ijars 707
DESCRIPTION
substation.123TRANSCRIPT
International Journal of Applied Research and Studies (iJARS)
ISSN: 2278-9480 Volume 3, Issue 1 (Jan - 2014)
www.ijars.in
Manuscript Id: iJARS/707 1
Review Paper
Power Flow Analysis of 110/11KV Substation Using ETAP
Authors:
1 Aswani R *, 2
Sakthivel R
Address For correspondence:
1 PG Scholar, Department of Electrical and Electronics Engineering V.S.B Engineering College, Karur 2 Asst. Professor, Department of Electrical and Electronics Engineering, V.S.B Engineering College,
Karur, India.
Abstract— Power flow analysis is the study of Real and
reactive power flow through the various buses and lines in
power system. In this paper power flow of a 110/11kV
Substation is analysed and during the analysis under voltage
and over voltage problems are found, These are reduced by
using capacitor bank at the suitable location .The analysis is
done by using an advanced software known as ETAP 12
version. The inputs given are based on the real time data
collected from a 110/11kV substation under K.S.E.B.
Keywords— Load flow Analysis, ETAP, Voltage
Intensification, Power factor improvement, Reactive Power
compensation
I. INTRODUCTION
In the study of power systems power flow study has the
significant importance. Power flow study deals with the study
of various quantities of the power systems such as real power,
reactive power, and magnitude of voltage and angle of voltage.
Load flow study is done on a power system to ensure that
generation supplies load and losses. From load flow study, we
can ensure that bus voltage should be near to the rated values
and the generation operates within real and reactive power
limits. We can insure that transmission lines and transformers
are not overloaded.
The objective of load flow analysis is in the planning stage
of new networks, adding and erection of a new network to the
existing substation. It gives the nodal voltages and phase
angles, power injection at all the buses and power flows
through interconnecting power channels. It is helpful in
determining the best location as well as optimal capacity of
proposed generating station, substation and new lines. It
determines the voltage of the buses and keeps within the
closed tolerances.
From the load flow analysis the location of maximum
voltage variation can be obtained. Due to load fluctuations
during peak load conditions under voltage problems also will
be present. But during some other load conditions over
voltage or over load conditions may occur. Many software are
available for load flow analysis of huge power system. On
these Electrical Transient Analyzer Program (ETAP) is very
effective.
II. POWER FLOW ANALYSIS USING NEWTON RAPHSON
METHOD
Power flow analysis is the study of power system under
steady state conditions subject to certain inequality constraints
under which the system operates. These constraints may be
load nodal voltages, reactive power generation of the
generators, the tap settings of a tap changing under load
transformer etc. The load flow solution gives the nodal
voltages and phase angles and hence the power injection at all
the buses and power flows through inter connecting power
channels. Load flow solution is essential for designing a new
power system and for planning extension of the existing one
for increased load demand. These analyses require the
calculation of numerous load flows under normal and
abnormal operating conditions.
Load flow solution gives the initial conditions of the system
when transient behaviour of the system to be studied. Load
flow solution can be done for balanced and unbalanced
conditions. The load flow solution of a system involves
mainly three steps.
[email protected] *Corresponding Author Email-Id
International Journal of Applied Research and Studies (iJARS)
ISSN: 2278-9480 Volume 3, Issue 1 (Jan - 2014)
www.ijars.in
Manuscript Id: iJARS/707 2
They are drawing of single line diagram of network,
Formulation of network equations and suitable mathematical
equations for the solution of the equations. The mathematical
techniques include Gauss-Siedel method, Newton raphson
method, advanced newton raphsons method and Fast
decoupled method etc. In this paper load flow problem is
solved by using Newton raphson method.
(1)
(2)
(3)
These three sets of equations are the load flow equations
which are non linear equations in terms of real and imaginary
components of nodal voltages. Here Pp,Qp for a load bus and
Pp ,Vp for a generator bus are specified and eP and fP are
unknown quantities .For n-bus systems ,the number of
unknown are 2(n-1) because the voltage at slack bus is known
and is kept fixed both in magnitude and phase angles. Newton
raphson method is an iterative method which approximates the
set of non linear simultaneous equations to a set of linear
simultaneous equations using Taylor’s series expansion and
the terms are limited to first approximation.Electrical
Transient Analyser program (ETAP) is one of the efficient
software used to analyse the very complex power systems .
