![Page 1: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/1.jpg)
How to Connect to ION7350 with ION Enterprise via
PMC-1380Communication Port WiringION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380 Ethernet Port 1 connects to the LAN. PC connects to the LAN.
Communication ParametersION7350ID = 106, Baud Rate = 9600, Protocol = IONPMC-1380Serial Port 2:Mode = RS-485, Baud Rate = 9600, Data Bits = 8, Parity = None, Stop Bits = 1, IP Port = 20001Ethernet Port 1:IP Address = 192.168.0.127Subnet Mask = 255.255.255.0Gateway = 192.168.0.1
PC:
1
![Page 2: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/2.jpg)
IP Address = 191.0.1.120Subnet Mask = 255.255.255.0Gateway = 191.0.1.3TCP/IP Properties Advance Add
2
![Page 3: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/3.jpg)
Configure ION Enterprise1) Start ION Services.
2) Management ConsoleAdd an Ethernet Gateway Site.
3
![Page 4: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/4.jpg)
4
![Page 5: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/5.jpg)
Add a Serial Device on Ethernet Gateway Site.
5
![Page 6: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/6.jpg)
6
![Page 7: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/7.jpg)
3) Restart PC.4) Start Vista. Select File Generate Network Diagram. Click on the ION7350 device. Select a
framework.
5) Start Designer. Select the ION7350 device. Right-click on a module type and select a module to display the detailed diagram.
7
![Page 8: ibd.cet-global.com · Web viewHow to Connect to ION7350 with ION Enterprise via PMC-1380 Communication Port Wiring ION7350 COM1 Port (RS-485) connects to PMC-1380 Serial Port 2. PMC-1380](https://reader034.vdocuments.us/reader034/viewer/2022042104/5e8258a21c5ee20ab006bd0e/html5/thumbnails/8.jpg)
If the PMC-1380 RS-485 port 2 connection is broken, the communications with ION 7350 break. When the connection recovers, the communications resume.
If the PMC-1380 Ethernet 1 connection is broken, the communications with ION 7350 break. When the connection recovers, the communications resume.
8