[ieee 2012 ieee power electronics and machines in wind applications (pemwa) - denver, co, usa...
TRANSCRIPT
Modeling and control of a pitch-controlledvariable-speed wind turbine driven by a DFIG with
frequency control support in PSS/E
Mikel de Prada Gil∗ Andreas Sumper ∗†‡ Oriol Gomis-Bellmunt∗†‡[email protected] [email protected] [email protected]
∗IREC Catalonia Institute for Energy Research, Jardins de les Dones de Negre 1, 2a.
08930 Sant Adria de Besos, Barcelona (Spain)†Centre d’Innovacio Tecnologica en Convertidors Estatics i Accionaments (CITCEA-UPC),
Departament d’Enginyeria Electrica, Universitat Politecnica de Catalunya EU d’Enginyeria Tecnica Industrial de Barcelona,
C. Comte d’Urgell, 187, Pl. 1. 08036 Barcelona, Spain†Centre d’Innovacio Tecnologica en Convertidors Estatics i Accionaments (CITCEA-UPC),
Departament d’Enginyeria Electrica, Universitat Politecnica de Catalunya ETS d’Enginyeria Industrial de Barcelona,
Av. Diagonal, 647, Pl. 2. 08028 Barcelona, Spain
Abstract—In recent years, due to the rising penetration of windenergy conversion systems (WECS) into the electricity networks,increasingly comprehensive studies and accurate dynamic modelsare required to analyze its behavior under grid faults. A completemodel of a pitch-controlled variable-speed wind turbine driven bya doubly fed induction generator (DFIG) and its control schemeare implemented. All encompassed subsystems, such as windturbine, pitch actuator, two-mass drive train model, DFIG model,converters and protections are modeled in FORTRAN usingthe power system simulation software PSS/E. A cascade controlstructure is used where the outer control loop concerns the speedcontrol and the inner control loop is responsible for the electricalcontrol. Additionally, a frequency control support is developed inorder to accomplish with the Grid Codes requirements enhancingthe grid power quality. The model performance under varioussystem disturbances is tested by means of simulations.
I. INTRODUCTION
W IND energy has become one of the most important
and promising sources of renewable energy all over
the world, mainly due to its contribution for a low-carbon
society and its economical viability. The increasing size of
the turbines and the rising penetration of the wind energy
conversion systems (WECS) into the grid have encouraged the
use of power electronic converters [1], in order to address the
potential concerns of transmission systems operators (TSO) in
terms of power quality [2] and fault ride-through capability [3].
Detailed models of wind turbines and their associated controls
and protections are required for grid integration studies both
for analysis of the wind turbine under grid faults [4] and for
power system stability studies [5].
Many comprehensive studies have been carried out regard-
ing modeling and control of a DFIG-based wind turbine,
and several models have been developed by researchers using
different softwares, such as MATLAB-Simulink [3], [6], [19],
PSCAD [7], [8] or DigSilent [9].
In this paper, an accurate user-model consisting of a pitch-
controlled variable-speed wind turbine driven by a doubly fed
induction generator (DFIG) and modeled in FORTRAN using
PSS/E is presented. A frequency support controller is also
implemented with the aim of accomplish with the Danish Grid
Code requirement [10].
II. MODELING
A schematic diagram of the overall WECS is illustrated in
Figure 1. It consists of four main functional blocks, namely
the aerodynamic (wind turbine model), mechanical (drive train
model), electrical (DFIG and power converter model), and
pitch servo subsystems. All these blocks and its controls
are written in FORTRAN using the power system simulation
software PSS/E.
Wind Wind Turbine Model
Drive Train Model
Doubly Fed InductionGenerator
Model
Grid
Converter and control ModelPitch angle
controller
- Speed Control- Electrical Control- Frequency Control
Windspeed
Pitch angle
Low speed shaft velocity
Low speed shaft torque
High speed shaft
torque High speedshaft
velocity
Voltageand
frequency
Voltageand
frequency
Active and reactive power
Torque and reactive power set points
Rotorvoltages
Fig. 1. General structure of the pitch-controlled variable-speed wind turbinedriven by a DFIG model.
