Mitsubishi Low Voltage Air Circuit Breaker AE-SS AE-SH ADVANCED AND EVER ADVANCING 00 B ISO 9001 NATIONAL ACCREDITATION OF CERTIFICATION BODIES Mitsubishi Electric Corporation's Fukuyama Works, which produces these products, is certified as meeting the ISO 14001 environmental management system standard.

Upload: ryan661213

Post on 25-Apr-2015

134 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Mitsubishi Low Voltage Air Circuit BreakerAE-SS AE-SH

ADVANCED AND EVER ADVANCING

00BISO 9001

NATIONALACCREDITATION

OF CERTIFICATIONBODIES

Mitsubishi Electric Corporation's Fukuyama Works, which produces these products, is certified as meeting the ISO 14001 environmental management system standard.

Page 2: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

With the highly advanced informationtechnologies, dependability as well as safetyand ease of handling of the electrical powersupply are ever-growing requirements. Therecent introduction of systemized and intelligentbuildings, upgrading, and space-saving, andsevere safety standard of power distribution hasbecome a major subject within the electricalpower supply industry. To cope with all thesecircumstances, Mitsubishi now presents theSuper AE series Low Voltage AirCircuit Breakers.

1

Page 3: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

FeaturesMain unit features ...........................................3~4Electronic trip relay features............................5~8

External view andInternal construction ..................................9~10

Product introduction ...........................11~12

Product specificationSpecification<IEC60947-2 Ics/Icu>.............13~14Specification<JIS C8372, Shipping standard> ....................15~16

Connecting methods ................................17

Charging methods......................................18

AccessoriesFor breaker unit ...........................................19~22For drawout frame .......................................23~24

Electronic trip relaySpecification table .......................................25~26General use (S type) ...................................27~28Generator protection use (M type) ..............29~30Special use (B type) ....................................31~32Electronic trip relay accessories..................33~35Circuit diagram of the electronic trip relay .........36

Operating CharacteristicsGeneral use (S type) .........................................37Generator protection use(M type) .....................38Special use (B-C0 type) ....................................39

Tripping characteristics settingSetting procedure..............................................40How to adjust the trip Relay ........................41~44

Wiring Diagram .....................................45~46

Outline DimensionsDraw-out type..............................................47~51Fixed type....................................................52~54Panel cut, drawout handle, terminal adapter.....55Neutral CT, External ZCT ..................................56

Technical information .........................57~62

Ordering informationGeneral use (Example) .....................................63General use (S type) .........................................64Generator protection use (M type) ....................65

Contents

2

Page 4: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Main unit features

3

Easier Operation

Plenty Type Composition The addition of 4000A, 5000A and 6300A frame to the universal series makes applicable

for a wide range of types from 630A to 6300A. The addition of high breaking capacity (AE-SH) series (630A-3200A frame) has enabled

the design of economic sequences.

Expanded selective interruption range With the increased short-time current rating, the selective interruption range can be

expanded with the use of the electronic trip relays with MCR function.

Full moulding Since the breaker is fully insulated with mouldings, it is safe to use for a wide range of

applications.

Long service life 10,000 mechanical open/close operations for all types. (Except for AE4000-SS~AE6300-SS,

AE4000-SSC)

AE630-SS ~ AE3200-SS 65kAAE4000-SSAE5000-SSAE6300-SS

85kAAE4000-SSC 75kA

Zero arc space Arc exhaust space to the outside of the breaker is drastically reduced for safer operation.

(AE630-SS ~ AE3200-SS, AE4000-SSC q 600VAC)

Reverse connection available Line and Load is not defined on the Main circuit terminals.

Therefore reverse connection is available without any limitation.

Page 5: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

4

More complete New AE4000-SSC The new AE4000-SSC which is smaller and economical makes fill up the AE-SS series.

AE4000-SSC has realized smaller and lighter than AE4000-SS.

Number of Operating cycles has been increased (2000 cycles→5000 cycles).

note 1: Only 3-pole type is available.note 2: The Max. rated current is 3600A on JIS C8372.

368565

AE4000-SSC

480

430

368875

AE4000-SS

DRAWOUT TYPE 3P DRAWOUT TYPE 3P(volume ratio)

(weight ratio)

58%

240kg 61% 145kg

Page 6: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Electronic trip relay features (1/2)

5

Multi functions available

Grouped electronic trip relays foreasier selection

Meets with a wide range of need depending on the application. Contributes to selective co-ordination, and ensures fine characteristic setting.

1 Electronic trip relay series

2 Common features

Pre-alarm function (PAL)The load current exceeds the value of the setting, before the breaker trips, the PALoperates, it contributes electrical continuity and easy maintenance.

Trip indicator (TI)The trip indicator (TI) is operated simultaneously with the OCR alarm (AL), when thebreaker trips because of Long time delay, short time delay/Instantaneous and Ground faultor Earth leakage. The relavent cause of tripping will be displayed on the appropriateindication LED and a relay contact will provide an output signal.

Temperature alarm (TAL)The TAL is operated by an unusual temperature of the breaker contacts.

Earth leakage protection (ER)A choice of earth leakage alarm or earth leakage tripping function is available improvingthe discrimination and the safety in circuit design.

Application Relay type

US3

S

M

B-C0A

Measuring & Display

Communication

Generaluse

Generator protection

use

Special use

Remarks Function

• Multi-function L, S, I/MCR characteristics• Ground fault/ Earth leakage protection• Trip indicator

• Plenty of electrical data is measured and displayed• Measured data, alarm and setting value is transmitted on CC-Link bus line• Remote ON/OFF operation

US3 type

S, M type

B-C0A

• INST/MCR characteristics

Provides CC-Link communication, data measuring and display for adaption to networking systems.

A multi-function type that provides all the characteristics required for the main circuit.

Only INST/MCR characteristics is provided.

Provided with characteristics for protecting generators for private power generation and marine vessels.

Option

Option

Option

Option

Page 7: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

6

Meets Many NeedsOvercurrent protection on the

neutral pole (NP)In a 3-phase 4-wire circuit such that as provided to a computer, DC power unit or otherload devices, higher harmonics are liable to be generated which could cause damage asmore load current flows in the neutral plole.NP will eliminate such a possibility.

Ground fault protection (GFR)Either a ground fault trip or alarm function can be selected by a change-over switch. A control supply is not necessary.

Load current indication LEDsThe load current can be easily checked with the indication LEDs on the electronic triprelay.

More secure protection owing todetection of effective value (RMS)

Effective value detection that is most suitable for the protection of electronic devices.Effective value detection independently provided for each phase, which is effective fordistorted wave forms, is used to cope with the increasing use of electronics devices,including inverters.

Distorted current

Sine wave current

AC/DC Effective value conversionMaximum phase selection

Over Currentprotection(LTD circuit)

Option

Page 8: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Electronic trip relay features (2/2)

7

MDU (Measuring Display

Available for AE630-SS~AE6300-SS

Measurement functions

The full line up through MCCB 400A to ACB 6300A enables measurementsdisplay and transmission of electric circuit information.

PAL and AL are standard function

AE-SS MDU

MDU relay types

Type

US3P

US3G

US3E

Transmission

CC-Link

Characteristics

LTD+STD+INST/MCR

LTD+STD+INST/MCR+GFR

LTD+STD+INST/MCR+ER

1Electronic trip relay (US3P etc.)2MDU display unit3CC-Link!nterface unit

Measured items(accuracy) Contents

Present value (I1, I2, I3, IN )Demand value (I1, I2, I3, IN )Maximum demand value (max. phase)

Present valueDemand valueMaximum demand value

Energy (accumulated value)Time electric energyMaximum time electric energy

Present valueDemand valueMaximum demand value

Reactive energy (accumulated value)Time electric energyMaximum time electric energyPresent value

Present value

Present value (V1-2, V2-3, V3-1)Demand value (V1-2, V2-3, V3-1)Maximum demand value (max. phase)

Present value (V1-N, V2-N, V3-N)Demand value (V1-N, V2-N, V3-N)

Present value at 3rd, 5th, 7th (I1, I2, I3, IN )Maximum value at 3rd, 5th, 7th (max. phase)Present value of total harmonics (I1, I2, I3, IN )Demand value of total harmonics (I1, I2, I3, IN )Maximum demand value of harmonics (max. phase)

Load current(±2.5%)

Power(±2.5%)

Electric energy(±2.5%)

Reactive power(±2.5%)

Reactive energy(±2.5%)

Power factor(±5%)Frequency

Line voltage(±2.5%)

Phase voltage(±2.5%)

Harmonics(±2.5%)

In case of 4P AE-SS, IN and phase voltage measuring are available.

MDU Display unit

CC-Link Interface unit

AE1600-SS with MDU

Page 9: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

8

Transmission itemsIncorporation of transmission function

Function Contents

Remote monitoring

Output

Input

Measured data (refer to page 7)Circuit condition (PAL pickup, PAL OUT, OVER)Fault information (Trip cause & Trip current)Setting of the Electronic trip relay (!n,!p, TL,!sd...)Demand time settingData clear (Accumulated data, Fault information)Error (Measuring, Transmission)

AE-SS ON/OFF status (by AXa) and other two “a” contact inputs

For remote ON/OFF

Unit) lineup for AE-SS

PLC networkingThe CC-Link transmission facilitates networking with high level systems (such as SCADA)via PLC

Specifications for CC-Link transmission

Item Specifications

Transmission speed

Connection system

Number of connectable unit per system

Unit type

Number of exclusive station

Selection from among 156kbps/625kbps/2.5Mbps/5Mbps/10Mbps

Broadcast polling

Max. 42unit

Maximum transmission distance Max. 1200m (156kbps, when using a dedicated cable)

Remote device station(station which can transmit word data as well as input/output)

1 station

CC-Link

System bus

ServerorPC

CC-Link master unit

MELSEC series PLC

MDU breaker AE-SS MDU

CC-LinkInterface

unit

Example of the PC monitoring

Page 10: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

External view and Internal construction

9

Fixed typeAE-SS Series

Drawout typeAE-SS Series

AE1600-SS 3P

Cradle

Automatic control circuit connector

Lifting hole

Charging handle

Drawout position indicationExtention rail

Position lock

Aperture for the drawout handle

Drawout handle

Padlock position

Arc extinguishing chamber

Control circuit terminal block

Electronic trip relay

OFF button

ON button

Charging handle

Charging indicator

ON/OFF indicator

AE1600-SS 3P

Lifting hooks (HP) is supplied in the case of a fixed type AE-SS series.

Page 11: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

10

Drawout typeAE-SH Series

Internal ConstructionAE-SS Series

Fixing bolt

Extension rail

Position lock

Control circuit terminal

Cradle

Charging handle

Automatic control circuit connector

Aperture for the drawout handle

Drawout handle

Drawout position indication

AE3200-SH 3P

qControl circuit terminal block

wAutomatic control circuit connector

eAuxiliary switches

rShunt trip device, Closing coil

tElectronic trip relay

yFront Cover

uTripping mechanism

iClosing mechanism

oCharging mechanism

!0Closing spring

!1Draw-out mechanism

!2 Insulated base

!3Arc extinguishing chamber

!4Main movable contacts

!5Main fixed contacts

!6Conductors on the breaker

!7Conductors on the cradle

!8Main circuit junction

!9Base

@0Contact spring

@1Conductors on the breaker

@2Conductors on the cradle

@3Power supply CT

@4Current sensor coil

@5Cradle

Page 12: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Product introduction

11

Super AE series allows easiercustomer selection

Standardmodel

Highbreaking

model

Type Page Page Page Page

AE630-SSAE1000-SSAE1250-SSAE1600-SSAE2000-SSAE2500-SSAE3200-SSAE4000-SSCAE4000-SSAE5000-SSAE6300-SS

AE630-SH

AE1000-SH

AE1250-SH

AE1600-SH

AE2000-SH

AE2500-SH

AE3200-SH

13~16

1Standard

IEC 60947-2

BS EN 60947-2

VDE 0660

JIS C8372

JIS C8370

Shipping standard

LR

GL

DNV

AB

BV

NK

Cell switchShorting-B contactLifting hooksSafety shutterSafety shutter lockMis-insertion preventorTest jumper

13~16 17

2Connecting

method

Fixed type

23, 24

3Cradle

Draw-out type

Horizontalterminals

Verticalterminals

Frontterminals

Emission

StandardDescription test procedure

IEC60947-2

Immunity

Conducted RF disturbances

Radiated RF disturbances

Electrostatic discharge

Electromagnetic field

Fast transients / burst

Conducted radio frequency

Surge

EN55011:1991 (Class A, Group 1)

EN55011:1991 (Class A, Group 1)

IEC61000-4-2 (contact Level 4)

IEC61000-4-3 (Level 3)

IEC61000-4-4 (Level 4)

IEC61000-4-6 (Level 3)

IEC61000-4-5 (Level 4)

Electromagnetic Compatibility

Earthleakage protection is not applicable for these tests.

Page 13: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

12

Electricalaccessories

Mechanicalaccessories

Accessories Page

Auxiliary switch

Motor charging device

Closing coil

Shunt trip device

Under voltage trip device

Condenser trip device

Push button cover

Counter

Cylinder lock

Door interlock

Terminal cover

Door frame

Dust cover

Interphase barrier

Mechanical interlock

18~20, 22

21, 22

4Trip indicatorGround fault protectionEarth leakage protectionPre-alarmOCR-alarmTemperature alarm

General use:• S typeGeneratorprotection use• M typeSpecial use• B-C0A type

General use:• US3 type Data Meauring Display (MDU) with CC-Link communication

Neutral CTExternal ZCTField test device

5Electronictrip relay Page Page

33, 3425~32

7, 8 34, 35

Relay accessories

Moisture-fungustreatment

Extra-corrosionproofspecifications

6Special

environment Page

58

Vertical terminaladapter

Front terminaladapter

Terminal adapter Page

17, 55

Page 14: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Product Specification

13

Specification <IEC 60947-2, BS EN60947-2,

AE630-SSTypeFrame size (A)Rated insulation voltageRated operating voltage

(VAC)(VAC)

Number of poles (P)

Rated current of neutral pole (A)

Rated short time current !cw(RMS kA)

Maximum total breaking time(s)(s)

Closing time

Number of operating cycles. (Note 1)

690VAC

With instantaneous trip

With MCR

Without instantaneous (Note2)

With MCR

Without instantaneous (Note2)

600VAC500VAC240VAC690VAC600VAC500VAC240VAC690VAC

500VAC

500VAC1 s2 s3 s

With rated currentWithout rated current

abcdabcd

Manual charging typeFixed type

Drawout type(including cradle)

Weight

(kg)

Motor charging typeManual charging typeMotor charging type

Cradle only

Ratedbreakingcapacity

!cs/!cu

(RMS kA)

690VAC 10510514318788.210514314352.552.5

10510514318788.210514314352.552.5

10510514318788.210514314352.552.5

10510514318788.210514314352.552.5

14314318718710514314314394.594.5

14314318718710514314314394.594.5

14314318718710514314314394.594.5

With instantaneous trip600VAC500VAC240VAC690VAC600VAC500VAC240VAC690VAC

Ratedmakingcapacity

!Cm

(Peak kA)

Rated current

(A)

(!n)General use

(Current rating adjustable)

Generator protection use

(Current rating fixed)

6301000690

315-378-441-504-567-630250-300-350-400-450-500157-189-220-252-284-315

63050/5050/5065/6565/8542/4250/5065/6565/6525/25

654030

0.040.085000

10000340 425410 410290 29038 38

300 385430 430368 36861 6140 5043 5363 7766 8026 30

3 4

AE1000-SS10001000690

500-600-700-800-900-1000

100050/5050/5065/6565/8542/4250/5065/6565/6525/25

654030

0.040.08500010000

340 425410 410290 29038 38300 385430 430368 36861 6141 5144 5464 7867 8126 30

3 4

AE1250-SS12501000690

625-750-875-1000-1125-1250

125050/5050/5065/6565/8542/4250/5065/6565/6525/25

654030

0.040.08500010000

340 425410 410290 29038 38300 385430 430368 36861 6141 5144 5464 7867 8126 30

3 4

AE1600-SS16001000690

800-960-1120-1280-1440-1600

1600-1920-2240-2560-2880-3200

1000-1200-1400-1600-1800-2000

800-960-1120-1280-1440-1600

625-750-875-1000-1125-1250

160050/5050/5065/6565/8542/4250/5065/6565/6525/25

656050

0.040.08500010000

340 425410 410290 29038 38300 385430 430368 36861 6142 5245 5565 7968 8226 30

3 4

AE2000-SS20001000690

200050/6565/6585/8585/8550/5065/6565/6565/6545/45

656565

0.040.081500

50/5065/6565/6565/6545/45

656565

0.040.081500

50/5065/6565/6565/6545/45

656565

0.040.081000

10000475 605410 410290 29038 38435 565430 430368 36861 6160 7263 7592 11395 11635 43

475 605410 410290 29038 38435 565430 430368 36861 6161 7364 7693 11496 11735 43

475 605410 410290 29038 38435 565430 430368 36861 6163 7566 7895 11698 11936 44

3 4

AE2500-SS25001000690

1250-1500-1750-2000-2250-2500

250050/6565/6585/8585/85

10000

3 4

AE3200-SS32001000690

320050/6565/6585/8585/85

10000

3 4

200 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 625 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200

25/25 25/25 25/25 25/25 45/45 45/45 45/45

SS type (standard model)Type

Out

line

dim

ensi

on (

mm

)

Fix

ed ty

peD

raw

out t

ype

a c d

b

a c d

b

Note 1 : The number of operating cycles without rated current also include the number of operating cycles with rated current.

