range of 88.1 to 92.1 ohms/1000 metres sensor cable length  Verify correct fault or trouble alarm signaling at sensor cable interface unit where  supplied and at any  central Fire Alarm Control Panel  to which  the  linear detection  is  connected by disconnecting one of  the  sensor  cable  conductors  from  the in‐line or end of line terminations.    Verify correct alarm signaling by placing a short circuit across the  sensor  cable  conductors.  After  correct  signaling  is confirmed remove the short circuits and re‐set the system.  Where PROLINE supplied ZI‐01 single channel interfaced units are  installed please  read  the  Installation & Operating  guide supplied with the device.   This includes description of the following three points: 

1. Local and remote sensor cable termination 2. Simple push button calibration facility  3. Accurate point location indication via a colour coded 

backlit LCD display.  

 

THE  ABOVE  CHECK  SHOULD  BE  CARRIED  OUT  BY  QUALIFIED  –  END  USER  SITE  APPROVED  INDIVIDUALS  AND SHOULD BE PERFORMED UPON INITIAL EQUIPMENT INSTALLATION AND AT LEAST ONCE A YEAR THEREAFTER – or more frequently if required by authority having jurisdiction.  

 

           

                                

Page 3: Installation, Commissioning, Testing and Trouble Shooting

   

 

                                

 PRODUCT TEST PROCEDURES  

Please ensure that all devices designed to operate automatically upon receipt of an alarm condition from the linear heat detection system are first disabled before carrying out the following tests.  It is recommended that one of the following test procedures be adopted.  Selection of the most appropriate identified test options will be dependent upon whether the end user wishes to view a simulated alarm or actual flame test  

TEST PROCEDURE – Option 1  

Fault‐Trouble Condition – disconnect one of the sensor cable conductors from an in‐line joint or end of line terminations.   Fire/Alarm Condition – place a short circuit across the sensor cable or interconnecting cable conductors.  

TEST PROCEDURE – Option 2  

Fault/Trouble Condition – As option 1 above  Fire/Alarm  –Operate  key  switch  on  in‐line  located  test  point  device  if  installed.    This  places  a  short  circuit  across  sensor  cable conductors.  

TEST PROCEDURE – Option 3  

Fault/Trouble Condition – As option 1 above Connect “in series” a short  test  length of PROLINE TH sensor cable and apply heat or  flame  to  that  length  to generate an alarm signal.  After testing remove the short length and re‐connect original installed sensor cable.  This may be an end user preferred test method but must NEVER be carried out in areas deemed to be classified as HAZARDOUS. 

 SYSTEM MUST NOW BE RE‐SET   SENSOR CABLE TROUBLESHOOTING – NO PROLINE SUPPLIED ZI INTERFACE INCLUDED  

CONDITION  ACTION OPEN CIRCUIT ON SENSOR CABLE  CHECK END OF LINE RESISTOR IS FITTED CORRECTLY 

OPEN CIRCUIT ON SENSOR CABLE  ENSURE GOOD CONNECTIONS WITHIN ANY INLINE JUNCTION BOXES

OPEN CIRCUIT ON SENSOR CABLE  PHYSICALLY CHECK SENSOR CABLE FOR MECHANICAL DAMAGE 

SHORT CIRCUIT ON SENSOR CABLE  MEASURE  SENSOR  CABLE  RESISTANCE  USING MULTI‐METER  TO  HELP  IDENTIFY  LOCATION  OF  SHORT CIRCUIT 

SHORT CIRCUIT ON SENSOR CABLE  HAS SENSOR BEEN EXPOSED TO TEMPERATURES ABOVE ITS ALARM RATING 

SHORT CIRCUIT ON SENSOR CABLE  CHECK FOR VISIBLE SIGNS OF PHYSICAL CRUSHING

                

                                Registered Office:  Registered No: 4421495  www.lineardetection.com Kings Worthy House                                                                                           V.A.T. No:  GB799 9244 45                                                                             [email protected]                     Court Road, Kings Worthy                                                                                                                                                                                                             Tel:  00357 26 623660 Winchester Hampshire SO23 7QA  U.K.