info_mitsubishi lv acb_ae-ss and ae-sh
TRANSCRIPT
Mitsubishi Low Voltage Air Circuit BreakerAE-SS AE-SH
ADVANCED AND EVER ADVANCING
00BISO 9001
NATIONALACCREDITATION
OF CERTIFICATIONBODIES
Mitsubishi Electric Corporation's Fukuyama Works, which produces these products, is certified as meeting the ISO 14001 environmental management system standard.
With the highly advanced informationtechnologies, dependability as well as safetyand ease of handling of the electrical powersupply are ever-growing requirements. Therecent introduction of systemized and intelligentbuildings, upgrading, and space-saving, andsevere safety standard of power distribution hasbecome a major subject within the electricalpower supply industry. To cope with all thesecircumstances, Mitsubishi now presents theSuper AE series Low Voltage AirCircuit Breakers.
1
FeaturesMain unit features ...........................................3~4Electronic trip relay features............................5~8
External view andInternal construction ..................................9~10
Product introduction ...........................11~12
Product specificationSpecification<IEC60947-2 Ics/Icu>.............13~14Specification<JIS C8372, Shipping standard> ....................15~16
Connecting methods ................................17
Charging methods......................................18
AccessoriesFor breaker unit ...........................................19~22For drawout frame .......................................23~24
Electronic trip relaySpecification table .......................................25~26General use (S type) ...................................27~28Generator protection use (M type) ..............29~30Special use (B type) ....................................31~32Electronic trip relay accessories..................33~35Circuit diagram of the electronic trip relay .........36
Operating CharacteristicsGeneral use (S type) .........................................37Generator protection use(M type) .....................38Special use (B-C0 type) ....................................39
Tripping characteristics settingSetting procedure..............................................40How to adjust the trip Relay ........................41~44
Wiring Diagram .....................................45~46
Outline DimensionsDraw-out type..............................................47~51Fixed type....................................................52~54Panel cut, drawout handle, terminal adapter.....55Neutral CT, External ZCT ..................................56
Technical information .........................57~62
Ordering informationGeneral use (Example) .....................................63General use (S type) .........................................64Generator protection use (M type) ....................65
Contents
2
Main unit features
3
Easier Operation
Plenty Type Composition The addition of 4000A, 5000A and 6300A frame to the universal series makes applicable
for a wide range of types from 630A to 6300A. The addition of high breaking capacity (AE-SH) series (630A-3200A frame) has enabled
the design of economic sequences.
Expanded selective interruption range With the increased short-time current rating, the selective interruption range can be
expanded with the use of the electronic trip relays with MCR function.
Full moulding Since the breaker is fully insulated with mouldings, it is safe to use for a wide range of
applications.
Long service life 10,000 mechanical open/close operations for all types. (Except for AE4000-SS~AE6300-SS,
AE4000-SSC)
AE630-SS ~ AE3200-SS 65kAAE4000-SSAE5000-SSAE6300-SS
85kAAE4000-SSC 75kA
Zero arc space Arc exhaust space to the outside of the breaker is drastically reduced for safer operation.
(AE630-SS ~ AE3200-SS, AE4000-SSC q 600VAC)
Reverse connection available Line and Load is not defined on the Main circuit terminals.
Therefore reverse connection is available without any limitation.
4
More complete New AE4000-SSC The new AE4000-SSC which is smaller and economical makes fill up the AE-SS series.
AE4000-SSC has realized smaller and lighter than AE4000-SS.
Number of Operating cycles has been increased (2000 cycles→5000 cycles).
note 1: Only 3-pole type is available.note 2: The Max. rated current is 3600A on JIS C8372.
368565
AE4000-SSC
480
430
368875
AE4000-SS
DRAWOUT TYPE 3P DRAWOUT TYPE 3P(volume ratio)
(weight ratio)
58%
240kg 61% 145kg
Electronic trip relay features (1/2)
5
Multi functions available
Grouped electronic trip relays foreasier selection
Meets with a wide range of need depending on the application. Contributes to selective co-ordination, and ensures fine characteristic setting.
1 Electronic trip relay series
2 Common features
Pre-alarm function (PAL)The load current exceeds the value of the setting, before the breaker trips, the PALoperates, it contributes electrical continuity and easy maintenance.
Trip indicator (TI)The trip indicator (TI) is operated simultaneously with the OCR alarm (AL), when thebreaker trips because of Long time delay, short time delay/Instantaneous and Ground faultor Earth leakage. The relavent cause of tripping will be displayed on the appropriateindication LED and a relay contact will provide an output signal.
Temperature alarm (TAL)The TAL is operated by an unusual temperature of the breaker contacts.
Earth leakage protection (ER)A choice of earth leakage alarm or earth leakage tripping function is available improvingthe discrimination and the safety in circuit design.
Application Relay type
US3
S
M
B-C0A
Measuring & Display
Communication
Generaluse
Generator protection
use
Special use
Remarks Function
• Multi-function L, S, I/MCR characteristics• Ground fault/ Earth leakage protection• Trip indicator
• Plenty of electrical data is measured and displayed• Measured data, alarm and setting value is transmitted on CC-Link bus line• Remote ON/OFF operation
US3 type
S, M type
B-C0A
• INST/MCR characteristics
Provides CC-Link communication, data measuring and display for adaption to networking systems.
A multi-function type that provides all the characteristics required for the main circuit.
Only INST/MCR characteristics is provided.
Provided with characteristics for protecting generators for private power generation and marine vessels.
Option
Option
Option
Option
6
Meets Many NeedsOvercurrent protection on the
neutral pole (NP)In a 3-phase 4-wire circuit such that as provided to a computer, DC power unit or otherload devices, higher harmonics are liable to be generated which could cause damage asmore load current flows in the neutral plole.NP will eliminate such a possibility.
Ground fault protection (GFR)Either a ground fault trip or alarm function can be selected by a change-over switch. A control supply is not necessary.
Load current indication LEDsThe load current can be easily checked with the indication LEDs on the electronic triprelay.
More secure protection owing todetection of effective value (RMS)
Effective value detection that is most suitable for the protection of electronic devices.Effective value detection independently provided for each phase, which is effective fordistorted wave forms, is used to cope with the increasing use of electronics devices,including inverters.
Distorted current
Sine wave current
AC/DC Effective value conversionMaximum phase selection
Over Currentprotection(LTD circuit)
Option
Electronic trip relay features (2/2)
7
MDU (Measuring Display
Available for AE630-SS~AE6300-SS
Measurement functions
The full line up through MCCB 400A to ACB 6300A enables measurementsdisplay and transmission of electric circuit information.
PAL and AL are standard function
AE-SS MDU
MDU relay types
Type
US3P
US3G
US3E
Transmission
CC-Link
Characteristics
LTD+STD+INST/MCR
LTD+STD+INST/MCR+GFR
LTD+STD+INST/MCR+ER
1Electronic trip relay (US3P etc.)2MDU display unit3CC-Link!nterface unit
Measured items(accuracy) Contents
Present value (I1, I2, I3, IN )Demand value (I1, I2, I3, IN )Maximum demand value (max. phase)
Present valueDemand valueMaximum demand value
Energy (accumulated value)Time electric energyMaximum time electric energy
Present valueDemand valueMaximum demand value
Reactive energy (accumulated value)Time electric energyMaximum time electric energyPresent value
Present value
Present value (V1-2, V2-3, V3-1)Demand value (V1-2, V2-3, V3-1)Maximum demand value (max. phase)
Present value (V1-N, V2-N, V3-N)Demand value (V1-N, V2-N, V3-N)
Present value at 3rd, 5th, 7th (I1, I2, I3, IN )Maximum value at 3rd, 5th, 7th (max. phase)Present value of total harmonics (I1, I2, I3, IN )Demand value of total harmonics (I1, I2, I3, IN )Maximum demand value of harmonics (max. phase)
Load current(±2.5%)
Power(±2.5%)
Electric energy(±2.5%)
Reactive power(±2.5%)
Reactive energy(±2.5%)
Power factor(±5%)Frequency
Line voltage(±2.5%)
Phase voltage(±2.5%)
Harmonics(±2.5%)
In case of 4P AE-SS, IN and phase voltage measuring are available.
MDU Display unit
CC-Link Interface unit
AE1600-SS with MDU
8
Transmission itemsIncorporation of transmission function
Function Contents
Remote monitoring
Output
Input
Measured data (refer to page 7)Circuit condition (PAL pickup, PAL OUT, OVER)Fault information (Trip cause & Trip current)Setting of the Electronic trip relay (!n,!p, TL,!sd...)Demand time settingData clear (Accumulated data, Fault information)Error (Measuring, Transmission)
AE-SS ON/OFF status (by AXa) and other two “a” contact inputs
For remote ON/OFF
Unit) lineup for AE-SS
PLC networkingThe CC-Link transmission facilitates networking with high level systems (such as SCADA)via PLC
Specifications for CC-Link transmission
Item Specifications
Transmission speed
Connection system
Number of connectable unit per system
Unit type
Number of exclusive station
Selection from among 156kbps/625kbps/2.5Mbps/5Mbps/10Mbps
Broadcast polling
Max. 42unit
Maximum transmission distance Max. 1200m (156kbps, when using a dedicated cable)
Remote device station(station which can transmit word data as well as input/output)
1 station
CC-Link
System bus
ServerorPC
CC-Link master unit
MELSEC series PLC
MDU breaker AE-SS MDU
CC-LinkInterface
unit
Example of the PC monitoring
External view and Internal construction
9
Fixed typeAE-SS Series
Drawout typeAE-SS Series
AE1600-SS 3P
Cradle
Automatic control circuit connector
Lifting hole
Charging handle
Drawout position indicationExtention rail
Position lock
Aperture for the drawout handle
Drawout handle
Padlock position
Arc extinguishing chamber
Control circuit terminal block
Electronic trip relay
OFF button
ON button
Charging handle
Charging indicator
ON/OFF indicator
AE1600-SS 3P
Lifting hooks (HP) is supplied in the case of a fixed type AE-SS series.
10
Drawout typeAE-SH Series
Internal ConstructionAE-SS Series
Fixing bolt
Extension rail
Position lock
Control circuit terminal
Cradle
Charging handle
Automatic control circuit connector
Aperture for the drawout handle
Drawout handle
Drawout position indication
AE3200-SH 3P
qControl circuit terminal block
wAutomatic control circuit connector
eAuxiliary switches
rShunt trip device, Closing coil
tElectronic trip relay
yFront Cover
uTripping mechanism
iClosing mechanism
oCharging mechanism
!0Closing spring
!1Draw-out mechanism
!2 Insulated base
!3Arc extinguishing chamber
!4Main movable contacts
!5Main fixed contacts
!6Conductors on the breaker
!7Conductors on the cradle
!8Main circuit junction
!9Base
@0Contact spring
@1Conductors on the breaker
@2Conductors on the cradle
@3Power supply CT
@4Current sensor coil
@5Cradle
Product introduction
11
Super AE series allows easiercustomer selection
Standardmodel
Highbreaking
model
Type Page Page Page Page
AE630-SSAE1000-SSAE1250-SSAE1600-SSAE2000-SSAE2500-SSAE3200-SSAE4000-SSCAE4000-SSAE5000-SSAE6300-SS
AE630-SH
AE1000-SH
AE1250-SH
AE1600-SH
AE2000-SH
AE2500-SH
AE3200-SH
13~16
1Standard
IEC 60947-2
BS EN 60947-2
VDE 0660
JIS C8372
JIS C8370
Shipping standard
LR
GL
DNV
AB
BV
NK
Cell switchShorting-B contactLifting hooksSafety shutterSafety shutter lockMis-insertion preventorTest jumper
13~16 17
2Connecting
method
Fixed type
23, 24
3Cradle
Draw-out type
Horizontalterminals
Verticalterminals
Frontterminals
Emission
StandardDescription test procedure
IEC60947-2
Immunity
Conducted RF disturbances
Radiated RF disturbances
Electrostatic discharge
Electromagnetic field
Fast transients / burst
Conducted radio frequency
Surge
EN55011:1991 (Class A, Group 1)
EN55011:1991 (Class A, Group 1)
IEC61000-4-2 (contact Level 4)
IEC61000-4-3 (Level 3)
IEC61000-4-4 (Level 4)
IEC61000-4-6 (Level 3)
IEC61000-4-5 (Level 4)
Electromagnetic Compatibility
Earthleakage protection is not applicable for these tests.
12
Electricalaccessories
Mechanicalaccessories
Accessories Page
Auxiliary switch
Motor charging device
Closing coil
Shunt trip device
Under voltage trip device
Condenser trip device
Push button cover
Counter
Cylinder lock
Door interlock
Terminal cover
Door frame
Dust cover
Interphase barrier
Mechanical interlock
18~20, 22
21, 22
4Trip indicatorGround fault protectionEarth leakage protectionPre-alarmOCR-alarmTemperature alarm
General use:• S typeGeneratorprotection use• M typeSpecial use• B-C0A type
General use:• US3 type Data Meauring Display (MDU) with CC-Link communication
Neutral CTExternal ZCTField test device
5Electronictrip relay Page Page
33, 3425~32
7, 8 34, 35
Relay accessories
Moisture-fungustreatment
Extra-corrosionproofspecifications
6Special
environment Page
58
Vertical terminaladapter
Front terminaladapter
Terminal adapter Page
17, 55
Product Specification
13
Specification <IEC 60947-2, BS EN60947-2,
AE630-SSTypeFrame size (A)Rated insulation voltageRated operating voltage
(VAC)(VAC)
Number of poles (P)
Rated current of neutral pole (A)
Rated short time current !cw(RMS kA)
Maximum total breaking time(s)(s)
Closing time
Number of operating cycles. (Note 1)
690VAC
With instantaneous trip
With MCR
Without instantaneous (Note2)
With MCR
Without instantaneous (Note2)
600VAC500VAC240VAC690VAC600VAC500VAC240VAC690VAC
500VAC
500VAC1 s2 s3 s
With rated currentWithout rated current
abcdabcd
Manual charging typeFixed type
Drawout type(including cradle)
Weight
(kg)
Motor charging typeManual charging typeMotor charging type
Cradle only
Ratedbreakingcapacity
!cs/!cu
(RMS kA)
690VAC 10510514318788.210514314352.552.5
10510514318788.210514314352.552.5
10510514318788.210514314352.552.5
10510514318788.210514314352.552.5
14314318718710514314314394.594.5
14314318718710514314314394.594.5
14314318718710514314314394.594.5
With instantaneous trip600VAC500VAC240VAC690VAC600VAC500VAC240VAC690VAC
Ratedmakingcapacity
!Cm
(Peak kA)
Rated current
(A)
(!n)General use
(Current rating adjustable)
Generator protection use
(Current rating fixed)
6301000690
315-378-441-504-567-630250-300-350-400-450-500157-189-220-252-284-315
63050/5050/5065/6565/8542/4250/5065/6565/6525/25
654030
0.040.085000
10000340 425410 410290 29038 38
300 385430 430368 36861 6140 5043 5363 7766 8026 30
3 4
AE1000-SS10001000690
500-600-700-800-900-1000
100050/5050/5065/6565/8542/4250/5065/6565/6525/25
654030
0.040.08500010000
340 425410 410290 29038 38300 385430 430368 36861 6141 5144 5464 7867 8126 30
3 4
AE1250-SS12501000690
625-750-875-1000-1125-1250
125050/5050/5065/6565/8542/4250/5065/6565/6525/25
654030
0.040.08500010000
340 425410 410290 29038 38300 385430 430368 36861 6141 5144 5464 7867 8126 30
3 4
AE1600-SS16001000690
800-960-1120-1280-1440-1600
1600-1920-2240-2560-2880-3200
1000-1200-1400-1600-1800-2000
800-960-1120-1280-1440-1600
625-750-875-1000-1125-1250
160050/5050/5065/6565/8542/4250/5065/6565/6525/25
656050
0.040.08500010000
340 425410 410290 29038 38300 385430 430368 36861 6142 5245 5565 7968 8226 30
3 4
AE2000-SS20001000690
200050/6565/6585/8585/8550/5065/6565/6565/6545/45
656565
0.040.081500
50/5065/6565/6565/6545/45
656565
0.040.081500
50/5065/6565/6565/6545/45
656565
0.040.081000
10000475 605410 410290 29038 38435 565430 430368 36861 6160 7263 7592 11395 11635 43
475 605410 410290 29038 38435 565430 430368 36861 6161 7364 7693 11496 11735 43
475 605410 410290 29038 38435 565430 430368 36861 6163 7566 7895 11698 11936 44
3 4
AE2500-SS25001000690
1250-1500-1750-2000-2250-2500
250050/6565/6585/8585/85
10000
3 4
AE3200-SS32001000690
320050/6565/6585/8585/85
10000
3 4
200 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 625 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200
25/25 25/25 25/25 25/25 45/45 45/45 45/45
SS type (standard model)Type
Out
line
dim
ensi
on (
mm
)
Fix
ed ty
peD
raw
out t
ype
a c d
b
a c d
b
Note 1 : The number of operating cycles without rated current also include the number of operating cycles with rated current.
