LION Controller
Installation & Commissioning Instructions
Copyright © 2009 Honeywell GmbH All Rights Reserved EN1Z-0921GE51 R0709 3.4
LION SYSTEM
INSTALLATION AND COMMISSIONING INSTRUCTIONS
CONTENTS
Safety Information............................................................. 3 General Safety Information ............................................ 3 Safety Information as per EN60730-1........................... 3
System Overview............................................................... 4 System Architecture....................................................... 4 I/O Modules ................................................................... 5 Interfaces and Bus Connections .................................... 9 Technical Data............................................................... 9
Planning ........................................................................... 10 Overview...................................................................... 10 Transformer Selection ................................................. 10 Fusing Specifications................................................... 11 System Protective Earth Grounding............................. 11 Lightning Protection ..................................................... 11 Panel Bus Topologies.................................................. 11 LONWORKS Bus Topologies.......................................... 12 C-Bus Topologies ........................................................ 12 Accessories ................................................................. 12 Cable Specifications .................................................... 13 Dimensions .................................................................. 16
Mounting/Dismounting Modules.................................... 18 Mounting/Dismounting Controller/Sockets ................... 18 Mounting/Dismounting Electronic Modules .................. 20 Mounting/Dismounting Manual Disconnect Modules ... 21 Mounting/Dismounting Auxiliary Terminal Packages ... 22 Mounting/Dismounting Cross Connectors.................... 23 Mounting/Dismounting Swivel Label Holders............... 23
Wiring and Setting Up the System................................. 24 General Safety Considerations .................................... 24 Wiring Push-in Terminals............................................. 24 Connecting Power Supply............................................ 25 Connecting Single Bus Controller Systems ................. 26 Connecting Panel Bus and LONWORKS Bus Mixed Controller Systems ...................................................... 27 Setting Address of Panel Bus I/O Modules .................. 29
Setting I/O Bus Switch ................................................. 29 Connecting Field Devices ............................................ 30 Commissioning I/O Modules ........................................ 31 Updating Software ....................................................... 31
Connecting to External Systems or Interfaces ............. 32 Connecting via LONWORKS Bus.................................... 32 Connecting via C-Bus .................................................. 33 Connecting HMIs or Laptops ....................................... 33 Connecting Modems .................................................... 33
Description of the CLLIONLC01 ..................................... 34 Overview...................................................................... 34 Features....................................................................... 35
Description of the I/O Modules....................................... 40 Common Features ....................................................... 40 Analog Input Modules .................................................. 40 Analog Output Modules ............................................... 45 Binary Input Modules ................................................... 50 Relay Output Modules ................................................. 53 Floating Output Module................................................ 58 Mixed Panel Bus I/O Module CLIOP830A ................... 62
Description of Extra Parts............................................... 65 Manual Disconnect Modules........................................ 65 XS814 Auxiliary Terminal Package.............................. 66 XS830 Auxiliary Terminal Package.............................. 66 XS831 Auxiliary Terminal Package.............................. 66 Cross Connectors ........................................................ 67 XAL10 Swivel Label Holders........................................ 67 XAL11 Swivel Label Holders........................................ 67 XS816 Bridge Connectors ........................................... 67
LON Software Interface Description .............................. 68 Overview...................................................................... 68 CLIOL821A Analog Input Module ................................ 68 CLIOL(R)822A Analog Output Module......................... 70 CLIOL823A Binary Input Module ................................. 72 CLIOL(R)824A Relay Output Module........................... 73
LION System
EN1Z-0921GE51 R0709 2
Troubleshooting...............................................................74 Testing Wiring Connections..........................................74 Troubleshooting on the CLLIONLC01 Controller ..........74 I/O Modules Troubleshooting........................................78
Appendix 1: System Protective Earth Grounding .........82 LION Systems and SELV .............................................82 LION Systems and Standard EN60204-1.....................82 Earth Grounding of EN60204-1 Applicable Systems ....82
Appendix 2: Remote Communications...........................84 Approved Modems .......................................................84 Modem or ISDN Terminal Adapter Connection ............84 Modem Requirements ..................................................84 Troubleshooting............................................................84
Appendix 3: Sensor Characteristics...............................85 BALCO 500 ..................................................................85 NTC 20 kΩ....................................................................86 PT 1000........................................................................87 NI1000TK5000 .............................................................89 NTC 10 kΩ....................................................................90 PT 3000........................................................................91
Trademark Information Echelon, LON, LONMARK, LONTALK, LONWORKS, Neuron, are trademarks of Echelon Corporation registered in the United States and other countries.
LION System
3 EN1Z-0921GE51 R0709
Safety Information
General Safety Information When performing any work (installation, mounting, start-
up), all instructions given by the manufacturer and in particular the safety instructions provided in these Installation and Commissioning Instructions are to be observed.
The LION System (including the CLLIONLC01, I/O modules, manual disconnect modules, and the auxiliary terminal packages) may be installed and mounted only by authorized and trained personnel.
Rules regarding electrostatic discharge should be followed.
If the LION System is modified in any way, except by the manufacturer, all warranties concerning operation and safety are invalidated.
Make sure that the local standards and regulations are observed at all times. Examples of such regulations are VDE 0800 and VDE 0100 or EN 60204-1 for earth grounding.
Use only accessory equipment which comes from or has been approved by CentraLine.
It is recommended that devices are to be kept at room temperature for at least 24 hours before applying power. This is to allow any condensation resulting from low shipping/storage temperatures to evaporate.
The LION System must be installed in such a manner (e.g., in a lockable cabinet) as to ensure that uncertified persons have no access to the terminals.
Safety Information as per EN60730-1 Purpose The LION System is an independently mounted electronic control system with fixed wiring. It is used for the purpose of building HVAC control and is suitable for use only in non-safety controls for installation on or in appliances.
Pollution degree Pollution Degree 2, suitable for use in residential controls, commercial controls, in a clean environment.
Overvoltage category
Category II for mains-powered (16A) controls Category I for 24 V powered controls
Rated impulse voltage
2500 VAC
Automatic action Type 1.C (micro-interruption for the relay outputs)
Software class Class A
Ball-pressure test temperature
75 °C for all housing and plastic parts 125 °C in the case of devices applied with voltage-carrying parts and connectors
Electromagnetic interference
Tested at 230 VAC, with the modules in normal condition.
System transformer Europe: safety isolating transformers according to IEC61558-2-6 U.S.A. and Canada: NEC Class-2 transformers
Table 1 System data as per EN60730-1
System Overview LION System
EN1Z-0921GE51 R0709 4
System Overview
System Architecture An LION System consists of the CLLIONLC01 Controller and various I/O modules. The CLLIONLC01 Controller provides interface connections, which allow connection to external systems. Auxiliary parts enable special features.
Panel Bus (<40 m)
CLLIONLC01 + CLIOxx
CLMMI00N22 or CLMMI00N31MODEMLonWorks Bus
XFCLxxxXFCxxx SERVAL
LonWorks I/O (CLIOLxx)
Panel I/O (CLIOPxx)
C-Bus
existing XL500controllers
Fig. 1 LION System architecture
Controller I/O Modules
Fig. 2 CLLIONLC01 Controller and I/O modules
LION System System Overview
5 EN1Z-0921GE51 R0709
I/O Modules Variants of Pluggable I/O Modules There are 2 variants of pluggable I/O modules: • Panel Bus I/O modules with communication via Panel
Bus (light gray housings) Modules are automatically commissioned (with firmware download) by the CLLIONLC01 Controller
• LONWORKS Bus I/O modules (dark gray housings) with communication via LONWORKS (FTT10-A, link power compatible) for easy integration and use with 3rd-party controllers
Mixed I/O Modules Besides the pluggable Panel Bus I/O modules (consisting of a terminal socket and a removable electronic module), there are also mixed Panel Bus I/O modules. Specifically: the CLIOP830A is a mixed Panel Bus I/O modules, featuring an integrated terminal socket and a variety of inputs and outputs. Mixed Panel Bus I/O modules have a light-gray housing and are likewise automatically commissioned (with firmware download) by the CLLIONLC01 Controller.
Terminal Sockets Pluggable I/O modules are mounted on the appropriate terminal sockets. Pluggable Panel Bus I/O modules and pluggable LONWORKS Bus I/O modules use the same terminal sockets. The terminal sockets are available with push-in terminals (XS82…) or with screw-type terminals (XSU82…). Mixed I/O modules feature an integrated terminal socket. Color Coding To distinguish modules and components, the following color coding is used:
Color Part
Red All of the user-accessible adjustable mechanical parts (i.e., bridge connectors and locking mechanism) and operating controls (manual overrides, etc.)
Light-gray Panel Bus I/O modules
Dark-gray LONWORKS Bus I/O modules
Table 2 Color coding of LION Modules
CLLIONLC01
MIXED I/OspluggableANALOG OUTPUT
pluggableANALOG INPUT
pluggableBINARY INPUT
pluggableFLOATINGOUTPUT
pluggableRELAY OUTPUT
XS821-22XSU821-22
XS823XSU823
XS824-25XSU824-25
LonWorks or Panel Bus
CLIOP821A
CLIOL821A
CLIOP822A
CLIOPR822A
CLIOL822A
CLIOLR822A
CLIOP823A
CLIOL823A
CLIOP824A
CLIOPR824A
CLIOL824A
CLIOLR824A
CLIOPR825APANELBUS MODULES
LonWorksBUS MODULES
CLIOP830APANEL BUS I/O MODULE
Fig. 3 Overview of I/O modules and terminal sockets
System Overview LION System
EN1Z-0921GE51 R0709 6
I/O Module Overview
Panel Bus module
LONWORKS Bus module Description Inputs Outputs Manual controls LEDs 1)
CLIOP821A CLIOL821A Analog input module 8 – – –
CLIOP822A CLIOL822A Analog output module – 8 – 8 status LEDs
CLIOPR822A CLIOLR822A Analog output module – 8 8 Manual overrides 8 status LEDs
CLIOP823A CLIOL823A Binary input module 12 – – 12 status LEDs
CLIOP824A CLIOL824A Relay output module – 6 2) – 6 status LEDs
CLIOPR824A CLIOLR824A Relay output module – 6 2) 6 Manual overrides 6 status LEDs
CLIOPR825A – Floating output module – 3 3 Manual overrides 3 pairs of status LEDs
CLIOP830A -- Mixed I/O module 20 14 -- 18 status LEDs 1) In addition to the power LED and service LED 2) Changeover outputs
Table 3 Overview of I/O modules
Corresponding Terminal Sockets
I/O module CLIOP/CLIOL… Socket Scope of delivery
…821
…822
XS821-22 XSU821-22
1 terminal socket, 1 bridge connector 1 swivel label holder
…823 XS823 XSU823
1 terminal socket, 1 bridge connector 1 swivel label holder
…824
…825
XS824-25 XSU824-25
1 terminal socket, 1 bridge connector 1 swivel label holder 1 long cross connector
Table 4 Pluggable I/O modules and corresponding terminal sockets
Note In the following e.g., …822 is used to summarize all analog output modules (Panel Bus/LONWORKS Bus, with/without manual overrides)
LION System System Overview
7 EN1Z-0921GE51 R0709
Auxiliary Parts
Module Type Figure Corresponding I/O modules CLIOP/CLIOL…
Information
XS812
…821 …822 …823
Module allows disconnection of individual I/O signals
Manual disconnect modules
XS812RO
…824 …825
Module allows disconnection of individual I/O signals For 24 V applications only
XS814
All pluggable LION I/O modules
Two groups of 7 terminals connected to each other for redistributing voltage (see also Fig. 94)
XS830 A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
Two groups of nine internally-connected push-in terminals, for distributing signals/power (see also Fig. 96).
Auxiliary terminal package
XS831 A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
CLIOP830A, only Two groups of four pairs of push-in terminals, for converting 0…20 mA signals into 0…10 Vdc signals, and one push-in ground terminal per group. (see also Fig. 98)
Cross connectors, short (yellow) XS817
…824 …825
Connects 3 relay commons, required in case of line voltage and low voltage in the same I/O module
Table 5 Auxiliary parts
Spare Parts
System Overview LION System
EN1Z-0921GE51 R0709 8
Module Type Figure Corresponding I/O modules CLIOP/CLIOL…
Information
Cross connectors, long (red) XS815
…824 …825
Connects 6 relay commons
Connector bridge XS816
All LION I/O modules Connects CLLIONLC01 and I/O modules
Swivel label holder XAL10
All pluggable LION I/O modules
Can be plugged into socket, for attaching label generated by the engineering tool
Swivel label holder XAL11
CLIOP830A, only Can be plugged into module, for attaching label generated by the engineering tool.
Table 6 Spare parts
LION System System Overview
9 EN1Z-0921GE51 R0709
Interfaces and Bus Connections The LION System can be connected to the following devices and systems: Panel Bus • For communication with up to 16 Panel Bus I/O modules • Polarity-insensitive LONWORKS Bus • For communication with other LONWORKS Bus devices
within the building • FTT10, link power compatible
• Polarity-insensitive C-Bus • For communication with other controllers, e.g., existing
Excel 500 Controllers HMI • For connecting an operator interface (e.g., CLMMI00N22
or CLMMI00N31) or a laptop, e.g., for engineering Modem • For connecting a modem or an ISDN terminal adapter
Technical Data
System Data
Operating voltage 24 VAC, ± 20 %, 21 … 30 VDC
Max. number of C-Bus participants
30
Power consumption Max. 3.57 A (1 CLLIONLC01 Controller + 16 I/O modules)
Push-in terminals 1.5 mm2
Screw-type terminals 1.5 mm2
Overvoltage protection All inputs and outputs are protected against 24 VAC and 40 VDC overvoltage as well as against short-circuiting.
Calculated lifetime of weakest component under typical operating conditions
MTBF ≥ 13.7 years
Table 7 System data
Standards
Protection class IP20
Product standard EMC EN 60730-2-9
Testing electrical components
IEC68
Certification CE
System transformer The system transformer(s) must be safety isolating transformers according to IEC 61558-2-6. In the U.S.A. and Canada, NEC Class 2 transformers must be used.
Low-Voltage Device Safety Assessment
EN 60730-1 EN 60730-2-9
Table 8 Standards
Operational Environment
Ambient operating temperature
0 … 50 °C (32 … 122 °F)
Ambient operating humidity
5 … 93 % rel. humidity (non condensing)
Ambient storage temperature
–20 … 70 °C (–4 … +158 °F)
Ambient storage humidity
5 … 95 % rel. humidity (non condensing)
Vibration under operation
0.024” double amplitude (2 … 30 Hz), 0.6 g (30 … 300 Hz)
Dust, vibration According to EN60730-1
RFI, EMI Home environment
Table 9 Operational environment
Planning LION System
EN1Z-0921GE51 R0709 10
Planning
Overview Engineering with CARE During CARE engineering, the type of I/O modules, terminal assignment and module configuration are defined depending on the application. The same applies to engineering with COACH (which is possible starting with COACH version 2.02). Planning In this step, the following has to be defined, if applicable: • Power supply • Fusing • Earth grounding
• Lightning protection • Panel Bus wiring • Design of a LONWORKS network • Design of a C-Bus network
• Useful accessories • Cable selection
Transformer Selection Note In Europe the system transformer(s) must be safety isolating transformers according to IEC61558-2-6. In the U.S.A. and Canada, NEC Class-2 transformers must be used.
Power Consumption When selecting the appropriate transformer, take into account the number of individual modules, accessories, and field devices in determining the total power consumption.
Power consumption Devices powered
24 VAC 24 VDC
CLLIONLC01 with CLMMI00N22 (backlight ON) and with watchdog load (max. 500 mA)
690 mA 640 mA
CLLIONLC01 with CLMMI00N22 (backlight ON) but without watchdog load
190 mA 140 mA
…821 130 mA 80mA
…822 160 mA 90 mA
…823 180 mA 130 mA
…824 140 mA 90 mA
…825 140 mA 90 mA
CLIOP830A 200 mA 95 mA
Table 10 Power consumption of LION System components depending on power supply
Connectable Power Supplies CentraLine CRT Series (Europe)
Transformer Primary side Secondary side
CRT 2 220/230 VAC 24 VAC, 50 VA, 2 A
CRT 6 220/230 VAC 24 VAC, 150 VA, 6 A
CRT 12 220/230 VAC 24 VAC, 300 VA, 12 A
Table 11 CentraLine CRT series transformers data
LION System Planning
11 EN1Z-0921GE51 R0709
CentraLine 1450 Series (North America) • 50/60 Hz • Insulated accessory outputs
• Built-in fuses • Line transient /surge protection • AC convenience outlet • NEC Class-2
Part number 1450 7287 Primary side Secondary side
-001 120 VAC 24 VAC, 50 VA
-002 120 VAC 2 x 24 VAC, 40 VA, and 100 VA from separate transformer
-003 120 VAC 24 VAC, 100 VA, and 24 VDC; 600 mA
-004 240/220 VAC 24 VAC, 50 VA
-005 240/220 VAC 2 x 24 VAC, 40 VA, and 100 VA from separate transformer
-006 240/220 VAC 24 VAC, 100 VA, and 24 VDC, 600 mA
Table 12 CentraLine 1450 series transformers data
Standard Transformers (Europe, North America) Standard commercially available transformers used to supply power to LION Systems must fulfill the following specifications:
Output voltage Impedance AC current
24.5 VAC to 25.5 VAC ≤ 1.15 Ω max. 2 A
24.5 VAC to 25.5 VAC ≤ 0.40 Ω max. 6 A
24.5 VAC to 25.5 VAC ≤ 0.17 Ω max. 12 A
Table 13 Requirements for standard transformers
RIN-APU24 Uninterruptable Power Supply The RIN-APU24 Uninterruptable Power Supply can be wired to power LION Systems. See also RIN-APU24 Uninterruptable Power Supply – Mounting Instructions (MU1B-0258GE51) for detailed wiring diagrams.
Power Supply of Field Devices Depending upon the power consumption of the field devices used, it is possible to use either a single transformer to power both the CLLIONLC01 and attached field devices, or it may be necessary to employ an additional transformer. See also section "Field Device Cables" on page 14 and connection examples on page 30.
Fusing Specifications For connection examples see description of the I/O modules on page 40 and following. F1 (Fusing for CLLIONLC01 and I/O Modules)) Rating: 4 A, time-lag fuse (slo-blo) For example: Manufacturer: Littlefuse Type: 218004 F2 (Fusing for Active Field Devices) Depends upon loads in use.
System Protective Earth Grounding LION Systems comply with SELV (Safety Extra-Low Voltage). Earth grounding is therefore not recommended. However, if compliance with EN60204-1 is required, see Appendix 1.
Lightning Protection Please contact your local CentraLine representative for information on lightning protection.
Panel Bus Topologies • Up to 16 Panel Bus I/O modules can be controlled by a
single CLLIONLC01. • Panel Bus I/O modules must be addressed using the
HEX switch on the terminal socket. • Maximum distance between controller and Panel Bus
I/O module: 40 m.
• No bus termination • Polarity-insensitive
Planning LION System
EN1Z-0921GE51 R0709 12
LONWORKS Bus Topologies The LONWORKS Bus is a 78-kilobit serial link that uses transformer isolation so that the bus wiring does not have a polarity. I.e. it is not important which of the two LONWORKS Bus terminals are connected to each wire of the twisted pair. The LONWORKS Bus does not need to be shielded on the controller module side. The LONWORKS Bus can be wired in daisy chain, star, loop or any combination thereof as long as the maximum wire length requirements are met. Configuration The recommended configuration is a daisy chain with two bus terminations. This layout allows for max. LONWORKS Bus lengths, and its simple structure presents the least number of possible problems, particularly when adding on to an existing bus. See also “LONWORKS Mechanisms”, Product Literature no.: EN0B-0270GE51.
C-Bus Topologies Via the C-Bus up to 30 C-Bus devices (e.g., controllers, etc.) can communicate with one another and a PC central. The C-Bus must be connected via the individual controllers (open ring). Note Star connection is not allowed because uncontrollable line reflections may occur. Instead of LION Controllers, other C-Bus controllers (e.g., the Excel 500, Excel 100, PANTHER) can also be connected.
LION Excel 100 Excel 500 PANTHER
Fig. 4 C-Bus topology Excel 5000
Accessories Besides the auxiliary parts of Table 5 on page 7, the following accessories are available.
