ieee.c2.1997_2 163

2
 235El PART 2. SAFETY RULES FOR OVERHEAD LINES 235El m Table 235-6 Clearance in Any Direction From Line Conductors to Supports and to Vertical or Lateral Conductors, Span, or Guy Wires Attached to the Same Support (See also Rule 235El and 235E3b(2).) Supply lines Communication lines Circuit phase-to-phase voltage On jointly used Over 8.7 Over 50 Clearance of line In general structures Ot08.7kV to 50 kV to 814 kV 4.9 conductors from (mm) (mm) (mm) (mm) mm) 1. Vertical and lateral conductors: a. Of the same circuit 75 75 75 75 plus 6.5 per kV no value specified over 8.7 kV b. Of other circuits l2 75 75 150 5 150 plus 10 per kV 580 plus 10 per kV over 8.7 kV over 50 kV 2. Span or guy wires, lIar messengers attached to same structure: a. When parallel to line 75 7 1501,7 300 1 300 plus 10 per kV 740 plus 10 per kV over 8.7 kV over 50 kV Anchor guys 75 7 150 I 7 150 I 150 plus 6.5 per kV 410 plu s 6.5 per kV over 8.7 kV over 50 kV c. All other 75 7 1501,7 150 150 plus 10 per kV 580 plus 10 per kV over 8.7 kV over 50 kV 3. Surface of support arms 75 2 75 2 75 6 ,8 75 plus 5 per kV 280 plus 5 per kV over 8.7 kV 6,8.10 over 50 kV 4. Surface of structures: a. On jointly used structures 125 2 12 5 3 ,6.8 125 plus 5 per kV 330 plus 5 per kV b. All other 75 2 1 For guy wires, if practical. For clearances between span wires and communication conductors, see Rule 238C. On jointly used structures, guys that pass within 300 mm of sup ply conductors, and also pass within 300 mm o f communication cables, shall be protected with a suitable insulating covering where the guy passes the supply conductors, unless the guy is ef fectively grounded or insulated with a strain insulator at a point below the lowest supply conductor and above the highest commu nication cable. The clearance from an insulated or effectively grounded guy to a communication cable may be reduced to 75 mm when abrasion protection is provided on the guy or communication cable. 2 Communication conductors may be attached to supports on the sides or bottom of cross arms or surfaces of poles with less clearance. 3 This clearance applies only to supply conductors at the sup port below communication conductors, on jointly used structur es. Where supply conductors are above communication conduc tors, this clearance may be reduced to 75 mm. 4 All clearances for line over 50 kV shall be based on the maximum operating voltage. For voltages exceeding 814 kV, the clearance shall be determined by the alternate method given by Rule 235E3. 5 For supply circuits of 0 to 750 V, this clearance may be re duced to 75 rnm. - 125 over 8.7 kV 6,8,10 over 50 kV 75 6 8 75 plus 5 per kV 280 plus 5 per kV over 8.7 kV 6 8,10 over 50 kV 6 A neutral conductor meeting Rule 230El may be attached di rectly to the structure surface. 7 Guys and messengers may be attached to the same strain plates or to the same through bolts. 8 For open supply circuits of 0 to 750 V and supply cables of all voltages meeting Rule 23OCl, 2 or 3, this clearance may be re duced to 25 mm. No clearance is specified for phase conductors of such cables where they are physically restrained by a suitable bracket from abrasion against the pole. 9 The additional clearance for voltages in excess of 50 kV spec ified in Table 235-6 shall be increased 3 for each 300 m in ex cess of 1000 m above mean sea level. 1 Where the circuit is effectively ground ed and the neutral con ductor meets Rule 230El, phase-to-neutral voltage shall be used to determine the clearance from the surface of support arms and structures. 11 These clearances may be reduced by not more than 2 5 to a guy insulator, provided that full clearance is maintained to its me tallic end fittings and the guy wires. The clearance to an insulated section of a guy between two insulators may be reduced by not more than 25 provided that full clearance is maintained to the uninsulated portion of the guy. 12 Phase-to-phase voltages shall be determined according to Rule 235A3.

