I N S T R U C T I O N M A N U A L
T H E R O B O S L I D ER E S I D E N T I A L S L I D E G A T E O P E R A T O R
Installation instructions and manual book for architects, general contractors and dealers
®®
copyright © 2008 chamberlain professional products - www.liftmaster.com
11
• BEFORE attempting to install, operate or maintain the operator, you must read and fully understand this manual and follow all safety instructions.
• DO NOT attempt repair or service of your residential gate operator unless you are an Authorized Service Technician.
When you see these Safety Symbols and Signal Words on the following pages, they will alert you to the possibility of serious injury or death if you do not comply with the warnings that accompany them. The hazard may come from something mechanical or from electric shock. Read the warnings carefully.When you see this Signal Word on the following pages, it will alert you to the possibility of damage to your gate and/or the gate operator if you do not comply with the cautionary statements that accompany it. Read them carefully.
IMPORTANT NOTE
SPECIFICATIONS AND WARNINGSSpecifications and Warnings . . . . . . . . . . . . . . . . . . . . . . . . 2Safety Installation Information . . . . . . . . . . . . . . . . . . . . . . . 3Suggested Entrapment Protection Device Locations . . . . .4-5Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Warning Sign Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Safety Catch Rollers and Gate Rail Stops . . . . . . . . . . . . . . . 7
INSTALLATIONGetting Started . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Mounting Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Chain Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Earth Ground Rod Installation . . . . . . . . . . . . . . . . . . . . . . . 9
WIRINGControl Board Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Surge Suppressor Terminal Connections . . . . . . . . . . . . . . 11DC Power Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Solar Panel Connection - Optional . . . . . . . . . . . . . . . . . . . 13Fire Release Box - Optional. . . . . . . . . . . . . . . . . . . . . . . . . 14Input Board - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Solenoid/Maglock Connection . . . . . . . . . . . . . . . . . . . . . . 1612 VDC Photo Beam Wiring - Optional . . . . . . . . . . . . . . . . 17Optional Edge Sensor Wiring - Optional . . . . . . . . . . . . . . . 183-Button Control Station Wiring Connection . . . . . . . . . . . 193-Button Control Station Wiring Master/Secondary . . . . . . 20Single Operator Loop Size and Placement . . . . . . . . . . . . . 21Master/Secondary Loop Size and Placement . . . . . . . . . . . 2212 VDC External Loop Detector Wiring. . . . . . . . . . . . . . . . 23
ADJUSTMENTSGate Movement Direction . . . . . . . . . . . . . . . . . . . . . . . . . . 24Limit Switch Adjustments. . . . . . . . . . . . . . . . . . . . . . . . . . 25Setting Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25Master and Secondary with Timer . . . . . . . . . . . . . . . . . . . 26Master and Secondary without Timer. . . . . . . . . . . . . . . . . 27315 MHz Radio Receiver Programming . . . . . . . . . . . . .28-29Two-Way Adjustable Reversing Sensor . . . . . . . . . . . . . . . 30
OPERATION AND MAINTENANCEImportant Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . 31LED Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32-33How to Reset the Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . 34How to Check the Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Mechanical
Electrical
T A B L E O F C O N T E N T S
WARNING
WARNING
CAUTION
TROUBLESHOOTING The Gate Will Not Close . . . . . . . . . . . . . . . . . . . . . . . . . . . 35The Gate Will Not Open . . . . . . . . . . . . . . . . . . . . . . . . . . . 35If You Hear a Beep Sound . . . . . . . . . . . . . . . . . . . . . . . . . 36
REPAIR PARTSAccessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37Robo Slide Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39How to Order Repair Parts . . . . . . . . . . . . . . . . . . . . . . . . . 39
INSTALLATION CHECKLIST. . . . . . . . . . . . . . . . . . . . 40
2
S P E C I F I C A T I O N S A N D W A R N I N G S
Recommended Gate Setup Configuration
Gate Speed – 11 inch per secondMaximum Gate Length – 20 feet Maximum Gate Weight – 800 poundsMaximum Cycles – 70 cycles per day with Chamberlain Elite’s Plug-In Transformer. – Solar power cycles per day varies, Contact Chamberlain for more Information – Battery back-up cycles (50 cycles total)AC Power Supply – 25 VDC 1.6 Amp Plug-In Transformer (Part # A POW-1)AC Power Supply Wire – 14 gauge or greater landscape lighting cable rated for direct burial and 300 watts at maximum length of 1000 ft. DC Power Supply – Built-in, back-up for AC or Solar power failure onlySolar Power – Optional (Part # SOLAR 3)
Non-Pinch Rollers
Sensor Edges
Sensor Edges
Non-Pinch Rollers
3" Max. Width
(2"x 2" Screen)
Weld Physical Stops on Both Ends of Gate Rail
All “Pinch Points” MUST have protective safety devices.
Warning Placards Permanently Mounted
on Both Sides of Gate
S P E C I F I C A T I O N S
S A F E T Y I N S T A L L A T I O N I N F O R M A T I O N
33
1. Install the gate operator only when: a. The operator is appropriate for the construction and the usage class of the gate. b. All openings of a horizontal swing gate are guarded or screened from the bottom of the gate to a minimum of
4' (1.2 m) above the ground to prevent a 2-1/4" (6 cm) diameter sphere from passing through the openings anywhere in the gate, and in that portion of the adjacent fence that the gate covers in the open position.
c. All exposed pinch points are eliminated or guarded, and guarding is supplied for exposed rollers.
2. The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separateaccess opening.
3. The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment. Swinging gates shall not open into public access areas.
4. The gate must be properly installed and work freely in both directions prior to the installation of the gate operator.
5. Controls must be far enough from the gate so that the user is prevented from coming in contact with the gate while operatingthe controls.
6. Controls intended to be used to reset an operator after 2 sequential activations of the entrapment protection device or devices must be located in the line of sight of the gate, or easily accessible controls shall have a security feature to prevent unauthorized use.
7. All warning signs must be installed where visible, on each side of the gate.
8. For a gate operator utilizing a non-contact sensor: a. Reference owner’s manual regarding placement of non-contact sensor for each type of application. b. Care shall be exercised to reduce the risk of nuisance tripping, such as when a vehicle trips the sensor while the gate is
still moving. c. One or more non-contact sensors shall be located where the risk of entrapment or obstruction exists, such as the perimeter
reachable by a moving gate or barrier.
9. For a gate operator utilizing a contact sensor such as an edge sensor: a. A hard wired contact sensor shall be located and its wiring arranged so the communication between the sensor and the gate
operator is not subject to mechanical damage. b. A wireless contact sensor such as the one that transmits radio frequency (RF) signals to the gate operator for entrapment
protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures, natural landscaping or similar obstruction. A wireless contact sensor shall function under the intended end-use conditions.
c. One or more contact sensors shall be located at the leading edge, trailing edge and post mounted both inside and outside of a vehicular horizontal slide gate.
d. One or more contact sensors shall be located at the bottom edge of a vehicular vertical lift gate. e. One or more contact sensors shall be located on the inside and outside leading edge of a swing gate. Additionally, if the bottom
edge of a swing gate is greater than 6" (15 cm) above the ground at any point in its arc of travel, one or more contact sensors shall be located on the bottom edge.
