Inelastic dynamic analysis and non-linear static analysis of 6- and 17-story RC buildings of ductile frames designed in Mexico City J. A. Avila 1,2 1 Institute of Engineering, National University of Mexico (UNAM), Mexico 2 Faculty of Engineering, National University of Mexico (UNAM), Mexico Abstract A non-linear static analysis with monotonically increasing lateral loads was performed for two RC buildings with 6 and 17 stories, respectively, in order to compare their response against the results obtained from inelastic seismic analyses for the SCT-EW-85 record. The buildings are located in compressible seismic zone III b , and are designed according to Appendix A of the Mexico City Building Code (RDF-04), for a soil dominant period of T s =2 seconds, satisfying the maximum service and collapse limit states for story distortion. Resistances were designed taking into account a three-dimensional structural performance in addition to the vertical load effects and second order effects. Due to the use of seismic performance factors (Q=4 for the 6-story building and Q=3 for the 17- story building), and according to the Concrete Construction Standard, special requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered for the non-linear responses. Different inputs of lateral load patterns for the non-linear static analysis were taken into account. The comparisons were performed for base shear force–roof lateral displacement relations, global distribution of plastic hinges, failure mechanics tendency, local and global ductility demands, etc. Keywords: spectral modal dynamic analysis, non-linear static analysis, inelastic seismic analysis. Earthquake Resistant Engineering Structures IX 97 www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press doi:10.2495/ERES130081

Upload: others

Post on 27-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

Inelastic dynamic analysis and non-linear static analysis of 6- and 17-story RC buildings of ductile frames designed in Mexico City

J. A. Avila1,2 1Institute of Engineering, National University of Mexico (UNAM), Mexico 2Faculty of Engineering, National University of Mexico (UNAM), Mexico

Abstract

A non-linear static analysis with monotonically increasing lateral loads was performed for two RC buildings with 6 and 17 stories, respectively, in order to compare their response against the results obtained from inelastic seismic analyses for the SCT-EW-85 record. The buildings are located in compressible seismic zone IIIb, and are designed according to Appendix A of the Mexico City Building Code (RDF-04), for a soil dominant period of Ts=2 seconds, satisfying the maximum service and collapse limit states for story distortion. Resistances were designed taking into account a three-dimensional structural performance in addition to the vertical load effects and second order effects. Due to the use of seismic performance factors (Q=4 for the 6-story building and Q=3 for the 17-story building), and according to the Concrete Construction Standard, special requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered for the non-linear responses. Different inputs of lateral load patterns for the non-linear static analysis were taken into account. The comparisons were performed for base shear force–roof lateral displacement relations, global distribution of plastic hinges, failure mechanics tendency, local and global ductility demands, etc. Keywords: spectral modal dynamic analysis, non-linear static analysis, inelastic seismic analysis.

Earthquake Resistant Engineering Structures IX 97

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

doi:10.2495/ERES130081

Page 2: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

1 Introduction

This work determines and compares both, the non-linear seismic behavior (Push-Over) and the dynamic inelastic step by step behavior, of a 6- and a 17-story office building with reinforced concrete (RC) frames, located in the compressible zone of Mexico City. The design was made according to the service and failure limit states of the Mexico City Building Code (RDF-04, 2004), established in its corresponding Seismic and Concrete Complementary Technical Standards (NTC-Seismic, NTC-Concrete) [1]. The structures were designed as follows: A) with the design spectrum of the Main Text of the NTC-Seismic (seismic zone IIIb); and B) with the design spectrum according to the soil dominant period, defined in the Appendix A of the NTC-Seismic (Ts= 2 seconds). The time-history inelastic seismic responses were analyzed with representative records of maximum compressible soil damage in Mexico City obtained from the earthquake of September, 1985. For the Push-Over analyses, the responses under different lateral load distributions were obtained as well as the collapse mechanisms, the base shear force-roof lateral displacement curves and the maximum demands of local and global ductility. The influence of the possible over-resistance sources was included. From the results of this work it is to be noticed that there are no important variations between Main Text and Appendix A cases. Appendix A criterion allows to determine the displacement of the service and collapse conditions to which the structure may be subjected to.