The advantage of this method over other method makes it
suitable to our analysis. The number of iterations to be
performed by N-R method is less compared to G-S method.
Also the number of iteration is less dependent on size of the
system. The convergence characteristics of N-R method are
not affected by the selection of a slack bus. So inorder to solve
the problems of large systems like substations, it is very
advantageous to use this method.
II .STUDY SYSTEM
The system under study is one of the 110kV substations
under Kerala state electricity board. It consists of four power
transformers, Circuit breakers, Current transformers, potential
transformers, Lightning arresters ,Isolators, Many feeders etc. This substation is a step down as well as distribution
substation. There are four 110kV feeders. There are two
40MVA 110/66kV transformers .these transformers are
normally operated in parallel. Two 10 MVA transformer are
used to step down 66kV to 11kV.There are two numbers of
20MVAr shunt capacitor bank and are used to improve the
power factor. All 110kV circuit breakers are SF6 and motor
operated. All 66kV circuit breakers are SF6 type out of these
three are and pneumatically operated mechanism.
The sub transmission voltage 66kV line can serve as a
source to distribution substation. Distribution substation is
located near to the end user.
Fig.1 Single line diagram of substation
Distribution substation transformer changes the
transmission or sub transmission voltage to lower level for use
by end user. The distribution voltage is 11kV.
Both 110kV and 66Kv are single bus arrangement. There
are two incomer to 11kV switch gear panel; these are from
both 10 MVA transformer is not meant for parallel operation.
There is a bus coupler arrangement in 11kV panel. Normally
these two buses are working independently. Bus coupler can
close when other incomer is absent. There are six outgoing
feeders including one station auxiliary. The distance of 110kV
line is 40.93KM.
III.SIMULATION OF 110/11 kV SUBSTATION in
ETAP
The Fig 2 is the simulation diagram used to simulate the
above substation. The power grid will supply power to the
110kV Bus 1.Transformer 1 and 2 supply power to 66kV
buses. The transformers 3 and 4 will supply power to 11kV
buses. The six feeders are emanating from bus 7.
International Journal of Applied Research and Studies (iJARS)
ISSN: 2278-9480 Volume 3, Issue 1 (Jan - 2014)
www.ijars.in
Manuscript Id: iJARS/707 3
Fig 2.Simulated diagram of 110/11kV substation using ETAP
IV.LOAD FLOW ANALYSIS
Fig. 3 shows the Load Flow Analysis of the 110/11 kV substation carried out using ETAP in which Newton- Raphson
method [5],[6] is used and it is observed that at the Bus 7and
Bus 14 there is under voltage which can be clearly seen
from Fig.4 showing the sectional view of the feeders. At Bus
The above table shows the following details of under
voltage.
Fig 3.Load flow analysis of 110/11kV substation
Fig.4 Sectional view of feeders
From the sectional view it is clear that bus 7 and 14 are at under voltage. Only it operates with 89.3% of rated value.
The red indicates the abnormal condition in ETAP .Here it is
under voltage problem.
Table 1 shows the power flowing through the system; both
real and reactive power can be obtained from this study. The
power factor can be also obtainable from the analysis. From
this it is clear that power factor is very low in the range o.8 is
obtaining. The goal of a power flow study is to obtain
complete voltage angle and magnitude information for each
bus in a power system for specified load and generator real
power and voltage conditions
TABLE I
TABLE II
Description MW MVAR MVA % Power
factor
Swing Bus 7.709 5.445 9.438 81.68 lag
Total Demand 7.709 5.445 9.438 81.68 lag
Total Static Load 1.271 0.745 1.474 86.22 lag
Total Motor Load
6.371 3.735 7.385 86.27 lag
Apparent Losses 0.066 0.965 - -
Transformer T21 0.016 0.0731 - -
Transformer T23 0.016 0.0731 - -
Monitoring
Points
kV
MW
Mvar
%PF
BUS 2*
110
7.709
5.445
81.7
BUS 7
11
3.854
2.722
81.7
BUS 14
11
7.706
5.228
82.4
International Journal of Applied Research and Studies (iJARS)
ISSN: 2278-9480 Volume 3, Issue 1 (Jan - 2014)
www.ijars.in
Manuscript Id: iJARS/707 4
Device
Condition Rating Operating kV
Operating % ID
Not at Under
Bus 7 Voltage 11 kV 10.805 98.23
Not at Under
Bus 14 Voltage 11 kV 10.827 98.43
V. LOAD FLOW ANALYSIS WITH VOLTAGE
INTENSIFICATION
The simulation of 110/11kV substation is carried out in
Electrical Transient Analyzer Programme by placing the
capacitor bank at shunt with 11kV feeders .The rating of
capacitor bank is 9 Mvar. Fig 5 shows the load flow analysis
of this arrangement. Fig 6 shows the sectional view of this
arrangement.