Note 2 : The columns for “without instantaneous tripping” are the values when the bare (without electronic trip relay) main body and the

external relay are combined. Please apply for further detail.

Page 15: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

14

VDE0660 Ics/Icu>

10514318718710514316516594.594.5

105187286286105187187187105143

105187286286105187187187105143

105187286286105187187187105143

AE4000-SS40001000690

2000-2400-2800-3200-3600-4000

2000 q!n q 4000 2500 q!n q 5000 3150 q!n q 6300 315 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 1000 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200

320050/5085/85

130/130130/130

50/5085/8585/8585/8550/50

857070

0.050.08500

2000

857070

0.050.08500

2000

857070

0.050.08500

2000873 1003414 414290 290136 136875 1005480 480368 368123 123

875 1005480 480368 368123 123

875 1005480 480368 368123 123

160 180164 184240 263244 267125 140

240 263244 267125 140

240 263244 267125 140

3

AE4000-SSC40001000690

3200-3600-4000

3200 q!n q 4000

50/5065/6585/8585/8550/5065/6575/7575/7545/45

756565

0.040.08500500060541429013656543036815110911214514875

3 4

AE5000-SS50001000690

2500-3000-3500-4000-4500-5000

320050/5085/85

130/130130/130

50/5085/8585/8585/8550/50

873 1003414 414290 290136 136

160 180164 184

3 4

AE6300-SS63001000690

320050/5085/85

130/130130/130

50/5085/8585/8585/8550/50

873 1003414 414290 290136 136

160 180164 184

3 4

3150-3780-4410-5040-5670-6300

500-600-700-800-900-1000

315-378-441-504-567-630

625-750-875-1000-1125-1250

800-960-1120-1280-1440-1600

1000-1200-1400-1600-1800-2000

1250-1500-1750-2000-2250-2500

1600-1920-2240-2560-2880-3200

AE630-SH630

1000690

63065/6585/85

130/130130/130

––––

–––

–––

–––

–––

–––

–––

–––

0.040.083000

10000475 605410 410290 29068 68

485 615430 430398 39861 6166 7969 82

105 127108 13042 50

475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50

475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50

475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50

475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50

475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50

475 605410 410290 29068 68485 615430 430398 39861 6168 8171 84107 129110 13243 51

3 4

AE1000-SH10001000690

100065/6585/85

130/130130/130

–––

0.040.08300010000

3 4

AE1250-SH12501000690

125065/6585/85

130/130130/130

–––

0.040.08300010000

3 4

AE1600-SH16001000690

160065/6585/85

130/130130/130

–––

0.040.08200010000

3 4

AE2000-SH20001000690

200065/6585/85

130/130130/130

–––

0.040.08150010000

3 4

AE2500-SH25001000690

250065/6585/85

130/130130/130

–––

0.040.08150010000

3 4

AE3200-SH32001000690

320065/6585/85

130/130130/130

65/6545/45 65/65 65/65 – – – – – – –65/6585/85

130/130130/130

––––

–––

–––

–––

–––

–––

–––

65/6585/85

130/130130/130

65/6585/85

130/130130/130

65/6585/85

130/130130/130

65/6585/85

130/130130/130

65/6585/85

130/130130/130

65/6585/85

130/130130/130

– – – – – – ––––

0.040.08100010000

3 4

SH type (High breaking model)

Page 16: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Product Specification

15

Specification <JIS C 8372 (o-co-co duty)>

AE630-SSTypeFrame size (A)

Rated insulation voltage (VAC)(VAC)Rated operating voltage

Number of poles (P)

Rated current of neutral pole (A)

Rated short time current(RMS kA)

Maximum total breaking time (s)(s)Closing time

Number of operating cycles. (Note 1)

550VACWith instantaneoustrip

With instantaneoustrip

With MCR

Without instantaneous (Note2)

With MCR

460VAC550VAC460VAC550VAC550VAC460VAC220VAC550VAC

1 s2 s3 s

With rated currentWithout rated current

General use(Current rating adjustable)

Generator protection use(Current rating fixed)

630600550

315-378-441-504-567-630250-300-350-400-450-500157-189-220-252-284-315

63050/10565/14350/10565/14325/52.550/10565/143

85/195.550/105

100050/10565/14350/10565/14325/52.550/10565/143

85/195.550/105

125050/10565/14350/10565/14325/52.550/10565/143

85/195.550/105

160050/10565/14350/10565/14325/52.550/10565/143

85/195.550/105

654030

0.040.085000

10000

3 4

AE1000-SS1000600550

500-600-700-800-900-1000

654030

0.040.08500010000

3 4

AE1250-SS1250600550

625-750-875-1000-1125-1250

654030

0.040.08500010000

3 4

AE1600-SS1600600550

1000-1200-1400-1600-1800-2000

800-960-1120-1280-1440-1600

625-750-875-1000-1125-1250

656050

0.040.08500010000

3 4

AE2000-SS2000600550

200065/143

85/195.565/14365/14345/94.565/143

85/195.585/195.565/143

65/14385/195.565/14365/14345/94.565/143

85/195.585/195.565/143

65/14385/195.565/14365/14345/94.565/143

85/195.585/195.565/143

656565

0.040.081500

656565

0.040.081500

656565

0.040.081000

10000

3 4

AE2500-SS2500600550

1250-1500-1750-2000-2250-2500

2500

10000

3 4

AE3200-SS3200600550

3200

10000

3 4

200 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 625 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200

460VAC220VAC

65/14365/143

65/14365/143

65/14365/143

65/14365/143

65/14365/143

65/14365/143

65/14365/143

SS type (standard model)Type

Rated current

(A)

(!n)

Rated breakingcapacity(kA RMS

symmetrical)

JIS

C8372

O-CO-CO

JIS

C8370

O-CO

Rated makingcapacity

(kA peak value)Breaking duty

O-CO-CO

800-960-1120-1280-1440-1600

1600-1920-2240-2560-2880-3200

Shipping Standard <LR, AB, GL, DNV, BV, NK>

AE630-SSTypeFrame size (A)Rated insulation voltage (VAC)Number of poles (P)

600VACWith instantane-ous trip

With instantane-ous trip

With instantane-ous trip

With instantane-ous trip

With instantane-ous trip

With instantane-ous trip

NK

LR

ABS

GL

BV

DNV

500VAC

690VAC600VAC500VAC690VAC600VAC500VAC690VAC600VAC500VAC

690VAC600VAC500VAC

690VAC600VAC500VAC

Rated breakingcapacity(kA RMS

Symmetrical)

Rated makingcapacity

(kA peak value) Breaking

dutyO-CO-CO

General use(Fixed rated current)

6301000

3

50/11265/147

50/106–

65/15150/105

–65/14350/106

–65/151

3

50/11265/147

50/106–

65/15150/105

–65/14350/106

–65/151

3

50/11265/147

50/106–

65/15150/105

–65/14350/106

–65/151

3

50/11265/147

50/106–

65/15150/105

–65/14350/106

–65/151

AE1000-SS10001000

AE1250-SS12501000

AE1600-SS16001000

AE2000-SS20001000

3

65/14385/196

50/10665/14385/19650/10565/14385/18750/10665/14385/196

65/14385/196

50/10665/14385/19650/10565/14385/18750/10665/14385/196

65/14385/196

50/10665/14385/19650/10565/14385/18750/10665/14385/196

AE2500-SS25001000

3

AE3200-SS32001000

3

200 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 625 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200

50/105–

65/143

50/105–

65/143

50/105–

65/143

50/105–

65/143

50/10565/14385/187

50/10565/14385/187

50/106–

65/151

50/106–

65/151

50/106–

65/151

50/106–

65/151

50/10665/14385/196

50/10665/14385/196

50/10665/14385/19650/10565/14385/187

SS type (standard model)Type

Rated current(A)(!n)

Note 1 : The number of operating cycles without read current also include the number of operating cycles with rated current.Note 2 : The columns for “without instantaneous tripping” are the values when the bare (without electronic trip relay) main body and the external

relay are combined.

Page 17: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

16

AE4000-SS4000600550

2000-2400-2800-3200-3600-4000

2000 q!n q 4000 2500 q!n q 5000 3000 q!n q 6000 315 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 1000 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200

320085/195.5130/29985/195.585/195.565/143

––––

857070

85/195.5130/29985/195.585/195.565/143

––––

857070

85/195.5130/29985/195.585/195.565/143

––––

857070

0.050.08500

2000

0.050.08500

2000

0.050.08500

2000

3 4

AE5000-SS5000600550

2500-3000-3500-4000-4500-5000

3000-3600-4200-4800-5400-6000

3200

3 4

AE6300-SS6300600550

3200

3 4

315-378-441-504-567-630

500-600-700-800-900-1000

625-750-875-1000-1125-1250

800-960-1120-1280-1440-1600

1000-1200-1400-1600-1800-2000

1250-1500-1750-2000-2250-2500

1600-1920-2240-2560-2880-3200

AE630-SH630600550

63085/195.5130/299

–––

85/195.5130/299130/299

–––

85/195.5130/299

–––

85/195.5130/299130/299

–––

85/195.5130/299

–––

85/195.5130/299130/299

–––

85/195.5130/299

–––

85/195.5130/299130/299

–––

85/195.5130/299

–––

85/195.5130/299130/299

–––

85/195.5130/299

–––

85/195.5130/299130/299

–––

85/195.5130/299

–––

85/195.5130/299130/299

–– – – – – – –

– – – – – – –

––

0.040.083000

10000

3 4

AE1000-SH1000600550

1000

0.040.08300010000

3 4

AE1250-SH1250600550

1250

0.040.08300010000

3 4

AE1600-SH1600600550

1600

0.040.08200010000

3 4

AE2000-SH2000600550

2000

0.040.08150010000

3 4

––

AE4000-SSC4000600550

3200-3600

3200 q!n q 3600

–65/143

85/195.565/14375/16545/94.565/143

85/195.585/195.565/143

756565

0.040.085005000

3

75/16575/165

––

––

AE2500-SH2500600550

2500

0.040.08150010000

3 4

AE3200-SH3200600550

3200

0.040.08100010000

3 4

SH type (High breaking model)

AE4000-SS40001000

3

2000 q!n q 4000 2500 q!n q 50003150 q!n q 63003150 q!n q 5700

(for NK)

3200 q!n q 38003200 q!n q 3500

(for NK)315 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 1000 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200

87/211133/330

–87/211

133/330

–––

87/211133/330

–87/211

133/330

–––

87/211133/330

–87/211

133/330

87/211133/330

87/211133/330

87/211133/330

– – –

–––

AE5000-SS50001000

3

AE6300-SS63001000

3

AE630-SH630

10003

130/317

68/17387/211

133/330

130/317

68/17387/211133/330

130/317

68/17387/211133/330

130/317

68/17387/211133/330

130/317

68/17387/211133/330

130/317

68/17387/211133/330

130/317

68/17387/211133/330

–––

AE4000-SSC40001000

3

65/14385/196

51.1/11367/147

86.6/199––––––

–––

–––

–––

–––

–––

–––

–––

––––––

––––––

––––––

–––

––––––

–––

–––

–––

–– – –

–––

–––

–––

–––

––––––

––––––

––––––

–––

–––

–––

– – –

–––

–––

–––

AE1000-SH10001000

3

AE1250-SH12501000

3

AE1600-SH16001000

3

AE2000-SH20001000

3

AE2500-SH25001000

3

AE3200-SH32001000

3

SH type (High breaking model)

Page 18: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Connecting methods

17

Connection arrangementsThe following connecting methods are available for the AE type air circuit breaker.

ConnectingmethodMounting

method

Horizontal connection(Standard)

Vertical connection(VT)

Front connection(FT)

Vertical terminal adapter(VTA)

Front terminal adapter(FTA)

Fixed type(FIX)

Draw-outtype(DR)

(DR-VT) (DR-FT)

(VTA)

(VTA)

(FIX-FTA)

(DR-FTA)

Connecting Methods

Type

Type

Connecting method

Connecting method

AE630-SS

Horizontal terminal (Standard)

Vertical terminal

Fixed type

(FIX)

Fixed type

(FIX)

Options

Options

Options

Options

Draw-out

type (DR)

Draw-out

type (DR)

– – – – – – –

(VTA) –

(FIX-FTA) –

Horizontal terminal (Standard) –

(DR-VT)

(DR-FT) –

(VTA) –

(DR-FTA)

AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SS

AE4000-SSC AE5000-SS AE6300-SS

AE630-SH

Horizontal terminal (Standard)

(VTA)

(FIX-FTA)

Horizontal terminal (Standard)

(DR-VT)

(DR-FT)

(VTA)

(DR-FTA)

AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH

Note1: The terminal for AE4000-SSC, AE4000-SS ~ AE6300-SS shall be vertical terminal.

(Remarks) The white circle “”indicates that the product can be manufactured, while the blue “ ”indicates the standard connecting method.

(Note 1)

Page 19: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Charging methods

18

Manual chargingThe spring is charged by the manual charging handle. The breaker is closed when the ON button is pressed,and opened when the OFF button is pressed.

When the closing spring charging is completed, the charging indicator displays CHARGED. The indicator displays ON or OFF state of the main contacts. The breaker cannot be closed while the OFF button is being pressed. (Safety feature)

OFF lock is available by padlock (See P9, P24) as standard.

Motor charging device (MD)The closing spring is charged by an electric motor. When the breaker is closed, the spring is chargedautomatically (ON-charge method.) The closing coil (CC) is required to remotely close, and the shunt tripdevice is required to remotely open the breaker.

Manual charging is alsoavailable.

Pumping prevention isassured both electricallyand mechanically.

As the charging completioncontact is separate fromthe electrical chargingcircuit, its function in thecontrol scheme can bearranged as desired.

Motor charging rating

Ratedvoltage

Applicablevoltage range (V)

Appliedvoltage (V)

Inrush current(peak value)(A)

Steadycurrent (A)

Chargingtime (s)

DC24V 20.4 ~ 26.4 24 22 6 q 5

DC48V 36 ~ 52.8 48 14 3 q 5

AC • DC

100 ~ 125V85 ~ 137.5

100 10(10) 3(4) q 5

125 12(12) 3(4) q 5

AC • DC

200 ~ 250V170 ~ 275

200 5(7) 1(2) q 5

250 6(8) 1(2) q 5

( ): AE4000-SS~AE6300-SS

DC24, DC48V is not available for AE4000-SS~AE6300-SS

OFF charging method

Chargingcompletion

switch

MX

X1a

X2a

Controlrelay Motor

Motor charging circuitBreaker

Apply for further details of 24V DC and 48V DC.