44
Outside Safety
Loop
Inside Safety
Loop
Outside Property
Inside Property
Outside Safety
LoopOutOOOut
Entrapment D
anger
for OPEN Cycle
utside Safety
Loopde SOutsOOutsutsOOO
OOO
Inside Safety
Loop
Outside Property
Inside Property
Safety Danger
for CLOSE Cycle
S U G G E S T E D E N T R A P M E N T P R O T E C T I O N D E V I C E L O C A T I O N S
To prevent SERIOUS INJURY or DEATH from a moving gate: • Entrapment protection devices MUST be installed to protect anyone who may come near a moving gate. • Locate entrapment protection devices to protect in BOTH the open and close gate cycles. • Locate entrapment protection devices to protect between moving gate and RIGID objects, such as posts or walls.
WARNING
Install photo electric sensors to protect against any entrapment or safety conditions encountered in your gate application.See page 17.
Safety loops allows the gate to stay open when vehicles are obstructing the gate path. Suggested for vehicles 14 feet or longer.See pages 21 and 22.
Gate Rail Stops For safety reasons, physical stops MUST be installed on both ends of the gate rail prior to installation of the gate operator. This will assure that the gate does not derail while opening or closing fully.See page 7.
Non-Contact Sensors (Photo Electric Sensors)
5
Outside Safety
Loop
Inside Safety
Loop
Outside Property
Inside Property
OutsOOutsOOO
Entrapment Danger
Safety Danger
S U G G E S T E D E N T R A P M E N T P R O T E C T I O N D E V I C E L O C A T I O N S
To prevent SERIOUS INJURY or DEATH from a moving gate: • Entrapment protection devices MUST be installed to protect anyone who may come near a moving gate. • Locate entrapment protection devices to protect in BOTH the open and close gate cycles. • Locate entrapment protection devices to protect between moving gate and RIGID objects, such as posts or walls.
WARNING
Install edge sensors to protect against any entrapment or safety conditions encountered in your gate application.See page 18.
Safety loops allows the gate to stay open when vehicles are obstructing the gate path. Suggested for vehicles 14 feet or longer.See pages 21 and 22.
Gate Rail Stops For safety reasons, physical stops MUST be installed on both ends of the gate rail prior to installation of the gate operator. This will assure that the gate does not derail while opening or closing fully.See page 7.
Edge sensor for open cycle on wall.
Edge sensor for open cycle on wall.
Edge sensor for close cycle
on gate.
Edge sensor for close cycle on wall.
Edge sensor for open cycle on gate.
Contact Sensors (Edge Sensors)
To prevent SERIOUS INJURY or DEATH from a moving gate:• Entrapment protection devices MUST be installed to protect anyone who may come near a moving gate.• Locate entrapment protection devices to protect in BOTH the open and close gate cycles.• Locate entrapment protection devices to protect between moving gate and RIGID objects, such as posts or walls.
WARNING
S A F E T Y P R E C A U T I O N S
Property owners MUST never mount any gate operating device near the gate’s path!
Property owners MUST never allow anyone to hang or ride on the gate!
Property owners MUST never let pedestrians cross the path of a moving gate!
W A R N I N G S I G N P L A C E M E N T
THE ROBO SLIDE IS FOR USE ON VEHICULAR PASSAGE GATES ONLY AND NOT INTENDED FOR USE ON PEDESTRIAN PASSAGE GATES.
To prevent SERIOUS INJURY or DEATH from a moving gate:Install Warning signs on BOTH sides of EACH gate in PLAIN VIEW.
WARNING
6
77
Closing Gate
Closing Gate
Because the coasting distance may vary due to changes in temperature, it is NOT recommended to install a stop or catch post in front of the gates path. To do so will cause the gate to hit the post in certain instances.
It is only recommended to install catch rollers with safety covers on the side of a post or wall with a minimal distance of half an inch between the rollers and gate.
NOTE: For safety reasons, physical stops MUST be installed on both ends of the gate rail prior to installation of the gate operator. This will assure that the gate does not derail while opening or closing fully.
When fully opened, the end of the sliding gate should stop at least five inches from an obstructing wall.
End View of Gate and Wall
S A F E T Y C A T C H R O L L E R S A N D G A T E R A I L S T O P S
5"
1/2"1/2"
Gate Rail Stop
DO NOT use a Gate Catch Post.
8
6"
20"15"
10"
8"
ACCESS SYSTEMS INC
ACCESS SYSTEMS INC
OVERLOAD
POWER
CHARGE OK
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMERUP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5MMADE IN USA
ALARMSENSOR
REVERSESENSOR
HEAVYGATE
FIREDEPT
STRIKEOPEN
SAFETYLOOP
EXITLOOP
RADIOREC
CHARGINGPOWER
BOARDPOWER
CHECKFUSE
J2
POWER INPUT
18 VAC
SAFETY
LOOP
EXITLOOP
FIRE DEPT
KEY SWITCHSTRIKE OPEN
PUSH BUTTONRADIO
RECEIVERCLASS 2
SUPPLY
M O U N T I N G O P E R A T O R
C H A I N I N S T A L L A T I O N
Incorrect Chain Installation
Too High
Too Low
Gate
Incorrect Chain Spacing
4" MinimumGate
Correct Chain Spacing
Front of GateBack of Gate
POWER INPUT18 VAC
SAFETYLOOP
EXITLOOP
FIRE DEPTKEY SWITCH
STRIKE OPENPUSH BUTTON
RADIORECEIVER
CLASS 2SUPPLY
eliteaccess.com
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCROBO SURGE SUPPRESSOR
POWER INPUT18 VAC
SAFETYLOOP
EXITLOOP
FIRE DEPTKEY SWITCH
STRIKE OPENPUSH BUTTON
RADIORECEIVER
CLASS 2SUPPLY
eliteaccess.com
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCROBO SURGE SUPPRESSOR
Minimum space between gate and output sprocket must be 4". After you position the gate operator, bolt-down the operator to the concrete bed. Make certain that the concrete bed is solid.
Correct Chain Installation
InstallationG E T T I N G S T A R T E D
This gate operator is designed for single home application, or for limited commercial applications. An example of a commercial application would be a factory facility with limited cycles per day, using a plug in transformer or solar panel.
4 Concrete Anchors1/2" x 3 1/2"
Below the frost line. Check all local codes.
UL approved underground conduit(s).High voltage power wires run in
separate conduit.
Above Ground
9
OVERLOAD
POWER
CHARGE OK
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
POWER INPUT
18 VAC
SAFETY
LOOP
EXITLOOP
FIRE DEPT
KEY SWITCHSTRIKE OPEN
PUSH BUTTONRADIO
RECEIVERCLASS 2
SUPPLY
E A R T H G R O U N D R O D I N S T A L L A T I O N
Use 14 gauge / 300 watt direct burial, landscape lighting wire NOT to exceed 1000 ft. for transformer.
Wiring
To reduce the risk of SEVERE INJURY or DEATH:• ANY maintenance to the operator or in the area near the operator MUST not be performed until disconnecting the electrical power and locking-out the power via the operator power switch. Upon completion of maintenance the area MUST be cleared and secured, at that time the unit may be returned to service.• Disconnect battery and 25 Vdc transformer or solar panel BEFORE proceeding. Operator MUST be properly grounded and connected in accordance with local electrical codes. NOTE: The operator should be on a separate fused line of adequate capacity.• ALL electrical connections MUST be made by a qualified individual.
• DO NOT install any wiring or attempt to run the operator without consulting the wiring diagram. We recommend that you install an optional reversing edge BEFORE proceeding with the control station installation.• ALL power wiring should be on a dedicated circuit and well protected. The location of the power disconnect should be visible and clearly labeled.• ALL power and control wiring MUST be run in separate conduit.• BEFORE installing power wiring or control stations be sure to follow all specifications and warnings described below. Failure to do so may result in SEVERE INJURY to persons and/or damage to operator.