Preconfigured Connection Cables
Type Connecting CLLIONLC01 with
Features
XW882 CLMMI00N22 Operator Interface
5 m, shielded, RJ45 plug with clip
XW582 + XW586
CLMMI00N22 Operator Interface
See XW582 and XW586
XW884 Adapter cable for Excel 500/600 Controllers
0.2 m, shielded, RJ45 – 9 pin sub-D
XW885 Laptops 3 m, shielded, RJ45 plug with clip
XW585 + XW586 Laptops See XW582 and
XW586
XW586 Modems 1.8 m, RJ45 – 9 pin sub-D
Table 14 Preconfigured connection cables
XW882 Cable Details
12
36
78
45
CLMMI00N22WIRING
TERMINALS
XW882
SHIELDLOOSEENDS
RxDGND
+5VETxDYELLOW
GRAY (not used)
BROWNGREENWHITE
1
4 3 2
RJ45 plug with clip at front
+5V
Fig. 5 CLLIONLC01/CLMMI00N22 cable details
XW884 Cable Details
12
36
78
45
RS232 plugsub-D femaleSHIELD
XW884
67
89
12
34
5
RxDRTSTxD
GND
RJ45 plug with clip at front
+5V
Fig. 6 CLLIONLC01/Excel 500/600 cable details
LION System Planning
13 EN1Z-0921GE51 R0709
XW885 Cable Details
12
36
78
45
RJ45 plug with clip at front RS232 plugsub-D female
1 5
4 3
2
9 8
7 6
SHIELD
XW885
RxD
GND
RTS
+5V
TxD
Fig. 7 CLLIONLC01/laptop cable details
XW582 Cable Details
to XC5010C
1 5
4 3
2
9 8
7 6
XW582
SHIELD
RxDGND
+5VETxDYELLOW
BROWNGREENWHITE
1
4 3 2
CLMMI00N22WIRING
TERMINALS
LOOSEENDS
Fig. 8 XW582 cable details
XW585 Cable Details
1 5
4 3
2
9 8
7 6
1 5
4 3
2
9 8
7 6
XW585
SHIELD
+5V RxD
GND
RTSTxD
RS232 plugsub-D female
RS232 plugsub-D female
Fig. 9 XW585 cable details
XW586 Cable Details
1 5
4 3
2
9 8
7 6
12
36
78
45
RS232 plugsub-D maleSHIELD
DCDDSRRxDRTSTxDCTSDTRGND
XW586
RJ45 plug with clip at front
+5V
Fig. 10 XW586 cable details
LONWORKS Bus Termination Modules
Type Description
209541 LONWORKS Bus termination module
XAL-Term LONWORKS connection and termination module, which can be mounted on DIN rails and in fuse boxes
Table 15 LONWORKS Bus termination modules
Cable Specifications
Power Supply Cables When checking the length of the power supply cable, the connection cables to all I/O modules must be taken into account.
Max. length 3 m (per side of the controller), see Fig. 33 on page 26
Cross section min. 0.75 mm2 (AWG 18)
Table 16 Power supply cables specification
Panel Bus Cables
Max. length 40 m
Cable type twisted pair, e.g., J-Y-Y 2 x 2 x 0.8
Table 17 Panel Bus cables specification
Planning LION System
EN1Z-0921GE51 R0709 14
LONWORKS Bus Cables
Cable type Max. bus length
Belden 85102 (plenum) 2700 m (8900 ft)
Belden 8471 (non-plenum) 2700 m (8900 ft)
Level IV, 22 AWG 1400 m (4600 ft)
JY (St) Y 2 x 2 x 0.8 900 m (3000 ft)
TIA568A Cat. 5 24AWG, twisted pair 900 m (3000 ft)
Table 18 Doubly-terminated bus specifications
Notes • The cable types listed above are as recommended by
Echelon in their FTT-10A User Guide.
• The cable recommended by CentraLine is the level IV, 22 AWG, solid core, non-shielded cable.
• Belden part numbers are 9H2201504 (plenum) and 9D220150 (non-plenum).
FTT Specification The FTT specification includes two components that must be met for proper system operation: • The distance from each transceiver to all other
transceivers and to the termination must not exceed the max. node-to-node distance.
• If multiple paths exist, the maximum total wire length is the total amount of wire used.
Cable type Max. node-to-node distance
Max. total wire length
Belden 85102 500 m (1650 ft) 500 m (1650 ft)
Belden 8471 400 m (1300 ft) 500 m (1650 ft)
Level IV, 22AWG 400 m (1300 ft) 500 m (1650 ft)
JY (St) Y 2 x 2 x 0.8 320 m (1050 ft) 500 m (1650 ft)
TIA568A Cat. 5 24AWG, twisted pair 250 m (825 ft) 450 m (1500 ft)
Table 19 Free topology (singly-terminated) specifications
NOTICE
Unpredictable reflections on the bus due to step change in line impedance characteristics!
Do not use different wire types or gauges on the same LONWORKS network segment.
Note In the event that the limit on the total wire length is exceeded, the FTT physical layer repeaters (FTT 10A) can be added to interconnect segments. This increases the overall length by an amount equal to the original specification for that cable type and bus type for each repeater used. For example, adding repeaters for a doubly-terminated bus using JY (St) Y 2 x 2 x 0.8 cable increases the maximum length 900 m (3000 ft) for each repeater.
Field Device Cables
Cross-sectional area
Type of signal ≤ 100 m (300 ft) (Fig. 40 on p. 30) one transformer
≤ 400 m (1300 ft) (Fig. 41 on p. 30)
separate transformers
24 VAC power 1.5 mm2 (16 AWG)
not allowed for > 100 m (300 ft)
0…10 V signals 0.081 – 2.08 mm2 (28 – 14 AWG)
Table 20 Cable sizing for connection of field devices
For wiring field devices see page 30.
LION System Planning
15 EN1Z-0921GE51 R0709
C-Bus Cables Note Observe national regulations for C-Bus cables!
• For Europe only shielded cable is permitted.
• For the U.S. shielded or unshielded cable can be used.
Cable type Description Recommended for
J-Y-(ST)Y 2 x 2 x 0.8
shielded, twisted pair Europe, inside cabinet
A-Y-(ST)Y 2 x 2 x 0.8
shielded, twisted pair Europe, outside cabinet
AK 3702 unshielded, twisted pair
US not approved for Europe
AK 3740A shielded US (low-cost) not approved for Europe
Belden 9842 twisted pair Europe, US also possible
Belden 9841 shielded US
AK 3702 unshielded, twisted pair
US not approved for Europe
AK 3740A shielded US (low-cost) not approved for Europe
Table 21 C-Bus cable types
Maximum Cable Length The maximum C-Bus cable length is 1200 m (4000 ft). See section "C-Bus Topologies" on page 12.
Planning LION System
EN1Z-0921GE51 R0709 16
Dimensions
Controller Module 144 92.75
110
28
32
45
Fig. 11 Controller module, outside dimensions (in mm)
Pluggable I/O Modules
LOCK
89.5 94.1
51.5
45
83 67.5
14
110
XS814 Aux. Terminal Package (optional)
2830.6
SWIVEL LABEL HOLDER
38
SCREW-TYPETERMINALS
Fig. 12 Pluggable I/O modules (shown with manual overrides), including XS814 Aux. Terminal Package, dimensions (in mm)
LION System Planning
17 EN1Z-0921GE51 R0709
Mixed I/O Module 92.5
51.5
45
69
100
CLE
ARA
NC
E
15
110
28
SWIVEL LABEL HOLDER
B7
B1 B2 B3 B4 B5 B6
71 2 3 4 5 6
8 9 10 11 12B8 B9 B10 B11 B12 AI5
AI1 AI2 AI3 AI4 41G1 G2
42
1713 14 15 16
18 19 20AI6 AI7 AI8 AO5
2521 22 23 24
26 27 28 3529 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 12 23 34 45 56 67
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342
8 9
3
10
4
11
5
12
6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
DI
Binary Inputs Analog Inputs Analog Outputs 24V RelaysGND
S2
DO!
Install. Instr.EN1B-0375GE51
CLIOP830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
2 1 0 F E
D C B
9 8
7
6 5 4 3
A
40 External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75767778
COM aCOM b24V~24V~0
COM aCOM b
24V~24V~0
727374
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9A
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9B
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9C
216
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8D
D = XS831 Aux. Terminal Package (optional)A, B, and C = XS830 Aux. Terminal Packages (optional)
Fig. 13 Mixed I/O Module CLIOP830A (shown with four auxiliary terminal packages), dimensions (in mm)
Mounting/Dismounting Modules LION System
EN1Z-0921GE51 R0709 18
Mounting/Dismounting Modules
WARNING
Risk of electric shock or equipment damage! Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install
the LION System. More than one disconnect switch may be required to de-energize the system.
Do not reconnect the power supply until you have completed the installation.
Note The terminal socket of each pluggable I/O module can be mounted and wired before inserting and locking the corresponding electronic module.
8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1
87654321
PRESS PRES
S
PRESS PRES
S
PRESS PRES
S
1 2 3
AUTO0
!
A A A100
!
S1 S2210 F E DCB
9876543
A
71 COM a
72 COM b
73 24V~
74 24V 0~
71 COM a
72 COM b
73 24V~
74 24V 0~
COM a
COM b
24V~
24V 0~
21
22
23
14 4424 5434 64 25
13
12
11 31
32
33
41
42
43
51
52
53
61
62
61
62
6363
1 2 3 4 5 6 7 8
AUTO0
!
A A A A A A A A100
S1 S2210 F EDCB
9876
543
A
21
9
GND GND
AI/AOVAUX
10 11 12 13 14 15 16 17 18 25 26
22 1 2 3 4 5 6 7 8
1 2 3 4 5 6
--1--0--AUTO
!
S1 S2210 F E DCB
9876543
A
21
22
23
14 4424 5434 64 25
13
12
11 31
32
33
41
42
43
51
52
53
61
62
61
62
6363
1:ABCDFERTAQWESDERT12:ABCDFERTAQWESDERT23:ABCDFERTAQWESDERT34:ABCDFERTAQWESDERT45:ABCDFERTAQWESDERT56:ABCDFERTAQWESDERT67:ABCDFERTAQWESDERT78:ABCDFERTAQWESDERT8
1:ABCDFERTAQWESDERT12:ABCDFERTAQWESDERT23:ABCDFERTAQWESDERT34:ABCDFERTAQWESDERT45:ABCDFERTAQWESDERT56:ABCDFERTAQWESDERT67:ABCDFERTAQWESDERT78:ABCDFERTAQWESDERT8
1 2 3 4 5 6 7 8
!
21
9
GND GND
AI/AOVAUX
10 11 12 13 14 15 16 17 18 25 26
22 1 2 3 4 5 6 7 8
GND
BI
13 14 15 16 17 18 19 20 21 22 23 24 25 26
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
!
LON
LON C-Busin
C-Bus
S1 S2Modem
I/O Bus Rx TxPower/Alarm
C-Busout
C-BUS RESET PC/HMI
13 39 6
14 410 7
12 28 59.6k all
Panel
LONmid
end
76k
76k
11 1
1 2
4 5
3
6
Fig. 14 CLLIONLC01 and I/O modules mounted on multiple DIN rails
Legend 1 CLLIONLC01 2 Swivel label holder 3 Cable connection 4 Stopper (from 3rd-party supplier) 5 Bridge connectors 6 Auxiliary terminal package
Mounting/Dismounting Controller/Sockets
Mounting Sockets Notes • When using both Panel Bus and LONWORKS Bus I/O
modules in a LION System, group both Panel Bus modules (light gray) and LONWORKS Bus I/O modules (dark gray), e.g., on different rails.
• Up to 10 Panel Bus I/O modules can be mounted to one side of the controller. In total, up to 16 Panel Bus I/O modules can be mounted to one controller.
• The CLLIONLC01 and the mixed Panel Bus I/O module are mounted on the DIN rail in the same way as a terminal socket.
CLLIONLC01PANEL
BUSI/O
PANELBUSI/O
PANELBUSI/O
PANELBUSI/O
max. 10max. 16
max. 10
Fig. 15 Max. number of Panel Bus I/O modules
CLLIONLC01 LonWorksBUS I/O
LonWorksBUSI/O
max. 10max. 20
max. 10
LonWorksBUS I/O
LonWorksBUS I/O
LonWorksBUS I/O
Fig. 16 Max. number of LONWORKS Bus I/O modules with power supply via CLLIONLC01
LION System Mounting/Dismounting Modules
19 EN1Z-0921GE51 R0709
Angle the terminal socket at the upper edge of the DIN rail until it snaps in.
Swing the terminal socket down and apply gentle force until it snaps into position with an audible "click".
Position controller module and terminal sockets flush with one another along the rail.
If desired, mount stoppers at the ends of the rail to prevent sliding.
Fig. 17 Mounting terminal sockets
Note Take care to not bend the Omega clamp, which serves to establish the electrical contact with the DIN rail and which located on the back of the terminal socket.
Connecting Sockets Controller, terminal sockets, and mixed I/O modules on the same DIN rail can be connected mechanically and electrically with bridge connectors. Controller and terminal sockets on different DIN rails must be connected using cables, see Fig. 14 and page 25.
NOTICE
Risk of malfunction!
Wire Panel Bus I/O modules and LONWORKS Bus I/O modules separately.
When using both Panel Bus and LONWORKS Bus I/O modules in a LION System, LONWORKS Bus I/O modules must be connected to the controller via LON terminals 11 … 14.
Position the bridge connector on terminals 71 … 74 of the right hand terminal socket or mixed I/O module or controller and on terminals 75 … 78 of the left hand terminal socket or mixed I/O module or controller. Then press the bridge connector down.
Fig. 18 Connecting terminal sockets with bridge
connector
Notes • Bridge connectors transmit both communication signals
and power supply between modules.
• Removing bridge connectors will interrupt the trans-mission of both communication signals and power supply between the modules.
Mounting/Dismounting Modules LION System
EN1Z-0921GE51 R0709 20
Dismounting Sockets Disconnecting Sockets Release all bridge connectors before removing the controller module and/or the terminal sockets and/or mixed I/O modules from the DIN rail. Press down at the same time both the gray side wings
next to the red button and then pull the bridge connector out of the module.
Fig. 19 Releasing bridge connectors
Dismounting Controller / Terminal Sockets / Mixed I/O Modules Insert a screwdriver into the latch on the underside of the
module and lever the red latch 2–3 mm downwards. The module can then be swung away from the rail.
Fig. 20 Releasing latch
Mounting/Dismounting Electronic Modules
Mounting Electronic Modules Note Electronic modules can be removed from the socket or inserted into the sockets without switching off the power supply. The behavior of connected field devices must be taken into consideration. Make sure that terminal socket und electronic I/O module
match; see Table 4 on page 6. Make sure that the red locking mechanism is in the open,
i.e., left, position. Gently push the electronic module onto the terminal
socket until snug.
Fig. 21 Inserting the electronic module
Lock the red locking mechanism by sliding it to the right.
Fig. 22 Locking the electronic module
Note The red locking mechanism will not close if the electronic module is not properly mounted.
LION System Mounting/Dismounting Modules
21 EN1Z-0921GE51 R0709
Dismounting Electronic Modules Note Electronic modules can be removed from the socket or inserted into the sockets without switching off the power supply. The behavior of connected field devices must be taken into consideration. Open the red locking mechanism by sliding it to the left
and then gently pull the electronic module out of the terminal socket.
Fig. 23 Dismounting the electronic module
Mounting/Dismounting Manual Disconnect Modules XS812 and XS812RO Manual Disconnect Modules are mounted on the terminal socket appropriate for the electronic module, see Table 4 on page 6. The electronic module is mounted onto the manual disconnect module.
WARNING
Risk of electric shock or equipment damage! The XS812RO Manual Disconnect Module is designed for 24 V applications only!
Never use the XS812RO Manual Disconnect Module with line voltage.
Mounting Manual Disconnect Modules Make sure that manual disconnect module, electronic
module and terminal socket match, see Table 4 on page 6.
Make sure that the red locking mechanism is in the open, i.e., left, position.
Gently push the manual disconnect module onto the terminal socket until snug.
Lock the red locking mechanism by sliding it to the right.
Fig. 24 Mounting the manual disconnect modules
Mounting/Dismounting Modules LION System
EN1Z-0921GE51 R0709 22
Operating the Individual Switches Use a screwdriver to open/close the appropriate
disconnector switches of the manual disconnect modules.
Fig. 25 Operating the disconnector switches
Dismounting Manual Disconnect Modules Open the red lock mechanism by sliding it to the left and
then gently pull the electronic module out of the terminal socket.
Mounting/Dismounting Auxiliary Terminal Packages The XS814 Auxiliary Terminal Package can be mounted on any pluggable I/O module. The XS830 and XS831 Auxiliary Terminal Packages are suitable for mixed I/O modules, only. Specifically, they can be mounted on the top and/or bottom of the CLIOP830A. For reasons of mechanical stability, a maximum of two rows of Auxiliary Terminal Packages may be mounted together on any given I/O module.
Mounting Auxiliary Terminal Packages Push the auxiliary terminal package onto the grooves of
the corresponding terminal socket / the mixed I/O module.
Fig. 26 Mounting the auxiliary terminal package onto the
terminal socket / mixed I/O module
Dismounting Auxiliary Terminal Packages Push down the catch of the auxiliary terminal package
and pull it out of the grooves of the terminal socket / the mixed I/O module.
Fig. 27 Dismounting the auxiliary terminal package from
the terminal socket / the mixed I/O module
LION System Mounting/Dismounting Modules
23 EN1Z-0921GE51 R0709
Mounting/Dismounting Cross Connectors Note The long cross connector (incl. in the scope of the delivery) can be mounted to the XS824-25 or XSU824-25, as required (Fig. 29). It can be dismounted (see Fig. 28) and, if desired, replaced with one or two short connectors (optional accessory, see Table 5 on page 7). It is not permitted to replace these cross connectors with wire. Insert a screwdriver on one end of the cross connector
and swivel it to the right and to the left. Insert a screwdriver on the other end of the cross
connecter and swivel it to the right and to left until the cross connector is released.
If desired, insert another cross connector.
Fig. 28 Dismounting the cross connectors (long cross connector shown here)
Fig. 29 Mounting the cross connectors (short cross
connector shown here)
Mounting/Dismounting Swivel Label Holders Note A swivel label holder is included in the scope of delivery of each module. Use only the (short / long) swivel label holders appropriate for the given type (pluggable or mixed, respectively) of I/O module.
Mounting Swivel Label Holders Snap the swivel label holder onto the hinges of the
terminal socket / mixed I/O module. Apply self-adhesive labels to the holders.
Fig. 30 Mounting the swivel label holder
Dismounting Swivel Label Holders Press the hinges together and remove the swivel label
holder.
Wiring and Setting Up the System LION System
EN1Z-0921GE51 R0709 24
Wiring and Setting Up the System
General Safety Considerations • When connecting the CLLIONLC01 or LION I/O modules,
both VDE, National Electric Code (NEC) or equivalent, and any local regulations concerning grounding and zero voltage must be observed.
• Electrical work should be carried out by a qualified electrician.
• The electrical connections must be made at the terminal blocks. The corresponding connection diagrams are located on the individual controller module and I/O modules.
• For Europe only: To comply with CE requirements, devices with a voltage in the range of 50 ... 1000 VAC or 75 ... 1500 VDC, which are not provided with a supply cord and plug or with other means for disconnection from the supply having a contact separation of at least 3 mm in all poles, must have the means for disconnection incorporated in the fixed wiring.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before making connections
to or removing connections from terminals of controller or I/O modules.
Do not use spare terminals as wiring support points. Do not reconnect the power supply until you have
completed the installation.
Observe precautions for handling electrostatic sensitive
devices.
Wiring Push-in Terminals The terminal sockets of the pluggable I/O modules are available in versions (…82…) featuring convenient push-in terminals for easy wiring. The CLIOP830A likewise features push-in terminals. For correct wiring, cables must fulfill the following specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge 0.14 … 1.50 mm2
Solid conductor H05/07) V-U 0.25 … 1.50 mm2
Stranded conductor H05(07) V-K 0.25 … 1.50 mm2
Stranded conductor with wire end ferrules (without plastic collar)
0.25 ... 1.50 mm2
Stripping length 8.0 +1.0 mm
Table 22 Push-in terminals wiring specifications
Wiring Screw-Type Terminals The terminal sockets of the pluggable I/O modules are also available with screw-type terminals. For correct wiring, cables must fulfill the following specifications according to IEC664-1 / VDE 0110 (4.97):
Max. plug gauge 0.14 … 1.50 mm2
Solid conductor H05/07) V-U 0.25 … 1.50 mm2
Stranded conductor H05(07) V-K 0.25 … 1.50 mm2
Stranded conductor with wire end ferrules (without plastic collar)
0.25 ... 1.50 mm2
Stripping length 11.0 +1.0 mm
Table 23 Screw-type terminals wiring specifications
LION System Wiring and Setting Up the System
25 EN1Z-0921GE51 R0709
Connecting Power Supply The LION System can be powered by one or more external transformers. Note The maximum length for the power supply cable from a transformer is 3 m. This also includes the length of the modules and the connection cables between the rails. Referring to Fig. 31 the following conditions must be fulfilled: A + B ≤ 3 m and A + C ≤ 3 m
Single or the First Transformer Connect the transformer to terminals 1 and 2 of the
CLLIONLC01 Controller.
I/O I/O I/OCPU21
B CA
A + B 3 mAND
A + C 3 m
Fig. 31 Wiring power supply from the (first) transformer to
the controller module
Additional Transformer Connect the additional transformer in a second room or
cabinet to terminals 73 and 74 or 77 and 78 of an I/O module.
I/OI/O
71727374
MAX. 3 m
TRANS-FORMER 2
Fig. 32 Wiring the power supply from a second
transformer
NOTICE
Equipment damage!
Do not use bridge connectors to connect modules powered by different transformers.
When connecting modules powered by different transformers using cables, be sure to not connect terminals 73 and 77.
Wiring and Setting Up the System LION System
EN1Z-0921GE51 R0709 26
Connecting Single Bus Controller Systems This section describes how to connect a controller system which uses Panel Bus I/O modules only or LONWORKS Bus I/O modules only.
Controller and I/O Modules on a Single Rail Connect controller and I/O modules using the bridge
connectors. This provides power supply and communication connection. No further wiring is necessary.