A. Wind Turbine Model
The power generated by a wind turbine, Pwti, comes from
the kinetic energy of the wind and depends on the power
coefficient, CP , according to the following expression
978-1-4673-1130-4/12/$31.00 ©2012 IEEE
Pwti = CPPwind =1
2CP ρAv3w (1)
where Pwind is the air stream kinetic power, ρ is the air
density, A = πR2 is the surface covered by the wind wheel of
radius R and vw is the average wind speed at the hub height.
This CP power coefficient is unique for each turbine and can
be written as [11] [12]:
CP (λ, θpitch) = c1
(c2
1
Λ− c3θpitch − c4θ
c5pitch − c6
)e−c7
1Λ
(2)
where θpitch is the pitch angle, and λ is the so-called tip speed
ratio defined as:
λ =ωtR
vw(3)
and
1
Λ=
1
λ+ c8θpitch− c9
1 + θ3pitch(4)
where [c1 . . . c9] are characteristic constants for each wind
turbine and ωt is the low speed shaft angular velocity.
B. Drive Train Model
The drive train of a WECS transfers the aerodynamic torque
on the blades to the generator shaft. It encompasses the rotor,
the low- and high-speed shafts and the gearbox. In this paper, a
two-mass representation of the drive train is used. This model
is described by the following equations [13]:
2HMdωM
dt = TM −KSθS −DMωM
2HGdωG
dt = KSθS − TE −DGωG
dθSdt = ω0(ωM − ωG)
(5)
where θS is the torsional twist, KS is the shaft stiffness,
H is the inertia constant, T is the torque, D is the damping
coefficient, ω is the rotational speed and ω0 denotes the electric
system speed. The subscripts G and M and E stand for wind
turbine rotor, generator mechanical and generator electrical,
respectively.
C. Pitch System Model
As it is shown in Figure 2, the pitch system model is
divided into two blocks: the pitch controller and the pitch angle
actuator. The former determines the pitch angle reference,
βref , from the difference between the measured and the
desired rotor speed and is explained in Section III-B. The
latter consists of an actuator that rotates all the blades to a
certain pitch angle, β, equal to the desired one.
The pitch actuator is a nonlinear servo that can be modeled
in closed loop as a first-order dynamic system with saturation
in the amplitude and derivative of the output signal [14]. Figure
3 shows a block diagram of the first-order actuator model. The
�ref���
Fig. 2. Basic configuration of the pitch system model.
dynamic behaviour of the pitch actuator operating in its linear
region is described by the following differential equation
β = − 1
τpitchβ +
1
τpitchβref (6)
where τpitch is the time constant. Typically, β ranges from
−2◦ to 30◦ and varies at a maximum rate of ±10◦/s [14].
ref� �1
actuator s�
�
�
+ -
Fig. 3. Model of the pitch angle actuator.
D. DFIG Model
The DFIG dq equivalent circuit, shown in Figure 4, is
obtained from the following machine voltage equations [15]:
vsd = Rsisd − ωdλsq + Llsddt isd + Lm
ddt (isd + ird)
vsq = Rsisq + ωdλsd + Llsddt isq + Lm
ddt (isq + irq)
(7)
vrd = Rrird − ωdAλrq + Llrddt ird + Lm
ddt (isd + ird)
vrq = Rrirq + ωdAλrd + Llrddt irq + Lm
ddt (isq + irq)
(8)
where Lls and Llr are the stator and rotor leakage induc-
tances, Lm is the mutual inductance between stator and rotor
windings, Rs and Rr are the stator and rotor resistance and ωd
and ωdA are the dq-axis relative rotational speed with respect
to the stator and rotor, respectively. In this paper, a dq reference
frame rotating at synchronous speed, ωs, is used and, therefore,
ωd = ωs and ωdA = ωs −ωm = ωslip, being ωs the electrical
angular speed at the stator of the machine.
DC
DC
DC
DC
(a) d-axis
(b) q-axis
+
-
-
-
-
+
+
+
+
+
+
- -
- -
+
sR
sR rR
rRlsL
lsL lrL
lrL
sqdtd � rqdt
d �
rddtd �sddt
d � mL
mL rqvsqv
sdv rdv
sqd��
sdd��
sdi
rqi
rdi
sqi
rddA��
rqdA��
Fig. 4. DFIG dq-axis equivalent circuit.