WARNING
All power wiring should be on a dedicated circuit and well protected.NOTE: Calculated using NEC guidelines. Local codes and conditions must be reviewed for suitability of wire installation.
To prevent SERIOUS INJURY or DEATH from a moving gate:DO NOT disconnect the built-in audio alarm or reset switch.
WARNING
To AVOID damaging gas, power, or other underground utility lines, contact underground utility locating companies BEFORE digging more than 18" (46 cm) deep.
To AVOID damaging 25 Vdc plug-in transformer, it MUST be enclosed in a suitable weatherproof enclosure and provided with proper weatherproof fixtures.
CAUTION
CAUTIONProper grounding gives an electrical charge, such as from an electrical static discharge or a near lightning strike, a path from which to dissipate its energy safely into the earth.
Without this path, the intense energy generated by lightning could be directed towards the Elite gate operator. Although nothing can absorb the tremendous power of a direct lightning strike, proper grounding can protect the gate operator in most cases.
The earth ground rod must be located within 3 feet from the Elite gate operator. Use the proper type earth ground rod for yourlocal area.
The ground wire must be a single, whole piece of wire. Never splice two wires for the ground wire. If you should cut the ground wire too short, break it, or destroy its integrity, replace it with a single wire length.
Single Piece of 12 gauge wire
Check local codes for proper depth
Within 3 ft
1010
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMERUP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5MMADE IN USA
ALARMSENSOR
REVERSESENSOR
HEAVYGATE
FIREDEPT
STRIKEOPEN
SAFETYLOOP
EXITLOOP
RADIOREC
CHARGINGPOWER
BOARDPOWER
CHECKFUSE
J2
CHARGE OK
123 Low Battery Indicator LED4 Heavy Gate Indicator LED5 Open Relay LED6 Close Relay LED7 System on, Reversing Sensor and Alarm Sensor8 Alarm Sensor LED9 Reversing Sensor LED (Rebounder)1010 Central Control LED1111 Fire Department or Key Switch LED1212 Strike Open LED1313 Safety Loop or Photocell LED1414 Exit Loop LED1515 Radio Receiver LED
16171818 J2 Alternate Optional Output 1919 Movement Direction Sockets2020 Replace Fuse Indicator2121 Spike Suppressor2222 Jumper for Stop Button2323 Optional Input Board 24 24 Surge Suppressor Connector2525 Breaker Reset2626 Overload LED2727 On Board Open Button2828 On Board Stop Button2929 On Board Close Button
1515141413131212
1111
4
9
2323
8
7
1818
2424
2121
22221919
2020
1
2626
23
5
6
2525
OPE
NC
LOSE
STO
P
17171616
101027272828
2929
C O N T R O L B O A R D F U N C T I O N S
To AVOID damaging the control board, replace fuses ONLY with same type and rating specified above.
CAUTION
®
STRIKE OPENPUSH BUTTONSTRIKE OPEN
PUSH BUTTONFIRE DEPT
KEY SWITCHFIRE DEPT
KEY SWITCH
CLASS 2SUPPLYCLASS 2SUPPLYSAFETY
LOOPSAFETYLOOP
POWER INPUT25 VDC
RADIORECEIVER
RADIORECEIVER
EXITLOOPEXIT
LOOP
–– ++
P/N Q412PATENT PENDING
P/N Q412PATENT PENDINGROBO SURGE SUPPRESSOR
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
7 13121110981 654–––DC DC
4
7 8
0HELP
9
1 2 35 6
7
10 9
10 9
10 9
8
12 Volt
Neg.
Com.
Neg.
++
––
––
13
12
11
11
1 Red
2 Black
4 Green
3 White ®
11
13 ––++
4 313 11
6 5
13 11
13 11
4 3
Card Reader
Remote NOT Provided
External 12 VDC “Exit” Loop Detector
12 VDC Photo Electric Sensor (Safety)
External 12 VDC “Safety” Loop Detector
Master/Second Operator Link
315 MHz Factory Installed Radio Receiver
Push Button
Telephone Entry System
Fire or any Key SwitchNOTE: Terminals 11 and 12 are the ONLY terminals that will Open and Close with a single push of a button. All other terminals will ONLY open with a single push of a button.
Dry Contact
Dry Contact
Page 23
Page 23
Page 17
Output Power
Ground12 VDC
Remote Programming on pages 28 and 29.
Power
Power
Power
Separate powerfor card reader.
Separate powerfor second operator.
Separate powerfor TES.
To ENSURE proper operation of external devices:• ENSURE bare wires make good contact inside removable terminal connections.• DO NOT let wire insulation interfere with connection.
CAUTION
S U R G E S U P P R E S S O R T E R M I N A L C O N N E C T I O N S
11
12
Do not use solar panel and plug-in transformer at the same time.Use Chamberlain Elite’s optional 25 VDC plug-in transformer(APOW1). Hook up the transformer to 120 VAC. Use two, low voltage, 14 gauge / 300watt direct burial, landscape lighting cables. Hook these wires to the plug-in transformer and to the power input connection on the surge suppressor. Polarity does not matter.
25 VDC Plug-in Transformer
Use 14 gauge / 300 watt direct burial, landscape lightingwire NOT to exceed 1000 ft. for transformer.
Polarity Does Not Matter
To 120 VAC
®
STRIKE OPENPUSH BUTTONSTRIKE OPENPUSH BUTTON
FIRE DEPTKEY SWITCHFIRE DEPT
KEY SWITCH
CLASS 2SUPPLY
SAFETYLOOP
SAFETYLOOP
POWER INPUT25 VDC
RADIORECEIVER
RADIORECEIVER
EXITLOOPEXITLOOP
–– ++
P/N Q412PATENT PENDING
P/N Q412PATENT PENDINGROBO SURGE SUPPRESSOR
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
7 13121110981 654–––DC DC
®
POWER INPUT25 VDC
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
–DC DCLOWLOWVOLTAGEVOLTAGE
ONLY!ONLY!
When the plug-in transformer has been connected to the power source, connect the battery cable plug to the motor harness plug. You will hear 3 beeps. After the beeps, check the “Charge OK” LED...it must be “ON”.
Beep! Beep! Beep!
Motor Harness
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
OFF
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OKCHARGE OK
OPE
N
CLO
SE
STO
P
Alarm Sensor LED will flash 3 times during power connection. This means the board is OK.
D C P O W E R C O N N E C T I O N
To AVOID damaging 25 Vdc plug-in transformer, it MUST be enclosed in a suitable weatherproof enclosure and provided with proper weatherproof fixtures.To AVOID damaging control board, DO NOT use the solar panel and the plug-in transformer at the same time.
CAUTION
Earth Ground Rod Highly Recommended!
13
Polarity Does Not Matter
Solar Panel(SOLAR3)No Stand
30 AHr 12 VDC
®
STRIKE OPENPUSH BUTTONSTRIKE OPEN
PUSH BUTTONFIRE DEPT
KEY SWITCHFIRE DEPT
KEY SWITCH
CLASS 2SUPPLYCLASS 2SUPPLYSAFETY
LOOPSAFETYLOOP
POWER INPUT25 VDC
RADIORECEIVER
RADIORECEIVER
EXITLOOPEXIT
LOOP
– – + +
P/N Q412PATENT PENDING
P/N Q412PATENT PENDINGROBO SURGE SUPPRESSOR
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
7 13 12 11 10 9 8 1 6 5 4 – – – DC DC
®
POWER INPUT25 VDC
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
– DC DC
O P T I O N A L S O L A R P A N E L C O N N E C T I O N
To AVOID damaging 25 Vdc plug-in transformer, it MUST be enclosed in a suitable weatherproof enclosure and provided with proper weatherproof fixtures.To AVOID damaging control board, DO NOT use the solar panel and the plug-in transformer at the same time.
