improving the solar hot water system in the duke smart home · 2009-01-15 · 2 abstract the goal...
TRANSCRIPT
Pratt School of Engineering
Duke University
Department of Mechanical Engineering and Materials Science
Improving the Solar Hot Water
System in the Duke Smart Home
ME 160
Dr. Robert Kielb
Spring 2008
4/27/2008
Advisor: Milan Simonivic
Holly Hackman, Tiffany Hui, Jeff Schwane, Scott Strickland
2
ABSTRACT
The goal of this project was to improve the overall heat transfer rate of the solar hot water system
in the Duke Smart Home, thereby increasing both energy and cost savings. The design team spent a
semester investigating ways to improve the system’s efficiency through implementation of variable
speed pumps. Preliminary design work was performed and is summarized in this report. The variable
speed pumps were installed in the Smart Home and the programming and experimentation processes
are outlined herein as well. The experiment resulted in a marked efficiency improvement by running
the pumps at variable speed rather than constant speed. Results of this project are presented in detail
and suggestions for further improvements are presented in the conclusion.
Problem Definition
Purpose
The intent of this design project was to increase the heat transfer of the current solar water
heating system installed in the Home Depot Smart Home.
retrofitted to rely on variable speed circulators instead of the standard constant
constantly adjusting the flow of water, the new system would hopefully be able to take far greater
advantage of changes in external temperature and thus
Current Solar Water Heating System
The water heating system currently installed in the Smart Home relies on two constant
Taco 009 pumps to circulate water in a closed
system.
Figure 1 -
The water begins at the heat exchanger near the hot water storage tank in the basement of the
building, and it is pushed to the roof where a solar collector is used to heat the water.
flows back down, and its thermal energy is used to heat the water in the storage tank
3
The intent of this design project was to increase the heat transfer of the current solar water
heating system installed in the Home Depot Smart Home. To accomplish this task, the system was
retrofitted to rely on variable speed circulators instead of the standard constant-speed pumps.
constantly adjusting the flow of water, the new system would hopefully be able to take far greater
external temperature and thus achieve greater efficiency.
Current Solar Water Heating System
The water heating system currently installed in the Smart Home relies on two constant
Taco 009 pumps to circulate water in a closed-loop system. Figure 1 provides a simplistic model of this
- Schematic of Current Solar Hot Water Heating System
The water begins at the heat exchanger near the hot water storage tank in the basement of the
is pushed to the roof where a solar collector is used to heat the water.
flows back down, and its thermal energy is used to heat the water in the storage tank via a heat
The intent of this design project was to increase the heat transfer of the current solar water
To accomplish this task, the system was
speed pumps. By
constantly adjusting the flow of water, the new system would hopefully be able to take far greater
The water heating system currently installed in the Smart Home relies on two constant-speed
Figure 1 provides a simplistic model of this
The water begins at the heat exchanger near the hot water storage tank in the basement of the
The heated water
via a heat
exchanger. To regulate this process, a
thermocouples attached to both the roof
of a sixteen degree Fahrenheit or greater temperature difference between the collector and the tank,
power is sent from the Steca control unit to the pumps to turn them on,
pumps will continue to operate until
apparatus provides adequate heating, but it can be
Proposed Modifications to Solar Hot Water Heating System
By modifying the previous system, it may be possible to extract an even greater amount of
energy from the solar radiation. Figure 2 shows the retrofitted system.
Figure 2
The most obvious change to the standard system is the substitution of the variable speed circulators
for the constant speed ones. These new pumps can be controlled by an external
from 0 to 10V—a 0V signal will not move the pump, 5V is half speed, and 10V is maximum speed.
method by which these pumps are controlled is also altered.
before, there are now two. The Steca system still controls
however, once the pumps are on, flow control is regulated by the installed Siemens
4
To regulate this process, a Steca 0301U Temperature Difference Controller
thermocouples attached to both the roof-top solar panel and the storage tank are installed. In the case
degree Fahrenheit or greater temperature difference between the collector and the tank,
control unit to the pumps to turn them on, and water begins to flow.
pumps will continue to operate until the temperature differential drops to five degrees
apparatus provides adequate heating, but it can be improved.
Modifications to Solar Hot Water Heating System
By modifying the previous system, it may be possible to extract an even greater amount of
Figure 2 shows the retrofitted system.
- Schematic of Retrofitted Solar Water Heating System
The most obvious change to the standard system is the substitution of the variable speed circulators
These new pumps can be controlled by an external signal varying linearl
a 0V signal will not move the pump, 5V is half speed, and 10V is maximum speed.
method by which these pumps are controlled is also altered. Where there was one control system
The Steca system still controls whether the pumps will turn on or not;
however, once the pumps are on, flow control is regulated by the installed Siemens APOGEE
ference Controller and
top solar panel and the storage tank are installed. In the case
degree Fahrenheit or greater temperature difference between the collector and the tank,
and water begins to flow. The
s. The current
By modifying the previous system, it may be possible to extract an even greater amount of
The most obvious change to the standard system is the substitution of the variable speed circulators
signal varying linearly
a 0V signal will not move the pump, 5V is half speed, and 10V is maximum speed. The
Where there was one control system
whether the pumps will turn on or not;
APOGEE Modular
5
Equipment Controller (MEC). This controller is capable of accepting inputs from varying sources and
generating various kinds of outputs (current, voltage, etc.) that are regulated by a written program.
Additional temperature sensors were installed on the water pipe leading to the solar collector and the
water pipe heading away from it. Finally, a program to command the water flow by varying output
voltages to the pumps was generated and uploaded into the APOGEE MEC.
Intended Customer/Market
The most immediate and readily-available market for the activities of this project is the Home
Depot Smart Home, the end result of the Duke University Smart Home Project. The building was
constructed in 2007 to function as a living laboratory that combines the residential needs of college
students with the latest technologies in home design. One intended result of these technologies is to
create a more environmentally-friendly lifestyle for its inhabitants. Reclaimed water from the roof is
used to fill the toilets and wash clothes, high efficiency windows adorn the walls, and a solar hot water
heating system provides hot water to the showers and dishwasher. Improvements to this hot water
system would appropriately align with the goals of the Smart Home as an eco-friendly dorm.
Additionally, with oil prices approaching $115 a barrel at the time of this writing, and emitted
greenhouse gases leading to global warming, “green” living has become a global imperative. In 2006,
industry experts expected the green market to grow by 10-20 billion dollars in the next five years.
Additionally, 60 percent of all architects, designers, etc. responded that they incorporate
environmentally-friendly techniques into their new projects. By 2010, green building is expected to
account for 5-10 percent of all new construction (up from 2 percent in 2004).
