Inspection Report
54321 Manor Pl NW Stanwood, WA 98292
#253041
WA State Home Inspector License #952
Certified Inspector InterNACHI12102916
WSDA Structural Pest Inspector #84553
Company Information:
ABODE Inspection Services LLC Phone: 206-257-3404
Phone: 425-512-6400
Inspector: Clifford Keister
Client Name: Buyers Confidential
Date: 2/4/2014
Report #:
140204A
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
2
Inspection Overview
How to Read This Report
Chapters and Sections: This report is divided into chapters that parcel the home into logical inspection components. Each chapter is broken into sections that relate to a specific system or component of the home. Most sections will contain some descriptive information done in black font. Observation narrative, done in colored font, will be included if a system or component is found to be significantly deficient in some way. If a system or component of the home was deemed to be in satisfactory or serviceable condition, there will often be no narrative observation comments in that section. Observation Labels: All narrative observations are colored, numbered and labeled to help you find, refer back to, and understand the severity of the observation. Observation colors and labels used in this report are: 1. Major Concern: Repair items that may cost significant money to correct now or in the near future, or items that require immediate attention to prevent additional damage or eliminate safety hazards. 2. Repair: Repair and maintenance items noted during inspection. 3. Improve: Observations that are not necessarily defects, but which could be improved for safety, efficiency, or reliability reasons. 4. Monitor: Items that should be watched to see if correction may be needed in the future. 5. Due Diligence: Observation such as a buried oil tank that may require further investigation. 6. Future Project: A repair that may be deferred for some time but should be on the radar for repair or replacement in the near future. 7. Efficiency: Denotes observations that are needed to make the home more energy efficient as well as to bring the home up to modern insulation standards. This category typically includes windows and insulation. Other items, such as lighting and appliances, are not inspected for their energy status. 8. WDO: Denotes the presence of wood destroying organisms or conditions conducive to wood destroying organisms. This includes, but is not limited to, inadequate clearances, earth/wood contact, cellulose debris, inadequate ventilation, and excessive moisture. Please note that most WDO observations are related to high moisture conditions that could be conducive to mold-like substances. Abode Inspection Services is not a mold specialist and recommends consulting with an industrial hygienist or other mold remediation expert if concerned about mold. All observations with WDO are relevant to a Washington State pest inspection. 9. NOTE: Refers to aside information and /or any comments elaborating on descriptions of systems in the home. Further Evaluation: Whenever further evaluation of a system or component is recommended or whenever Due Diligence is recommended, this further evaluation or investigation should be done before closing as there is a chance of hidden costs or problems associated with the system or component in question. Drawing Chapter: The Drawing Chapter provides a space at the back of the report for crawl space and other drawings. These are used to indicate locations of active or conducive pest conditions or other difficult to find problem areas. Summary Page: The Summary Page is designed as a bulleted overview of all the observations noted during inspection. This helpful overview is not a substitution for reading the entire inspection report. The entire report must be read to get a complete understanding of this inspection report as the Summary page may not include every observation.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
3
Summary Page
Major Concerns
Crawl Space: Moderate water was noted in the crawl space. This condition may change
seasonally, or with rain intensity. Moisture is bad for crawl spaces and can lead to interior molds, structural settlement and wood destroying organisms. Hire a drainage specialist to further evaluate and correct this condition. Also see the Drainage section of this report for observations regarding any exterior drainage repairs that are needed.
Heating: This furnace is well past the end of its useful design life. The average life of these forced air furnaces is 15-20 years - this unit is 25 years old. Moderate to extensive corrosion was noted around the outside of the heat exchanger and inside where visible. On-going use of this furnace risks running the furnace with a cracked heat exchanger - this is a safety hazard that is not readily apparent or visible as the heat exchanger is not visible to inspection. Hire a licensed heating contractor to further evaluate and replace this furnace.
Repairs
Crawl Space: The plastic vapor barrier has been run up onto the wood framing (support
posts) and should be removed to prevent water being delivered to the wood framing of the home.