The electromagnetic torque and the stator reactive power,
which are the variables to be controlled by the rotor side
converter, can be expressed as [15]:
Γm =3
2pLm(isqird − isdirq) (9)
Qs =3
2(vsqisd − vsdisq) (10)
where p is the number of pole pairs.
E. Converter Model
The converter model consists of an IGBT voltage source
back-to-back power converter used as an interface between the
AC grid and the rotor windings. As it can be seen in Figure 5,
it is composed by two independent converters connected to a
common DC-bus. In order to consider that the applied voltages
by the converter fit in with the voltages set points (v∗rsc ≈ vrscand v∗gsc ≈ vgsc), it is assumed that the switching frequency
of the SVPWM is high (usually over 1 kHz) and the high-
frequency components of the voltage signals generated by the
inverters are filtered by the low pass nature of the machine and
the grid-side circuit [16]. In addition, the electronic switching
are considered to be ideal and without losses.
The DC-bus voltage, E, is calculated from an active power
balance in the back-to-back converter (see Figure 5). Thus,
in the case that the dc-chopper is switch on, the equation is
described as
Pgsc − Prsc = PDC + PChopper (11)
being
Pgsc =32 (vgscdild + vgscqilq)
Prsc =32 (vrscdird + vrscqirq)
PDC = 12C
ddtE
2
Pchopper = E2
Rchopper
(12)
���� ����
����� ���
��� ���
Fig. 5. Active power balance in the back-to-back converter.
The voltage equation of the grid side electrical circuit, given
by the space vector form, can be written as
vaz − vagsc = rgscial + Lgsc
d
dtial (13)
where vaz and vagsc are the voltage space vectors of the grid
and the AC side of the converter, respectively,ial is the current
space vector and rgsc and Lgsc are the resistance and the
inductance of the circuit. The superscript “a” indicates that
the space vectors are expressed as complex numbers with the
stator a-axis chosen as the reference axis with an angle of 0◦.
III. CONTROL SCHEME
The main control objectives in a WECS are to improve
efficiency and quality of power conversion, ensuring that the
turbine is kept within its safe operating region. These goals
are usually represented as the so-called ideal power curve
shown in Figure 6. It can be noted two different regions
with distinctive generation objectives. In partial load region
(I), which corresponds to wind speeds lower than the rated
speed, the aim is to maximize the energy capture from the
wind. Otherwise, at hight wind speeds (region II or full load
operation mode), the control goal is to limit the generated
power below its rated value to avoid overloading.
]/[ smvw
NP
][KW
Power
NVCut-in Cut-out
Partial load operation Full load operation
Fig. 6. Ideal power curve of a typical wind turbine.
To achieve these objectives, the control system is divided
into two levels (see Figure 7): a high-level control or speed
control and a low level control or electrical control. The
former gives the proper torque (Γ∗m), square dc voltage ((E2)∗)
and reactive powers (Q∗s and Q∗
z) set points to the converter
as function of the wind speed, the low speed shaft angular
velocity and the grid voltage. The latter, regulates the incoming
reference signals computing the appropriates voltage set points
to the back-to-back power converter.
Apart from this control system, if the machine is operating
in the full load region, pitch control is activated in order to
keep the extracting power at its nominal value.
DFIG
Gearbox
wv GRID
pitch�
RSC controller GSC controller
High-level controlwv
*sQ
*zQ2 *( )E*
m
t�
*rscv
*gscv
zv
Fig. 7. Control design of the system.
A. Speed Control
Depending on the region where the wind turbine is operat-
ing, two different control strategies are used. In the partial
load region, the main goal is to extract all the available
power from the wind. In this paper, a Maximum Power Point
Tracking (MPPT) strategy with only a rotation speed sensor
required, is used. The advantage of this method is to avoid
the measurement of the wind speed and, consequently, its
stochastic nature.