Note 2 : The columns for “without instantaneous tripping” are the values when the bare (without electronic trip relay) main body and the
external relay are combined. Please apply for further detail.
14
VDE0660 Ics/Icu>
10514318718710514316516594.594.5
105187286286105187187187105143
105187286286105187187187105143
105187286286105187187187105143
AE4000-SS40001000690
2000-2400-2800-3200-3600-4000
2000 q!n q 4000 2500 q!n q 5000 3150 q!n q 6300 315 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 1000 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200
320050/5085/85
130/130130/130
50/5085/8585/8585/8550/50
857070
0.050.08500
2000
857070
0.050.08500
2000
857070
0.050.08500
2000873 1003414 414290 290136 136875 1005480 480368 368123 123
875 1005480 480368 368123 123
875 1005480 480368 368123 123
160 180164 184240 263244 267125 140
240 263244 267125 140
240 263244 267125 140
3
AE4000-SSC40001000690
3200-3600-4000
3200 q!n q 4000
–
50/5065/6585/8585/8550/5065/6575/7575/7545/45
756565
0.040.08500500060541429013656543036815110911214514875
3 4
AE5000-SS50001000690
2500-3000-3500-4000-4500-5000
320050/5085/85
130/130130/130
50/5085/8585/8585/8550/50
873 1003414 414290 290136 136
160 180164 184
3 4
AE6300-SS63001000690
320050/5085/85
130/130130/130
50/5085/8585/8585/8550/50
873 1003414 414290 290136 136
160 180164 184
3 4
3150-3780-4410-5040-5670-6300
500-600-700-800-900-1000
315-378-441-504-567-630
625-750-875-1000-1125-1250
800-960-1120-1280-1440-1600
1000-1200-1400-1600-1800-2000
1250-1500-1750-2000-2250-2500
1600-1920-2240-2560-2880-3200
AE630-SH630
1000690
63065/6585/85
130/130130/130
––––
–––
–––
–––
–––
–––
–––
–
–––
0.040.083000
10000475 605410 410290 29068 68
485 615430 430398 39861 6166 7969 82
105 127108 13042 50
475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50
475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50
475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50
475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50
475 605410 410290 29068 68485 615430 430398 39861 6166 7969 82105 127108 13042 50
475 605410 410290 29068 68485 615430 430398 39861 6168 8171 84107 129110 13243 51
3 4
AE1000-SH10001000690
100065/6585/85
130/130130/130
–
–
–––
0.040.08300010000
3 4
AE1250-SH12501000690
125065/6585/85
130/130130/130
–
–
–––
0.040.08300010000
3 4
AE1600-SH16001000690
160065/6585/85
130/130130/130
–
–
–––
0.040.08200010000
3 4
AE2000-SH20001000690
200065/6585/85
130/130130/130
–
–
–––
0.040.08150010000
3 4
AE2500-SH25001000690
250065/6585/85
130/130130/130
–
–
–––
0.040.08150010000
3 4
AE3200-SH32001000690
320065/6585/85
130/130130/130
–
–
65/6545/45 65/65 65/65 – – – – – – –65/6585/85
130/130130/130
––––
–––
–––
–––
–––
–––
–––
–
65/6585/85
130/130130/130
–
–
65/6585/85
130/130130/130
–
–
65/6585/85
130/130130/130
–
–
65/6585/85
130/130130/130
–
–
65/6585/85
130/130130/130
–
–
65/6585/85
130/130130/130
–
–
– – – – – – ––––
0.040.08100010000
3 4
SH type (High breaking model)
Product Specification
15
Specification <JIS C 8372 (o-co-co duty)>
AE630-SSTypeFrame size (A)
Rated insulation voltage (VAC)(VAC)Rated operating voltage
Number of poles (P)
Rated current of neutral pole (A)
Rated short time current(RMS kA)
Maximum total breaking time (s)(s)Closing time
Number of operating cycles. (Note 1)
550VACWith instantaneoustrip
With instantaneoustrip
With MCR
Without instantaneous (Note2)
With MCR
460VAC550VAC460VAC550VAC550VAC460VAC220VAC550VAC
1 s2 s3 s
With rated currentWithout rated current
General use(Current rating adjustable)
Generator protection use(Current rating fixed)
630600550
315-378-441-504-567-630250-300-350-400-450-500157-189-220-252-284-315
63050/10565/14350/10565/14325/52.550/10565/143
85/195.550/105
100050/10565/14350/10565/14325/52.550/10565/143
85/195.550/105
125050/10565/14350/10565/14325/52.550/10565/143
85/195.550/105
160050/10565/14350/10565/14325/52.550/10565/143
85/195.550/105
654030
0.040.085000
10000
3 4
AE1000-SS1000600550
500-600-700-800-900-1000
654030
0.040.08500010000
3 4
AE1250-SS1250600550
625-750-875-1000-1125-1250
654030
0.040.08500010000
3 4
AE1600-SS1600600550
1000-1200-1400-1600-1800-2000
800-960-1120-1280-1440-1600
625-750-875-1000-1125-1250
656050
0.040.08500010000
3 4
AE2000-SS2000600550
200065/143
85/195.565/14365/14345/94.565/143
85/195.585/195.565/143
65/14385/195.565/14365/14345/94.565/143
85/195.585/195.565/143
65/14385/195.565/14365/14345/94.565/143
85/195.585/195.565/143
656565
0.040.081500
656565
0.040.081500
656565
0.040.081000
10000
3 4
AE2500-SS2500600550
1250-1500-1750-2000-2250-2500
2500
10000
3 4
AE3200-SS3200600550
3200
10000
3 4
200 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 625 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200
460VAC220VAC
65/14365/143
65/14365/143
65/14365/143
65/14365/143
65/14365/143
65/14365/143
65/14365/143
SS type (standard model)Type
Rated current
(A)
(!n)
Rated breakingcapacity(kA RMS
symmetrical)
JIS
C8372
O-CO-CO
JIS
C8370
O-CO
Rated makingcapacity
(kA peak value)Breaking duty
O-CO-CO
800-960-1120-1280-1440-1600
1600-1920-2240-2560-2880-3200
Shipping Standard <LR, AB, GL, DNV, BV, NK>
AE630-SSTypeFrame size (A)Rated insulation voltage (VAC)Number of poles (P)
600VACWith instantane-ous trip
With instantane-ous trip
With instantane-ous trip
With instantane-ous trip
With instantane-ous trip
With instantane-ous trip
NK
LR
ABS
GL
BV
DNV
500VAC
690VAC600VAC500VAC690VAC600VAC500VAC690VAC600VAC500VAC
690VAC600VAC500VAC
690VAC600VAC500VAC
Rated breakingcapacity(kA RMS
Symmetrical)
Rated makingcapacity
(kA peak value) Breaking
dutyO-CO-CO
General use(Fixed rated current)
6301000
3
50/11265/147
50/106–
65/15150/105
–65/14350/106
–65/151
3
50/11265/147
50/106–
65/15150/105
–65/14350/106
–65/151
3
50/11265/147
50/106–
65/15150/105
–65/14350/106
–65/151
3
50/11265/147
50/106–
65/15150/105
–65/14350/106
–65/151
AE1000-SS10001000
AE1250-SS12501000
AE1600-SS16001000
AE2000-SS20001000
3
65/14385/196
50/10665/14385/19650/10565/14385/18750/10665/14385/196
65/14385/196
50/10665/14385/19650/10565/14385/18750/10665/14385/196
65/14385/196
50/10665/14385/19650/10565/14385/18750/10665/14385/196
AE2500-SS25001000
3
AE3200-SS32001000
3
200 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 625 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200
50/105–
65/143
50/105–
65/143
50/105–
65/143
50/105–
65/143
50/10565/14385/187
50/10565/14385/187
50/106–
65/151
50/106–
65/151
50/106–
65/151
50/106–
65/151
50/10665/14385/196
50/10665/14385/196
50/10665/14385/19650/10565/14385/187
SS type (standard model)Type
Rated current(A)(!n)
Note 1 : The number of operating cycles without read current also include the number of operating cycles with rated current.Note 2 : The columns for “without instantaneous tripping” are the values when the bare (without electronic trip relay) main body and the external
relay are combined.
16
AE4000-SS4000600550
2000-2400-2800-3200-3600-4000
2000 q!n q 4000 2500 q!n q 5000 3000 q!n q 6000 315 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 1000 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200
320085/195.5130/29985/195.585/195.565/143
––––
857070
85/195.5130/29985/195.585/195.565/143
––––
857070
85/195.5130/29985/195.585/195.565/143
––––
857070
0.050.08500
2000
0.050.08500
2000
0.050.08500
2000
3 4
AE5000-SS5000600550
2500-3000-3500-4000-4500-5000
3000-3600-4200-4800-5400-6000
3200
3 4
AE6300-SS6300600550
3200
3 4
315-378-441-504-567-630
500-600-700-800-900-1000
625-750-875-1000-1125-1250
800-960-1120-1280-1440-1600
1000-1200-1400-1600-1800-2000
1250-1500-1750-2000-2250-2500
1600-1920-2240-2560-2880-3200
AE630-SH630600550
63085/195.5130/299
–––
85/195.5130/299130/299
–
–––
85/195.5130/299
–––
85/195.5130/299130/299
–
–––
85/195.5130/299
–––
85/195.5130/299130/299
–
–––
85/195.5130/299
–––
85/195.5130/299130/299
–
–––
85/195.5130/299
–––
85/195.5130/299130/299
–
–––
85/195.5130/299
–––
85/195.5130/299130/299
–
–––
85/195.5130/299
–––
85/195.5130/299130/299
–
–– – – – – – –
– – – – – – –
––
0.040.083000
10000
3 4
AE1000-SH1000600550
1000
0.040.08300010000
3 4
AE1250-SH1250600550
1250
0.040.08300010000
3 4
AE1600-SH1600600550
1600
0.040.08200010000
3 4
AE2000-SH2000600550
2000
0.040.08150010000
3 4
––
AE4000-SSC4000600550
3200-3600
3200 q!n q 3600
–65/143
85/195.565/14375/16545/94.565/143
85/195.585/195.565/143
756565
0.040.085005000
3
75/16575/165
––
––
AE2500-SH2500600550
2500
0.040.08150010000
3 4
AE3200-SH3200600550
3200
0.040.08100010000
3 4
SH type (High breaking model)
AE4000-SS40001000
3
2000 q!n q 4000 2500 q!n q 50003150 q!n q 63003150 q!n q 5700
(for NK)
3200 q!n q 38003200 q!n q 3500
(for NK)315 q!n q 630 500 q!n q 1000 625 q!n q 1250 800 q!n q 1600 1000 q!n q 2000 1250 q!n q 2500 1600 q!n q 3200
87/211133/330
–87/211
133/330
–––
87/211133/330
–87/211
133/330
–––
87/211133/330
–87/211
133/330
87/211133/330
87/211133/330
87/211133/330
– – –
–––
AE5000-SS50001000
3
AE6300-SS63001000
3
AE630-SH630
10003
130/317
68/17387/211
133/330
130/317
68/17387/211133/330
130/317
68/17387/211133/330
130/317
68/17387/211133/330
130/317
68/17387/211133/330
130/317
68/17387/211133/330
130/317
68/17387/211133/330
–––
AE4000-SSC40001000
3
65/14385/196
51.1/11367/147
86.6/199––––––
–––
–––
–––
–––
–––
–––
–––
––––––
––––––
––––––
–––
––––––
–––
–––
–––
–– – –
–––
–––
–––
–––
––––––
––––––
––––––
–––
–––
–––
– – –
–––
–––
–––
AE1000-SH10001000
3
AE1250-SH12501000
3
AE1600-SH16001000
3
AE2000-SH20001000
3
AE2500-SH25001000
3
AE3200-SH32001000
3
SH type (High breaking model)
Connecting methods
17
Connection arrangementsThe following connecting methods are available for the AE type air circuit breaker.
ConnectingmethodMounting
method
Horizontal connection(Standard)
Vertical connection(VT)
Front connection(FT)
Vertical terminal adapter(VTA)
Front terminal adapter(FTA)
Fixed type(FIX)
Draw-outtype(DR)
(DR-VT) (DR-FT)
(VTA)
(VTA)
(FIX-FTA)
(DR-FTA)
Connecting Methods
Type
Type
Connecting method
Connecting method
AE630-SS
Horizontal terminal (Standard)
Vertical terminal
Fixed type
(FIX)
Fixed type
(FIX)
Options
Options
Options
Options
Draw-out
type (DR)
Draw-out
type (DR)
–
– – – – – – –
(VTA) –
(FIX-FTA) –
Horizontal terminal (Standard) –
(DR-VT)
(DR-FT) –
(VTA) –
(DR-FTA)
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SS
–
–
–
–
–
–
–
AE4000-SSC AE5000-SS AE6300-SS
AE630-SH
Horizontal terminal (Standard)
(VTA)
(FIX-FTA)
Horizontal terminal (Standard)
(DR-VT)
(DR-FT)
(VTA)
(DR-FTA)
AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH
Note1: The terminal for AE4000-SSC, AE4000-SS ~ AE6300-SS shall be vertical terminal.
(Remarks) The white circle “”indicates that the product can be manufactured, while the blue “ ”indicates the standard connecting method.
(Note 1)
Charging methods
18
Manual chargingThe spring is charged by the manual charging handle. The breaker is closed when the ON button is pressed,and opened when the OFF button is pressed.
When the closing spring charging is completed, the charging indicator displays CHARGED. The indicator displays ON or OFF state of the main contacts. The breaker cannot be closed while the OFF button is being pressed. (Safety feature)
OFF lock is available by padlock (See P9, P24) as standard.
Motor charging device (MD)The closing spring is charged by an electric motor. When the breaker is closed, the spring is chargedautomatically (ON-charge method.) The closing coil (CC) is required to remotely close, and the shunt tripdevice is required to remotely open the breaker.
Manual charging is alsoavailable.
Pumping prevention isassured both electricallyand mechanically.
As the charging completioncontact is separate fromthe electrical chargingcircuit, its function in thecontrol scheme can bearranged as desired.
Motor charging rating
Ratedvoltage
Applicablevoltage range (V)
Appliedvoltage (V)
Inrush current(peak value)(A)
Steadycurrent (A)
Chargingtime (s)
DC24V 20.4 ~ 26.4 24 22 6 q 5
DC48V 36 ~ 52.8 48 14 3 q 5
AC • DC
100 ~ 125V85 ~ 137.5
100 10(10) 3(4) q 5
125 12(12) 3(4) q 5
AC • DC
200 ~ 250V170 ~ 275
200 5(7) 1(2) q 5
250 6(8) 1(2) q 5
( ): AE4000-SS~AE6300-SS
DC24, DC48V is not available for AE4000-SS~AE6300-SS
OFF charging method
Chargingcompletion
switch
MX
X1a
X2a
Controlrelay Motor
Motor charging circuitBreaker
Apply for further details of 24V DC and 48V DC.
