HYBRID’S, OPEX REDUCTION & TOTAL ENERGY EFFICIENCY PRESENTED BY: ALTERNATIVE ENERGY DIRECTOR TELECOM DIVISION MAY 2013

Upload: others

Post on 26-Dec-2019

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

HYBRID’S, OPEX

REDUCTION

&

TOTAL ENERGY

EFFICIENCY

PRESENTED BY:

ALTERNATIVE ENERGY DIRECTOR

TELECOM DIVISION

MAY 2013

Page 2: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 2

14.05.2013

ELTEK – SAVINGS TO DATE

ENERGY EFFICEIENCY - END to END

TCO – GREEN ENERGY

MARKET TECHNOLOGIES

SW & PERFOMANCE MONITORING

SUMMARY

CONTENT

Page 3: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 3

14.05.2013

ELTEK– SAVINGS TO DATE

CONTENT

E-MOBILITY

RENEWABLE

INDUSTRIAL TELECOM

Page 4: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 4

14.05.2013

SUMMARY – TOTAL SAVINGS TO DATE!

724,000 M WHR – This can power

72,400 US homes for one year @ 10,000Kwhr per home

28.8 M liters of DIESEL Fuel – This can power

5,500 Telecom CDC sites for 1 year @ 2.4kw load

$114 M USD – This can

Feed, cloth and provide basic health needs for 190,000 families in

Africa for One (1) year. (ref Hope for Africa)

529,366 tons CO2 = 144,241 tons of Carbon credits.

Since introduction of HE Product line

Page 5: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 5

14.05.2013

ENERGY EFFICEIENCY - END to END

CONTENT

Page 6: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 6

14.05.2013

ENERGY EFFICIENCY

MODULAR POWER SOLUTION

Energy from PV

Energy from Poor Grid

Energy from Generator

Energy from Wind Turbine

Excess Energy Stored

Energy AC or DC

Page 7: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 7

14.05.2013

WHY ENERGY EFFICIENCY IS SO IMPORTANT..

8% energy loss

(= heat) > Costs money

> Requires cooling = more energy

and cost

100 %

input 92 %

output

Page 8: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 8

14.05.2013

WHY ENERGY EFFICIENCY IS SO IMPORTANT..

3,5% energy

loss

100 %

input 96,5 %

output

• Saves money

• Reduces environmental impact

• Requires less cooling

~ HIGH EFFICIENCY ~

Since 2008

Page 9: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 9

14.05.2013

ENERGY EFFICIENCY CYCLE – *RECTIFIERS / SOLAR CHARGERS / WIND CONVERTERS & DC TO AC INVERTERS

GENSET ENERGY – HE Rectifier = 96.5%

SUN ENERGY – HE Solar Charger = 96.5%

WIND ENERGY – HE Wind Converter = 96.5%

GENSET ENERGY – Inverter = 96% EPC

STORED ENERGY – Inverter = 92% On Line

* Reference Eltek

Page 10: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 10

14.05.2013

TCO – GREEN ENERGY

CONTENT

Page 11: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 11

14.05.2013

Alternative Energy – Telecom

MOTIVATION for introducing Alternative Energies

Energy cost – reduced OPEX & TCO

Improved network reliability

Off grid sites in rural areas

Inaccessible

Energy source redundancy

Vandalism

Page 12: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 12

14.05.2013

ICEBERG SYNDROME – TCO – 24/7 GENSET

TRUE

TOTAL COST OF

OWNERSHIP

$128k

CAPEX $23KUSD

OPEX $105KUSD

(3year period)

OPEX includes,

Diesel, Genset maintenance,

replacement batteries, cooling

tech maintenance, and all other

periodic preventative

maintenance.

CAPEX includes,

goods, services, tax’s etc.

Page 13: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 13

14.05.2013

ICEBERG SYNDROME – TCO – CDC

TRUE

TOTAL COST OF

OWNERSHIP

$94k

CAPEX $31KUSD

OPEX $63KUSD

(3year period)

OPEX includes,

Diesel, Genset maintenance,

replacement batteries, cooling

tech maintenance, and all other

periodic preventative

maintenance.

CAPEX includes,

goods, services, tax’s etc.

Page 14: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 14

14.05.2013

ICEBERG SYNDROME – TCO – HYBRID SOLAR

TRUE

TOTAL COST OF

OWNERSHIP

$69k

CAPEX $42KUSD

OPEX $27KUSD

(3year period)

OPEX includes,

Diesel, Genset maintenance,

replacement batteries, cooling

tech maintenance, and all other

periodic preventative

maintenance.

CAPEX includes,

goods, services, tax’s etc.

Page 15: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 15

14.05.2013

Source: GSMA Development Fund. Green Power for Mobile. Top Ten findings

HOW TO REDUCE OPEX !