Crawl Space: Crawl space air vents have been obstructed. This is non-standard and reduces dry potential in this space and could lead to moisture problems. Have a qualified contractor remove the plastic covers and install 1/4 inch mesh screens.
Crawl Space: Moderate rodent damage was noted in the crawl space. Hire a rodent
control specialist to do a rodent report and implement a plan to eliminate all rodent entry points, set and monitor traps and remediate all contamination.
Electrical: The electric panel in the home is corroded and requires further evaluation
from a licensed electrician to insure safe and reliable performance. Corrosion inside the panel is a red flag that the panel is having moisture problems and this could result in poor and unsafe wiring connections. Repair or replace as recommended by a licensed electrician.
Electrical: Bushing/grommet needed where electrical wire enters garbage disposal to
protect wire from physical damage.
Electrical: The missing cover plates to electric receptacles and switches should be
installed to cover all access to wiring at switches and receptacles. There is a junction box above the garage door that is missing a cover plate; a switch by garage passage door is missing cover plate, and one junction box in attic missing a cover plate.
Electrical: The installation of carbon monoxide detectors is recommended for all homes that have fuel burning appliances such as gas or oil furnaces, gas water heaters, gas ovens and cook-tops, gas fireplaces and wood stoves. In addition, Washington State law (WAC 51-51-0315) now requires UL 2034 approved carbon monoxide detectors in all homes being sold in Washington State. Location should be outside of all sleeping areas and one on each floor of the home. Best practices are to have these detectors hardwired with a battery back-up - though generally installation must meet manufacturer's specifications. Carbon monoxide is a colorless, odorless gas that can cause sickness, nausea and potentially death. For more information, consult the Consumer Product Safety Commission at 1-800-638-2772 (C.P.S.C.).
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
4
Heating: The furnace is generally dirty. Red lips and a lazy flame were noted during
operation of the furnace. There is no evidence of servicing. Hire a licensed heating contractor to further evaluate the furnace and repair as needed. Budget to do annual servicing for safe and reliable heat.
Heating: The B-vent for the furnace flue has inadequate clearance from combustible
materials and insulation. A one inch clearance is recommended for these pipes. Move/Cut combustible materials back and use metal flanges to seal openings in finishes. Noted where B=vent enters the sheetrock in the garage ceiling and in the attic where it is surrounded by insulation. Hire qualified contractor to repair as needed.
Heating: Metal Collar tie that is designed to help keep water out of the roof flashing for the furnace vent pipe has become unfastened and is lying down on the roof. Have contractor repair as needed.
Plumbing: Minor leak by shut-off valve for front exterior faucet, this is located in SE
garage corner. Have licensed plumber repair as needed.
Plumbing: The discharge tube for the water heater relief valve is inadequate. Discharge
tubes should always terminate by pointing toward the ground to eliminate a scald hazard and should be between 6" and 18" off the ground. Ideally, the discharge tube terminates to an exterior or unfinished location or above a drain, though this is not always possible. The drain should also slope to drain to prevent water pooling inside the discharge tube. Have a licensed plumber install a TPRV discharge pipe.
Plumbing: Install listed seismic straps to support the water heater in the event of an
earthquake; none were noted during inspection. Two straps should be installed. One old strap is present but not installed.
Plumbing: Repair or replace the disconnected dryer vent. Be sure this dryer is vented to
the exterior. Use rigid metal pipe only in concealed spaces such as the crawl space. This vent has allowed much dryer air with substantial lint into the SW corner of crawlspace.
Main Hall Bath: The waste plumbing pipes below the bathroom sink is leaking in two
places and requires immediate repair. Hire a licensed plumber to further evaluate and repair.
Main Hall Bath: The bath tub faucet shower diverter was not operational, could not
switch water up to shower head. Have plumber repair.
Main Hall Bath: Caulking is needed between the tub and the floor to prevent water from
damaging the floor.
Kitchen: Disposal was very noisy, and needs repair or replacement.
Exterior/Garage: Localized vinyl siding repairs are needed to the exterior vinyl siding.
See photos attached for specific details. Please note that vinyl siding is impossible to see behind and it is impossible to tell if these defects have allowed water to enter the siding envelope or not. Hire a vinyl siding specialist to further evaluate and repair.
