infrared survey sample7/19/2008. . 23. attic left- is hole in elevator shaft , allowing conditioned...
TRANSCRIPT
![Page 1: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/1.jpg)
7/19/2008 www.infraredsurvey.com 1
Infrared SurveySample
![Page 2: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/2.jpg)
7/19/2008 www.infraredsurvey.com 2
IntroductionJohn Cannamela :Level II Thermographer ASNT II Vibration AnalystHVAC Licensed Journeyman20 years Building Diagnostics & Commissioning
![Page 3: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/3.jpg)
7/19/2008 www.infraredsurvey.com 3
The following issues were addressed:
Test and balance HVACCheck building envelope for infiltrationAlter building pressure from negative to positive
![Page 4: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/4.jpg)
7/19/2008 www.infraredsurvey.com 4
Topics of DiscussionWhat is IRHow to use IRHVACBalancingBuilding resultsPictures HVAC report
![Page 5: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/5.jpg)
7/19/2008 www.infraredsurvey.com 5
What is Infrared IR is part of the electromagnetic spectrum discovered in the 1800’sBy William Hershel
![Page 6: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/6.jpg)
7/19/2008 www.infraredsurvey.com 6
IR 101The IR imager sees emitted energy in the IR spectrum range from (shortwave) 3-5 microns (longwave)7-13 microns. The amount of energy is seen through the imager. The reason everything thing is colored is to give the eye something to interpret.Interpretation is key with Thermography.
![Page 7: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/7.jpg)
7/19/2008 www.infraredsurvey.com 7
IR examplesBuilding DiagnosticsElectricalRoof/water leaksMechanicalLocate pipesMany more
FLIR Systems
Hot Bearing
FLIR Systems
Open window in return chase
air infiltration in yellow
FLIR Systems
Chill return Chill return
Chill supply
Sp2:temp 48.8Sp1:temp 38.5
Sp4:temp 44.3
Chill supply
Sp3:temp 38.5
38.1
57.9 °F
40
50
FLIR Systems
![Page 8: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/8.jpg)
7/19/2008 www.infraredsurvey.com 8
Building HVAC 101Heating Ventilation & Air Conditioning
Buildings are conditioned by adding orremoving heat from a given space througha medium. In this case the medium is air.The air is circulated through a refrigeratedcoil or DX coil, which removes heat andtransfers the heat through the refrigerant tothe condenser coil, via a fan. Dirty filters orpoor air flow causes coils to freeze andcompressor failure.
![Page 9: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/9.jpg)
7/19/2008 www.infraredsurvey.com 9
Building HVAC 101Heating Ventilation & Air Conditioning cont.
Ventilation, aside from heating or cooling, means to exchange or move air to and from a given area. This is necessary for several reasons.1. Fresh air –ASHRAE standard
for people2. Fresh air for combustion, stoves
and boilers3. Exhaust for bathrooms and
cooking, elevators, and mechanical rooms
![Page 10: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/10.jpg)
7/19/2008 www.infraredsurvey.com 10
Test and BalancingT & B is performed to allow theHVAC system to perform efficientlyfor comfort and energy. Also to provide thebuilding a means of controlling moistureintroduced via showers etc. . Too muchexhaust will introduce unconditioned airthrough windows and doors. Unconditionedair causes moisture issues. A positivepressure building is desirable.
![Page 11: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/11.jpg)
7/19/2008 www.infraredsurvey.com 11
Building equipment status
Temp/RH-Upon arrival aver-77 Deg F 75% -0.08in build pressPost adjustment Temp aver-68 Deg F 67% +0.01 build press* w/ Kitchen & meeting room Exhaust fans off
![Page 12: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/12.jpg)
7/19/2008 www.infraredsurvey.com 12
Building layout
B
Meeting
![Page 13: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/13.jpg)
7/19/2008 www.infraredsurvey.com 13
EF 14 & 15 Corridors A&BEF #14 & #15 serving the corridors had disabled time clocks. Enabling these time clocks would help maintain/increase positive pressure in the corridors during non use hours:For example :10 pm to 5 am and 10 am to 4 pm.
Missing pins on 24/7
![Page 14: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/14.jpg)
7/19/2008 www.infraredsurvey.com 14
Lobby and LoungeRTU #2-Lobby & RTU #3-Lounge had blocked returns
![Page 15: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/15.jpg)
7/19/2008 www.infraredsurvey.com 15
Lobby and Lounge unitsInside of returns of RTU #2-Lobby & RTU #3-Lounge units and condenser coil. Both affect air flow and unit operation. Units should be replaced, and duct work cleaned.
Pitted and blocked coils, poor heat exchanger.
Plugged or missing traps and poor air flow cause excess moisture-growth.
![Page 16: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/16.jpg)
7/19/2008 www.infraredsurvey.com 16
Meeting roomsMeeting rooms with moisture problems, mostly due to blocked returns & lack of air flow through rooms.
www.infraredsurvey.com
Blue area’s below black above are cold- moisture meter shows over 30%
![Page 17: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/17.jpg)
7/19/2008 www.infraredsurvey.com 17
Meeting RoomsMeeting rooms A & B had blocked
return air grilles.