Controller and I/O Modules on Several Rails in a Single Cabinet The rails of a controller system are connected in series. Connect the rail ends as follows:
– Power supply via power supply terminals 73, 74 or 77, 78
– Communication via communication terminals 71, 72 or 75, 76
I/O
I/OI/O
I/O
I/O
I/O
I/O
I/O
I/O
75
75
71
71
71
71
76
76
72
72
72
72
77
77
73
73
73
73
78
78
74
74
74
74
CPU1 2
Fig. 33 Wiring the power supply and the communication
lines to the I/O modules
Maximum Power Cable Length The maximum length for power supply cable per side is 3 m. This also includes the connection cables between the rails, the lengths of the modules, and the cable from the transformer.
Panel Bus I/O Modules in Separate Rooms In this scenario, communication and reference voltage (24 V0) must be connected between the rooms. Connect the last module of room 1 to the first module of
room 2: – Reference voltage
via power supply terminals 74 or 78 terminals 73 and 77 must not be connected
– Communication via communication terminals 71, 72 or 75, 76
PANELI/O
PANELI/O
PANELI/O
75
7571
76
7672
77
7773
78
7874
MA
X. 4
0 m
24 V0
CPU1 2
Fig. 34 Wiring the Panel Bus I/O modules in separate
rooms
Maximum Cable Length The maximum cable length for connecting room 1 and room 2 is 40 m.
LION System Wiring and Setting Up the System
27 EN1Z-0921GE51 R0709
LonWorks Bus I/O Modules in Separate Rooms In this scenario, only communication lines must be connected between the rooms. Connect the last module of room 1 to the first module of
room 2: – via communication terminals 71, 72 or 75, 76
LonWorksI/O
LonWorksI/O
LonWorksI/O
75
7571
76
7672
77
7773
78
7874
CPU1 2
Fig. 35 Wiring the LONWORKS Bus I/O modules in
separate rooms
Maximum Cable Length For maximum cable lengths and cable specifications of the communication lines, see Table 18 and Table 19 on page 14.
Connecting Panel Bus and LONWORKS Bus Mixed Controller Systems
Connecting I/O Modules with Each Other For connecting the I/O modules with each other, proceed as described for single bus controller systems on page 25.
Connecting I/O Modules to the Controller Panel Bus I/O Modules Connect communication terminals 71 …74 or 75… 78 of
Panel Bus I/O modules to communication terminals 71 …74 or 75… 78 of the controller module using either – Bridge connectors
for flush mounting on a single DIN rail or – Cables
for separate mounting, e.g., on multiple rails, separate cabinets, etc.
LONWORKS Bus I/O Modules Connect communication terminals 71 … 74 or 75 … 78 of
LONWORKS Bus I/O modules to LONWORKS terminals 11 … 14 of the controller module using cables.
Wiring and Setting Up the System LION System
EN1Z-0921GE51 R0709 28
73
7172
7477
7576
7873
7172
13
11
14
123
1
4
2
7477
7576
7873
7172
7477
7576
7873
7172
7477
7576
78
XF... CLLIONLC01
Panel Bus I/O modules Panel Bus I/O modules
LonWorks Bus I/O modules
73
7172
7477
7576
7873
7172
7477
7576
7873
7172
7477
7576
78
73
7172
7477
7576
7873
7172
7477
7576
7873
7172
7477
7576
78
Fig. 36 Mixed bus system – correct wiring
73
7172
7477
7576
7873
7172
13
11
14
123
1
4
2
7477
7576
7873
7172
7477
7576
7873
7172
7477
7576
78
Panel Bus I/O modules LonWorks Bus modules
73
7172
7477
7576
7873
7172
7477
7576
7873
7172
7477
7576
78CLLIONLC01
Fig. 37 Mixed bus system – incorrect wiring
LION System Wiring and Setting Up the System
29 EN1Z-0921GE51 R0709
Setting Address of Panel Bus I/O Modules During engineering, each Panel Bus I/O module is assigned its own unique address. For the sake of clarity for maintenance personnel, it is recommended that you address the Panel Bus I/O modules in ascending order 0 through F.
Hex switch 0 1 2 3 4 5 6 7
Address 01 02 03 04 05 06 07 08
Hex switch 8 9 A B C D E F
Address 09 10 11 12 13 14 15 16
Table 24 HEX switch settings and addresses
Use the rotary HEX switch to set the address to the one
already defined using the engineering tool.
LOCK
44
Fig. 38 HEX switch location
Notes
• If the HEX switch is changed, the Panel Bus I/O module will revert to its default configuration.
• With LONWORKS Bus I/O modules, the HEX switch is without function.
Setting I/O Bus Switch Set the I/O Bus switch S2 of the CLLIONLC01 depending
on the modules connected to terminals 71 … 78 and the desired communication as follows:
Communication S2 setting Terminals
LONWORKS Bus only
LON 71 … 74 LONWORKS Bus75 … 78 LONWORKS Bus 11 … 14 LONWORKS Bus
Panel Bus and LONWORKS Bus
Panel 71 … 74 Panel Bus 75 … 78 Panel Bus 11 … 14 LONWORKS Bus
Table 25 I/O Bus switch settings
Panel
LO N
S2
I/O Bus
Fig. 39 S2 I/O Bus switch
Wiring and Setting Up the System LION System
EN1Z-0921GE51 R0709 30
Connecting Field Devices
Connecting Field Devices with Power Supply Depending on the distance from the controller, field devices can be supplied by the controller or need a separate transformer, see Table 20 on page 14. For fusing see section "Fusing Specifications" on page 11. Example 1: Power Supply via Controller • 24 V actuator connected to an analog output module • Less than 100 m away from the controller
Y (0...10 Vdc)24 V0
230 V~24 V~
max. 100 m
CLLIONLC01 822
12
9
1...8GND
Y24V~
11...18
F1
F2
Fig. 40 Power supply of field devices via I/O module
Example 2: Power Supply via Separate Transformer • 24 V actuator connected to an analog output module • 100 … 400 m away from the controller
Y (0...10 Vdc)24 V0
24 V0
230 V~
230 V~
24 V~
24 V~
max. 400 m
822
12 1...8
GNDY
24V~
11...18
F1F2
CLLIONLC01
Fig. 41 Power supply of field devices via a separate
transformer
Cabling Field Devices Cable Routing Route low-voltage signal and output cables separately from mains cables.
Cable Minimum distance
Shielded 10 mm (0.4 in.)
Unshielded 100 mm (4 in.)
Table 26 Minimum distances to power mains cables
All low-voltage signal and output cables should be regarded as communication circuits in accordance with VDE 0100 and VDE 0800 (or NEC or other equivalent). Cable Shielding • If the general guidelines for cable routing are observed, it
is not necessary to shield field device signal and power supply cables.
• If, for whatever reason, the routing guidelines cannot be observed, the field device signal and power supply cables must be shielded. – Shielding of cables leading to field devices must be
grounded only at the cabinet end. – The shield must not be terminated at the
CLLIONLC01.
LION System Wiring and Setting Up the System
31 EN1Z-0921GE51 R0709
Commissioning I/O Modules
Commissioning Panel Bus I/O Modules During engineering, the HEX address of the Panel I/O modules is defined. Note With Panel Bus I/O modules it is essential that the HEX switch be set to the address assigned by the engineering tool. The CLLIONLC01 Controller automatically commissions all Panel Bus I/O modules.
Commissioning LONWORKS Bus I/O Modules Commissioning is done using the engineering tool.
Updating Software CARE is used to update the CLLIONLC01 Controller.
Software with Panel Bus I/O Modules The CLLIONLC01 Controller automatically updates all Panel Bus I/O modules.
Software with LONWORKS Bus I/O Modules You can update the LONWORKS I/O modules using CARE or EXCELON.
Connecting to External Systems or Interfaces LION System
EN1Z-0921GE51 R0709 32
Connecting to External Systems or Interfaces
WARNING
Risk of electric shock or equipment damage! Do not touch any live parts in the cabinet! Disconnect the power supply before making connections
to or removing connections from terminals of controller or I/O modules.
Do not reconnect the power supply until you have completed installation.
Observe the rules regarding electrostatic discharge.
Connecting via LONWORKS Bus Via a LONWORKS Bus, a LION System can be connected to other controller systems, to additional LONWORKS Bus I/O modules, or to laptops.
LONWORKS Bus Termination Depending upon the configuration, either 1 or 2 termination modules are required for terminating a LONWORKS bus with FTT devices on it. The following 2 different LONWORKS termination units are available for this purpose: • 209541 LONWORKS Bus Termination Module and • XAL-Term LONWORKS Connection and Termination
Module, which can be mounted on DIN rails and in fuse boxes
Termination Examples
Brown BrownOrange Orange
Yellow Yellow
Fig. 42 Termination Module 209541 connections for a doubly-terminated FTT network
Fig. 43 Termination Module 209541 connections for a
singly-terminated FTT network
Fig. 44 XAL-Term Connection and Termination Module
LION System Connecting to External Systems or Interfaces
33 EN1Z-0921GE51 R0709
Connecting via C-Bus Via C-Bus, a LION Controller can be connected to other controller systems to form a network.
Connecting to the Controller Connect the C-Bus to the CLLIONLC01 as follows:
– Input to C-Bus terminals 8 and 9 – Output to C-Bus terminals 5 and 6 – Do not connect the C-Bus to the cabinet earth or any
other earth ground points
Setting C-Bus Termination Switch Set the C-Bus termination switch S1 appropriately.
al l
end
S1
C-Bus
mi d 9.6k
76k
76k
Fig. 45 C-Bus termination switch S1
Switch setting S1 Baud rate
9.6k all Up to 9600 baud (default setting)
76k mid Up to 76800 baud without bus termination
76k end Up to 76800 baud with bus termination
Table 27 CLLIONLC01 C-Bus termination switch settings
How to Shield In principle, data transmitting cables should be shielded in case of RFI. On the controller side, connect the shield to terminals 7
and 10. On the side of the device, connect the shield to the
respective terminals. Do not connect it to the cabinet ground or any other ground points.
Connecting HMIs or Laptops HMIs (e.g., the CLMMI00N22 or the CLMMI00N31) can be connected via the HMI interface of the CLLIONLC01. Laptops can be connected via the HMI interface or via the LONWORKS interface of the CLLIONLC01.
Connecting the CLMMI00N22 Operator Interface Connect the CLMMI00N22 Operator Interface to the HMI
interface of the CLLIONLC01 by means of – the XW882 cable or – the XW582 cable connected with an XW586 cable.
For mounting details refer to the CLMMI00N22 Installation Instructions (Product Literature no.: EN2B-0126GE51). For cable details refer to section "Preconfigured Connection Cables" on page 12.
Connecting the CLMMI00N31 Operator Interface Connect the CLMMI00N31 Operator Interface to the HMI
interface of the XCL8010 Controller Module by means of – the XW882 cable or – the XW586 cable connected with an XW585 cable.
For cable details refer to section "Preconfigured Connection Cables" on page 12.
Connecting Laptops (XL-Online/CARE) Connect a laptop (on which e.g., XL-Online or CARE has
been installed) to the HMI interface of the CLLIONLC01 by means of – the XW885 cable or – the XW585 cable connected with an XW586 Cable.
For cable details refer to section "Preconfigured Connection Cables" on page 12.
Connecting Modems An LION System can be connected to a modem or an ISDN terminal adapter via the Modem Interface of the CLLIONLC01 by means of the XW586 Cable. Connect the RJ45 female connector of the XW586 cable
to the modem interface of the CLLIONLC01 Controller. Connect the 9-pin sub-D connector to the modem. For cable details refer to section "Preconfigured Connection Cables" on page 12. Refer to Appendix 2 for details regarding remote communication.
Description of the CLLIONLC01 LION System
EN1Z-0921GE51 R0709 34
Description of the CLLIONLC01
Overview
Panel Bus (<40 m)
CLLIONLC01 + CLIOxx
CLMMI00N22 or CLMMI00N31MODEMLonWorks Bus
XFCLxxxXFCxxx SERVAL
LonWorks I/O (CLIOLxx)
Panel I/O (CLIOPxx)
C-Bus
existing XL500controllers
Fig. 46 Connections to the CLLIONLC01 Controller
8 7 6 5 4 3 2 1 8 7 6 5 4 3 21
87654321
!
71 COM a
72 COM b
73 24V~
74 24V0~
COM a 75
COM b 76
24V 77~
24V 0~ 78
LON
LON C-Busin
C-Bus
S1 S2Modem
I/O Bus RxTxPower/Alarm
C-Busout
C-BUS PC/HMI
13 396
14 410 7
12 2859.6k all
Panel
LONmid
end
76k
76k
11 1
3
12
4 5 6 7 8 9
11
1213
10
1415161718
12
Fig. 47 CLLIONLC01, front details
Legend 1 Power supply for I/O modules 2 I/O Bus communication terminals 3 LONWORKS interface 4 LONWORKS service button 5 LONWORKS service LED 6 C-Bus Tx LED 7 C-Bus Rx LED 8 Reset button 9 HMI interface and LEDs 10 Alarm LED 11 Power LED 12 Power supply terminals 13 Alarm/watchdog outputs 14 Modem interface and LEDs 15 S2 I/O Bus switch 16 S1 C-Bus termination switch 17 C-Bus terminals 18 LONWORKS terminals
LION System Description of the CLLIONLC01
35 EN1Z-0921GE51 R0709
CLLIONLC01 Terminals
74
14 10 7
234
7873
13 9 6
1
7772
12 8 5
7671
11
75
24V~
24V~
24V~
24V~0
LON2
C- C-C+ C+LON
2LON
1
LON1
24V~024
V~0NC
24V~0
COMB
COMB
COMA
COMA
SHIELD SHIELD
87 65 4 3 2 1
**Watch Dog
Relay
Fig. 48 Terminal assignment and internal connections of the CLLIONLC01
Ter-minal Signal Comment
71, 75 COM a 2-wire communication bus (LON/Panel Bus)
72, 76 COM b 2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply for I/O modules
74, 78 24 V~0 Power supply for I/O modules
1 24 V~ Power supply from transformer
2 24 V~0 Power supply from transformer
3 24 V~0 Alarm/watchdog output
4 NC Alarm/watchdog output
5, 8 C+ C-Bus
6, 9 C- C-Bus
7, 10 Shield C-Bus shield
11, 12 LON LONWORKS IN
13, 14 LON LONWORKS OUT
Table 28 Description of CLLIONLC01 terminals
Features
LONWORKS Interface and Terminals The CLLIONLC01 Controller Module features • An RJ45 socket serving as an interface
to connect laptops to the LONWORKS Bus • LONWORKS terminals 11, 12, 13, and 14
to connect LONWORKS Bus I/O modules or other LONWORKS devices to the CLLIONLC01 Controller or other LONWORKS controllers.
68 7 35 4 2 1
11121314
LON
Fig. 49 LONWORKS interface and LONWORKS terminals
LONWORKS Interface Signals on RJ45 Socket
Pin Signal type
1 Connection to LONWORKS Bus
2 Connection to LONWORKS Bus
3 … 8 Not used
Table 29 Signals of LONWORKS interface
LONWORKS Service LED and Button The CLLIONLC01 is equipped with a LONWORKS service button and corresponding LONWORKS Service LED (status: yellow/OFF).
Fig. 50 LONWORKS service button (1) and service LED (2)
See also section "Troubleshooting" on page 74.
Description of the CLLIONLC01 LION System
EN1Z-0921GE51 R0709 36
C-Bus Tx LED and Rx LED The CLLIONLC01 is equipped with a Tx LED (status: yellow/OFF) and an Rx LED (status: yellow/OFF).
Fig. 51 C-Bus Tx LED (1) and Rx LED (2)
C-Bus LEDs
Tx (1) flickering
The controller is sending data onto the C-Bus
Rx (2) flickering
The controller is receiving data from the C-Bus
Table 30 Controller C-Bus LEDs
Reset Button The CLLIONLC01 is equipped with a reset button.
Fig. 52 Reset button (1)
Pushing the reset button (1), e.g. using a paperclip, will cause the CLLIONLC01 to reset. Note In the event of a reset, all non-volatile memory contents are permanently deleted, though the clock will not be set to zero. In order to avoid problems, we therefore recommend that you always save your application changes (e.g., time program changes) to FLASH memory.
HMI Interface The controller module is equipped with an HMI Interface for the connection of HMIs (e.g., the CLMMI00N22 or the CLMMI00N31) or a laptop (with XL-Online/CARE).
3 12 45 78 8
Tx Rx
2 1
7 6 5 4 3 2 1
Fig. 53 HMI interface, Tx LED (1) and Rx LED (2)
HMI interface LEDs on RJ45 socket
Tx (1) flickering
The controller is transmitting data to the HMI
Rx (2) flickering
The controller is receiving data from the HMI
Table 31 HMI interface LEDs
HMI interface Signals on RJ45 socket
Pin Signal type
1 -
2 Receive
3 Transmit
4 -
5 Signal ground
6 -
7 5 V
8 -
Table 32 Signals of the HMI interface
NOTICE
Equipment damage!
Make sure that the controller is not connected to earth ground.
If nonetheless earth grounding is required, make sure that only terminal 2 is connected to earth ground. Terminal 1 must not be connected to earth ground. See also Appendix 1.
LION System Description of the CLLIONLC01
37 EN1Z-0921GE51 R0709
Alarm and Power LEDs The CLLIONLC01 is equipped with an alarm LED and a power LED.
1 2
Fig. 54 Alarm LED (1) and power LED (2)
Alarm LED (1, red)
Off Normal operation On Watchdog alarm output is powered
• The controller has encountered a hardware problem
• The application has a fault • The controller has been powered up
without an application or the operator has manually stopped the application, e.g., using XL-Online. In this case, the LED will light up 13 minutes after power-up without application
Flashing The watchdog alarm output has not yet been powered, although the controller has encountered a problem. The controller performs a warm start. If the problem persists, the LED will become lit constantly, see above. See section "Troubleshooting" on page 74.
Table 33 Controller alarm LED
Power LED (2, green) On Normal operation Flashing One or more of the internal voltage
supplies are outside of the permissible ranges. The controller stops operation. Check wiring or see section "Trouble-
shooting" on page 74. Goes out briefly
• The operator has activated the reset button
• The controller is performing a warm start
Table 34 Controller power LED
Watchdog Watchdog status
Status Signal on terminal 4
Failure (= alarm) 24 V
Normal operation 0 V
Table 35 Watchdog status 4
Permissible Load of Normally Closed Contact (Terminal 4)
Max. load Min. current
Per normally closed contact (terminal 4)
19…29 VAC current at cos φ ≥ 0.95: 0.5 A, current at cos φ ≥ 0.6: 0.5 A 19…29 VDC 0.5 A resistive or inductive
10 mA
Table 36 Permissible load of terminal 4
Description of the CLLIONLC01 LION System
EN1Z-0921GE51 R0709 38
Modem Interface The controller module is equipped with a modem interface for the connection of a modem or an ISDN terminal adapter.
3 12 6 45 78
Tx Rx
2 1
Fig. 55 Modem interface, Tx LED (1) and Rx LED (2)
Modem LEDs on RJ45 socket
Tx (1) flickering The controller is transmitting data to the HMI, e.g., CLMMI00N22 or CLMMI00N31
Rx (2) flickering
The controller is receiving data from the HMI
Table 37 HMI interface LEDs
Modem Signals on RJ45 socket
Pin Signal type
1 Carrier detect
2 Receive
3 Transmit
4 Data terminal ready
5 Signal ground
6 -
7 5 V
8 Clear to send
Table 38 Signals of the modem interface
Communication Speed Default setting: 9600 baud The communication speed can be set to as high as 38.4 Kbaud, e.g., using the CLMMI00N22 or CLMMI00N31 or a laptop with XL-Online, see Appendix 2.
I/O Bus Switch S2 The CLLIONLC01 features a 2-position I/O Bus switch S2. I/O Bus switch S2 must be set in accordance with the kind of I/O modules connected to communication terminals 71, 72 and 75, 76 of the controller module. Terminals 71, 72 and 75, 76 must be all connected either to Panel Bus I/O modules or to LONWORKS Bus I/O modules. The default setting is Panel.
Panel
LO N
S2
I/O Bus
Fig. 56 I/O Bus switch S2
Communication S2 setting
LONWORKS Bus only LON
Panel Bus and LONWORKS Bus LONWORKS BUS modules connected to terminals 11 …. 14 of the controller
Panel
Panel Bus connected to terminals 71, 72 or 75, 76 of the controller
Panel
Table 39 I/O Bus switch settings
LION System Description of the CLLIONLC01
39 EN1Z-0921GE51 R0709
C-Bus Termination Switch S1 The CLLIONLC01 features a 3-position C-Bus termination switch S1. This switch must be set in accordance with the given C-Bus configuration.
al l
end
S1
C-Bus
mi d 9.6k
76k
76k
Fig. 57 C-Bus termination switch
Switch setting S1 Baud rate
9.6k all Up to 9600 baud (default setting)
76k mid Up to 76800 baud without bus termination
76k end Up to 76800 baud with bus termination controller at the end of the C-Bus
Table 40 CLLIONLC01 C-Bus termination switch S1 settings
Memory Memory Size Usage
SRAM 512 KB For controller application, modem trend and firmware RACL application: 128 KB Total application: 192 KB
Flash 2 MB Firmware (1 MB) and application (1 MB) storage
EPROM 128 KB For bootstrap loader
Table 41 CLLIONLC01 memory
Note The CLLIONLC01 does not contain a battery. RAM (data and realtime clocktime) is buffered for 3 days by a super capacitor.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 40
Description of the I/O Modules
Common Features Switches located on the Terminal Socket
Feature Function
Service button S1 (pluggable I/O modules, only)
• LED test, see section "Troubleshooting" on page 74
• LONWORKS service button functionality for LONWORKS Bus I/O modules
Hex switch S2
• Module addressing for Panel Bus I/O modules
LEDs located on the I/O Module
Feature Function
Service LED (yellow)
• Service information, see section "Troubleshooting" on page 74
Power LED (green)
• Information on power supply, see section "Troubleshooting" on page 74
For the location of these elements, see figures of the relative modules.