Exterior/Garage: A bollard is needed in the garage to protect the furnace and water heater from physical damage from cars. This is a safety hazard that should be corrected as soon as possible. Hire a qualified contractor to repair.
Exterior/Garage: Repair the damaged or inadequate weather stripping on the bottom of
the garage door at the south side. This is important to prevent water and rodent entry.
Exterior/Garage: The overhead garage door must be opened manually. It is difficult to
open without using brute force. The hardware needs adjustment or repair. Note there is a electrical outlet installed in the ceiling for an automatic opener. Installing an automatic door opening system would be a logical improvement.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
5
Grounds: Eliminate siding /soil contact to reduce the chances for rot and pest damage
and repair any hidden rot as needed. Generally, a 6 inch clearance between soils and wood is recommended. This is often not realistic on older homes, but repairs should be made to get as much clearance as is possible and all contact must be eliminated.
Grounds: The exterior concrete stairway leading to the main entry is poorly sloped; it is
sloping towards the house instead of away from the house. It appears to have settled significantly. This can be difficult to correct as it may necessitate rebuilding the stairs. Hire a qualified person to further evaluate and repair.
Master Bath 3/4: Caulking is needed between the shower stall and the floor to prevent
water from damaging the floor.
Master Bath 3/4: Shower Drain seal appears to have a gap in its seal and could
potentially leak, have plumber further evaluate and repair as needed.
Improvement Items
Roof/Attic: The kitchen fan duct was noted to be un-insulated in the attic. This can contribute to seasonal condensation. Insulation on these pipes is recommended.
Monitoring Items
Grounds: Typical cracks were noted in driveway and concrete flatwork. This is a
cosmetic defect. No immediate repair appears necessary, though water will continue to deteriorate the surface until the driveway is repaired or replaced.
Future Projects
Plumbing: This water heater is likely close to the end of its useful service life. The
average life of these water heaters is 8-12 years; this one is at 11 years. It would be prudent to budget to replace this water heater at any time.
Notes
Structure and Basement: This report includes a structural pest inspected imbedded
within the report. All observations in the base of the report that begin with WDO are a part of a Washington State Pest Inspection. Abode Inspection Services LLC employs Clifford Keister #84553, a Licensed Structural Pest Inspector with the State of Washington and includes a structural pest inspection with all home inspections. Pest Inspection Standards in Washington State - WAC 16-228-2045 - require that a diagram/drawing be prepared for Wood Destroying Organism (WDO) reports. If the pictures and descriptions in this report are inadequate, a drawing is available upon request.
Plumbing: Front hose bib was winterized, not tested. Back hose bib was operational.
Interior/Fireplaces: Squeaky sub-floor was noted at the first bedroom on the second floor. This happens when inadequate adhesive was used to secure the sub-floor to the floor frame. Screws can be used to secure loose sub-floor if the framing lay-out can be found. Finding the lay-out can be difficult if the ceiling below is finished. Often this involves removing the carpet to find the lay out and screw / secure the loose sub-floor. This is a cosmetic defect that should be repaired as desired.
Please contact me directly with questions about this report.
My cell phone number is (425) 512-6400.