2 Elastic response calculation

2.1 Description of the structures and design procedure

The studied structures correspond to office buildings of 6 and 17 stories of reinforced concrete, symmetric and regular in plan and elevation. They have a foundation rigid box. The 17-story building has point piles. The concrete is class 1 with f´c= 250 kg/cm2 and elastic modulus Ec= 14,000 times square root of f´c, and the longitudinal and transverse steel with fy= 4,200 kg/cm2. The structural system is composed of reinforced concrete frames with girders and columns rigidly connected by a solid slab of 10 cm thick. Fig. 1 shows the main details in plan and elevation of the studied buildings. The column and girder resistances were designed for the last mechanic elements of the spectral modal dynamic analysis, considering the three-dimensional structural performance plus the vertical load effects (dead loads and live loads) and second order effects. For the ductile frame special requirements were considered as it is established in the Concrete Standards, due to the use of seismic performance factors Q= 4 for the 6-story building, and Q= 3 for the 17-story building.

2.2 Vibration periods

Table 1 compares the three periods of vibration modes (X, Y and θ directions) of the 6- and 17-story buildings, respectively. There are no differences between

98 Earthquake Resistant Engineering Structures IX

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 3: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

Column

Girder

Slab

Secondary beam

Meters

N1

N2

N3

N4

NCIM

NSOT

NPB

C19C15 C17 C21

31 2 4

N5

N7

N6

N9

N8

N11

N10

N13

N12

N15

N14

N17

N16

3

3,75

4.45

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

3,5

BASEME. GROUND L.

FOUND.

LEVEL

Figure 1: Structural plant-type (dimensions in meters) and transversal cuts of 6-story and 17-story buildings.

Main Text and Appendix A cases, as expected. For the 17-story building, due to symmetry in the structure, the periods in the X and Y directions are the same. Figs 2 and 3 show the design spectra of the RDF-04 of the Main Text (seismic zone IIIb) and the Appendix A (Ts= 2 seconds), the elastic and inelastic response spectra of the record SCT-EW-85 (critical viscous damping of 5%) as well as the location of the fundamental periods of vibration of the 6-story (T1x= 0.832 seconds) and 17-story buildings (T1x= 1.752 seconds) in the X direction.

17 Levels 6 Levels

Earthquake Resistant Engineering Structures IX 99

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 4: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

Table 1: Vibration periods of 6-story and 17-story buildings.

Vibration periods, Ti (seconds)

Direction 6-story 17-story T1 T2 T3 T1 T2 T3

X 0.832 0.279 0.138 1.752 0.643 0.374

Y 0.837 0.278 0.138 1.752 0.643 0.374

θ (torsion) 0.676 0.228 0.114 1.346 0.518 0.306

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0

g

Period, T (s) Elastic SCT EW - 85 Ductility = 2 (SCT EW - 85) Ductility = 4 (SCT EW - 85) RDF - 04 (Q = 1) RDF - 04 (Q = 2) RDF - 04 (Q = 4) Case B2 - Line 2 Case B2 - Line A Case D2 - Line 2 Case D2 - Line A

Sa/g

Figure 2: Location of fundamental period of vibration of 6-story structure, regarding the design spectra (Q= 1 and 4) and the response spectra (µ= 1 and 4) of SCT-EW-85 record.

2.3 Maximum story drifts

The 6-story building under earthquake in both directions, accomplishes with the permissible limit of 0.006 specified in the main text, and with the permissible limit of 0.002 for Appendix A. The collapse limit of 0.03 was not a governing condition for the performance of the design. The 17-story building accomplishes with both permissible limits, being slightly above the service condition of Appendix A.

3 Calculation of the inelastic dynamic response

Inelastic dynamic responses step-by-step are determined by using the E-W SCT accelerogram, registered on September 19th of 1985. The responses were

100 Earthquake Resistant Engineering Structures IX

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 5: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

0.00

0.10

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1.10

1.20

1.30

0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00

S a/g

Period, Ti (seconds)

SCT-EW Elastic ( =1) SCT-EW Inelastic ( =3) Appendix A. Elastic (Q=1)Appendix A. Inelastic (Q=3) Main Body. Elastic (Q=1) Main Body. Inelastic (Q=3)T (17 levels)

µµ

1

Figure 3: Location of fundamental period of vibration of the 17-story structure, regarding the design spectra (Q= 1 and 3) and the response spectra (µ= 1 and 3) of SCT-EW-85 record.

calculated for the axes 2 (X direction) and A (Y direction) of the 6-story building, and axes C and B for the 17-story building (see fig. 1), respectively. The corresponding frames were “calibrated” to ensure static and dynamic behavior similar to the three-dimensional model.