(TS+)

(TS-)

(M+)

(M-)

Control supply

413

414

U1

U2

U1

U2

Control supply

AXb

Breaker

Motorcharging circuit

Charginglimit switch

(M+)

(M–)

A OFF charging method is also available. The closingspring is charged automatically when the breaker isopened. This is available only by externally connecting inseries b contact (AXb) of the auxiliary switch to the motorcharging circuit.In case of DC power supply, please use high capacityauxiliary switch (HAX).

Option

Page 20: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Accessories (for Breaker unit 1/2)

19

Closing coil (CC)The closing coil is a device to close the breaker by remote control.

An interlock to prevent pumping is provided electrically.

Closing time is from the initial energization of the closing coil to the completion of theclosing of the main contacts.

Because of pumping prevention is not performed, do not use AXb contact for a cut-offswitch.

Operating time AE4000-SS~AE6300-SS is 0.05 s or less.

Diode rectifier is not used for control source 24-48V DC.

Shunt trip device (SHT)This is the switch used to open the breaker by remote control. A cut-offswitch is included.

Rated voltage(Applicable voltage range)

DC24-48V(18~52.8)

AC • DC common100-250V(75-275)

Closingtime

0.08 sor less

Operating voltage • Operating inrush current (VA)

AC

AC100V 0.5A (100VA)

AC250V 1.0A (150VA)

DC

DC24V 3.5A (100W)

DC48V 7.0A (200W)

DC100V 0.6A (100W)

DC250V 1.3A (200W)

Rated voltage(Applicable voltage range)

DC24~48V(16.8~52.8)

AC380~500V(266~550)

AC • DC common100~250V(75~275)

Operatingtime

0.04sor less

Operating voltage • Operating inrush current (VA)

AC

AC100V 0.6A (100VA)

AC250V 1.7A (150VA)

AC460V 0.6A (200VA)

DC

DC24V 3.5A (100W)

DC48V 7.0A (200W)

DC100V 0.8A (100W)

DC250V 2.0A (250W)

(CC+)

(CC–)

Breaker C.C. Unit

A1

A2

Controlsupply One-pulse

circuit

CC

CC circuit diagram

Breaker Cut-off switchSHT unit

C1

C2

Controlsupply

SHT

(S+)

(S–)

SHT circuit diagram

Diode rectifier is not used for control source24-48V DC.

Motor charging device (MD)The closing spring is charged electrically, and the breaker will be ready to

be closed. When specifying the motor charging device, be sure to order the closing

coil (CC) and the shunt trip device (SHT) for remote operation. Refer to page 18 for details.

Option

Option

Option

Page 21: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

20

Under voltage trip device (UVT)This device is used to trip the breaker if the supply voltage is reduced below its nominalvalue, and consists of a UVT coil and UVT controller. Two types are available: theinstantaneous type which trips the breaker instantly, and a time delay type which trips thebreaker after a delay of 0.5 or 3 seconds from when the supply voltage has reduced belowits nominal value. The UVT controller can be mounted on the lefthand side of the breakerlooking from the front.

(Note 1) If dual rated voltages are used, a lower value is applied.(Note 2) If a remote trip function is required remove the wire shorting terminals DT1 DT2 and

connect a normally closed switch, rated 1mA at 100VDC across them.(Note 3) The operating time is a guarantee value when it drops from 85% or more of the rated

voltage. The following delay should be allowed between applying the voltage to the UVT, and closing the

breaker.UVT-SSB∗ : 1.5 s, UVT-05SSB∗ : 1.5 s, UVT-30SSB∗ : 3 s

TypeOperation

FrequencyPick-up voltageDrop-out voltage

Trip function(Note 2)

Power consumption

Ratedvoltage+10%–15%

UVT-SSB*Instantaneous0.1 s max.

100-120/200-240/380-460VAC24VDC48VDC

100-110VDC120-125VDC50/60 Hz(AC)

65~85% (Note 1)45~70% (Note 1)

With open circuit of terminals (DT1, DT2)operation time 0.1 s max.

UVT-05SSB*

0.5 s min.

UVT-30SSB*

3 s min.Operation time(Note 3)Time delay

( )

20 VA

Air circuit breaker

Circuitvoltage

Controlcircuit

UVT coil

D4J1

(U+) (U+)

(U–) (U–)

J2

J1

J2

DT

1

DT

2

(UO

–)

(UO

+)

D3D2D1

AC200-240V(UL2)AC100-120V(UL1)

AC380-460V(UL3)

Common(UL0)

Trip button

UVT circuit diagram

UVT controller

6.5 215

182.2

14.5

14.6

45

11

UVT controller

19.8

118 7.

89.

3

87.9 72

19

Terminal screw M3.5Plus-minus screw

Mounting screw

(mm)

Con

tact

capa

city

(A

)

AC

DC

460V250V125V250V125V30V

TypeAX(standard)

Resistance load510100.30.610

Inductive load210100.30.66

HAX (high capacity type)Resistance load

5101031010

Inductive load2.510101.5610

Maximum contacts

Change-over sequenceBreaker state

ONOFF

a-contact (NO)ONOFF

b-contact (NC)OFFON

5 a 5 b 5 a 5 b

Auxiliary switch(AX-standard, HAX-high capacity type)

This is the contact that is used to remotely indicate the ON or OFF status of the breaker.

The a and b contacts may turn simultaneously to ON instantaneously at the time of changing the contact; Pay attention to the contact state when designing circuits.

The chattering time at the time of contact ON-OFF is below 0.025 s. For special environment specification, the contact capacity gets deteriorated.

Apply for further detail.

Option

Option

Page 22: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Accessories (for Breaker unit 2/2)

21

Push button cover

The cover is to prevent careless manual operation (ON,OFF) of the push buttons.BC-L can be locked by a padlock (The padlock beingsupplied by the customer.)For the size of the a suitable padlock, refer to Page 24.

Counter (CNT)

The open/close operations of the breaker are shown on a5 digit counter.

Cylinder lock (CYL)

The breaker is locked OFF with the cylinder lock. Since it is an interlock which only allows the key to be

removed when the breaker is locked off, it can be usedfor interlocking two or more breakers.

Door interlock (DI)

The panel door cannot be opened unless the breaker isopen. A wire type mechanical interlock is used to allow

flexibility in positioning breakers in the switchboard. The parts of the Door panel should be supplied by

customer.

Dust cover

Dust cover prevents the dust or water entering into thepanel board from the breaker panel cut.Protection degree IP 54.

Interphase Barrier (BA)

The interphase insulation of the circuit breaker has beenintensified to prevent the short circuit due to conductivematters or dust. Easily detachable, in design, the barrier isapplicable to fixed type, draw-out type, horizontal terminalor vertical terminal. (For further detail, see the “Table ofMountable Barriers” given below.

Table of Mountable BarriersDoor lock unit

Door panel

Breaker

Horizontal terminal (standerd)

Horizontal terminal (standerd)

Vertical terminal adapter

Front terminal adapter

Vertical terminal adapter

Vertical terminal

Front terminal adapter

Front terminal

AE630-SS~AE1600-SS

Connectingmethod

AE2000-SS~AE3200-SS

AE-SHType

Not available for AE4000-SSC, AE4000-SS~AE6300-SS

Fixed type

Draw-outtype

Option

Option

Option

Option

Option

Door frame (DF)

The door frame improves the appearance, after cutting outthe panel door to install the breaker.

Option

Terminal cover (TTC)

The transparent terminal cover prevents from carelesstouching to the live control terminals.Protection degree IP20.

Option

Push button cover

Interphase barrier (BA) 2 pcs (3-pole), 3 pcs (4-pole)

Page 23: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

22

Mechanical interlock (MI)The mechanical interlock is a secure interlock prohibiting the parallel closing of two or three breakers. Any combination between AE630-SS~AE3200-SH and AE4000-SSC is possible. Please apply for further

details of AE4000~6300-SS. It can be simply installed on either fixed or drawout type breakers. With the drawout type, the interlock operates at the connecting point and can be released at other positions,

providing secure maintenance and inspections of the breaker. There are restrictions on ordering MI and DI together, please apply for further details. It is impossible to secure interlock among 3 pcs of AE4000-SS~AE6300-SS.

Condenser trip device (COT)Even if the power supply fails, the breaker can be electrically opened by remote operation within a definitetime. This device is combined with the shunt trip device (SHT).

Note 1: The rated charging voltage is the voltagestored during capacitor saturation. It iscontinuously supplied by the rectifiedvoltage of the rated AC input voltage.

Note 2: The charging time starts when thecapacitor begins to supply power at 85%of the rated AC input voltage andcontinues until the capacitor chargingvoltage reaches 60% of rating.

Note 3: The time period in which the shunt tripdevice can perform its one operationstarts from when the capacitor is chargeto 100% the supply voltage is removed.

ON OFF

G

ON

ON

OFF

Change over of two power supplies

The followinginterlocks are available.

Change over of two supply systems

Up to any two breakers can be closed.(Please apply for further details)

Vertical mounting Horizontal mounting(mm)

Breaker

1000(Max.)10

00(M

ax.)

144

0~12

134

Breaker

Breaker arrangement (630AF~3200AF)

47(Max.)

Type KF-100

100/110VAC

50~60Hz

140/155V

660µF

60~125%

1VA

0.5 s max.

15 minutes min.

Black (N1.5)

2000VAC

100~250VAC • DC

KF-200

200/220VAC

280/310V

150µF

5 minutes min.

Rated input voltage

Rated frequency

Rated charging voltage (Note1)

Condenser capacity

Voltage range

Power supply capacity

Charging time (Note 2)

Trip limit time (Note 3)

Paint color

Withstand voltage (1 minute)

Applicable shunt trip voltage

60~125%

50~60Hz

1VA

0.5 s max.

Black (N1.5)

100~250VAC • DC

2000VAC

90

90

75110.6

4-R6

Condensertrippingdevice

4-M3×0.5Cover screw

13.315.4168790106

100

4-M4 screw(for wiring)

4-M6 Mounting screw

4545

4545

f104

4-f7

AC1

AC2

S1 R1

R2

R3

N6

DC+

DC–

C

SHT

C1

C2

Open button

Front view Side view Drilling plan Circuit diagram (mm)

Outline dimensions (mm)

Option

Option

Page 24: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Accessories (for Drawout frame)

23

Cell switch (CL)

The switch is used to indicate the drawout positions(CONNECTED, TEST, DISCONNECTED).

Shorting b-contact (SBC)

When moving the breaker from the connected to the testpositions, use this contact to short circuit auxiliary switch(AXb) thus maintaining the correct sequence of operationof the external control circuit.When ordered, the same number of shorting b-contacts asauxiliary switches (AXb) will be provided.

Lifting hooks (HP)

This is used to remove the drawout type breaker from thecradle.The option is not necessary when the special lifter (buckettype) for AE-SS·SH is used.The fixed type breaker is equipped with HP as standard.

Safety shutters (SST)

The safety shutters cover the conductors (cradle side) andprevent contact with them when the breaker is drawn out. When checking the main circuit, supply and load sides

of the shutters can be kept OPEN independently. (theyare released automatically when the breaker is pushedin.)

Safety shutter lock (SST-LOCK)

This kit is used to lock the safety shutters using 2 padlocks(the padlocks to be customer’s supply). The safetyshutters close when the breakers drawn out to preventaccidental contact with the main contacts.

CL-C(CONNECTED)

Drawout positionof breaker

Display position ofdrawout operation

CL-T(TEST)

CL-D(DISCONNECTED)

Sw

itch

func

tion

Con

tact

cap

acity

(A

)

Chan

ge-o

ver s

eque

nce

(a-c

onta

ct)

DISCON TEST CONNECT

ON

ON

ON

OFF

OFF

OFF

Disconnected Connected

Voltage (V)

Number that may be installed Total 4c max.

AC

DC

460

250

125

250

125

30

Resistive load Inductive load

2.5

10

1.5

6

10

10

5

3

10

10

Operating sequence and contact rating

OptionOption

Option

Option

Option

Page 25: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

24

Mis-insertionpreventor (MIP)

This option prevents any other circuit breakers exceptthose specified from being inserted into the cradle, 5settings are available.(Note) It is not available for AE4000-SS~AE6300-SS.

Test jumper (TJ)

With the breaker taken out of its cradle, this device willenable the breaker to be electrically opened and closed,and the operating sequence to be checked.Note 1: Remove the breaker out of its cradle before using

this device.

Drawout interlockA safety device prohibits push-in and drawout whenthe breaker is ON. The drawout handle cannot beinserted unless the OFF button is pressed.

Position lockThis device is for locking the drawout mechanism atthe TEST position this then indicates the “TESTposition”. The lock can be used during either thedrawing out or pushing in operation.The lock is released when the lock plate is pushed in,and the next operation becomes possible.Padlocking is possible at the CONNECTED, TEST,and DISCONNECTED positions. Use this lock toprevent unauthorized changing of positions.

The padlock should be supplied by customer.

16

5

35

(mm)

CONNECTED position TEST position DISCONNECTED position DRAWOUT position

Main circuit is disconnected, but the control circuit is connected. The breaker operation can be tested with the door closed.

Both main and control circuits are disconnected.

This is the position for removing the breaker. The breaker is drawn out of the cradle on the extension rails.

The door can be closed.

Both main and control circuits are connected.

Normal in use condition.

Standard equipment

Operating position of drawout type

Option

Option

The earthling points are located on both sides of the cradle, and they make contact between the breaker and the cradleat CONNECTED, TEST, and DISCONNECTED positions.

Lock plate

Page 26: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Electronic trip relay specifications table

25

Use

Type S ST SPT

General use

SPGT SPET M

Generator

MT

Protection

Overload, Short circuit (L+S+I) (Note 1)

Not required

Required

Required

Required

Required

Not required

Required

Neutral protection (NP)

Making Current Release (MCR) (Note 2)

Pre-alarm (PAL)

Ground fault (GFR) (Note 3)

Earth leakage (ER)

Load current indication LEDs, Alarm

Load current indication LEDs

OCR alarm (AL)

Trip indicator (TI)

Temperature alarm (TAL)

Others

Control power supply

Test terminal

STD lock button

: Standard equipped: Optional equipped: Not available

Classification of typesExample

Type

Not required

Control voltageCode

0

AE630-SS

630

500

315Low

rating

AE1000-SS

1000 1250 1600 2500 3200 4000 4000 5000

6000 (JIS)

6300

AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SSC AE4000-SS AE5000-SS AE6300-SS

(A)

1

2

4

AC100-120/AC200-240V

DC100-125V

DC24-60V

Note 1:Note 2:Note 3:Note 4:

L → LTD, S → STD, I → INSTMCR function is not available for AE-SH.GFR is not availabe for AE630-SS (!n max = 315A, 500A), nor AE630-SH.B-C0A relay and BARE are not available for AE-SH series.

Table 1 Control supply voltage code

Table 2 CT rating (Rated current MAX.)

2000

1600

1250Low

rating

AE630-SH AE1000-SH

1000630 1250 1600 25002000 3200

AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH

SPT

Page 27: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

26

MPT

protection use Special use No relayRemarks Ref. Page

37~39

33

34

33

33, 35

28, 30, 32

34

28, 30

34

34

28, 30

Required

MPGT

Required

B-C0A(Note 4)

BARE(Note 4)

Only INST

Only INST

Not required

Not required

LTD, STD and INST characteristics are standard equipped. Only INST is equipped for B-C0A relay

NP characteristics is same as live poles. AE-SS 4P

With MCR, Instantaneous tripping is only possible if a short circuit occurs during switch-ON. After the initial switch-ON, the Inst characteristic is cancelled to keep selectivity. INST/MCR set is changeable.PAL is indicated LED and a contact output if the load current is exceeded PAL setting value. Operating characteristic is half of LTD characteristic. Auto reset type.GFR ALARM/TRIP is changeable. When the switch is set to “ALARM” position a indicator LED will light up and the relay output will be activated when a ground fault occurs. However ACB will not trip.