Upload: sj-comp-uta

Post on 06-Oct-2015

3 views

Category:

Documents


0 download

DESCRIPTION

a

TRANSCRIPT

  • 235El PART 2. SAFETY RULES FOR OVERHEAD LINES 235El

    m

    Table 235-6 Clearance in Any Direction From Line Conductors to Supports and to

    Vertical or Lateral Conductors, Span, or Guy Wires Attached to the Same Support (See also Rule 235El and 235E3b(2).)

    Supply lines Communication lines

    Circuit phase-to-phase voltage

    On jointly used Over 8.7 Over 50

    Clearance of line In general structures Ot08.7kV to 50 kV to 814 kV 4.9 conductors from (mm) (mm) (mm) (mm) (mm)

    1. Vertical and lateral conductors: a. Of the same circuit 75 75 75 75 plus 6.5 per kV no value specified

    over 8.7 kV

    b. Of other circuits l2 75 75 150 5 150 plus 10 per kV 580 plus 10 per kV over 8.7 kV over 50 kV

    2. Span or guy wires, lIar messengers attached to same structure: a. When parallel to line 75 7 1501,7 300 1 300 plus 10 per kV 740 plus 10 per kV

    over 8.7 kV over 50 kV

    b. Anchor guys 75 7 150 I. 7 150 I 150 plus 6.5 per kV 410 plus 6.5 per kV over 8.7 kV over 50 kV

    c. All other 75 7 1501,7 150 150 plus 10 per kV 580 plus 10 per kV over 8.7 kV over 50 kV

    3. Surface of support arms 75 2 75 2 75 6,8 75 plus 5 per kV 280 plus 5 per kV over 8.7 kV 6,8.10 over 50 kV

    4. Surface of structures: a. On jointly used structures - 125 2 125 3,6.8 125 plus 5 per kV 330 plus 5 per kV

    b. All other 75 2

    1 For guy wires, if practical. For clearances between span wires and communication conductors, see Rule 238C.

    On jointly used structures, guys that pass within 300 mm of sup-ply conductors, and also pass within 300 mm of communication cables, shall be protected with a suitable insulating covering where the guy passes the supply conductors, unless the guy is ef-fectively grounded or insulated with a strain insulator at a point below the lowest supply conductor and above the highest commu-nication cable.

    The clearance from an insulated or effectively grounded guy to a communication cable may be reduced to 75 mm when abrasion protection is provided on the guy or communication cable.

    2 Communication conductors may be attached to supports on the sides or bottom of cross arms or surfaces of poles with less clearance.

    3 This clearance applies only to supply conductors at the sup-port below communication conductors, on jointly used structures.

    Where supply conductors are above communication conduc-tors, this clearance may be reduced to 75 mm.

    4 All clearances for line over 50 kV shall be based on the maximum operating voltage. For voltages exceeding 814 kV, the clearance shall be determined by the alternate method given by Rule 235E3.

    5 For supply circuits of 0 to 750 V, this clearance may be re-duced to 75 rnm.

    -

    125

    over 8.7 kV 6,8,10 over 50 kV

    75 6 8 75 plus 5 per kV 280 plus 5 per kV over 8.7 kV 6, 8,10 over 50 kV

    6 A neutral conductor meeting Rule 230El may be attached di-rectly to the structure surface.

    7 Guys and messengers may be attached to the same strain plates or to the same through bolts.

    8 For open supply circuits of 0 to 750 V and supply cables of all voltages meeting Rule 23OCl, 2 or 3, this clearance may be re-duced to 25 mm. No clearance is specified for phase conductors of such cables where they are physically restrained by a suitable bracket from abrasion against the pole.

    9 The additional clearance for voltages in excess of 50 kV spec-ified in Table 235-6 shall be increased 3% for each 300 m in ex-cess of 1000 m above mean sea level.

    10 Where the circuit is effectively grounded and the neutral con-ductor meets Rule 230El, phase-to-neutral voltage shall be used to determine the clearance from the surface of support arms and structures.

    11 These clearances may be reduced by not more than 25% to a guy insulator, provided that full clearance is maintained to its me-tallic end fittings and the guy wires. The clearance to an insulated section of a guy between two insulators may be reduced by not more than 25% provided that full clearance is maintained to the uninsulated portion of the guy.

    12 Phase-to-phase voltages shall be determined according to Rule 235A3.