Furthermore, the United States government and other organizations have realized the necessity of
preserving the environment. The United States Green Building Council (USGBC) is an organization
dedicated to sustainable building and construction. They have a green building rating system called
Leadership in Environmental and Energy Design
Platinum rating at the time of this writing, which is the highest rating a building can achieve.
United States offers tax incentives to those attempting to lead a more sustainable lifestyle. The green
market is growing rapidly, and its expansion opens an enormous market for the modifications presented
in this report. The techniques presented within can be used by bo
construction of new buildings and the renovations of old ones in the years to come.
INFORMATION GATHERED
Existing Products
The solar hot water system initially installed in the Smart Home is a fairly effective system used
for extracting the sun’s energy. The original system utilized Taco constant speed pumps, shown in
Figure 3, which would run at 10 volts when the system was activated. The system, made by Sundance
Power Systems, was programmed to turn on when the solar c
sixteen degrees hotter than the hot water tank. The system would then run until the temperature
difference decreased to five degrees, at which point the system would shut off.
6
Leadership in Environmental and Energy Design (LEED). The Smart Home is expected achieve a LEED
Platinum rating at the time of this writing, which is the highest rating a building can achieve.
ffers tax incentives to those attempting to lead a more sustainable lifestyle. The green
market is growing rapidly, and its expansion opens an enormous market for the modifications presented
in this report. The techniques presented within can be used by both builder and consumer in the
construction of new buildings and the renovations of old ones in the years to come.
The solar hot water system initially installed in the Smart Home is a fairly effective system used
for extracting the sun’s energy. The original system utilized Taco constant speed pumps, shown in
, which would run at 10 volts when the system was activated. The system, made by Sundance
Power Systems, was programmed to turn on when the solar collector reached a temperature at least
degrees hotter than the hot water tank. The system would then run until the temperature
difference decreased to five degrees, at which point the system would shut off.
Figure 3 - TACO 009 Constant Speed Pump
(LEED). The Smart Home is expected achieve a LEED
Platinum rating at the time of this writing, which is the highest rating a building can achieve. Finally, the
ffers tax incentives to those attempting to lead a more sustainable lifestyle. The green
market is growing rapidly, and its expansion opens an enormous market for the modifications presented
th builder and consumer in the
The solar hot water system initially installed in the Smart Home is a fairly effective system used
for extracting the sun’s energy. The original system utilized Taco constant speed pumps, shown in
, which would run at 10 volts when the system was activated. The system, made by Sundance
ollector reached a temperature at least
degrees hotter than the hot water tank. The system would then run until the temperature
7
This design certainly saves energy and money since hot water from the solar system minimizes the
use of the natural gas boiler. The overall current Sundance Power Systems design is professionally
installed and proven effective. There are temperature sensors on both the incoming and outgoing pipes
which send signals to a Siemens APOGEE system. Additionally, there are temperature sensors on the
solar collector and the hot water tank. These sensors send signals to the Sundance System, which
controls when the system turns on and off.
While this system is effective, there are potential energy losses since the system runs at a constant
speed regardless of temperature difference. It was noticed that the system sometimes runs too fast or
too slow to maintain an optimal temperature difference between the incoming and outgoing pipes. If
the constant speed pumps were replaced with variable speed pumps, there would be great potential to
increase heat transfer. The increased cost of the variable speed pumps over the constant speed pumps
could likely be made up through cost and energy savings from decreased use of natural gas.
Expert Consultation
A number of experts were consulted for the project. First, multiple Duke engineering professors
were contacted regarding theory and application. Dr. Jon Protz provided insight concerning the heat
transfer analysis of the system. He helped establish a quantitative model that would determine both
mass flow rate and overall heat transfer rate. Throughout the semester, the model was adjusted with
his assistance. Dr. Edward Shaughnessy was helpful in fluid dynamics modeling as well.
Next, Dr. Rhett George provided some insight into electrical drives and motors. He determined that
it would be very difficult to control the existing system variably. It would involve accessing the two
internal windings, generating a signal whose frequency determines revolutions per minute, and
installing a separate amplifier for each winding. This would be an extremely complicated procedure,
particularly for mechanical engineers with little electrical circuit experience. Additionally, the pulsing
8
that would arise from this procedure would create a great loss in efficiency. There would be electrical
losses from restarting the motor and the restoring of momentum takes a lot of additional power. This is
hence counter-productive and would not be a viable way to alter the system.
Dr. Michael Gustafson’s expert advice was sought concerning electrical controls. He suggested two
main methods for controlling variable speed pumps if they were installed. One method would be to use
a Parallax Basic Stamp. This converts the measured temperature difference to a voltage between zero
and ten volts. This would require a DC chip conversion to produce an analog signal. Another potential
way to control the pump was to use the Siemens APOGEE system which is currently installed in the Duke
Smart Home. There is a computer installed in the Smart Home which contains the program Insight. This
is a Siemens program which is used to control the APOGEE system. In order to control this system,
additional help from someone familiar with Siemens systems was necessary.
Woody Cheek, a Duke energy control specialist, was consulted regarding controlling the Sundance
system by means of the Siemens system. He specializes in Siemens systems control across Duke’s
campus, and was very knowledgeable about the practicality of controlling a system of this type.
Installation of the system would not be very difficult; it was essential to determine how to control the
system numerically through quantitative analysis. He recommended reevaluating the model and
coming up with a table statement to deterministically control the system.
Mark Wilkinson, another Duke energy control specialist, was also consulted regarding splitting
signals to send to the Siemens system. Because the sensors measuring the temperature of the solar
collector and the hot water tank send signals to the Sundance system, an additional signal needed to be
sent to the Siemens system. It was not possible to splice the wires and duplicate the signal as was
originally proposed. One possible solution was to add an additionally sensor on the hot water tank and
the solar collector. It was determined that this would add unnecessary additional costs. Rather, the
model was reevaluated using the temperatures of the incoming and outgoing pipes from the tank to the
9
collector. High accuracy thermistors were added to the pipes to measure the temperatures. Signals
were then sent from these thermistors to the Siemens APOGEE system and the control code was based
on the temperature difference between these two sensors.
PRELIMINARY DESIGN WORK
Product Design Specification (PDS)
When designing a product, it is necessary to address customer and market needs. Therefore,
some overall goals were determined from analyzing these needs. A detailed PDS is included in Appendix
I.
Customer Needs:
The most important aspects of this system for a customer are energy efficiency, effective water
heating, and reliability. The energy payback should ideally be less than 5 years; this is a reasonable
energy payback for a homeowner.