CAUTION
Chamberlain Elite recommends using a larger battery (12 VDC, 30 AHr) (Part # A12330SGLPK) in this operator when using the optional solar panel.
CAUTION
If you use Chamberlain Elite’s optional solar panel (Solar3). Connect the two wires from the solar panel to the power input connection on the surge suppressor (Polarity does not matter). Sunlight will energize the batteries through the solar panel. This solar panel will charge up to 1000 Mamp/Hr in optimum conditions & 300 Mamp/Hr in light overcast conditions. For further details about Chamberlain Elite’s solar panel, consult the “Solar 3” Installation sheet that is included with the solar panel. Do not use solar panel and plug-in transformer at the same time.
Energizing this operator with solar power only needs the radio receiver to operate the gate. The only recommended external devices other than radio receivers are dry-contact command devices which do not consume any current like key switches. Using other devices that consume high current such as telephone access, magnetic locks or loop detectors will cause excess drainage of the battery and eventually completely drain the battery. For more details, contact your local dealer.
14
The chain is held in place by a spring loaded pin.
Pull firmly on the “T” Handle to release the chain.
The “Fire Release Box”, is designed for use on sliding gates. It consists of a plated box, with doors on the front and back. The doors can be locked with your own padlock, or the fire department’s padlock. The fire box would be fixed to the gate pickets. It can be opened from either side of the gate. A steel cable with a T-handle runs from the box to the release mechanism at the rear end of the chain. We do not provide the 1/2" EMT to run the cable through. The release mechanism, is placed where the chain bolt would normally be. When you pull on the T-handle, you release the chain from the bolt. To reset, simply reinsert the pin into the housing for normal operation (Part # ACP17).
Contact your local dealer for more information.
“ O P T I O N A L ” F I R E R E L E A S E B O X
15
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OK
The optional board allows extra control of the gate, is available only from Chamberlain Elite Access Systems. Installation is simple; just clip the optional board to the J2 slot on the top of the control board. Below lists the function of each pin.
16 2 4 6 8 10 12 14
15 13 11 9 7 5 3 1
16-Pin Plug
OPE
N
Open Switch (N.O.)Stop Switch (N.C.) (Cut W1 Jumper at Bottom of Board)Timer Close Output to SlaveTimer Input from Master (Close Command or Close Switch) (N.O.)Alarm Output will be set off with very heavy gates or object preventing gate operation.(Not Burglar Alarm) (9 = +12 VDC, 10 = Alarm)Emergency Open Switch (Direct Command from Battery to Motor)Emergency Close Switch (Direct Command from Battery to Motor)Magnetic Lock - Dry Contact Relay (13 = Com, 14 = N.C.)Center Loop Option (For Swing Gate Operators Only)
1 & 2 3 & 4 5 & 6 7 & 8 9 &10
d 11 & 4 12 & 7
13 & 14 15 & 16
W1
“ O P T I O N A L ” I N P U T B O A R D
16
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OK
The “Optional” input board MUST be used to perform this function (Part# Q203).
16 2 4 6 8 10 12 14
15 13 11 9 7 5 3 1
N.C. Powerfor
MaglockCommon
Part # A MG 1300
13
14
16-Pin Plug
Dry Contact Relay
Relay Contact Rating 0.5 Amp - 125 VAC
1 Amp - 24 VDC
S O L E N O I D / M A G L O C K C O N N E C T I O N
To ENSURE proper operation of external devices:• ENSURE bare wires make good contact inside removable
terminal connections.• DO NOT let wire insulation interfere with connection.
CAUTION
17
®
STRIKE OPENPUSH BUTTONSTRIKE OPENPUSH BUTTON
FIRE DEPTKEY SWITCHFIRE DEPT
KEY SWITCH
CLASS 2SUPPLY
CLASS 2SUPPLYSAFETY
LOOPSAFETYLOOP
POWER INPUT25 VDC
RADIORECEIVER
RADIORECEIVER
EXITLOOPEXITLOOP
– – + +
P/N Q412PATENT PENDING
P/N Q412PATENT PENDINGROBO SURGE SUPPRESSOR
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
7 13 12 11 10 9 8 1 6 5 4 – – – DC DC
11 13
– +
1 4
Power
(Part # A OMRON 12V) (Failsafe)
Contact your local dealer for more information.
Photo Beam (Safety) 12 VDC
Blue Orange White Brown
It is best to use 12 VDC Failsafe Photo Beam Sensors for this Safety Option
Failsafe Photo Beam: If a failsafe photo beam is not working or loses power or photo beam is blocked, then thephoto beam will stop all gate operation.
NOTE: If photo beam is blocked the gate will stop and reopen. The gate will remain open until the obstruction is cleared.
“ O P T I O N A L ” 1 2 V D C P H O T O B E A M W I R I N G
To prevent SERIOUS INJURY or DEATH from a moving gate:• Locate entrapment protection devices to protect in BOTH the
open and close gate cycles.• Locate entrapment protection devices to protect between
moving gate and RIGID objects, such as posts or walls.
WARNING
18
O P T I O N A L E D G E S E N S O R W I R I N G
®
STRIKE OPENPUSH BUTTONSTRIKE OPEN
PUSH BUTTONFIRE DEPT
KEY SWITCHFIRE DEPT
KEY SWITCH
CLASS 2SUPPLYCLASS 2SUPPLYSAFETY
LOOPSAFETYLOOP
POWER INPUT25 VDC
RADIORECEIVER
RADIORECEIVER
EXITLOOPEXIT
LOOP
– – + +
P/N Q412PATENT PENDING
P/N Q412PATENT PENDINGROBO SURGE SUPPRESSOR
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
7 13 12 11 10 9 8 1 6 5 4 – – – DC DC
Miller Edge Models: MGR20 or MGS20
• Never Paint Sensing Edge
• Never Pull On Wires
• Never Cut or Puncture Edge
• Never Operate Unguarded Equipment
1 4
Contact your local dealer for more information.
To prevent SERIOUS INJURY or DEATH from a moving gate:• Locate entrapment protection devices to protect in BOTH the open and close gate cycles.• Locate entrapment protection devices to protect between moving gate and RIGID objects, such as posts or walls.
WARNING
NOTE: When touched, these electrically activated edge sensors immediately signal the gate operator to stop and reverse. Property owners are obligated to test edges monthly. See page 37 for edge sensor part numbers.
19
IMPORTANT NOTE: The “Optional” input board (Q203) must be used to perform this function.
Cut W1 jumper at the bottom of Board to use the stop button in the 3-button control station.
16 2 4 6 8 10 12 14
15 13 11 9 7 5 3 1
N.C.
W1
1 2
4
8 7
3
16-Pin Plug
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OK
OPE
N
CLO
SE
STO
P
There can be NO common wires within this 3-button control station.
Open-N.O. ContactStop-N.C. ContactClose-N.O. Contact
3 - B U T T O N C O N T R O L S T A T I O N W I R I N G C O N N E C T I O N
To ENSURE proper operation of external devices:• ENSURE bare wires make good contact inside removable
terminal connections.• DO NOT let wire insulation interfere with connection.
