iec curve ref rom siprotec
TRANSCRIPT
-
8/3/2019 IEC Curve Ref Rom Siprotec
1/8
Normal Inverse
t = Trip time in seconds
I = Fault current
Ip = Setting value of the pickup current
Tp = Time dial
Time Factor = 0.19 0.05 0.1 0.2 0.4 0.8 1.6 3.2
Pickup Current = 1 1 1 1 1 1 1 1
Fault Current Time Curve
1.1 13.94 3.67 7.34 14.67 29.35 58.70 117.40 234.80
1.2 7.28 1.92 3.83 7.66 15.33 30.66 61.32 122.64
1.3 5.06 1.33 2.66 5.32 10.64 21.29 42.58 85.15
1.4 3.94 1.04 2.07 4.15 8.29 16.59 33.17 66.35
1.5 3.27 0.86 1.72 3.44 6.88 13.76 27.51 55.02
1.6 2.82 0.74 1.48 2.96 5.93 11.86 23.72 47.44
1.7 2.49 0.66 1.31 2.62 5.25 10.50 21.00 41.99
1.8 2.25 0.59 1.18 2.37 4.74 9.47 18.94 37.89
1.9 2.06 0.54 1.08 2.17 4.33 8.67 17.34 34.68
2 1.91 0.50 1.00 2.01 4.01 8.02 16.05 32.09
2.1 1.78 0.47 0.94 1.87 3.75 7.49 14.98 29.97
2.2 1.67 0.44 0.88 1.76 3.52 7.05 14.09 28.19
2.3 1.58 0.42 0.83 1.67 3.33 6.67 13.34 26.67
2.4 1.51 0.40 0.79 1.59 3.17 6.34 12.68 25.36
2.5 1.44 0.38 0.76 1.51 3.03 6.06 12.11 24.22
2.6 1.38 0.36 0.73 1.45 2.90 5.80 11.61 23.222.7 1.33 0.35 0.70 1.40 2.79 5.58 11.16 22.33
2.8 1.28 0.34 0.67 1.35 2.69 5.38 10.77 21.53
2.9 1.24 0.33 0.65 1.30 2.60 5.20 10.41 20.82
3 1.20 0.32 0.63 1.26 2.52 5.04 10.08 20.17
3.1 1.16 0.31 0.61 1.22 2.45 4.89 9.79 19.58
3.2 1.13 0.30 0.59 1.19 2.38 4.76 9.52 19.03
3.3 1.10 0.29 0.58 1.16 2.32 4.63 9.27 18.54
3.4 1.07 0.28 0.57 1.13 2.26 4.52 9.04 18.08
3.5 1.05 0.28 0.55 1.10 2.21 4.41 8.83 17.66
3.6 1.03 0.27 0.54 1.08 2.16 4.32 8.63 17.26
3.7 1.00 0.26 0.53 1.06 2.11 4.22 8.45 16.90
3.8 0.98 0.26 0.52 1.03 2.07 4.14 8.28 16.563.9 0.96 0.25 0.51 1.01 2.03 4.06 8.12 16.24
4 0.95 0.25 0.50 1.00 1.99 3.98 7.97 15.94
4.1 0.93 0.24 0.49 0.98 1.96 3.91 7.83 15.65
4.2 0.91 0.24 0.48 0.96 1.92 3.85 7.69 15.39
4.3 0.90 0.24 0.47 0.95 1.89 3.78 7.57 15.13
4.4 0.88 0.23 0.47 0.93 1.86 3.72 7.45 14.90
4.5 0.87 0.23 0.46 0.92 1.83 3.67 7.33 14.67
4.6 0.86 0.23 0.45 0.90 1.81 3.61 7.23 14.46
4.7 0.85 0.22 0.45 0.89 1.78 3.56 7.13 14.25
4.8 0.83 0.22 0.44 0.88 1.76 3.51 7.03 14.06
4.9 0.82 0.22 0.43 0.87 1.73 3.47 6.94 13.87
5 0.81 0.21 0.43 0.86 1.71 3.42 6.85 13.705.1 0.80 0.21 0.42 0.85 1.69 3.38 6.76 13.53
2.21
t=
0.14
IIp
0 .02
1
Tp
-
8/3/2019 IEC Curve Ref Rom Siprotec
2/8
5.2 0.79 0.21 0.42 0.84 1.67 3.34 6.68 13.36
5.3 0.78 0.21 0.41 0.83 1.65 3.30 6.60 13.21
5.4 0.78 0.20 0.41 0.82 1.63 3.26 6.53 13.06
5.5 0.77 0.20 0.40 0.81 1.61 3.23 6.46 12.92
5.6 0.76 0.20 0.40 0.80 1.60 3.19 6.39 12.78
5.7 0.75 0.20 0.40 0.79 1.58 3.16 6.32 12.65
5.8 0.74 0.20 0.39 0.78 1.57 3.13 6.26 12.52
5.9 0.74 0.19 0.39 0.77 1.55 3.10 6.20 12.40
6 0.73 0.19 0.38 0.77 1.53 3.07 6.14 12.28
6.1 0.72 0.19 0.38 0.76 1.52 3.04 6.08 12.16
6.2 0.72 0.19 0.38 0.75 1.51 3.01 6.03 12.05
6.3 0.71 0.19 0.37 0.75 1.49 2.99 5.97 11.95
6.4 0.70 0.19 0.37 0.74 1.48 2.96 5.92 11.84
-
8/3/2019 IEC Curve Ref Rom Siprotec
3/8
1 10 100
0.1
1
10
100
Column L
Column K
Column J
Column I
Column H
Column G
Column F
Column E
I/Ip
t [s]
-
8/3/2019 IEC Curve Ref Rom Siprotec
4/8
-
8/3/2019 IEC Curve Ref Rom Siprotec
5/8
-
8/3/2019 IEC Curve Ref Rom Siprotec
6/8
-
8/3/2019 IEC Curve Ref Rom Siprotec
7/8
-
8/3/2019 IEC Curve Ref Rom Siprotec
8/8