Demand:
There are a number of reasons why a variable speed pump system would be desirable over a
constant speed pump system. Ideally, to market this product, the pumps should provide smoother
water flow, more accurate temperature control, energy and cost savings, a longer lifespan, and quieter
operation.
10
Performance Goals:
This system should be self-sustaining and fully operable without user control necessary. The
Siemens system allows for the system to run based on a program, which an operator can change at any
time if it becomes necessary. However, the system should not require user input to operate.
Quality Function Development (QFD)
QFD is a design tool used to analyze a design idea and generate possible improvements during
the planning process. It compares customer needs and requirements with engineering parameters of
the design.
Four different design ideas were compared to various customer needs. These included two possible
ways to reduce shower-warm-up waste, which was an originally proposed idea, a plan to alter the
temperature threshold of the current system, and to exchange the standard pumps for variable speed
pumps. Each design idea was ranked according to its ability to meet each customer need (1 = weak
correlation, 5 = strong correlation). The significant custom requirements included water conservation,
energy conservation, operating safety, cost effectiveness, reliability, water heating effectiveness, ease of
installation, and ease of use. The QFD can be seen in Appendix II.
Each of the four ideas was assigned correlations to the customer needs according to our best
judgments. A total score was determined for each idea. The QFD returned results that the variable
speed pumps would best meet the relevant customer needs. For example, simply altering the
temperature threshold of the current system would probably not be very beneficial. Because the
system is already installed, it would certainly be safe to operate, easy to install and use, and reliable.
There’s a possibility for increased energy and cost savings, but it would be relatively low. The
mechanical and electromechanical shower warm-up waste reduction devices could potentially save a
significant amount of water. They would not save much in terms of energy. There could be potential
11
safety issues, particularly with the electromechanical device. As mechanical engineers, we have limited
experience with electrical circuitry, so this would not be the ideal project. Furthermore, competitors
already have an existing product to achieve this, known as Shower Start. It is unlikely a much better
product could be produced given the knowledge base for this type of project.
Replacing the existing pumps with variable speed pumps could potentially save a lot of energy, and
hence money. It would be cost-effective, easy to operate and install, reliable, and safe. It is most likely
more effective than the current system and is therefore the method chosen to improve the solar hot
water system in the Duke Smart Home.
Theory of Inventive Problem Solving (TRIZ)
Engineering design problems generally face contradictions between numerous parameters. TRIZ
is an engineering problem solving method invented by Genrich Altschuller in 1946 to specifically combat
this problem of contradicting parameters. TRIZ has 39 engineering characteristics and 40 inventive
principles which are used to solve these contradictions. The main function of TRIZ is to eliminate the
disadvantages of these contradictions rather than compromise the product.
For this particular problem, there were three main design contradictions which needed to be
addressed. The first of these was to increase the speed of the device without significantly increasing the
complexity of the device. The main resolution to this contradiction was to replace a mechanical means
with a sensory means or to disregard a portion of the system which has served its function. In this case,
the control of the new speed pumps would in fact be controlled by a sensory control, the SIEMENS
system, which is the basis of the project.
The second contradiction encountered was between decreasing the amount of energy wasted
without increasing device complexity. Once again, this is the main basis of our project and hence was
very important to consider. The TRIZ principle to consider was to introduce some form of feedback
12
action to improve the process. This is precisely the type of control for which the Siemens APOGEE
system is designed.
The third and final contradiction faced in the design of this project was improving accuracy of
measurement without compromising the reliability of the device. There were two main inventive
principles that could be utilized to minimize this contradiction. The first was to increase the degree of
device segmentation. This would ensure that if one component of the device fails, it would be more
easily replaceable and hopefully would not jeopardize the entire device. This was utilized in the project
by keeping the Steca control system in place along with the Siemens APOGEE system; this will be
discussed later in more detail. The second inventive principle pertaining to this problem was to
introduce feedback to improve the process. Again, this was similar to the second problem and will be
discussed further.
The following figure shows the TRIZ method and how it can be used to solve engineering
contradictions.
Worsening →
Improving ↓
Device
Complexity
Reliability
Speed -Mechanics substitution
-Discard Function
X
Energy Efficiency -Feedback X
Accuracy of
Measurement
X -Feedback
-Segmentation Table 1 - TRIZ Contradictions
Design Decision
The results obtained from the QFD and TRIZ led towards adapting parameters for the final
design decisions. Most importantly, the QFD led to the decision to implement a variable speed pump to
improve the solar hot water system in the Duke Smart Home. Additionally, the TRIZ method confirmed
use of the Siemens APOGEE system as a reliable way to control the system.
In order to further ensure system reliability, it was determined that the Steca system would
continue to control when the system turns on and off.
new system, the Steca system would ensure the system ran as it did previously.
The Siemens system utilizes a feedback PID controller. This ensures the device will run base
external conditions. This should increase energy savings and hence cost savings, which are in
customer requirements.
Higher-accuracy thermistors were installed on the incoming and outgoing pipes as well. This was to
ensure accurate, reliable control and measurement of the system. Because the temperature differential
determines the speed of the operating system, it was essential to have accurate temperature
measurements.
The following figure shows the prototype design:
13
In order to further ensure system reliability, it was determined that the Steca system would
l when the system turns on and off. If something went wrong in installation of the
new system, the Steca system would ensure the system ran as it did previously.
The Siemens system utilizes a feedback PID controller. This ensures the device will run base
external conditions. This should increase energy savings and hence cost savings, which are in
were installed on the incoming and outgoing pipes as well. This was to
able control and measurement of the system. Because the temperature differential
determines the speed of the operating system, it was essential to have accurate temperature
gure shows the prototype design:
Figure 4 - Prototype Design System Layout
In order to further ensure system reliability, it was determined that the Steca system would
something went wrong in installation of the
The Siemens system utilizes a feedback PID controller. This ensures the device will run based on
external conditions. This should increase energy savings and hence cost savings, which are in-line with
were installed on the incoming and outgoing pipes as well. This was to
able control and measurement of the system. Because the temperature differential
determines the speed of the operating system, it was essential to have accurate temperature
14
QUANTITATIVE ANALYSIS
Summary of Overall Approach
The process of determining the equation to use in the SIEMENS APOGEE system for controlling
the variable speed pump can be broken down into two parts. First, an analytical approach was used to
model the solar hot water heat exchanger system, utilizing Maple to solve for heat transfer in terms of
specific temperatures and differentiate with respect to mass flow. Then, a numerical approach was used
to solve for the mass flow value that maximizes heat transfer and plot a linear fit for corresponding
voltage and temperature difference values.