Thank you,
Cliff Keister
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
6
Table of Contents
Summary Page ....................................................................................................................................................... 3 Structure and Basement .......................................................................................................................................... 7 Crawl Space ........................................................................................................................................................... 8 Electrical .............................................................................................................................................................. 10 Heating ................................................................................................................................................................ 12 Cooling/ Fuel Storage/ Gas Distribution ................................................................................................................ 14 Plumbing.............................................................................................................................................................. 15 Main Hall Bath ..................................................................................................................................................... 18 Master Bath 3/4 .................................................................................................................................................... 19 Half bath - Laundry room ..................................................................................................................................... 20 Kitchen ................................................................................................................................................................ 21 Interior/Fireplaces ................................................................................................................................................ 22 Roof/Attic ............................................................................................................................................................ 23 Exterior/Garage .................................................................................................................................................... 24 Grounds ............................................................................................................................................................... 26
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
7
Structure and Basement Foundation
% of Foundation Not Visible: 0.6
Evidence of Seismic Protection: None noted Building Configuration: Crawl space, Slab on grade
Foundation Description: Poured concrete
Floor, Wall and Ceiling Framing
Wall Framing: 2x6
Wall Insulation: Not visible
Wall Sheathing: OSB
Floor Framing: 2x10
Sub-Floor Material: OSB
Ceiling Framing: Bottom cord of truss, partly visible
Basement General None
Basement Floor and Ceiling Not applicable
Basement Moisture Not applicable
Sump Pumps and Drains
Floor Drain: Not applicable
Sump Pumps: Not applicable
Wood Destroying Organisms
Visible Evidence of Active Wood Destroying Insects: None noted
Visible Evidence of Inactive Wood Destroying Insects: None noted
Visible Evidence of Active Wood Decay and Fungi: None noted
Visible Evidence of Damage from Wood Destroying Organisms: None noted
Visible Evidence of Conditions Conducive to Wood Destroying Organisms: Present
1. Note, WDO :> This report includes a structural pest inspected imbedded within the report. All observations in the base of the report that begin with WDO are a part of a Washington State Pest Inspection. Abode Inspection Services LLC employs Clifford Keister #84553, a Licensed Structural Pest Inspector with the State of Washington and includes a structural pest inspection with all home inspections. Pest Inspection Standards in Washington State - WAC 16-228-2045 - require that a diagram/drawing be prepared for Wood Destroying Organism (WDO) reports. If the pictures and descriptions in this report are inadequate, a drawing is available upon request.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
8
Crawl Space Crawl Space Access
Method of Inspection: Crawled
Vapor Barrier
Vapor Barrier Material: Plastic
2. Repair, WDO :> The plastic vapor barrier has been run up onto the wood framing (support posts) and should be removed to prevent water being delivered to the wood framing of the home.
Crawl Space Ventilation
Ventilation Method: Exterior wall vents, Non-standard
3. Repair, WDO :> Crawl space air vents have been obstructed. This is non-standard and reduces dry potential in this space and could lead to moisture problems. Have a qualified contractor remove the plastic covers and install 1/4 inch mesh screens.
Remove.
Posts and Footings Standard
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
9
Insulation
Insulation Type: Fiberglass
Approximate R-Value: R-24
Moisture Conditions Present
4. Major Concern, WDO :> Moderate water was noted in the crawl space. This condition may change seasonally, or with rain intensity. Moisture is bad for crawl spaces and can lead to interior molds, structural settlement and wood destroying organisms. Hire a drainage specialist to further evaluate and correct this condition. Also see the Drainage section of this report for observations regarding any exterior drainage repairs that are needed.
Crawlspace has standing water in several areas.
Rodents Present
5. Repair :> Moderate rodent damage was noted in the crawl space. Hire a rodent control specialist to do a rodent report and implement a plan to eliminate all rodent entry points, set and monitor traps and remediate all contamination.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
10
Electrical Service Equipment Volts: 120/240
Service Drop: Underground
Meter Base Amperage: 200 Service Entrance (SE) conductor Size: Aluminum, 4/0, 200 amps
Main Panel Amperage: 200 amps
Electric Service Amperage: 200 amps
Main Electric Panel Location: Garage
6. Repair :> The electric panel in the home is corroded and requires further evaluation from a licensed electrician to insure safe and reliable performance. Corrosion inside the panel is a red flag that the panel is having moisture problems and this could result in poor and unsafe wiring connections. Repair or replace as recommended by a licensed electrician.
Corrosion in Main Electrical Service Panel
Sub-Panel / 2nd Service None noted
Branch Wiring
Wire Material: Copper and Multi-strand Aluminum
Wiring Method: Non-metallic sheathed cable
7. Repair :> Bushing/grommet needed where electrical wire enters garbage disposal to protect wire from physical damage.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
11
Receptacles and Fixtures
Inspection Method: Random Testing
Outlets: Three wire outlets
8. Repair :> The missing cover plates to electric receptacles and switches should be installed to cover all access to wiring at switches and receptacles. There is a junction box above the garage door that is missing a cover plate; a switch by garage passage door is missing cover plate, and one junction box in attic missing a cover plate.
