impacts of voltage reduction - ieee power & energy society
TRANSCRIPT
![Page 2: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/2.jpg)
Topics
• Highlights of equipment testing• Seasonal impacts• Types of heating• Future performance of CVR
2
![Page 3: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/3.jpg)
Seasonal CVR FactorsEPRI Green Circuits Field Trials
Winter 0.33Shoulder 0.67Summer 0.77
3
![Page 4: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/4.jpg)
Residential HVAC Testing
![Page 5: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/5.jpg)
EPRI HVAC Tests
Outdoor temp (F)
COP CVRf
82 3.2 0.61
95 3.0 0.41
115 2.0 0.27
![Page 6: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/6.jpg)
Coefficient of Performance
inputEnergy energy Cooling COP =
6
![Page 7: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/7.jpg)
COP versus Voltage
1
1.5
2
2.5
3
3.5
4
4.5
185 195 205 215 225 235 245 255
COP
Voltage (V)
82F95F115F
![Page 8: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/8.jpg)
0.9
0.95
1
1.05
1.1
180 200 220 240 260
Per-
unit
Aver
age
Ener
gy(C
OP
norm
alize
d at
240
V)
Voltage (240 V nominal)
82F95F115F
CVR =∆E/∆V
![Page 9: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/9.jpg)
Air Conditioner Impacts from Voltage Reduction
1. Improved air conditioner efficiency
![Page 10: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/10.jpg)
Air Conditioner Impacts from Voltage Reduction
1. Improved air conditioner efficiency
2. HVAC doesn’t need to work as hard
![Page 11: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/11.jpg)
![Page 12: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/12.jpg)
0.6
0.7
0.8
0.9
1
1.1
1.2
0.8 0.85 0.9 0.95 1 1.05 1.1
Re
lati
ve R
eal P
ow
er
(pu
)
Voltage (pu)
Relative Power Comparison for Residental Lights
Incandescent
CFL
LED
![Page 13: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/13.jpg)
Commercial Lighting
0.85
0.87
0.89
0.91
0.93
0.95
0.97
0.99
1.01
1.03
1.05
0.8 0.85 0.9 0.95 1 1.05 1.1
Rela
tive
Rea
l Pow
er (p
u)
Voltage (pu)
Comparison of Relative Real Power - T8, Metal Hallide,High Pressure Sodium
T8 Magnetic_MH Electronic_HPS
![Page 14: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/14.jpg)
Impact of Season
![Page 15: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/15.jpg)
Impact of Air Conditioner Age
![Page 16: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/16.jpg)
Impact of Heating Type
![Page 17: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/17.jpg)
Impact of Thermostatic Control of Heating
![Page 18: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/18.jpg)
Seasonal CVR FactorsField Trials
Winter Shoulder SummerNEEA feeder 0.66 0.72 0.74NEEA customer 0.51 0.58 0.78EPRI Green Circuits 0.33 0.67 0.77Hydro Quebec 0.20 0.67
18
![Page 19: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/19.jpg)
EPRI Green Circuit Field Trials
![Page 20: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/20.jpg)
Predictions of Residential CVR Factors
![Page 21: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/21.jpg)
21
![Page 22: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/22.jpg)
Extras22
![Page 23: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/23.jpg)
Summary of the Test Results -HVAC
HVAC – Cooling Mode
HVAC – Heating Mode
Outdoor Temp(F) Indoor Temp(F) CVR_Energy CVR_Demand Data Source47 70 0.59 0.667 New EPRI Testing
Outdoor Temp(F) Indoor Temp(F) CVR_Energy CVR_Demand Data Source82 70 0.61 0.57 New EPRI Testing95 70 0.401 0.4084 New EPRI Testing115 70 0.267 0.2185 New EPRI Testing85 80 0.26-0.73 0.6-0.42 Old EPRI Testing95 80 0.51-0.49 0.46-0.51 Old EPRI Testing115 80 0.34- -0.12 0.42-0.15 Old EPRI Testing95 80 0.272 0.475 PG&E95 80 0.56 0.6 SMUD
![Page 24: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/24.jpg)
Lighting
Appliance CVR_Energy CVR_Demand1-phase induction motor with fan load 0.747 0.7473-phase induction motors with constant torque load 0.886 0.8863-phase induction motors with drives 0.21 0.21
Motors and Drives
Appliance CVR_Energy CVR_DemandIncandescent bulb 1.505 1.505CFL bulbs 0.783 0.783LED bulbs -0.061 -0.061Tube lights -0.070 -0.070Commercial lights with magnetic ballasts 1.204 1.204Commercial lights with electronic ballasts -0.036 -0.036
![Page 25: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/25.jpg)
Appliance CVR_Energy CVR_DemandCRT TV 1.170 1.170LCD TV -0.055 -0.055LED TV -0.015 -0.015Desktop power supply -0.027 -0.027Cooking range Top -0.157 1.646Cooking range oven 0.071 2.178Clothes dryer 0.024 1.820New refrigerator 0.310 0.459Old refrigerator 1.073 0.746Washing machine 1.060 1.020Old Freezer 1.320 1.010Resistive water heater 0.114 1.770Microwave -0.230 1.354
![Page 26: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/26.jpg)
Summary of Lighting Test Results Type CVRfReal CVRfReactive Median
PF Data Source
Incandescent 1.51 1.00 New EPRI Testing Incandescent 1.51 1.00 PNNL CFL 0.76 1.10 0.52 New EPRI Testing CFL 0.81 0.00 0.82 PNNL LED -0.02 0.46 0.98 New EPRI Testing LED -0.11 -0.42 0.96 PNNL Tube Lights, electronic ballast -0.07 0.68 0.99 New EPRI Testing HPS and MH with magnetic ballasts
1.20 1.11 0.98 New EPRI Testing
HPS, electronic balllast -0.03 2.05 0.99 New EPRI Testing MH, electronic ballast -0.04 1.79 0.98 New EPRI Testing Mercury Vapor 0.04 Old EPRI Testing Sodium 0.64 Old EPRI Testing
![Page 27: Impacts of Voltage Reduction - IEEE Power & Energy Society](https://reader034.vdocuments.us/reader034/viewer/2022042417/625f65bc67ed9a7839083d78/html5/thumbnails/27.jpg)
Type Real Power CVR Factor
Reactive Power CVR
Factor
Median Power Factor at Rated
Voltage1-phase induction motor with fan load
0.747 2.0846 0.8
3-phase induction motors with constant torque load
0.8862 NA 0.78 – 0.88
Induction Motors
Type Real Power CVR Factor
Reactive Power CVR
Factor
Median Power Factor at
Rated Voltage
3-phase induction motors with drives 0.21 0.6263 0.56
Induction Motors with Drives (75% and 50% Loading)