Indicates load current in percentage indicator LEDs.30ms 1pulse output signal will be activated. Self-hold circuit is reqired when continuous signal is needed. It will notactivated when ER operates.Fault cause is indicated LED and A contact. The signal is reset by pushing reset button or turning off the control power supply of the relay.

OperatingVA: 5VA Vairious voltage code is shown below left table 1.

This button is used during characteristic check.

Operating characteristics (LTD, STD, INST, GFR, PAL) are checked by field test device for AE-SS/AE-SH. Each pole characteristic is is checked individually for M type relay.

TAL is indicated LED and a contact output if the temperature around main contacts is exceeded usual level. The signal is reset by pushing reset button or turning off the contorl power supply of the relay.

External ZCT is reqired. Alarm output (A contact) signal will be activated. Also ACB can be tripped with SHT trippingdevice.

MCROCRalarm

Control voltagecode

Temperaturealarm

Voltage (V)

AC120

250

30

125 0.2 0.1

2 2

DC

Resistiveload

Inductiveload

(A)Table 3 Contact rating of Trip indicator and alarm

C 2 A T

Page 28: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

27

Electronic trip relay (General use

27

S type (General use)

Rated current Max. (!n max) Refer to P25 Table 2.

Adjustable setting range

0.5-0.6-0.7-0.8-0.9-1.0 ×!n max

0.8-0.9-1.0 ×!n max (AE4000-SSC)

0.8-0.82-0.84-0.86-0.88-0.9-0.92-0.94-0.96-1.0 ×!n

1.15 ×!u ±10%

12-25-50-100-150 s ±20% (at 2 × !u)

2-3-4-6-8-10 ×!n ±15%

0-0.1-0.2-0.3-0.4-0.5 s ±20% (at 1.5 ×!sd)

4-6-8-10-12-16 ×!n ±15%4-6-8-10-12 ×!n ±15% (AE5000-SS)4-6-8-10 ×!n ±15% (AE6300-SS)

0.7-0.8-0.9-1.0-OVER ×!u ±10%

0.5 × TL ±20%

0.1-0.2-0.3-0.5 ×!n max ±20% 0.2-0.3-0.5 ×!n max ±20% (AE4000-SSC, 4000-SS~6300-SS)

0.3-0.8-1.5-3 s ±20% (at 1.5 ×!g)

1-2-3-5 A ±20%

0.3-0.8-1.5-3 s ±20% (at 1.5 ×!∆n)

Rated current (!n)

Short-timedelay

Uninterrupted current (!u)

LTD current Long-timedelay

LTD time (TL)

STD current ( !sd)

STD time (Tsd)

INST current (!i) Instantaneous

PAL current (!p)

PAL time (Tp)

GFR current (!g)

GFR time (Tg)

ER current (!∆n)

Ground-faultprotection

Earth-leakageprotection

ER time (Te)

Pre-alarm

Rated current Max. (!n max)

Rated current (!n) PAL current (!p)

Load current indication LEDs

INST current (!i)

STD current (!sd)

Uninterrupted current (!u)

GFR current (!g)

ER current (!∆n)

Unless specified when ordering the electronic trip relay will be set to in blue.

S type setting dial operation schematic

Page 29: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

S type)

28

N

AB

E

G

OQ

PH R

J

KMIL

F

CD

MADE IN JAPAN

MODEL

1600 A

ELECTRONIC TRIP RELAY

TRIP INDICATOR

ALARM

LOAD CURRENT % Iu

SPGT–C1AT

ALARMTRIP

0.20.1

0.5GFR P.U. Ig

0.3

0.50.4

0.10

0.20.3150

122550

1003.01.5

0.30.8

106 8 161210.88

23

STD P.U. Isd

4

UNINTERRUPTED

864

INST P.U. Ii

.80

.84 .921.0 OVER

PAL P.U. Ip

0.9

0.70.8

STD LOCK MCRINST

RESET

OVER

TAL

S/I GL

1008060

RATED CURRENT MAX.

1.0

1.0

.96

TEST

PAL P.U. PAL OUT

(CT RATING)

=In maxRATED CURRENT In

CURRENT Iu

XIn max

X In max

XIu XIn XIn XIn

s s s

Iu × 2 Isd×1.5

GFR TIME LTD TIME STD TIME

0.90.80.7

0.60.5

A Trip indicator

PAL indicator

Temperature alarm indicator

Reset button

Load current indication LEDs

Rated current setting dial

Uninterrupted current setting dial

LTD time setting dial

STD current setting dial

STD time setting dial

STD lock button

INST current setting dial

INST/MCR switch

PAL current setting dial

GFR or ER current setting dial

GFR or ER time setting dial

GFR TRIP/ALARM switch

TEST terminal

BCDEFGHIJKLMNOPQR

Page 30: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Electronic trip relay (Generator

29

M type (Generator protector use)

Rated current Max. (!n max)

Rated current (!n) PAL current (!p)

Load current indication LEDs

INST current (!i)

STD current (!sd)

LTD current (!L)

GFR current (!g)

Rated current Max. (!n max) Refer to P25 Table 2.

Adjustable setting range

0.5~1.0 ×!n max 0.8~1.0 ×!n max (AE4000-SSC)

1-1.05-1.1-1.15-1.2 ×!n ±5%

15-20-25-30-40-60 s ±20% (at 1.2 ×!L)

2-2.5-3-3.5-4-4.5 ×!n ±15%

0-0.1-0.2-0.3-0.4-0.5 s ±20% (at 1.5 ×!sd)when “0” setting, operating time is 0.04~0.08 s.

4-6-8-10-12-16 ×!n ±15%4-6-8-10-12 ×!n ±15% (AE5000-SS)4-6-8-10 ×!n ±15% (AE6300-SS)

0.84-0.88-0.92-0.96-1.0 ×!L ±5%

0.5 × TL ±20%

0.1-0.2-0.3-0.5 ×!n max ±20% 0.2-0.3-0.5 ×!n max ±20% (AE4000-SSC, 4000-SS~6300-SS)

0.3-0.8-1.5-3 s ±20% (at 1.5 ×!g)

Rated current (!n)

Short-timedelay

LTD current (!L) Long-timedelay

LTD time (TL)

STD current (Isd)

STD time (Tsd)

INST current (Ii)Instantaneous

PAL current (Ip)

PAL time (Tp)

GFR current (Ig)

GFR time (Tg)

Ground-faultprotection

Pre-alarm

(setting by factory side)

Unless specified when ordering the electronic trip relay will be set to in blue.

M type setting dial operation schematic

Page 31: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

30

protection use M types)

LOAD CURRENT % IL

PAL P.U. Ip

RESET

TAL

S/I GL

PAL P.U. PAL OUT

1600 A=In max.

IL×1.2 Isd ×1.5

MADE IN JAPAN

MPGT–1ATMODEL

ELECTRONIC TRIP RELAY

TRIP INDICATOR

ALARM

1.0.96

.88.84

.92

1283 A

FINE

90 1007050

3.5 4.5

2.53

4

60403025

XIn XIn XIn

1.05

1.21.1

1.0

LTD P.U. IL1.15

ALARMTRIP

0.20.1

0.5GFR P.U. Ig

0.3

0.50.4

0.10

0.20.3

1520

3.01.5

0.30.8

161210

2

STD P.U. Isd INST P.U. Ii

864

STD LOCK

CT RATING RATED CURRENT In

TEST

(RATED CURRENT MAX)

XIn max.

XIL

s s s

GFR TIME LTD TIME STD TIME

G

AB

E

F

H

M

N

O

P

CD

I

J

K

L

Q

A Trip indicator

PAL indicator

Temperature alarm indicator

Reset button

Load current indication LEDs

LTD current setting dial

LTD time setting dial

LTD time fine setting dial

STD current setting dial

STD time setting dial

STD lock button

INST current setting dial

PAL current setting dial

GFR current setting dial

GFR time setting dial

GFR TRIP/ALARM switch

TEST terminal

BCDEFGHIJKLMNOPQ

Page 32: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

31

Electronic trip relay (Special useB type (Special use)

Rated current Max. (!n max) Refer to P25 Table 2.

Adjustable setting range

0.5-0.6-0.7-0.8-0.9-1.0 ×!n max (setting by factory side) 0.8-0.9-1.0 ×!n max (AE4000-SSC)

Non

Non

4-6-8-10-12-16 ×!n ±15%4-6-8-10-12 ×!n ±15% (AE5000-SS)4-6-8-10 ×!n ±15% (AE6300-SS)

Rated current (!n)

Short-time delay

Long-time delay

INST current (!i)Instantaneous

Rated current Max. (!n max)

Rated current (!n) INST current (!i)

Load current indication LEDs

Unless specified when ordering the electronic trip relay will be set to in blue.

B type setting dial operation schematic

Page 33: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

32

B type)

LOAD CURRENT % In

INST P.U. Ii

MCRINST

XIn

MADE IN JAPAN

RATED CURRENT

In

B–C0A

=

MODEL

60 80 100 OVER

810 12 16

ELECTRONIC TRIP RELAY

1600 A

64

TEST

NON LTD

NON STD

A

B

C

D

A Load current indication LEDs

INST current setting dial

INST/MCR switch

TEST terminal

BCD

Page 34: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Electronic trip relay accessories

33

Ground fault protection (GFR)

Sometimes the Long-time-delay or Short-time-delayfunctions will not protect a circuit even if there is aground fault of several hundred amps. In which case,the ground fault protection function (GFR) is used. Thesensitivity is selectable in the range of 0.1-0.2-0.3-0.5times the Rated current MAX. (!n max), and the operatingtime is selectable from the range of 0.3-0.8-1.5-3seconds. A control supply is not required for theoperation of the ground fault protection.Note 1: In a 3-phase, 4-wire circuit, ground fault

protection is also possible with a 3 pole breakerand a Neutral CT (NCT) see page 35, 56.

Note 2: The ground fault protection (G) is not available forAE-SS series with the Rated current MAX. (!n max)coming to 315 A or 500 A, or for AE630-SH.

Neutral pole overcurrent protection (NP)

This function protects the neutral pole (4 pole) of thecircuit breaker from overcurrent with S type relay.Neutral overcurrent protection can be set to operateat 100% of the rated current. Load equipment (forexample: computer equipment, DC power supplies,etc) which is liable to generate third harmonic waveforms that may cause more load current to flow inthe neutral pole, which may cause damage, theneutral pole overcurrent protection will preventdamage from occuring.

Earth leakage protection (ER)The earth leakage alarm facility is provided by using a electronic trip relay with earth leakage protection and aexternal ZCT (see page 37, 56.)Even if several amperes of earth leakage current flow, the alarm alone operates but the breaker does not trip.This is therefore suitable when a continuous power supply is required. Should the breaker be required to tripon earth leakage, the above should be used with a SHT.Note 1: The shunt tripping device (SHT) is suitable for 100-250V AC/DC or less.Note 2: Output contact is self-hold type.

The output contact is turned off when the reset button is pressed or control supply is turned off.

Connection diagram (Earth leakage alarm system) Connection diagram (Earth leakage tripping system)

4 pole breaker Current sensor coil

GFR

Electronic trip relay(with ground fault protection)

ER

N2

544

513

L2 L1

BZ

N1External ZCT

SPET relay

Relaycontrol supply

BZ controlsupply

Relaycontrol supply

SHT controlsupply

External ZCTfor ground wire

Earth leakagealarm buzzer

ER

N2714

713

C1C2

L2 L1

N1External ZCT

SPET relayExternal ZCTfor ground wire

SHT

Connection diagram

Same phase

Current sensor coil

Load equipment whichgenerates electric currentof the third harmonicwave form.

Option

Option

Page 35: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

34

Temperature alarm (TAL)If the temperature of the main contact rises above a pre-determined level, a LED will light and a relay contact(1a) will energize. This will prevent trouble and increase contact life, a useful preventive maintenance feature.(The control supply and the reset button are used in common with the trip indicator.)

Pre-alarm (PAL)

If the load current of the breaker exceeds the set value, A “PAL” LED lights and a relay output is energized.This is useful in securing a continuous power supply to a important circuit. The operating characteristic shownon the curve is proportional to half of the Longtime-delay tripping characteristic. The relay output is of an autoreset type.

OCR alarm (AL)

The OCR alarm (AL) is a short-time operating switch(1a) for the electrical indication of when the breakertrips due to overcurrent. The AL is an integral part of theelectronic trip relay. Though it operates when thebreaker trips due to the Long-time-delay, Short-time-delay, Instantaneous/MCR, Ground fault protection(GFR), It does not operate when the breaker trips dueto the Earth leakage protection (ER).

Note:Though a control supply is not required for theoperation of the OCR alarm (AL), a self-hold circuitis required since the relay output only operates for0.03 seconds.

Note:When a continuous output signal from the OCRalarm (AL) is required please use the output signalfrom the trip indicator (TI) which is operated by thesame causes as the OCR alarm (AL).

Option

Option

Field test device

The electronic trip relay can be checked without the breaker being connected to the main supply. The breakerwill trip when tested.Y-160 test device is not available for M type relay.

Type Y-160Y-2000

AC100-240V50-60HZ

Test function

Power supply

Test current signal setting

Ammeter –equipped

equippedequippedTime counter

LTD, STD, INST, GFRLTD, STD, INST, GFRPre-alarm

Battery use

• AC100-120V• AC200-240V

6-point setting possible(20%, 50%, 125%, 200%, 500%, 2000%)

10%~2000%(continuously variable)

Option

Page 36: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Electronic trip relay accessories

35

Neutral CT (NCT)

The neutral CT is used for ground fault protection when a 3 pole breader is used on a 3 phase 4 wires system.It should be used together with the electronic trip relay that has the ground fault protection (G) option. (refer toP56)

External ZCT

This option is used to detect several amperes of earth leakage when use in combination with a electronic triprelay that has the earth leakage tripping (ER) option.Two methods are available: The first is where the all load conductors pass through the ZCT. The other methoduses a smaller ZCT through which the supply transformer’s ground wire passes through to earth. (refer to P56)

Type Applicable CT type

AE 630-SS/SH CW-40LM 630A

AE 1000-SS/SH CW-40LM 1000A

AE 1250-SS/SH CW-40LM 1250A

AE 1600-SS/SH CW-40LM 1600A

AE 2000-SS/SH CW-40LM 2000A

AE 2500-SS/SH CW-40LM 2500A

AE 3200-SS/SH

AE 4000-SS, SSC

AE 5000-SS

AE 6300-SS

CW-40LM 3200A

CW-40LM 4000A

CW-40LM 5000A

CW-40LM 6300ACW-40LM 6000A (JIS)

Note: A suitable resistor (0.1 10W) and screened wire (2m) is attached on the product.

Neutral CT

ResistorElectronic trip relay(with ground fault protection )

3 pole breaker

Currentsensor coil

Wiring diagram

N1

N2

Type

Application

Type ZCT163 ZCT323 ZCT324 ZT15A ZT30A ZT40A ZT60A ZT80A ZT100A

External ZCT for load circuits External ZCT for transformer ground wire

Note: A screened wire (2m) is attached on the product.

SHT

ER

SHTcontrol supply

Relaycontrol supply

SPET relay

External ZCT

C2 714N2 N1

L2 L1

713

C1

1. Wiring diagram (load circuit method)

SHT

ER

SHTcontrol supply

Relaycontrol supply

SPET relayExternal ZCT

C2 714 N2 N1

L2 L1

713

C1

2. Wiring diagram (transformer ground wire method)

Option

Option

Page 37: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Circuit diagram of the electronic trip relay

36

Circuit diagram of the electronic trip relay(SPGT)

Operating function of each device

Power supply CTEnergy is supplied for the operation of the overcurrent tripping and ground fault tripping (GFR) function ofthe electronic trip relay.Current sensor coilThe current in each phase flowing through in the breaker is detected. A coreless coil which has goodlinearity is achieved. The integrating circuit integrates the output voltage and provides a signal voltagewaveform which is in proportion with the load current.LTDThis is an effective value detection type which is strong against the distored wave. It has a memory effectfor the overcurrent state. If the electronic trip relay is tripped, the overcurrent memory is reset.Pre-alarmThis is an effective value detection system. It has a memory effect for the overcurrent state.STD/INSTThis is a peak value detection system, and is suitable for short time operation.Ground fault circuitThe signals in each phase are summed in the vector mode in order to detect the ground fault value.Trip indicator circuitFault cause and pre-alarm is indicated with control power supply.OCR alarm circuit1 pulse 30ms signal output without control power supply.