Smoke Detectors and
Carbon Monoxide Detectors
Present
9. Repair :> The installation of carbon monoxide detectors is recommended for all homes that have fuel burning appliances such as gas or oil furnaces, gas water heaters, gas ovens and cook-tops, gas fireplaces and wood stoves. In addition, Washington State law (WAC 51-51-0315) now requires UL 2034 approved carbon monoxide detectors in all homes being sold in Washington State. Location should be outside of all sleeping areas and one on each floor of the home. Best practices are to have these detectors hardwired with a battery back-up - though generally installation must meet manufacturer's specifications. Carbon monoxide is a colorless, odorless gas that can cause sickness, nausea and potentially death. For more information, consult the Consumer Product Safety Commission at 1-800-638-2772 (C.P.S.C.).
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
12
Heating Heating System
Energy Source: Natural gas
Heating Method: Forced air furnace Manufacturer: Rheem
Capacity: 50,000 BTU
Age: 25 years
Last Service Record: None
Filtration System: Disposable
10. Major Concern :> This furnace is well past the end of its useful design life. The average life of these forced air furnaces is 15-20 years - this unit is 25 years old. Moderate to extensive corrosion was noted around the outside of the heat exchanger and inside where visible. On-going use of this furnace risks running the furnace with a cracked heat exchanger - this is a safety hazard that is not readily apparent or visible as the heat exchanger is not visible to inspection. Hire a licensed heating contractor to further evaluate and replace this furnace.
11. Repair :> The furnace is generally dirty. Red lips and a lazy flame were noted during operation of the furnace. There is no evidence of servicing. Hire a licensed heating contractor to further evaluate the furnace and repair as needed. Budget to do annual servicing for safe and reliable heat.
12. Repair :> The B-vent for the furnace flue has inadequate clearance from combustible materials and insulation. A one inch clearance is recommended for these pipes. Move/Cut combustible materials back and use metal flanges to seal openings in finishes. Noted where B=vent enters the sheetrock in the garage ceiling and in the attic where it is surrounded by insulation. Hire qualified contractor to repair as needed.
B-Vent is without the 1 inch recommended clearance to combustibles
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
13
13. Repair :> Metal Collar tie that is designed to help keep water out of the roof flashing for the furnace vent pipe has become unfastened and is lying down on the roof. Have contractor repair as needed.
Red arrow points to collar that should be tightly wrapped around the pipe where the green arrow is pointing, and then caulked to prevent water entering the attic.
Heating Distribution System
Heat Source in Each Room: Present
Distribution Method: Ductwork
Additional Heat Sources Present
Description: Heat lamp
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
14
Cooling/ Fuel Storage/ Gas Distribution
Cooling/Heat Pumps None Noted
Oil Storage None noted
Propane Storage None noted
Gas Meter and Gas Plumbing Present
Gas Shutoff Location: South side of structure Gas Pipe Materials: Steel and flex pipe
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
15
Plumbing Water Service Supply
Pipe Material: Copper
Well or Public Supply: Public Water Pressure: 70 PSI
Pressure Reducing Valve: None noted
Main Water Shut-off Location: Garage
Distribution Pipe
Circulation Pump: None noted
Supply Pipe Materials: Copper
Functional Flow: Average
14. Repair :> Minor leak by shut-off valve for front exterior faucet, this is located in SE garage corner. Have this repaired by a licensed plumber.
Waste Pipe and Discharge
Discharge Type: Public sewer
Waste and Vent Pipe Materials: ABS plastic
Hot Water Heater
System Type: Tank
Manufacturer: GE
Size: 40 gal
Age: 11 years Energy Source: Gas
15. Future Project :> This water heater is likely close to the end of its useful service life. The average life of these water heaters is 8-12 years; this one is at 11 years. It would be prudent to budget to replace this water heater at any time.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
16
16. Repair :> The discharge tube for the water heater relief valve is inadequate. Discharge tubes should always terminate by pointing toward the ground to eliminate a scald hazard and should be between 6" and 18" off the ground. Ideally, the discharge tube terminates to an exterior or unfinished location or above a drain, though this is not always possible. The drain should also slope to drain to prevent water pooling inside the discharge tube. Have a licensed plumber install a TPRV discharge pipe.