(TS+)
(TS-)
(M+)
(M-)
Control supply
413
414
U1
U2
U1
U2
Control supply
AXb
Breaker
Motorcharging circuit
Charginglimit switch
(M+)
(M–)
A OFF charging method is also available. The closingspring is charged automatically when the breaker isopened. This is available only by externally connecting inseries b contact (AXb) of the auxiliary switch to the motorcharging circuit.In case of DC power supply, please use high capacityauxiliary switch (HAX).
Option
Accessories (for Breaker unit 1/2)
19
Closing coil (CC)The closing coil is a device to close the breaker by remote control.
An interlock to prevent pumping is provided electrically.
Closing time is from the initial energization of the closing coil to the completion of theclosing of the main contacts.
Because of pumping prevention is not performed, do not use AXb contact for a cut-offswitch.
Operating time AE4000-SS~AE6300-SS is 0.05 s or less.
Diode rectifier is not used for control source 24-48V DC.
Shunt trip device (SHT)This is the switch used to open the breaker by remote control. A cut-offswitch is included.
Rated voltage(Applicable voltage range)
DC24-48V(18~52.8)
AC • DC common100-250V(75-275)
Closingtime
0.08 sor less
Operating voltage • Operating inrush current (VA)
AC
–
–
AC100V 0.5A (100VA)
AC250V 1.0A (150VA)
DC
DC24V 3.5A (100W)
DC48V 7.0A (200W)
DC100V 0.6A (100W)
DC250V 1.3A (200W)
Rated voltage(Applicable voltage range)
DC24~48V(16.8~52.8)
AC380~500V(266~550)
AC • DC common100~250V(75~275)
Operatingtime
0.04sor less
Operating voltage • Operating inrush current (VA)
AC
–
–
AC100V 0.6A (100VA)
AC250V 1.7A (150VA)
AC460V 0.6A (200VA)
DC
DC24V 3.5A (100W)
DC48V 7.0A (200W)
DC100V 0.8A (100W)
DC250V 2.0A (250W)
–
(CC+)
(CC–)
Breaker C.C. Unit
A1
A2
Controlsupply One-pulse
circuit
CC
CC circuit diagram
Breaker Cut-off switchSHT unit
C1
C2
Controlsupply
SHT
(S+)
(S–)
SHT circuit diagram
Diode rectifier is not used for control source24-48V DC.
Motor charging device (MD)The closing spring is charged electrically, and the breaker will be ready to
be closed. When specifying the motor charging device, be sure to order the closing
coil (CC) and the shunt trip device (SHT) for remote operation. Refer to page 18 for details.
Option
Option
Option
20
Under voltage trip device (UVT)This device is used to trip the breaker if the supply voltage is reduced below its nominalvalue, and consists of a UVT coil and UVT controller. Two types are available: theinstantaneous type which trips the breaker instantly, and a time delay type which trips thebreaker after a delay of 0.5 or 3 seconds from when the supply voltage has reduced belowits nominal value. The UVT controller can be mounted on the lefthand side of the breakerlooking from the front.
(Note 1) If dual rated voltages are used, a lower value is applied.(Note 2) If a remote trip function is required remove the wire shorting terminals DT1 DT2 and
connect a normally closed switch, rated 1mA at 100VDC across them.(Note 3) The operating time is a guarantee value when it drops from 85% or more of the rated
voltage. The following delay should be allowed between applying the voltage to the UVT, and closing the
breaker.UVT-SSB∗ : 1.5 s, UVT-05SSB∗ : 1.5 s, UVT-30SSB∗ : 3 s
TypeOperation
FrequencyPick-up voltageDrop-out voltage
Trip function(Note 2)
Power consumption
Ratedvoltage+10%–15%
UVT-SSB*Instantaneous0.1 s max.
100-120/200-240/380-460VAC24VDC48VDC
100-110VDC120-125VDC50/60 Hz(AC)
65~85% (Note 1)45~70% (Note 1)
With open circuit of terminals (DT1, DT2)operation time 0.1 s max.
UVT-05SSB*
0.5 s min.
UVT-30SSB*
3 s min.Operation time(Note 3)Time delay
( )
20 VA
Air circuit breaker
Circuitvoltage
Controlcircuit
UVT coil
D4J1
(U+) (U+)
(U–) (U–)
J2
J1
J2
DT
1
DT
2
(UO
–)
(UO
+)
D3D2D1
AC200-240V(UL2)AC100-120V(UL1)
AC380-460V(UL3)
Common(UL0)
Trip button
UVT circuit diagram
UVT controller
6.5 215
182.2
14.5
14.6
45
11
UVT controller
19.8
118 7.
89.
3
87.9 72
19
Terminal screw M3.5Plus-minus screw
Mounting screw
(mm)
Con
tact
capa
city
(A
)
AC
DC
460V250V125V250V125V30V
TypeAX(standard)
Resistance load510100.30.610
Inductive load210100.30.66
HAX (high capacity type)Resistance load
5101031010
Inductive load2.510101.5610
Maximum contacts
Change-over sequenceBreaker state
ONOFF
a-contact (NO)ONOFF
b-contact (NC)OFFON
5 a 5 b 5 a 5 b
Auxiliary switch(AX-standard, HAX-high capacity type)
This is the contact that is used to remotely indicate the ON or OFF status of the breaker.
The a and b contacts may turn simultaneously to ON instantaneously at the time of changing the contact; Pay attention to the contact state when designing circuits.
The chattering time at the time of contact ON-OFF is below 0.025 s. For special environment specification, the contact capacity gets deteriorated.
Apply for further detail.
Option
Option
Accessories (for Breaker unit 2/2)
21
Push button cover
The cover is to prevent careless manual operation (ON,OFF) of the push buttons.BC-L can be locked by a padlock (The padlock beingsupplied by the customer.)For the size of the a suitable padlock, refer to Page 24.
Counter (CNT)
The open/close operations of the breaker are shown on a5 digit counter.
Cylinder lock (CYL)
The breaker is locked OFF with the cylinder lock. Since it is an interlock which only allows the key to be
removed when the breaker is locked off, it can be usedfor interlocking two or more breakers.
Door interlock (DI)
The panel door cannot be opened unless the breaker isopen. A wire type mechanical interlock is used to allow
flexibility in positioning breakers in the switchboard. The parts of the Door panel should be supplied by
customer.
Dust cover
Dust cover prevents the dust or water entering into thepanel board from the breaker panel cut.Protection degree IP 54.
Interphase Barrier (BA)
The interphase insulation of the circuit breaker has beenintensified to prevent the short circuit due to conductivematters or dust. Easily detachable, in design, the barrier isapplicable to fixed type, draw-out type, horizontal terminalor vertical terminal. (For further detail, see the “Table ofMountable Barriers” given below.
Table of Mountable BarriersDoor lock unit
Door panel
Breaker
Horizontal terminal (standerd)
Horizontal terminal (standerd)
Vertical terminal adapter
Front terminal adapter
Vertical terminal adapter
Vertical terminal
Front terminal adapter
Front terminal
AE630-SS~AE1600-SS
–
–
–
–
–
Connectingmethod
AE2000-SS~AE3200-SS
–
–
–
–
–
–
AE-SHType
–
–
–
–
–
–
–
Not available for AE4000-SSC, AE4000-SS~AE6300-SS
Fixed type
Draw-outtype
Option
Option
Option
Option
Option
Door frame (DF)
The door frame improves the appearance, after cutting outthe panel door to install the breaker.
Option
Terminal cover (TTC)
The transparent terminal cover prevents from carelesstouching to the live control terminals.Protection degree IP20.
Option
Push button cover
Interphase barrier (BA) 2 pcs (3-pole), 3 pcs (4-pole)
22
Mechanical interlock (MI)The mechanical interlock is a secure interlock prohibiting the parallel closing of two or three breakers. Any combination between AE630-SS~AE3200-SH and AE4000-SSC is possible. Please apply for further
details of AE4000~6300-SS. It can be simply installed on either fixed or drawout type breakers. With the drawout type, the interlock operates at the connecting point and can be released at other positions,
providing secure maintenance and inspections of the breaker. There are restrictions on ordering MI and DI together, please apply for further details. It is impossible to secure interlock among 3 pcs of AE4000-SS~AE6300-SS.
Condenser trip device (COT)Even if the power supply fails, the breaker can be electrically opened by remote operation within a definitetime. This device is combined with the shunt trip device (SHT).
Note 1: The rated charging voltage is the voltagestored during capacitor saturation. It iscontinuously supplied by the rectifiedvoltage of the rated AC input voltage.
Note 2: The charging time starts when thecapacitor begins to supply power at 85%of the rated AC input voltage andcontinues until the capacitor chargingvoltage reaches 60% of rating.
Note 3: The time period in which the shunt tripdevice can perform its one operationstarts from when the capacitor is chargeto 100% the supply voltage is removed.
ON OFF
G
ON
ON
OFF
Change over of two power supplies
The followinginterlocks are available.
Change over of two supply systems
Up to any two breakers can be closed.(Please apply for further details)
Vertical mounting Horizontal mounting(mm)
Breaker
1000(Max.)10
00(M
ax.)
144
0~12
134
Breaker
Breaker arrangement (630AF~3200AF)
47(Max.)
Type KF-100
100/110VAC
50~60Hz
140/155V
660µF
60~125%
1VA
0.5 s max.
15 minutes min.
Black (N1.5)
2000VAC
100~250VAC • DC
KF-200
200/220VAC
280/310V
150µF
5 minutes min.
Rated input voltage
Rated frequency
Rated charging voltage (Note1)
Condenser capacity
Voltage range
Power supply capacity
Charging time (Note 2)
Trip limit time (Note 3)
Paint color
Withstand voltage (1 minute)
Applicable shunt trip voltage
60~125%
50~60Hz
1VA
0.5 s max.
Black (N1.5)
100~250VAC • DC
2000VAC
90
90
75110.6
4-R6
Condensertrippingdevice
4-M3×0.5Cover screw
13.315.4168790106
100
4-M4 screw(for wiring)
4-M6 Mounting screw
4545
4545
f104
4-f7
AC1
AC2
S1 R1
R2
R3
N6
DC+
DC–
C
SHT
C1
C2
Open button
Front view Side view Drilling plan Circuit diagram (mm)
Outline dimensions (mm)
Option
Option
Accessories (for Drawout frame)
23
Cell switch (CL)
The switch is used to indicate the drawout positions(CONNECTED, TEST, DISCONNECTED).
Shorting b-contact (SBC)
When moving the breaker from the connected to the testpositions, use this contact to short circuit auxiliary switch(AXb) thus maintaining the correct sequence of operationof the external control circuit.When ordered, the same number of shorting b-contacts asauxiliary switches (AXb) will be provided.
Lifting hooks (HP)
This is used to remove the drawout type breaker from thecradle.The option is not necessary when the special lifter (buckettype) for AE-SS·SH is used.The fixed type breaker is equipped with HP as standard.
Safety shutters (SST)
The safety shutters cover the conductors (cradle side) andprevent contact with them when the breaker is drawn out. When checking the main circuit, supply and load sides
of the shutters can be kept OPEN independently. (theyare released automatically when the breaker is pushedin.)
Safety shutter lock (SST-LOCK)
This kit is used to lock the safety shutters using 2 padlocks(the padlocks to be customer’s supply). The safetyshutters close when the breakers drawn out to preventaccidental contact with the main contacts.
CL-C(CONNECTED)
Drawout positionof breaker
Display position ofdrawout operation
CL-T(TEST)
CL-D(DISCONNECTED)
Sw
itch
func
tion
Con
tact
cap
acity
(A
)
Chan
ge-o
ver s
eque
nce
(a-c
onta
ct)
DISCON TEST CONNECT
ON
ON
ON
OFF
OFF
OFF
Disconnected Connected
Voltage (V)
Number that may be installed Total 4c max.
AC
DC
460
250
125
250
125
30
Resistive load Inductive load
2.5
10
1.5
6
10
10
5
3
10
10
Operating sequence and contact rating
OptionOption
Option
Option
Option
24
Mis-insertionpreventor (MIP)
This option prevents any other circuit breakers exceptthose specified from being inserted into the cradle, 5settings are available.(Note) It is not available for AE4000-SS~AE6300-SS.
Test jumper (TJ)
With the breaker taken out of its cradle, this device willenable the breaker to be electrically opened and closed,and the operating sequence to be checked.Note 1: Remove the breaker out of its cradle before using
this device.
Drawout interlockA safety device prohibits push-in and drawout whenthe breaker is ON. The drawout handle cannot beinserted unless the OFF button is pressed.
Position lockThis device is for locking the drawout mechanism atthe TEST position this then indicates the “TESTposition”. The lock can be used during either thedrawing out or pushing in operation.The lock is released when the lock plate is pushed in,and the next operation becomes possible.Padlocking is possible at the CONNECTED, TEST,and DISCONNECTED positions. Use this lock toprevent unauthorized changing of positions.
The padlock should be supplied by customer.
16
5
35
(mm)
CONNECTED position TEST position DISCONNECTED position DRAWOUT position
Main circuit is disconnected, but the control circuit is connected. The breaker operation can be tested with the door closed.
Both main and control circuits are disconnected.
This is the position for removing the breaker. The breaker is drawn out of the cradle on the extension rails.
The door can be closed.
Both main and control circuits are connected.
Normal in use condition.
Standard equipment
Operating position of drawout type
Option
Option
The earthling points are located on both sides of the cradle, and they make contact between the breaker and the cradleat CONNECTED, TEST, and DISCONNECTED positions.
Lock plate
Electronic trip relay specifications table
25
Use
Type S ST SPT
General use
SPGT SPET M
Generator
MT
Protection
Overload, Short circuit (L+S+I) (Note 1)
–
–
–
–
–
Not required
–
–
–
–
Required
–
–
Required
–
Required
–
Required
–
–
–
–
–
–
–
Not required
–
–
–
–
–
–
Required
Neutral protection (NP)
Making Current Release (MCR) (Note 2)
Pre-alarm (PAL)
Ground fault (GFR) (Note 3)
Earth leakage (ER)
Load current indication LEDs, Alarm
Load current indication LEDs
OCR alarm (AL)
Trip indicator (TI)
Temperature alarm (TAL)
Others
Control power supply
Test terminal
STD lock button
–
: Standard equipped: Optional equipped: Not available
Classification of typesExample
Type
Not required
Control voltageCode
0
AE630-SS
630
500
315Low
rating
AE1000-SS
1000 1250 1600 2500 3200 4000 4000 5000
6000 (JIS)
6300
AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SSC AE4000-SS AE5000-SS AE6300-SS
(A)
1
2
4
AC100-120/AC200-240V
DC100-125V
DC24-60V
Note 1:Note 2:Note 3:Note 4:
L → LTD, S → STD, I → INSTMCR function is not available for AE-SH.GFR is not availabe for AE630-SS (!n max = 315A, 500A), nor AE630-SH.B-C0A relay and BARE are not available for AE-SH series.
Table 1 Control supply voltage code
Table 2 CT rating (Rated current MAX.)
2000
1600
1250Low
rating
AE630-SH AE1000-SH
1000630 1250 1600 25002000 3200
AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH
SPT
26
MPT
protection use Special use No relayRemarks Ref. Page
37~39
33
–
34
33
33, 35
28, 30, 32
34
28, 30
34
–
34
28, 30
–
–
–
–
Required
MPGT
–
–
–
Required
B-C0A(Note 4)
BARE(Note 4)
Only INST
Only INST
–
–
–
–
–
Not required
–
–
–
–
–
–
–
–
–
–
–
Not required
LTD, STD and INST characteristics are standard equipped. Only INST is equipped for B-C0A relay
NP characteristics is same as live poles. AE-SS 4P
With MCR, Instantaneous tripping is only possible if a short circuit occurs during switch-ON. After the initial switch-ON, the Inst characteristic is cancelled to keep selectivity. INST/MCR set is changeable.PAL is indicated LED and a contact output if the load current is exceeded PAL setting value. Operating characteristic is half of LTD characteristic. Auto reset type.GFR ALARM/TRIP is changeable. When the switch is set to “ALARM” position a indicator LED will light up and the relay output will be activated when a ground fault occurs. However ACB will not trip.