8

7

6

5

4

3

2

1

N2

N1

N

OCR alarmcircuit

L1L2L3

544

554

524

PAL OUT

513

534

30ms1 pulse

97

98

Trip indicatorcircuit

PAL pick-up LED

Load LED

STD

LTD

Watch-dogtimercircuit

INST.circuit

Pha

sese

lect

ion

sam

plin

g

L

S/I

G

Settinginput

Ground faultcircuit

I/O

Acc

umu-

lato

rA

/Dco

nver

tor Overload

/PAL

S/W

S/W

S/WPAL

LTD

STD/INST

GFR

Controlpowercircuit

Triggercircuit

Custom IC

Electronic trip relay

Characteristicsetting part

CPU

Trip coil

Peak valueconversion/Max. phaseselectioncircuit

GroundfaultIntegration/compositioncircuitNCT, ZCT input

Lower terminals

Test

con

nect

or

Cur

rent

sen

sor

coil

Pow

er s

uppl

y C

T

Upper terminals

Rec

tifie

rsi

gnal

circ

uit

Inte

grat

ing

circ

uit

Rec

tifie

rci

rcui

t

Pow

er s

uppl

yci

rcui

t

Page 38: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Operating characteristics (General use)

37

% of uninterrupted current (!U)% of rated current (!n)Current

% of rated current MAX. (!n max)

Long time delay pre-alarmShort time delay/instantaneous

Ground faultCharacteristics from the factory

Adjustable characteristics

Ope

ratin

g tim

e (s

econ

ds)

Maximum breaking time(In case ofAE4000-SS~AE6300-SS,it is 0.05s.)

INST current (Ii)4-6-8-10-12-16 In±15%4-6-8-10-12 In±15% (AE5000-SS)4-6-8-10 In±15% (AE6300-SS)

with MCR (AE-SS series only)

GFR time (Tg)0.3-0.8-1.5-3s±20%

STD time (Tsd)0-0.1-0.2-0.3-0.4-0.5s±20%

STD current (Isd)2-3-4-6-8-10 In±15%

LTD time (TL)12-25-50-100-150s±20%

GFR current (Ig)0.1-0.2-0.3-0.5 In max±20%

0.2-0.3-0.5 In max±20%(AE4000-SSC~AE6300-SS)

PAL current (Ip) 0.7-0.8-0.9-1.0-OVER Iu±10%

PAL time (Tp)TL/2±20%

5000200202

500

400

300

200

60

500505

1

2

3

5

4

10

20

30

40

50

1000

100

100010010

.04

.05

.1

.2

.3

.4

.5

.01

.02

.03

125 1600 2000

S type

Page 39: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Operating characteristics (Generator protection use)

38

M typeO

pera

ting

time

(sec

onds

)

% of Long time delay current (!L)% of rated current(!n)Current

% of rated current MAX.(!n max)

pre-alarmLong time delay/Short time delay/instantaneous

Ground faultCharacteristics from the factory

Adjustable characteristics

PAL time (Tp)TL/2±20%

LTD time (TL)15-20-25-30-40-60s±20%

LTD current (IL)1.0-1.05-1.1-1.15-1.2 In±5%

PAL current (Ip) 0.84-0.88-0.92-0.96-1.0 IL±10%

GFR current (Ig)0.1-0.2-0.3-0.5 In max±20%

0.2-0.3-0.5 In max±20%(AE4000-SSC~AE6300-SS)

STD current (Isd)2-2.5-3-3.5-4-4.5 In±15%

STD time (Tsd)0-0.1-0.2-0.3-0.4-0.5s±20%

GFR time (Tg)0.3-0.8-1.5-3s±20%

INST current (Ii)4-6-8-10-12-16 In±15%4-6-8-10-12 In±15% (AE5000-SS)4-6-8-10 In±15% (AE6300-SS)

Maximum breaking time(In case ofAE4000-SS~AE6300-SS,it is 0.05s.)

20001600120

.03

.02

.01

.5

.4

.3

.2

.1

.05

.04

10 100 1000

100

1000

50

40

30

20

10

4

5

3

2

1

5 50 500

60

200

300

400

500

2 20 200 5000

Page 40: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

39

MAX. time of let-through current and B type relaycharacteristics

B-COA

% of Rated currentCurrent

time(

seco

nds)

Characteristics from the factory Adjustable characteristics

INST current (Ii)4-6-8-10-12-16 In±15%4-6-8-10-12 In±15%(AE5000-SS)4-6-8-10 In±15%(AE6300-SS)

Maximum breaking time(In case ofAE4000-SS~AE6300-SS,it is 0.05s.)

Max.Ratedshort timecurrent (1s)

Max.time of let-through current

External OCR max. setting

500020020

500400

300

200

60

500505

1

2

3

54

10

20

30

4050

1000

100

100010010

.04

.05

.1

.2

.3

.4

.5

.01

.02

.03

1600 2000

(Not available for AE-SH)

Page 41: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Tripping characteristics setting

40

Setting procedure

1.A small flat-tipped screwdriver is prepared.

2.Insert the flat-tipped screwdriver into the opening of theelectronic trip relay cover. Then, lightly press thescrewdriver leftward, and the cover will open.

3.There are 3 types of switches for setting up the requiredtripping characteristics and they should be used asfollows:-

qStep adjustable typeA rotary switch is used. Do not stop the switch betweensteps as it would be the same setting value as thatassociated with the nearest step line. (Operate theswitch with a torque of 0.1N•m or less.)

wSlide switch typeSlide the switch to the left or right. (operate the switchwith a force of 10N or less.)

ePushbutton typeA pushbutton is provided for termporary operation.Press it with a force of 10N or less. Before operatingmake sure that the push-button is in its initial state.

4.When the characterisitics have been set, they should bechecked using a field tester.

5.Two methods for sealing the cover are provided, selecteither from the following:

qStick the sealing label on the opening of the electronictrip relay cover, and close the cover. The cover can notbe opened unless the sealing label is removed.Note: The sealing label is supplied with the relay.

wSeal the electronic trip relay cover by using the leadsealing hole at the bottom of the cover.

Operating hole for Resetting

Press the screwdriver in the direction of the arrowto open the cover.

6mm

max

.0.

8mm

max

.

Side view of the flat tip

XInXInXInXIu

XIn max

XIn max

CURRENT Iu

RATED CURRENT InIn max=

(CT RATING)

.96

1.0

0.70.8

0.60.5

0.91.0

RATED CURRENT MAX.

60 80 100 OVER

INST MCRSTD LOCK

0.80.7

0.9

PAL P.U. IpOVER1.0

.92.84

.80

INST P.U. In

46

8

UNINTERRUPTED

4

STD P.U. Isd

32

.88 10 12 1686 10

0.3

GFR P.U. Ig0.5

0.10.2

TRIP ALARM

LOAD CURRENT % Iu

1600 A

q Step type e Push-button type w Slide switch type

Coverw Lead sealing hole

q Sealing label

Operating hole for Resetting

Page 42: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

41

How to adjust the trip relay

AE-SS has very intelligent relay with multi functions.

But sometime, it seemed to be difficult to adjust it.

This report can help you to solve such questions.

<Front view of the relay>The relay is set as follows.

Here!n max = Maximum rated current!n = Rated current!u = Uninterrupted currentLTD TIME = Long time delay tripping time!sd = Short time delay pick-up currentSTD TIME = Short time delay tripping time!i = Instantaneous pick-up current!p = Pre-alarm (PAL) operating current!g = Ground fault pick-up currentGFR TIME = Ground fault operating time

TEST

MADE IN JAPAN

MODEL

SPGT–C1A

ELECTRONIC TRIP RELAY

STD TIMELTD TIMEGFR TIME

Isd × 1.5Iu × 2

sss

XInXInXInXIu

XIn max

XIn max

CURRENT Iu

RATED CURRENT InIn max=

(CT RATING)

PAL OUTPAL P.U.

.96

1.0

0.70.8

0.60.5

0.91.0

RATED CURRENT MAX.

60 80 100

L GS/I

OVER

RESET

INST MCRSTD LOCK

0.80.7

0.9

PAL P.U. IpOVER1.0

.92.84

.80

INST P.U. Ii

46

8

UNINTERRUPTED

4

STD P.U. Isd

32

.88 10 12 1686 10

0.80.3

1.53.0 100

502512

150 0.30.2

00.1

0.40.5

0.3

GFR P.U. Ig0.5

0.10.2

TRIP ALARM

LOAD CURRENT % Iu

ALARM

TRIP INDICATOR

1600 A

Page 43: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Tripping characteristics setting (2/3)

42

TEST

MADE IN JAPAN

MODEL

SPGT–C1A

ELECTRONIC TRIP RELAY

STD TIMELTD TIMEGFR TIME

Isd × 1.5Iu × 2

sss

XInXInXInXIu

XIn max

XIn max

CURRENT Iu

RATED CURRENT InIn max=

(CT RATING)

PAL OUTPAL P.U.

.96

1.0

0.70.8

0.60.5

0.91.0

RATED CURRENT MAX.

60 80 100

L GS/I

OVER

RESET

INST MCRSTD LOCK

0.80.7

0.9

PAL P.U. IpOVER1.0

.92.84

.80

INST P.U. Ii

46

8

UNINTERRUPTED

4

STD P.U. Isd

32

.88 10 12 1686 10

0.80.3

1.53.0 100

502512

150 0.30.2

00.1

0.40.5

0.3

GFR P.U. Ig0.5

0.10.2

TRIP ALARM

LOAD CURRENT % Iu

ALARM

TRIP INDICATOR

1600 A

!n =0.8×!n max

=0.8×1600=1280A

!sd=3×!n

=3×1280=3840A

!i =12×!n

=12×1280=15360A

!n max=1600A

!u =0.9×!n

=0.9×1280A=1152A

!g =0.1×!n max

=0.1×1600=160A

GFR TIME=0.8s

!p =0.8×!u

=0.8×1152=921.6A

at!g×1.5=160×1.5= 240A

LTD TIME=100sat!u×2=1152×2= 2304A

STD TIME=0.3sat!sd×1.5=3840×1.5= 5760A

at!u×2=1152×2= 2304A

PAL pick-up time=50% of LTD time=50s

( )

(

(

)

)

( )

Actual settings are as following table.

LTD TIME

STD TIME

PAL pick-up time

=1600A

=1280A

=1152A

=100s±20% (at 2304A)

=3840A±15%

=0.3s±20% (at 5760A )

=15360A±15%

=921.6A±10%

=50s±20% (at 2304A)

=160A±20%

=0.8s±20% (at 240A)

!i

!p

GFR TIME

!g

!sd

!n max

!n

!u

How to get the current settings and operating times

<Actual setting>Current settings and operating times are calculated.

Page 44: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

43

How to get the current settings and operating times

<Characteristic curve>In above settings, operating characteristics are set as follows.

Current (%)

Characteristic curve

INST current (Ii) setting range

GFR time (Tg) setting range

STD time (Tsd) setting range

STD current (Isd) setting range

LTD time (TL) setting range

GFR current (Ig) setting range

PAL current (Ip) setting range

Ope

ratin

g tim

e (s

)

20001600125

.03

.02

.01

.5

.4

.3

.2

.1

.05

.04

10 100 1000

100

1000

50

40

30

20

10

4

5

3

2

1

5 50 500

60

200

300

400

500

20 200 5000

Page 45: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Tripping characteristics setting (3/3)

44

Actual operating characteristics are shown is following curve by %-A figure.

Characteristic curve

X0.8

X0.1

X3

X12

TL=100s

TP=50s

0.8s

0.3s

1536057603840230414401209.6921.6240160

500

400

300

200

60

1

2

3

5

4

10

20

30

40

50

100

.04

.05

.1

.2

.3

.4

.5

.02

.03

500

400

300

200

60

1

2

3

5

4

10

20

30

40

50

1000

100

.04

.05

.1

.2

.3

.4

.5

.02

.03

current (A)

oper

atio

n tim

e (s

)

Page 46: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Wiring diagram (According to EN50005)

45

Internal wiring diagram

See Table 1

Xa

TR!P

X

1500V

(Dielectric voltage)

2000V

(Dielectric voltage)

342

341 331 321 311

L3 L2 554 534 524 98344 332 334 322 324 312 314

L1 564 544 513 97

AL

TAL GFRorER

CL CL CL CL

PAL STD/!NST

LTD

Electronictrip relay

Main circuit Cell switches Electronic trip relay

Powersupply CT

Currentsensor

coil

Reset

only

ope

rate

30m

s

13 Auxiliary switch contact a

413 414

Auxiliary switch contact b

Charged signal a

Motor charging

Closing coil

Shunt trip

Under voltage trip

Earth leakage trip output (for SHT trip)

L1 L2 L3

Cell switch

Electronic relay unit control power supply

564 Temperature alarm contact

554 Pre-alarm indication contact

Trip indication contact

OCR alarm contact

For N-pole CT or external ZCT connection

Applicable power supply

(Table-1)

Voltage(V) Input terminal

Com

mon 100 – 120 L1 , L2

L1 , L2

L1 , L3200 – 240

100 – 12524 – 60

DC

AC

Terminal Symbols~

713 714

524 544

54

U1 U2

A1 A2

C1 C2

J1 J2

97 98

N1 N2

M1 M211 ~ 52

~

311 344~

The following wiring diagram shown accessories fully equipped.

Page 47: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

46

See P19

2000V

(Dielectric voltage)

OFF

OFF

ON

ONCharge

M1 N1 713

UVT SHT CC

J1 C1 A1

M2 N2 714 J2 C2 A2

U1 413 51 41 31

U2 414 52 42 32

21 11 53 43

22 12 54 44

33 23

34 24 14

M

AX AX AX AX AX AX AX AX AX AX

SB

C

SB

C

SB

C

SB

C

SB

C

13

See P35

SHT

Under voltage trip Electrical operation circuit Charged signal Auxiliary switches

M Motor

CC Closing coil

SHT Shunt trip device

UVT Under voltage trip coil

AL OCR alarm (30ms)

LTD Long-time-delay trip indication LAMP

STD/INST Short-time-delay or instantaneous trip indication LAMP

– – – Wiring by the user

Wiring completed by the factory

X Self-hold relay

TAL Temperature alarm indication LAMP

PAL Pre-alarm indication LAMP

GFR or ER Ground fault trip or earth leakage indication LAMP

Accessory Symbols

The Fig. below is the wiring diagram at fully equipped state. CL and SBC are accessories for draw-out type. On the draw-out type, the control circuit terminal block should be

moved to the left or right by 5mm, after cables connecting. When usin coil loads such as DC magnetic switch, etc. as operating

voltage in the peripheral circuits, install diodes, surge absorbers,etc. as a countermeasure against the surge (counter electromotiveforce) at the time of switching.

Because of pumping prevention is not performed, do not use AXbcontact for a cut-off of closing coil.

Page 48: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Outline dimensions (1/5)

47

Drawout type AE630-SS~AE1600-SS

Front view Side view

Rear view

Main circuit terminal dimensions

85 85 85 85 858585 8585

50

4P 3P4P 3P3P4P

Front terminalVertical terminalHorizontal terminal

Neutralpole

Neutralpole

Neutralpole

Operating panel center Operating panel center Operating panel center

Outlineof breaker

Outlineof breaker

Outlineof breaker

61

57

9253

15

132

145

15

50

117

100

50

66

9215

370

132

15

311

23

368

40

48

452

15

25

51

3534

0430

40

228

235(150)150

59 149

42.5

200

234(149)

366

15

172

Earth terminalM8 screw

4P3P

Neutral pole

Operating panelcenterUVT controller, etc

Lifting hook hole

Front face ofcontrol terminal M3.5 self-up screw

Inside of the panel(thickness1.6~3.2)

Panel

Fully drawoutposition

Test

Disconnected

Aperture fordrawout handle

Control terminals M3.5 self-up screw

4-f14

Horizontalterminal

Verticalterminal

Frontterminal

220

: Mounting pitch The numerals shown in parentheses are for 3 poles.