According to [16], the maximum CP and, therefore, the
maximum power generation for a single wind turbine, is
guaranteed to match the generator electrical torque with
KCP optω2t .
where KCP optis a constant parameter that depends on the
geometry of the turbine and is expressed as follows
KCP opt=
1
2
(c1c2c7
)e−
c6c7c2
−1ρAR3
( c2c7c2c9c7+c6c7+c2
)3(14)
The control strategy changes in the full load region. In this
case, the torque reference signal (Γ∗m) is fixed whereas the
pitch control is activated to limit the captured power to its
nominal value.
B. Pitch Control
The pitch controller is sketched in Figure 8. It consists
in regulating the rotational wind turbine speed by means
of a Gain Scheduling function block (GAINS) and a PI-
controller, resulting a pitch angle reference (βref ) to the pitch
actuator described above in Section II-C. Gain Scheduling is a
technique commonly used in the control of nonlinear systems
[14], [17]. In the case of Figure 8, the gain scheduled controller
is implemented as a PI control and a gain depending on the
pitch angle [14].
PIGAINS+ -
*t�
t�
ref�
Fig. 8. Pitch controller design.
To evaluate the effectiveness of the pitch control method,
Figures 9 and 10 are shown. In Figure 9, the rotational wind
turbine speed step response to a sudden increase in wind speed
from 12 to 15m/s is simulated. It can be observed as the turbine
speed increases due to the sudden change in wind speed, and
then it is regulated by the pitch control system, returning to its
rated value. In Figure 10, the pitch angle actuator behavior is
presented. As it can be noted, the pitch angle reference (βref ,
green) changes at 20 seconds due to the pitch control and
the pitch angle (β, blue) follows it according to a first-order
system with saturation in the amplitude and rate of change,
as it is modeled. The pink line represents the pitch angle βexpressed in degrees.
C. Electrical Control
The electrical control or low level control is divided into
two subsystems: the rotor side converter (RSC) control and the
grid side converter (GSC) control . Both inner control loops
are assumed to be ideal since the WT electric system time
Fig. 9. Wind turbine speed response (green) when the wind speed is increasedin one step from 12 to 15m/s at 20 seconds. Values are in SI untis.
Fig. 10. Pitch angle actuator response. Pitch angle reference, βref (green),pitch angle in radians, β (blue) and pitch angle in degrees (pink).
responses are much faster than the outer speed control loop
or high level control [16]. Thus, it is possible to dissociate
both control loops and to define a cascade control structure
where the inner control loop concerns the back-to-back power
converter and the outer control loop concerns the speed
control.
Besides the RSC and GSC controls, the dc-chopper is
implemented in order to dissipate the excess of energy that
cannot be evacuated to the grid during a fault. The system
control also includes the voltage and currents limits according
to the capacity of the generator and the rating of the converters.
1) Rotor Side Converter Control: The RSC objective con-
trol is to regulate both the generator torque and the stator
reactive power. In order to do so, a vector control approach
is deployed. A synchronously rotating dq-axis frame with the
q-axis oriented along the stator flux vector position is chosen
(λsd = 0). This enables a decoupled control of the torque and
the stator reactive power, which can be expressed as a function
of the direct and quadrature components of the rotor current
references, respectively, as follows [3]
i∗rd =2LsΓ
∗m
3pLmλsq(15)
i∗rq ≈ λsq +2Q∗
sLs
3vsd
Lm(16)
The rotor current control is implemented by the following
state linearization feedback [3]:
vrscd = vrscd − ωdAλrq
vrscq = vrscq + ωdAλrd(17)
where the vrscd and vrscq are the output voltages of the dq-
axis rotor currents controller. Thus, replacing the equation 17
in 8 and neglecting the stator current transients, the following
decoupled system is obtained
idqr (s) =
[ 1Rr+Lrs
0
0 1Rr+Lrs
]︸ ︷︷ ︸
G(s)
vdqrsc(s) (18)
The PI controllers are designed according to the Direct
Synthesis methodology detailed in [18], with the desired close
loop transfer function, M(s), and the plant, G(s), as
M(s) = ird(s)i∗rd(s)
=irq(s)i∗rq(s)
= 1δs+1
G(s) = Kτs+1 =
1Rr
sLrRr
+1
(19)
being
Kp =τ
Kδ=
Lr
δy Ki =
1
Kδ=
Rr
δ(20)
To sum up, the generator torque control loop and the stator
reactive power control loop are shown in Figures 11 and 12,
respectively.
