inspection of distribution piping systems: a risk based
TRANSCRIPT
![Page 1: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/1.jpg)
Inspection of Distribution
Piping Systems: A Risk
Based Approach
IDEA’s 27th Campus Energy
Conference
February 18-21, 2014
Atlanta
Joe Maciejczyk, PE
Structural Integrity Associates
![Page 2: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/2.jpg)
Why inspect?
RISK
KNOWING
WHERE
YOU ARE
“CORROSION
NEVER SLEEPS”
![Page 3: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/3.jpg)
Why inspect?
RISK
PERSONNEL SAFETY!
Risk from unknown hazards
Protection from negligence claims
Disruptions
Unbudgeted expenditures
![Page 4: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/4.jpg)
Forced Maintenance
• End user disruptions
• Loss of efficiency
• Safety issues
• Unbudgeted Expenditures
![Page 5: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/5.jpg)
Why inspect?
KNOWING
WHERE
YOU ARE INFRASTRUCTURE CONDITION
PLANNING
NEW
CONSTRUCTION
![Page 6: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/6.jpg)
Why inspect?
“CORROSION
NEVER SLEEPS”
SELECTIVE WELD ATTACK
![Page 7: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/7.jpg)
Damage Mechanisms
- Corrosion
- Eternal (protection system failure)
- Internal (water chemistry issues)
- Corrosion under insulation
- MIC (Microbial induced)
- Erosion
- Flow induced
- Particulate
- Stresses
- Low cycle thermal fatigue (start-ups/shut-downs)
- Primary pressure (wall loss)
![Page 8: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/8.jpg)
Traditional Piping
Inspection Programs
• Exception based
– No inspection program unless failure (forensic vs. proactive)
– Reactionary mode
– Opportunity driven
• Ease of access
– Out of sight, out of mind (buried, vaulted, cased)
– Insulation concerns
– Safety
• Limited review
– Point selection
– Selection basis
![Page 9: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/9.jpg)
Diverse Infrastructure
![Page 10: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/10.jpg)
Localized Issues
![Page 11: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/11.jpg)
RISK
BASED
PROGRAM
![Page 12: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/12.jpg)
Risk Based Program
• Data Collection
• Definition of Corrosion Segments
• Risk Assessment
• Inspections
• Program Maintenance
![Page 13: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/13.jpg)
Risk Based Program
Data Collection • Piping drawings - compilation and review of drawings
• Structural details
• Support and anchor details
• Piping Specifications
• Flow diagrams
• P&ID diagrams
• Failure history
• Past Inspection results
• Repair history
• Water treatment - assembly of water chemistry and water chemistry history,
and water treatment and treatment history
• Leakage history
• Cathodic protection history including coating inspections
• ID cleaning history
• System walkdowns
• Safety record (e.g. near miss incidents, etc.)
![Page 14: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/14.jpg)
Risk Based Program
• Define segments
Corrosion Segment Definition
![Page 15: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/15.jpg)
Prioritization Examples
High Risk Zones/Services
High Risk Services
Localized Issues (expansion joints, bolting, etc.)
Component Issues
![Page 16: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/16.jpg)
Risk Based Program
• Data Collection
• Definition of Corrosion Segments
• Risk Assessment
• Inspection plan
• Program Maintenance
![Page 17: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/17.jpg)
Program
• Segment and Risk Priorities
• Walk downs
– Leaks/Exceptions (local issues)
– Hangers, Supports, Anchor inspections
– Specification issues
– As-built design
• Stress Analysis (if needed)
• Apply the Non Destructive Examination “Toolbox”
– Surface Examinations
– Volumetric Examinations
– Metallurgical Examinations
– Screening Technologies
![Page 18: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/18.jpg)
INSPECTION
PLAN
![Page 19: Inspection of Distribution Piping Systems: A Risk Based](https://reader031.vdocuments.us/reader031/viewer/2022012506/618172b03927d7324f30a645/html5/thumbnails/19.jpg)
Program Maintenance
• Maintain
specifications
• Document
• Failure Analysis
Program