Variables and Assumptions
As the figure 5 illustrates, the Q1 heat flows from the solar panel to the water coming up from the
water tank, and the Q2 heat flows from the heat exchanger in the tank to the water. Q3 can be defined as
the overall heat flow in the system. The heat exchanger equations below model these three heat flows.
Because the water pipes are well insulated, it can be assumed that there is negligible heat loss along the
pipes. In addition, constant specific heat was assumed for the relevant temperatures.
Equation 1 - Modeling Heat Flows
)(
)1()(
)1()(
343
242
311
2
1
TTcmQ
eTTcmQ
eTTcmQ
p
cm
UA
p
cm
UA
p
p
p
−⋅⋅=
−⋅−⋅⋅=
−⋅−⋅⋅=
⋅
−
⋅
−
15
Figure 5 - Diagram of Heat Flows and Temperatures
Approximating Overall Heat Transfer Coefficient
The overall heat transfer coefficients UA of heat exchangers are constant for ideal heat
exchangers. However, because the solar hot water system does not have ideal heat exchangers, Excel was
used to find a way to approximate UA1 (for the solar panel) and UA2 (for the water tank heat exchanger).
The equations for Q1 and Q2 were set equal to each other and were solved for UA1, yielding the equation
below. Similarly, the equations Q2 and Q3 were set equal to each other and solved for UA2. Using these
equations, UA1 and UA2 were calculated for all the preliminary collected temperature data. Then, the UA
values were plotted against their corresponding temperature differences on Excel. As shown in the graphs
in figure 6, a linear fit equation was determined to approximate UA1 and UA2. The linear fits had R2
values of 0.888 and 0.943 respectively.
T1
T2
T3 T4
Q1
Q2
pcmTT
TTUA ⋅⋅
−
−−=
31
411 ln
Figure 6 – Overall heat transfer coefficients times area vs. temperature difference of pipes for
0.0
1000.0
2000.0
3000.0
4000.0
5000.0
6000.0
7000.0
8000.0
0
UA
0.0
100.0
200.0
300.0
400.0
500.0
600.0
700.0
800.0
900.0
0
UA
16
Equation 2 - UA Values
Overall heat transfer coefficients times area vs. temperature difference of pipes for solar collector (UA
tank heat exchanger (UA2)
y = 375.2x
R² = 0.888
5 10 15 20
∆T
UA1 vs. ∆T (pipes)
y = 40.05x
R² = 0.943
5 10 15 20
∆T
UA1 vs. ∆T (pipes)
pcmTT
TTUA ⋅⋅
−
−−=
24
232 ln
solar collector (UA1) and
y = 375.2x
R² = 0.888
25
y = 40.05x
R² = 0.943
25
17
Analytical Quantitative Analysis with Maple
The Q1, Q2, and Q3 equations (equation 1) were manipulated in Maple, shown in equation 3. First,
Q was written in terms of T1 and T2. This was done by setting Q1 and Q2 equal and solving for T3. Then,
Q2 and Q3 were set equal and solved for T4. Finally, the expression for T4 was plugged into the Q2
equation and the resulting equation was solved in terms of T1 and T2. This resulting equation is shown
below.
Equation 3 – Q2 in terms of T1 and T2, the temperatures of the collector and tank
Then Maple was used to differentiate this equation with respect to mass flow. The very complicated
equation is shown below and further simplified and factored with Maple.
18
Equation 4 - ���
��� with respect to constants and T1 and T2
Using the analytical approach, the above equation must be set equal to zero and solved for the optimal
mass flow.
Numerical Quantitative Analysis with Excel
Equation 4 cannot be solved explicitly for �� , the mass flow rate. Thus, Excel’s “goal seek”
function was used to numerically solve this equation and find the optimal mass flow through iteration.
With each temperate data set collected, an optimal mass value was determined. Then, using the equation
below, mass values were normalized to give output voltages. 0.37 kg/s is the maximum pump speed and
10V is the maximum voltage.
Equation 5 - Normalized Voltage
Finally, the output voltages were plotted with respect to their corresponding temperature differences
in Excel. A linear fit equation was determined by Excel, as shown in figure 7 and equation 6, and was
used for the voltage control programmed into the SIEMENS APOGEE system.
Vskg
mVoltage 10
/37.0⋅
=
&
Figure 7
Equation 6
Prototype Construction
Materials and Devices Used
When discussing the materials and devices used in this experiment, one must begin with the
pumps themselves. The two Taco 009
pumps.
0.00000
20.00000
40.00000
60.00000
80.00000
100.00000
120.00000
0
Vo
lta
ge
19
Figure 7 – Optimal voltage for given temperature differences
Equation 6 – Control voltage given temperature difference
When discussing the materials and devices used in this experiment, one must begin with the
pumps themselves. The two Taco 009-VV Cartridge Circulators are relatively small, variable speed
Figure 8 - Taco 009-VV Circulators
y = 5.493x
R² = 0.904
5 10 15 20
∆T
Voltage vs. ∆T (pipes)
When discussing the materials and devices used in this experiment, one must begin with the
VV Cartridge Circulators are relatively small, variable speed
y = 5.493x
R² = 0.904
25
They were chosen because they are identical (except for the voltage
previously installed, which makes for easy integration with the previous system. Like the old pumps, the
new ones are constructed from bronze as opposed to cast iron. This deci
oxidation effects that plague cast iron in a non
pumps possess a head range of 0 to 34 ft. and are capable of flow ranging from of 0 to 8 gallons per
minute (GPM). Finally, their speed can be controlled linearly by varying the input
to 10 V.
The next installation components to consider are the pipe temperature sensors.
Figure
The two installed Mamac TE-704
their 6 foot plenum rated cables and 2 inch 304 SS probes, they are capable of detecting temperature
differences as minute as ± 0.2˚C. The final primary component to consider is the S
Modular Equipment Controller (MEC). While one may consider the pumps to be the heart of this project,
the MEC is without doubt the brain.
20
because they are identical (except for the voltage-varying components) to those
previously installed, which makes for easy integration with the previous system. Like the old pumps, the
new ones are constructed from bronze as opposed to cast iron. This decision was made to minimize the
oxidation effects that plague cast iron in a non-isolated system: bronze is immune to these effects. The
pumps possess a head range of 0 to 34 ft. and are capable of flow ranging from of 0 to 8 gallons per
y, their speed can be controlled linearly by varying the input control
The next installation components to consider are the pipe temperature sensors.
Figure 9 - Mamac TE-704-A-3 Pipe Temperature Sensors
704-A-3 Pipe Temperature Sensors are highly accurate instruments. Via
their 6 foot plenum rated cables and 2 inch 304 SS probes, they are capable of detecting temperature
˚C. The final primary component to consider is the Siemens APOGEE
Modular Equipment Controller (MEC). While one may consider the pumps to be the heart of this project,
the MEC is without doubt the brain.