PIsqm
msrd pL
Li�3
2 **
rqmsqssq iLiL ��
*m *
rdi ��
rdi
� �
_ ( )·( )rscd comp d m m sq r rqV L i L i� � � � �sqirqi
^
rscdV
_rscd compV
SVPWM*rscdV
sq�sqirqi
RSC
Fig. 11. Block diagram of the generator torque control loop.
PI
*sQ
sq�
*rqi
��
rqi
� �
_ ( )·( )rscq comp d m m sd r rdV L i L i� � � �sdirdi
_rscq compV
rscqV
SVPWM*rscqV
rqmsqssq iLiL ��sqi
rqim
sd
sssq
rq LVLQ
i 32 *
*�
�
sdV*rqi
RSC
Fig. 12. Block diagram of the stator reactive power control loop.
2) Grid Side Converter Control: The objectives of the GSC
are to keep the DC-link voltage constant and to control the
grid side reactive power, by means of regulating the dq-axis
currents (idql ) and appying the proper voltages to the grid side.
Using a vector control approach, with a synchronously rotating
dq-axis frame and aligning the d-axis of the reference frame
along the stator-voltage vector position (vsq = vzd = 0),
enables a decoupled control between the DC-voltage and the
reactive power.
In the case of the reactive power control loop, the current
reference is directly computed as
i∗lq = − 2Q∗z
3vzd(21)
However, the calculation of the d-axis grid side current
reference (i∗ld) becomes more complex and some assumptions
need to be considered [19]. A cascade control structure is
implemented, where the outer control loop is responsible for
regulating the square dc voltage and the inner control loop
consist in controling the grid side currents (see Figure 13). It
is considered that the current response is much faster than the
dynamics of the outer loop due to the slow response of the
capacitors. Furthermore, the dc-chopper is not considered in
the control design.
As in the RSC case, PI parameters are tuning according to
the Direct Synthesis methodology, with M(s) equals to a first
order transfer function and
G(s) =E2
P ∗DC
=2
c · s (22)
Thus, as can be seen in the equation 23, a proportional
controller (P) is only needed for tuning the controller R(s)
R(s) =M(s)
G(s)(1−M(s))=
1δs+1
Ks (1− 1
δs+1 )=
1
Kδ(23)
being
Kp =1
Kδ=
C
2δ(24)
Aligning the d-axis of the reference frame along the stator-
voltage position, the d-axis grid side current reference (i∗ld)
can be written as
i∗ld =2P ∗
gsc
3vzd(25)
A similar analysis for the control of the dq-axis rotor
currents can likewise be done for the control of the dq-axis
grid side currents. Therefore, the following state feedback is
used to linearize the current dynamics.
vgscd = − ˆvgscd + vzd + ωdLgscilq
vgscq = − ˆvgscq − ωdLgscild
(26)
where the vgscd and vgscq are the output voltages of the
dq-axis grid side currents controller. The decoupling leads to
idql (s) =
[1
rgsc+Lgscs0
0 1rgsc+Lgscs
]︸ ︷︷ ︸
G(s)
vdqgsc(s) (27)
Finally, using the Direct Synthesis methodology, the result-
ing PI parameters are computed as
Kp =τ
Kδ=
Lgsc
δy Ki =
1
Kδ=
rgscδ
(28)
Analogously to the RSC case, both the square dc voltage
and the grid side reactive power control loops are shown in
Figures 13 and 14, respectively.
_gscd compV
SVPWM*gscdV
_gscd comp zd d gsc lqV V L i� �zdVlqi
ldi
*ldi
** 2
3gsc
ldzd
Pi
V PI�
��
PI��
� �
GSC
2E
2*)(E
rscP
*DCP
*gscP
^
gscdV �
Fig. 13. Block diagram of the square dc voltage control loop.