Indicates load current in percentage indicator LEDs.30ms 1pulse output signal will be activated. Self-hold circuit is reqired when continuous signal is needed. It will notactivated when ER operates.Fault cause is indicated LED and A contact. The signal is reset by pushing reset button or turning off the control power supply of the relay.
OperatingVA: 5VA Vairious voltage code is shown below left table 1.
This button is used during characteristic check.
Operating characteristics (LTD, STD, INST, GFR, PAL) are checked by field test device for AE-SS/AE-SH. Each pole characteristic is is checked individually for M type relay.
TAL is indicated LED and a contact output if the temperature around main contacts is exceeded usual level. The signal is reset by pushing reset button or turning off the contorl power supply of the relay.
External ZCT is reqired. Alarm output (A contact) signal will be activated. Also ACB can be tripped with SHT trippingdevice.
–
–
MCROCRalarm
Control voltagecode
Temperaturealarm
Voltage (V)
AC120
250
30
125 0.2 0.1
2 2
DC
Resistiveload
Inductiveload
(A)Table 3 Contact rating of Trip indicator and alarm
C 2 A T
27
Electronic trip relay (General use
27
S type (General use)
Rated current Max. (!n max) Refer to P25 Table 2.
Adjustable setting range
0.5-0.6-0.7-0.8-0.9-1.0 ×!n max
0.8-0.9-1.0 ×!n max (AE4000-SSC)
0.8-0.82-0.84-0.86-0.88-0.9-0.92-0.94-0.96-1.0 ×!n
1.15 ×!u ±10%
12-25-50-100-150 s ±20% (at 2 × !u)
2-3-4-6-8-10 ×!n ±15%
0-0.1-0.2-0.3-0.4-0.5 s ±20% (at 1.5 ×!sd)
4-6-8-10-12-16 ×!n ±15%4-6-8-10-12 ×!n ±15% (AE5000-SS)4-6-8-10 ×!n ±15% (AE6300-SS)
0.7-0.8-0.9-1.0-OVER ×!u ±10%
0.5 × TL ±20%
0.1-0.2-0.3-0.5 ×!n max ±20% 0.2-0.3-0.5 ×!n max ±20% (AE4000-SSC, 4000-SS~6300-SS)
0.3-0.8-1.5-3 s ±20% (at 1.5 ×!g)
1-2-3-5 A ±20%
0.3-0.8-1.5-3 s ±20% (at 1.5 ×!∆n)
Rated current (!n)
Short-timedelay
Uninterrupted current (!u)
LTD current Long-timedelay
LTD time (TL)
STD current ( !sd)
STD time (Tsd)
INST current (!i) Instantaneous
PAL current (!p)
PAL time (Tp)
GFR current (!g)
GFR time (Tg)
ER current (!∆n)
Ground-faultprotection
Earth-leakageprotection
ER time (Te)
Pre-alarm
Rated current Max. (!n max)
Rated current (!n) PAL current (!p)
Load current indication LEDs
INST current (!i)
STD current (!sd)
Uninterrupted current (!u)
GFR current (!g)
ER current (!∆n)
Unless specified when ordering the electronic trip relay will be set to in blue.
S type setting dial operation schematic
S type)
28
N
AB
E
G
OQ
PH R
J
KMIL
F
CD
MADE IN JAPAN
MODEL
1600 A
ELECTRONIC TRIP RELAY
TRIP INDICATOR
ALARM
LOAD CURRENT % Iu
SPGT–C1AT
ALARMTRIP
0.20.1
0.5GFR P.U. Ig
0.3
0.50.4
0.10
0.20.3150
122550
1003.01.5
0.30.8
106 8 161210.88
23
STD P.U. Isd
4
UNINTERRUPTED
864
INST P.U. Ii
.80
.84 .921.0 OVER
PAL P.U. Ip
0.9
0.70.8
STD LOCK MCRINST
RESET
OVER
TAL
S/I GL
1008060
RATED CURRENT MAX.
1.0
1.0
.96
TEST
PAL P.U. PAL OUT
(CT RATING)
=In maxRATED CURRENT In
CURRENT Iu
XIn max
X In max
XIu XIn XIn XIn
s s s
Iu × 2 Isd×1.5
GFR TIME LTD TIME STD TIME
0.90.80.7
0.60.5
A Trip indicator
PAL indicator
Temperature alarm indicator
Reset button
Load current indication LEDs
Rated current setting dial
Uninterrupted current setting dial
LTD time setting dial
STD current setting dial
STD time setting dial
STD lock button
INST current setting dial
INST/MCR switch
PAL current setting dial
GFR or ER current setting dial
GFR or ER time setting dial
GFR TRIP/ALARM switch
TEST terminal
BCDEFGHIJKLMNOPQR
Electronic trip relay (Generator
29
M type (Generator protector use)
Rated current Max. (!n max)
Rated current (!n) PAL current (!p)
Load current indication LEDs
INST current (!i)
STD current (!sd)
LTD current (!L)
GFR current (!g)
Rated current Max. (!n max) Refer to P25 Table 2.
Adjustable setting range
0.5~1.0 ×!n max 0.8~1.0 ×!n max (AE4000-SSC)
1-1.05-1.1-1.15-1.2 ×!n ±5%
15-20-25-30-40-60 s ±20% (at 1.2 ×!L)
2-2.5-3-3.5-4-4.5 ×!n ±15%
0-0.1-0.2-0.3-0.4-0.5 s ±20% (at 1.5 ×!sd)when “0” setting, operating time is 0.04~0.08 s.
4-6-8-10-12-16 ×!n ±15%4-6-8-10-12 ×!n ±15% (AE5000-SS)4-6-8-10 ×!n ±15% (AE6300-SS)
0.84-0.88-0.92-0.96-1.0 ×!L ±5%
0.5 × TL ±20%
0.1-0.2-0.3-0.5 ×!n max ±20% 0.2-0.3-0.5 ×!n max ±20% (AE4000-SSC, 4000-SS~6300-SS)
0.3-0.8-1.5-3 s ±20% (at 1.5 ×!g)
Rated current (!n)
Short-timedelay
LTD current (!L) Long-timedelay
LTD time (TL)
STD current (Isd)
STD time (Tsd)
INST current (Ii)Instantaneous
PAL current (Ip)
PAL time (Tp)
GFR current (Ig)
GFR time (Tg)
Ground-faultprotection
Pre-alarm
(setting by factory side)
Unless specified when ordering the electronic trip relay will be set to in blue.
M type setting dial operation schematic
30
protection use M types)
LOAD CURRENT % IL
PAL P.U. Ip
RESET
TAL
S/I GL
PAL P.U. PAL OUT
1600 A=In max.
IL×1.2 Isd ×1.5
MADE IN JAPAN
MPGT–1ATMODEL
ELECTRONIC TRIP RELAY
TRIP INDICATOR
ALARM
1.0.96
.88.84
.92
1283 A
FINE
90 1007050
3.5 4.5
2.53
4
60403025
XIn XIn XIn
1.05
1.21.1
1.0
LTD P.U. IL1.15
ALARMTRIP
0.20.1
0.5GFR P.U. Ig
0.3
0.50.4
0.10
0.20.3
1520
3.01.5
0.30.8
161210
2
STD P.U. Isd INST P.U. Ii
864
STD LOCK
CT RATING RATED CURRENT In
TEST
(RATED CURRENT MAX)
XIn max.
XIL
s s s
GFR TIME LTD TIME STD TIME
G
AB
E
F
H
M
N
O
P
CD
I
J
K
L
Q
A Trip indicator
PAL indicator
Temperature alarm indicator
Reset button
Load current indication LEDs
LTD current setting dial
LTD time setting dial
LTD time fine setting dial
STD current setting dial
STD time setting dial
STD lock button
INST current setting dial
PAL current setting dial
GFR current setting dial
GFR time setting dial
GFR TRIP/ALARM switch
TEST terminal
BCDEFGHIJKLMNOPQ
31
Electronic trip relay (Special useB type (Special use)
Rated current Max. (!n max) Refer to P25 Table 2.
Adjustable setting range
0.5-0.6-0.7-0.8-0.9-1.0 ×!n max (setting by factory side) 0.8-0.9-1.0 ×!n max (AE4000-SSC)
Non
Non
4-6-8-10-12-16 ×!n ±15%4-6-8-10-12 ×!n ±15% (AE5000-SS)4-6-8-10 ×!n ±15% (AE6300-SS)
Rated current (!n)
Short-time delay
Long-time delay
INST current (!i)Instantaneous
Rated current Max. (!n max)
Rated current (!n) INST current (!i)
Load current indication LEDs
Unless specified when ordering the electronic trip relay will be set to in blue.
B type setting dial operation schematic
32
B type)
LOAD CURRENT % In
INST P.U. Ii
MCRINST
XIn
MADE IN JAPAN
RATED CURRENT
In
B–C0A
=
MODEL
60 80 100 OVER
810 12 16
ELECTRONIC TRIP RELAY
1600 A
64
TEST
NON LTD
NON STD
A
B
C
D
A Load current indication LEDs
INST current setting dial
INST/MCR switch
TEST terminal
BCD
Electronic trip relay accessories
33
Ground fault protection (GFR)
Sometimes the Long-time-delay or Short-time-delayfunctions will not protect a circuit even if there is aground fault of several hundred amps. In which case,the ground fault protection function (GFR) is used. Thesensitivity is selectable in the range of 0.1-0.2-0.3-0.5times the Rated current MAX. (!n max), and the operatingtime is selectable from the range of 0.3-0.8-1.5-3seconds. A control supply is not required for theoperation of the ground fault protection.Note 1: In a 3-phase, 4-wire circuit, ground fault
protection is also possible with a 3 pole breakerand a Neutral CT (NCT) see page 35, 56.
Note 2: The ground fault protection (G) is not available forAE-SS series with the Rated current MAX. (!n max)coming to 315 A or 500 A, or for AE630-SH.
Neutral pole overcurrent protection (NP)
This function protects the neutral pole (4 pole) of thecircuit breaker from overcurrent with S type relay.Neutral overcurrent protection can be set to operateat 100% of the rated current. Load equipment (forexample: computer equipment, DC power supplies,etc) which is liable to generate third harmonic waveforms that may cause more load current to flow inthe neutral pole, which may cause damage, theneutral pole overcurrent protection will preventdamage from occuring.
Earth leakage protection (ER)The earth leakage alarm facility is provided by using a electronic trip relay with earth leakage protection and aexternal ZCT (see page 37, 56.)Even if several amperes of earth leakage current flow, the alarm alone operates but the breaker does not trip.This is therefore suitable when a continuous power supply is required. Should the breaker be required to tripon earth leakage, the above should be used with a SHT.Note 1: The shunt tripping device (SHT) is suitable for 100-250V AC/DC or less.Note 2: Output contact is self-hold type.
The output contact is turned off when the reset button is pressed or control supply is turned off.
Connection diagram (Earth leakage alarm system) Connection diagram (Earth leakage tripping system)
4 pole breaker Current sensor coil
GFR
Electronic trip relay(with ground fault protection)
ER
N2
544
513
L2 L1
BZ
N1External ZCT
SPET relay
Relaycontrol supply
BZ controlsupply
Relaycontrol supply
SHT controlsupply
External ZCTfor ground wire
Earth leakagealarm buzzer
ER
N2714
713
C1C2
L2 L1
N1External ZCT
SPET relayExternal ZCTfor ground wire
SHT
Connection diagram
Same phase
Current sensor coil
Load equipment whichgenerates electric currentof the third harmonicwave form.
Option
Option
34
Temperature alarm (TAL)If the temperature of the main contact rises above a pre-determined level, a LED will light and a relay contact(1a) will energize. This will prevent trouble and increase contact life, a useful preventive maintenance feature.(The control supply and the reset button are used in common with the trip indicator.)
Pre-alarm (PAL)
If the load current of the breaker exceeds the set value, A “PAL” LED lights and a relay output is energized.This is useful in securing a continuous power supply to a important circuit. The operating characteristic shownon the curve is proportional to half of the Longtime-delay tripping characteristic. The relay output is of an autoreset type.
OCR alarm (AL)
The OCR alarm (AL) is a short-time operating switch(1a) for the electrical indication of when the breakertrips due to overcurrent. The AL is an integral part of theelectronic trip relay. Though it operates when thebreaker trips due to the Long-time-delay, Short-time-delay, Instantaneous/MCR, Ground fault protection(GFR), It does not operate when the breaker trips dueto the Earth leakage protection (ER).
Note:Though a control supply is not required for theoperation of the OCR alarm (AL), a self-hold circuitis required since the relay output only operates for0.03 seconds.
Note:When a continuous output signal from the OCRalarm (AL) is required please use the output signalfrom the trip indicator (TI) which is operated by thesame causes as the OCR alarm (AL).
Option
Option
Field test device
The electronic trip relay can be checked without the breaker being connected to the main supply. The breakerwill trip when tested.Y-160 test device is not available for M type relay.
Type Y-160Y-2000
AC100-240V50-60HZ
Test function
Power supply
Test current signal setting
Ammeter –equipped
equippedequippedTime counter
LTD, STD, INST, GFRLTD, STD, INST, GFRPre-alarm
Battery use
• AC100-120V• AC200-240V
6-point setting possible(20%, 50%, 125%, 200%, 500%, 2000%)
10%~2000%(continuously variable)
Option
Electronic trip relay accessories
35
Neutral CT (NCT)
The neutral CT is used for ground fault protection when a 3 pole breader is used on a 3 phase 4 wires system.It should be used together with the electronic trip relay that has the ground fault protection (G) option. (refer toP56)
External ZCT
This option is used to detect several amperes of earth leakage when use in combination with a electronic triprelay that has the earth leakage tripping (ER) option.Two methods are available: The first is where the all load conductors pass through the ZCT. The other methoduses a smaller ZCT through which the supply transformer’s ground wire passes through to earth. (refer to P56)
Type Applicable CT type
AE 630-SS/SH CW-40LM 630A
AE 1000-SS/SH CW-40LM 1000A
AE 1250-SS/SH CW-40LM 1250A
AE 1600-SS/SH CW-40LM 1600A
AE 2000-SS/SH CW-40LM 2000A
AE 2500-SS/SH CW-40LM 2500A
AE 3200-SS/SH
AE 4000-SS, SSC
AE 5000-SS
AE 6300-SS
CW-40LM 3200A
CW-40LM 4000A
CW-40LM 5000A
CW-40LM 6300ACW-40LM 6000A (JIS)
Note: A suitable resistor (0.1 10W) and screened wire (2m) is attached on the product.
Neutral CT
ResistorElectronic trip relay(with ground fault protection )
3 pole breaker
Currentsensor coil
Wiring diagram
N1
N2
Type
Application
Type ZCT163 ZCT323 ZCT324 ZT15A ZT30A ZT40A ZT60A ZT80A ZT100A
External ZCT for load circuits External ZCT for transformer ground wire
Note: A screened wire (2m) is attached on the product.
SHT
ER
SHTcontrol supply
Relaycontrol supply
SPET relay
External ZCT
C2 714N2 N1
L2 L1
713
C1
1. Wiring diagram (load circuit method)
SHT
ER
SHTcontrol supply
Relaycontrol supply
SPET relayExternal ZCT
C2 714 N2 N1
L2 L1
713
C1
2. Wiring diagram (transformer ground wire method)
Option
Option
Circuit diagram of the electronic trip relay
36
Circuit diagram of the electronic trip relay(SPGT)
Operating function of each device
Power supply CTEnergy is supplied for the operation of the overcurrent tripping and ground fault tripping (GFR) function ofthe electronic trip relay.Current sensor coilThe current in each phase flowing through in the breaker is detected. A coreless coil which has goodlinearity is achieved. The integrating circuit integrates the output voltage and provides a signal voltagewaveform which is in proportion with the load current.LTDThis is an effective value detection type which is strong against the distored wave. It has a memory effectfor the overcurrent state. If the electronic trip relay is tripped, the overcurrent memory is reset.Pre-alarmThis is an effective value detection system. It has a memory effect for the overcurrent state.STD/INSTThis is a peak value detection system, and is suitable for short time operation.Ground fault circuitThe signals in each phase are summed in the vector mode in order to detect the ground fault value.Trip indicator circuitFault cause and pre-alarm is indicated with control power supply.OCR alarm circuit1 pulse 30ms signal output without control power supply.
