installation check list
TRANSCRIPT
-
7/30/2019 Installation Check List
1/2
Site : Location :
Job No. : Voltage :
Rating : Designation : Transformer
Make : Sr. No.:
No. CHECK REMARKS
1.
2.
3.
4.
5.
Foundation, Co-ordinates, Location, Level -ok?
Installation as per equipment Tag no., Area of
classification, layout drawing ok?
Transformer centre line, level, roller stopper,
ant-seismic mounting clamps etc ok?
Assembly of all accessories and fittings
completed?
All cooling fans and fan control cubicle
installed and connected?
6.
7.
Oil cooling pump and piping connections
completed?
Oil / winding temperature gauges / relays
installed?
8. Buchholz relay
a) Piping as per drawing
b) Arrow towards conservator
c) Float elements free
d) Mercury Switches intact
9. Breather
a) Piping to conservator as per drawing
b) Silica gel colour blue
c) Air entry hole open
d) Oil filled in bottom compartment10. Eplosion Vent
Both and diaphragms intact
11. Bushings
a) No cracks observator
b) Air Released
c) Arcing horn gaps as per drawing
12. All gaskets intact and new, drain valve closed?
Dehydrated oil filled and topped up to level
Oil level gauge in conservator ok & calibrated?
-
7/30/2019 Installation Check List
2/2
12. All gaskets intact and new, drain valve closed?
Dehydrated oil filled and topped up to level
Oil level gauge in conservator ok & calibrated?
13 Radiator
a) Valves open
b) No leakage at flanges & joints
14 Air release from
a) Radiators
b) Bushings
c) Buchholz relay
d) Transformer tank
e) OLTC Tank & Surge relay
15 Instruments (OTI & WTI)
a) Bulb inserted in pocket
b) Pocket filled with oil
c) Capacity checked and fixed properly
16
17
18
Marshalling box installed and connected?
Tap Changer manual operation is free
Bus duct installed and bus size and
connections checked?
19
20
O.H.HV jumpers, power and control cables
terminated? size? connections?
Earthing of neutral and body and Rail
21
22
Danger Boards Installed?
Fire extinguishers installed? Fire fightingsystem?
23
24
Oil soak pit with gravel /collection pit?
All unwanted materials cleared and
Transformer kept clean?