PI*lqi �
�
lqi
�
ldi
_gscq compV
gscqV
SVPWM*gscqV*
zQ
zdV
** 2
3z
lqzd
QiV
�
_gscq comp d gsc ldV L i� �
�
GSC
Fig. 14. Block diagram of the grid side reactive power control loop.
IV. FREQUENCY CONTROL
Due to increased wind penetration into the grid, a potential
concern of transmission system operators is the capability of
wind farms to provide dynamic frequency support if a sudden
event occurs and the grid frequency deviates from its nominal
value.
Hence, in recent years, the various national Grid Codes have
imposed some frequency and active power requirements on
wind farms. In this paper, a frequency control is proposed
according to the Danish Grid Code [10]. In Figure 15, this
frequency and active power requirements are shown. Between
49.9 and 50.1Hz (deadband), no special requirement is needed
since frequency is in the acceptable operating range to ensure
power quality. From 50.1 to 51Hz the active power output
of individual wind generators should be limited according
to a slope, Kfrec, depending on whether the wind turbine
operates at full (black line) or partial (blue line) capacity of
its available power from the wind. Finally, if the frequency
drops below 49.9Hz, due to either a loss of generation or a
increased demand, the wind generators should provide more
power output. However, this is only possible if the wind
turbine fix its set point power below its maximum and a
percentage of reserve power is available (blue line).
5150,1
50
0
100
49,9
80
Frequency [Hz]
% Activepower Deadband
Fig. 15. Frequency and active power requeriments according to the DanishGrid Code.
Previous research work has investigated different method-
ologies for contributing to frequency support of DFIG-based
wind farms [20]–[22]. In this paper, the proposed frequency
support controller consists of an additional control loop that
adapts the torque set point, calculated previously in Section
III-A, as a function of the grid frequency deviation, Δf (see
Figure 16).
+ -
*_ totalm Converter
control
*m
+ - freqKf�
gridf
reff P�
�
t�
t�
*m
t�
Fig. 16. Block diagram of the frequency support controller.
Thus, a proportional controller is activated when the grid
frequency exceeds certain limits (deadband). The proportional
gain constant, Kfreq , is given by the following equation
Kfreq = −ΔP/Mbase
Δf/fbase(29)
where fbase is nominal frequency of the system (50Hz) and
Mbase is the nominal apparent power of the machine (3MVA).
V. SIMULATION RESULTS
With the aim to evaluate the behavior of the system under
grid faults conditions, some simulations are carried out using
PSS/E. To that purpose, the equivalent grid shown in Figure
17 and provided by Asociacion Empresarial Eolica (AEE)
is chosen [23]. The parameters of the lines, transformers,
generators and loads, shown in Figure 17, are expressed in per
unit with Sbase equal to 100MVA. The 3MW wind generator
used for this study is connected to the 0.69kV busbar (501).
20 kV
TR22500MVA
X= 0.004 pu
PCC
GS2
R=0.003 puX=0.03 puG
S1
TR32000MVA
X=0.006 pu
R=0.001 puX=0.01 pu
P=1700 MWQ=500 MVAr
PV GenP=1.600 MWV=1.035 p.u.
B=0.4 pu B=0.133 pu
1 101 201
301 401
G3 MW
TR13.5MVA
X=0.06 pu501
0.69 kVSlack Gen
V=1.035 p.u.
Fig. 17. Equivalent electrical grid provided by Asociacion Empresarial Eolica(AEE) [23].
A. Fault ride-through
In order to evaluate the fault ride-through capability of the
model and check the overall system behavior, a symmetrical
three-phase voltage sag is introduced at PCC (bus 201).
The simulation results are compared with the requirements
established by the operation procedure P.O.12.3 developed by
REE (Red Electrica de Espana) [24]. This procedure is one of
the standards for grid connection in Spain and is addressed
to answer requirements for voltage dips in electrical wind
installations. The characteristic parameters of the simulation
are shown in table I.