8
7
6
5
4
3
2
1
N2
N1
N
OCR alarmcircuit
L1L2L3
544
554
524
PAL OUT
513
534
30ms1 pulse
97
98
Trip indicatorcircuit
PAL pick-up LED
Load LED
STD
LTD
Watch-dogtimercircuit
INST.circuit
Pha
sese
lect
ion
sam
plin
g
L
S/I
G
Settinginput
Ground faultcircuit
I/O
Acc
umu-
lato
rA
/Dco
nver
tor Overload
/PAL
S/W
S/W
S/WPAL
LTD
STD/INST
GFR
Controlpowercircuit
Triggercircuit
Custom IC
Electronic trip relay
Characteristicsetting part
CPU
Trip coil
Peak valueconversion/Max. phaseselectioncircuit
GroundfaultIntegration/compositioncircuitNCT, ZCT input
Lower terminals
Test
con
nect
or
Cur
rent
sen
sor
coil
Pow
er s
uppl
y C
T
Upper terminals
Rec
tifie
rsi
gnal
circ
uit
Inte
grat
ing
circ
uit
Rec
tifie
rci
rcui
t
Pow
er s
uppl
yci
rcui
t
Operating characteristics (General use)
37
% of uninterrupted current (!U)% of rated current (!n)Current
% of rated current MAX. (!n max)
Long time delay pre-alarmShort time delay/instantaneous
Ground faultCharacteristics from the factory
Adjustable characteristics
Ope
ratin
g tim
e (s
econ
ds)
Maximum breaking time(In case ofAE4000-SS~AE6300-SS,it is 0.05s.)
INST current (Ii)4-6-8-10-12-16 In±15%4-6-8-10-12 In±15% (AE5000-SS)4-6-8-10 In±15% (AE6300-SS)
with MCR (AE-SS series only)
GFR time (Tg)0.3-0.8-1.5-3s±20%
STD time (Tsd)0-0.1-0.2-0.3-0.4-0.5s±20%
STD current (Isd)2-3-4-6-8-10 In±15%
LTD time (TL)12-25-50-100-150s±20%
GFR current (Ig)0.1-0.2-0.3-0.5 In max±20%
0.2-0.3-0.5 In max±20%(AE4000-SSC~AE6300-SS)
PAL current (Ip) 0.7-0.8-0.9-1.0-OVER Iu±10%
PAL time (Tp)TL/2±20%
5000200202
500
400
300
200
60
500505
1
2
3
5
4
10
20
30
40
50
1000
100
100010010
.04
.05
.1
.2
.3
.4
.5
.01
.02
.03
125 1600 2000
S type
Operating characteristics (Generator protection use)
38
M typeO
pera
ting
time
(sec
onds
)
% of Long time delay current (!L)% of rated current(!n)Current
% of rated current MAX.(!n max)
pre-alarmLong time delay/Short time delay/instantaneous
Ground faultCharacteristics from the factory
Adjustable characteristics
PAL time (Tp)TL/2±20%
LTD time (TL)15-20-25-30-40-60s±20%
LTD current (IL)1.0-1.05-1.1-1.15-1.2 In±5%
PAL current (Ip) 0.84-0.88-0.92-0.96-1.0 IL±10%
GFR current (Ig)0.1-0.2-0.3-0.5 In max±20%
0.2-0.3-0.5 In max±20%(AE4000-SSC~AE6300-SS)
STD current (Isd)2-2.5-3-3.5-4-4.5 In±15%
STD time (Tsd)0-0.1-0.2-0.3-0.4-0.5s±20%
GFR time (Tg)0.3-0.8-1.5-3s±20%
INST current (Ii)4-6-8-10-12-16 In±15%4-6-8-10-12 In±15% (AE5000-SS)4-6-8-10 In±15% (AE6300-SS)
Maximum breaking time(In case ofAE4000-SS~AE6300-SS,it is 0.05s.)
20001600120
.03
.02
.01
.5
.4
.3
.2
.1
.05
.04
10 100 1000
100
1000
50
40
30
20
10
4
5
3
2
1
5 50 500
60
200
300
400
500
2 20 200 5000
39
MAX. time of let-through current and B type relaycharacteristics
B-COA
% of Rated currentCurrent
time(
seco
nds)
Characteristics from the factory Adjustable characteristics
INST current (Ii)4-6-8-10-12-16 In±15%4-6-8-10-12 In±15%(AE5000-SS)4-6-8-10 In±15%(AE6300-SS)
Maximum breaking time(In case ofAE4000-SS~AE6300-SS,it is 0.05s.)
Max.Ratedshort timecurrent (1s)
Max.time of let-through current
External OCR max. setting
500020020
500400
300
200
60
500505
1
2
3
54
10
20
30
4050
1000
100
100010010
.04
.05
.1
.2
.3
.4
.5
.01
.02
.03
1600 2000
(Not available for AE-SH)
Tripping characteristics setting
40
Setting procedure
1.A small flat-tipped screwdriver is prepared.
2.Insert the flat-tipped screwdriver into the opening of theelectronic trip relay cover. Then, lightly press thescrewdriver leftward, and the cover will open.
3.There are 3 types of switches for setting up the requiredtripping characteristics and they should be used asfollows:-
qStep adjustable typeA rotary switch is used. Do not stop the switch betweensteps as it would be the same setting value as thatassociated with the nearest step line. (Operate theswitch with a torque of 0.1N•m or less.)
wSlide switch typeSlide the switch to the left or right. (operate the switchwith a force of 10N or less.)
ePushbutton typeA pushbutton is provided for termporary operation.Press it with a force of 10N or less. Before operatingmake sure that the push-button is in its initial state.
4.When the characterisitics have been set, they should bechecked using a field tester.
5.Two methods for sealing the cover are provided, selecteither from the following:
qStick the sealing label on the opening of the electronictrip relay cover, and close the cover. The cover can notbe opened unless the sealing label is removed.Note: The sealing label is supplied with the relay.
wSeal the electronic trip relay cover by using the leadsealing hole at the bottom of the cover.
Operating hole for Resetting
Press the screwdriver in the direction of the arrowto open the cover.
6mm
max
.0.
8mm
max
.
Side view of the flat tip
XInXInXInXIu
XIn max
XIn max
CURRENT Iu
RATED CURRENT InIn max=
(CT RATING)
.96
1.0
0.70.8
0.60.5
0.91.0
RATED CURRENT MAX.
60 80 100 OVER
INST MCRSTD LOCK
0.80.7
0.9
PAL P.U. IpOVER1.0
.92.84
.80
INST P.U. In
46
8
UNINTERRUPTED
4
STD P.U. Isd
32
.88 10 12 1686 10
0.3
GFR P.U. Ig0.5
0.10.2
TRIP ALARM
LOAD CURRENT % Iu
1600 A
q Step type e Push-button type w Slide switch type
Coverw Lead sealing hole
q Sealing label
Operating hole for Resetting
41
How to adjust the trip relay
AE-SS has very intelligent relay with multi functions.
But sometime, it seemed to be difficult to adjust it.
This report can help you to solve such questions.
<Front view of the relay>The relay is set as follows.
Here!n max = Maximum rated current!n = Rated current!u = Uninterrupted currentLTD TIME = Long time delay tripping time!sd = Short time delay pick-up currentSTD TIME = Short time delay tripping time!i = Instantaneous pick-up current!p = Pre-alarm (PAL) operating current!g = Ground fault pick-up currentGFR TIME = Ground fault operating time
TEST
MADE IN JAPAN
MODEL
SPGT–C1A
ELECTRONIC TRIP RELAY
STD TIMELTD TIMEGFR TIME
Isd × 1.5Iu × 2
sss
XInXInXInXIu
XIn max
XIn max
CURRENT Iu
RATED CURRENT InIn max=
(CT RATING)
PAL OUTPAL P.U.
.96
1.0
0.70.8
0.60.5
0.91.0
RATED CURRENT MAX.
60 80 100
L GS/I
OVER
RESET
INST MCRSTD LOCK
0.80.7
0.9
PAL P.U. IpOVER1.0
.92.84
.80
INST P.U. Ii
46
8
UNINTERRUPTED
4
STD P.U. Isd
32
.88 10 12 1686 10
0.80.3
1.53.0 100
502512
150 0.30.2
00.1
0.40.5
0.3
GFR P.U. Ig0.5
0.10.2
TRIP ALARM
LOAD CURRENT % Iu
ALARM
TRIP INDICATOR
1600 A
Tripping characteristics setting (2/3)
42
TEST
MADE IN JAPAN
MODEL
SPGT–C1A
ELECTRONIC TRIP RELAY
STD TIMELTD TIMEGFR TIME
Isd × 1.5Iu × 2
sss
XInXInXInXIu
XIn max
XIn max
CURRENT Iu
RATED CURRENT InIn max=
(CT RATING)
PAL OUTPAL P.U.
.96
1.0
0.70.8
0.60.5
0.91.0
RATED CURRENT MAX.
60 80 100
L GS/I
OVER
RESET
INST MCRSTD LOCK
0.80.7
0.9
PAL P.U. IpOVER1.0
.92.84
.80
INST P.U. Ii
46
8
UNINTERRUPTED
4
STD P.U. Isd
32
.88 10 12 1686 10
0.80.3
1.53.0 100
502512
150 0.30.2
00.1
0.40.5
0.3
GFR P.U. Ig0.5
0.10.2
TRIP ALARM
LOAD CURRENT % Iu
ALARM
TRIP INDICATOR
1600 A
!n =0.8×!n max
=0.8×1600=1280A
!sd=3×!n
=3×1280=3840A
!i =12×!n
=12×1280=15360A
!n max=1600A
!u =0.9×!n
=0.9×1280A=1152A
!g =0.1×!n max
=0.1×1600=160A
GFR TIME=0.8s
!p =0.8×!u
=0.8×1152=921.6A
at!g×1.5=160×1.5= 240A
LTD TIME=100sat!u×2=1152×2= 2304A
STD TIME=0.3sat!sd×1.5=3840×1.5= 5760A
at!u×2=1152×2= 2304A
PAL pick-up time=50% of LTD time=50s
( )
(
(
)
)
( )
Actual settings are as following table.
LTD TIME
STD TIME
PAL pick-up time
=1600A
=1280A
=1152A
=100s±20% (at 2304A)
=3840A±15%
=0.3s±20% (at 5760A )
=15360A±15%
=921.6A±10%
=50s±20% (at 2304A)
=160A±20%
=0.8s±20% (at 240A)
–
!i
!p
GFR TIME
!g
!sd
!n max
!n
!u
How to get the current settings and operating times
<Actual setting>Current settings and operating times are calculated.
43
How to get the current settings and operating times
<Characteristic curve>In above settings, operating characteristics are set as follows.
Current (%)
Characteristic curve
INST current (Ii) setting range
GFR time (Tg) setting range
STD time (Tsd) setting range
STD current (Isd) setting range
LTD time (TL) setting range
GFR current (Ig) setting range
PAL current (Ip) setting range
Ope
ratin
g tim
e (s
)
20001600125
.03
.02
.01
.5
.4
.3
.2
.1
.05
.04
10 100 1000
100
1000
50
40
30
20
10
4
5
3
2
1
5 50 500
60
200
300
400
500
20 200 5000
Tripping characteristics setting (3/3)
44
Actual operating characteristics are shown is following curve by %-A figure.
Characteristic curve
X0.8
X0.1
X3
X12
TL=100s
TP=50s
0.8s
0.3s
1536057603840230414401209.6921.6240160
500
400
300
200
60
1
2
3
5
4
10
20
30
40
50
100
.04
.05
.1
.2
.3
.4
.5
.02
.03
500
400
300
200
60
1
2
3
5
4
10
20
30
40
50
1000
100
.04
.05
.1
.2
.3
.4
.5
.02
.03
current (A)
oper
atio
n tim
e (s
)
Wiring diagram (According to EN50005)
45
Internal wiring diagram
See Table 1
Xa
TR!P
X
1500V
(Dielectric voltage)
2000V
(Dielectric voltage)
342
341 331 321 311
L3 L2 554 534 524 98344 332 334 322 324 312 314
L1 564 544 513 97
AL
TAL GFRorER
CL CL CL CL
PAL STD/!NST
LTD
Electronictrip relay
Main circuit Cell switches Electronic trip relay
Powersupply CT
Currentsensor
coil
Reset
only
ope
rate
30m
s
13 Auxiliary switch contact a
413 414
Auxiliary switch contact b
Charged signal a
Motor charging
Closing coil
Shunt trip
Under voltage trip
Earth leakage trip output (for SHT trip)
L1 L2 L3
Cell switch
Electronic relay unit control power supply
564 Temperature alarm contact
554 Pre-alarm indication contact
Trip indication contact
OCR alarm contact
For N-pole CT or external ZCT connection
Applicable power supply
(Table-1)
Voltage(V) Input terminal
Com
mon 100 – 120 L1 , L2
L1 , L2
L1 , L3200 – 240
100 – 12524 – 60
DC
AC
Terminal Symbols~
713 714
524 544
54
U1 U2
A1 A2
C1 C2
J1 J2
97 98
N1 N2
M1 M211 ~ 52
~
311 344~
The following wiring diagram shown accessories fully equipped.
46
See P19
2000V
(Dielectric voltage)
OFF
OFF
ON
ONCharge
M1 N1 713
UVT SHT CC
J1 C1 A1
M2 N2 714 J2 C2 A2
U1 413 51 41 31
U2 414 52 42 32
21 11 53 43
22 12 54 44
33 23
34 24 14
M
AX AX AX AX AX AX AX AX AX AX
SB
C
SB
C
SB
C
SB
C
SB
C
13
See P35
SHT
Under voltage trip Electrical operation circuit Charged signal Auxiliary switches
M Motor
CC Closing coil
SHT Shunt trip device
UVT Under voltage trip coil
AL OCR alarm (30ms)
LTD Long-time-delay trip indication LAMP
STD/INST Short-time-delay or instantaneous trip indication LAMP
– – – Wiring by the user
Wiring completed by the factory
X Self-hold relay
TAL Temperature alarm indication LAMP
PAL Pre-alarm indication LAMP
GFR or ER Ground fault trip or earth leakage indication LAMP
Accessory Symbols
The Fig. below is the wiring diagram at fully equipped state. CL and SBC are accessories for draw-out type. On the draw-out type, the control circuit terminal block should be
moved to the left or right by 5mm, after cables connecting. When usin coil loads such as DC magnetic switch, etc. as operating
voltage in the peripheral circuits, install diodes, surge absorbers,etc. as a countermeasure against the surge (counter electromotiveforce) at the time of switching.
Because of pumping prevention is not performed, do not use AXbcontact for a cut-off of closing coil.
Outline dimensions (1/5)
47
Drawout type AE630-SS~AE1600-SS
Front view Side view
Rear view
Main circuit terminal dimensions
85 85 85 85 858585 8585
50
4P 3P4P 3P3P4P
Front terminalVertical terminalHorizontal terminal
Neutralpole
Neutralpole
Neutralpole
Operating panel center Operating panel center Operating panel center
Outlineof breaker
Outlineof breaker
Outlineof breaker
61
57
9253
15
132
145
15
50
117
100
50
66
9215
370
132
15
311
23
368
40
48
452
15
25
51
3534
0430
40
228
235(150)150
59 149
42.5
200
234(149)
366
15
172
Earth terminalM8 screw
4P3P
Neutral pole
Operating panelcenterUVT controller, etc
Lifting hook hole
Front face ofcontrol terminal M3.5 self-up screw
Inside of the panel(thickness1.6~3.2)
Panel
Fully drawoutposition
Test
Disconnected
Aperture fordrawout handle
Control terminals M3.5 self-up screw
4-f14
Horizontalterminal
Verticalterminal
Frontterminal
220
: Mounting pitch The numerals shown in parentheses are for 3 poles.