50

15

25

38

2-f13

50

15

25

38

2-f132-f13

38

15

25 50

Horizontal terminal Vertical terminal Front terminal

Connecting areaConnecting area Connecting area

Page 49: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

48

Drawout type AE2000-SS~AE3200-SS

Front view Side view

Rear view

Main circuit terminal dimensions

Earth terminalM8 screw

Neutral pole

Operating panelcenterUVT controller, etc

Lifting hook hole

Front face ofcontrol terminal M3.5 self-up screw

Inside of the panel

Panel

Fully drawoutposition

Test

Disconnected

Aperture fordrawout handle

Control terminalsM3.5 self-up screw

Horizontalterminal

Verticalterminal

Frontterminal

(thickness1.6~3.2)

324(194)23959

42.5 40

325(195)243

228

17215

366

430

340

35

51

25

15

452

48

40

368

23

311

132

370

92

61

T T

5337

0

132

92

57 T

125

125

182

67

83

25

20

Dimension of TType

AE2000,2500-SS

AE3200-SS

4P3P

4-f14200 220

TT : Mounting pitch

The numerals shown in parentheses are for 3 poles.

Front terminalVertical terminalHorizontal terminal

Neutral pole Neutral pole Neutral pole

Operating panel center Operating panel center Operating panel center

Outlineof breaker

Outlineof breaker

Insulationblock

130

23

130130

W

3P4P

130 130 130

T

130130130

23

W

23

4P 3P4P 3P

Horizontal terminal Vertical terminal Front terminal

Connecting areaConnecting area Connecting area

AE2000,2500-SS

AE3200-SS

Type

103

95

34

15

W

2525

4-f13

25

38

15

2525

5-f13

2525

125

25

4-f13

2525

15

38

W

Dimension of W

Page 50: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

49

Outline dimensions (2/5)

Drawout type AE4000-SSC (3P)

Only vertical connection is availableM3.5 self-up screw

L,R pole:T10 W150 4 piecesC pole :T10 W150 3 pieces

Aperture fordrawout handle

4-f14

151

125

125

6718

2 370

340

368

35

51

311

366

172

452

23220

40

48

15

25

430

15

324

200

23959

42.5

40325243

228 Connection bus bar

Operating panelcenterUVT controller, etc Control terminals

: Mounting pitch

Lifting hook hole

Front face ofcontrol terminal M3.5 self-up screw

Test

Disconnected

Earth terminalM8 screw

Inside of the panel(thickness1.6~3.2)

Panel

Fully drawoutposition

53

25

2525

5-f13

2525

125

Connecting area

Front view Side view

Rear view

Main circuit terminal dimensions

10

10

493

90

42.5

195195

70

10

10

Operating panel center

Outline of breaker

Insulation block

Page 51: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

50

Drawout type AE4000-SS~AE6300-SS

Earth terminalM8 screw

Neutral pole

Operating panelcenter

UVT controller, etcLifting hook hole

Front face ofcontrol terminal M3.5 self-up screw

Inside of the panel (thickness1.6~3.2)

Panel

Fully drawoutposition

Test

Disconnected

Aperture for drawout handle

Fixing bolts2-M12

Drawout handleradius 100

Control terminals M3.5 self-up screw

44

530

42.5

228

184

90

28 28588.5(458.5)373.5

610(480)395

345.5

4P3P

4-M12

40048

0

7534

0

48

368 123

23220

17240

51

35

311

420

182

125

125

117

15

366

Insulation block

M12 weld nut

Mounting angle

15

: Mounting pitch The numerals shown in parentheses are for 3 poles.

5-f13

125

2525

2525

53

25

Connecting area

Front view Side view

Rear view

Main circuit terminal dimensions

W

431.5

T25

196

561.5(431.5)

382

262 262

42.5

14

The mounting angle should beprepared by the customer.

Operating panel center

Outline of breaker

2-M12 for mounting

Mounting angle (SUS)Neutralpole

4P 3P

Type

105

100

Dimension of W

25

20

Dimension of T

AE6300-SS

AE4000,5000-SS

Page 52: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Outline dimensions (3/5)

51

Drawout type AE630-SH~AE3200-SH

Earth terminalM8 screw

Neutralpole

Operating panelcenterUVT controller, etc

Lifting hook hole

Front face ofcontrol terminal M3.5 self-up screw

Dimensions from inside of the panel

Panel

Fully drawoutposition

Test

Disconnected

Aperture fordrawout handle

Drawouthandleradius100

Control terminals M3.5 self-up screw

Fixing bolt2-M12

Horizontalterminal

Verticalterminal

Frontterminal

(thickness1.6~3.2)

Dimension of TType

42.5

350(220)265

228

33

243 325(195)

200

40

134

4-f14

T

430

340

25

15

35

51

370

132

T

92

23

61

202

398

396

220

40

48

452

341

15

83

6718

2

125

125

T57

9213

2 370

53

TT

AE3200-SH

AE630~2500-SH 20

25 : Mounting pitch

The numerals shown in parentheses are for 3 poles.

Front terminalVertical terminalHorizontal terminal

Neutral pole Neutral pole Neutral pole

Operating panel center Operating panel center Operating panel center

Outlineof breaker Outline

of breaker

Insulationblock

130

23

130130

W

4P 3P

23

W

130130130

3P4P

23

130 130 130

T

3P4P

Horizontal terminal Vertical terminal Front terminal

Connecting areaConnecting area Connecting area

Type

103

95

Dimension of W

W

38

15

2525

4-f13

25

125

2525

5-f13

2525

15

38

25

4-f13

2525

W

15

34

AE3200-SH

AE630~2500-SH

Front view Side view

Rear view

Main circuit terminal dimensions

Page 53: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

52

Fixed type AE630-SS/SH~AE3200-SS/SH

4-f14

268

227(142)142

255(170)

241(156)

228

156

17038

4-f14

317

268

232

38 260

246

228

331(201)

345(215)

4P3P

Neutral pole

Neutral pole

Control terminalM3.5 self-up screw Control terminal M3.5 self-up screw

Operating panelcenter Operating panel

centerUVT controller,etc

UVT controller,etc

EarthterminalM8 screw

EarthterminalM8 screw

4P3P

AE630~1600-SS AE2000~3200-SS AE630~3200-SH

AE2000~3200-SS

AE630~1600-SS

Type Dimension of T

15

20

: Mounting pitch The numerals shown in parentheses are for 3 poles.

144

132

722020

32

7

70

31Panel Panel

288

31

40

7

17

4-f13

2525

38

95

17

2-f13290

340

175

40

88

410

350

5

288

340

290

175

40

14488

410

350

5

T 7213

2

T

25

38

25 50

AE630~3200-SS AE630~3200-SH

Inside of the panel (thickness1.6~3.2)

EarthterminalM8 screw

EarthterminalM8 screw

Inside of the panel (thickness1.6~3.2)

Connectingarea

Connectingarea

AE2000~3200-SSAE630~ 3200-SH

AE630~ 1600-SS

85

2323

514(384)

959550

8585 130 130 130130 130 130

4P 3P3P4P

Operating panel center Operating panel center Operating panel center

Insulationblock

Neutralpole

NeutralpoleNeutral

pole

Outlineof breaker

Outlineof breaker

AE630~1600-SS

4P 3P

AE2000~3200-SS AE630~3200-SH

Side view Main circuit terminal dimensions

Front view

Rear view

Page 54: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Outline dimensions (4/5)

53

Fixed type AE4000-SSC (3P)

4-f14

317

268

232

38 260

246

228

331

345

Control terminal M3.5 self-up screw

Operating panelcenter

UVT controller,etc

EarthterminalM8 screw

: Mounting pitch

Only vertical connection is available

125

288

125

934

0

7

88 144

414

354

182

72.5

136290

31

40

175

25

53

125

25

5-f13

2525

25

Connection bus bar

Per 1 pole: T10 W150 3 pieces (All poles)

PanelEarthterminalM8 screw

Inside of the panel(thickness1.6~3.2)

Connectingarea

42.5

195 195

10

70

10

Operating panel center

Outline of breaker

Side view Main circuit terminal dimensions

Front view

Rear view

Page 55: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

54

Fixed type AE4000-SS~AE6300-SS

4-f14

3P 4P

581.5(451.5)

268

366.5

38 394

380.5

228

595.5(465.5)

609(479)

Control terminal M3.5 self-up screw

Operating panelcenter

UVT controller,etc

Earth terminalM8 screw

: Mounting pitch

125

57

288

125

934

0

7

88 144

414

354

182

72.510

136290

31

40

175

Bus bar

Panel Earth terminalM8 screw

Inside of the panel (thickness1.6~3.2)

25

53

125

25

5-f13

2525

25

Connecting area

Front view Side view

Rear view

Main circuit terminal dimensions

42.5

197 262 262

100

2020

Operating panel center

Outline of breaker

Neutral pole

3P4P

Page 56: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Outline dimensions (5/5)

55

Panel-cut, Drawout handle, Terminal adapter

f22

200 16

9

max 173

200

f12

7.7

405

345

235

295

381

271

247235

324

A

357

A

345

8-f7

245AE4000~6300-SS

179AE4000-SSC (FIX)

195

175

Dimension of AType

Operating panel center

Breakermounting frame

OutlinePanel-cut dimensions

Breaker

Operating panel center

Breaker mounting frame

Drawout Type

Fixed Type

53

D

25

34

15

D

25 25 25

C

T

37.5

50

100

15 15 15

2525

25

115

T

T

125

2525

2525

38

38

15

15

15

50

25

25

100

38

38

25

Mtg.holesf13

f13

f13

AE630~ 1600-SS

AE2000~3200-SSAE630~3200-SH

Con

nect

ing

area

Connecting area

Connecting area

25

25

20

20

20

15

15

15

Dimension of T

103

95

95

95

95

95

50

50

50258.5

145

145

258.5

Fixedtype Down side

Up side

Drawout type

Fixedtype

Drawout type

Fixedtype

Drawout type

Down side

Down side

Up side

Up side

AE3200-SH

AE630~2500-SH

Dimension of DDimension of C

145

258.5

145

145

145

AE3200-SS

AE2000,2500-SS

AE630~1600-SS

Type

25

20

Dimension of TType

AE2000,2500-SS AE630~2500-SH

AE3200-SS AE3200-SH

AE630~1600-SS AE2000~3200-SSAE630~3200-SH

42

225

45BA

C

Type

AE2000~3200-SSAE630~3200-SH

AE630~1600-SS

Operating panel center

3

310

180 225

225 23

23

01352204

3 135 135 0

CB

Dimensions

A

Numberof poles

(Side view) (Rear view)

Dimensions

4Panel

Neutralpole

Outline of breaker

Panel-cut dimensions Door frame panel-cut dimensions Drawout handle dimensions

Vertical terminal adapter Front terminal adapter

Panel-cut dimensions (Breaker rear side)

Page 57: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

56

Neutral CT (NCT), External ZCT

CW40-LM 5000~6300ACW40-LM 630~4000A

M

87

66

L

55

38

K

11

9

J

68

51CW40-LM 630~2000A

CW40-LM 2500~4000A 162 4 219 160 31 48 192 212

97 5.5 137 105 16.5 28 122 142

A B C D E F G H

C

102

40

79

4

4021

7

298

328

285

88

251

H

G

FE

M

K

L

J

D

BA

KL

Dimensions(mm)

Slit for M8 bolt

Terminals M5 screw Terminals M5 screw

KL

Slit for M10 bolt

K

B200

108

ZCT163

ZCT323

ZCT324

230

370

500 108

C

323 250

460 400

600 550

47

E

47

48

DBA

60

C

D

72

92

E

A

Slit for M8 bolt

Dimensions(mm)

Terminals M3.5 screw

External ZCT for transformer ground wire

Neutral CT (NCT)

External ZCT for load circuits

C

D

7.7

C

DG

ZT60A

ZT80A

ZT100A

140 60 73 150 46

160 80 82 169 48

185 100 93 190 50

A B C D E

40

30

ZT40A

ZT30A

85 43 92 81 40 100 50

25

H

50

70

G

90

15

F

30

46

E

66

62

D

82

29

3768

ZT15A

B

15

A

48

C

A

90

E

70

1230

100

AE 52

28

40H

3

B

F

2

B

Slit for M5 screwSlit for M5 screw

Dimensions(mm)Dimensions(mm)

Terminals M3.5 screwTerminals M3.5 screw

Page 58: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

57

Technical information (1/3)

For the terminal connections, use M12 bolts, washers and springwashers.In order to prevent increased contact resistance due to humidity,silver plating of the contact surface of the conductor which isconnected to the terminal of the breaker, is recommended. Alsoclean the contact surface, and securely connect them at a suitabletorque.

1Pre-cautions when making connections

Silver platedconductor

Terminal

15~23mm

25Standard Tightening Torque

Screw size

M12

Tightening torque (N • m)

40~50

Since fault current flowing through theconductors cause large electromagneticforces, the conductors should be securedfirmly, using the values in Table on the rightas a reference. Max busbar supportingdistance nearest to ACB is less than 200mm.

Electromagnetic force in N per 1m conductor(in the case of three phase short circuit)

Type (A)AE630-SS

AE1600-SS

AE2000-SS

AE3200-SSAE–SH

AE4000-SS

AE6300-SS

Conductor distance (mm)

30 (0.2)

Prospective fault currentkA (pf)

85

7500 4500 2300

42 (0.2) 14600 8900 4500

50 (0.2) 20800 12500 6300

65 (0.2) 35100 21200 10600

85 (0.2) 60200 36200 18100

100 (0.2) 50100 25100

130 (0.2) 84700 42400

130

AE4000-SSC

3400

6700

9400

15900

27200

195 262

(N)

When selecting conductors for connection to a SeriesAE breaker, ensure that they have a sufficient currentcapacity, refer to Table on the right.

Conductor Size (IEC-60947-1 ; 40°C Ambient Temp., Open air)

Rated current

Max. (A)

Connecting conductors (copper bus bar)

ArrangementWith long surface vertical

With long surface vertical

With long surface verticalWith long surface vertical

With long surface verticalWith long surface vertical

With long surface verticalWith long surface verticalWith long surface vertical

With long surface vertical

2 40 5

Quantity Conductor size(mm)

630

2 60 51000

2 80 51250

2 100 51600

3 100 52000

4 100 52500

3 100 103150(3200) 1

4 100 104000 2

4 150 105000

4 200 106300

1.

2.

The temperature rise of rated current 3200A conforms to the requirement of IEC 60947-1 for the connecting conductor size of a rated current of 3150A.In case of more then 3200A, conductor sizes are not given in IEC 60947-1.In case of AE-4000-SSC, refer to P49, 53.

AE–SSAE–SH

Bus bar

Fixing support

Max.200mm

Page 59: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

58

When a short-circuit current is interrupted, hot gasblows out discharged from the exhaust port of the arcextinguishing chamber, so provid a clearance as shownin the following table. On the fixed type, maintenance is possible with

following clearance.

2Line side insulation clearance

If under ordinary conditions the following normalworking conditions are all satisfied, the AE Series aircircuit breaker may be used unless otherwise specified.1. Ambient air temperature

A range of max. +40˚C to min. –5˚C is recommended.However, the average over 24 hours must notexceed +35˚C.

2. Altitude2,000m (6,600 feet) or less

3. Environmental conditionsThe air must be clean, and the relative humidity 85%or less at a max. of +40˚C. Do not use and store inatmospheres with sulfide gas, ammonia gas etc.(H2S q 0.01ppm SO2 q 0.1ppm NH3 q a few ppm.)

4. Installation conditionsWhen installing the AE Series air circuit breaker,refer to the installation instructions in the catalogueand instruction manual.