Fig 5.Simulated diagram of 110/11kV substation
From the load flow analysis, it can be seen that the
operating voltage of bus 7 has improved from 89.3% to
98.35%.This is shown in fig 6.
Fig.6 Power flow analysis of 110/11kV substation
Fig.7 sectional view of 11kV feeders
Table III on comparing with table I, the voltage profile is
improved and also power factor, real power and reactive
power flows were improved.
TABLE III
Table IV shows demand and losses. These are also
improved due to the presence of shunt capacitor banks.
Therefore voltage profile is enhanced due to the placement of
capacitors at 11 kV side.
TABLE IV
VI.CONCLUSIONS
In this paper power flow study of 110/11kV substation using
ETAP is carried out to overcome the low power factor and
under voltage problem. Load flow study using ETAP software
is an excellent tool for system planning. A number of
operating procedures can be analysed such as the loss of
generator, a transmission line, a transformer or a load. Load
flow studies can be used to determine the optimum size and
Monitoring points
kV MW Mvar %PF
Bus 2 110 7.957 1.4 98.5
Bus 7 11 2.83 1.1 98.18
Bus 14 11 2.83 1.1 98.18
International Journal of Applied Research and Studies (iJARS)
ISSN: 2278-9480 Volume 3, Issue 1 (Jan - 2014)
www.ijars.in
Manuscript Id: iJARS/707 5
location of capacitors to surmount the problem of an under
voltage. Also, they are useful in determining the system
voltages under conditions of suddenly applied or disconnected
loads. Load flow studies determine if system voltages remain
within specified limits under various contingency conditions,
and whether equipment such as transformers and conductors
are overloaded. Load-flow studies are often used to
identify the need for additional generation, capacitive, or
inductive VAR support, or the placement of capacitors and/or
reactors to maintain system voltages within specified limits.
REFERENCES
[1] Rohit Kapahi, ”Load flow analysis of 132kV substation using
ETAP software”, International Journal of Scientific
&Engineering Research Volume 4,Issue 2,February 2013 ISSN
2229-5518.
[2] Pravin Chopade1 and Dr. Marwan Bikdash, “Minimizing Cost
and Power loss by Optimal Placement of Capacitor using
ETAP”, 978-1-4244-9593-1/11/ ©2011 IEEE 24.
[3] M.A.Pai, “Computer Techniques in Power System Analysis”,
second edition, ISBN: 0-07-059363-9, Tata McGraw Hill
[22005].
[4] R.O.Gorman and M.A.Redfern,”Voltage Control Problems on
Modern Distribution Systems” Proceedings of the IEEE Power
Engineering Society General Meeting IEEE Publication, ISBN
0-7803-X, Denver, Jul2004.
[5] M.P.Selvan and K.S. Swarup, “Distribution System Load Flow
using Object-Oriented Methodology”,2004 international
Conference
on Power system technology-POWERCON 2004, Singapore,
21-24 Nov.2004.
[6] J.Arrillaga and N.R.Watson “Computer Modelling of
Electrical Power Systems”, second edition, ISBN: 978-0-
471-87249-8, John Wiley and Sons June 2001.
[7] Charles Mozina “Undervoltage Load Shedding”, ISBN: 978-
1-4244-0855-9, IEEE, Page(s): 39-54.
[8] D.M. Tagare Reactive power management Mc-Graw Hill
2000.
[9] Rani and Vijaya, “Distribution system loss reduction by
capacitors”, Proceedings of National Conference on Emerging
Trends in Engineering (2000), Husur.
Distribution Feeders with Distorted Substation Voltages”, IEEE
Trans. on Power Delivery, Vol. 5, No. 2, April 1990, pp. 650-