Analog Input Modules
Types of Analog Input Modules and Terminal Socket Type Description Housing
CLIOP821 Panel Bus analog input module
Light gray
CLIOL821 LONWORKS Bus analog input module
Dark gray
XS821-822 XSU821-822
Terminal socket Light gray
Table 42 LION Analog Input Modules
Features • 8 analog inputs • Sensor-break and short-circuit detection, see section
"Troubleshooting" on page 74.
21
3 4
Fig. 58 CLIOP821A Analog Input Module with terminal
socket
Legend 1 Service button S1 2 Hex switch S2 3 Service LED 4 Power LED Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following.
LION System Description of the I/O Modules
41 EN1Z-0921GE51 R0709
Terminals
25 26
74 7873 7772 7671 75
24V~
24V~
24V~0
24V~0
COMB
COMB
COMA
COMA
AI8
8AI7
7AI6
6AI5
5AI4
4AI3
3AI2
2AI1
1
18171615141312GND
11GND GND GND GND GND GND GND
22V
21
10GND
9GND
AUX VAUX
Fig. 59 Terminal assignment and internal connections of
analog input modules
Ter-minal SIGNAL Comment
71, 75 COM a 2-wire communication bus (LON/Panel Bus)
72, 76 COM b 2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply 74, 78 24 V~0 Power supply 1…8 AI1 … AI8 Analog inputs 1…8
9…18 GND Ground. All grounds are connected internally to each other
21, 22 10 VDC/ 5 mA, ±2 %
Auxiliary voltage signal (used e.g. for supplying setpoint potentiometers)
25, 26 Shield connection (functional earth), internally connected to the DIN rail
Table 43 Description of analog input module terminals
Notes • Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a LONWORKS shield, since LONWORKS requires a resistor and a capacitor.
• If additional shield terminals are needed, the XS814 Auxiliary Terminal Package can be installed.
Technical Data Input
• 0(2) ... 10 VDC • 0(4) ... 20 mA
(via external 499 Ω/0.25 % resistor • NTC20k (-50…+150 °C; default) • PT1000-1 (-50…+150 °C) • PT1000-2 (0…+400 °C) • PT3000 (-50…+150 °C) • BALCO500 (-30…+120 °C) • Slow binary input
Protection Protected against failure voltage (24 VAC, 40 VDC)
Resolution 16-bit resolution
Accuracy ±75 mV (0 ... 10 V), without sensor
Table 44 Analog input modules data
Range
PT10
00-1
PT10
00-2
Bal
co50
0(1
PT30
00
NTC
20kΩ
(d
efau
lt)
NTC
10kΩ
(2
NI1
000T
K50
00(3
-50...-20 °C (-58...-4 °F) ≤ 1.2 K – ≤ 1.2 K ≤ 1.2 K ≤ 5.0 K ≤ 5.0 K ≤ 1.2 K
-20…0 °C (-4…+32 °F) ≤ 0.7 K – ≤ 0.7 K ≤ 0.7 K ≤ 1.0 K ≤ 1.0 K ≤ 0.7 K
0...30 °C (32…86 °F) ≤ 0.5 K ≤ 0.5 K ≤ 0.5 K ≤ 0.5 K ≤ 0.3 K ≤ 0.5 K ≤ 0.5 K
30...70 °C (86...158 °F) ≤ 0.7 K ≤ 0.7 K ≤ 0.7 K ≤ 0.7 K ≤ 0.5 K ≤ 0.5 K ≤ 0.7 K
70...100 °C (158...212 °F) ≤ 1.2 K ≤ 1.2 K ≤ 1.2 K ≤ 1.2 K ≤ 1.0 K ≤ 1.0 K ≤ 1.2 K
100...130 °C(212...266 °F) ≤ 1.2 K ≤ 1.2 K ≤ 1.2 K ≤ 1.2 K ≤ 3.0 K – ≤ 1.2 K
130...150 °C(266...302 °F) ≤ 1.2 K ≤ 1.2 K – ≤ 1.2 K ≤ 5.5 K – –
150…400 °C(302…752 °F)
– ≤ 1.2 K – – – – –
(1 Balco specified for -30 °C … +120 °C, only (2 NTC10kΩ specified for -30 °C … +100 °C, only (3 NI1000TK5000 specified for -30 °C … +130 °C, only
Table 45 Accuracy of analog input sensors
Note The accuracy of the sensor itself is not included in this table.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 42
Internal Impedance when Connecting Sensors
Fig. 60 Analog input low impedance (input circuit for
PT1000, Balco500, PT3000, NI1000TK5000, slow binary input)
Fig. 61 Analog input high impedance (input circuit for
voltage input for active sensors)
Fig. 62 Analog input impedance setpoint (input circuit for
NTC10kΩ, NTC20kΩ, wall module setpoint)
LION System Description of the I/O Modules
43 EN1Z-0921GE51 R0709
Connection Examples Active Sensor and Potentiometer
74737772767175
22
VAUX VAUX
21
9
74 78737271
1025 26GND
24V~
24V~
24V~
24V~0
24V~0
24V~ 0
COMB
COMB
COMB
COMA
COMA
COMA
GND
1 2 3
1 2 3 4 5 6 7A1 A2 A3 A4 A5 A6 A7
CLIOP821A Analog Input Module
1 2 3
0...10V
F1F2
Shieldinternally
connected
toDIN
rail
11GND
12GND
13GND
14GND
15GND
16GND
17GND
18GND
1AI1
2 3 4 5 6 7 8AI2 AI3 AI4 AI5 AI6 AI7 AI8
Optional
Aux.
Terminal Module XS814
9GND
10GND
Active
Sensor1:
24V~
power
supply2:
0...10
VDC
signal3:
GND
Aux.
Voltage
+
Pot.1:
signal2:
GND3:
10
VDC
auxiliary
CLIOP821A
Fig. 63 Analog input module, wiring example 1
For fusing specifications see section "Fusing Specifications" on page 11.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 44
Passive Sensor and 0 (4) … 20 mA Signal
74737772767175
22
VAUX VAUX
21
9
74 78737271
1025 26GND
24V~
24V~
24V~
24V~0
24V~0
24V~ 0
COMB
COMB
COMB
COMA
COMA
COMA
GND
1 2
11GND
12GND
13GND
14GND
15GND
16GND
17GND
18GND
1AI1
2 3 4 5 6 7 8AI2 AI3 AI4 AI5 AI6 AI7 AI8
9GND
10GND
Temp.
sensor(NTC20k
or
PT1000)
1 2
0(4)...20mA
777675
78
24V~24
V~ 0
COMB
COMA
External 499 Ωresistor withtwin wire-endferrules required
CLIOP821A Analog Input Module
CLIOP821ACLIOP821A
Fig. 64 Analog input module, wiring example 2
LION System Description of the I/O Modules
45 EN1Z-0921GE51 R0709
Analog Output Modules
Types of Analog Output Modules and Terminal Socket Type Description Housing
CLIOP822 Panel Bus analog output module
Light gray
CLIOPR822 Panel Bus analog output module with manual overrides
Light gray
CLIOL822 LONWORKS Bus analog output module
Dark gray
CLIOLR822 LONWORKS Bus analog output module with manual overrides
Dark gray
XS821-22 XSU821-22
Terminal socket Light gray
Table 46 LION Analog Output Modules
Features • 8 analog outputs; can also be configured per output as
binary outputs (0 … 10 V, 2 … 10 V, ON/OFF, or floating) • Corresponding output status LEDs (red) • …R822: 8 manual overrides, see figure below
5 64
3
21
Fig. 65 CLIOP822A Analog Output Module with terminal socket
Legend 1 Service button S1 2 Hex switch S2 3 Manual overrides 4 Output LEDs 5 Service LED 6 Power LED
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following. In the event of communication problems, the analog outputs will move to the safety positions you have configured using the engineering tool, see analog output point description in the CARE – User Guide, 74-5587/EN2B-0182GE51.
Terminals
Fig. 66 Terminal assignment and internal connections of
the analog output modules
Ter-minal Signal COMMENT
71, 75 COM a 2-wire communication bus (LON/Panel Bus)
72, 76 COM b 2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply 74, 78 24 V~0 Power supply 1…8 AO1…AO8 Analog outputs 1…8
9…18 GND Ground. All grounds are connected internally to each other
21, 22 N.C. Do not use!
25, 26 Shield connection (functional earth), internally connected to the DIN rail
Table 47 Description of the analog output module terminals
Notes • Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a LONWORKS shield, since LONWORKS requires a resistor and a capacitor.
• If additional shield terminals are needed, the XS814 Auxiliary Terminal Package can be installed.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 46
Technical Data Voltage rating 0(2)…11 V (default)
Current rating max. ±1 mA
Resolution 8 bit
Accuracy ±150 mV
Zero output voltage < 200 mV
Protection Short-circuit protected; protected against failure voltage (24 VAC, 40 VDC)
Feedback signal Auto/manual mode and output value
Table 48 Analog output modules data
Status LED Behavior Automatic mode Brightness follows the
commanded output signal
Override mode Flashes
Table 49 Analog output status LED behavior
Status LEDs with Manual Overrides 1 2 3 4 5 6 7 8
AUTO0
!
100
Fig. 67. Manual overrides (rotary knobs)
The CLIOPR822A/CLIOLR822A Analog Output Modules are equipped with manual overrides: one for each analog output. These rotary knobs can be manually set to either "AUTO" or "0…100%" (infinitely adjustable).
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs. Do not use excessive force. Adjust only by hand.
Manual Override in the AUTO Position When a manual override of the CLIOPR822A/CLIOLR822A is set to AUTO, and the corresponding analog output has been configured, the following applies: • If the LONWORKS network is functioning properly, the
output voltage of the analog output will be as commanded.
• If the LONWORKS network is not functioning properly, the output voltage of the analog output will be the safety position value.
• The brightness of the status LED (red) of the analog output will be proportional to the commanded output signal.
When a manual override of the CLIOPR822A/CLIOLR822A is set to AUTO, and the corresponding analog output has not been configured, the following applies: • Regardless as to whether the LONWORKS network is
functioning properly or not, the output voltage of the analog output will be 0 V (values from the LONWORKS Bus will be ignored, and there will be no heartbeat or safety position).
• The feedback signal on the LONWORKS network nvoAoActPosnFb[ ] will have a value of 0% and a state of 0.
• The analog output status LED will be dark. Manual Override in the Override Position (0…100%) When a manual override of the CLIOPR822A/CLIOLR822A is set to 0…100%, and the corresponding analog output has been configured, the following applies: • The output voltage of the analog output will be 0…10 V
(direct) or 10…0 V (reverse). • The feedback signal on the LONWORKS network
nvoAoActPosnFb[ ] will have a value of 0…100% and a state of -1.
• The status LED (red) of the analog output will flash to indicate “manual override.”
When a manual override of the CLIOPR822A/CLIOLR822A is set to 0…100%, and the corresponding analog output has not been configured, the following applies: • The output voltage of the analog output will be 0…10 V. • The feedback signal on the LONWORKS network
nvoAoActPosnFb[ ] will have a value of 0…100% and a state of -1.
• The status LED (red) of the analog output will flash to indicate “manual override.”
Analog Outputs Configured as Binary Outputs Using the engineering tool, the analog outputs can be configured individually as binary outputs. The voltage output is then 0 V or 10 V, depending upon the signal from the controller.
LION System Description of the I/O Modules
47 EN1Z-0921GE51 R0709
Connection Example
74737772767175
2221
9
74 78737271
1025 26GND
24V~
24V~
24V~
24V~0
24V~0
24V~ 0
COMB
COMB
COMB
COMA
COMA
COMA
GND
1 2 3 4 5 6 7A1 A2 A3 A4 A5 A6 A7
1 2 3
0...10V
F1F2
Shieldinternally
connected
toDIN
rail
11GND
12GND
13GND
14GND
15GND
16GND
17GND
18GND
1AO1
2 3 4 5 6 7 8
Optional
Aux. Terminal Module XS814
9GND
10GND
24V~
drive
with0...10V
signal1:
24V~
power
supply2:
GND3:
SignalM
1 2A1 A2
XS814
NC NC
CLIOP822A Analog Output Module
CLIOP822AAO2 AO3 AO4 AO5 AO6 AO7 AO8
Fig. 68 Analog output connection example
For fusing specifications see section "Fusing Specifications" on page 11.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 48
Synchronization Behavior of Analog Output Module Configured as Floating Output In order to regularly update the real actuator position with the calculated position and thus ensure that the actuator definitely reaches its end position, a synchronization process is performed by the analog output module. During the synchronization process, the analog output module will continue running for the configured runtime once it reaches the calculated end position.
This updating (synchronization) is performed: • If the calculated position of the actuator
< lower synchronization threshold (2 %) = synchronization towards 0 %
• If the calculated position of the actuator > upper synchronization threshold (98 %) = synchronization towards 100 %
• Following any power-up or any reset
Shieldinternally
Connected toDIN RAIL
123
M
12
M
Fig. 69 Connection example with Relay Module MCD 3
• The relay module facilitates the control of peripheral devices with high load via the analog outputs. • Input terminal 17 controls of MCD3 controls changeover contact K3. • Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2. For fusing specifications, see section "Fusing Specifications" on page 11.
LION System Description of the I/O Modules
49 EN1Z-0921GE51 R0709
1
9 9
74 747873 737772 727671 7175
10 1011 12 13 14 15 16 17 18 25 26
2 3 4 5 6 7 8
GND GND
24V~
24V~
24V~
24V~0
24V~0
24V~0
COMB
COMB
COMB
COMA
COMA
COMA
GND GNDGND GND GND GND GND GND GND GND
1 2 3 4 5 6 7A1 A2 A3 A4 A5 A6 A7
1 2A1 A2
XS814
CLIOP822A Analog Output Module
CLIOP822A
24V Drive with0...10V Signal1: 24V power supply2: GND3: signal
~
~
1 2 3
0...10VM
NC NC21 22
AO1 AO2 AO3 AO4 AO5 AO6 AO7 AO8
F1F2 MCE 3
K3K2K1
max. 240 V0.2 A 2 A
1 2 3 4 5 6 7 8
11 12 13 14 15 16 17 18
K1 K2 K3
Exte
rnal
gro
up re
quire
dto
pow
er e
xter
nal d
evic
es.
Optional Aux. Terminal Module XS814
Shieldinternally
Connected toDIN RAIL
Fig. 70 Connection example with Relay Module MCE 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs. • Input terminal 16 of MCE3 controls the N.O. contact K3. • Input terminal 17 of MCE3 controls the changeover contact K2. • Input terminal 18 of MCE3 controls the changeover contact K1. For fusing specifications, see section "Fusing Specifications" on page 11.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 50
Binary Input Modules
Types of Binary Input Modules and Terminal Socket Type Description Housing
CLIOP823 Panel Bus binary input module Light gray
CLIOL823 LONWORKS Bus binary input module
Dark gray
XS823 XSU823
Terminal socket Light gray
Table 50 LION Binary Input Modules
Features • 12 binary inputs • 12 configurable status LEDs (green/red, yellow/OFF) • Binary inputs can be used as
– Static digital inputs as dry-contacts (default) – Fast totalizers (up to 20 Hz)
4 53
21
Fig. 71 CLIOP823A Binary Input Module with terminal socket
Legend 1 Service button S1 2 Hex switch S2 3 Input LEDs 4 Service LED 5 Power LED Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following.
Terminals
BI12
12
25 26
74 7873 7772 7671 75
24V~
24V~
24V~0
24V~0
COMB
COMB
COMA
COMA
BI11
11BI10
10BI9
9BI8
8BI7
7BI6
6BI5
5BI4
4BI3
3BI2
2BI1
1
2423222120191817161514GND
13GND GND GND GND GND GND GND GND GND GND GND
Fig. 72 Terminal assignment and internal connections of
binary input modules
Ter-minal Signal COMMENT
71, 75 COM a 2-wire communication bus (LON/Panel Bus)
72, 76 COM b 2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply 74, 78 24 V~0 Power supply 1…12 BI1…BI12 Binary inputs 1…12
13…24 GND Ground. All grounds are connected internally to each other.
25, 26 Shield connection (functional earth), internally connected to the DIN rail.
Table 51 Description of binary input module terminals
Notes • Shield connection to be used for shielded I/O cables only.
It is not allowed to connect a LONWORKS shield, since LONWORKS requires a resistor and capacitor.
• If additional shield terminals are needed, the XS814 Auxiliary Terminal Package can be installed.
LION System Description of the I/O Modules
51 EN1Z-0921GE51 R0709
Technical Data
Input type Dry-contact or open collector
Current rating (closed input)
2 mA
Open contact voltage 16…22 VDC
Protection Protected against failure voltage (24 VAC, 40 VDC)
Status LED Behavior Using the engineering tool, the status LEDs can be configured individually for use as either alarm LEDs (red/green) or as status LEDs (yellow/OFF [default]). Given a state of "logical ON," the LED will be lit (yellow or red).
Configuration as Fast Totalizer Using the engineering tool, the binary inputs can be configured as fast totalizers for operation in conjunction with devices equipped with an open collector output.
Frequency max. 20 Hz
Pulse ON min. 25 ms
Pulse OFF min. 25 ms
Bounce max. 5 ms
Table 52 Binary inputs used as fast totalizers
Fig. 73 Configuration of binary input as fast totalizer
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 52
Connection Example
1
74 747873 737772 727671 7175
13 14 15 16 17 18 19 20 21 22 23 24 25 26
2 3 4 5 6 7 8 9 10 11 12
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11BI12
24V~
24V~
24V~
24V~0
24V~0
24V~0
B BB
A AA
Dry
contact1:
signal2:
GND1 2
Drycontact
Totalizer1: signal2: GND
1 2
Totalizermin. 25 ms
Shieldinternally
connected toDIN rail
CLIOP823A Binary Input Module
CLIOP823A
F1
Fig. 74 CLIOP823A connection examples
For fusing specifications, see section "Fusing Specifications" on page 11.
LION System Description of the I/O Modules
53 EN1Z-0921GE51 R0709
Relay Output Modules
Types of Relay Output Modules and Terminal Socket Type Description Housing
CLIOP824 Panel Bus relay output module Light gray
CLIOPR824 Panel Bus relay output module with manual overrides
Light gray
CLIOL824 LONWORKS Bus relay output module
Dark gray
CLIOLR824 LONWORKS Bus relay output module with manual overrides
Dark gray
XS824-25 XSU824-25
Terminal socket; can be fitted with long (red) cross connector (incl. in scope of the delivery)
Light gray
Table 53 LION Relay Output Modules
Features • 6 relays (changeover contacts), arranged in two blocks • …R824: 6 manual overrides
• Low and line voltage allowed, see WARNING.
21
5 64
3
Fig. 75 CLIOP824A Relay Output Module with terminal socket
Legend 1 Service button S1 2 Hex switch S2 3 Manual overrides 4 Status LEDs 5 Service LED 6 Power LED
Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following. In the event of communication problems, the relay outputs will move to the safety positions you have configured using the engineering tool, see relay output point description in the CARE – User Guide, 74-5587/EN2B-0182GE51.
WARNING
Risk of electric shock or equipment damage! Low voltage and line voltage must not be wired within the same relay block. Wire low voltage e.g., to relay block 1 and line voltage to
relay block 2 or vice versa. In this case the short cross connectors must be used, see Table 5 on page 7.
NOTICE
Risk of malfunction! Cross connectors may only be used if the same voltage is used on all relays they connect.
Do not use a cross connector if different voltages are used on the relays. E.g., use a short cross connector for relay block 1 with line voltage and no cross connector for relay block 2 with 12 V low voltage for relay 4 and 24 V low voltage for relays 5 and 6.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 54
Terminals
31 41 51 6132 42 52 6233 43 53 6334 44 54 64
NO
NC
COM
CON
NO
NC
COM
CON
11121314
21
22
23
24 25
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
Relay block 2
74 7873 7772 7671 75
24V~
24V~
24V~0
24V~0
COMB
COMB
COMA
COMA
Cross connector (can be removed, as desired)
Relay block 1
Fig. 76 Terminal assignment and internal connections of
relay output modules
Terminal Signal Comment
71, 75 COM a 2-wire communication bus (LON/Panel Bus)
72, 76 COM b 2-wire communication bus (LON/Panel Bus)
73, 77 24 V~ Power supply 74, 78 24 V~0 Power supply
11 REL1 N.O. Relay 1 N.O. contact 12 REL1 N.C. Relay 1 N.C. contact 13 R1 COM relay 1 common contact
14 R1 COM For connection of relay 1 common via cross connector*
21 REL2 N.O. Relay 2 N.O. contact 22 REL2 N.C. Relay 2 N.C. contact 23 R2 COM Relay 2 common contact
24 R2 COM For connection of relay 2 common via cross connector*
31 REL3 N.O. Relay 3 N.O. contact 32 REL3 N.C. Relay 3 N.C. contact 33 R3 COM Relay 3 common contact
REL
AY
BLO
CK
1
34 R3 COM For connection of relay 3 common via cross connector*
41 REL4 N.O. Relay 4 N.O. contact 42 REL4 N.C. Relay 4 N.C. contact 43 R4 COM Relay 4 common contact
44 R4 COM For connection of relay 4 common via cross connector*
51 REL5 N.O. Relay 5 N.O. contact 52 REL5 N.C. Relay 5 N.C. contact 53 R5 COM Relay 5 common contact
54 R5 COM For connection of relay 5 common via cross connector*
61 REL6 N.O. Relay 6 N.O. contact 62 REL6 N.C. Relay 6 N.C. contact 63 R6 COM Relay 6 common contact
REL
AY
BLO
CK
2
64 R6 COM For connection of relay 6 common via cross connector*
25 Shield connection (functional earth), internally connected to the DIN rail
* Do not connect by wire!