3.1 Global ductility maximum demands, μG

All buildings, with nominal resistances, experimented inelastic performance; generally, with over-resistance effects, having lower global ductility demands. In no case μG was over the values of 4 or 3, which are equal to the values of the seismic performance factor (Q) for which the elastic design spectra were reduced (see table 2).

3.2 Curves of base shear force-roof lateral displacement

When inelastic behavior is present, it is observed that, as the structure dissipates more amount of seismic energy, the responses have more hysteretic area, and there are further reductions in the base shear force and the roof horizontal displacement. Figs. 4 and 5 compare the curves of base shear force-roof lateral displacement of the 6- and 17-story buildings under elastic and inelastic step-by-step seismic analysis with nominal and over-resistances. The hysteretic curve of the 6-story model with nominal resistances is slightly wider, which means a lightly larger incursion in the nonlinear range and higher energy dissipation. The

Earthquake Resistant Engineering Structures IX 101

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 6: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

Table 2: Calculated global ductility maximum demands of 6- and 17-story buildings under inelastic step-by-step seismic analysis with nominal and over-resistances.

Nominal resistance Over-resistance

Levels ∆Y (cm)

∆max

inelastic (cm)

µG ∆Y (cm)

∆max

inelastic (cm)

µG

6 (Q= 4) 5.23 18.44 3.53 5.16 5.91 1.15

17 (Q= 3) 19.24 42.85 2.23 29.01 47.01 1.62 µG = ∆max inelastic / ∆Y ; ∆Y = roof lateral displacement for the first yield. ∆max inelastic = roof maximum lateral displacement for the inelastic performance.

-200

-150

-100

-50

0

50

100

150

200

-20 -16 -12 -8 -4 0 4 8 12 16 20

Corta

nte b

asal

(t)

Desplazamiento lateral en azotea (cm)

Roof lateral displacement (cm)

Elastic

Base

shea

r for

ce (t

)

-200

-150

-100

-50

0

50

100

150

200

-20 -16 -12 -8 -4 0 4 8 12 16 20

Corta

nte b

asal

(t)

Desplazamiento lateral en azotea (cm)

Roof lateral displacement (cm)

Inelastic (Nominal resistance)

Base

shea

r for

ce (t

)

-200

-150

-100

-50

0

50

100

150

200

-20 -16 -12 -8 -4 0 4 8 12 16 20

Cor

tant

e ba

sal (

t)

Desplazamiento lateral en azotea (cm)

Roof lateral displacement (cm)

Inelastic (Over-resistance)

Base

shea

r fo

rce

(t)

Figure 4: Curves of base shear force–roof lateral displacement, elastic and inelastic step-by-step seismic analysis (nominal and over-resistances), 6-story structure.

102 Earthquake Resistant Engineering Structures IX

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 7: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

-2000

-1500

-1000

-500

0

500

1000

1500

2000

-80 -60 -40 -20 0 20 40 60 80

Base

she

ar fo

rce

(t)

Roof lateral displacement (cm )ELASTIC AA-INE-N

-2000

-1500

-1000

-500

0

500

1000

1500

2000

-80 -60 -40 -20 0 20 40 60 80

Base

she

ar fo

rce

(t)

Roof lateral displacement (cm )ELASTIC AA-INE-OR

Figure 5: Curves of base shear force–roof lateral displacement, elastic and inelastic step-by-step seismic analysis (nominal and over-resistances), 17-story structure.

17-story models tend to have a larger hysteretic area, and over-resistance cases show a slight inelastic behavior, although on a less important way than the condition of nominal resistance.