![Page 18: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/18.jpg)
7/19/2008 www.infraredsurvey.com 18
Roof tops Kitchen & meeting Rooms missing or plugged traps
Plugged and missing traps cause excess water build up in the drain pans and overflow back down the duct. Traps are needed due to the negative pressure in the return area. without them the condensate won’t drain properly.
Missing traps
Plugged Trap
![Page 19: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/19.jpg)
7/19/2008 www.infraredsurvey.com 19
Kitchen Roof topMissing traps cause water to over flow inside of unit and gets pulled over evaporator coil into fan section.
![Page 20: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/20.jpg)
7/19/2008 www.infraredsurvey.com 20
Kitchen Hood
Kitchen hood starter :Besides fan shroud being corroded through, the contactors are hot.
![Page 21: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/21.jpg)
7/19/2008 www.infraredsurvey.com 21
Typical Room / PTACRusted PTAC bases and poor window and or insulation allow infiltration of moisture into the building & envelope.
Areas in yellow is heat. OA temp 98
room temp 74
![Page 22: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/22.jpg)
7/19/2008 www.infraredsurvey.com 22
Attic
Attic penetrations need to be sealed. Cold air in blue causes condensation that has run down into the interior walls and cause moisture to build up with no where to drain to.
www.infraredsurvey.com
www.infraredsurvey.com
hot moist attic air will condense here and fall down conduit
63.8
92.0 °F
65
70
75
80
85
90
FLIR Systems
70.1
88.8 °F
75
80
85
FLIR Systems
![Page 23: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/23.jpg)
7/19/2008 www.infraredsurvey.com 23
AtticLeft- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire.Bellow is broken fire damper .Doors are propped open which allow more air to flow into the attic which helps but all are
Fire hazard’s
Fire damper
should be open for
ventilation
Looking from attic space
Looking from attic space
Partition door should be
closed
Fire damper
![Page 24: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/24.jpg)
7/19/2008 www.infraredsurvey.com 24
AtticMissing or misplaced insulation cause cold spots which cause condensation.
www.infraredsurvey.com
notice uninsulated space is actually affecting roof area above
72.9
84.2 °F
74
76
78
80
82
84
FLIR Systems
![Page 25: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/25.jpg)
7/19/2008 www.infraredsurvey.com 25
AtticAttic penetration-cooler temps produce condensation-Notice Rust
www.infraredsurvey.com
![Page 26: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/26.jpg)
7/19/2008 www.infraredsurvey.com 26
AtticAttic penetration- Attic temp 95 at 7AM Outside temp 85 degrees-Notice penetration Temp.Multiplied times hundreds of unsealed penetrations and higher humidity.
www.infraredsurvey.com
![Page 27: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/27.jpg)
7/19/2008 www.infraredsurvey.com 27
Attic above kitchenAttic ductwork showing Cold air leaking. Blue area is cold
65 degree air leak
Duct-board has low life span www.infraredsurvey.com
![Page 28: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/28.jpg)
7/19/2008 www.infraredsurvey.com 28
Equipment summaryAll thermostats need to be calibrated or replaced and/or night setback’s programmed.All returns needed to cleaned and/or dampers forced to the “open” position.All exhaust fans need timer switches installed and/or put back in operation-(EF-14 &15 main corridors) except for mechanical/electrical rooms.Attic penetrations need to be sealed.All Roof Top Units need traps on condensate drain lines.Air flow in attic should be conditioned, if sealing the attic envelop does not stop the moisture infiltration into the attic/hotel interior walls.Fire Hazards in attic need to be addressed.
![Page 29: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/29.jpg)
7/19/2008 www.infraredsurvey.com 29
Mechanical lifeThings in the mechanical world have a lifeexpectancy, which are determined by three things:
1. Proper maintenance2. Manufacture flaws3. Installation
Most things that are poorly installed, misaligned, orhave a manufacturing flaw, fail in the warrantystage. Poor maintenance will cause failures at theworst possible time of operation, according toMurphy’s Law.
![Page 30: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/30.jpg)
7/19/2008 www.infraredsurvey.com 30
Data InterpretationCollecting data is half the picture. Experience of the subject and conditions of which the data is collected is the most important part of these technologies.They are just tools- Phenomenal tools.
![Page 31: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/31.jpg)
7/19/2008 www.infraredsurvey.com 31
State of the Art Equipment
FLIR (IR) AlnorFlukeEx-techAll are used by the US NAVY, Boeing, NASA and many other top companies.
![Page 32: Infrared Survey Sample7/19/2008. . 23. Attic Left- is hole in elevator shaft , allowing conditioned air to flow in attic : or worse smoke & fire. Bellow is broken fire damper . Doors](https://reader033.vdocuments.us/reader033/viewer/2022042103/5e80738e7249844157077092/html5/thumbnails/32.jpg)