Table 54 Description of relay output module terminals
Permissible Loads Max. load Min. load
Per relay output module (total)
19…250 VAC current at cos φ ≥ 0.6: 12 A 1…29 VDC 12 A resistive, 3 A inductive
–
Per normally open contact
19…250 VAC current at cos φ ≥ 0.6: 4 A 1…29 VDC 4 A resistive, 1 A inductive
50 mW
Per normally closed contact
19…250 VAC current at cos φ ≥ 0.95: 2 A, current at cos φ ≥ 0.6: 1 A 1…29 VDC 4 A resistive, 1 A inductive
50 mW
Table 55 Permissible loads of relay output modules
Notes • In the case of voltages above 30 VAC/DC and if inductive
components are to be connected to relays switching more often than once every 2 minutes, these com-ponents must be prevented from causing harmful interference to radio or television reception (conformance with EN 55014).
• Max. voltage for UL 864-compliant applications is 24 V.
Status LED Behavior Relay output
Mode LED N.O.* (direct)
N.C.* (reverse)
Automatic mode, logical state “ON”
ON ON OFF
Automatic mode, logical state “OFF”
OFF OFF ON
Override mode (setting “0”) Flashes OFF ON Override mode (setting “1”) Flashes ON OFF
*As configured using the engineering tool.
Table 56 Relay output status LED behavior
Status LEDs with Manual Overrides 1 2 3 4 5 6
--1--0--AUTO
!
Fig. 77 Manual overrides (toggle switches)
The …R824A Relay Output Modules are equipped with manual overrides: one for each relay output. These sliding switches can manually be set to either "auto" or "0" or "1".
LION System Description of the I/O Modules
55 EN1Z-0921GE51 R0709
Manual Override in the AUTO Position When a manual override of the …R824 Relay Output Module is set to the “AUTO” position, and the corresponding relay output has been configured, the following applies: • If the LONWORKS network is functioning properly, the
logical status of the relay output will be “AUTO.” • If the LONWORKS network is not functioning properly, the
feedback signal will be switched to the safety position value.
• The feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of either 0% or 100%, and a state of -1.
• The status LED (yellow) will indicate the actual logical state of the relay output as commanded (by nviDoSwitch[ ]).
When a manual override of the …R824 Relay Output Module is set to the “AUTO” position, and the corresponding relay output has not been configured, the following applies: • Regardless as to whether the LONWORKS network is
functioning properly or not, values from the LONWORKS Bus will be ignored, and there will be no heartbeat or safety position.
• The feedback signal on the LONWORKS network: nvoDoActPosnFb[ ] will have a value of 0% and a state of 0.
• The status LED will be dark.
Manual Override in the ON Position When a manual override of the …R824 Relay Output Module is set to the “ON” position, the following applies: • If the relay output has been configured, its logical state
will depend upon the actual output configuration. • If the relay output is unconfigured, it will be switched ON. • Regardless of configuration, the feedback signal on the
LONWORKS network: nvoDoActPosnFb[ ] will have a value of 1000…0% and a state of -1.
• Regardless of configuration, the status LED (yellow) will flash to indicate “manual override.”
Manual Override in the OFF Position When a manual override of the …R824 Relay Output Module is set to the “OFF” position, the following applies: • If the relay output has been configured, its logical state
will depend upon the actual output configuration. • If the relay output is unconfigured, it will be switched
OFF. • Regardless of configuration, the feedback signal on the
LONWORKS network: nvoDoActPosnFb[ ] will have a value of 0% (direct) or 100% (reverse) and a state of -1.
• Regardless of configuration, the status LED (yellow) will flash to indicate “manual override.”
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 56
Connection Example
74 747873 737772 727671 7175
24V~
24V~
24V~
24V~0
24V~0
24V~0
COMB
COMB
COMB
COMA
COMA
COMA
25
1 2 3 4 5 6 7A1 A2 A3 A4 A5 A6 A7
Optional Aux. Terminal Module XS514
CLIOP824A Relay Output Module
Power Supply230 V~
Shield internallyconnected to DIN RAIL
Cross Connector (Factory mounted)
NO
NC
COM
111213
CON 14
NO
NC
COM
21
22
23
CON 24
313233
NO
NC
COM
34CON
414243
NO
NC
COM
44CON
515253
NO
NC
COM
54CON
616263
NO
NC
COM
64CON
NL
F1Field Device1: 230 V (L)2: 230 V (N)
Field Device1: 230 V (L)2: 230 V (N)
1 12 2
M M230V 230V
230
V
Fig. 78 CLIOP824A connection example (both relay blocks with line voltage)
For fusing specifications see section "Fusing Specifications" on page 11.
LION System Description of the I/O Modules
57 EN1Z-0921GE51 R0709
Fig. 79 CLIOP824A connection example (relay blocks with low and line voltage)
For fusing specifications see section "Fusing Specifications" on page 11.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 58
Floating Output Module
Features • Type: CLIOPR825A Floating Output Module • Housing: light gray • Floating outputs sufficient for driving up to 3 floating
actuators • Manual overrides and 3 corresponding pairs of status
LEDs In the event of communication problems, the 3 floating outputs will move to the safety positions you have configured using the engineering tool, see floating output point description in the CARE – User Guide, 74-5587/EN2B-0182GE51.
5 64
3
21
Fig. 80 CLIOPR825A Floating Output Module with
terminal socket
Legend 1 Service button S1 2 Hex switch S2 3 Manual overrides 4 Status LEDs 4 Service LED 5 Power LED Functionality of service LED and power LED: see Table 77 to Table 79 on page 78 and following.
WARNING
Risk of electric shock or equipment damage! Low voltage and line voltage must not be wired within the same relay block. Wire low voltage e.g., to relay block 1 and line voltage to
relay block 2 or vice versa. In this case the short cross connectors must be used, see Table 5 on page 7.
NOTICE
Risk of malfunction! Cross connectors may only be used if the same voltage is used on all relays they connected.
Do not use a cross connector if different voltages are used on the relays. E.g., use a short cross connector for relay block 1 with line voltage and no cross connector for relay block 2 with 12 V low voltage for relay 4 and 24 V low voltage for relays 5 and 6.
Permissible loads
Max. load Min. load
Per relay output module (total)
19…250 VAC current at cos φ ≥ 0.6: 12 A 1…29 VDC 12 A resistive, 3 A inductive
–
Per normally open contact
19…250 VAC current at cos φ ≥ 0.6: 4 A) 1…29 VDC 4 A resistive, 1 A inductive
50 mW
Per normally closed contact
19…250 VAC current at cos φ ≥ 0.95: 2 A, current at cos φ ≥ 0.6: 1 A 1…29 VDC 4 A resistive, 1 A inductive
50 mW
Table 57 Permissible loads of floating output modules
Notes • In the case of voltages above 30 VAC/DC and if inductive
components are to be connected to relays switching more often than once every 2 minutes, these com-ponents must be prevented from causing harmful interference to radio or television reception (conformance with EN 55014).
• Max. voltage for UL 864-compliant applications is 24 V.
LION System Description of the I/O Modules
59 EN1Z-0921GE51 R0709
Terminals
Actuator 2 Actuator 3
31 41 51 6132 42 52 6233 43 53 6334 44 54 64
NO
NC
COM
CON
NO
NC
COM
CON
11121314
21
22
23
24 25
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
NO
NC
COM
CON
74 7873 7772 7671 75
24V~
24V~
24V~0
24V~0
COMB
COMB
COMA
COMA
Cross connector (can be removed, as desired)
Actuator 1
Fig. 81 Terminal assignment and internal connections of
floating output module
Ter-minal Signal Comment
71, 75 COM a 2-wire communication bus (LON/Panel Bus)72, 76 COM b 2-wire communication bus (LON/Panel Bus)73, 77 24 V~ Power supply 74, 78 24 V~0 Power supply
11 REL1 N.O. Floating relay 1 N.O. contact 12 REL1 N.C. Floating relay 1 N.C. contact 13 R1 COM Floating relay 1 common contact
14 R1 COM For connection of floating relay 1 common via cross connector*
21 REL2 N.O. Floating relay 2 N.O. contact 22 REL2 N.C. Floating relay 2 N.C. contact 23 R2 COM Floating relay 2 common contact A
CTU
ATO
R 1
24 R2 COM For connection of floating relay 2 common via cross connector*
31 REL3 N.O. Floating relay 3 N.O. contact 32 REL3 N.C. Floating relay 3 N.C. contact 33 R3 COM Floating relay 3 common contact
34 R3 COM For connection of floating relay 3 common via cross connector*
41 REL4 N.O. Floating relay 4 N.O. contact 42 REL4 N.C. Floating relay 4 N.C. contact 43 R4 COM Floating relay 4 common contact A
CTU
ATO
R 2
44 R4 COM For connection of floating relay 4 common via cross connector*
51 REL5 N.O. Floating relay 5 N.O. contact 52 REL5 N.C. Floating relay 5 N.C. contact 53 R5 COM Floating relay 5 common contact
54 R5 COM For connection of floating relay 5 common via cross connector*
61 REL6 N.O. Floating relay 6 N.O. contact 62 REL6 N.C. Floating relay 6 N.C. contact 63 R6 COM Floating relay 6 common contact A
CTU
ATO
R 3
64 R6 COM For connection of floating relay 6 common via cross connector*
25 Shield connection (functional earth), internally connected to the DIN rail
* Do not connect by wire!
Table 58 Description of floating output module terminals
Status LED Behavior The respective pair of status LEDs will display the following:
Actuator 1 Mode LED
Closing Opening Not moving
Green LED ON OFF OFF Auto
Red LED OFF ON OFF
Green LED Flashing OFF Flashing Override
Red LED OFF Flashing Flashing
Table 59 LED behavior (for e.g., floating output 1)
Status LEDs with Manual Overrides 1 2 3
AUTO0
!
100
Fig. 82 Manual overrides (rotary knobs)
The floating output module is equipped with manual overrides: one for each floating output. These rotary knobs can be manually set to either "AUTO" or "0 … 100%" (infinitely adjustable).
NOTICE
Damage to the electronic module!
Do not use a tool to adjust the rotary knobs. Do not use excessive force. Adjust only by hand.
Manual Override in the AUTO Position When a manual override of the CLIOPR825A is set to AUTO, the following applies: • The output signal of the respective floating output (R1 +
R2 or R3 + R4 or R5 + R6) will be as commanded. • The respective pair of status LEDs will be ON/OFF as
commanded. Manual Override in the Override Position (0…100%) When a manual override of the CLIOPR825A is set to 0…100%, the respective floating output will drive to the set position. The runtime depends upon the actuator runtime configured using the engineering tool and on the actual position.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 60
Configured Floating Relay Output If a floating relay output has been configured, the following applies: The corresponding manual override can be used to adjust the respective floating actuator so that it drives to any desired position between fully closed (0%) and fully open (100%). The "open" relay or "closed" relay – as the case may be – is then switched ON for the time the actuator requires to drive to the desired position, whereupon it will stop. This required time depends upon the configured motor runtime (time to open / time to close), while the direction of movement is dependent upon the configured direct/reverse setting. Unconfigured Floating Relay Output
AUTO0 100
BOTH RELAYS OFFACTUATOR STOPS
AUTO100
RELAY “N” CLOSEDRELAY “N+1” OPENACTUATOR CLOSES
AUTO
RELAY “N” OPENRELAY “N+1” CLOSED
ACTUATOR OPENS
100
50 50
0 0
Fig. 83. Use of manual override (floating relay output unconfigured)
If a floating relay output has not been configured (see Fig. 83), the following applies: Although the motor runtime is unknown to the CLIOPR825A, the corresponding manual override can be used during the commissioning phase to adjust the respective floating actuator so that it drives to any desired position between fully closed (0%) and fully open (100%). The "open" relay (relay "n," i.e. “1,” “3,” or “5”) and the "closed" relay (relay "n+1," i.e. “2,” “4,” or “6”) are then switched ON and/or OFF, respectively, when the corresponding manual override is set to "0…100%." Specifically, the actuator will drive towards its closed position as long as the manual override is set to "0…50%," and it will drive towards its open position as long as it is set to "50…100%." Setting the manual override to "AUTO" stops the actuator.
LION System Description of the I/O Modules
61 EN1Z-0921GE51 R0709
Connection Example
74 747873 737772 727671 7175
24V~
24V~
24V~
24V~0
24V~0
24V~0
COMB
COMB
COMB
COMA
COMA
COMA
1 2 3 4 5 6 7A1 A2 A3 A4 A5 A6 A7
CLIOPR825A Floating Output Module
NO
NC
COM
21
22
23
313233
NO
NC
COM
414243
NO
NC
COM
515253
NO
NC
COM
616263
NO
NC
COM
64CON
NL
123
M
Power
supply230
V
or
other~
CON 24 34CON 44CON 54CONCON 14
NO 11NC 12
COM 13
25
F1
Cross
connector
(factory
-mounted)
Shield
internallyconnected to DIN rail
Optional
aux.
Terminal
Module
XS814
1:
2:
3:
N
Floating
actuatorwith
24~V
(requires
two
relays)
Fig. 84 CLIOPR825A Connection example (floating actuator)
For fusing specifications see section "Fusing Specifications" on page 11.
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 62
Mixed Panel Bus I/O Module CLIOP830A
Features • Type: CLIOP830A Mixed Panel Bus I/O Module • Housing: light-gray In the event of communication problems, the relay outputs will move to the safety positions you have configured using the engineering tool, see relay output point description in the CARE – User Guide, EN2B-0182GE51 / 74-5587.
AI5
AI1 AI2 AI3 AI4 41G1 G2
42
1713 14 15 16
18 19 20AI6 AI7 AI8 AO5
2521 22 23 24
26 27 28 3529 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 2 3 4 5 6
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342 3 4 5 6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
Analog Inputs Analog OutputsGND
DO!
CLIOP830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9A
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9B
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9C
24V Relays
2 1 0 F E
D C B
9 8
7
6 5 4 3
A
40 External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75767778
COM aCOM b24V~24V~0
COM aCOM b
24V~24V~0
727374 S2
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8D
B7
B1 B2 B3 B4 B5 B6
B8 B9 B10 B11 B12
DI
Binary Inputs
Install. Instr.EN1B-0375GE51
71 2 3 4 5 6
8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Fig. 85 CLIOP830A Mixed I/O Module (shown with aux.
terminal packages)
AI5
AI1 AI2 AI3 AI4 41G1 G2
42
1713 14 15 16
18 19 20AI6 AI7 AI8 AO5
2521 22 23 24
26 27 28 3529 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 2 3 4 5 6
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342 3 4 5 6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
Analog Inputs Analog OutputsGND
DO!
CLIOP830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
24V Relays
2 1 0 F E
D C B
9 8
7
6 5 4 3
A
40 External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75767778
COM aCOM b24V~24V~0
COM aCOM b
24V~24V~0
727374 S2
B7
B1 B2 B3 B4 B5 B6
B8 B9 B10 B11 B12
DI
Binary Inputs
Install. Instr.EN1B-0375GE51
71 2 3 4 5 6
8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
2 3 4
1
Fig. 86 CLIOP830A Mixed I/O Module - features
Legend 1 Hex switch S2 2 Status LEDs 3 Service LED 4 Power LED Functionality of service LED and power LED: see Table 77 to Table 79 on page 78.
WARNING
Risk of electric shock or equipment damage! It is not permitted to wire the relays of the mixed Panel Bus I/O modules for anything other than low voltage.
Permissible Loads
load min. load
per mixed Panel Bus I/O module (total for all relay contacts)
24 VDC/VAC max. 3 A resistive or induc-tive, cos φ ≥ 0.6, no capacitive load
–
per normally open contact
24 VDC/VAC min. 0.05 A resistive or inductive, cos φ ≥ 0.6, max. 0.5 A resistive or inductive, cos φ ≥ 0.6, no capacitive load
>50 mW
Table 60 Permissible loads of mixed Panel Bus I/O modules
LION System Description of the I/O Modules
63 EN1Z-0921GE51 R0709
Terminals
ANALOGINPUTS
ANALOGOUTPUTS 24 V RELAYSGNDBINARY
INPUTS
1B1
2B2
3B3
4B4
5B5
6B6
7B7
8 9 10 11 12B8 B9 B10 B11 B12
13 1414 15 16AI1AI2AI2 AI3 AI417 18 19 20AI5 AI6 AI7 AI8
25 26 27
21 22 23 24
28AO5 AO6 AO7
AO1 AO2 AO3 AO4
AO8
41G1
42G2
74737271
24V~24
V~0
COMB
COMA
78777675
24V~24
V~0
COMB
COMA
J1 J2 J3 J4 J5
IN1
NO1
35
29
IN2
NO2
36
30
IN3
NO3
37
31
IN4
NO4
38
32
IN5
NO5
39
33
IN6
NO6
40
34
R1 R2 R3 R4 R5 R6
EXT. 24VAC FORRELAY COMMON
JUMPER JUMPER JUMPER JUMPER JUMPER
Fig. 87 Terminal assignment and internal connections of mixed Panel Bus I/O module terminals
Terminal Signal LED Comment
71, 75 COM a status 2-wire communication bus (Panel Bus)
72, 76 COM b status 2-wire communication bus (Panel Bus)
73, 77 24 V~ power Power supply
74, 78 24 V~0 power Power supply
1…7 BI1…7 1…7 Binary inputs 1…7
8…12 BI8…12 24…28 Binary inputs 8…12
13…20 AI1…8 -- Analog inputs 1…8
41, 42 GND -- Ground. Both grounds are internally connected to each other and to 24 VAC0.
21…28 AO1…AO8 -- Analog outputs 1…8
29…34 NO1…6 29…34 Relays 1…6, normally-open contacts
35…39 IN1…5 --
Common contacts of relays 1…5. May be set to common supply voltage via terminal 40 by inserting jumpers J1…J5 into their lower positions. When, in contrast, a jumper is in the upper position (the so-called “parking position” = default setting), the corresponding relay receives no supply voltage from terminal 40.
40 IN6 --
Common contact of relay 6, internally connected to the middle contact of jumpers J1…J5. May be used to connect common supply voltage.
Table 61 Description of mixed Panel Bus I/O module terminals
Description of the I/O Modules LION System
EN1Z-0921GE51 R0709 64
Connection Example
74 7873 7772 7671 75
24V~
24V~
24V~0
24V~0
COMB
COMB
COMA
COMA
41 42
B10 B11 B12 AI5
AI1
AI6
AI2
AI7
AI3
AI8
AI4
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
IN1
NO1
IN2
NO2
IN3
NO3
IN4
NO4
IN5
NO5
IN6
NO6
B7 B8 B9
7 8 9 10 11 12 17
13
18
14
19
15
20
16
25
21
26
22
27
23
28
24
35
29
36
30
37
31
38
32
39
33
40
34
B1 B2 B3 B4 B5 B6
1 2 3 4 5 6
A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9
7 77 78 88 89 99 9
A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6
1 11 12 22 23 33 34 44 45 55 56 66 6
2 21 1 2 23 31 11 2 1 2
F1
G1 G2
Fig. 88 CLIOP830A Connection example
For fusing specifications see section "Fusing Specifications" on page 11. For internal connections of auxiliary terminal modules, see section “XS830 Auxiliary Terminal Package” and section “XS831 Auxiliary Terminal Package” on page 66.
74 7873 7772 7671 75
24V~
24V~
24V~0
24V~0
COMB
COMB
COMA
COMA
41G1 G2
42
B10 B11 B12 AI5
AI1
AI6
AI2
AI7
AI3
AI8
AI4
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4 NO1NO2NO3NO4NO5NO6
B7 B8 B9
7 8 9 10 11 12 17
13
18
14
19
15
20
16
25
21
26
22
27
23
28
24
35
29
36
30
37
31
38
32
39
33
40
34
B1 B2 B3 B4 B5 B6
1 2 3 4 5 6
A7
A4 A8
A7B7 B7A8
B4 B8
A8B8 B8A9
G1 G2
A9B9 B9
7
7 7
77 78
8 8
88 89
9 9
99 9
A1
A1 A5
A1B1 B1A2
B1 B5
A2B2 B2A3
A2 A6
A3B3 B3A4
B2 B6
A4B4 B4A5
A3 A7
A5B5 B5A6
B3 B7
A6B6 B6
1
1 1
11 12
2 2
22 23
3 3
33 34
4 4
44 45
5 5
55 56
6 6
66 6
2 31
F1
IN1 IN2 IN3 IN4 IN5 IN6
Fig. 89 CLIOP830A Connection example (for current inputs)
LION System Description of Extra Parts
65 EN1Z-0921GE51 R0709
Description of Extra Parts
Manual Disconnect Modules Types
Manual disconnect module
Corresponding I/O modules CLIOP/CLIOL…
XS812 …821 …822 …823
XS812RO
…824 …825
Table 62 Manual disconnect modules
For mounting the manual disconnect modules, see Fig. 24 on page 21.
