hydrogen sulfide detector-transmitter e2608-h2s 0 · re2 (high): set 20; release16 ppm for 0...2000...
TRANSCRIPT
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation
Hydrogen SulfideDetector-TransmitterE2608-H2S
Features
Wall-mount or duct-mount version
Industrial IP65 housing
Two relays for alarm / ventilation control
Two analog outputs settable to 4-20 mA or 0-10 V
RS485 Modbus RTU digital interface
Attached or remote sensor
Specifications
Calibration Hydrogen Sulfide H2S
Sensing method Electrochemical cell
Sampling method Diffusion
Typical detection range 0...100 ppm 0...2000 ppmMaximum overload 500 ppm ndResolution 0,1 ppm 2 ppmResponse time T90 < 30 seconds < 25 secondsOutput scale 0-1000 0-1000Operating temperature -30...+50 °C -40...+50 °C
Signal update every 1 second
Response time < 30 seconds
Maintenance interval 6 months
Sensor lifetime > 2 years
Self-diagnostics Full functionality check at start-up
Warm-up time ≤ 1 min
Power supply 11...30 VDC or 90...265 VAC
Power consumption < 2 VA
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays 2 × SPST relays (closing contact),250 VAC / 30 VDC, 5 A max
Default alarm set-points for 0...100 ppm range:RE1 (LOW): set 10; release 8 ppmRE2 (HIGH): set 20; release16 ppmfor 0...2000 ppm range:defined by user
Enclosure Light grey ABS plastic, wall mount,protection class IP65
Dimensions H85 × W82 × D55 mm
Remote sensor probe protection IP65,shielded cabledefault cable length 3.0 m
Operating environment industrial indoor and outdoor locations
Operating conditions 15...90 %RH,atmospheric pressure ±10%; non ATEX rated areas
Ask for other versions or custom designed products
0
Wall mount version
Duct mount version
Remote probe
Connection diagram
4-20 mA/0-10 V4-20 mA/0-10 V
0V / GND
OUT1OUT20VAB
RS485
+U = 11.. .30 VDC
RE1
RE2
Fieldbus
24VDC
S
NL 90...265 VAC
J2 - OUT2 typeJ1 - OUT1 type
J3 - return to factory sett ings
Cont rol LED
J1 J2
5520
0
M16
Ø35
203
M25
35
8287
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation
Hydrogen Sulfide DetectorE2613-H2S
FeaturesMaintenance free sensor
SPDT relay for alarm / ventilation control
Range of compact wall mount enclosures
Low cost for volume HVAC applications
Specifications
Sensor type Electrochemical
Sampling method Diffusion
Detection range 0-10 / 0-50 ppm
Sensor protection Microporous PTFE dust filter
Warm-up time ≤ 1 min
Typical response time ≤ 30 s
Relay output switch-over contact (SPDT),250 VAC / 30 VDC, 5 A max
Power supply 12...30 VDC
Power consumption < 1 W
Sensor lifetime < 2 years
Indoors enclosure White, ivory or black ABS plastic,option -IP20 wall mount, protection class IP20
Weatherproof enclosure Light or dark grey ABS plastic,option -IP65 wall mount, protection class IP65
for IP20 enclosure: no condensation
Operating conditions -30 to 50 C (-20 to 40 C continuous);0 to 100% RH (15 to 95% continuous)atmospheric pressure ±10%
EMC Emissions to EN 61000-6-3, EN 61326-1
EMC Immunity to EN 61000-6-1, EN 61000-6-2
NOTE: The sensor may ehxibit considerable sensitivity to SO2, O3, NO,NO2, Cl2
IP20 orIP65
0
Ask for other versions or custom designed products
IP20 Enclosure
IP65 Enclosure
52
50
70
36
70
52
50
66
80
36
2771
71
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation
Hydrogen Sulfide TransmitterE2615-H2S
FeaturesMaintenance free sensor
User selectable output 4-20 mA / 0-10 V
Range of compact wall mount enclosures
Low cost for volume HVAC applications
Specifications
Sensor type Electrochemical
Sampling method Diffusion
Detection range 0-10 / 0-50 ppm
Sensor protection Microporous PTFE dust filter
Warm-up time ≤ 1 min
Typical response time ≤ 30 s
Analog output 4-20 mA / 0-10 V, user settable
Power supply 12...30 VDC
Power consumption < 1 W
Sensor lifetime < 2 years