50
15
25
38
2-f13
50
15
25
38
2-f132-f13
38
15
25 50
Horizontal terminal Vertical terminal Front terminal
Connecting areaConnecting area Connecting area
48
Drawout type AE2000-SS~AE3200-SS
Front view Side view
Rear view
Main circuit terminal dimensions
Earth terminalM8 screw
Neutral pole
Operating panelcenterUVT controller, etc
Lifting hook hole
Front face ofcontrol terminal M3.5 self-up screw
Inside of the panel
Panel
Fully drawoutposition
Test
Disconnected
Aperture fordrawout handle
Control terminalsM3.5 self-up screw
Horizontalterminal
Verticalterminal
Frontterminal
(thickness1.6~3.2)
324(194)23959
42.5 40
325(195)243
228
17215
366
430
340
35
51
25
15
452
48
40
368
23
311
132
370
92
61
T T
5337
0
132
92
57 T
125
125
182
67
83
25
20
Dimension of TType
AE2000,2500-SS
AE3200-SS
4P3P
4-f14200 220
TT : Mounting pitch
The numerals shown in parentheses are for 3 poles.
Front terminalVertical terminalHorizontal terminal
Neutral pole Neutral pole Neutral pole
Operating panel center Operating panel center Operating panel center
Outlineof breaker
Outlineof breaker
Insulationblock
130
23
130130
W
3P4P
130 130 130
T
130130130
23
W
23
4P 3P4P 3P
Horizontal terminal Vertical terminal Front terminal
Connecting areaConnecting area Connecting area
AE2000,2500-SS
AE3200-SS
Type
103
95
34
15
W
2525
4-f13
25
38
15
2525
5-f13
2525
125
25
4-f13
2525
15
38
W
Dimension of W
49
Outline dimensions (2/5)
Drawout type AE4000-SSC (3P)
Only vertical connection is availableM3.5 self-up screw
L,R pole:T10 W150 4 piecesC pole :T10 W150 3 pieces
Aperture fordrawout handle
4-f14
151
125
125
6718
2 370
340
368
35
51
311
366
172
452
23220
40
48
15
25
430
15
324
200
23959
42.5
40325243
228 Connection bus bar
Operating panelcenterUVT controller, etc Control terminals
: Mounting pitch
Lifting hook hole
Front face ofcontrol terminal M3.5 self-up screw
Test
Disconnected
Earth terminalM8 screw
Inside of the panel(thickness1.6~3.2)
Panel
Fully drawoutposition
53
25
2525
5-f13
2525
125
Connecting area
Front view Side view
Rear view
Main circuit terminal dimensions
10
10
493
90
42.5
195195
70
10
10
Operating panel center
Outline of breaker
Insulation block
50
Drawout type AE4000-SS~AE6300-SS
Earth terminalM8 screw
Neutral pole
Operating panelcenter
UVT controller, etcLifting hook hole
Front face ofcontrol terminal M3.5 self-up screw
Inside of the panel (thickness1.6~3.2)
Panel
Fully drawoutposition
Test
Disconnected
Aperture for drawout handle
Fixing bolts2-M12
Drawout handleradius 100
Control terminals M3.5 self-up screw
44
530
42.5
228
184
90
28 28588.5(458.5)373.5
610(480)395
345.5
4P3P
4-M12
40048
0
7534
0
48
368 123
23220
17240
51
35
311
420
182
125
125
117
15
366
Insulation block
M12 weld nut
Mounting angle
15
: Mounting pitch The numerals shown in parentheses are for 3 poles.
5-f13
125
2525
2525
53
25
Connecting area
Front view Side view
Rear view
Main circuit terminal dimensions
W
431.5
T25
196
561.5(431.5)
382
262 262
42.5
14
The mounting angle should beprepared by the customer.
Operating panel center
Outline of breaker
2-M12 for mounting
Mounting angle (SUS)Neutralpole
4P 3P
Type
105
100
Dimension of W
25
20
Dimension of T
AE6300-SS
AE4000,5000-SS
Outline dimensions (3/5)
51
Drawout type AE630-SH~AE3200-SH
Earth terminalM8 screw
Neutralpole
Operating panelcenterUVT controller, etc
Lifting hook hole
Front face ofcontrol terminal M3.5 self-up screw
Dimensions from inside of the panel
Panel
Fully drawoutposition
Test
Disconnected
Aperture fordrawout handle
Drawouthandleradius100
Control terminals M3.5 self-up screw
Fixing bolt2-M12
Horizontalterminal
Verticalterminal
Frontterminal
(thickness1.6~3.2)
Dimension of TType
42.5
350(220)265
228
33
243 325(195)
200
40
134
4-f14
T
430
340
25
15
35
51
370
132
T
92
23
61
202
398
396
220
40
48
452
341
15
83
6718
2
125
125
T57
9213
2 370
53
TT
AE3200-SH
AE630~2500-SH 20
25 : Mounting pitch
The numerals shown in parentheses are for 3 poles.
Front terminalVertical terminalHorizontal terminal
Neutral pole Neutral pole Neutral pole
Operating panel center Operating panel center Operating panel center
Outlineof breaker Outline
of breaker
Insulationblock
130
23
130130
W
4P 3P
23
W
130130130
3P4P
23
130 130 130
T
3P4P
Horizontal terminal Vertical terminal Front terminal
Connecting areaConnecting area Connecting area
Type
103
95
Dimension of W
W
38
15
2525
4-f13
25
125
2525
5-f13
2525
15
38
25
4-f13
2525
W
15
34
AE3200-SH
AE630~2500-SH
Front view Side view
Rear view
Main circuit terminal dimensions
52
Fixed type AE630-SS/SH~AE3200-SS/SH
4-f14
268
227(142)142
255(170)
241(156)
228
156
17038
4-f14
317
268
232
38 260
246
228
331(201)
345(215)
4P3P
Neutral pole
Neutral pole
Control terminalM3.5 self-up screw Control terminal M3.5 self-up screw
Operating panelcenter Operating panel
centerUVT controller,etc
UVT controller,etc
EarthterminalM8 screw
EarthterminalM8 screw
4P3P
AE630~1600-SS AE2000~3200-SS AE630~3200-SH
AE2000~3200-SS
AE630~1600-SS
Type Dimension of T
15
20
: Mounting pitch The numerals shown in parentheses are for 3 poles.
144
132
722020
32
7
70
31Panel Panel
288
31
40
7
17
4-f13
2525
38
95
17
2-f13290
340
175
40
88
410
350
5
288
340
290
175
40
14488
410
350
5
T 7213
2
T
25
38
25 50
AE630~3200-SS AE630~3200-SH
Inside of the panel (thickness1.6~3.2)
EarthterminalM8 screw
EarthterminalM8 screw
Inside of the panel (thickness1.6~3.2)
Connectingarea
Connectingarea
AE2000~3200-SSAE630~ 3200-SH
AE630~ 1600-SS
85
2323
514(384)
959550
8585 130 130 130130 130 130
4P 3P3P4P
Operating panel center Operating panel center Operating panel center
Insulationblock
Neutralpole
NeutralpoleNeutral
pole
Outlineof breaker
Outlineof breaker
AE630~1600-SS
4P 3P
AE2000~3200-SS AE630~3200-SH
Side view Main circuit terminal dimensions
Front view
Rear view
Outline dimensions (4/5)
53
Fixed type AE4000-SSC (3P)
4-f14
317
268
232
38 260
246
228
331
345
Control terminal M3.5 self-up screw
Operating panelcenter
UVT controller,etc
EarthterminalM8 screw
: Mounting pitch
Only vertical connection is available
125
288
125
934
0
7
88 144
414
354
182
72.5
136290
31
40
175
25
53
125
25
5-f13
2525
25
Connection bus bar
Per 1 pole: T10 W150 3 pieces (All poles)
PanelEarthterminalM8 screw
Inside of the panel(thickness1.6~3.2)
Connectingarea
42.5
195 195
10
70
10
Operating panel center
Outline of breaker
Side view Main circuit terminal dimensions
Front view
Rear view
54
Fixed type AE4000-SS~AE6300-SS
4-f14
3P 4P
581.5(451.5)
268
366.5
38 394
380.5
228
595.5(465.5)
609(479)
Control terminal M3.5 self-up screw
Operating panelcenter
UVT controller,etc
Earth terminalM8 screw
: Mounting pitch
125
57
288
125
934
0
7
88 144
414
354
182
72.510
136290
31
40
175
Bus bar
Panel Earth terminalM8 screw
Inside of the panel (thickness1.6~3.2)
25
53
125
25
5-f13
2525
25
Connecting area
Front view Side view
Rear view
Main circuit terminal dimensions
42.5
197 262 262
100
2020
Operating panel center
Outline of breaker
Neutral pole
3P4P
Outline dimensions (5/5)
55
Panel-cut, Drawout handle, Terminal adapter
f22
200 16
9
max 173
200
f12
7.7
405
345
235
295
381
271
247235
324
A
357
A
345
8-f7
245AE4000~6300-SS
179AE4000-SSC (FIX)
195
175
Dimension of AType
Operating panel center
Breakermounting frame
OutlinePanel-cut dimensions
Breaker
Operating panel center
Breaker mounting frame
Drawout Type
Fixed Type
53
D
25
34
15
D
25 25 25
C
T
37.5
50
100
15 15 15
2525
25
115
T
T
125
2525
2525
38
38
15
15
15
50
25
25
100
38
38
25
Mtg.holesf13
f13
f13
AE630~ 1600-SS
AE2000~3200-SSAE630~3200-SH
Con
nect
ing
area
Connecting area
Connecting area
25
25
20
20
20
15
15
15
Dimension of T
103
95
95
95
95
95
50
50
50258.5
145
145
258.5
Fixedtype Down side
Up side
Drawout type
Fixedtype
Drawout type
Fixedtype
Drawout type
Down side
Down side
Up side
Up side
AE3200-SH
AE630~2500-SH
Dimension of DDimension of C
145
258.5
145
145
145
AE3200-SS
AE2000,2500-SS
AE630~1600-SS
Type
25
20
Dimension of TType
AE2000,2500-SS AE630~2500-SH
AE3200-SS AE3200-SH
AE630~1600-SS AE2000~3200-SSAE630~3200-SH
42
225
45BA
C
Type
AE2000~3200-SSAE630~3200-SH
AE630~1600-SS
Operating panel center
3
310
180 225
225 23
23
01352204
3 135 135 0
CB
Dimensions
A
Numberof poles
(Side view) (Rear view)
Dimensions
4Panel
Neutralpole
Outline of breaker
Panel-cut dimensions Door frame panel-cut dimensions Drawout handle dimensions
Vertical terminal adapter Front terminal adapter
Panel-cut dimensions (Breaker rear side)
56
Neutral CT (NCT), External ZCT
CW40-LM 5000~6300ACW40-LM 630~4000A
M
87
66
L
55
38
K
11
9
J
68
51CW40-LM 630~2000A
CW40-LM 2500~4000A 162 4 219 160 31 48 192 212
97 5.5 137 105 16.5 28 122 142
A B C D E F G H
C
102
40
79
4
4021
7
298
328
285
88
251
H
G
FE
M
K
L
J
D
BA
KL
Dimensions(mm)
Slit for M8 bolt
Terminals M5 screw Terminals M5 screw
KL
Slit for M10 bolt
K
B200
108
ZCT163
ZCT323
ZCT324
230
370
500 108
C
323 250
460 400
600 550
47
E
47
48
DBA
60
C
D
72
92
E
A
Slit for M8 bolt
Dimensions(mm)
Terminals M3.5 screw
External ZCT for transformer ground wire
Neutral CT (NCT)
External ZCT for load circuits
C
D
7.7
C
DG
ZT60A
ZT80A
ZT100A
140 60 73 150 46
160 80 82 169 48
185 100 93 190 50
A B C D E
40
30
ZT40A
ZT30A
85 43 92 81 40 100 50
25
H
50
70
G
90
15
F
30
46
E
66
62
D
82
29
3768
ZT15A
B
15
A
48
C
A
90
E
70
1230
100
AE 52
28
40H
3
B
F
2
B
Slit for M5 screwSlit for M5 screw
Dimensions(mm)Dimensions(mm)
Terminals M3.5 screwTerminals M3.5 screw
57
Technical information (1/3)
For the terminal connections, use M12 bolts, washers and springwashers.In order to prevent increased contact resistance due to humidity,silver plating of the contact surface of the conductor which isconnected to the terminal of the breaker, is recommended. Alsoclean the contact surface, and securely connect them at a suitabletorque.
1Pre-cautions when making connections
Silver platedconductor
Terminal
15~23mm
25Standard Tightening Torque
Screw size
M12
Tightening torque (N • m)
40~50
Since fault current flowing through theconductors cause large electromagneticforces, the conductors should be securedfirmly, using the values in Table on the rightas a reference. Max busbar supportingdistance nearest to ACB is less than 200mm.
Electromagnetic force in N per 1m conductor(in the case of three phase short circuit)
Type (A)AE630-SS
AE1600-SS
AE2000-SS
AE3200-SSAE–SH
AE4000-SS
AE6300-SS
Conductor distance (mm)
30 (0.2)
Prospective fault currentkA (pf)
85
7500 4500 2300
42 (0.2) 14600 8900 4500
50 (0.2) 20800 12500 6300
65 (0.2) 35100 21200 10600
85 (0.2) 60200 36200 18100
100 (0.2) 50100 25100
130 (0.2) 84700 42400
130
AE4000-SSC
3400
6700
9400
15900
27200
195 262
(N)
When selecting conductors for connection to a SeriesAE breaker, ensure that they have a sufficient currentcapacity, refer to Table on the right.
Conductor Size (IEC-60947-1 ; 40°C Ambient Temp., Open air)
Rated current
Max. (A)
Connecting conductors (copper bus bar)
ArrangementWith long surface vertical
With long surface vertical
With long surface verticalWith long surface vertical
With long surface verticalWith long surface vertical
With long surface verticalWith long surface verticalWith long surface vertical
With long surface vertical
2 40 5
Quantity Conductor size(mm)
630
2 60 51000
2 80 51250
2 100 51600
3 100 52000
4 100 52500
3 100 103150(3200) 1
4 100 104000 2
4 150 105000
4 200 106300
1.
2.
The temperature rise of rated current 3200A conforms to the requirement of IEC 60947-1 for the connecting conductor size of a rated current of 3150A.In case of more then 3200A, conductor sizes are not given in IEC 60947-1.In case of AE-4000-SSC, refer to P49, 53.
AE–SSAE–SH
Bus bar
Fixing support
Max.200mm
58
When a short-circuit current is interrupted, hot gasblows out discharged from the exhaust port of the arcextinguishing chamber, so provid a clearance as shownin the following table. On the fixed type, maintenance is possible with
following clearance.
2Line side insulation clearance
If under ordinary conditions the following normalworking conditions are all satisfied, the AE Series aircircuit breaker may be used unless otherwise specified.1. Ambient air temperature
A range of max. +40˚C to min. –5˚C is recommended.However, the average over 24 hours must notexceed +35˚C.
2. Altitude2,000m (6,600 feet) or less
3. Environmental conditionsThe air must be clean, and the relative humidity 85%or less at a max. of +40˚C. Do not use and store inatmospheres with sulfide gas, ammonia gas etc.(H2S q 0.01ppm SO2 q 0.1ppm NH3 q a few ppm.)
4. Installation conditionsWhen installing the AE Series air circuit breaker,refer to the installation instructions in the catalogueand instruction manual.