Figure 10 - Siemens APOGEE MEC
varying components) to those
previously installed, which makes for easy integration with the previous system. Like the old pumps, the
sion was made to minimize the
isolated system: bronze is immune to these effects. The
pumps possess a head range of 0 to 34 ft. and are capable of flow ranging from of 0 to 8 gallons per
control voltage from 0
The next installation components to consider are the pipe temperature sensors.
3 Pipe Temperature Sensors are highly accurate instruments. Via
their 6 foot plenum rated cables and 2 inch 304 SS probes, they are capable of detecting temperature
iemens APOGEE
Modular Equipment Controller (MEC). While one may consider the pumps to be the heart of this project,
The APOGEE system, by accepting a wide assortment of inputs and genera
analog outputs, is capable of controlling numerous devices
programming it through the Powers Process Control Logic, it is capable of varying the voltage sent to
these circulators in a controlled and prede
Fabrication
The fabrication of this product required
pumps, connect the pumps to the APOGEE system, integrate the high accuracy pipe sensors, and write
the system code. Obtaining project approval was no small matter, for the Duke
Administrators take students tampering with the school’s property very seriously.
Meetings, request letters, and an on
stages.
The next necessary task was the actual replacement of t
all the water running through the pumps b
Once the water was stopped, the old constant
bolts attaching them to the pipe.
21
The APOGEE system, by accepting a wide assortment of inputs and generating both digital and
analog outputs, is capable of controlling numerous devices—including the Taco pumps. By
programming it through the Powers Process Control Logic, it is capable of varying the voltage sent to
these circulators in a controlled and predetermined manner.
ication of this product required five main steps: obtain project approval, replace the
pumps, connect the pumps to the APOGEE system, integrate the high accuracy pipe sensors, and write
btaining project approval was no small matter, for the Duke Faculty
dministrators take students tampering with the school’s property very seriously.
Figure 11 - Obtaining Project Approval
Meetings, request letters, and an on-site inspection were all required to get past this most crucial of
the actual replacement of the circulators. The first step was
all the water running through the pumps by turning two shut-off valves above and below their positions.
stopped, the old constant-speed circulators were removed by loosening several
ting both digital and
including the Taco pumps. By
programming it through the Powers Process Control Logic, it is capable of varying the voltage sent to
steps: obtain project approval, replace the
pumps, connect the pumps to the APOGEE system, integrate the high accuracy pipe sensors, and write
Faculty and
site inspection were all required to get past this most crucial of
he circulators. The first step was to shut off
off valves above and below their positions.
removed by loosening several
The Taco 009-VV pumps were chos
installing them into the current system
the two new pumps where the previous ones were, tightening the
that was needed. Once the new circulators
Controller. Wires were run from the MEC’s outputs to the input connections on the Taco pumps.
Figure 13 - Connections on Taco Pump (left)
Once the pumps were installed and connected,
These sensors measure the temperature of a pipe’s outer wall. In doing this, a
of the inside water’s temperature may be obtained. The first step
the pipe, for this coating may interfere with heat transfer.
22
Figure 12 - Replacing Pumps
VV pumps were chosen because of their similarity to the preexisting ones. To this end,
installing them into the current system was quite easy. Simply reversing the previous process by placing
the two new pumps where the previous ones were, tightening the bolts, and opening the valves
circulators were installed, they had to be connected to the APOGEE
run from the MEC’s outputs to the input connections on the Taco pumps.
Connections on Taco Pump (left), Output Connection on APOGEE Controller (right)
were installed and connected, the pipe temperature sensors had to
These sensors measure the temperature of a pipe’s outer wall. In doing this, an accurate approximation
of the inside water’s temperature may be obtained. The first step was to sand away the outer coating of
y interfere with heat transfer.
en because of their similarity to the preexisting ones. To this end,
the previous process by placing
the valves was all
be connected to the APOGEE
run from the MEC’s outputs to the input connections on the Taco pumps.
Connection on APOGEE Controller (right)
had to be installed.
n accurate approximation
s to sand away the outer coating of
Next, to increase heat transfer, thermal compound
resided. Finally, the sensors were strapped to the pipe and connected to the Siemens APOGEE system.
The final step in the fabrication of this project wa
within the system.
Results and Analysis
Experimental Setup
After the installation of new circulators into the solar hot water system, it was necessary to setup
the system for testing. A successful system tests was accomplished by comparing the
the new variable speed solar hot water system to the constant speed one. The setup of the old system
could essentially be emulated by driving the pumps at 10V, or their full sp
system setup before and after the addition of the
Siemens APOGEE controller included in the layout. T
of the solar collectors, T2 is the temperature in the solar hot water tank, and T
temperatures of the outgoing and incoming pipe, respectively, from the collector.
23
Figure 14 - Installing Temperature Sensors
at transfer, thermal compound had to be placed on the spots where the sensors
strapped to the pipe and connected to the Siemens APOGEE system.
he fabrication of this project was to create the code that will govern the f
After the installation of new circulators into the solar hot water system, it was necessary to setup
A successful system tests was accomplished by comparing the heat transfer of
new variable speed solar hot water system to the constant speed one. The setup of the old system
could essentially be emulated by driving the pumps at 10V, or their full speed. Figure 1
system setup before and after the addition of the new temperature sensors on the pipes, with the
controller included in the layout. T1 represents the temperature in the
is the temperature in the solar hot water tank, and T3 and T4 are the
temperatures of the outgoing and incoming pipe, respectively, from the collector.
be placed on the spots where the sensors
strapped to the pipe and connected to the Siemens APOGEE system.
will govern the flow of water
After the installation of new circulators into the solar hot water system, it was necessary to setup
heat transfer of
new variable speed solar hot water system to the constant speed one. The setup of the old system
15 shows the
new temperature sensors on the pipes, with the
represents the temperature in the absorber plate
are the
24
Figure 15 – Schematic of changes to solar hot water system
The experimental process consisted of recording data via the Siemens APOGEE System. Table 2
shows the variables that were collected, and the description for each one.