Indoors enclosure White, ivory or black ABS plastic,option -IP20 wall mount, protection class IP20
Weatherproof enclosure Light or dark grey ABS plastic,option -IP65 wall mount, protection class IP65
for IP20 enclosure: no condensation
Operating conditions -30 to 50 C (-20 to 40 C continuous);0 to 100% RH (15 to 95% continuous)atmospheric pressure ±10%
EMC Emissions to EN 61000-6-3, EN 61326-1
EMC Immunity to EN 61000-6-1, EN 61000-6-2
NOTE: The sensor may ehxibit considerable sensitivity to SO2, O3, NO,NO2, Cl2
4-20 mAor 0-10 V
IP20 orIP65
0
Ask for other versions or custom designed products
IP20 Enclosure
IP65 Enclosure
2771
71
+UOUT0V
+24V0V
E2615Power Supply
+-
Controller
100...250 Ohm
4-20 mA
+UOUT0V
+24V0V
E2615Power Supply
+-
Controller
>250 kOhm
0/2-10 V
Two-wire current loop connection
Three-wire voltage output connection
52
50
70
36
70
52
50
66
80
36
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation
Hydrogen Sulfide TransmitterE2618-H2S
FeaturesAccurate and stable measurement
Wall mount or duct-mount robust enclosure
Remote probe option
Two analog outputs settable to 4-20 mA or 0-10 V
RS485 Modbus RTU digital interface
LCD indicator option
Specifications
Calibration Hydrogen Sulfide H2S
Sensor type Electrochemical cell
Sampling method Diffusion
Typical detection range 0...100 ppm 0...2000 ppmMaximum overload 500 ppm ndResolution 0,1 ppm 2 ppmResponse time T90 < 30 seconds < 25 secondsOutput scale 0-1000 0-1000Operating temperature -30...+50 °C -40...+50 °CSignal update every 1 second
Maintenance interval 12 months
Sensor lifetime > 2 years
Self-diagnostics Full functionality check at start-up
Warm-up time ≤ 1 min
Power supply 11...30 VDC / 24 VAC
Power consumption < 2 VA
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Enclosure Light grey ABS plastic,protection class IP65
Dimensions H82 × W80 × D55 mm
Remote sensor probe Protection IP65,shielded cabledefault cable length 3.0 m
Operating environment Industrial indoor and outdoor areas
Operating conditions 15...90 %RH,atmospheric pressure ±10%; non ATEX rated areas
LCD indicator optionOperating temperature 0...+50 °C,Display dimensions 72 × 36 mmNumber of digits 3.5 7-segmentCharacter height 14 mmOther features Backlight
55200Ø28203
M2534
50
Ø4 mm
55 80
130
8 2
M25
70
0
Wall-mount version
Duct-mount version
Connection diagram
Remote probe
36
77
Ø35...36 Ø50
120°
Ø65
80 327
Ø34 max
Hole
35
200
M1680
Ø35
203
M25
35
82
55
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation Revision 12.12.2018
Hydrogen Sulfide Detector-TransmitterE2638-H2S
FeaturesAccurate and stable measurement
Easy to install robust enclosure
Remote probe option
Two analog outputs settable to 4-20 mA or 0-10 V
RS485 Modbus RTU digital interface
Relay option
LCD indicator option
Specifications
Calibration Hydrogen Sulfide H2S
Sensor type Electrochemical cell
Sampling method Diffusion
Typical detection range 0...100 ppm 0...2000 ppmMaximum overload 500 ppm ndResolution 0,1 ppm 2 ppmResponse time T90 < 30 seconds < 25 secondsOutput scale 0-1000 0-1000Operating conditions -30...+50 °C -40...+50 °C
Signal update Every 1 second
Maintenance interval 6 months
Sensor lifetime > 2 years
Self-diagnostics Full functionality check at start-up
Warm-up time ≤ 1 min
Power supply 11...30 VDC / 24 VAC
Power consumption < 2 VA
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Enclosure Grey ABS plastic,protection class IP65
Dimensions H90 × W145 × D55 mmH140 with cable glands
Operating environment Industrial indoor and outdoor areas
Operating conditions 15...90 %RH,atmospheric pressure ±10%;non ATEX rated areas
RS485Modbus
4-20 mA0-10 VIP65
0
LCDindicator
option
145
115
90 65
~14
0
55130
E2638
30 M 61
M25
Dimensions
Connection diagram
OUT1OUT20VAB+U
J3
J1 J2
Fieldbus
Controller
SupplyPower
Control LED
Input 1 4-20 mA / 0-10 VInput 4-20 mA / 0-10 V2