CAUTION
20
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OK
OPE
N
CLO
SE
STO
P
NO NO
®
STRIKE OPENPUSH BUTTONSTRIKE OPENPUSH BUTTON
FIRE DEPTKEY SWITCHFIRE DEPT
KEY SWITCH
CLASS 2SUPPLY
CLASS 2SUPPLYSAFETY
LOOPSAFETYLOOP
POWER INPUT18 VAC
POWER INPUT18 VAC
RADIORECEIVER
RADIORECEIVER
EXITLOOPEXITLOOP
– – + +
P/N Q412PATENT PENDING
P/N Q412PATENT PENDINGROBO SURGE SUPPRESSOR
®
ACCESS SYSTEMS INCACCESS SYSTEMS INCACCESS SYSTEMS INC
7 12 10 9 8 1 6 5 4 – – – AC AC 11 13
There can be NO common wires within this 3-button control station.
The timers MUST be turned OFF on BOTH operators.
16 2 4 6 8 10 12 14
15 13 11 9 7 5 3 1
W1
16 2 4 6 8 10 12 14
15 13 11 9 7 5 3 1
16-Pin Plug 16-Pin Plug
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OK
OPE
N
CLO
SE
STO
P
1
3
+
+
3 Amp Minimum
DPDT12 VDCRelay
+ –
Com
Com
N.O.
N.O.
–
Com Com
7 8
8 7
2
4
Cut W1 jumper at the bottom of each board to use the stop button in the 3-button control station
– 13 11
Open-N.O. ContactStop-N.C. ContactClose-N.O. Contact
3 - B U T T O N C O N T R O L S T A T I O N W I R I N G M A S T E R / S E C O N D A R Y
To ENSURE proper operation of external devices:• ENSURE bare wires make good contact inside removable
terminal connections.• DO NOT let wire insulation interfere with connection.
CAUTIONIMPORTANT NOTE: The “Optional” input board (Q203) must be used to perform this function. A 12 VDC Double Pull Double Throw (DPDT) 3 Amp Minimum Relay must be used (not provided).
21
S I N G L E O P E R A T O R L O O P S I Z E A N D P L A C E M E N T
It is VERY important to have enough separation between loops and gates to prevent false detection.
If A = Then C =
6 Feet
4 Feet
9 Feet
4.5 Feet
12 Feet
5 Feet
15 Feet
5 Feet
18 Feet
5.5 Feet
21 Feet
6 Feet
This is for a typical single Robo Slide loop installation. Individual circumstances may alter dimensions.
Maximum gate length for Robo Slide is 20 Feet.
As A increases in size to cover a larger gate opening, the gate will cause a larger change of inductance when opening and closing. Therefore dimension C must increase as A increases.
If the Inside and outside safety loop are connected to the same loop detector they should be series connected. Dimension A, B and C should be the same for each loop. Both loops should have the same number of turns of wire.
Dimension D should be equal to or greater than the larger of the “Inside Safety Loop” or “Exit Loop's” dimension B.
Out
In
Inside Safety Loop
Outside Safety Loop
Exit Loop A
B B B
C C D
Drawing not to scale
4 Feet
To AVOID damaging control board, disconnect all power to operator BEFORE installing plug-in loop detectors.Use a different frequency for every loop detector installed.
CAUTION
22
M A S T E R / S E C O N D A R Y L O O P S I Z E A N D P L A C E M E N T
If A =Then C =
6 Feet
4 Feet
9 Feet
4.5 Feet
12 Feet
5 Feet
15 Feet
5 Feet
18 Feet
5.5 Feet
28 Feet
6 Feet
Maximum gate length for each Robo Slide is 20 Feet.
As A increases in size to cover a larger gate opening, the gate will cause a larger change of inductance when opening and closing. Therefore dimension C must increase as A increases.
If the Inside and outside safety loop are connected to the same loop detector they should be series connected. Dimension A, B and C should be the same for each loop. Both loops should have the same number of turns of wire.
Dimension D should be equal to or greater than the larger of the “Inside Safety Loop” or “Exit Loop's” dimension B.
It is VERY important to have enough separation between loops and gates to prevent false detection.
Out
In InsideSafetyLoop
OutsideSafetyLoop
ExitLoop A
BB B
D CC
Drawing not to scale
This is for a typical master/secondary loop installation. Individual circumstances may alter dimensions.
4 Feet
To AVOID damaging control board, disconnect all power to operator BEFORE installing plug-in loop detectors.Use a different frequency for every loop detector installed.
CAUTION
Min 1"
EXITLOOP
INSIDESAFETYLOOP
OUTSIDE
SAFETY LOOP
Inside
Property
Outside
Property
P/N Q410 Patent Pending
P/N Q410 Patent Pending
Strike OpenPush ButtonStrike OpenPush Button 24 Volts DC24 Volts DC
Fire DeptKey SwitchFire Dept
Key SwitchM/S LinkM/S Link
P/N 001C6064Patent PendingP/N 001C6064Patent Pending
Class 2SupplyClass 2Supply
CenterLoop
CenterLoop
SafetyLoop
SafetyLoop
RadioReceiver
RadioReceiver
ExitLoopExitLoop
GG BB AA
–– ++
Robo-UL Surge Suppressor®
7 12 10 9 8 1 6 5 4 3 2
11 13
11 13
G A B 13 11
+
5 6
3 4
–
12 VDC External “Safety” Loop Detector - Allows gate to stay open when vehicles are obstructing path. Caution: Suggested for vehicles 14 feet or longer.If the “Inside” and “Outside” safety loops are connected to the same loop detector: • They should be series connected to the detector. • Have the same dimensions. • Have the same number of wire turns (See table below).
12 VDC External “Exit” Loop Detector - Allows gate to automatically open forexiting vehicles.
Part # A23(Sold Individually)
10 feet to 13 feet14 feet to 26 feet27 feet to 80 feet
80 feet and up
4321
The wire is continuously wound in the loop saw cut for the required number of turns. One turn shown. (Refer to table)
Recommended Loop Wire XLPE 12-18 gauge(Use heavier wire gauge for a more durable loop area).
Remove sharp inside corners by making corner cuts
The wire MUST be twisted together 6 twists per foot from the end of the feeder slot to the loop detector.
Loop Perimeter
Number of Wire Turns Needed for Loop SizesNumber of Wire Turns
Road Surface
Sealant
Feeder Slot
Saw Cut
1/8" to 1/4" Width Saw Cut
2" to 2.5" DepthSaw Cut
Home Run
Backer Rod
Insulated loop wire3 turns shown, amount varies.
Refer to table
NOTE: Wire mesh or reinforcement imbedded in the road surface should be cut away a minimum of 6 inches from the perimeter of the loop wires.
Installing Insulated Loop Wire
NOTE: Refer to the 12 VDC loop detector manual for more specific information.
2323
1 2 V D C E X T E R N A L L O O P D E T E C T O R W I R I N G
24
OUT
IN
Open to Right
Open to Left
Socket 1
Socket 2
OVERLOAD
POWER
CHARGE OK
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
W1
OFF
OPEN TO RIGHT
Socket 1 Socket 2
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
OPE
N
CLO
SE
STO
P
ACCESS SYSTEMS INC
ACCESS SYSTEMS INC
ACCESS SYSTEMS INC
ACCESS SYSTEMS INC
OUT
IN
Plug in the motor harness wires to the left (Socket 1) if your gate, from the inside of the property, opens to the left. Plug into the right (Socket 2) if the gate opens to the right.