5. Strage temperatureA range of max. +60˚C to min. –20˚C is recommendedto store. However, the average over 24 hours must notexceed +35˚C.
6. ReplacementApprox. 15 years.Please refer to the instruction manual.
3Service conditions
Dimensions
Type
AE630-SS
AE3200-SS
AE4000-SSC
AE4000-SS
AE6300-SS
AE-SH
Applicable voltage AC600V or less AC660V,690V AC690V or less
Fix type
Drowout type
A 0(Note 1) 100(Note 1) 200(Note 1)
B 50(Note 3) 50(Note 3) 50(Note 3)
C 162 162 –
D 50(Note 2) 50(Note 2) 200
A 0 100 200(Note 1)
B 50(Note 3) 50(Note 3) 50(Note 3)
C 240 240 –
D 50(Note 2) 50(Note 2) 200
300mm or more clearance is necessary to inspect the arc-extinguishing chamber and contacts.The wiring space reguired for the control terminal block.In case dimension B becomes larger when the UVT controller, the mechanical interlock, door interlock, etc, are installed.
Note 1 :
Note 2 :
Note 3 :
(mm)
A
BB
Sideplate
CAD
Mountingsurface
Electrical equipment, appliances and screen
In the case of special service condition, modified aircircuit breakers are available. Please specify whenordering. Service life may be shorter depend on serviceconditions.1. Special environmental conditions
If it is used at high temperature and/or high humidity,the insulation durability and other electrical/mechanicalfeatures may deteriorate. Therefore, the breakershould be specially treated. Moisture fungus treatmentwith increased corrosion-resistance is recommended.Since some parts may pose problems due tocorrosion in the environments where corrosive gasresults from the corrosion, the increased Extra-corrosion proof specifications is recommended.
2. Special ambient temperatureIf the ambient temperature exceeds +40˚C, theuninterrupted current rating will be reduced. Sincethe reduction value is different depending on theapplicable standard, refer to P60.
3. Special altitudeIf it is used at the 2,000m or higher the heat radiationrate is reduced decreasing the operating voltagerating, continuous current capacity and breakingcapacity. Moreover the durability of the insulation isalso decreased owing to the atmospheric pressure.Apply for further detail.
1 Normal service condition 2 Special service conditions
Technical information (2/3)
59
4Internal resistance, reactance and power consumption (per pole)
Type Connection Internal resistance (mΩ)
Reactance(mΩ)
Power consumption(W)
AE630-SSFixed type 0.028 0.059 11
Drawout type 0.042 0.089 17
AE630-SHFixed type 0.020 0.047 8
Drawout type 0.030 0.071 12
AE1000-SSFixed type 0.026 0.060 26
Drawout type 0.040 0.091 40
AE1000-SHFixed type 0.018 0.047 18
Drawout type 0.028 0.071 28
AE1250-SSFixed type 0.024 0.060 38
Drawout type 0.038 0.091 60
AE1250-SHFixed type 0.016 0.047 25
Drawout type 0.026 0.071 41
AE1600-SSFixed type 0.016 0.063 41
Drawout type 0.030 0.095 77
AE1600-SHFixed type 0.014 0.047 36
Drawout type 0.024 0.071 61
AE2000-SSFixed type 0.010 0.047 40
Drawout type 0.020 0.071 80
AE2000-SHFixed type 0.012 0.047 48
Drawout type 0.022 0.071 88
AE2500-SSFixed type 0.008 0.047 50
Drawout type 0.018 0.071 113
AE2500-SHFixed type 0.010 0.047 63
Drawout type 0.020 0.071 125
AE3200-SSFixed type 0.008 0.048 72
Drawout type 0.014 0.072 143
AE4000-SSCFixed type 0.008 0.048 128
Drawout type 0.014 0.072 224
AE4000-SSFixed type 0.010 0.038 160
Drawout type 0.013 0.062 210
AE5000-SSFixed type 0.009 0.038 225
Drawout type
AE6300-SSFixed type
0.011 0.062 275
Drawout type
0.008 0.038 318
0.0085 0.062 340
The above values are applicable for one pole.
AE3200-SHFixed type 0.009 0.048 92
Drawout type 0.016 0.072 164
60
5Deratings by ambient temperature
Standard
JISC8372(Standard : 40°C)
IEC60947-2BS
(Standard : 40°C)
NK(Standard : 45°C)
LR,AB,GLDNV,BV
(Standard : 45°C)
Ambienttemperature
40°C
45°C
50°C
55°C
60°C
40°C
45°C
50°C
55°C
60°C
45°C
50°C
55°C
60°C
45°C
50°C
55°C
60°C
AE630-SSAE630-SH
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
AE1000-SSAE1000-SH
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
AE1250-SSAE1250-SH
1250
1250
1250
1200(1250)
1150(1250)
1250
1250
1250
1250
1200(1250)
1250
1250
1200(1250)
1150(1250)
1250
1250
1250
1200
AE1600-SSAE1600-SH
1600
1600
1500(1600)
1450(1600)
1400(1600)
1600
1600
1600
1550(1600)
1500(1600)
1600
1500(1600)
1450(1600)
1400(1600)
1600
1600
1550(1600)
1500(1600)
AE2000-SSAE2000-SH
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
AE2500-SSAE2500-SH
2500
2500
2500
2350
2250
2500
2500
2500
2450
2350
2500
2500
2350
2250
2500
2500
2450
2350
AE3200-SSAE3200-SH
3200
3200
3000
2900
2800
3200
3200
3200
3000
2900
3200
3000
2900
2800
3200
3200
3050
2900
AE4000-SS
4000
4000
4000
4000
4000
4000
4000
4000
3900
3750
4000
4000
4000
4000
4000
4000
3900
3750
AE5000-SS
5000
5000
5000
4900
4700
5000
5000
5000
5000
4750
5000
5000
4800
4600
5000
5000
5000
4750
AE6300-SS
6000
5800
5600
5450
5250
6300
6300
5750
5500
5200
5700
5500
5300
5100
6300
5750
5500
5200
Note : The figures in ( ) in the above Table indicate reduced current values exclusive to AE-SH series.
(A)
AE4000-SSC
3600
3500
3350
3200
3050
4000
3800
3650
3500
3300
3500
3350
3200
3050
Technical information (3/3)
61
Selective interrupting combinations tableAE-SS Series air circuit breakers provide easy selective co-ordination with branch circuit breakers.For selective co-ordinations, refer to the following table.
Main circuit breaker AE-SSBranchcircuit breaker
Unit breaking capacity
NF
-S •
MB
NF
-C
NF30-SPMB30-SPMB50-CPNF50-SPNF60-SPMB50-SPNF50-HPNF60-HPNF50-HRPNF100-SPNF100-SEPMB100-SPNF100-HPNF250-SPNF250-SEPMB250-SPNF250-HPNF400-SPNF400-SEPNF400-HEPNF400-REPNF630-SPNF630-SEPNF630-HEPNF630-REPNF800-SEPNF800-HEPNF800-REPNF50-CPNF60-CPNF100-CPNF250-CPNF400-CPNF630-CPNF800-CEPNF100-RPNF100-UPNF250-RPNF250-UPNF400-UEPNF630-UEPNF800-UEP
The values in the table represent the max. rated current for both Series AE-SS air circuit breakers and branch breakers, and the selective co-ordination applies when the AE-SS series air circuit breakers instantaneous pick up is set to maximum.
The numerals shown in parentheses are for AE-SS with MCR. (When set MCR).
Please apply in case of AE-SH.
5
10
25
85
50
100
50
1008585100
5
253050
1258585
5050
10012585100125
AE630-SS65
5
9(10)
9(25)
9(65)
9(50)
9(65)
9(50)
9(65)–
9(65)
5
9(25)9(30)
–
9(65)9(65)
––
––
–––––
AE1000-SS65
5
10
25
50(65)
45(50)
50(65)
20(50)
25(65)–
15(65)
5
15(25)15(30)15(50)
15(65)15(65)
–15(65)
––
15(65)15(65)
–––
AE1250-SS65
5
10
25
65
50
65
22(50)
40(65)20(65)
5
18(25)18(30)20(50)
20(65)20(65)
20(65)–
18(65)
–18(50)
18(65)18(65)18(65)18(65)18(65)
AE1600-SS65
5
10
25
65
50
65
42(50)
6527(65)
5
24(25)24(30)27(50)
27(65)27(65)
27(65)24(65)24(65)
24(50)24(50)
24(65)24(65)24(65)24(65)24(65)
AE2000-SS85
5
10
25
85
50
85
50
8542(65)
5
2530
42(50)
42(65)42(65)
42(65)30(65)30(65)
30(50)30(50)
30(65)30(65)30(65)30(65)30(65)
AE2500-SS85
5
10
25
85
50
85
50
8570
5
253050
7070
7040(65)40(65)
40(50)40(50)
40(65)40(65)40(65)40(65)40(65)
AE3200-SS85
5
10
25
85
50
85
50
8585
8585
5
253050
8560(65)60(65)
5050
60(65)60(65)60(65)60(65)60(65)
AE4000-SSC85
5
10
25
85
50
85
50
85858585
5
253050
858585
5050
8585858585
AE5000-SS130
5
10
25
85
50
100
50
1008585
100
5
253050
1258585
5050
8585858585
5050
AE6300-SS130
5
10
25
85
50
100
50
1008585
1001258585
5
253050
8585858585
AE4000-SS130
5
10
25
85
50
100
50
1008585
100
5
253050
1258585
5050
8585858585
NF
-U
8510012585100125
125200125200200200200
6565
9(65)9(65)9(65)
––
65656565
15(65)15(65)
–
65656565
18(65)18(65)18(65)
65656565
29(65)24(65)24(65)
85858585
48(65)30(65)30(65)
8585858585
37(65)37(65)
85858585856868
85858585858585
125130125130130120120
125130125130130120120
125130125130130120120
AC220V sym kA
62
Main circuit breaker AE-SSBranchcircuit breaker
Unit breaking capacity
NF
-S •
MB
NF
-C
NF30-SPMB30-SPMB50-CPNF50-SPNF60-SPMB50-SPNF50-HPNF60-HPNF50-HRPNF100-SPNF100-SEPMB100-SPNF100-HPNF250-SPNF250-SEPMB250-SPNF250-HPNF400-SPNF400-SEPNF400-HEPNF400-REPNF630-SPNF630-SEPNF630-HEPNF630-REPNF800-SEPNF800-HEPNF800-REPNF50-CPNF60-CPNF100-CPNF250-CPNF400-CPNF630-CPNF800-CEPNF100-RPNF100-UPNF250-RPNF250-UPNF400-UEPNF630-UEPNF800-UEP
The values in the table represent the max. rated current for both Series AE-SS air circuit breakers and branch breakers, and the selective co-ordination applies when the AE-SS series air circuit breakers instantaneous pick up is set to maximum.
The numerals shown in parentheses are for AE-SS with MCR. (When set MCR).
Please apply in case of AE-SH.
2.5
7.5
10
30
25
50
25
50505065
2.5
101525
1255050
3535
651255065125
AE630-SS65
2.5
7.5
9(10)
9(30)
7(25)
9(50)
7(25)
7(50)–
9(50)
2.5
9(10)9(15)
–
9(65)9(65)
––
––
–––––
AE1000-SS65
2.5
7.5
10
30
20(25)
30(50)
14(25)
15(50)–
15(50)
2.5
1015
15(25)
15(65)15(65)
–15(50)
––
15(65)15(65)
–––
AE1250-SS65
2.5
7.5
10
30
25
50
19(25)
25(50)18(50)
2.5
1015
18(25)
18(65)18(50)
18(65)–
18(50)
–18(35)
18(65)18(65)18(50)18(65)18(65)
AE1600-SS65
2.5
7.5
10
30
25
50
25
42(50)24(50)
2.5
1015
24(25)
24(65)24(50)
24(65)24(50)24(50)
24(35)24(35)
24(65)24(65)24(50)24(65)24(65)
AE2000-SS85
2.5
7.5
10
30
25
50
25
5033(50)
2.5
101525
33(65)33(50)
33(65)33(50)30(50)
30(35)30(35)
30(65)30(65)30(50)30(65)30(65)
AE2500-SS85
2.5
7.5
10
30
25
50
25
5045(50)
2.5
101525
45(65)45(50)
45(65)45(50)40(50)
3535
40(65)40(65)40(50)40(65)40(65)
AE3200-SS85
2.5
7.5
10
30
25
50
25
5050
6550
2.5
101525
805050
3535
60(65)60(65)60(50)60(65)60(65)
AE4000-SSC85
2.5
7.5
10
30
25
50
25
50505065
2.5
101525
855050
3535
6585506585
AE5000-SS130
2.5
7.5
10
30
25
50
25
50505065
2.5
101525
1105050
3535
6585506585
3535
AE6300-SS130
2.5
7.5
10
30
25
50
25
50505065
1105050
2.5
101525
6585506585
AE4000-SS130
2.5
7.5
10
30
25
50
25
50505065
2.5
101525
1105050
3535
6585506585
NF
-U
125200125200200200200
35(65)50(65)9(65)9(65)9(65)
––
6565
50(65)65
15(65)15(65)
–
65656565
18(65)18(65)18(65)
65656565
29(65)24(65)24(65)
85858585
48(65)30(65)30(65)
8585858585
37(65)37(65)
85858585856868
85858585858585
125130125130130120120
125130125130130120120
125130125130130120120
AC460V sym kA
Neutral CT(NCT)External ZCT(ZCT) Type Refer P37
Y-2000 field test device AC100 – 240VY-160 field test device AC100 – 120V
AC200 – 240V
;
SST T…Trip indicationSPT P…Pre-alarmSPGTSPET
BARE Relay not require Note7
Electronic trip relay type
Blank LTD+STD+INST
C LTD+STD+INST/MCR
Tripping characteristics Note5
A OCR alarm(30ms 1 pulse)T Temperature alarm(LED & 1a contact)
Electronic trip relay accessories
0 Not required(Only for S type)1 AC100 – 120/200 – 240V2 DC100 – 125V4 DC24 – 60V
Control supply
Condenser trip device(COT)
AC100 – 110VAC200 – 220V
AC • DC100 – 125VAC • DC200 – 250VDC24VDC48V
Closing coil(CC)
Shunt trip device (SHT)
AC • DC100 – 250VDC24 – 48V
Under voltage trip device AC100 – 120/200 – 240/380 – 460V
DC24VDC48VDC100 – 110VDC120 – 125V
Instantaneous(UVT-SSB)0.5 s Time-delay type (UVT-05SSB)
3 s Time-delay type (UVT-30SSB)
AC • DC100 – 250VAC380 – 500VDC24 – 48V
Data
Test report
Specifications
P22
Remark
Production date
Customer(name) Order No. Number of units units
Number of poles
Rated current A
Applicablestandard
3P
IEC 60947-2 JIS C8372
Ambienttemperature 40°C
Cell switch CL- (Maximum: 4 pcs.)Shorting-B contact(SBC)Lifting hooks(HP)Safety shutter(SST)
Shutter lock(SST-LOCK)Mis-insertion preventer(MIP)Test jumper(TJ)
Vertical terminal adapter(VTA)Front terminal adapter(FTA)
Others °C Note2
Others
4P
C T D
Connection P17 Fixed type(FIX)
Main circuitterminal
Only for Horizontalterminals
Drawout type(DR)
Horizontal terminals(standard)Vertical terminals(DR-VT)Front terminals(DR-FT)
Drawout type accessories P23~24
P21~22 Push button cover(BC-L)Counter(CNT)Cylinder lock(CYL)Door interlock(DI) Note8
Terminal cover(TTC)Door frame(DF)Dust cover(DUC)Interphase barrier(BA)Mechanical interlock(MI)
P58
for 2unitsfor 3units
Type P13~16 AE -SS AE -SH
Electronic triprelay
P18~20 Auxiliary switchStandard(AX)High capacity(HAX)
Motor charging(MD)
A B Max.5A5B
"A"and"B"should be same.