Variables Description
VC39Test Test Status - Outputs a “1” if 10V constant mode is enabled, outputs a “0” for variable
“program” control
C39P01 Pump Status - Outputs a “1” if pumps are turned on, outputs a “0” if pumps are off
VC39DT01 Temperature Difference between pipes (T4-T3)
C39PZ01 Voltage speed signal sent to the pumps (4.3-10VDC)
VC39PZ01 Voltage desired by the program to run pumps at optimal speed (can exceed pump limits) Table 2 – Collected Experimental Variables and Descriptions
The primary concern with testing was to figure out a method for keeping as many conditions
constant as possible. Since it would be necessary to run the pumps for a period of time at constant
speed, and a period of time at variable speed, it was of the upmost importance to control for any
variations in weather or outside conditions that would vary the heat transfer rates. It was speculated
that since every half-hour interval of time throughout the day has relatively constant condition (in terms
of temperatures and light intensities), the pumps could be run by alternating between the constant 10V
mode, and variable “program” control every fifteen minutes. A separate variable, VC39Test, kept track
of which mode the pumps were being run in.
T4
T3
Output
s
Input
s
Pump
Output
sInput
s
T2
T1
Steca Controller
Siemens
Controller
Pump
Output
s
Input
s
T2
T1
Steca Controller
Programming the Pumps
The program for controlling the pumps was coded onto the Siemens
Siemens program, Insight. It was written in the
BASIC. A computer in the Smart Home clean lab was connected via Ethernet to the
and allowed full access to the system.
Figure 16
The first section of the code set
clock. This timer was used for testing purposes to alternate every 15 minutes between program control
and constant speed. The second section of code calculated the
two pipe temperature sensor inputs.
The third section of code was added to
been off for a while. This was instituted because the solar hot water system is a drain
it therefore takes a minute or two for water to flow continuously throughout the system when the
25
The program for controlling the pumps was coded onto the Siemens APOGEE Controller using the
Siemens program, Insight. It was written in the Powers Process Control Language, which is similar to
A computer in the Smart Home clean lab was connected via Ethernet to the APOGEE
and allowed full access to the system. Figure 16 shows the code of the program.
– Siemens APOGEE program code for controlling pumps
first section of the code set up a timer that counted in seconds, and was synchronized to a real
used for testing purposes to alternate every 15 minutes between program control
The second section of code calculated the ∆T variable between the pipes from the
two pipe temperature sensor inputs.
The third section of code was added to allow the pumps to come on at full speed after they have
stituted because the solar hot water system is a drain-
it therefore takes a minute or two for water to flow continuously throughout the system when the
Controller using the
, which is similar to
APOGEE controller,
s synchronized to a real
used for testing purposes to alternate every 15 minutes between program control
∆T variable between the pipes from the
allow the pumps to come on at full speed after they have
-back system, and
it therefore takes a minute or two for water to flow continuously throughout the system when the
26
pumps have been off for a period of time. It was desired to have full head when the system was initially
turned on, and because pump head is a function of rotor speed, the maximum speed was set on startup.
The fourth section of code alternates the pump control between a constant 10 V and variable speed
every fifteen minutes. The optimal voltage, as found earlier from the quantitative analysis (equation 6)
was governed by the following linear equation:
����� ����� � 5.49 � ∆�
Because the calculated optimal voltage can be higher than 10V, the upper limit for the pump speed
signal, and lower than 4.3V, the lower limit for which there is enough pressure to pump the water
through the system, additional code had to be written to prevent the pump speed signal from going out
of bounds. The last statement of the code sends the program back to the top, thereby allowing the
code to run in a continuous loop.
Results
The pertinent variables for the experiment were logged in Siemens APOGEE system. The computer
recorded values every minute in the APOGEE controller, and the data was logged to the Siemens
computer in the clean lab every three hours. The Insight program has a plotter module, which allows
collected data to be plotted vs. time. The results for the first four days are shown in figure 17, and
additional days are shown in Appendix V.
27
Figure 17 – Graphs of data collected for the first four days of testing (4/17 – 4/20). The blue line is the optimal voltage,
the red line is the actual voltage sent to the pump, the green line is ∆T, the purple line is the pump status, and the yellow line
is the test status.
The first two days of testing were very sunny days, as noted by the large parabolic shaped curves of
the blue and green lines. Since the green line represents ∆T, and ∆T is a function of Q, the heat transfer,
the height of the green line reflects the amount of heat transferred throughout the day. The second
two days of testing were partly cloudy. As seen in the data, during various portions of the day, the heat
transfer dropped substantially when the sun was behind the clouds.
MATLAB Analysis
From graphs of the data, it seems that our variable pumping method was much more valuable
during cloudy days. Throughout these days, the optimal voltage often dipped below the upper limit of
10V, and the pumps were able to run variably. For the sunny days, the only gains obtained from a
variable system are at the beginning and end of the days, when the sun intensity is lower. It can be seen
28
from the sunny days, however, that the solar hot water system would have benefitted from having
pumps with a maximum speed about two or three times faster than the pumps installed in the system.
The data was then exported into Microsoft Excel, where it was formatted properly for input into
programs for analysis. The first attempt to analyze the data was via MATLAB. Because the data in the
two different time intervals (constant and variable speed) needed to be compared against each other
directly, a program had to be written to perform the proper integration. To find the total heat transfer
for each day, the time intervals had to be separated for constant and variable speed, and then
integrated over time throughout the day. Dividing by the amount of time that each is active, the
average heat transfer rate for each method can be analyzed. Figure 18 shows the initial attempt at
coding in MATLAB.
Figure 18 – Initial MATLAB code written to analyze test data
29
JMP Analysis
While writing the MATLAB code, however, it was decided that a different program would be more
useful for analyzing the collected data. JMP, a statistical analysis program, was designed to organize and
analyze large amounts of easily. All 9,320 useable data points obtained over the course of a week were
tabulated in JMP. The results were quite encouraging. In general, the modified system performed
significantly better than the one originally installed. The average heat transfer for both standard and
modified systems for each of the days included in the study is presented below.
Date Standard
System (W)
Modified
System (W)
Difference (W)
4/19/2008 1345.46 1449.05 103.58
4/20/2008 1529.08 1879.10 350.02
4/21/2008 -672.22 -1141.89 -469.67
4/22/2008 -487.39 1103.58 1590.98
4/23/2008 911.95 1437.78 525.83
4/24/2008 2269.75 2563.35 293.60
2/25/2008 1226.01 1550.01 324.01 Table 3 - Heat Transfer Values for Given Date
As can be readily seen from the last column, in only one out of the 7 days tested did the original
system outperform our modifications. Looking at the values for April 21st brings an interesting point. In
order for the system to run properly, the program is set to run the pumps at 10 volts for approximately 3
minutes. This is necessary to allow the stagnant water in the outgoing pipe to move through the
system. Additionally, since the incoming pipe feeds water into a drainback tank, there will be a lower
temperature in this pipe while the system is off. When the system first starts, it takes a while for the
temperature sensor in the outgoing pipe to return to the temperature of the water. This explains why
there are negative values of ∆T, and therefore heat transfer. Weather conditions which would run the
system at short, intermittent periods throughout the day could lead to an overall heat transfer value
that is negative.