TPRV is missing discharge pipe.
17. Repair :> Install listed seismic straps to support the water heater in the event of an earthquake; none were noted during inspection. Two straps should be installed. One old strap is present but not installed.
No earthquake straps around the water heater.
Exterior Hose Bibs Winterized - not tested, Operating
18. Note :> Front hose bib was winterized, not tested. Back hose bib was operational.
Additional Sinks Tested - Laundry sink
Sewage Ejector Pumps None noted
Washer Washer hook-ups only, no appliance
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
17
Dryer Dryer hook-ups only, no appliance
Power Source: Gas and electric
Duct to Exterior: Ducted
19. Repair :> Repair or replace the disconnected dryer vent. The excessive moisture this contributes is a conducive condition for wood destroying organisms. Be sure the dryer is vented to the exterior. Use rigid metal pipe only in concealed spaces such as the crawl space. This vent has deposited substantial amount of dryer lint into the SW area of crawlspace.
Dyer lint is piling up in many places around this area.
Additional Plumbing None noted
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
18
Main Hall Bath Sinks and Cabinets Tested
20. Repair :> The waste plumbing pipes below the bathroom sink is leaking in two places and requires immediate repair. Hire a licensed plumber to further evaluate and repair.
Toilet Tested
Bathtub / Shower Tested
21. Repair :> The bath tub faucet shower diverter was not operational, could not switch water up to shower head. Have plumber repair.
The diverter handle would not lift up to divert water to the shower head.
22. Repair :> Caulking is needed between the tub and the floor to prevent water from damaging the floor.
Bathroom Ventilation
Type: Bath fan
General Bath Condition Standard
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
19
Master Bath 3/4 Sinks and Cabinets Tested
Toilet Tested
Bathtub / Shower Tested
23. Repair :> Caulking is needed between the shower stall and the floor to prevent water from damaging the floor.
24. Repair :> Shower Drain seal appears to have a gap in its seal and could potentially leak, have plumber further evaluate and repair as needed.
Bathroom Ventilation
Type: Bath fan
General Bath Condition Standard
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
20
Half bath - Laundry room Sinks and Cabinets Tested - only a laundry sink
Toilet Tested
Bathtub / Shower None Noted
Bathroom Ventilation Type: Bath fan
General Bath Condition Standard
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
21
Kitchen Sinks and Faucets Tested
Cabinets and Countertops Countertop Material: Granite tiles
Cabinet Material: Wood laminate
Ventilation Method Fan ducted to exterior
Appliances
Refrigerator: Operating
Dishwasher: Operated
Dishwasher Air Gap: None noted
Range/ Oven /Cook-tops: Electric
Disposer: Operated
25. Repair :> Disposal is very noisy, and needs repair or replacement.
General Kitchen Condition Standard
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
22
Interior/Fireplaces Floors
Floor Materials: Carpet, Wood Laminate, Tile
Floor Settlement: Minor
26. Note :> Squeaky sub-floor was noted at the first bedroom on the second floor. This happens when inadequate adhesive was used to secure the sub-floor to the floor frame. Screws can be used to secure loose sub-floor if the framing lay-out can be found. Finding the lay-out can be difficult if the ceiling below is finished. Often this involves removing the carpet to find the lay out and screw / secure the loose sub-floor. This is a cosmetic defect that should be repaired as desired.