3.3 Global distribution of plastic hinge and demands of local ductility

The overall distribution of plastic hinges for all the structures had a general tendency to the failure mechanism known as the “beam” type; this means that the plastic hinges are present in most of the beams, and only in some columns, which is consistent with the design philosophy of “strong column-weak beam” of the RDF-04 code. Fig. 6 has global distributions of plastic hinges on the 17-story building without and with over-resistances. Colors described different times in which each plastic hinge was introduced from blue color in the beginning until the end of the most intensive phase of the record SCT-EW-85. Fig. 7 shows the maximum local ductility demands developed in beams, for Main Text and Appendix A conditions of the studied 17-story building; columns behave almost in the elastic range, with maximum demands less than 1.5. The maximum demands for the nominal cases present values between 4 and 6 in beams, whereas in columns, the values are less than 2; with the over-resistance effects, such that the maximum demands in beams are from 2 to 3 and columns behave elastically, for practical purposes. The maximum value in beams in the 17-story building varies between 3 and 7 with nominal resistance and between 1.5 and 3 when over-resistance effects are considered.

AA-Nominal

AA-Over resistance

Earthquake Resistant Engineering Structures IX 103

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 8: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

2

100 112 109 113

888

11 93 73 82 74 49

59

51

2241

19

3247

55

40

30 31

3824 17

9

7

337

3520

21

23

39 26

13 4

18

1

362553

562

85 34 60

54

79 89 86

929687103

97

72

52

58

114

122

98

91

77

61

50

33

15

12

10

2

6

14

16

95

90

83

84 63

76 45

70 29

67 43

4265

68 48

71 28

75 44

78 27

4680118

69 815766

94

101

99

111

108

126

123

107

117

124 121

120 116

115

102104

127 125

110

56 64119

106

105

1 31 62 93 127

88 104 106 121

9220

24 86 77 66 84 26

28

21

956

38

5730

27

19

12 44

5310 4

2

3

151

486

7

11

22 59

40 5

18

13

536732

6376

94 70 99

81

116 114109

72

65

68

97

75

54

35

29

16

14

15

8

17

23

25

112

95

83

82 71

64 60

46 42

41 47

4535

39 50

43 37

52 49

61 34

5862105

68 657873

79

89

85

99

98

93

110

113

107

74 80

100 101

91

103102

31 7990

115

111

87

120

108

117

118

119

122

Figure 6: Apparition sequence and global distribution of plastic hinges, 17-story structure, with nominal resistances (NR) and over-resistances (OR) effects.

NR

OR

104 Earthquake Resistant Engineering Structures IX

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 9: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

0123456789

1011121314151617

-8 -6 -4 -2 0 2 4 6 8

Level

Local ductility maximum demands developed in beamsAA-INE-N AA-INE-OR MB-INE-N MB-INE-OR

Figure 7: Local ductility maximum demands developed in beams, inelastic step by step analysis with nominal resistances (N) and over-resistances (OR), 17-story building, Main Text and Appendix A designs.

4 Non-linear static analysis (Push-over)

The non-linear static analysis with four different distributions of lateral load, were made with and without the over-resistance effects, to know: 1) SMD distribution with forces at the floor level (Fi), determined from the story shear forces (Vi) of the spectral modal dynamic analysis, involving all modes of lateral vibration; 2) Elastic step-by-step distribution with forces at floor level (Fi), calculated with the story shear forces (Vi) for a “ti” time from an step-by-step analysis, when the structure is working in the elastic range; 3) Inelastic step-by-step distribution with forces at floor level (Fi), defined with the story shear forces (Vi) for a “ti” time from a step-by-step analysis when the structure the maximum inelastic roof displacement is shown; 4) Linear triangular distribution from Fi forces as a result of the hypothesis of static seismic analysis (linear). Fig. 8 shows the lateral load distributions for the non-linear static analysis (Push-over) of the 17-story building. The results shown are only for the case in which the distributions are obtained from a spectral modal dynamic analysis (SMD), with the participation of all modes of lateral vibration. The Push-over analyses were made to the following conditions: a) maximum demands of the local ductility in beams are equal to 35, b) maximum demands of the local ductility in columns are equal to 20, c) maximum story drift of the collapse condition is 0.03, according to Appendix A of the NTC-Seismic of RDF-04 Code for structures for ductile concrete frames with Q= 3 or 4, d) the mechanism of collapse of the structure is reached.