TABLE ICHARACTERISTIC PARAMETERS OF THE SIMULATION
Parameter Value UnitVbase 690 VSbase 100 MVADepth of the voltage sag 0.105 puInstant when it appears 40 sDuration dip 550 msShort-circuit impedance 0.02 ΩWind speed 12 m/sQ∗
s 0 kVArQ∗
z 0 kVAr
As can be seen from Figures 18 and 19, the wind turbine
remains connected to the grid during the fault according to
the requirements specified in the P.O.12.3 [24]. In addition,
the active power generated and the electromagnetic torque
drops rapidly down to zero during the fault and recovers
its nominal values once the fault is cleared. The settling
time of both signals are 30ms. This reduction implies the
wind turbine speed increase as is shown in Figure 19. Once
the electromagnetic torque returns to its nominal value, the
machine begins to decrease its angular speed until it reaches
the rated one, according to equation 5 described in the drive
train model. Finally, the reactive power exchanged with the
grid at bus 501 (sum of Q∗s and Q∗
z) is zero before and after
the voltage dip, as expected.
B. Frequency response
In the last case of study, simulations are done to show the
ability of wind turbines to support primary frequency control.
In Figure 20, the wind turbine step response is analyzed when
Fig. 18. RMS terminal voltage (pink), active power (green) and reactivepower (blue) during a three-phase fault in the PCC. Values are in per unit.
Fig. 19. Wind turbine speed (green) and electromagnetic torque (blue) duringa three-phase fault in the PCC. Values are in SI units.
the grid frequency is increased from 50 to 50.55Hz as a result
of a sudden load decrement in the system. As is explained
in Section IV, the Danish Grid Code is used as a reference,
in order to compare the established requirements with the
obtained machine response.
As can be observed in Table II, when the frequency of the
system is stepped-up from 50 to 50.55Hz, the active power
generated should be halved.
It can be noticed in Figure 20 the proper response of the
wind turbine to the frequency increase, being reduced the
100% of its active power generated (which corresponds to
1,34 MW for a 9m/s wind speed) to only the 50% of its power
TABLE IICHARACTERISTIC PARAMETERS OF THE SIMULATION
Parameter Value UnitInitial frequency 50 HzFinal frequency 50.55 HzInitial active power capacity 100 %Desired final percentage of active power 50 %Wind speed 9 m/s
output capacity (670kW).
Fig. 20. Power output response (green) when the frequency is increased inone step from 50 to 50.55Hz (blue). Wind speed at 9m/s.
VI. CONCLUSION
A complete user-model consisting of a pitch regulated
variable speed wind turbine driven by a DFIG is presented.
The implemented control scheme is based on two levels: a
high control level or speed control and a low control level or
electrical control. A vector control approach is used to regulate
both rotor and grid side converters. The operating voltages
and current limits are considered, as well as the inclusion
of dc-chopper protection under fault ride through situations.
The performance of the overall system is evaluated under grid
faults by means of simulations carried out using PSS/E. In
order to improve the grid stability, a frequency control support
is implemented and analyzed. Satisfactory results are obtained
accomplishing with the Grid Codes requirements.
ACKNOWLEDGMENT
This work was supported by the Ministerio de Ciencia e
Innovacion under the project ENE2009-08555.
REFERENCES
[1] E. Pouresmaeil, D. Montesinos-Miracle, and O. Gomis-Bellmunt. Con-trol scheme of three-level h-bridge converter for interfacing betweenrenewable energy resources and ac grid. In Power Electronics andApplications (EPE 2011), Proceedings of the 2011-14th EuropeanConference on, pages 1 –9, 30 2011-sept. 1 2011.
[2] A. Sumper, O. Gomis-Belmunt, A. Sudria-Andreu, R. Villafafila-Robles,and J. Rull-Duran. Short-term voltage stability of fixed-speed windturbines: Comparison of single and double cage. In Power and EnergySociety General Meeting, 2010 IEEE, pages 1 –8, july 2010.
[3] O. Gomis-Bellmunt, A. Junyent-Ferre, A. Sumper, and J. Bergas-Jan. Ride-through control of a doubly fed induction generator underunbalanced voltage sags. Energy Conversion, IEEE Transactions on,23(4):1036 –1045, dec. 2008.