5. Strage temperatureA range of max. +60˚C to min. –20˚C is recommendedto store. However, the average over 24 hours must notexceed +35˚C.

6. ReplacementApprox. 15 years.Please refer to the instruction manual.

3Service conditions

Dimensions

Type

AE630-SS

AE3200-SS

AE4000-SSC

AE4000-SS

AE6300-SS

AE-SH

Applicable voltage AC600V or less AC660V,690V AC690V or less

Fix type

Drowout type

A 0(Note 1) 100(Note 1) 200(Note 1)

B 50(Note 3) 50(Note 3) 50(Note 3)

C 162 162 –

D 50(Note 2) 50(Note 2) 200

A 0 100 200(Note 1)

B 50(Note 3) 50(Note 3) 50(Note 3)

C 240 240 –

D 50(Note 2) 50(Note 2) 200

300mm or more clearance is necessary to inspect the arc-extinguishing chamber and contacts.The wiring space reguired for the control terminal block.In case dimension B becomes larger when the UVT controller, the mechanical interlock, door interlock, etc, are installed.

Note 1 :

Note 2 :

Note 3 :

(mm)

A

BB

Sideplate

CAD

Mountingsurface

Electrical equipment, appliances and screen

In the case of special service condition, modified aircircuit breakers are available. Please specify whenordering. Service life may be shorter depend on serviceconditions.1. Special environmental conditions

If it is used at high temperature and/or high humidity,the insulation durability and other electrical/mechanicalfeatures may deteriorate. Therefore, the breakershould be specially treated. Moisture fungus treatmentwith increased corrosion-resistance is recommended.Since some parts may pose problems due tocorrosion in the environments where corrosive gasresults from the corrosion, the increased Extra-corrosion proof specifications is recommended.

2. Special ambient temperatureIf the ambient temperature exceeds +40˚C, theuninterrupted current rating will be reduced. Sincethe reduction value is different depending on theapplicable standard, refer to P60.

3. Special altitudeIf it is used at the 2,000m or higher the heat radiationrate is reduced decreasing the operating voltagerating, continuous current capacity and breakingcapacity. Moreover the durability of the insulation isalso decreased owing to the atmospheric pressure.Apply for further detail.

1 Normal service condition 2 Special service conditions

Page 60: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Technical information (2/3)

59

4Internal resistance, reactance and power consumption (per pole)

Type Connection Internal resistance (mΩ)

Reactance(mΩ)

Power consumption(W)

AE630-SSFixed type 0.028 0.059 11

Drawout type 0.042 0.089 17

AE630-SHFixed type 0.020 0.047 8

Drawout type 0.030 0.071 12

AE1000-SSFixed type 0.026 0.060 26

Drawout type 0.040 0.091 40

AE1000-SHFixed type 0.018 0.047 18

Drawout type 0.028 0.071 28

AE1250-SSFixed type 0.024 0.060 38

Drawout type 0.038 0.091 60

AE1250-SHFixed type 0.016 0.047 25

Drawout type 0.026 0.071 41

AE1600-SSFixed type 0.016 0.063 41

Drawout type 0.030 0.095 77

AE1600-SHFixed type 0.014 0.047 36

Drawout type 0.024 0.071 61

AE2000-SSFixed type 0.010 0.047 40

Drawout type 0.020 0.071 80

AE2000-SHFixed type 0.012 0.047 48

Drawout type 0.022 0.071 88

AE2500-SSFixed type 0.008 0.047 50

Drawout type 0.018 0.071 113

AE2500-SHFixed type 0.010 0.047 63

Drawout type 0.020 0.071 125

AE3200-SSFixed type 0.008 0.048 72

Drawout type 0.014 0.072 143

AE4000-SSCFixed type 0.008 0.048 128

Drawout type 0.014 0.072 224

AE4000-SSFixed type 0.010 0.038 160

Drawout type 0.013 0.062 210

AE5000-SSFixed type 0.009 0.038 225

Drawout type

AE6300-SSFixed type

0.011 0.062 275

Drawout type

0.008 0.038 318

0.0085 0.062 340

The above values are applicable for one pole.

AE3200-SHFixed type 0.009 0.048 92

Drawout type 0.016 0.072 164

Page 61: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

60

5Deratings by ambient temperature

Standard

JISC8372(Standard : 40°C)

IEC60947-2BS

(Standard : 40°C)

NK(Standard : 45°C)

LR,AB,GLDNV,BV

(Standard : 45°C)

Ambienttemperature

40°C

45°C

50°C

55°C

60°C

40°C

45°C

50°C

55°C

60°C

45°C

50°C

55°C

60°C

45°C

50°C

55°C

60°C

AE630-SSAE630-SH

630

630

630

630

630

630

630

630

630

630

630

630

630

630

630

630

630

630

AE1000-SSAE1000-SH

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

AE1250-SSAE1250-SH

1250

1250

1250

1200(1250)

1150(1250)

1250

1250

1250

1250

1200(1250)

1250

1250

1200(1250)

1150(1250)

1250

1250

1250

1200

AE1600-SSAE1600-SH

1600

1600

1500(1600)

1450(1600)

1400(1600)

1600

1600

1600

1550(1600)

1500(1600)

1600

1500(1600)

1450(1600)

1400(1600)

1600

1600

1550(1600)

1500(1600)

AE2000-SSAE2000-SH

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

AE2500-SSAE2500-SH

2500

2500

2500

2350

2250

2500

2500

2500

2450

2350

2500

2500

2350

2250

2500

2500

2450

2350

AE3200-SSAE3200-SH

3200

3200

3000

2900

2800

3200

3200

3200

3000

2900

3200

3000

2900

2800

3200

3200

3050

2900

AE4000-SS

4000

4000

4000

4000

4000

4000

4000

4000

3900

3750

4000

4000

4000

4000

4000

4000

3900

3750

AE5000-SS

5000

5000

5000

4900

4700

5000

5000

5000

5000

4750

5000

5000

4800

4600

5000

5000

5000

4750

AE6300-SS

6000

5800

5600

5450

5250

6300

6300

5750

5500

5200

5700

5500

5300

5100

6300

5750

5500

5200

Note : The figures in ( ) in the above Table indicate reduced current values exclusive to AE-SH series.

(A)

AE4000-SSC

3600

3500

3350

3200

3050

4000

3800

3650

3500

3300

3500

3350

3200

3050

Page 62: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Technical information (3/3)

61

Selective interrupting combinations tableAE-SS Series air circuit breakers provide easy selective co-ordination with branch circuit breakers.For selective co-ordinations, refer to the following table.

Main circuit breaker AE-SSBranchcircuit breaker

Unit breaking capacity

NF

-S •

MB

NF

-C

NF30-SPMB30-SPMB50-CPNF50-SPNF60-SPMB50-SPNF50-HPNF60-HPNF50-HRPNF100-SPNF100-SEPMB100-SPNF100-HPNF250-SPNF250-SEPMB250-SPNF250-HPNF400-SPNF400-SEPNF400-HEPNF400-REPNF630-SPNF630-SEPNF630-HEPNF630-REPNF800-SEPNF800-HEPNF800-REPNF50-CPNF60-CPNF100-CPNF250-CPNF400-CPNF630-CPNF800-CEPNF100-RPNF100-UPNF250-RPNF250-UPNF400-UEPNF630-UEPNF800-UEP

The values in the table represent the max. rated current for both Series AE-SS air circuit breakers and branch breakers, and the selective co-ordination applies when the AE-SS series air circuit breakers instantaneous pick up is set to maximum.

The numerals shown in parentheses are for AE-SS with MCR. (When set MCR).

Please apply in case of AE-SH.

5

10

25

85

50

100

50

1008585100

5

253050

1258585

5050

10012585100125

AE630-SS65

5

9(10)

9(25)

9(65)

9(50)

9(65)

9(50)

9(65)–

9(65)

5

9(25)9(30)

9(65)9(65)

––

––

–––––

AE1000-SS65

5

10

25

50(65)

45(50)

50(65)

20(50)

25(65)–

15(65)

5

15(25)15(30)15(50)

15(65)15(65)

–15(65)

––

15(65)15(65)

–––

AE1250-SS65

5

10

25

65

50

65

22(50)

40(65)20(65)

5

18(25)18(30)20(50)

20(65)20(65)

20(65)–

18(65)

–18(50)

18(65)18(65)18(65)18(65)18(65)

AE1600-SS65

5

10

25

65

50

65

42(50)

6527(65)

5

24(25)24(30)27(50)

27(65)27(65)

27(65)24(65)24(65)

24(50)24(50)

24(65)24(65)24(65)24(65)24(65)

AE2000-SS85

5

10

25

85

50

85

50

8542(65)

5

2530

42(50)

42(65)42(65)

42(65)30(65)30(65)

30(50)30(50)

30(65)30(65)30(65)30(65)30(65)

AE2500-SS85

5

10

25

85

50

85

50

8570

5

253050

7070

7040(65)40(65)

40(50)40(50)

40(65)40(65)40(65)40(65)40(65)

AE3200-SS85

5

10

25

85

50

85

50

8585

8585

5

253050

8560(65)60(65)

5050

60(65)60(65)60(65)60(65)60(65)

AE4000-SSC85

5

10

25

85

50

85

50

85858585

5

253050

858585

5050

8585858585

AE5000-SS130

5

10

25

85

50

100

50

1008585

100

5

253050

1258585

5050

8585858585

5050

AE6300-SS130

5

10

25

85

50

100

50

1008585

1001258585

5

253050

8585858585

AE4000-SS130

5

10

25

85

50

100

50

1008585

100

5

253050

1258585

5050

8585858585

NF

-U

8510012585100125

125200125200200200200

6565

9(65)9(65)9(65)

––

65656565

15(65)15(65)

65656565

18(65)18(65)18(65)

65656565

29(65)24(65)24(65)

85858585

48(65)30(65)30(65)

8585858585

37(65)37(65)

85858585856868

85858585858585

125130125130130120120

125130125130130120120

125130125130130120120

AC220V sym kA

Page 63: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

62

Main circuit breaker AE-SSBranchcircuit breaker

Unit breaking capacity

NF

-S •

MB

NF

-C

NF30-SPMB30-SPMB50-CPNF50-SPNF60-SPMB50-SPNF50-HPNF60-HPNF50-HRPNF100-SPNF100-SEPMB100-SPNF100-HPNF250-SPNF250-SEPMB250-SPNF250-HPNF400-SPNF400-SEPNF400-HEPNF400-REPNF630-SPNF630-SEPNF630-HEPNF630-REPNF800-SEPNF800-HEPNF800-REPNF50-CPNF60-CPNF100-CPNF250-CPNF400-CPNF630-CPNF800-CEPNF100-RPNF100-UPNF250-RPNF250-UPNF400-UEPNF630-UEPNF800-UEP

The values in the table represent the max. rated current for both Series AE-SS air circuit breakers and branch breakers, and the selective co-ordination applies when the AE-SS series air circuit breakers instantaneous pick up is set to maximum.

The numerals shown in parentheses are for AE-SS with MCR. (When set MCR).

Please apply in case of AE-SH.

2.5

7.5

10

30

25

50

25

50505065

2.5

101525

1255050

3535

651255065125

AE630-SS65

2.5

7.5

9(10)

9(30)

7(25)

9(50)

7(25)

7(50)–

9(50)

2.5

9(10)9(15)

9(65)9(65)

––

––

–––––

AE1000-SS65

2.5

7.5

10

30

20(25)

30(50)

14(25)

15(50)–

15(50)

2.5

1015

15(25)

15(65)15(65)

–15(50)

––

15(65)15(65)

–––

AE1250-SS65

2.5

7.5

10

30

25

50

19(25)

25(50)18(50)

2.5

1015

18(25)

18(65)18(50)

18(65)–

18(50)

–18(35)

18(65)18(65)18(50)18(65)18(65)

AE1600-SS65

2.5

7.5

10

30

25

50

25

42(50)24(50)

2.5

1015

24(25)

24(65)24(50)

24(65)24(50)24(50)

24(35)24(35)

24(65)24(65)24(50)24(65)24(65)

AE2000-SS85

2.5

7.5

10

30

25

50

25

5033(50)

2.5

101525

33(65)33(50)

33(65)33(50)30(50)

30(35)30(35)

30(65)30(65)30(50)30(65)30(65)

AE2500-SS85

2.5

7.5

10

30

25

50

25

5045(50)

2.5

101525

45(65)45(50)

45(65)45(50)40(50)

3535

40(65)40(65)40(50)40(65)40(65)

AE3200-SS85

2.5

7.5

10

30

25

50

25

5050

6550

2.5

101525

805050

3535

60(65)60(65)60(50)60(65)60(65)

AE4000-SSC85

2.5

7.5

10

30

25

50

25

50505065

2.5

101525

855050

3535

6585506585

AE5000-SS130

2.5

7.5

10

30

25

50

25

50505065

2.5

101525

1105050

3535

6585506585

3535

AE6300-SS130

2.5

7.5

10

30

25

50

25

50505065

1105050

2.5

101525

6585506585

AE4000-SS130

2.5

7.5

10

30

25

50

25

50505065

2.5

101525

1105050

3535

6585506585

NF

-U

125200125200200200200

35(65)50(65)9(65)9(65)9(65)

––

6565

50(65)65

15(65)15(65)

65656565

18(65)18(65)18(65)

65656565

29(65)24(65)24(65)

85858585

48(65)30(65)30(65)

8585858585

37(65)37(65)

85858585856868

85858585858585

125130125130130120120

125130125130130120120

125130125130130120120

AC460V sym kA

Page 64: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Neutral CT(NCT)External ZCT(ZCT) Type Refer P37

Y-2000 field test device AC100 – 240VY-160 field test device AC100 – 120V

AC200 – 240V

;

SST T…Trip indicationSPT P…Pre-alarmSPGTSPET

BARE Relay not require Note7

Electronic trip relay type

Blank LTD+STD+INST

C LTD+STD+INST/MCR

Tripping characteristics Note5

A OCR alarm(30ms 1 pulse)T Temperature alarm(LED & 1a contact)

Electronic trip relay accessories

0 Not required(Only for S type)1 AC100 – 120/200 – 240V2 DC100 – 125V4 DC24 – 60V

Control supply

Condenser trip device(COT)

AC100 – 110VAC200 – 220V

AC • DC100 – 125VAC • DC200 – 250VDC24VDC48V

Closing coil(CC)

Shunt trip device (SHT)

AC • DC100 – 250VDC24 – 48V

Under voltage trip device AC100 – 120/200 – 240/380 – 460V

DC24VDC48VDC100 – 110VDC120 – 125V

Instantaneous(UVT-SSB)0.5 s Time-delay type (UVT-05SSB)

3 s Time-delay type (UVT-30SSB)

AC • DC100 – 250VAC380 – 500VDC24 – 48V

Data

Test report

Specifications

P22

Remark

Production date

Customer(name) Order No. Number of units units

Number of poles

Rated current A

Applicablestandard

3P

IEC 60947-2 JIS C8372

Ambienttemperature 40°C

Cell switch CL- (Maximum: 4 pcs.)Shorting-B contact(SBC)Lifting hooks(HP)Safety shutter(SST)

Shutter lock(SST-LOCK)Mis-insertion preventer(MIP)Test jumper(TJ)

Vertical terminal adapter(VTA)Front terminal adapter(FTA)

Others °C Note2

Others

4P

C T D

Connection P17 Fixed type(FIX)

Main circuitterminal

Only for Horizontalterminals

Drawout type(DR)

Horizontal terminals(standard)Vertical terminals(DR-VT)Front terminals(DR-FT)

Drawout type accessories P23~24

P21~22 Push button cover(BC-L)Counter(CNT)Cylinder lock(CYL)Door interlock(DI) Note8

Terminal cover(TTC)Door frame(DF)Dust cover(DUC)Interphase barrier(BA)Mechanical interlock(MI)

P58

for 2unitsfor 3units

Type P13~16 AE -SS AE -SH

Electronic triprelay

P18~20 Auxiliary switchStandard(AX)High capacity(HAX)

Motor charging(MD)

A B Max.5A5B

"A"and"B"should be same.