4.1 Curves of base shear force–roof lateral displacement

Figs. 9 and 10 compare the results of the base shear force-roof lateral displacement relationships of the Push-over analyses against relationship of the corresponding inelastic step-by-step analyses without and with over-resistance

Earthquake Resistant Engineering Structures IX 105

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 10: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

Figure 8: Lateral loads distributions for the non-linear static analysis (Push-over), 17-story building.

c S = 0.179 c S = 0.165

- 200 - 150

- 100

- 50

0

50 100

150

200

- 60 - 45 - 30 - 15 0 15 30 45 60

Roof lateral displacement (cm) Step-by-step dynamic - nominal

Push - over (spectral modal dynamic - nominal) Push - over (maximum lateral displacement, step-by-step dynamic -nominal)

- = 1.08

Base shear force (t)

Cs(Push-over) / Cs(step-by-step)= 1.08

6-story

c S = 0.252 c S = 0.217

- 200

- 150

- 100

- 50

0

50

100

150

200

- 60 - 45 - 30 - 15 0 15 30 45 60 (

Roof lateral displacement (cm) Step-by-step dynamic over-resistance

Push - over (spectral modal dynamic over - resistances) Push - over (maximum lateral desplacement, step-by-step dynamic over - resistances)

Cs(Push-over) / Cs(step-by-step)= 1.16

Base shear force (t)

6-story

Figure 9: Curves of base shear force–roof lateral displacement comparison, non-linear static analysis (Push-over) and inelastic step-by-step dynamic analysis with nominal resistance and over-resistances effects, 6-story structure.

106 Earthquake Resistant Engineering Structures IX

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 11: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

-700

-500

-300

-100

100

300

500

700

-60 -40 -20 0 20 40 60 80 100 120

Base

she

ar f

orce

(t)

Roof lateral displacement (cm)

17 levelsAA-Nominal

Push-over

Step-by-step

-1000

-800

-600

-400

-200

0

200

400

600

800

1000

-60 -40 -20 0 20 40 60 80 100 120

Base

she

ar f

orce

(t)

Roof lateral displacement (cm)

Push-over

Step-by-step

17 levelsAA-Over resistance

Figure 10: Curves of shear force–roof lateral displacement relationships comparison, non-linear static analysis (Push-over) and inelastic step-by-step dynamic analysis with nominal resistance and over-resistances, 17-story structures.

effects, of the 6- and 17-story models, designed with Appendix A. For 6-story models, the resulting performance from Push-over analysis was governed generally by the condition of permissible drift of collapse of 0.03. For 17-story models, the resulting behavior from Push-over analysis was governed generally by the condition of permissible drift of collapse of 0.03. The influence of over-resistance effects is very important. The results of both types of analysis, confirm the lateral stiffness and lateral resistance of each structure as well as their capacity of energy dissipation facing the typical seismic effects of Mexico City.

5 Conclusions

Buildings designed with the Seismic Technical Standards of the Mexico City Building Code (RDF-04) show satisfactory performance, with sufficient resistance reserve, to avoid brittle failure. Significant variations between the designs of the Main Text and Appendix A conditions are not presented. With the help of the over- resistance effects, the maximum responses tended to be

Earthquake Resistant Engineering Structures IX 107

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press

Page 12: Inelastic dynamic analysis and non-linear static analysis ... · requirements were considered for the ductile frame. Nominal resistance and over-resistance effects were considered

lower. The tendency of plastic hinges from step-by-step and non-linear static (Push-over) analyses show, in general, a strong column-weak girder performance according to the current design philosophy, which ensures a ductile behavior. The Push-over analysis results show consistency regarding to responses of dynamic analysis in time history.

References

[1] Gaceta Oficial del Gobierno del Distrito Federal (2004), “Reglamento de Construcciones de la ciudad de México y Normas Técnicas Complementarias”

108 Earthquake Resistant Engineering Structures IX

www.witpress.com, ISSN 1743-3509 (on-line) WIT Transactions on The Built Environment, Vol 132, © 2013 WIT Press