WARNING
Risk of electric shock or equipment damage due to improper use of XS812RO manual disconnect module!
Do not connect line voltage to the XS812RO.
Features • Disconnector switches are used to manually disconnect
individual terminals of the corresponding electronic module of pluggable I/O modules.
• Useful for troubleshooting and installation. Diagrams
Fig. 90 XS812 and analog input/analog output modules
Fig. 91 XS812 and binary input modules
XS824-25 Terminal Socket
... 824 or CLIOPR825 Electronic Module
1
NO1
NO2
NO3
NO4
NO5
NO6
NC1
NC2
NC3
NC4
NC5
NC6
2 3 4 5 6 7 8 9 10 11 12
XS812RO
Fig. 92 XS812RO and relay modules/floating module
Description of Extra Parts LION System
EN1Z-0921GE51 R0709 66
XS814 Auxiliary Terminal Package Features • Type: XS814 Auxiliary Terminal Package • For mounting onto already installed pluggable
I/O modules in order to equip them with additional terminals.
• Each unit consists of 2 terminal blocks (the "A" block and the "B" block), each with 7 terminals with a maximum load of 12 A.
Fig. 93 XS814 Auxiliary Terminal Package
Terminal Assignment
1 2 3 4 5 6 7A1 A2 A3 A4 A5 A6 A7
1 2 3 4 5 6 7B1 B2 B3 B4 B5 B6 B7
Fig. 94 Terminal assignment and internal connections of
XS814 Auxiliary Terminal Package
XS830 Auxiliary Terminal Package Features • Type: XS830 Auxiliary Terminal Package • For mounting onto the top and/or bottom of already-
installed CLIOP830A mixed I/O modules in order to equip them with additional terminals.
• Each unit consists of two groups of terminal blocks (the "A" block and the "B" block), each with nine internally-connected push-in terminals with a maximum load of 12 A.
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
Fig. 95 XS830 Auxiliary Terminal Package
Terminal Assignment
1 12 23 34 45 56 6A1 B1A2 B2A3 B3A4 B4A5 B5A6 B6A7 A8 A9 B7 B8 B9
7 8 9 7 8 9
Fig. 96 Terminal assignment and internal connections of
XS830 Auxiliary Terminal Package
XS831 Auxiliary Terminal Package Features • Type: XS831 Auxiliary Terminal Package • For mounting onto the top and/or bottom of already-
installed CLIOP830A mixed I/O modules in order to equip them with additional terminals.
• Each unit consists of two groups of four pairs of push-in terminals (A1B1, A2B2, … A8B8, each with a 499Ω resistor) for converting 0…20 mA signals (maximum load per resistor = 25 mA) into 0…10 Vdc signals, and one push-in ground terminal per group. See also Fig. 98.
Note The ground side of each of the eight incoming 0…20 mA signals (A1B1, A2B2, … A8B8) must be connected to a ground terminal.
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
Fig. 97 XS831 Auxiliary Terminal Package
Terminal Assignment
1 12 23 34 45 56 6A1 B1 A2 B2 A3 B3 A4 B4 G1 A5 B5 A6 B6 A7 A8B7 B8 G2
7 8 9 7 8 9
Fig. 98 Terminal assignment and internal connections of
XS831 Auxiliary Terminal Package
LION System Description of Extra Parts
67 EN1Z-0921GE51 R0709
Cross Connectors XS815 Cross Connector Features • For connecting the common terminals of all 6 relays of
the CLIOL824 and CLIOLR824 Relay Output Modules and the CLIOLR825 Floating Output Module. This is permitted when all terminal blocks carry the same voltage
• Long, red • Supplied with the terminal socket
Fig. 99 XS815 Cross Connector
XS817 Cross Connector Features • For connecting the common terminals of only relays 1–3
or of relays 4–6 of the CLIOL824 and CLIOLR824 Relay Output Modules and the CLIOLR825 Floating Output Module.
• Short, yellow • Must be ordered separately
Fig. 100 XS817 Cross Connector
XAL10 Swivel Label Holders • Type: XAL10 Swivel Label Holder. • Supplied with the terminal socket. • For applying self-adhesive labels with application
information generated using the engineering tool to the pluggable I/O modules.
• For use with standard commercially-available labels, e.g., AVERY 6572 or 6578
XAL11 Swivel Label Holders • Type: XAL11 Swivel Label Holder. • Supplied with the mixed I/O module. • For applying self-adhesive labels with application
information generated using the engineering tool to the mixed I/O modules.
• For use with standard commercially-available labels, e.g., AVERY 5444, 5523, 8253, 16163, or 15513
XS816 Bridge Connectors • Type: XS816 Bridge Connectors • Bridge connectors transmit both communication signals
and power supply between LION modules • Supplied with the terminal socket / CLIOP830A
LON Software Interface Description LION System
EN1Z-0921GE51 R0709 68
LON Software Interface Description
Overview
LonTalk Protocol LION LONWORKS Bus I/O Modules use a LONTALK protocol communication with other nodes on the LONWORKS network, with commissioning tools und supervisory devices. Features • Network variables for communications between nodes,
but no explicit messages • Configuration network variables • LONMARK FPT protocol for downloading a LION
LONWORKS Bus I/O Module firmware via LONWORKS: loadable apbG file (supported by CARE and EXCELON)
Addressing, binding, and commissioning LION LONWORKS Bus I/O Modules are addressed, bound, and commissioned using CARE or any other standard LONWORKS commissioning tool based on LNS 2.0 and higher, e.g., LonMaker for Windows. Configuration LION LONWORKS Bus I/O Modules are configured using CARE or COACH.
CLIOL821A Analog Input Module For the CLIOL821A Analog Input Module the LONMARK Profile 520 "Analog Input" has been assigned per input. Each input object has its own configuration properties, except for heartbeat configuration, which will be shared among all objects.
Fig. 101 LONMARK analog input object
Input types and corresponding NVs
Input type NV used
NTC10kΩ NTC20kΩ PT1000-1 NI1000TK5000 PT3000 BALCO500
nvoAiTempP
PT1000-2 nvoAiTemp
0(2)…10V nvoAiValuePct
Slow binary input nvoAiSwitch
Other Sensors
Sensor break/short circuit INVALID
Table 63 Input types and corresponding NVs
Transmission/Updates These variables are transmitted immediately when their value has been changed by a higher rate than the configured "send on delta" (default: 0.3 K). These variables are also transmitted as heartbeat output (default: 60 sec) on a regular basis as dictated by the maximum send time (nciSndHrtBt) configuration variable.
LION System LON Software Interface Description
69 EN1Z-0921GE51 R0709
Default Service Type The default service type of these variables is unacknowledged.
Analog Sensor Output – nvoAiValuePct[ ] This network variable output represents the percentage level for the appropriate input, if configured for voltage input. Valid Ranges for 0 … 10 V Input
Value Representation
< 0 V 0 %
0 V … 10 V 0 … 100 %
> 10 V 100 %
Table 64 Analog input values: 0 … 10 V
Valid Ranges for 2 … 10 V Input
Value Representation
< 1.5 V Sensor break/short circuit
1.5 V … 2 V 0 %
2 V … 10 V 0 … 100 %
> 10 V 100 %
Table 65 Analog input values: 2 … 10 V
Default Value The default value is set after power-up or reset and remains until the module has measured a valid value. nvoAiValuePct = INVALID = 0x7FFF (=163.835 %) The sensor failure behavior can be configured for 2 … 10 V.
Temperature Sensor Output – nvoAiTempP[ ] If configured for temperature sensor input (but not from PT1000-2 temperature sensors), this network variable output represents the temperature for the appropriate input. Range: see Table 44 and Table 45 on page 41. Default Value The default value is set after power-up or reset and remains until the module has measured a valid value. nvoAiTempP = INVALID = 0x7FFF (= 327.67 °C)
Slow Digital Input – nvoAiSwitch[ ] This network variable output represents a slow digital input connected to the universal input terminals. Valid Range
Sensor Value State
Enabled 100 % 1
Disabled 0 % 0
Not configured 0 % -1
Table 66 Slow digital input values
Temperature#2 Sensor Output – nvoAiTemp[ ] If configured for temperature sensor input (from PT1000-2 temperature sensors, only), this network variable output represents the temperature for the appropriate input. Range: see Table 44 and Table 45 on page 41. Default Value The default value is set after power-up or reset and remains until the module has measured a valid value. nvoAiTemp = INVALID = 0xFFFF (= 6279.5 °C)
LON Software Interface Description LION System
EN1Z-0921GE51 R0709 70
CLIOL(R)822A Analog Output Module For the CLIOL822A/CLIOLR822A Analog Output Module, the LONMARK open-loop actuator object has been assigned per output. Each analog output object has its own configuration properties, except for heartbeat configuration and nciAoConfig, which will be shared among all objects.
Fig. 102 LONMARK analog output object
Receive Heartbeat The default configuration for “Receive Heartbeat” is 300 sec. If no nvi update is received during this time, the actuators will go to their configured safety positions. Start-up Behavior At start-up, i.e., power-up or reset, all nvi's will be initialized with INVALID, and after 1 minute, the actuators will go to their configured safety positions.
Analog Output Control Level – nviAoValuePct[ ] This network variable is used to drive the analog output to 0 … 100 %. If both nviAoSwitch[ ] and nviAoValuePct[ ] receive valid values, nviAoValuePct[ ] will have priority. Valid Ranges
Fig. 103 Analog output control levels – direct actuator
Fig. 104 Analog output control levels – reverse actuator
Default Value nvoAoValuePct = INVALID = 0x7FFF (=163.835 %) This will cause the actuator to adopt a predefined position defined for failure behavior.
LION System LON Software Interface Description
71 EN1Z-0921GE51 R0709
Analog Output Feedback – nvoAoPosnFb[ ] This value represents the current status of the analog output including feedback related to manual override initiated from the manual override. This is typically used for monitoring purposes at a supervisory station or for diagnostic purposes. Valid Range
Value State Current analog output position
0.5 … 100 % 1
0 % (OFF) 0
Analog output position due to normal control by nviAoSwitch or nviAoValuePct
0 … 100 % -1 Manual override position via the manual override panel
0xFF -1 Current position unknown or synchronization active, analog output not configured
Table 67 Analog output feedback range
Transmission This variable is transmitted immediately when the corresponding network input variable has changed more than 1 % or immediately as an answer to an nviAoValuePct[ ] or nviAoSwitch[ ] update. Default Service Type The default service type is unacknowledged.
Analog Output Command – nviAoSwitch[ ] This network variable is used to drive the analog output to 0 … 100 %. It is typically bound to a LONWORKS control device issuing an output level 0 … 100 %. If both nviAoSwitch[ ] and nviAoValuePct[ ] receive valid values, nviAoValuePct[ ] will have priority. Default Value Value = 0 State = –1
LON Software Interface Description LION System
EN1Z-0921GE51 R0709 72
CLIOL823A Binary Input Module One instance of the LONMARK open-loop sensor object has been assigned per input of the CLIOL823A Binary Input Module. Each digital input object has its own configuration properties, except for heartbeat configuration, which will be shared among all objects.
nvoDiSwitch[x]SNVT_switch
nvoDiCount[x]SNVT_count
ConfigurationParameterValue File
Open Loop Sensor Object(LonMark Object Type 1)
|1
#1
nciDiConfig[x]UCPT_DIConfig
nciSndHrtBtSCPTmaxSendTime
Fig. 105 LONMARK digital input object
Transmission These variables are transmitted immediately when its value has been changed by a higher rate than the configured "send on delta" (in the case of the totalizer, “send on delta” has a default value of 5 counts). These variables are also transmitted as a heartbeat output on a regular basis as dictated by the maximum send time (nciSndHrtBt) (default = 0 = disabled) configuration variable. Default Service Type The default service type of these variables is unacknowledged.
Fast Binary Input – nvoDiSwitch[ ] This network variable output represents the logical state of a fast binary input connected to the binary input terminals. Valid Range
Logical input state Value State
ON 100 % 1
OFF 0 % 0
Not configured 0 % -1
Table 68 Slow digital input values
Default Value The default value is set after power-up or reset and remains until the module has measured a valid value. Value = 0 State = -1
Totalizer Count – nvoDiCount[ ] This network variable output indicates the total number of transitions from 0 to 1 since the last reset due to power-up or network reset. Valid Range
Fig. 106 Totalizer
State Value
For totalizer counts 0 … 65534
For power-up/reset 65535
Table 69 Totalizer counts
Power-up/Reset After power-up and reset, the value 0xFFFF = 65535 will be sent to the network to indicate that previous count values have been lost due to a reset.
LION System LON Software Interface Description
73 EN1Z-0921GE51 R0709
CLIOL(R)824A Relay Output Module One instance of the LONMARK open-loop sensor object has been assigned per input of the CLIOL824A/CLIOLR824A Relay Output Module. Each output object has its own configuration properties, except for heartbeat configuration, which will be shared among all objects.
ConfigurationParameterValue File
nviDoSwitch[x]SNVT_switch
nvoDoActPosnFb[x]SNVT_switch
Open Loop Actuator Object(LonMark Object Type 3)
nciDoConfig[x]UCPT_DOConfig
nciRcvHrtBt[x]SCPTmaxRcvTime
|1
#1
Fig. 107 LONMARK output object
Relay Output Command – nviDoSwitch[ ] This network variable is used to drive the relay output. It is typically bound to a LONWORKS control device issuing an output level ON/OFF, respectively 0 … 100 %. Valid Range
Value State Action
N/a 0 OFF
0 1 OFF
0.5 … 100 % 1
Outputs are switched according to actual output type configuration
N/a -1 INVALID: as defined for failure behavior
Table 70 Relay output command values
Default Value Value = 0 State = -1 Start-up Behavior At start-up, i.e., power-up or reset, all nvi's will be initialized with INVALID, leading the actuator to drive to the configured safety position after 1 minute. Receive Heartbeat The default configuration for “Receive Heartbeat” is 300 sec. If no nvi update is received during this time, the field devices will go to their configured safety positions.
Troubleshooting LION System
EN1Z-0921GE51 R0709 74
Troubleshooting
Testing Wiring Connections Push-in terminals feature small holes (1 mm in diameter) which can be used to measure the signals. Insert a probe (1) as shown on the right.
Fig. 108 Testing wiring connections
Troubleshooting on the CLLIONLC01 Controller The following LEDs of the CLLIONLC01 Controller can be used for troubleshooting purposes: • Power LED (green) • Alarm LED (red) • LONWORKS service LED • C-Bus Tx and Rx LEDs • HMI Tx and Rx LEDs • Modem Interface Tx and Rx LEDs
Power LED (green) case Power LED Meaning Remedy
1 ON Normal operation No action necessary
2 Flashing One or more of the internal voltage supplies are outside of the permissible ranges. The controller stops operation.
Check power Check wiring If the problem persists, replace
hardware
3 Goes out briefly • The operator has activated the reset button • The controller is performing a warm start
No action necessary
Table 71 CLLIONLC01 power LED
LION System Troubleshooting
75 EN1Z-0921GE51 R0709
Alarm LED (red) Case Alarm LED Meaning Remedy
1 OFF Normal operation No action necessary
2 ON Watchdog alarm output is powered – The controller has encountered a
hardware problem - or -
– The application has a fault - or -
– The controller has been powered up without an application or the operator has manually stopped the application, e.g., using XL-Online. In this case, the LED will light up 13 minutes after power-up without application
Try powering down and then powering up the CLLIONLC01.
If the problem persists, check and – if necessary – reload the application.
If the problem still persists, replace hardware
3 Flashing Although the controller has encountered a problem, the watchdog alarm output has not yet been powered. If the problem persists, the LED will become lit constantly, see case #2. The controller performs a warm start.
If it happens only once, the controller has performed a restart If, however, it happens multiple times, then there is an application or hardware problem (see case #2)
Table 72 CLLIONLC01 alarm LED
Troubleshooting LION System
EN1Z-0921GE51 R0709 76
LONWORKS Service LED
Fig. 109 Flashing pattern of the LONWORKS service LED
The LONWORKS service LED of the controller module displays the following flashing patterns indicating possible failure modes:
case When can it occur? Meaning Remedy
1 Anytime Node is configured and running normally No action necessary
2 Power up of controller Bad node hardware Replace hardware
3 Power up of controller Bad node hardware Replace hardware
4 Power up / reset Node lacks application. May be caused by neuron chip firmware when a mismatch occurs on application checksum
Using EXCELON, set module to “configured online”
If the problem persists, the MIP software on LW interface has been erased due to wrong setting performed using ECHELON tool: Replace hardware
5 Anytime Watchdog timer resets occurring. Possible corrupt EEPROM and bootstrap mode
Download firmware
6 Anytime Node is unconfigured but has an application Proceed with commissioning
Table 73 CLLIONLC01 LONWORKS service LED
LION System Troubleshooting
77 EN1Z-0921GE51 R0709
C-Bus Tx and Rx LEDs case C-Bus LEDs Meaning Remedy
If the C-bus is functioning properly, then the CLLIONLC01 Controller is functioning properly
No action necessary 1
Both LEDs are flashing
If the C-bus is not functioning properly, then the termination can be wrong
Check C-bus termination switch S1 (location: see Fig. 47 on page 34)
2 Both LEDs are OFF No C-bus communication Check C-bus settings
3 Both LEDs are flashing synchronously
No C-bus communication Check C-bus wiring
Table 74 CLLIONLC01 C-Bus Tx and Rx LEDs
HMI Tx and Rx LEDs case HMI LEDs Meaning Remedy
1 Both LEDs are flashing If the HMI Interface is functioning properly, then the CLLIONLC01 Controller is functioning properly
No action necessary
2 Both LEDs are OFF No HMI Interface communication Check HMI Interface connection and proper earthing of connected hardware
Table 75 CLLIONLC01 HMI Tx and Rx LEDs
Modem Tx and Rx LEDs case Modem LEDs Meaning Remedy
1 Both LEDs are flashing If the Modem Interface is functioning properly, then the CLLIONLC01 Controller is functioning properly
No action necessary
2 Both LEDs are OFF No Modem Interface communication Check Modem Interface connection
Table 76 CLLIONLC01 modem Tx and Rx LEDs
Troubleshooting LION System
EN1Z-0921GE51 R0709 78
I/O Modules Troubleshooting Check if the power supply voltage level is OK and that there is no high voltage (> 24 VAC or > 40 VDC) connected to the
inputs/outputs of the …821, …822, …823 I/O modules. Replace the problem I/O module with another module of the same kind.
– If the problem persists, this is an indication that the problem is caused by the application or incorrect wiring. – If the problem is solved, this is an indication that the I/O module was defective.
For troubleshooting purposes, the following features can be used: • Power LED (all LION I/O modules) • Service LED (all LION 800 I/O modules) • Service button (pluggable LION I/O modules, only) In addition, a module-specific troubleshooting may be necessary.
Power LED of I/O Modules case Power LED Meaning Remedy
1 ON I/O module is powered No action necessary
2 OFF No power Check power supply
3 Flashing continuously If the I/O module’s service LED is likewise flashing, the I/O module is in the boot mode
Wait until rebooting (firmware download) has been completed
Table 77 Power LED of I/O modules
LION System Troubleshooting
79 EN1Z-0921GE51 R0709
Service LED of I/O Modules case Service LED Meaning Remedy 1 LED remains OFF after
power-up If the power LED is also OFF, then
– Defective device hardware – Possible power supply problems, clock
problems, or defective processor
Replace hardware
2 LED is lit continuously after first power-up
• LONWORKS Bus I/O modules: – Defective hardware
• Panel Bus I/O modules: – I/O module has not yet been configured
by XCL8010 – Boot loader is active – Failure during last firmware download – Checksum error
LONWORKS Bus I/O modules: Replace hardware Panel Bus I/O modules: Set the hex address to the position configured
with CARE Ensure that I/O Bus switch S2 of XCL8010
Controller is set to position "Panel" Check the Panel Bus wiring:
- Check for cable breaks - Check for cable short-circuits - If using separate transformers: Check ground
connection Eliminate any mixture of Panel Bus I/Os and
LonWorks I/Os on same wire Allow XCL8010 to configure I/O module Unplug and replug the module If problem persists, replace hardware
3 Alternating flash between service LED and power LED
Panel Bus I/O modules, only: Download error or application checksum error. Boot loader is running
Panel Bus I/O modules, only: Wait until rebooting (firmware download) has been completed
4 LED flashes at power up, goes OFF, and then is lit continuously
LONWORKS Bus I/O modules, only: The LONWORKS Bus I/O module lacks application
Download application
5 LED repeatedly blinks ON for 1 sec and OFF for 1 sec
LONWORKS Bus I/O modules, only: The LONWORKS Bus I/O module is unconfigured, but has an application
Set module to configured mode
6 LED remains OFF after a short ON duration
I/O module is configured and running normally No action necessary
7 LED flashes continuously in following pattern: 4 x ON/OFF followed by pause
Sensor failure of analog input module (in the case of LONWORKS Bus I/O modules, this behavior can occur only if the appropriate NV has been bound)
Check sensor or connection Check sensor configuration
8 LED flashes continuously in following pattern: 5 x ON/OFF followed by pause
LONWORKS Bus I/O modules, only: LONWORKS I/O Bus module has received the wink command from network, physical outputs are unaffected
No action necessary
9 LED flashes continuously in following pattern: 6 x ON/OFF followed by pause
Boot loader problem or hardware defect Replace hardware
10 LED flashes continuously in following pattern: 7 x ON/OFF followed by pause
Communications failure Check bus wiring Check I/O Bus switch S2 of CLLIONLC01
Controller Ensure that LONWORKS Bus I/O modules and
Panel Bus I/O modules are not sharing the same bus
In case of Panel Bus I/O modules, only: Check for incorrect HEX addresses (2 Panel Bus I/O modules using the same HEX address)
In case of LONWORKS Bus I/O modules, only: Check heartbeat
Table 78 Service LED of I/O modules
Troubleshooting LION System
EN1Z-0921GE51 R0709 80
LED Test for I/O Modules (pluggable I/O modules, only) Press the service button S1 of the pluggable I/O module, e.g. using a paperclip.