30
Looking at the individual days is beneficial, but taking the total values for the week provides a much
more adequate evaluation. Over the course of a week, the system is tested much more thoroughly, for
it is subjected to a wider assortment of environmental conditions. Furthermore, a larger amount of data
points leads to better statistical results. The averaged results over the entire week are presented below.
Date Standard
System (W)
Modified
System (W)
Difference (W)
Week 1164.29 1625.45 461.16
Table 4 - Averaged Weekly Heat Transfer
For the entire week, the modified variable speed system averaged an additional 461.16 W of heat
transfer when compared to the original. After running a significance test on the data, it is determined
that these results are statistically significant and not merely the results of random chance. The following
figures further analyze the data. Figure 19 provides a histogram showing the number of data points
falling within a given heat transfer distribution range.
Figure 19 - Histograms of Modified System (left), Original System (right)
Figure 20 plots heat transfer as a function of time and include a second degree polynomial fit to the
data. While the fit may be a poor predictor of heat transfer given the changing environmental
conditions, it does provide considerable insight into heat transfer trends.
31
Figure 20 - Plots of Heat Transfer vs. Time for Modified (left), Original (right)
Upon investigating the polynomial fits and their respective units, one can easily determine that the
heat transfer for the modified fit is greater at all points in time than that for the original fit.
Cost and Energy Savings
The final task in evaluating the effectiveness of the system modifications was to determine the
energy and money saved in a typical year. Using the new system, it was projected that 928.04 kilowatt
hours of electricity or natural gas will be saved during a typical year. The cost benefits of this increase in
efficiency are presented in table 5.
Energy Source Energy Saving
(KWh/yr)
Cost of Heating
Source* ($/KWh)
Heating Efficiency Cost Savings
($/yr)
Natural Gas 928.04 $0.04 80% $46.40
Electricity 928.04 $0.10 90% $103.12 Table 5 - Savings on Water Heating Costs for Gas and Electric Resistance Heaters (*Source: Colorado Renewable Energy
Society)
The modifications to the Home Depot Smart Home’s solar water heating system do indeed produce
tangible results. On a natural gas system such as that employed by the Smart Home, a homeowner
would save $46.40 per year. An electric customer would save $103.12 per year. The final question to
answer is whether these modifications are worth the cost involved. The additional costs involved in
switching to variable speed pumps and adding temperature sensors amounted to
This means the payback period for the natural
payback period for an electric customer is under five.
Energy Source Cost ($)
Natural Gas $445
Electricity $445
These payback periods are not unreasonable considering the expected life of the system is over 30
years. The variable speed modification to the Smart Home
valuable, tangible results.
Figure 21 – Payback of system modifications for life of system for different heating methods
-1000
-500
0
500
1000
1500
2000
2500
3000
0 5
Inv
est
me
nt
($)
Payback for Life of System
Eletric Resistance Heating
32
switching to variable speed pumps and adding temperature sensors amounted to approximately
This means the payback period for the natural gas-using Smart Home is just under ten years.
payback period for an electric customer is under five. This information is summarized in
Cost Savings
($/yr)
Cost of Heating
Source ($/KWh)
Payback
Period (yr)
$46.40 $0.04 9.59
$103.12 $0.10 4.32Table 6 - Payback Periods
These payback periods are not unreasonable considering the expected life of the system is over 30
years. The variable speed modification to the Smart Home solar hot water system does indeed prod
Payback of system modifications for life of system for different heating methods
10 15 20 25 30
Time (years)
Payback for Life of System
Eletric Resistance Heating Natural Gas Boiler
approximately $445.
using Smart Home is just under ten years. The
This information is summarized in table 6.
Payback
Period (yr)
9.59
4.32
These payback periods are not unreasonable considering the expected life of the system is over 30
solar hot water system does indeed produce
Payback of system modifications for life of system for different heating methods
30 35
Monte Carlo Simulation
As a part of designing for Six Sigma, Monte Carlo simulations
deterministic model is found, it can be run using randomly distributed input values. The corresponding
output yields a probabilistic analysis.
In the payback analysis above, it
during a typical year. This number was obtained from our experimental results. It can be assumed that
this value in actuality has a gaussian distribution. The standard deviation of this distribution was
estimated to be about 150 kilowatt hours.
cost savings per year can be calculated based on the distribution, and is displayed in the histogram in
figure 22.
Figure 22 – Histogram for cost savings per year for Monte Carlo
0
5
10
15
20
25
30
50 60 70
Fre
qu
en
cy
Histogram for Savings Per Year
33
As a part of designing for Six Sigma, Monte Carlo simulations can be extremely valuable. After a
deterministic model is found, it can be run using randomly distributed input values. The corresponding
output yields a probabilistic analysis.
it was projected that 928.04 kilowatt hours of energy
. This number was obtained from our experimental results. It can be assumed that
this value in actuality has a gaussian distribution. The standard deviation of this distribution was
ilowatt hours. Using the deterministic model calculated above, the actual
cost savings per year can be calculated based on the distribution, and is displayed in the histogram in
Histogram for cost savings per year for Monte Carlo Simulation
80 90 100 110 120 130 140 150
Dollars Saved / Year
Histogram for Savings Per Year
can be extremely valuable. After a
deterministic model is found, it can be run using randomly distributed input values. The corresponding
energy will be saved
. This number was obtained from our experimental results. It can be assumed that
this value in actuality has a gaussian distribution. The standard deviation of this distribution was
Using the deterministic model calculated above, the actual
cost savings per year can be calculated based on the distribution, and is displayed in the histogram in
150 More
34
CONCLUSIONS
Project Takeaways
The variable speed control program successfully increased the overall heat transfer of the solar
hot water system in the Duke Smart Home. Yearly payback was lower than expected, but nonetheless
did result in cost and energy savings. This system is particularly worthwhile if the back-up heating
system is an electrical resistance one. The payback for a system of this type is around four years. The
payback for a system with a natural gas backup system is around 10 years.
The system proved reliable and effective. The variable system is particularly advantageous on
cloudy days, where the program frequently runs the pumps at a lower speed. There is no energy loss to
using this system rather than the previous system. Therefore, given the additional savings that can be
achieved during cloudy weather, it is advantageous to choose a variable speed system over a constant
one.
Future Project Directions
The main way to improve the effectiveness of this system is to install pumps which are capable
of operating at a mass flow rate greater than the current pumps. There were many instances where the
program calculated the ideal voltage to be much higher than ten volts. If pumps allowing greater flow
rates were installed, much larger savings would be possible.