0V / GND
0V
+24V
J1: OUT1 type (open: 4-20 mA; closed: 0-10 V)J : OUT type2 2 (open: 4-20 mA; closed: 0-10 V)J : 3 return to factory settings
SENSOR
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation Revision 12.12.2018
Additional options
Remote sensor probe Protection IP65,shielded cabledefault cable length 3.0 m
Relay outputs
Output relays 2 × SPST relays (closing contact),250 VAC / 30 VDC, 5 A max
Default alarm set-points for 0...100 ppm range:RE1 (LOW): set 10; release 8 ppmRE2 (HIGH): set 20; release16 ppmfor 0...2000 ppm range:defined by user
Visual alarm Red and green LEDs (option)
Acoustic alarm Buzzer 85 dB (option)
Power supply mains 90...265 VAC power unit(option)
LCD indicatorOperating temperature 0...+50 °C,Display dimensions 72 × 36 mmNumber of digits 3.5 7-segmentCharacter height 14 mmOther features BacklightNote: only one analog output is available for a version with LCD
35
36
77
80Ø
65
3
Ø 3 5 ...3 6 Ø50
120°
27
Ø34 m ax
Hole
Remote probe
Connection diagram for relay version
4-20 mA / 0-10 V4-20 mA / 0-10 V
0V / GND
OUT1OUT20VAB
RS485
+U = 11...30 VDC
RE 1
RE2
Fie ldbus
24 VDC
S
NL
90...265 VAC
J 3
Control LED
J1 J 2
J1: OUT1 type (open: 4-20 mA; closed: 0-10 V)J : OUT type2 2 (open: 4-20 mA; closed: 0-10 V)J : 3 return to factory settings
LCD indicator option
Evikon MCI OÜ • Teaduspargi 7, Tartu, 50411 Estonia • Tel +372 7336310 • [email protected] • www.evikon.eu
Sensor TechnologiesMeasurement & Control Instrumentation
Hydrogen Sulfide Detector-TransmitterE2648-H2S
FeaturesAccurate and stable measurement
Wall mount robust enclosure
Two analog outputs settable to 4-20 mA or 0-10 V
RS485 Modbus RTU digital interface
Relay option
Remote probe option
Specifications
Calibration Hydrogen Sulfide H2SSensor type Electrochemical cellSampling method Diffusion
Typical detection range 0...100 ppm 0...2000 ppmMaximum overload 500 ppm ndResolution 0,1 ppm 2 ppmResponse time T90 < 30 seconds < 25 secondsOutput scale 0-1000 0-1000Operating temperature -30...+50 °C -40...+50 °CSignal update Every 1 secondMaintenance interval 6 monthsSensor lifetime > 6 yearsSelf-diagnostics Full functionality check at start-upWarm-up time ≤ 1 minPower supply 11...30 VDC / 24 VAC
Option: 90...265 VAC power unitPower consumption < 2 VADigital interface RS485, Modbus RTU protocolAnalog outputs 2 × 4-20 mA / 0-10 V, user settableEnclosure Die-cast aluminium, wall mount,
protection class IP66Dimensions H101 × W101 × D58 mm
(overall H~150 × W101 × D55 mm)Operating environment Industrial indoor and outdoor areasOperating conditions 15...90 %RH,
atmospheric pressure ±10%; non ATEX rated areas
Relay outputs (option)
Output relays 2 × SPST relays (closing contact),250 VAC / 30 VDC, 5 A max
Default alarm set-points for 0...100 ppm range:RE1 (LOW): set 10; release 8 ppmRE2 (HIGH): set 20; release16 ppmfor 0...2000 ppm range:defined by user(within 5-95% of the detection range)
Other options:Remote sensor probe Protection IP65,
shielded cable, default length 3.0 m
55200203 M2534
0
IP66 4-20 mA0-10 V
RS485Modbus
Dimensions
Connection diagrams
Remote probe
30101
M16
M25
58
101
80
79
47
9
OUT1OUT20VAB+U
J3
J1 J2
Fieldbus
Controller
SupplyPower
Control LED
Input 1 4-20 mA / 0-10 VInput 4-20 mA / 0-10 V2
0V / GND
0V
+24V
J1: OUT1 type (open: 4-20 mA; closed: 0-10 V)J : OUT type2 2 (open: 4-20 mA; closed: 0-10 V)J : 3 return to factory settings
SENSOR
35
36
77
Ø 3 5 ...3 6 Ø50
120°
Ø6
580 3
27
Ø34 m ax
Hole
4 -20 mA / 0-10 V4-20 mA / 0-10 V
0V / GNDOUT1OUT20VAB RS485+U = 11...30 VDC
RE1
RE2
Fieldbus
24 VDC
S
NL 90...265 VAC
J3
LED1
J1J1 UT1 type: O (open: 4-20 mA; closed: 0-10 V)J UT type2: O 2 (open: 4-20 mA; closed: 0-10 V)J3: return to factory settings
LED2
LED1: device status controlLED2: power indication**only for enclosures with LED indicators
J2