[4] A. Junyent-Ferre, O. Gomis-Bellmunt, M. Martinez-Rojas, A. Sumper,M. Sala, and M. Mata. Digital simulation of voltage dip characteristicsof wind turbine systems. In Electrical Power Quality and Utilisation,2007. EPQU 2007. 9th International Conference on, 1 –6, oct. 2007.
[5] A. Sumper, O. Gomis-Bellmunt, A. Sudria-Andreu, R. Villafafila-Robles, and J. Rull-Duran. Response of fixed speed wind turbines tosystem frequency disturbances. Power Systems, IEEE Transactions on,24(1):181 –192, feb. 2009.
[6] A. Babaie Lajimi, S. Asghar Gholamian, and M. Shahabi. Modeling andControl of a DFIG-Based Wind Turbine During a Grid Voltage Drop.ETASR - Engineering, Technology & Applied Science Research, 5(1):121–125, 2011.
[7] L. Xu, and Y. Wang. Dynamic Modeling and Control of DFIG-BasedWind Turbines Under Unbalanced Network Conditions. PowerSystems, IEEE Transactions on, 22(1):314 –323, feb. 2007.
[8] Y. Ren, L. Cao, J. Zhou, L. Liu, M. Zhang, and H. Li. The Modelingand Control of VSCF DFIG Wind Power Generation Based on PSCAD.International Conference on Intelligent Control and Information Pro-cessing, Aug. 13-15, 2010. Dalian, China.
[9] C. Hamon, K. Elkington, and M. Ghandhari. Doubly-fed Induction Gen-erator Modeling and Control in DigSilent PowerFactory. InternationalConference on Power System Technology, 2010.
[10] Eltra. Specifications for connecting wind farms to the transmisionnetwork. Technical report, Eltra, 2000.
[11] S. Heier. Grid Integration of Wind Energy Conversion Systems. JohnWiley and Sons, 1998.
[12] Z.Lubosny. Wind Turbine Operation in Electric Power Systems.Springer, 2003.
[13] V. Akhmatov. Analysis of Dynamic Behaviour of Electric Power Systemswith Large Amount of Wind Power. PhD thesis, Technical University ofDenmark, 2003.
[14] Fernando D. Bianchi, Hernan De Battista, and Ricardo J. Mantz. WindTurbine Control Systems. British Library Cataloguing, 2007.
[15] Ned Mohan. Advanced Electric Drives. MNPERE, 2001.[16] R. Pena, J.C. J.C. Clare, and G.M. Asher. Doubly fed induction generator
using back-to-back PWM convertersand its application to variable-speedwind-energy generation. IEE Proceedings Electric Power Applications,143(3):231–241, 1996.
[17] E. Valsera-Naranjo, A. Sumper, O. Gomis-Bellmunt, A. Junyent-Ferre,and M. Martinez-Rojas. Design of a pitch control of a wind turbineto improve system frequency response. In Power Electronics andApplications, 2009. EPE ’09. 13th European Conference, 1 –11, 2009.
[18] Cesar de Prada. Pid controllers and tuning. Universidad de Valladolid.[19] A. Junyent-Ferre. Modelitzacio i control d’un sistema de generacio
electrica de turbina de vent. Master’s thesis, UPC, 2007.[20] G. Ramtharan, J.B. Ekanayake, and N. Jenkins. Frequency support from
doubly fed induction generator wind turbines. IET Renewable PowerGeneration, 1(1):3–9, March 2007.
[21] J. Morren, S.W.H. de Haan, W.L. Kling, and J.A. Ferreira. Windturbines emulating inertia and supporting primary frequency control.IEEE Transactions on Power Systems, 21(1):433–434, Feb. 2006.
[22] M. Kayikci and J. V. Milanovic. Dynamic contribution of dfig-basedwind plants to system frequency disturbances. IEEE Transactions onPower Systems, 24(2):859–867, May 2009.
[23] AEE. Procedimiento de verificacion, validacion y certificacion de losrequisitos del p.o.12.3 sobre la respuesta de las instalaciones eolicas antehuecos de tension., Noviembre 2007.
[24] REE. P.O.12.3. Requisitos de respuesta frente a huecos de tension delas instalaciones de produccion de regimen especial.