G A T E M O V E M E N T D I R E C T I O N
Adjustments
2525
Limit Switches
TIMER
ON 60 0
TIMER
OFF
L I M I T S W I T C H A D J U S T M E N T S
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMER UP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5M MADE IN USA
ALARM SENSOR
REVERSE SENSOR
HEAVY GATE
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CHARGING POWER
BOARD POWER
CHECK FUSE
J2
CHARGE OK
OPE
N
CLO
SE
STO
P
TIMER TIMER UP
ON ON
OFF
60 60 0 0
PW
CLO
SE
STO
P
Set Timer 0 to 60 seconds
TIMERTIMER UP
ON
OFFOFF
60 0
PW
CLO
SEST
OP
S E T T I N G T I M E R
Push and hold lock plate to release limit nuts. Roll limit nuts to adjust the open and close limit switches.
Each notch is an estimated one inch of gate travel.
To use the automatic close for the gate system the timer switch should be put in the “ON” position.
To use the push close command, the timer should be switched to the “OFF” position.
To reduce the risk of SERIOUS INJURY or DEATH:Disconnect power BEFORE performing ANY adjustments.
CAUTION
26
M A S T E R A N D S E C O N D A R Y W I T H T I M E R
To use the master/secondary option with Robo Slide, you must purchase the Optional Input Board (Elite Part # Q203) and connect it to the J2 slot of each operator (Refer to page 15).
1 3
5 7 9 11 13 15
10 8
6 4
2
12 14 16 16 14 12 10
8 6 4
2
15 13 11 9
7 5 3
Master J2 Plug 1. Make master/secondary J2 plug connections as shown above
2. Turn timers on BOTH control boards to the “ON” position
3. Use MASTER timer ONLY for the auto close time adjustment (0 to 60 sec)
4. Turn the SECONDARY timer adjustment all the way Counterclockwise
Secondary J2 Plug Master Pin 1 to Secondary Pin 1
Master Pin 5 to Secondary Pin 7
Master Pin 6 to Secondary Pin 8
Master Pin 2 to Secondary Pin 2
25 VDC plug-in transformer, per gate operator required
1
TIMER TIMER UP
ON ON
OFF
60 60 0 0
PW
Master Timer “ON”
Master Secondary
TIMER TIMER UP
ON ON
OFF
60 0
PW
Secondary Timer “ON”
Maximum Counterclockwise
Setting
CLO
SE
STO
P
CLO
SE
STO
P
Set Timer 0 to 60 seconds
Run low voltage 16-18 gauge wire in UL approved conduit to connect operators together.Never run high voltage and low voltage wires in same conduit.
NOTE: Disconnect the second radio receiver when using a master/second setup.
27
M A S T E R A N D S E C O N D A R Y W I T H O U T T I M E R
To use the master/secondary option with Robo Slide, you must purchase the Optional Input Board (Part # Q203) and connect it to the J2 slot of each operator (Refer to page 15).
1 3 5 7 9 11 13 15
10 8 4 6
2
12 14 16 16 14 12 10 6 8 4
2
15 13 11 9 5 7 3
Master J2 Plug
1. Make master/secondary J2 plug connections as shown above
2. Turn timers on BOTH control boards to the “OFF” position
Secondary J2 Plug Master Pin 1 to Secondary Pin 1
Master Pin 2 to Secondary Pin 2
25 VDC plug-in transformer, per gate operator required
1
Master Timer “OFF” Secondary Timer “OFF”
TIMER TIMER UP
ON
OFF OFF
60 0
PW TIMER TIMER UP
ON
OFF OFF
60 0
PW
CLO
SE
STO
P
CLO
SE
STO
P
Master Secondary
Run low voltage 16-18 gauge wire in UL approved conduit to connect operators together.
Never run high voltage and low voltage wires in same conduit.
2828
3 1 5 M H Z R A D I O R E C E I V E R P R O G R A M M I N G
HIGH
NORM HIGH
NORM
MC
MC
Setting Security Mode (High) or (Normal):
Setting Output Duration (M) or (C):
P4P2
Changing security from High to Normal.
Changing output duration from Momentary to Constant.
The receiver is factory set at HIGH security mode. To verify, refer to the label next to jumper P4. (See illustration below)The Receiver can be used with up to 15 rolling code remotes or passwords in HIGH security mode. Alternately, it can be used with up to 31 of any type remote in NORMAL security mode, including any combination of rolling code, billion code, or dip switch remotes.When changing from NORMAL to HIGH security mode, all previous remote control codes must be erased. See next page to erase and reprogram remote controls that are being used.
The receiver is factory set at (M) Momentary. To verify, refer to the label next to jumper P2. (See illustration above)For commercial applications, the receiver can be set to either (C) constant or (M) momentary closure.With the jumper in the (M) momentary position, the contacts will close for 1/4 second regardless of the length of remote control transmission. With the jumper in (C) constant position, the contacts will stay closed as long as the remote control continues transmitting. Push and HOLD remote button to open or close gate.
To reduce the risk of SERIOUS INJURY or DEATH from a moving gate:• ALWAYS keep remote controls out of reach of children. NEVER permit children to operate, or play with remote control.• Activate gate ONLY when it can be seen clearly, is properly adjusted, and there are no obstructions in gate’s path.• ALWAYS keep gate in sight until completely closed. NEVER permit anyone to cross path of a moving gate.
WARNING
To AVOID damaging receiver, disconnect receiver’s power before changing jumpers.
CAUTION
To reduce the risk of SERIOUS INJURY or DEATH, the use of CONSTANT OPERATION on residential operators is PROHIBITED.
WARNING
29
3 1 5 M H Z R A D I O R E C E I V E R P R O G R A M M I N G
Optional 315 MHz Hand Held Remotes
Part # 371LM
LearnButton
Part # 372LM
Part # 373LM
Part # 374LM
Mini 3 ButtonPart # 370LM
IMPORTANT: Hand Held Remote NOT provided.
NOTE: Receiver wiring on page 11. Disconnect the second receiver when using a master/second setup.
Programming Radio Receiver:1. Press and release the “Learn ” button on the receiver. The learn indicator light will glow steadily for 30 seconds.
2. Within 30 seconds, press and hold the button on the hand-held remote. The operator will now operate when the push button on the remote control is pressed. Repeat Steps 1 and 2 for each remote control that will be used.
Erase ALL Remote Control Codes:Press and hold the “Learn ” button on the receiver panel until the indicator light turns off (about 6 seconds). All previous codes are now erased. Reprogram each remote you wish to use.
Part # CPT13
Part # CPT23
Part # CPT33
Part # CPT43
Mini 3 ButtonPart # CPTK33
Mini 3 Button with HID Prox, SensorPart # CPTK33PH
NOTICE: To comply with FCC and or Industry Canada (IC) rules, adjustment or modifications of this receiver and/or transmitter are prohibited, except for changing the code setting or replacing the battery. THERE ARE NO OTHER USER SERVICEABLE PARTS.Tested to Comply with FCC Standards FOR HOME OR OFFICE USE. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
30
T W O - W A Y A D J U S T A B L E R E V E R S I N G S E N S O R
NOW YOUR INSTALLATION IS COMPLETE
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMERUP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5MMADE IN USA
ALARMSENSOR
REVERSESENSOR
HEAVYGATE
FIREDEPT
OPE
NC
LOSE
STO
P
STRIKEOPEN
SAFETYLOOP
EXITLOOP
RADIOREC
CHARGINGPOWER
BOARDPOWER
CHECKFUSE
J2
CHARGE OK
SYSTEM ON
ALARMSENSOR
REVERSEREVERSESENSORSENSOR
HEAVYGATE
Maximum Sensitivity
Minimum Sensitivity
There is a “Heavy Gate” LED which will light up when the gate is heavier than normal. This is a diagnostic LED and the operator will still function normally when this indicator is on.