• Reduce “On Time” of the generator

• Reduced diesel consumption

• Reduced maintenance costs

1. Energy Optimization

• 96.5% efficient rectifiers

• 96.5% efficient solar chargers

2. Utilization of

High Efficiency Converters

• Reduce the dependency on ACU 3. Use Passive Cooling

Page 16: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 16

14.05.2013

MARKET TECHNOLOGIES

CONTENT

Page 17: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 17

14.05.2013

SOLAR CONVERTER TECHNOLOGIES

98-99% conversion

efficiency

x No MPPT(*)

x No galvanic isolation

between panels and batteries

/telecom equipment

x The battery clamps the

output of the panels

x Maximum 70-80% panel

utilization

Direct Feed

Close to 100%

panel utilization

Full galvanic isolation

between panels and

batteries/telecom equipment

Typically a two-stage

converter with boost

input stage

Converter efficiency 96%

ELTEK VALERE Isolated MPPT

WITH ELTEK VALERE’S

MPPT SOLAR CHARGER

YOU CAN GET AN EXTRA

20% – 30% EXTRA ENERGY *over and above Direct feed designs

Page 18: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 18

14.05.2013

PV HIGH VOLTS DC INPUT –

CONTROLLED DC OUTPUT

Features

Maximum Power Point Tracking

Galvanic isolation

Supported by current Smartpacks

Characteristics

• Input voltage: 85 – 265 Vdc - Typical feed from one string of 4 to 6 solar panels

• Output power: 1500 W

• Output voltage: 48 – 58 Vdc

• Flatpack2 size - 1U high

- 4 pos power shelf

- 400mm deep

SOLAR CONVERTER

TELECOM STANDARD TECHNOLOGY

Greater than 96% efficiency!

Page 19: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 19

14.05.2013

TOTAL SITE CONTROL

S P S or Smart Pack 1 or Smart Pack 2

Page 20: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 20

14.05.2013

SOLUTIONS PART A

CONTENT

Page 21: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 21

14.05.2013

CHARGE DISCHARGE CHARGE

CYCLIC - CDC

Page 22: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 22

14.05.2013

CDC SOLUTION

Page 23: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 23

14.05.2013

Gen-Set

On

Load

Batteries

By periodically running the load on batteries,

you can :

power a larger load, thus the genset will be

more efficient per litre of diesel

Considerably reduce Opex cost due to

less frequent re-supply, maintenance,

repair and replacement

Have less of an impact on the environment

Generator Optimisation

CDC SOLUTION

Float voltage over time

Battery Discharging Battery Charging

Gen-Set

/ Off

Once batteries are sufficiently charged

Page 24: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 24

14.05.2013

HYBRID – SOLAR – WIND

Page 25: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 25

14.05.2013

Energy storage

Power core

Energy source

Hybrid solution

Energy flow Control/monitor

• Designed for telecom

• Modularity for future expansion

• High Efficiency (HE) for less losses

• One controller for ease of integration

Page 26: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 26

14.05.2013

SW & PERFOMANCE MONITORING

CONTENT

Page 27: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 27

14.05.2013

SOFTWARE TOOLS

A) - Power monitoring

B) - Alarm monitoring

Page 28: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 28

14.05.2013

MULTI SITE MONITORING

A) - POWER MONITORING

Page 29: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 29

14.05.2013

Slide 29

14.05.2013

Page 30: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 30

14.05.2013

Slide 30

14.05.2013

Filter on site types

Page 31: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 31

14.05.2013

Slide 31

14.05.2013

Page 32: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 32

14.05.2013

Slide 32

14.05.2013

Page 33: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 33

14.05.2013

Slide 33

14.05.2013

SKIP

Page 34: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 34

14.05.2013

Fuel consumption - generator runtime –

efficiency (*)

(*)Smartpack 1 – FW 3.06 or above required

Page 35: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 35

14.05.2013

SITE MONITORING – SNMP

B) – ALARM MONITORING

Page 36: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 36

14.05.2013

Page 37: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 37

14.05.2013

Remote Configuration

• Launch by double-clicking on a network icon

• Password protected

Double-click on a network icon to launch

Screenshots and device photos are for illustrations only. Subject to change without notice.

Page 38: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 39

14.05.2013

Fault Management

> Alarms such as

• Battery Low/High Voltage, Breaker Open

• AC Mains, Rectifier etc.

> Time-stamped Event Log

> Sophisticated Alarm Management

• Eliminate duplicate alarms

• Correlate alarm (auto-acknowledgement)

• Notification via email or audio

> SMS Notification (optional)

Requires a GSM Terminal

Page 39: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 40

14.05.2013

Graphical Report Views

Page 40: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 41

14.05.2013

SUMMARY

CONTENT

Page 41: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 42

14.05.2013

SUMMARY – HYBRIDS / CDC / ECB

96,5% Converter Efficiency

Fully integrated Single Controller

Reduced Service Requirements

Remote Monitoring & Control

Diesel reduction up to 80%

Total OPEX Reduction up to 75%

Reduced CO2 emissions >78%

20% to 30% more

Converter Energy = MPPT

EXTRA PV Energy 10%+ at low

irradiation MIN.

Local Service and support

Page 42: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 43

14.05.2013

Bangladesh- Present Scenario of Solar PV

Hybrid for BTS in Terms of Efficiency

Page 43: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 44

14.05.2013

Typically, Gen-sets have poor efficiency when

powering a small load

Generator Optimization-

Gen-sets operate with greater efficiency when

under higher loads

Gen-sets are not made to operate at low loads for long periods, so in addition to poor

performance, the generators will break-down more often

Page 44: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 45

14.05.2013

Break Even Point Based for On Going Solar Hybrid

System in Bangladesh

(1,000,000)

(500,000)

-

500,000

1,000,000

1,500,000

2,000,000

1 2 3 4 5 6 7 8 9 10

Page 45: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 46

14.05.2013

Financial Breakdown and Assumption

Page 46: HYBRID’S, OPEX REDUCTION TOTAL ENERGY …...Slide 23 14.05.2013 Gen-Set On Load Batteries By periodically running the load on batteries, you can : power a larger load, thus the genset

Slide 47

14.05.2013