– The service LED and all other LEDs of that Panel Bus I/O module light up for as long as the service button is pressed.
LED Correct behavior
Power LED ON continuously (if it flashes, check the 24 VAC power supply)
Service LED ON continuously
Analog output module status LEDs ON continuously
Relay output module status LEDs ON continuously
Digital input module status LEDs Red -> green -> yellow -> red -> green -> yellow, cyclically every 0.5 sec
Table 79 Effects of pressing and holding down service button of pluggable I/O modules
An LED is defective if it is not lit as shown above.
Analog Input Modules Troubleshooting case Problem Possible causes Remedy
Wrong sensor configuration Reconfigure sensor
Incorrect wiring Rewire
Sensor failure Replace sensor
1 Incorrect sensor measurement
Negative voltage on at least one channel Check polarity of active sensor inputs.
2 Unstable sensor measurements
Incorrect grounding of active sensors Ground active sensors individually (see Fig. 63 and Fig. 64 on page 43 and following)
3 a voltage of about 8.88 V(*) is measured (with an external volt-meter) at an open analog input configured for: NTC20kΩ or Pt1000-1/-2 or Pt3000 or Balco 500 or NTC10kΩ or NI1000TK5000.
Sensor is not connected Connect the configured sensor
4 a voltage of about 8.88 V(*) is measured (with an external voltmeter) at an open analog input configured for: 0…10V with pull-up or slow Digital Input
Normal value for open input that is configured to listed types
No action necessary
(*): voltage may differ slightly depending on the input impedance of the used voltmeter
Table 80 Failure modes of analog input modules
LION System Troubleshooting
81 EN1Z-0921GE51 R0709
Analog Output Modules Troubleshooting case Problem Possible causes Remedy
Manual override settings Check manual override settings
Outputs are in safety position Check communication
Software problem Power down and then power up If the problem persists, replace
hardware
1 All outputs always have zero voltage
Internal undervoltage detection has been activated
Replace hardware
2 Unstable output voltage Incorrect grounding of actuators Ground actuators individually (see Fig. 68 on page 47)
Table 81 Failure modes of analog output modules
Binary Input Modules Troubleshooting case Problem Possible causes Remedy
1 Unexpectedly, all status LEDs are always OFF
Internal overload protection has been activated
Power down and then power up
Table 82 Failure modes of binary input modules
Relay Output Modules Troubleshooting case Problem Possible causes Remedy
Improper manual override settings Check manual override settings
Outputs are in safety position Check communication
Software problem Power down and then power up If the problem persists, replace
hardware
1 Unexpectedly, all outputs are in unpowered position
Internal undervoltage detection has been activated
Replace hardware
Table 83 Failure modes of relay output modules
Floating Output Modules Troubleshooting case Problem Possible causes Remedy
Improper manual override settings Check manual override settings to check outputs
Outputs are in safety position Check communication
Software problem Power down and then power up If the problem persists, replace
hardware
1 Unexpectedly, all outputs are in unpowered position
Internal undervoltage detection has been activated
Replace hardware
Table 84 Failure modes of floating output modules
Appendix 1: System Protective Earth Grounding LION System
EN1Z-0921GE51 R0709 82
Appendix 1: System Protective Earth Grounding
LION Systems and SELV In order to avoid distribution of noise or earth ground potential differences over networks or other connections, the CLLIONLC01 is designed to be in compliance with SELV (Safety Extra-Low Voltage). Furthermore, SELV offers the greatest possible safety against electrical impact. To support SELV, all CentraLine external (CRT series) or internal transformers comply with standard EN60742. Earth grounding is therefore not recommended.
LION Systems and Standard EN60204-1 However, if compliance with EN60204-1 is required, note the following:
General Information about EN60204-1 EN60204-1 defines electrical safety for a complete application/machine including controllers, sensors, actuators and any connected/controlled electrical device. EN60204-1 requires controllers to be powered by PELV (Protective Extra-Low Voltage) and earth grounding of the secondary side of the used transformers or earth grounding of the system ground. Earth grounding is prescribed to prevent unexpected start-up of connected rotating/moving machines due to an insulation fault and double earth grounding somewhere in the plant. The use of an earth leakage monitor is also possible to fulfill PELV if earth grounding is prohibited.
When is EN60204-1 Applicable to LION Systems? • Safety against electrical impact
EN60204-1 is not mandatory; this is because electrical safety is provided by the use of SELV and transformers according to standard EN60742.
• Safety against unexpected start-up of rotating/moving machines – If the application/plant does not contain machines that
can be harmful to the operator due to an unexpected start-up, the standard EN60204-1 is not applicable.
If such machines are encountered, then EN60204-1 must be followed. Grounding is required.
Earth Grounding of EN60204-1 Applicable Systems If system protective earth grounding is planned, use a
cable as short as possible for grounding: min. 1.5 mm² (16 AWG).
For connection details refer to the following examples. Example 1 Connecting a single transformer with multiple CLLIONLC01 Controllers earth-grounded as per EN60204-1 Connect earth ground to terminal 2 of the CLLIONLC01
Controllers
CLIOP/CLIOL
CLIOP/CLIOL
CLIOP/CLIOL
CLIOP/CLIOL
CLIOP/CLIOL
CLIOP/CLIOL
24 V~
24 V0
CLLIONLC0124V~1 2
24V~0
CLLIONLC0124V~1 2
24V~0
LINE
NOISE-FREE EARTH GROUND(ONLY ONE PER SYSTEM)
Fig. 110 Connecting and earth grounding multiple
CLLIONLC01 Controllers (single transformer)
LION System Appendix 1: System Protective Earth Grounding
83 EN1Z-0921GE51 R0709
Example 2 Connecting a LION System together with other controllers earth-grounded as per EN60204-1 Notes • Use a noise-free earth ground inside the cabinet.
• Use one star-point to split power for controllers and field devices.
• If the transformer is used for several controllers, each controller ground has to be wired separately to the star-point.
• If a field device that prohibits earth grounding is connected to the system ground, an isolation monitoring device must be used instead of earth grounding.
• If the field device transformer is physically far away from the controller, earth grounding must still be performed for the controller.
Connect earth ground to the respective terminal of the
controllers, see figure below.
24 V~
24 V0
XCL5010 XL100C24V~
24V~
2 711 72
24V~0
XSL51124V~2 1
24V~0
XL5024V~2 1
24V~0
24V~0
CLLIONLC0124V~1 2
24V~0
FIELDDEVICE
24V~
GND
YLINE
NOISE-FREE EARTH GROUND(ONLY ONE PER SYSTEM)
Fig. 111 Connecting and earth grounding mixed
controllers (single transformer)
NOTICE
Equipment damage! Terminals 1 and 2 are assigned differently on the XCL5010 and CLLIONLC01 Controllers. Make sure that earth ground is connected to the correct
terminal according to Fig. 111 and the respective connection diagrams.
The XL40, XL50, XL100C, Distributed IO, Smart IO, and the LION System can share one transformer. The XC5010C Controller always requires its own transformer. If EN60204-1 is applicable for the given type of controller, the system ground has the same potential as one terminal of the power supply.
Example 3 Connecting a C-Bus with controllers earth-grounded as per EN60204-1 Notes • Use a noise-free earth ground inside the cabinet.
• Do not use the controller terminals which are normally used for C-Bus shield connection.
• Be sure to wire the shield only once per bus connection to the earth ground; this is to prevent any current draw over the shield.
• A permanent earth ground potential difference of more than 24 VAC may destroy the related controllers.
Connect earth ground to the respective terminal of the
controllers, see figure below.
XCL5010CC+ C-
1615 1817
CLLIONLC01
NOISE-FREE EARTHGROUND (ONLY ONEPER CONNECTION)
MAX. 24 V POTENTIALDIFFERENCE ALLOWED
BETWEEN EARTH GROUNDS
C+ C+C- C-
5 5
C+
86 6
C-
9
SHIELD
10
XCL5010 XL50
Fig. 112 Connecting C-Bus with multiple controllers earth-
grounded as per EN60204-1
If a system ground of the controller is connected to the earth ground, the available terminals for shielding the C-Bus must not be used. Instead, the C-Bus shield must be connected to the earth ground, but only once per bus connection.
Appendix 2: Remote Communications LION System
EN1Z-0921GE51 R0709 84
Appendix 2: Remote Communications
For remote communications with up to three centrals, a modem or ISDN terminal adapter can be connected directly to the modem interface of the CLLIONLC01. Notes Remote communication via modem or ISDN terminal adapter requires firmware version V2.1.0 or higher. XBSi building supervisors are not supported for remote communication.
Approved Modems For information on modems approved for use with the LION System, please refer to the “Frequently Asked Questions and Troubleshooting” document available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under:
http://web.ge51.honeywell.de/tac Go there, and enter the catchword "modemfaq" in the
search field.
Modem or ISDN Terminal Adapter Connection The modem interface of the CLLIONLC01 accepts a standard modem cable with a female 9-pin connector.
Fig. 113 Modem interface
Connect the cable that is supplied with the modem/ISDN
terminal adapter to the modem interface of the CLLIONLC01 Controller.
Modem Requirements A “Frequently Asked Questions and Troubleshooting” document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under:
http://web.ge51.honeywell.de/tac Go there, and enter the catchword "modemfaq" in the
search field.
Troubleshooting In case of any problems, the handbook of the modem or ISDN terminal adapter must be consulted. A “Frequently Asked Questions and Troubleshooting” document is available via the Honeywell Technical Assistance Center (TAC) or, for Honeywell employees, on the Intranet under:
http://web.ge51.honeywell.de/tac Go there, and enter the catchword "modemfaq" in the
search field.
LION System Appendix 3: Sensor Characteristics
85 EN1Z-0921GE51 R0709
Appendix 3: Sensor Characteristics
Note The following sensor characteristics do not include failures due to:
• Sensor failures
• Wiring resistance or wiring failures
• Missreadings due to a meter connected to measure resistance or voltage at the input
BALCO 500Temp.
[°C] Resistance
[Ω] Terminal
voltage [V]
-30.0 397 0.157 -29.0 399 0.158 -28.0 401 0.158 -27.0 403 0.159 -26.0 404 0.160 -25.0 406 0.160 -24.0 408 0.161 -23.0 410 0.162 -22.0 412 0.163 -21.0 413 0.163 -20.0 415 0.164 -19.0 417 0.165 -18.0 419 0.165 -17.0 421 0.166 -16.0 423 0.167 -15.0 425 0.168 -14.0 426 0.168 -13.0 428 0.169 -12.0 430 0.170 -11.0 432 0.171 -10.0 434 0.171 -9.0 436 0.172 -8.0 438 0.173 -7.0 440 0.174 -6.0 442 0.174 -5.0 444 0.175 -4.0 445 0.176 -3.0 447 0.176 -2.0 449 0.177 -1.0 451 0.178 0.0 453 0.179 1.0 455 0.179 2.0 457 0.180 3.0 459 0.181 4.0 461 0.182 5.0 463 0.183 6.0 465 0.183 7.0 467 0.184 8.0 469 0.185 9.0 471 0.186
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
10.0 473 0.186 11.0 475 0.187 12.0 477 0.188 13.0 479 0.189 14.0 481 0.190 15.0 483 0.190 16.0 485 0.191 17.0 487 0.192 18.0 489 0.193 19.0 491 0.193 20.0 493 0.194 21.0 495 0.195 22.0 497 0.196 23.0 499 0.196 24.0 501 0.197 25.0 503 0.198 26.0 506 0.199 27.0 508 0.200 28.0 510 0.201 29.0 512 0.201 30.0 514 0.202 31.0 516 0.203 32.0 518 0.204 33.0 520 0.205 34.0 522 0.205 35.0 524 0.206 36.0 527 0.207 37.0 529 0.208 38.0 531 0.209 39.0 533 0.210 40.0 535 0.210 41.0 537 0.211 42.0 539 0.212 43.0 542 0.213 44.0 544 0.214 45.0 546 0.215 46.0 548 0.215 47.0 550 0.216 48.0 553 0.217 49.0 555 0.218
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
50.0 557 0.219 51.0 559 0.220 52.0 561 0.220 53.0 564 0.221 54.0 566 0.222 55.0 568 0.223 56.0 570 0.224 57.0 572 0.225 58.0 575 0.226 59.0 577 0.226 60.0 579 0.227 61.0 581 0.228 62.0 584 0.229 63.0 586 0.230 64.0 588 0.231 65.0 590 0.231 66.0 593 0.233 67.0 595 0.233 68.0 597 0.234 69.0 600 0.235 70.0 602 0.236 71.0 604 0.237 72.0 607 0.238 73.0 609 0.239 74.0 611 0.240 75.0 614 0.241 76.0 616 0.241 77.0 618 0.242 78.0 621 0.243 79.0 623 0.244 80.0 625 0.245 81.0 628 0.246 82.0 630 0.247 83.0 632 0.248 84.0 635 0.249 85.0 637 0.249 86.0 639 0.250 87.0 642 0.251 88.0 644 0.252 89.0 647 0.253
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
90.0 649 0.254 91.0 651 0.255 92.0 654 0.256 93.0 656 0.257 94.0 659 0.258 95.0 661 0.259 96.0 664 0.260 97.0 666 0.261 98.0 668 0.261 99.0 671 0.262 100.0 673 0.263 101.0 676 0.264 102.0 678 0.265 103.0 681 0.266 104.0 683 0.267 105.0 686 0.268 106.0 688 0.269 107.0 691 0.270 108.0 693 0.271 109.0 696 0.272 110.0 698 0.273 111.0 701 0.274 112.0 703 0.275 113.0 706 0.276 114.0 708 0.276 115.0 711 0.278 116.0 713 0.278 117.0 716 0.280 118.0 718 0.280 119.0 721 0.281 120.0 724 0.283
Appendix 3: Sensor Characteristics LION System
EN1Z-0921GE51 R0709 86
NTC 20 kΩ Temp.
[°C] Resistance
[kΩ] Terminal
voltage [V]
-50.0 1659 8.78 -49.0 1541 8.77 -48.0 1432 8.76 -47.0 1331 8.75 -46.0 1239 8.74 -45.0 1153 8.72 -44.0 1073 8.71 -43.0 1000 8.70 -42.0 932 8.69 -41.0 869 8.67 -40.0 811 8.66 -39.0 757 8.64 -38.0 706 8.62 -37.0 660 8.60 -36.0 617 8.58 -35.0 577 8.56 -34.0 539 8.54 -33.0 505 8.52 -32.0 473 8.49 -31.0 443 8.47 -30.0 415 8.44 -29.0 389 8.41 -28.0 364 8.38 -27.0 342 8.35 -26.0 321 8.32 -25.0 301 8.28 -24.0 283 8.25 -23.0 266 8.21 -22.0 250 8.17 -21.0 235 8.13 -20.0 221 8.08 -19.0 208 8.04 -18.0 196 7.99 -17.0 184 7.94 -16.0 174 7.89 -15.0 164 7.83 -14.0 154 7.78 -13.0 146 7.72 -12.0 137 7.66 -11.0 130 7.60 -10.0 122 7.53 -9.0 116 7.46 -8.0 109 7.39 -7.0 103 7.32 -6.0 97.6 7.25 -5.0 92.3 7.17 -4.0 87.3 7.09 -3.0 82.6 7.01 -2.0 78.2 6.93 -1.0 74.1 6.85 0.0 70.2 6.76 1.0 66.5 6.67 2.0 63.0 6.58 3.0 59.8 6.49 4.0 56.7 6.40
Temp. [°C]
Resistance [kΩ]
Terminal voltage [V]
5.0 53.8 6.30 6.0 51.1 6.20 7.0 48.5 6.10 8.0 46.0 6.00 9.0 43.7 5.90
10.0 41.6 5.80 11.0 39.5 5.70 12.0 37.6 5.59 13.0 35.7 5.49 14.0 34.0 5.38 15.0 32.3 5.28 16.0 30.8 5.17 17.0 29.3 5.07 18.0 27.9 4.96 19.0 26.6 4.85 20.0 25.3 4.75 21.0 24.2 4.64 22.0 23.0 4.53 23.0 22.0 4.43 24.0 21.0 4.32 25.0 20.0 4.22 26.0 19.1 4.12 27.0 18.2 4.01 28.0 17.4 3.91 29.0 16.6 3.81 30.0 15.9 3.71 31.0 15.2 3.62 32.0 14.5 3.52 33.0 13.9 3.43 34.0 13.3 3.33 35.0 12.7 3.24 36.0 12.1 3.15 37.0 11.6 3.06 38.0 11.1 2.97 39.0 10.7 2.89 40.0 10.2 2.81 41.0 9.78 2.72 42.0 9.37 2.64 43.0 8.98 2.57 44.0 8.61 2.49 45.0 8.26 2.42 46.0 7.92 2.34 47.0 7.60 2.27 48.0 7.29 2.20 49.0 7.00 2.14 50.0 6.72 2.07 51.0 6.45 2.01 52.0 6.19 1.94 53.0 5.95 1.88 54.0 5.72 1.82 55.0 5.49 1.77 56.0 5.28 1.71 57.0 5.08 1.66 58.0 4.88 1.61 59.0 4.69 1.56
Temp. [°C]
Resistance[kΩ]
Terminal voltage [V]
60.0 4.52 1.51 61.0 4.35 1.46 62.0 4.18 1.41 63.0 4.03 1.37 64.0 3.88 1.32 65.0 3.73 1.28 66.0 3.59 1.24 67.0 3.46 1.20 68.0 3.34 1.16 69.0 3.21 1.13 70.0 3.10 1.09 71.0 2.99 1.06 72.0 2.88 1.02 73.0 2.78 0.991 74.0 2.68 0.960 75.0 2.58 0.929 76.0 2.49 0.900 77.0 2.41 0.872 78.0 2.32 0.844 79.0 2.24 0.818 80.0 2.17 0.792 81.0 2.09 0.767 82.0 2.02 0.744 83.0 1.95 0.720 84.0 1.89 0.698 85.0 1.82 0.676 86.0 1.76 0.655 87.0 1.70 0.635 88.0 1.65 0.616 89.0 1.59 0.597 90.0 1.54 0.578 91.0 1.49 0.561 92.0 1.44 0.544 93.0 1.40 0.527 94.0 1.35 0.511 95.0 1.31 0.496 96.0 1.27 0.481 97.0 1.23 0.466 98.0 1.19 0.452 99.0 1.15 0.439 100.0 1.11 0.425 101.0 1.08 0.413 102.0 1.05 0.401 103.0 1.01 0.389 104.0 0.98 0.378 105.0 0.95 0.367 106.0 0.92 0.356 107.0 0.90 0.346 108.0 0.87 0.336 109.0 0.84 0.326 110.0 0.82 0.317 111.0 0.79 0.308 112.0 0.77 0.299 113.0 0.75 0.290 114.0 0.73 0.282
Temp. [°C]
Resistance[kΩ]
Terminal voltage [V]
115.0 0.70 0.274 116.0 0.68 0.266 117.0 0.66 0.259 118.0 0.64 0.252 119.0 0.63 0.245 120.0 0.61 0.238 121.0 0.59 0.231 122.0 0.57 0.225 123.0 0.56 0.219 124.0 0.54 0.213 125.0 0.53 0.207 126.0 0.51 0.201 127.0 0.50 0.196 128.0 0.49 0.191 129.0 0.47 0.186 130.0 0.46 0.181 131.0 0.45 0.176 132.0 0.43 0.171 133.0 0.42 0.167 134.0 0.41 0.162 135.0 0.40 0.158 136.0 0.39 0.154 137.0 0.38 0.150 138.0 0.37 0.146 139.0 0.36 0.142 140.0 0.35 0.139 141.0 0.34 0.135 142.0 0.33 0.132 143.0 0.32 0.128 144.0 0.32 0.125 145.0 0.31 0.122 146.0 0.30 0.119 147.0 0.29 0.116 148.0 0.29 0.113 149.0 0.28 0.110 150.0 0.27 0.107
LION System Appendix 3: Sensor Characteristics
87 EN1Z-0921GE51 R0709
PT 1000 Temp.