The main restriction for this application was that it required rearranging the pipes in the system for
the appropriate pumps to be installed. Therefore, this method is only feasible when installing a new
system rather than improving a previously-installed system.
35
A second improvement would be to control the system entirely with the Siemens APOGEE system
rather than with the Steca control as well. Since the Steca program was already programmed to turn
the pumps on and off, those signals remained as they were. However, if the system were built from
scratch, the signals from the temperature sensors could be sent to the Siemens system for overall
control. This would be ideal since the Siemens system is proven very reliable, and it is desirable to have
only one control for the system.
A third suggestion would be to analyze the power requirements of the pumps. Since pumps running
at a slower speed consume less electric power, there may also be energy savings in this area. For our
analysis, it was assumed that this energy savings would be negligible compared to heat energy gains
from running at variable speeds. However, a test to determine how much energy could be saved by
running the pumps at a lower speed could be valuable.
36
References
Cengel, Y. A. (2007). Heat and Mass Transfer: A Practical Approach (3rd Edition ed.). New York:
McGraw-Hill.
http://ezinearticles.com/?Booming-Green-Building-Market-Continues-to-Grow&id=179435
http://www.cres-energy.org/blogs/blogs_roedern06Jan.html
37
APPENDIX I
Product Design Specification
1.0 Product Title
1.1 Smart Home Variable Speed Water Pump for the Solar Hot Water System
2.0 Mission Statement
2.1 To retrofit and improve the Home Depot Smart Home’s Solar Water Heating system by
focusing on heating capability and efficiency
3.0 Customer Needs
3.1 Energy Conservation
3.2 Effective Water Heating
3.3 Reliability
4.0 New or Special Features
4.1 Variable speed water pump
4.2 Reprogramming of temperature thresholds
4.3 Additional sensors to accurately measure temperature change
4.4 Additional sensors to effectively measure power consumption
5.0 Competition
Competition is comprised of other hydronic system companies including:
5.1 MetLund D’MAND Systems – pumpless system
5.2 Laing Instant Hot Water Pumps – recirculation pumps
6.0 Intended Market
6.1 TACO – Hydronic Systems and Components company sells a variety of pumps and pump
accessories. TACO pump currently installed on solar hot water heater in the Smart Home.
6.2 Other hydronic systems companies
7.0 Relationship to Existing Product Line
Currently, TACO sells a variety of multi-purpose valves to ensure more reliable pump flow.
Products include:
7.1 shut-off valves
7.2 flow control valves
7.3 non-slam check valves
7.4 flow-metering valves
New products to be introduced applying specifically to solar hot water heating systems include:
7.5 Solar X-Pump Block – combines stainless steel flat plate heat exchanger, variable speed
mixing control, 2 bronze circulators, and solar differential temperature control
7.6 New circulators with integral temperature differential controls
38
Variable speed mixing control can be added to systems already in place that simply have single-
speed temperature differential control. Must be easily installed in current TACO system, be
consistent with sizing and materials for standard operation.
8.0 Market Demand
Variable speeds pumps offer a variety of components desirable for consumers:
8.1 Smoother water flow
8.2 More accurate temperature control
8.3 Uses less power – energy and cost savings
8.4 Less wear and tear on pump – longer lifespan
8.5 Quieter operation
9.0 Price
9.1 Current TACO circulator pumps range from $75 - $275
10.0 Functional Performance
10.1 Easily controllable
10.2 Easy to wire
10.3 Variable speed control
10.4 Voltage range of controller
10.5 Ability to analyze outside conditions for optimal heat transfer
10.6 Low power requirements
10.7 Pump can withstand temperatures up to 180F
11.0 Physical Requirements
11.1 Because the controller will probably be hidden, the physical requirements are not strict.
The controller must be UL approved, and fit into a compact box. Any outdoor sensors must also
be UL listed and waterproof.
12.0 Service Environment
12.1 Outdoor sensors will be exposed to the elements (corrosive environment, dirt and dust,
humidity)
12.2 Pump and controller will perform in a controlled environment with temperature
fluctuations between 50 and 80 F. Humidity will be controlled. Pump will need to handle fluid
temperatures up to about 180F.
13.0 Life-Cycle Issues
13.1 Should have a working life as long as the entire solar hot water product system, or be easily
replaceable or fixable during the life of the system
13.2 Eco-friendly materials should be recyclable and contain minimal heavy metals
14.0 Human Factors
14.1 One-time installation will be required.
14.2 The modified factors will require no additional maintenance compared to the fixed speed
pump.
14.3 Monitoring system will be required to ensure system is running at optimal conditions.
14.4 Aesthetics considerations are not relevant because the system will be installed in the
basement of the Smart Home.
39
15.0 Corporate Constraints
15.1 Convincing Residential Life and Housing Services that the Smart Home Variable Speed
Water Pump saves a significant amount of energy and therefore should be installed in the Smart
Home.
15.2 The Pratt School of Engineering must also approve the installation of the Variable Speed
Water Pump in the Smart Home.
16.0 Legal Requirements
16.1 Making sure the name “Smart Home” does not infringe on trademark rights
16.2 Verifying that the product does not violate patent laws on similar inventions
16.3 Investigate list of related patents
16.4 Making sure the product is UL listed for safety considerations
40
APPENDIX II
QFD
41
APPENDIX III
Gantt ChartSmart Home Variable Speed Water Pump
1/10/2008 1/17/2008 1/24/2008 1/31/2008 2/7/2008 2/14/2008 2/21/2008 2/28/2008 3/6/2008 3/13/2008 3/20/2008 3/27/2008 4/3/2008 4/10/2008 4/17/2008 4/24/2008
Conceptual Design
Preliminary Design
Product Design Specification
Schedule
Expert Meeting
Budget
Prototype Description
Order Parts
Detailed Design
Build Prototype
Obtain Approval for Installation
Test Prototype
Final Report
42
APPENDIX IV
Budget
Items Purchased Quantity Price Total
Price
TACO MODEL 009-VVBF5 VARIABLE SPEED SETPOINT CIRCULATOR
PUMPS
2 $ 476.00 $ 952.00
Mamac Systems TE-704-A-3 Pipe Temperature Sensors 2 $ 15.00 $ 30.00
Subtotal $ 982.00
Items Replaced
TACO MODEL 009-BF5 BRONZE CIRCULATOR PUMPS 2 $ 268.50 $ 537.00
Net Cost $ 445.00
43
Appendix V
Additional Charts
Figure 23 – Graphs of data collected for the last five days of testing (4/21 – 4/25). The blue line is the optimal voltage,
the red line is the actual voltage sent to the pump, the green line is ∆T, the purple line is the pump status, and the yellow line
is the test status.