Important Note!
The level of reverse sensitivity depends on the weight of the gate and the condition of installation.
Sensor is set too sensitive = if the gate stops in midcycle or reverses by itself.
Sensor is not set sensitive enough = if the gate hits an object and does not stop or reverse.
Adjust the “Reverse Sensor” on the control board. Alarm Sensor does not need to be adjusted except where noted below.
31
1. Disconnect power before servicing.2. The gate area should be kept clean to insure proper
operation.3. Make sure the reversing sensor is functioning properly.
Check it monthly (Page 30).4. Make sure the gate track is clear of dirt, rocks or other
substances.5. Make sure the wheels are operating smoothly on the track.6. Oil the chain regularly with a chain lubrication oil available at
most motorcycle stores.7. Replace blown fuses ONLY with sizes specified (Page 34).8. Check for proper synthetic oil level in the gear box.
(10W-30 weight synthetic oil).
9. Severe or high cycle usage will require more frequent maintenance checks.10. Inspection and service should always be performed anytime a malfunction is observed or suspected.11. When servicing, please do some “house cleaning” of the operator and the area around the operator. Pick up any debris in the area. Clean the operator as needed.12. It is suggested that while at the site voltage readings be taken at the operator. Using a Digital Voltmeter, verify that the incoming voltage to the operator it is within ten percent of the operators rating.
IMPORTANT SAFETY INSTRUCTIONS
To reduce the risk of SEVERE INJURY or DEATH:1. READ AND FOLLOW ALL INSTRUCTIONS.2. NEVER let children operate or play with gate controls.
Keep the remote control away from children.3. ALWAYS keep people and objects away from the gate.
NO ONE SHOULD CROSS THE PATH OF THE MOVING GATE.
4. Test the gate operator monthly. The gate MUST reverse on contact with a rigid object or stop when an object activates the non-contact sensors. After adjusting the force or the limit of travel, retest the gate operator. Failure to adjust and retest the gate operator properly can increase the risk of INJURY or DEATH.
5. Use the emergency release ONLY when the gate isnot moving.
6. KEEP GATES PROPERLY MAINTAINED. Read the owner’s manual. Have a qualified service person make repairs to gate hardware.
7. The entrance is for vehicles ONLY. Pedestrians MUST use separate entrance.
8. Disconnect ALL power BEFORE performing ANY maintenance.
9. ALL maintenance MUST be performed by a Chamberlain professional.
10. SAVE THESE INSTRUCTIONS.
WARNING
Operation and Maintenance
To reduce the risk of FIRE or INJURY to persons use ONLY Chamberlain part # ABT12 for replacement battery.
CAUTION
32
Power at all times when there is one or more power sourcesie: Battery, 25 VDC or solar
Charger OK on when there is any charging powerie: 25 VDC - solar
Battery Low normally off - it will indicate low battery
System On will work only when the gate is in motion
Alarm Sensor when LED goes on you will hear a “beep” sound for about 20 seconds
Heavy Gate will work only when the gate is in motion
Open Relay Open relay is not energized
1. No power source at all If dimmed down 1. Bad board power fuse
1. No Transformer or Solar If dimmed down 1. Bad Charging power fuse
1. Motor stop 2. No motor current detected
Battery OK Battery voltage is over minimum required limit
Gate weight and condition are OK
System is OK
Open relay is energized
Flashing LED - Battery is less than required limit needs to be recharged
Power source OK and board power fuse OK
Transformer or solar OK and charging power fuse OK
1. Excess usage 2. Bad charging system 3. Under rate solar panel 4. Bad battery 5. Bad battery connection
1. Hearing beep sound means overload 2. Gate is too heavy 3. Broken wheel 4. Gate off track 5. Unwanted object has physically stopped gate
1. Gate is too heavy 2. Bad wheels 3. Bad rollers 4. Chain is too tight 5. Steep slope on open or close cycle 6. Low battery
Close Relay Close relay is not energized Close relay is energized
Detecting motor current
NOTE: Circled red numbers indicates location on control board, identified on page 10.
1 1
2 2
3 3
5 5
6 6
7 7
8 8
4 4
LED Description LED On LED Off
LED will flash 3 times for “board OK” during power connection.
L E D D E S C R I P T I O N
33
LED Description LED On LED Off
NOTE: Circled red numbers indicates location on control board, identified on page 10.
9 9 Reversing Sensor No obstruction is detected Sensor is detecting obstruction
11 11 Fire Dept
10 10 Central Control
12 12 Strike Open
13 13 Safety Loop
14 14 Exit Loop
15 15 Radio Rec
17 17 Timer UP
16 16 Timer PW
Receiving signal at the surge suppressor terminal block 7 & 8
Receiving signal at the surge suppressor terminal block 9 & 10
Receiving signal at the surge suppressor terminal block 1 & 4
Receiving signal at the surge suppressor terminal block 5 & 6
Receiving signal at the surge suppressor terminal block 11 & 12
Not receiving signal at the surge suppressor terminal block 7 & 8
Not receiving any command
Acknowledgement of receiving open command from one of the surge suppressor terminals
• Fire Department 7 & 8 • Strike Open 9 & 10 • Safety Loop 1 & 4 • Exit Loop 5 & 6 • Radio Receiver 11 & 12
Not receiving signal at the surge suppressor terminal block 9 & 10
Not receiving signal at the surge suppressor terminal block 1 & 4
Not receiving signal at the surge suppressor terminal block 5 & 6
Not receiving signal at the surge suppressor terminal block 11 & 12
Output signal to close relay Not receiving signal to close relay
Timer power is on Timer is not on
L E D D E S C R I P T I O N - C O N T I N U E D
34
OVERLOAD
POWER
BATTERY LOW
OPEN RELAY
CLOSE RELAY
DC OPE MAD
HEAVY GATE
CHARGING POWER
BOARD POWER
CHECK CHECK FUSE FUSE
J2
CHARGE OK
OPEN TO RIGHT
If the gate is not moving in any direction be sure to check all of the LED displays on the control board. If the board power or charging power LEDs are “ON”, change the corresponding fuse on the top left corner of the board.
The breaker reset is located at the bottom left corner of the control board as shown
Replace fuse with 1.5A - 250V fuse
(Part # Q162)Robo Fuse
H O W T O R E S E T T H E B R E A K E R
H O W T O C H E C K T H E F U S E S
To prevent SERIOUS INJURY or DEATH from a moving gate:ALWAYS disconnect the battery before resetting the breaker or injury could occur as the gate starts.
WARNING
.
If all electronic sensors fail or are not adjusted properly due to heavy gates, off-track gate, or obstructed gate path, the breaker will kick-out. Reset the breaker by pressing the reset button located on the bottom left corner of the control board.
To AVOID damaging the control board, replace fuses ONLY with same type and rating specified above.
CAUTION
35
0
PW
CENTRAL CONTROL
DC OPERATOR v 5M MADE IN USA
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CLO
SE
STO
P
0
PW
CENTRAL CONTROL
DC OPERATOR v 5M MADE IN USA
FIRE DEPT
STRIKE OPEN
SAFETY LOOP
EXIT LOOP
RADIO REC
CLO
SE
STO
P
Symptom: The radio receiver LED on the control board remains “ON” when using the remote control. Possible Solutions: Stuck remote control button. The radio receiver has malfunctioned in the “ON” position.
Symptom: The radio receiver LED on the control board remains “OFF” when using the remote control. Possible Solutions: Dead battery in the remote control. Remote control code switches are different from radio receiver code switches. The radio receiver has malfunctioned in the “OFF” position.