P25~36

Specialenvironments

Moisture-fungustreatment Extra-corrosion proof specification

Electricalaccessories

Machineaccessories

S…Standard

Can be connected to the Horizontal terminals

Note7

Note:When specifying MD, be sureto order the closing coil(CC)andshunt trip device(SHT)for remoteoperation.

G…Ground fault protection Note5

E…Earth leakage protection Note6

Note1. Not available for AE4000-SSC.Note2. There is case to derate by ambient temperature.Note3. Not available for AE4000~6300-SS.Note4. The terminal for AE4000-SSC, AE4000~6300-SS shall be vertical terminal. Note5. Not available for AE-SS series with maximum rated current (In max) coming to 315A or 500A, nor AE630-SH. Neutral CT is needed for Ground fault protection when a 3 pole breaker is used on a 3 phase 4 wires system.Note6. In case of Earth leakage alarm, It need external ZCT. In case of Earth leakage tripping, It also need SHT.Note7. Not available for AE-SH. Note8. If install together with MI, Please ask us.

Note1

Note4

Note3

Note4units

Note1,3

Example

63

Ordering information for Mitsubishi AE-SS series air circuit breaker (General use ……S Type)

Page 65: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Neutral CT(NCT)External ZCT(ZCT) Type Refer P37

Y-2000 field test device AC100 – 240VY-160 field test device AC100 – 120V

AC200 – 240V

;

SST T…Trip indicationSPT P…Pre-alarmSPGTSPET

BARE Relay not require Note7

Electronic trip relay type

Blank LTD+STD+INST

C LTD+STD+INST/MCR

Tripping characteristics Note5

A OCR alarm(30ms 1 pulse)T Temperature alarm(LED & 1a contact)

Electronic trip relay accessories

0 Not required(Only for S type)1 AC100 – 120/200 – 240V2 DC100 – 125V4 DC24 – 60V

Control supply

Condenser trip device(COT)

AC100 – 110VAC200 – 220V

AC • DC100 – 125VAC • DC200 – 250VDC24VDC48V

Closing coil(CC)

Shunt trip device (SHT)

AC • DC100 – 250VDC24 – 48V

Under voltage trip device AC100 – 120/200 – 240/380 – 460V

DC24VDC48VDC100 – 110VDC120 – 125V

Instantaneous(UVT-SSB)0.5 s Time-delay type (UVT-05SSB)

3 s Time-delay type (UVT-30SSB)

AC • DC100 – 250VAC380 – 500VDC24 – 48V

Data

Test report

Specifications

P22

Remark

Production date

Customer(name) Order No. Number of units units

Number of poles

Rated current A

Applicablestandard

3P

IEC 60947-2 JIS C8372

Ambienttemperature 40°C

Cell switch CL- (Maximum: 4 pcs.)Shorting-B contact(SBC)Lifting hooks(HP)Safety shutter(SST)

Shutter lock(SST-LOCK)Mis-insertion preventer(MIP)Test jumper(TJ)

Vertical terminal adapter(VTA)Front terminal adapter(FTA)

Others °C Note2

Others

4P

C T D

Connection P17 Fixed type(FIX)

Main circuitterminal

Horizontalterminals

Drawout type(DR)

Horizontal terminals(standard)Vertical terminals(DR-VT)Front terminals(DR-FT)

Drawout type accessories P23~24

P21~22 Push button cover(BC-L)Counter(CNT)Cylinder lock(CYL)Door interlock(DI) Note8

Terminal cover(TTC)Door frame(DF)Dust cover(DUC)Interphase barrier(BA)Mechanical interlock(MI)

P58

for 2unitsfor 3units

Type P13~16 AE -SS AE -SH

Electronic triprelay

P18~20 Auxiliary switchStandard(AX)High capacity(HAX)

Motor charging(MD)

A B Max.5A5B

"A"and"B"should be same.

P25~36

Specialenvironments

Moisture-fungustreatment Extra-corrosion proof specification

Electricalaccessories

Machineaccessories

S…Standard

Can be connected to the Horizontal terminals

Note7

Note:When specifying MD, be sureto order the closing coil(CC)andshunt trip device(SHT)for remoteoperation.

G…Ground fault protection Note5

E…Earth leakage protection Note6

Note1. Not available for AE4000-SSC.Note2. There is case to derate by ambient temperature.Note3. Not available for AE4000~6300-SS.Note4. The terminal for AE4000-SSC, AE4000~6300-SS shall be vertical terminal.Note5. Not available for AE-SS series with maximum rated current (In max) coming to 315A or 500A, nor AE630-SH. Neutral CT is needed for Ground fault protection when a 3 pole breaker is used on a 3 phase 4 wires system.Note6. In case of Earth leakage alarm, It need external ZCT. In case of Earth leakage tripping, It also need SHT.Note7. Not available for AE-SH. Note8. If install together with MI, Please ask us.

Note1

Note4

Note3

Note4units

Note1,3

64

Ordering information for Mitsubishi AE-SS series air circuit breaker (General use ……S Type)

Page 66: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

65

Condenser trip device(COT)

AC100 – 110VAC200 – 220V

AC • DC100 – 125VAC • DC200 – 250VDC24VDC48V

Closing coil(CC)

Shunt trip device (SHT)

AC • DC100 – 250VDC24 – 48V

Under voltage trip device AC100 – 120/200 – 240/380 – 460V

DC24VDC48VDC100 – 110VDC120 – 125V

Instantaneous(UVT-SSB)0.5 s Time-delay type (UVT-05SSB)

3 s Time-delay type (UVT-30SSB)

AC • DC100 – 250VAC380 – 500VDC24 – 48V

P22

Remark

Production date

Customer(name) Order No. Number of units units

Number of poles

Rated current A

Applicablestandard

3P

LR AB

Ambienttemperature 45°C

Cell switch CL- (Maximum: 4 pcs.)Shorting-B contact(SBC)Lifting hooks(HP)Safety shutter(SST)

Shutter lock(SST-LOCK)Mis-insertion preventer(MIP)Test jumper(TJ)

Vertical terminal adapter(VTA)Front terminal adapter(FTA)

Others °C Note3

GL BVDNV NKOthersIEC 60947-2

4P

C T D

Connection P17 Fixed type(FIX)

Main circuitterminal

Only for Horizontalterminals

Drawout type(DR)

Horizontal terminals(standard)Vertical terminals(DR-VT)Front terminals(DR-FT)

Drawout type accessories P2324

Type P13~16 AE -SS AE -SH

P18~20 Auxiliary switchStandard(AX)High capacity(HAX)

Motor charging(MD)

A B Max.5A5B

"A"and"B"should be same.

Electricalaccessories

Y-2000 field test device AC100 – 240V

Neutral CT(NCT)

; A OCR alarm(30ms 1 pulse)T Temperature alarm(LED & 1a contact)

Electronic trip relay accessories

0 Not required(Only for M type)1 AC100 – 120/200 – 240V2 DC100 – 125V4 DC24 – 60V

Control supplyM M…StandardMT T…Trip indicationMPT P…Pre-alarmMPGT G…Ground fault protection Note6

Electronic trip relay typeSpecify the tripping characteristics Refer to P28, 46, 47.

LTD CurrentLTD TimeSTD CurrentSTD TimeINST CurrentPAL CurrentPAL TimeGFR CurrentGFR Time

% of Rated Currents at 120% of LTD Current% of Rated Currents at 150% of STD Current% of Rated Current% of LTD Current% of LTD Time% of Rated Current MAX.s at 150% of GFR Current

Electronic triprelay

P25~36

Note1. Not available for 4 pole breaker with LR, AB, GL, DNV, BV, NK standard.Note2. Not available for AE4000-SSC.Note3. There is case to derate by ambient temperature.Note4. Not available for AE4000~6300-SS.Note5. The terminal for AE4000-SSC, AE4000~6300-SS shall be vertical terminal.Note6. Not available for AE-SS series with maximum rated current (In max) coming to 315A or 500A, nor AE630-SH. Neutral CT is needed for Ground fault protection when a 3 pole breaker is used on a 3 phase 4 wires system. Note7. If install together with MI, Please ask us.

Can be connected to the Horizontal terminals

50

Note:When specifying MD, be sureto order the closing coil(CC)andshunt trip device(SHT)for remoteoperation.

Note1, Note2

Note5 Note5

Note4

units

Data

Test report

Specifications

P21~22 Push button cover(BC-L)Counter(CNT)Cylinder lock(CYL)Door interlock(DI) Note7

Terminal cover(TTC)Door frame(DF)Dust cover(DUC)Interphase barrier(BA)Mechanical interlock(MI)

P58

for 2unitsfor 3units

Specialenvironments

Moisture-fungustreatment Extra-corrosion proof specification

Machineaccessories

Note4

Note4

Ordering information for Mitsubishi AE-SS series air circuit breaker (Generator protection use ……M Type)

Page 67: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Service networkCountry / Region

U.K.

Ireland

Germany

Italy

Spain

Sweden

Norway

Denmark

Greece

The Netherlands

Switzerland

Belgium

Poland

Turkey

Slovania

South Africa

Lebanon

Saudi Arabia

Egypt

Kuwait

China

Hong Kong

Taiwan

Korea

Singapore

Indonesia

Philippines

Thailand

Pakistan

Vietnam

Lao PDR

Myanmer

Nepal

Australia

New Zealand

Colombia

Chile

Uruguay

Peru

Venezuela

Company

Mitsubishi Electric Europe B.V. UK-Branch.

Mitsubishi Electric Europe B.V. Irish Branch.

Mitsubishi Electric Europe B.V. German Branch.

Carpaneto & C. S.P.A

Mitsubishi Electric Europe B.V. Spanish Branch.

Euro Energy Components AB

SCANELEC

Louis Poulsen CO. A/S

Antonios Drepanias. S.A.

R+H Technology BV.

Trielec A G

Emac S.A.

MPL Technology Sp zo.o.

HEDEF

INEA

M.S.A.MANUFACTURING(PTY)LTD.

COMPTOIR D'ELECTRICITEGENERALE INTERNATIONAL

CENTER OF ELECTRICAL GOODS

CAIRO ELECTRICAL GROUP

SALEM M AL-NISF ELECTRICAL CO.W.L.L.

SHANGHAI SETSUYO TRADING CO., LTD.

RYODEN INTERNATIONAL LTD.

Ryoden international Ltd.

Setsuyo Enterprise Co., Ltd.

HAN NEUNG TECHNO Co., Ltd.

MITSUBISHI ELECTRIC ASIA PTE LTD.

P.T.SAHABAT INDONESIA.

EDISON ELECTRIC INTEGRATED, INC.

UNITED TRADING & IMPORT CO. LTD.

Prince Electric Co.

Sa Giang Techno Co., Ltd.

SOCIETE LAO IMPORT-EXPORT

PEACE MYANMAR ELECTRIC CO., LTD.

Watt & Volt House Co., Ltd.

Mitsubishi Electric Australia Pty. Ltd

Melco Sales (N.Z.) Ltd.

Proelectrico Representaciones S.A.

RHONA S.A.

Fierro Vignoli S.A.

I.T.E.

ADESCO C.A.

Address

Travellers Lane, Hatfield, Herts, AL10 8xB, U.K.

Westgate Business Park, Ballymount, Dublin 24, Ireland.

Gothaer Strasse 8, 40880 Ratingen, Germany.

10090 CASCINE VICA-RIVOLI (TO)Via Ferrero, 10-Ang. Pavia 6 Italy.Polingono Industrial "Can Magi", Calle Joan Buscalla 2-4, Apartado de Correos 420,08190 Sant Cugat del Valles, Barcelona, Spain.

Energigatan 15 Box 10161, S-434 22 Kungsbacka, Sweden

Leivikasen 43B, P.O. box 55, 5074 Godvik, Norway

Geminivej 32, DK-2670 Greve, Denmark.

52, Arkadias

STR.GR 121 32. Peristeri Athens Greece.

3361 HJ Sliedrecht Industrieweg 30. Netherland.

Mühlentalstrasse 136, 8201 Schaffhausen, Switzerland

1702 Groot-Bijgaarden Industrialaan 1, Belgium.

30011 Krakow UI. Wroclawska 53 Poland.

Barboros Bulv. iba Bloklari Gazi Umur P. So Balmumcu-Istanbul Turkey.

61230 Domzale Ljubljanska 80 Slovenia.

Bramley 2018, Johannesburg, South Africa.

Cebaco Center-Block A. Autostrade Dora, P.O. BOX: 90-1314 Beirut-Lebanon.

Al-Nabhaniya Street-4Th Crossing, Al-Hassa Road, P.O. BOX: 15955, Riyadh 11454,Saudi Arabia.9 Rostoum Street Garden City, APT. 5,P.O. BOX: 165-11516, Cairo-Egypt.

P.O. Box 4784. Safat. 13048 Kuwait.

Building of Innovation Center, Room No. 406A, 680 Guiping Road Shanghai, P.R.China

(Shanghai) 3F, Block 5, 103Cao Bao Road, Shanghai, China

10/F Manulife Tower 169 Electric Road North Point. Hong Kong.

6F, NO. 105 Wu-Kung 3rd rd., Wu-Ku Hsiang,

Taipei Hsien Taiwan

2 Fl. Dong Seo Game Channel Bldg ., 1F 660-11 Deungchon-Dong, Kanguseo-Ku, Seoul, 157-030 Korea

307 Alexandra Road #05-01/02 MitsubishiElectric Building Singapore 159943

JL Muara Karang Selatan Blok A/Utara No.1 kav. NO.11 P.O. Box 5045/Jakarta/11050. Jakarta Indonesia.

24th Fl. Galleria Corporate Center Edsa Cr, Ortigas Ave. Quezon City, Metro Manila. Philippines.

77/12 Bumrungmuang Road, Klong Mahanak, Pomprab Bangkok 10100.

16 Brandreth Road Lahore 54000. Pakistan.

207/4 Nguyen Van Thu St., Dist 1, Ho Chi Minh City, Vietnam

43-47 Lane Xang Road P.O. BOX 2789 VTVientiane Lao PDR.

NO. 216, Bo Aung Gyaw Street,Botataung 11161, Yangon, Myanmar.

KHA 2-65, Volt House Dilli Bazar Post Box: 2108,kathmandu, Nepal

348 Victoria Road, Rydalmere, N.S.W. 2116, Australia

1 Parliament Street Lower Hutt. New Zealand.

Cra 53 No 29C-73 U.I.C.- Medellin. COLOMBIA.

Vte. Agua Santa 4211 Casilla 30-D (P.O. Box) Viña Del Mar. Chile

P.O. box 20022/Suc Upae, Montevideo. Uruguay.

Ingenieros s.a. Paseo de la Republica 3573 Lima 27. Peru.

Lle 8, Calpon Elinsu,La Urbina-EDO, Miranda P.O.BOX 78034 Caracas 1074A., Venezuela

Telephone

44-1707-276-100

353-1-4505007

49-2102-4860

39-11-9590111

34-93-565-3131

46-300-518-00

47-55-506000

45-43-95-95-95

30(1)5781599, 30(1)5781699

31-104871251

41-52-6258425

32-2-4810211

48-12-322885

90-212-2754876

386-61-718000

27-11-444-8080

961-1-240430

966-1-4770149

20-2-7961337

965-484-5660

021-6485-6611

021-6475-3228

28878870

02-2298-8889

017-255-0174

65-473-2308

021-6621780

02-643-8691

223-4220-3

042-7654342

848-821-6453

21-215043, 21-215110

951-295426

977-1-411330

612-9684, 7586

644-569-7350

574-235-00-28

(32)-611896

598-2-92-08-08

(1) 221-2710

58-2-241-7634

Page 68: Info_mitsubishi Lv Acb_ae-ss and Ae-sh

Catalogue NO. Y-0446-M 0010(ROD) Printed in JapanNew publication, effective Sept. 2000

Specifications subject to change without notice.

Safety Tips : Be sure to read the instruction manual fully before using this product.