P25~36
Specialenvironments
Moisture-fungustreatment Extra-corrosion proof specification
Electricalaccessories
Machineaccessories
S…Standard
Can be connected to the Horizontal terminals
Note7
Note:When specifying MD, be sureto order the closing coil(CC)andshunt trip device(SHT)for remoteoperation.
G…Ground fault protection Note5
E…Earth leakage protection Note6
Note1. Not available for AE4000-SSC.Note2. There is case to derate by ambient temperature.Note3. Not available for AE4000~6300-SS.Note4. The terminal for AE4000-SSC, AE4000~6300-SS shall be vertical terminal. Note5. Not available for AE-SS series with maximum rated current (In max) coming to 315A or 500A, nor AE630-SH. Neutral CT is needed for Ground fault protection when a 3 pole breaker is used on a 3 phase 4 wires system.Note6. In case of Earth leakage alarm, It need external ZCT. In case of Earth leakage tripping, It also need SHT.Note7. Not available for AE-SH. Note8. If install together with MI, Please ask us.
Note1
Note4
Note3
Note4units
Note1,3
Example
63
Ordering information for Mitsubishi AE-SS series air circuit breaker (General use ……S Type)
Neutral CT(NCT)External ZCT(ZCT) Type Refer P37
Y-2000 field test device AC100 – 240VY-160 field test device AC100 – 120V
AC200 – 240V
;
SST T…Trip indicationSPT P…Pre-alarmSPGTSPET
BARE Relay not require Note7
Electronic trip relay type
Blank LTD+STD+INST
C LTD+STD+INST/MCR
Tripping characteristics Note5
A OCR alarm(30ms 1 pulse)T Temperature alarm(LED & 1a contact)
Electronic trip relay accessories
0 Not required(Only for S type)1 AC100 – 120/200 – 240V2 DC100 – 125V4 DC24 – 60V
Control supply
Condenser trip device(COT)
AC100 – 110VAC200 – 220V
AC • DC100 – 125VAC • DC200 – 250VDC24VDC48V
Closing coil(CC)
Shunt trip device (SHT)
AC • DC100 – 250VDC24 – 48V
Under voltage trip device AC100 – 120/200 – 240/380 – 460V
DC24VDC48VDC100 – 110VDC120 – 125V
Instantaneous(UVT-SSB)0.5 s Time-delay type (UVT-05SSB)
3 s Time-delay type (UVT-30SSB)
AC • DC100 – 250VAC380 – 500VDC24 – 48V
Data
Test report
Specifications
P22
Remark
Production date
Customer(name) Order No. Number of units units
Number of poles
Rated current A
Applicablestandard
3P
IEC 60947-2 JIS C8372
Ambienttemperature 40°C
Cell switch CL- (Maximum: 4 pcs.)Shorting-B contact(SBC)Lifting hooks(HP)Safety shutter(SST)
Shutter lock(SST-LOCK)Mis-insertion preventer(MIP)Test jumper(TJ)
Vertical terminal adapter(VTA)Front terminal adapter(FTA)
Others °C Note2
Others
4P
C T D
Connection P17 Fixed type(FIX)
Main circuitterminal
Horizontalterminals
Drawout type(DR)
Horizontal terminals(standard)Vertical terminals(DR-VT)Front terminals(DR-FT)
Drawout type accessories P23~24
P21~22 Push button cover(BC-L)Counter(CNT)Cylinder lock(CYL)Door interlock(DI) Note8
Terminal cover(TTC)Door frame(DF)Dust cover(DUC)Interphase barrier(BA)Mechanical interlock(MI)
P58
for 2unitsfor 3units
Type P13~16 AE -SS AE -SH
Electronic triprelay
P18~20 Auxiliary switchStandard(AX)High capacity(HAX)
Motor charging(MD)
A B Max.5A5B
"A"and"B"should be same.
P25~36
Specialenvironments
Moisture-fungustreatment Extra-corrosion proof specification
Electricalaccessories
Machineaccessories
S…Standard
Can be connected to the Horizontal terminals
Note7
Note:When specifying MD, be sureto order the closing coil(CC)andshunt trip device(SHT)for remoteoperation.
G…Ground fault protection Note5
E…Earth leakage protection Note6
Note1. Not available for AE4000-SSC.Note2. There is case to derate by ambient temperature.Note3. Not available for AE4000~6300-SS.Note4. The terminal for AE4000-SSC, AE4000~6300-SS shall be vertical terminal.Note5. Not available for AE-SS series with maximum rated current (In max) coming to 315A or 500A, nor AE630-SH. Neutral CT is needed for Ground fault protection when a 3 pole breaker is used on a 3 phase 4 wires system.Note6. In case of Earth leakage alarm, It need external ZCT. In case of Earth leakage tripping, It also need SHT.Note7. Not available for AE-SH. Note8. If install together with MI, Please ask us.
Note1
Note4
Note3
Note4units
Note1,3
64
Ordering information for Mitsubishi AE-SS series air circuit breaker (General use ……S Type)
65
Condenser trip device(COT)
AC100 – 110VAC200 – 220V
AC • DC100 – 125VAC • DC200 – 250VDC24VDC48V
Closing coil(CC)
Shunt trip device (SHT)
AC • DC100 – 250VDC24 – 48V
Under voltage trip device AC100 – 120/200 – 240/380 – 460V
DC24VDC48VDC100 – 110VDC120 – 125V
Instantaneous(UVT-SSB)0.5 s Time-delay type (UVT-05SSB)
3 s Time-delay type (UVT-30SSB)
AC • DC100 – 250VAC380 – 500VDC24 – 48V
P22
Remark
Production date
Customer(name) Order No. Number of units units
Number of poles
Rated current A
Applicablestandard
3P
LR AB
Ambienttemperature 45°C
Cell switch CL- (Maximum: 4 pcs.)Shorting-B contact(SBC)Lifting hooks(HP)Safety shutter(SST)
Shutter lock(SST-LOCK)Mis-insertion preventer(MIP)Test jumper(TJ)
Vertical terminal adapter(VTA)Front terminal adapter(FTA)
Others °C Note3
GL BVDNV NKOthersIEC 60947-2
4P
C T D
Connection P17 Fixed type(FIX)
Main circuitterminal
Only for Horizontalterminals
Drawout type(DR)
Horizontal terminals(standard)Vertical terminals(DR-VT)Front terminals(DR-FT)
Drawout type accessories P2324
Type P13~16 AE -SS AE -SH
P18~20 Auxiliary switchStandard(AX)High capacity(HAX)
Motor charging(MD)
A B Max.5A5B
"A"and"B"should be same.
Electricalaccessories
Y-2000 field test device AC100 – 240V
Neutral CT(NCT)
; A OCR alarm(30ms 1 pulse)T Temperature alarm(LED & 1a contact)
Electronic trip relay accessories
0 Not required(Only for M type)1 AC100 – 120/200 – 240V2 DC100 – 125V4 DC24 – 60V
Control supplyM M…StandardMT T…Trip indicationMPT P…Pre-alarmMPGT G…Ground fault protection Note6
Electronic trip relay typeSpecify the tripping characteristics Refer to P28, 46, 47.
LTD CurrentLTD TimeSTD CurrentSTD TimeINST CurrentPAL CurrentPAL TimeGFR CurrentGFR Time
% of Rated Currents at 120% of LTD Current% of Rated Currents at 150% of STD Current% of Rated Current% of LTD Current% of LTD Time% of Rated Current MAX.s at 150% of GFR Current
Electronic triprelay
P25~36
Note1. Not available for 4 pole breaker with LR, AB, GL, DNV, BV, NK standard.Note2. Not available for AE4000-SSC.Note3. There is case to derate by ambient temperature.Note4. Not available for AE4000~6300-SS.Note5. The terminal for AE4000-SSC, AE4000~6300-SS shall be vertical terminal.Note6. Not available for AE-SS series with maximum rated current (In max) coming to 315A or 500A, nor AE630-SH. Neutral CT is needed for Ground fault protection when a 3 pole breaker is used on a 3 phase 4 wires system. Note7. If install together with MI, Please ask us.
Can be connected to the Horizontal terminals
50
Note:When specifying MD, be sureto order the closing coil(CC)andshunt trip device(SHT)for remoteoperation.
Note1, Note2
Note5 Note5
Note4
units
Data
Test report
Specifications
P21~22 Push button cover(BC-L)Counter(CNT)Cylinder lock(CYL)Door interlock(DI) Note7
Terminal cover(TTC)Door frame(DF)Dust cover(DUC)Interphase barrier(BA)Mechanical interlock(MI)
P58
for 2unitsfor 3units
Specialenvironments
Moisture-fungustreatment Extra-corrosion proof specification
Machineaccessories
Note4
Note4
Ordering information for Mitsubishi AE-SS series air circuit breaker (Generator protection use ……M Type)
Service networkCountry / Region
U.K.
Ireland
Germany
Italy
Spain
Sweden
Norway
Denmark
Greece
The Netherlands
Switzerland
Belgium
Poland
Turkey
Slovania
South Africa
Lebanon
Saudi Arabia
Egypt
Kuwait
China
Hong Kong
Taiwan
Korea
Singapore
Indonesia
Philippines
Thailand
Pakistan
Vietnam
Lao PDR
Myanmer
Nepal
Australia
New Zealand
Colombia
Chile
Uruguay
Peru
Venezuela
Company
Mitsubishi Electric Europe B.V. UK-Branch.
Mitsubishi Electric Europe B.V. Irish Branch.
Mitsubishi Electric Europe B.V. German Branch.
Carpaneto & C. S.P.A
Mitsubishi Electric Europe B.V. Spanish Branch.
Euro Energy Components AB
SCANELEC
Louis Poulsen CO. A/S
Antonios Drepanias. S.A.
R+H Technology BV.
Trielec A G
Emac S.A.
MPL Technology Sp zo.o.
HEDEF
INEA
M.S.A.MANUFACTURING(PTY)LTD.
COMPTOIR D'ELECTRICITEGENERALE INTERNATIONAL
CENTER OF ELECTRICAL GOODS
CAIRO ELECTRICAL GROUP
SALEM M AL-NISF ELECTRICAL CO.W.L.L.
SHANGHAI SETSUYO TRADING CO., LTD.
RYODEN INTERNATIONAL LTD.
Ryoden international Ltd.
Setsuyo Enterprise Co., Ltd.
HAN NEUNG TECHNO Co., Ltd.
MITSUBISHI ELECTRIC ASIA PTE LTD.
P.T.SAHABAT INDONESIA.
EDISON ELECTRIC INTEGRATED, INC.
UNITED TRADING & IMPORT CO. LTD.
Prince Electric Co.
Sa Giang Techno Co., Ltd.
SOCIETE LAO IMPORT-EXPORT
PEACE MYANMAR ELECTRIC CO., LTD.
Watt & Volt House Co., Ltd.
Mitsubishi Electric Australia Pty. Ltd
Melco Sales (N.Z.) Ltd.
Proelectrico Representaciones S.A.
RHONA S.A.
Fierro Vignoli S.A.
I.T.E.
ADESCO C.A.
Address
Travellers Lane, Hatfield, Herts, AL10 8xB, U.K.
Westgate Business Park, Ballymount, Dublin 24, Ireland.
Gothaer Strasse 8, 40880 Ratingen, Germany.
10090 CASCINE VICA-RIVOLI (TO)Via Ferrero, 10-Ang. Pavia 6 Italy.Polingono Industrial "Can Magi", Calle Joan Buscalla 2-4, Apartado de Correos 420,08190 Sant Cugat del Valles, Barcelona, Spain.
Energigatan 15 Box 10161, S-434 22 Kungsbacka, Sweden
Leivikasen 43B, P.O. box 55, 5074 Godvik, Norway
Geminivej 32, DK-2670 Greve, Denmark.
52, Arkadias
STR.GR 121 32. Peristeri Athens Greece.
3361 HJ Sliedrecht Industrieweg 30. Netherland.
Mühlentalstrasse 136, 8201 Schaffhausen, Switzerland
1702 Groot-Bijgaarden Industrialaan 1, Belgium.
30011 Krakow UI. Wroclawska 53 Poland.
Barboros Bulv. iba Bloklari Gazi Umur P. So Balmumcu-Istanbul Turkey.
61230 Domzale Ljubljanska 80 Slovenia.
Bramley 2018, Johannesburg, South Africa.
Cebaco Center-Block A. Autostrade Dora, P.O. BOX: 90-1314 Beirut-Lebanon.
Al-Nabhaniya Street-4Th Crossing, Al-Hassa Road, P.O. BOX: 15955, Riyadh 11454,Saudi Arabia.9 Rostoum Street Garden City, APT. 5,P.O. BOX: 165-11516, Cairo-Egypt.
P.O. Box 4784. Safat. 13048 Kuwait.
Building of Innovation Center, Room No. 406A, 680 Guiping Road Shanghai, P.R.China
(Shanghai) 3F, Block 5, 103Cao Bao Road, Shanghai, China
10/F Manulife Tower 169 Electric Road North Point. Hong Kong.
6F, NO. 105 Wu-Kung 3rd rd., Wu-Ku Hsiang,
Taipei Hsien Taiwan
2 Fl. Dong Seo Game Channel Bldg ., 1F 660-11 Deungchon-Dong, Kanguseo-Ku, Seoul, 157-030 Korea
307 Alexandra Road #05-01/02 MitsubishiElectric Building Singapore 159943
JL Muara Karang Selatan Blok A/Utara No.1 kav. NO.11 P.O. Box 5045/Jakarta/11050. Jakarta Indonesia.
24th Fl. Galleria Corporate Center Edsa Cr, Ortigas Ave. Quezon City, Metro Manila. Philippines.
77/12 Bumrungmuang Road, Klong Mahanak, Pomprab Bangkok 10100.
16 Brandreth Road Lahore 54000. Pakistan.
207/4 Nguyen Van Thu St., Dist 1, Ho Chi Minh City, Vietnam
43-47 Lane Xang Road P.O. BOX 2789 VTVientiane Lao PDR.
NO. 216, Bo Aung Gyaw Street,Botataung 11161, Yangon, Myanmar.
KHA 2-65, Volt House Dilli Bazar Post Box: 2108,kathmandu, Nepal
348 Victoria Road, Rydalmere, N.S.W. 2116, Australia
1 Parliament Street Lower Hutt. New Zealand.
Cra 53 No 29C-73 U.I.C.- Medellin. COLOMBIA.
Vte. Agua Santa 4211 Casilla 30-D (P.O. Box) Viña Del Mar. Chile
P.O. box 20022/Suc Upae, Montevideo. Uruguay.
Ingenieros s.a. Paseo de la Republica 3573 Lima 27. Peru.
Lle 8, Calpon Elinsu,La Urbina-EDO, Miranda P.O.BOX 78034 Caracas 1074A., Venezuela
Telephone
44-1707-276-100
353-1-4505007
49-2102-4860
39-11-9590111
34-93-565-3131
46-300-518-00
47-55-506000
45-43-95-95-95
30(1)5781599, 30(1)5781699
31-104871251
41-52-6258425
32-2-4810211
48-12-322885
90-212-2754876
386-61-718000
27-11-444-8080
961-1-240430
966-1-4770149
20-2-7961337
965-484-5660
021-6485-6611
021-6475-3228
28878870
02-2298-8889
017-255-0174
65-473-2308
021-6621780
02-643-8691
223-4220-3
042-7654342
848-821-6453
21-215043, 21-215110
951-295426
977-1-411330
612-9684, 7586
644-569-7350
574-235-00-28
(32)-611896
598-2-92-08-08
(1) 221-2710
58-2-241-7634
Catalogue NO. Y-0446-M 0010(ROD) Printed in JapanNew publication, effective Sept. 2000
Specifications subject to change without notice.
Safety Tips : Be sure to read the instruction manual fully before using this product.
HEAD OFFICE: MITSUBISHI DENKI BLDG., MARUNOUCHI, TOKYO 100-8310. TELEX: J24532 CABLE: MELCO TOKYO
This catalogue is made from recycled paper.