For further information, contact your local dealer.
T H E G A T E W I L L N O T C L O S E
T H E G A T E W I L L N O T O P E N
Troubleshooting
36
After fixing the problem, the Robo Slide will automatically reset itself.
The gate is hitting a wall or vehicle.
The gate has one or more broken wheels. The gate is off the track.
Debris is on the gate's track such as mud, rocks, dirt, etc.
The gate is TOO Heavy. ALARM SENSOR
ALARM SENSOR
ALARM SENSOR
ALARM SENSOR
ALARM SENSOR
I F Y O U H E A R A B E E P S O U N D
37
Stop ButttonPart # AEXITP
Solar Panel(UL Listed Class 2 Output)Part # SOLAR3
12 VDC External Loop DetectorsPart # A23
Plug-In Loop DetectorsPart # AELD
Magnetic Locks (Outdoor)
Part # MG1300
3-Button Control StationPart # 02103
12 VDC Photo SensorPart # AOMRON12V
Remote Controls4 inch
4 inch5 inch 5 inch6 inch
6 inch
V-Groove Power Wheels Series Brackets
UL Approved Round Sensing EdgePart # G65MGR20xx = length (4, 5, 6 ,8 ft)(e.g. G65MGR206 is 6 ft)
UL Approved Square Sensing EdgePart # G65MGS20xx = length (4, 5, 6 ,8 ft)(e.g. G65MGS204 is 4 ft)
Accessories
25 Vdc TransformerPart # APOW1 For more information about accessories:
www.chamberlain.com
38
R O B O S L I D E P A R T S
OVERLOAD
POWER
CHARGE OK
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMERUP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5MMADE IN USA
ALARMSENSOR
REVERSESENSOR
HEAVYGATE
FIREDEPT
STRIKEOPEN
SAFETYLOOP
EXITLOOP
RADIOREC
CHARGINGPOWER
BOARDPOWER
CHECKFUSE
J2
OPE
NC
LOSE
STO
P
NOTE: *Sold individually, 2 shown.For part list, refer to next page.
Q241
*Q004
*Q003
Q006
Q162
Q203
Q206
Q214
Q206
BatteryHarness
Q205Robo SW/SL Conversion Kit
Q134
Q133
Q132
Q131
Q412
Q214
Q212
Q180
Q123
*Q129
Q124
ABT12
AH110#41
AH113 AH125
AH111#40
*Q029
Q137
Q135
Q156 *Q032
*Q101
POWER INPUT
18 VAC
SAFETYLOOP
EXITLOOP
FIRE DEPT
KEY SWITCHSTRIKE OPEN
PUSH BUTTONRADIO
RECEIVER
CLASS 2
SUPPLY
Q412
POWER INPUT
18 VAC
SAFETYLOOP
EXITLOOP
FIRE DEPT
KEY SWITCHSTRIKE OPEN
PUSH BUTTONRADIO
RECEIVER
CLASS 2
SUPPLY
OVERLOAD
POWER
CHARGE OK
BATTERY LOW
OPEN RELAY
CLOSE RELAY
TIMERUP
ON
W1
OFF
OPEN TO RIGHT
60 0
PW
CENTRAL CONTROL
SYSTEM ON
DC OPERATOR v 5MMADE IN USA
ALARMSENSOR
REVERSESENSOR
HEAVYGATE
FIREDEPT
STRIKEOPEN
SAFETYLOOP
EXITLOOP
RADIOREC
CHARGINGPOWER
BOARDPOWER
CHECKFUSE
J2
OPE
NC
LOSE
STO
P
Repair Parts
39
Multiple Parts “Q” Number
ABT12 - 12 VDC, 7 amp. Battery with HarnessAH110 - Gate Chain #41 (10 ft) (20 ft included)AH111 - Gate Chain #40 (10 ft) OptionalAH113 - Master Link #41AH125 - Master Link #40APOW1 - 25VDC 1.6A Q003 - Chain BoltQ004 - Chain BracketQ006 - PC Board Nuts (1 Set)Q029 - Limit SwitchQ032 - Limit Switch Adjustment NutQ101 - Limit Switch Bearing HolderQ123 - Motor - DC - 12V
Robo SW / SL Conversion Kit
Q205
Q211 - Limit/Motor HarnessQ412 - Surge Suppressor TerminalQ206 - Control BoardBattery Harness
Q124 - Chassis - Robo SlideQ129 - Idler Sprocket with Bolt/NutQ131 - Limit Switch Drive SprocketQ132 - Limit Switch SprocketQ133 - Drive SprocketQ135 - Limit Switch Bolt (Shaft)Q137 - Limit Switch BoxQ156 - 1/2 Inch CollarQ162 - FuseQ180 - 1 inch Diameter CouplingQ203 - Option Board with HarnessQ206 - Control BoardQ212 - Gear Reducer 40 - 30:1Q214 - Limit/Motor HarnessQ241 - Cover, Polyethylene Robo SlideQ412 - Surge Suppressor Terminal
P A R T S L I S T
OUR LARGE SERVICE ORGANIZATION SPANS AMERICA. INSTALLATION AND SERVICE INFORMATION IS AS NEAR AS YOUR TELEPHONE. SIMPLY DIAL OUR TOLL FREE NUMBER:
1-800-528-2806
H O W T O O R D E R R E P A I R P A R T S
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE FOLLOWING INFORMATION: • PART NUMBER • PART NAME • MODEL NUMBER
Address orders to:THE CHAMBERLAIN GROUP, INC.
Technical Support Group6050 S. Country Club Road
Tucson, Arizona 85706
40
1. Owner and Installer must read all warnings and safety precautions (Pages 2-7).
2. Make sure concrete mounting pad is big enough and deep enough for operator (Page 8).
3. Operator must be securely fastened to concrete pad (Page 8).
4. Operator chain must be 4 inch Minimum from gate. Chain must not be too tight or too loose (Page 8).
5. Gate operator should be grounded to an earth ground rod within 3 feet (Page 9).
6. Verify that both the battery and plug-in transformer are connected properly. Know where the main power disconnect plug is to disconnect all power to operator (Page 12).
7. Verify that the gate opens and closes as needed (Page 24 & 25).
8. When gate hits object during operation, it must stop or reverse, depending on the direction gate is traveling (Page 30).
9. Make sure that any pinch point or potential entrapment are guarded by means of safety devices or like (Pages 2, 4, 5).
10. Warning placards need to be permanently mounted on both sides of gate (Page 6).
11. Test all additional equipment connected to operator.
12. Make sure all wire connections are securely fastened.
13. Review typical maintenance on operator (Page 31).
14. Schedule periodic maintenance on operator by qualified service technician.
15. Inquire about Manufacturers “operator warranty”. (Warranty Card Included with operator)
16. Inquire about separate “installation warranty” with installer.
Installer Company Name, Address and Phone Number
Installation Checklist
Date of installation:
© 2008, The Chamberlain Group, Inc. – All Rights Reserved01-50528B
A T T E N T I O N
In order to reduce any severe injuries, Chamberlain professional Products recommends the electric gate be either; covered with a mesh or installed in such a way which to prevent small children or any other persons from being able to stand, hang or climb on the electric gate.
WARNING SIGNUse a warning sign on gate to prevent injury to children.
POWER WHEELS These wheels are the best choice
for high trafic sliding applications.
F E A T U R E S A N D S P E C I F I C A T I O N S
We suggest the following items manufactured by Chamberlain Professional Products for better and safer operations.