Walls, Ceilings and Closets
Wall and Ceiling Materials: Drywall
Stairs and Railings Standard
Interior Doors Hollow Core
Windows
Window Glazing: Double pane
Interior Window Frame: Vinyl
Window Styles: Sliding
Gas Fireplaces None noted
Solid Fuel Fireplaces None noted
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
23
Roof/Attic Roof Materials
Method of Roof Inspection: Walked on roof, Viewed from window
Roof Style: Gable Roof Materials: Architectural grade composition shingle
Approximate Age of Roof: one year
Skylights None noted
Gutters and Downspouts Galvanized
Attic Access No access. Vaulted ceiling, Viewed at
access, Only partial access
Attic Rodent Activity Some signs
Roof Framing and Sheathing
Rafters: Truss
Sheathing: OSB
Attic Insulation
Insulation Type: Rock wool
Approximate Insulation R-Value on Attic Floor: 38
Approximate Insulation R-Value on Attic Ceiling: Not needed
Approximate Insulation R-Value on Attic Walls: 19
Attic and House Ventilation
Bath Fan Ducting: Ducted to exterior
Kitchen Fan Ducting: Ducted to exterior
Attic Ventilation Method: Soffit vents, Roof jack vents, Ridge vents
27. Improvement Item :> The kitchen fan duct was noted to be un-insulated in the attic. This can contribute to seasonal condensation. Insulation on these pipes is recommended.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
24
Exterior/Garage Siding and Trim
Trim Material: Plastic
Siding Material: Vinyl
28. Repair :> Localized vinyl siding repairs are needed to the exterior vinyl siding. See photos attached for specific details. Please note that vinyl siding is impossible to see behind and it is impossible to tell if these defects have allowed water to enter the siding envelope or not. Hire a vinyl siding specialist to further evaluate and repair.
Eaves Vinyl
Exterior Doors Solid core, Sliding glass
Exterior Window Frames Vinyl
Decks None noted
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
25
Porches Present
Chimneys None noted
Garage Attached
Automatic Garage Opener: None noted
Garage Door Type: Wood
29. Repair :> A bollard is needed in the garage to protect the furnace and water heater from physical damage from cars. This is a safety hazard that should be corrected as soon as possible. Hire a qualified contractor to repair.
30. Repair :> Repair the damaged or inadequate weather stripping on the bottom of the garage door at the south side. This is important to prevent water and rodent entry.
31. Repair :> The overhead garage door must be opened manually. It is difficult to open without using brute force. The hardware needs adjustment or repair. Note there is a electrical outlet installed in the ceiling for an automatic opener. Installing a automatic door opening system would be a logical improvement.
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
26
Grounds Drainage and Lot Location
Clearance to Grade: Non-standard
Downspout Discharge: Below grade Lot Description: Flat
32. Repair :> Eliminate siding /soil contact to reduce the chances for rot and pest damage and repair any hidden rot as needed. Generally, a 6 inch clearance between soils and wood is recommended. This is often not realistic on older homes, but repairs should be made to get as much clearance as is possible and all contact must be eliminated.
Driveways/Walkways/Flatwork
Driveway: Concrete
Walkways: Concrete
Patios: Concrete
33. Monitoring Item :> Typical cracks were noted in driveway and concrete flatwork. This is a cosmetic defect. No immediate repair appears necessary, though water will continue to deteriorate the surface until the driveway is repaired or replaced.
Window and Stairwells None Noted
Grounds, Trees and Vegetation
Trees/Vegetation too near building: No
Retaining Walls None noted
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
27
Exterior Stairs Non-standard
34. Repair :> The exterior concrete stairway leading to the main entry is sloping towards the house. It should slope away from house. This condition could contribute to foundation settling or excessive moisture in crawlspace. The concrete flatwork appears to have settled significantly. This can be difficult to correct as it may necessitate rebuilding the stairs. Hire a qualified contractor to further evaluate and repair.
Fences Present
Carport, Outbuildings and Other None noted
54321 Manor Pl NW, Stanwood, WA 98292 ICN#: 3311BE008
This report is prepared exclusively for: Buyer Confidential
© Abode Inspection Services LLC
28
Inspection Receipt
REPORT NO: 140204A
INSPECTION DATE: 2/4/2014 PROPERTIES INSPECTED FOR:
Buyers Confidential 54321 Manor Pl NW, Stanwood, WA 98292 Qty Description Amount
1 Single Family with digital narrative report $ XXX Total Paid $ XXX
Thank you for your business
Abode Inspection Services LLC C/O Cliff Keister
(206) 257-3404
(425) 512-6400