[°C] Resistance
[Ω] Terminal
voltage [V]
-50.0 803 0.312 -49.0 807 0.314 -48.0 811 0.315 -47.0 815 0.317 -46.0 819 0.318 -45.0 823 0.320 -44.0 827 0.321 -43.0 831 0.323 -42.0 835 0.324 -41.0 839 0.326 -40.0 843 0.327 -39.0 847 0.329 -38.0 851 0.330 -37.0 855 0.332 -36.0 859 0.333 -35.0 862 0.335 -34.0 866 0.336 -33.0 870 0.338 -32.0 874 0.339 -31.0 878 0.341 -30.0 882 0.342 -29.0 886 0.344 -28.0 890 0.345 -27.0 894 0.347 -26.0 898 0.348 -25.0 902 0.350 -24.0 906 0.351 -23.0 910 0.353 -22.0 914 0.354 -21.0 918 0.356 -20.0 922 0.357 -19.0 926 0.359 -18.0 929 0.360 -17.0 933 0.361 -16.0 937 0.363 -15.0 941 0.364 -14.0 945 0.366 -13.0 949 0.367 -12.0 953 0.369 -11.0 957 0.370 -10.0 961 0.372 -9.0 965 0.373 -8.0 969 0.375 -7.0 973 0.376 -6.0 977 0.378 -5.0 980 0.379 -4.0 984 0.380 -3.0 988 0.382 -2.0 992 0.383 -1.0 996 0.385 0.0 1000 0.386 1.0 1004 0.388 2.0 1008 0.389 3.0 1012 0.391 4.0 1016 0.392 5.0 1020 0.394 6.0 1023 0.395 7.0 1027 0.396 8.0 1031 0.398 9.0 1035 0.399
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
10.0 1039 0.401 11.0 1043 0.402 12.0 1047 0.404 13.0 1051 0.405 14.0 1055 0.406 15.0 1058 0.408 16.0 1062 0.409 17.0 1066 0.411 18.0 1070 0.412 19.0 1074 0.413 20.0 1078 0.415 21.0 1082 0.416 22.0 1086 0.418 23.0 1090 0.419 24.0 1093 0.420 25.0 1097 0.422 26.0 1101 0.423 27.0 1105 0.425 28.0 1109 0.426 29.0 1113 0.428 30.0 1117 0.429 31.0 1121 0.431 32.0 1124 0.432 33.0 1128 0.433 34.0 1132 0.435 35.0 1136 0.436 36.0 1140 0.438 37.0 1144 0.439 38.0 1148 0.441 39.0 1152 0.442 40.0 1155 0.443 41.0 1159 0.445 42.0 1163 0.446 43.0 1167 0.448 44.0 1171 0.449 45.0 1175 0.451 46.0 1179 0.452 47.0 1182 0.453 48.0 1186 0.455 49.0 1190 0.456 50.0 1194 0.458 51.0 1198 0.459 52.0 1202 0.461 53.0 1205 0.462 54.0 1209 0.463 55.0 1213 0.465 56.0 1217 0.466 57.0 1221 0.467 58.0 1225 0.469 59.0 1229 0.470 60.0 1232 0.471 61.0 1236 0.473 62.0 1240 0.474 63.0 1244 0.476 64.0 1248 0.477 65.0 1252 0.479 66.0 1255 0.480 67.0 1259 0.481 68.0 1263 0.483 69.0 1267 0.484
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
70.0 1271 0.486 71.0 1275 0.487 72.0 1278 0.488 73.0 1282 0.490 74.0 1286 0.491 75.0 1290 0.493 76.0 1294 0.494 77.0 1297 0.495 78.0 1301 0.497 79.0 1305 0.498 80.0 1309 0.499 81.0 1313 0.501 82.0 1317 0.502 83.0 1320 0.503 84.0 1324 0.505 85.0 1328 0.506 86.0 1332 0.508 87.0 1336 0.509 88.0 1339 0.510 89.0 1343 0.512 90.0 1347 0.513 91.0 1351 0.515 92.0 1355 0.516 93.0 1358 0.517 94.0 1362 0.519 95.0 1366 0.520 96.0 1370 0.522 97.0 1374 0.523 98.0 1377 0.524 99.0 1381 0.525 100.0 1385 0.527 101.0 1389 0.528 102.0 1393 0.530 103.0 1396 0.531 104.0 1400 0.532 105.0 1404 0.534 106.0 1408 0.535 107.0 1412 0.537 108.0 1415 0.538 109.0 1419 0.539 110.0 1423 0.541 111.0 1427 0.542 112.0 1430 0.543 113.0 1434 0.545 114.0 1438 0.546 115.0 1442 0.547 116.0 1446 0.549 117.0 1449 0.550 118.0 1453 0.551 119.0 1457 0.553 120.0 1461 0.554 121.0 1464 0.555 122.0 1468 0.557 123.0 1472 0.558 124.0 1476 0.560 125.0 1479 0.561 126.0 1483 0.562 127.0 1487 0.564 128.0 1491 0.565 129.0 1494 0.566
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
130.0 1498 0.567 131.0 1502 0.569 132.0 1506 0.570 133.0 1510 0.572 134.0 1513 0.573 135.0 1517 0.574 136.0 1521 0.576 137.0 1525 0.577 138.0 1528 0.578 139.0 1532 0.580 140.0 1536 0.581 141.0 1539 0.582 142.0 1543 0.584 143.0 1547 0.585 144.0 1551 0.586 145.0 1554 0.587 146.0 1558 0.589 147.0 1562 0.590 148.0 1566 0.592 149.0 1569 0.593 150.0 1573 0.594 151.0 1577 0.596 152.0 1581 0.597 153.0 1584 0.598 154.0 1588 0.600 155.0 1592 0.601 156.0 1596 0.602 157.0 1599 0.603 158.0 1603 0.605 159.0 1607 0.606 160.0 1610 0.607 161.0 1614 0.609 162.0 1618 0.610 163.0 1622 0.612 164.0 1625 0.613 165.0 1629 0.614 166.0 1633 0.615 167.0 1636 0.617 168.0 1640 0.618 169.0 1644 0.619 170.0 1648 0.621 171.0 1651 0.622 172.0 1655 0.623 173.0 1659 0.625 174.0 1662 0.626 175.0 1666 0.627 176.0 1670 0.629 177.0 1674 0.630 178.0 1677 0.631 179.0 1681 0.632 180.0 1685 0.634 181.0 1688 0.635 182.0 1692 0.636 183.0 1696 0.638 184.0 1699 0.639 185.0 1703 0.640 186.0 1707 0.642 187.0 1711 0.643 188.0 1714 0.644 189.0 1718 0.645
Appendix 3: Sensor Characteristics LION System
EN1Z-0921GE51 R0709 88
Temp. [°C]
Resistance [Ω]
Terminal voltage [V]
190.0 1722 0.647 191.0 1725 0.648 192.0 1729 0.649 193.0 1733 0.651 194.0 1736 0.652 195.0 1740 0.653 196.0 1744 0.655 197.0 1747 0.656 198.0 1751 0.657 199.0 1755 0.658 200.0 1758 0.659 201.0 1762 0.661 202.0 1766 0.662 203.0 1769 0.663 204.0 1773 0.665 205.0 1777 0.666 206.0 1780 0.667 207.0 1784 0.669 208.0 1788 0.670 209.0 1791 0.671 210.0 1795 0.672 211.0 1799 0.674 212.0 1802 0.675 213.0 1806 0.676 214.0 1810 0.678 215.0 1813 0.679 216.0 1817 0.680 217.0 1821 0.681 218.0 1824 0.683 219.0 1828 0.684 220.0 1832 0.685 221.0 1835 0.686 222.0 1839 0.688 223.0 1843 0.689 224.0 1846 0.690 225.0 1850 0.692 226.0 1854 0.693 227.0 1857 0.694 228.0 1861 0.695 229.0 1865 0.697 230.0 1868 0.698 231.0 1872 0.699 232.0 1875 0.700 233.0 1879 0.702 234.0 1883 0.703 235.0 1886 0.704 236.0 1890 0.705 237.0 1894 0.707 238.0 1897 0.708 239.0 1901 0.709 240.0 1905 0.711 241.0 1908 0.712 242.0 1912 0.713 243.0 1915 0.714 244.0 1919 0.716 245.0 1923 0.717 246.0 1926 0.718 247.0 1930 0.719 248.0 1934 0.721 249.0 1937 0.722
Temp. [°C]
Resistance [Ω]
Terminal voltage [V]
250.0 1941 0.723 251.0 1944 0.724 252.0 1948 0.726 253.0 1952 0.727 254.0 1955 0.728 255.0 1959 0.729 256.0 1962 0.730 257.0 1966 0.732 258.0 1970 0.733 259.0 1973 0.734 260.0 1977 0.736 261.0 1980 0.737 262.0 1984 0.738 263.0 1988 0.739 264.0 1991 0.740 265.0 1995 0.742 266.0 1998 0.743 267.0 2002 0.744 268.0 2006 0.746 269.0 2009 0.747 270.0 2013 0.748 271.0 2016 0.749 272.0 2020 0.750 273.0 2024 0.752 274.0 2027 0.753 275.0 2031 0.754 276.0 2034 0.755 277.0 2038 0.757 278.0 2042 0.758 279.0 2045 0.759 280.0 2049 0.760 281.0 2052 0.761 282.0 2056 0.763 283.0 2060 0.764 284.0 2063 0.765 285.0 2067 0.766 286.0 2070 0.768 287.0 2074 0.769 288.0 2077 0.770 289.0 2081 0.771 290.0 2085 0.773 291.0 2088 0.774 292.0 2092 0.775 293.0 2095 0.776 294.0 2099 0.777 295.0 2102 0.778 296.0 2106 0.780 297.0 2110 0.781 298.0 2113 0.782 299.0 2117 0.784 300.0 2120 0.785 301.0 2124 0.786 302.0 2127 0.787 303.0 2131 0.788 304.0 2134 0.789 305.0 2138 0.791 306.0 2142 0.792 307.0 2145 0.793 308.0 2149 0.794 309.0 2152 0.796
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
310.0 2156 0.797 311.0 2159 0.798 312.0 2163 0.799 313.0 2166 0.800 314.0 2170 0.802 315.0 2173 0.803 316.0 2177 0.804 317.0 2181 0.805 318.0 2184 0.806 319.0 2188 0.808 320.0 2191 0.809 321.0 2195 0.810 322.0 2198 0.811 323.0 2202 0.812 324.0 2205 0.814 325.0 2209 0.815 326.0 2212 0.816 327.0 2216 0.817 328.0 2219 0.818 329.0 2223 0.820 330.0 2226 0.821 331.0 2230 0.822 332.0 2234 0.823 333.0 2237 0.824 334.0 2241 0.826 335.0 2244 0.827 336.0 2248 0.828 337.0 2251 0.829 338.0 2255 0.830 339.0 2258 0.831 340.0 2262 0.833 341.0 2265 0.834 342.0 2269 0.835 343.0 2272 0.836 344.0 2276 0.838 345.0 2279 0.839 346.0 2283 0.840 347.0 2286 0.841 348.0 2290 0.842 349.0 2293 0.843 350.0 2297 0.845 351.0 2300 0.846 352.0 2304 0.847 353.0 2307 0.848 354.0 2311 0.849 355.0 2314 0.850 356.0 2318 0.852 357.0 2321 0.853 358.0 2325 0.854 359.0 2328 0.855 360.0 2332 0.856 361.0 2335 0.857 362.0 2339 0.859 363.0 2342 0.860 364.0 2346 0.861 365.0 2349 0.862 366.0 2353 0.863 367.0 2356 0.864 368.0 2360 0.866 369.0 2363 0.867
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
370.0 2367 0.868 371.0 2370 0.869 372.0 2373 0.870 373.0 2377 0.871 374.0 2380 0.872 375.0 2384 0.874 376.0 2387 0.875 377.0 2391 0.876 378.0 2394 0.877 379.0 2398 0.878 380.0 2401 0.879 381.0 2405 0.881 382.0 2408 0.882 383.0 2412 0.883 384.0 2415 0.884 385.0 2419 0.885 386.0 2422 0.886 387.0 2426 0.888 388.0 2429 0.889 389.0 2432 0.890 390.0 2436 0.891 391.0 2439 0.892 392.0 2443 0.893 393.0 2446 0.894 394.0 2450 0.896 395.0 2453 0.897 396.0 2457 0.898 397.0 2460 0.899 398.0 2463 0.900 399.0 2467 0.901 400.0 2470 0.902
LION System Appendix 3: Sensor Characteristics
89 EN1Z-0921GE51 R0709
NI1000TK5000 Temp.
[°C] Resistance
[Ω] Terminal
voltage [V]
-30 871.7 0.338
-29 875.8 0.340
-28 880 0.341
-27 884.1 0.343
-26 888.3 0.344
-25 892.5 0.346
-24 896.7 0.348
-23 900.8 0.349
-22 905.1 0.351
-21 909.3 0.352
-20 913.5 0.354
-19 917.7 0.355
-18 922 0.357
-17 926.2 0.359
-16 930.5 0.360
-15 934.7 0.362
-14 939 0.363
-13 943.3 0.365
-12 947.6 0.367
-11 951.9 0.368
-10 956.2 0.370
-9 960.6 0.371
-8 964.9 0.373
-7 969.3 0.375
-6 973.6 0.376
-5 978 0.378
-4 982.4 0.380
-3 986.7 0.381
-2 991.2 0.383
-1 995.6 0.384
0 1000 0.386
1 1004.4 0.388
2 1008.9 0.389
3 1013.3 0.391
4 1017.8 0.393
5 1022.3 0.394
6 1026.7 0.396
7 1031.2 0.398
8 1035.8 0.399
9 1040.3 0.401
10 1044.8 0.403
11 1049.3 0.404
12 1053.9 0.406
13 1058.4 0.408
14 1063 0.409
15 1067.6 0.411
16 1072.2 0.413
17 1076.8 0.415
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
18 1081.4 0.416
19 1086 0.418
20 1090.7 0.420
21 1095.3 0.421
22 1100 0.423
23 1104.6 0.425
24 1109.3 0.427
25 1114 0.428
26 1118.7 0.430
27 1123.4 0.432
28 1128.1 0.433
29 1132.9 0.435
30 1137.6 0.437
31 1142.4 0.439
32 1147.1 0.440
33 1151.9 0.442
34 1156.7 0.444
35 1161.5 0.446
36 1166.3 0.447
37 1171.2 0.449
38 1176 0.451
39 1180.9 0.453
40 1185.7 0.455
41 1190.6 0.456
42 1195.5 0.458
43 1200.4 0.460
44 1205.3 0.462
45 1210.2 0.463
46 1215.1 0.465
47 1220.1 0.467
48 1225 0.469
49 1230 0.471
50 1235 0.473
51 1240 0.474
52 1245 0.476
53 1250 0.478
54 1255 0.480
55 1260.1 0.482
56 1265.1 0.484
57 1270.2 0.485
58 1275.3 0.487
59 1280.3 0.489
60 1285.4 0.491
61 1290.6 0.493
62 1295.7 0.495
63 1300.8 0.496
64 1306 0.498
65 1311.1 0.500
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
66 1316.3 0.502
67 1321.5 0.504
68 1326.7 0.506
69 1331.9 0.508
70 1337.1 0.510
71 1342.4 0.512
72 1347.6 0.513
73 1352.9 0.515
74 1358.2 0.517
75 1363.5 0.519
76 1368.8 0.521
77 1374.1 0.523
78 1379.4 0.525
79 1384.8 0.527
80 1390.1 0.529
81 1395.5 0.531
82 1400.9 0.533
83 1406.3 0.535
84 1411.7 0.537
85 1417.1 0.538
86 1422.5 0.540
87 1428 0.542
88 1433.4 0.544
89 1438.9 0.546
90 1444.4 0.548
91 1449.9 0.550
92 1455.4 0.552
93 1460.9 0.554
94 1466.5 0.556
95 1472 0.558
96 1477.6 0.560
97 1483.2 0.562
98 1488.8 0.564
99 1494.4 0.566
100 1500 0.568
101 1505.6 0.570
102 1511.3 0.572
103 1517 0.574
104 1522.6 0.576
105 1528.3 0.578
106 1534 0.580
107 1539.7 0.582
108 1545.5 0.584
109 1551.2 0.586
110 1557 0.589
111 1562.8 0.591
112 1568.5 0.593
113 1574.4 0.595
Temp. [°C]
Resistance[Ω]
Terminal voltage [V]
114 1580.2 0.597
115 1586 0.599
116 1591.8 0.601
117 1597.7 0.603
118 1603.6 0.605
119 1609.5 0.607
120 1615.4 0.609
121 1621.3 0.611
122 1627.2 0.613
123 1633.2 0.616
124 1639.1 0.618
125 1645.1 0.620
126 1651.1 0.622
127 1657.1 0.624
128 1663.1 0.626
129 1669.1 0.628
130 1675.2 0.630
Appendix 3: Sensor Characteristics LION System
EN1Z-0921GE51 R0709 90
NTC 10 kΩ Temp.
[°C] Resistance
[kΩ] Terminal
voltage [V]
-30 177 7.904
-29 166.35 7.848
-28 156.413 7.790
-27 147.136 7.730
-26 138.47 7.666
-25 130.372 7.601
-24 122.8 7.534
-23 115.718 7.464
-22 109.089 7.392
-21 102.883 7.318
-20 97.073 7.241
-19 91.597 7.161
-18 86.471 7.080
-17 81.667 6.996
-16 77.161 6.910
-15 72.932 6.821
-14 68.962 6.731
-13 65.231 6.639
-12 61.723 6.545
-11 58.424 6.448
-10 55.321 6.351
-9 52.399 6.251
-8 49.648 6.150
-7 47.058 6.047
-6 44.617 5.943
-5 42.317 5.838
-4 40.15 5.732
-3 38.106 5.624
-2 36.18 5.516
-1 34.363 5.408
0 32.65 5.299
1 31.027 5.189
2 29.494 5.079
3 28.047 4.969
4 26.68 4.859
5 25.388 4.750
6 24.166 4.641
7 23.01 4.532
8 21.916 4.423
9 20.88 4.316
10 19.898 4.209
11 18.968 4.103
Temp. [°C]
Resistance [kΩ]
Terminal voltage [V]
12 18.087 3.998
13 17.252 3.894
14 16.46 3.792
15 15.708 3.690
16 14.995 3.591
17 14.319 3.492
18 13.678 3.396
19 13.068 3.300
20 12.49 3.207
21 11.94 3.115
22 11.418 3.025
23 10.921 2.937
24 10.449 2.850
25 10 2.767
26 9.572 2.684
27 9.165 2.603
28 8.777 2.524
29 8.408 2.447
30 8.057 2.372
31 7.722 2.299
32 7.402 2.228
33 7.098 2.159
34 6.808 2.091
35 6.531 2.025
36 6.267 1.962
37 6.015 1.900
38 5.775 1.840
39 5.546 1.781
40 5.327 1.724
41 5.117 1.669
42 4.917 1.616
43 4.726 1.564
44 4.543 1.514
45 4.369 1.465
46 4.202 1.418
47 4.042 1.373
48 3.889 1.329
49 3.743 1.286
50 3.603 1.244
51 3.469 1.204
52 3.34 1.166
53 3.217 1.128
Temp. [°C]
Resistance[kΩ]
Terminal voltage [V]
54 3.099 1.092
55 2.986 1.057
56 2.878 1.023
57 2.774 0.990
58 2.675 0.959
59 2.579 0.928
60 2.488 0.898
61 2.4 0.870
62 2.316 0.842
63 2.235 0.815
64 2.158 0.790
65 2.083 0.765
66 2.011 0.740
67 1.943 0.718
68 1.877 0.695
69 1.813 0.673
70 1.752 0.652
71 1.694 0.632
72 1.637 0.612
73 1.583 0.593
74 1.531 0.575
75 1.481 0.557
76 1.433 0.541
77 1.387 0.524
78 1.342 0.508
79 1.299 0.493
80 1.258 0.478
81 1.218 0.464
82 1.179 0.450
83 1.142 0.436
84 1.107 0.423
85 1.072 0.411
86 1.039 0.399
87 1.007 0.387
88 0.976 0.375
89 0.947 0.365
90 0.918 0.354
91 0.89 0.344
92 0.863 0.334
93 0.838 0.324
94 0.813 0.315
95 0.789 0.306
Temp. [°C]
Resistance[kΩ]
Terminal voltage [V]
96 0.765 0.297
97 0.743 0.289
98 0.721 0.280
99 0.7 0.276
100 0.68 0.265
LION System Appendix 3: Sensor Characteristics
91 EN1Z-0921GE51 R0709
PT 3000Temp.
[°C] Resistance
[kΩ] Terminal
voltage [V]
-50 2.823 1.018 -45 2.868 1.033 -40 2.913 1.047 -35 2.957 1.061 -30 3.002 1.076 -25 3.046 1.090 -20 3.090 1.104 -15 3.134 1.118 -10 3.178 1.132 -5 3.222 1.146 0 3.266 1.160 5 3.310 1.173
10 3.353 1.187 15 3.397 1.200 20 3.440 1.214 25 3.484 1.227 30 3.527 1.241 35 3.570 1.254 40 3.613 1.267 45 3.656 1.280 50 3.699 1.293 55 3.742 1.306 60 3.784 1.319 65 3.827 1.332 70 3.869 1.345 75 3.912 1.358 80 3.954 1.370 85 3.996 1.383 90 4.038 1.395 95 4.080 1.408 100 4.122 1.420 105 4.164 1.433 110 4.206 1.445 115 4.247 1.457 120 4.289 1.469 125 4.330 1.481 130 4.371 1.493 135 4.413 1.505 140 4.454 1.517 145 4.495 1.529 150 4.536 1.541
LION
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
CentraLine Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Tel +49 7031 637 845 Fax +49 7031 637 846 [email protected] www.centraline.com
CentraLine Honeywell Control Systems Ltd. Arlington Business Park UK-Bracknell, Berkshire RG12 1EB Tel +44 13 44 656 565 Fax +44 13 44 656 563 [email protected] www.centraline.com
Printed in Germany. Subject to change without notice. EN1Z-0921GE51 R0709